OUTPUTS:
10kW -530kW
TECHNICAL DATA SHEET
50501
ATLANTIC BOILERS was formed in 1980 to promote
highly efficient boilerplant and within 2 years had supplied the first
commercial gas condensing boilers in the United Kingdom. After 25
years, ATLANTIC BOILERS has supplied both gas and oil condensing
boilers to many Universities, Hotels, Hospitals, Medical and Social
Care Buildings, Leisure Centres, Schools, Offices and Housing
Developments plus scores of other types of Buildings.
Coupled with the supply, ATLANTIC BOILERS provides back-up
commissioning, spares and servicing by way of a network of
merchants throughout the United Kingdom. ATLANTIC BOILERS also
supplies condensing and highly efficient domestic hot water
generation, based on stainless steel manufacture.
R-SeriesYEAR-ROUND MAXIMUMCONDENSING OIL & GASBOILERS
CE-0645 BL105 ECA ^Energy rating ‘A’
Busby Hall, North Yorkshire
2 - 150kW OIL CONDENSING
Bannatyne Leisure Centre, Kent
2 - 300kW GAS CONDENSING
South East London Police Station
3 - 530kW DUAL FUEL CONDENSING
tested *
ISO 9001
� 92.0% to 99.5% GCV (110% ncv) efficiency� Modulating, High/Low and On/Off Burners� Balanced or Conventional Flues up to 50metres or more
The ATLANTIC R-Series Year-Round Maximum Condensing Boiler has two distinct heatexchangers, the first of developed quality steel design and the second of high gradeplastic design.
The flue gases leave the first heat exchanger at temperatures below 90˚C, and arethen extracted from the second condensing heat exchanger at temperatures alwaysbelow 50˚C.
The introduction ofcombustion air throughthe condensing exchangerlowers the flue gastemperature below dew-point, hence there is noneed for return watertemperature to be low.
The boiler will condenseto it's maximum efficiencyeven at 82˚C Flow & 71˚Creturn. For combustion air,at inlet temperaturesbelow 30˚C, efficienciesalways exceed 92%. Theseconditions apply throughoutthe year in the UK.
The lower part of thecondensing exchangerhas a condensateneutralising section builtin, eliminating the needfor separate equipment inthe future. The ATLANTICR Series boiler pipeworkrequirements are asstraight forward as aconventional boiler or ahigh efficiency boiler.
NO SPECIAL CIRCUITSARE REQUIRED TOCREATE CONDENSING.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
W
X
Y
Z
TECHNICAL DATA SHEET
50501
T L A N T I C
O I L E R S
S E R I E S
main heat exchanger
burner
condensing exchanger
heating flow
heatingreturn
fresh air
flue gases
condensate
Front view of main heat exchangerCross section main heat exchanger
APPLICATIONS� Hospitals
� Old Peoples' Homes
� Residential Nursing Homes
� Boarding Schools
� Children's Homes
� Greenhouses & Botanical
Gardens
� Halls of Residence
� Residential Hostels
� Hotels & Motels
� Leisure & Sports Centres
� Motorway Services
� Nurses's Homes
� Prisons
� Residential Clubs
� Swimming Pools
� Ambulance Stations
� Colleges
� Fire Stations
� Office Buildings
� Police Stations
� Polytechnics
� Postal Sorting Offices
� Telephone Exchanges
� Universities
� Air terminals
� Day Nurseries
� Art Galleries
� Department Stores
� Libraries
� Museums
� Shopping Malls
� Theatres
� Warehouses
� Banks
� Cathedrals
� Listed Buildings
� 3, 4 or 5 BARS maximum working pressure� 95˚C maximum working temperature� Demountable for access through most openings
IN-BUILT FEATURES
� Minimum flow and minimum temperature requirements are achieved with pump, 4 port valve and sensor
� Domestic hot water can be generated by pump and sensor� Variable temperature radiator circuit is compensated via outside sensor
and flow sensor. Pump circulates the system up to approx 30kPA� The comprehensive controls package can include sequencing, variable boiler flow
temperature, and separate heating circuit control� Under-floor heating can be controlled by 3-port valve, sensor, outside sensor
and circulated by pump
All the above systems can be wired into the boiler, with each of the three separatecircuits having their own time and temperature programmes.
Alternatively, the ATLANTIC R Series boiler(s) can be enabled by a BMSsystem and also can provide alarm signals to a BMS system. The boiler(s) willcontinue their own in-house operational control ensuring correct combustionand hydraulic functions.
� 92% to 99.5% GCV efficiency� Modulating, high/low and on/off oil & gas control� Low NOx levels, maximum 50 ppm on gas, 80 ppm oil 0% O2 DAF� Balanced or conventional flues up to 50 metres or more� 3BARS, 4BARS or 5BARS maximum working pressure� 95'C maximum working temperature� Demountable for access through most doorways and lifts
Height 1165 1275 1430 1668 1880 2138 2308 2308Width 350 445 545 695 845 1280 1440 1440Depth 940 940 1220 1670 2070 2800 2850 2850Height - demountable 600 600 725 850 960 1390 1560 1560Width - demountable 410 410 505 670 810 1150 1150 1150Depth - demountable 645 645 835 1060 1290 2002 2003 2003Access front 500 500 500 700 1000 1000 1000 1000Access one side 100 100 100 100 100 100 100 500Access other side 500 500 500 500 500 500 500 500Access rear 300 300 300 300 300 300 300 300Access top 300 300 300 300 300 500 500 500
PERFORMANCE
CONNECTIONS
DIMENSIONS mm
Model 15 ^22 ^40 * 90 150 300 400 500Maximum Output kW 17 22.4 41.3 90.9 153 315 460 530Minimum Output kW 10 14.1 25.1 51 71 150 200 250Efficiency oil & gas %gcv 99.5 99.5 99.5 99.5 99.5 99.5 99.5 99.5NOx-oil-120 Zurich standard mg/kWhr 120 120 120 120 120 120 120 120CO mg/KWhr 22 2 22 0 15 43 40 43NOx-gas-80 Zurich standard mg/kWhr 80 80 80 80 80 80 80 80CO mg/KWhr 3 3 14 1 31 14 12 14
Gas used m3/Hr maximum 1.7 2.24 4.13 9.09 15.3 31.5 46.1 53.1Gas used m3/Hr minimum 1.5 1.41 2.51 5.49 9.52 15 20 25Fuel oil used ltrs/Hr maximum 1.71 2.21 4.01 9.01 15.2 31.2 45.7 52.6Fuel oil used ltrs/Hr minimum 1.51 1.41 2.51 5.11 7.11 15.1 20.1 25.1 Electricity watts oil 380 380 380 550 1050 1450 2010 2250Electricity watts gas 260 260 260 370 820 1450 2010 2250Exit Flue gases@30°C,m3/Hr 15 20 40 85 145 300 400 500
Dry Weight kg 125 175 275 680 980 1500 1875 1975Water content ltrs 26 36 70 197 330 910 1450 1475Min water pressure BARS 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5Standard water pressure BARS 3 3 3 3 3 3 3 3Max (on order) BARS 4 or 5 4 or 5 4 or 5 4 or 5 4 or 5 4 or 5 4 or 5 4 or 5Minimum Flow l/sec ZERO inbuilt shunt pumpFriction to flow ZERO inbuilt shunt pump
Fresh air inlet 75 75 75 110 110 150 150 150Flue gas outlet 75 75 75 110 125 200 200 200Heating flow 25 25 25 40 50 65 80 80Heating return 25 25 25 40 50 65 80 80Hot water primaries 25 25 25 32 40 50 50 50Condensate 50 50 50 50 50 50 50 50*
* tested by BSRIA tothe Boiler Efficiency
Directive^Energy rating ‘A’
SPECIFICATION
The boiler body is made of 3mm thick quality steel with a water-cooled combustionchamber. The burner fires horizontally through the combustion camber and makes aseries of passes through a horizontal heat exchanger. The steel boiler is externallycovered with an 80mm layer of rock wool thermal insulation. Access to the heatexchanger is through a panel at the front of the boiler secured by four bolts.
The condensing exchanger is made of polypropylene and contains a series of smoothpolypropylene heat exchanger tubes. The bottom of the condensing exchanger has asection containing limestone granules to neutralise the condensate.
The boiler has a pre-wired control panel incorporating an isolator switch withindicator lamps, modulating, high/low or on/off burner control, water flow sensorwith indicator lamps, a safety limit thermostat, hours run indicator, flue gasthermometer & a weather-controlled programmer for two separately operatedheating circuits, and domestic hot water primary circuit
The boiler assembly includes a 4 way valve, a shunt pump, both pre-wired andoperated by the control panel, and a shunt pipe arrangement with connections forconstant temperature circuits
The pressurised Oil or Gas burner has; aluminum body, motorised fan air supply, oilor gas valve with controlled rate of opening, ignition transformer, air/oil or air/gasmixing, combustion head, differential pressure switch, control box with ionisationflame protection, balanced flue pressure switch controls. Burners are supplied withmodulating, high/low or on/off operation.
The flue gas fan, in each boiler bank, contains; Aerodynamic polypropylenehousing, vibration free mountings, minimum pressure loss inlet & outlet, totallyenclosed synchronous motor, maintenance free, dust & water proof bearings,infinitely adjustable fan motor speed regulator. The fan on models up to 90kW ismounted within the boiler casing.
� Pre-wired panel with control to three circuits or equivalent� Easy maintenance of boiler, burner and controls� Built in shunt pump and header� Direct connection to any circuit, any temperature
R150
R500
4 way valve, variabletemperature circuit
Constanttemperature circuit,flow and return
Boiler shunt pump
Flue gas extractor
R Series BoilerIsometric
View of burner, pre-heated combustion air tube and control panel
R150 with acoustic hood over the burner R300 in restricted roof void space two R150 boilers installed with minimum, yet sufficient access
SECRMA
Heating CircuitsINSTALLATION & CONTROL ARRANGEMENT
Each boiler has its own header with in-built shunt pump. This guaranteesminimum water flow and temperatureprotection. Each boiler has in-built controlfor three systems, for example weathercompensated radiators, under-floor heatingand domestic hot water.
Group boiler installations can use abalancing vessel as a neutral heatoutlet. Here 3 boilers serve abalancing vessel. Two space heatingsystems and one DHW calorifier arethen served from the vessel.
Overall, the group boilers can controltheir own cascade, the two spaceheating systems and the DHWcalorifier.
ABOVE: Three 530kW R Series Boilers: Each burner with pre-heated air for combustion
Three 530kW R Series Boilers: Each boiler with bank of flue gasextract fans and neat arrangement of flow/return headers
Const Tempto DHW
Const Tempto AHU
Var Tempto HTG Const Temp
to DHWConst Temp
to AHUVar Temp
to HTG
R150Right: R150 rear view of 4-port control valve, shuntpump and flue gas extractor
SIMPLE REPLACEMENT OF WORN-OUT or IN-EFFICIENT BOILERS by R SERIES
Existing installation with New Generation Condensing Boilers.Simple connection to existing valves.Improved efficiency and circulation
Existing installation with old inefficient boiler plant
R SeriesNEW
GENERATION CONDENSING BOILERS
S!
f
a
FlueARRANGEMENTS
Atlantic 2000 Box 11, Ashton Under Lyne, Lancashire, OL6 7TRTel: 0161 621 5960 or: 020 7237 4912 Fax: 0161 621 5966 E-mail: [email protected]: www.atlanticboilers.com
CALL ATLANTIC FOR FREE QUOTATION ALL PART OF THE SERVICE.... FREE DESIGN SERVICE
FREE COMPUTER GENERATED DIAGRAMS
FREE EQUIPMENT SIZING AND SELECTION
bg
a
f
Boilers can have either balanced or conventional flues forboth oil and gas. The ATLANTIC R Series boiler fluerequirements are economic - often cutting the materialand labour costs when compared to other boilers. As theflue gas exit temperature is always low, the volume ofthe gases is always greatly reduced throughout the year.
In addition, the ATLANTIC R Series boiler has a bank ofvariable speed flue gas extract fans which operatecomfortably at the low temperatures. The fans permitextensive vertical and horizontal flue ducts in lower cost,carefully chosen plastic materials. In addition, the fanvariable speed control minimises the energyconsumption in expelling the flue gases.
Standard through the wall balanced flue
Vertical balanced fluethrough a chimney
Vertical balanced fluethrough a flat or pitched roof
MINIMUM DIMENSIONS in accordance with BS5440 (GAS) and BS5410 (OIL)
a = 10mm, b = 150mm, f = 150mm, g = 300mm