TM COMPACT DEHUMIDIFIER - VICTORY PLUS SERIES SPECIFICATION *Note:- Other voltage options available are 200/220/240/380/440/460 VAC, 1Ph/3Ph, 50/60 Hz MODEL TM VICTORY PLUS 200 TM VICTORY PLUS 420 TM VICTORY PLUS 700 TM VICTORY PLUS 1000 TM VICTORY PLUS 1500 TM VICTORY PLUS 2000 PROCESS AIR FLOW (CMH) 200 420 700 1000 1500 2000 PROCESS ESP (Pa.) 200 200 200 200 200 200 PROCESS MOTOR (KW) 0.24 0.24 0.3 0.3 1.6 1.6 REACT. AIR FLOW (CMH) 39 83 138 197 295 393 REACT. ESP (Pa.) 200 200 200 200 200 200 REACT. MOTOR (KW) 0.12 0.12 0.15 0.15 0.3 0.3 REACT. HEATER (KW) 1.4 2.8 4.8 7.2 10.8 13.9 POWER * REQD. (v/Ø/Hz.) 230 /1/ 50 230 /1/ 50 415 /3/ 50 415 /3/ 50 415 /3/ 50 415 /3/ 50 APPROX. WEIGHT (Kg.) 60 70 130 135 290 290 NOISE LEVEL AT 3 METRE dB(A) 66 66 66 66 66 66 High Efficiency and Reliability § A totally self contained unit with compatibility for both 100 mm and 200 mm deep rotors § Rotor media consisting of high performance metal silicates § Rotor incorporating robust internal structure with stainless steel (SS 304) perimeter flange for industrial quality, durability and easy serviceability § Extended media and seal life by rotor perimeter flange § Edge hard face coating on rotor ensuring longer life and good sealing for media and seals § Non-flammable rotor with organic < 2% § Insulated process and reactivation air flow sectors § Unique teflon coating with silicon seal design for minimum air leakage § Speed controlled brushless/EC fans § TM Process fan with brushless DC motors for Victory Plus 200, 420, 700 and 1000 models on sliding plate for easy access § TM Process fan with EC motors in Victory Plus 1500 and 2000 models on sliding plate for easy access § CNC fabricated unit(s) with stainless steel (SS 304) construction § TM PTC heaters for Victory Plus 200 and 420 models § Fully automated operation using PLC § Access and maintenance to components from operation side only § Integrated bypass purge air Necessary Controls and Safety § Differential air pressure switch for providing react air flow for TM Victory Plus 700 and above models § Thermostat cutout for safety from high temperature present in TM Victory Plus 700 and above models § Microprocessor based controller for easy operation and multiple options § Electrical interlocking of fan motors, heaters and rotor drive for better synchronization Options § Humidity control through digital humidistat § Measuring and display differential pressure or air flow § Touch screen panel for smooth and quick operation § Weatherproof design § Pre and post cooling modules § Temperature display for process inlet/outlet & react outlet § Airflow % display § Output: 3 x 0.10V (extra;control valve, SCR) § PID regulator for variable process air flow § PID regulator for control valves and heaters § Modbus communication Easy to Install § Several mounting and installation options § Small footprints: low volume/weight per CMH Easy to Operate § Specially designed for longer and uninterrupted operations Easy to Maintain § Quick and easily serviceable § Water washable rotor FEATURE HIGHLIGHTS www.bryair.com Technical Data Sheet TM series Compact Dehumidifier
Transcript
Page 1: Technical Data Sheet - Bryair · 2017-07-05 · DATA & DUCT CONNECTION DIMENSIONS (mm) 1. Process Air Inlet 2. Process Air Outlet 3. Reactivation Air Inlet 4. Reactivation Air Outlet

TMCOMPACT DEHUMIDIFIER - VICTORY PLUS SERIES SPECIFICATION

*Note:- Other voltage options available are 200/220/240/380/440/460 VAC, 1Ph/3Ph, 50/60 Hz

MODEL

TM VICTORY PLUS 200TM VICTORY PLUS 420TM VICTORY PLUS 700TM VICTORY PLUS 1000TM VICTORY PLUS 1500TM VICTORY PLUS 2000

PROCESS

AIR FLOW

(CMH)

200

420

700

1000

1500

2000

PROCESS

ESP

(Pa.)

200

200

200

200

200

200

PROCESS

MOTOR

(KW)

0.24

0.24

0.3

0.3

1.6

1.6

REACT.

AIR FLOW

(CMH )

39

83

138

197

295

393

REACT.

ESP

(Pa.)

200

200

200

200

200

200

REACT.

MOTOR

(KW)

0.12

0.12

0.15

0.15

0.3

0.3

REACT.

HEATER

(KW)

1.4

2.8

4.8

7.2

10.8

13.9

POWER *

REQD.

(v/Ø/Hz.)

230 /1/ 50

230 /1/ 50

415 /3/ 50

415 /3/ 50

415 /3/ 50

415 /3/ 50

APPROX.

WEIGHT

(Kg.)

60

70

130

135

290

290

NOISELEVEL

AT 3 METRE

dB(A)

66

66

66

66

66

66

High Efficiency and Reliability

§ A totally self contained unit with compatibility for both 100 mm and 200 mm deep rotors

§ Rotor media consisting of high performance metal silicates

§ Rotor incorporating robust internal structure with stainless steel (SS 304) perimeter flange for industrial quality, durability and easy serviceability

§ Extended media and seal life by rotor perimeter flange

§ Edge hard face coating on rotor ensuring longer life and good sealing for media and seals

§ Non-flammable rotor with organic < 2%

§ Insulated process and reactivation air flow sectors

§ Unique teflon coating with silicon seal design for minimum air leakage

§ Speed controlled brushless/EC fans

§TM Process fan with brushless DC motors for Victory Plus 200,

420, 700 and 1000 models on sliding plate for easy access

§TMProcess fan with EC motors in Victory Plus 1500 and 2000

models on sliding plate for easy access

§ CNC fabricated unit(s) with stainless steel (SS 304) construction

§TMPTC heaters for Victory Plus 200 and 420 models

§ Fully automated operation using PLC

§ Access and maintenance to components from operation side only

§ Integrated bypass purge air

Necessary Controls and Safety

§ Differential air pressure switch for providing react air flow for TMVictory Plus 700 and above models

§ Thermostat cutout for safety from high temperature present in TMVictory Plus 700 and above models

§ Microprocessor based controller for easy operation and multiple options

§ Electrical interlocking of fan motors, heaters and rotor drive for better synchronization

Options

§ Humidity control through digital humidistat

§ Measuring and display differential pressure or air flow

§ Touch screen panel for smooth and quick operation

§ Weatherproof design

§ Pre and post cooling modules

§ Temperature display for process inlet/outlet & react outlet

§ Airflow % display

§ Output: 3 x 0.10V (extra;control valve, SCR)

§ PID regulator for variable process air flow

§ PID regulator for control valves and heaters

§ Modbus communication

Easy to Install

§ Several mounting and installation options

§ Small footprints: low volume/weight per CMH

Easy to Operate

§ Specially designed for longer and uninterrupted operations

Easy to Maintain

§ Quick and easily serviceable

§ Water washable rotor

FEATURE HIGHLIGHTS

www.bryair.com

Technical Data Sheet

TM

series

Compact Dehumidifier

Page 2: Technical Data Sheet - Bryair · 2017-07-05 · DATA & DUCT CONNECTION DIMENSIONS (mm) 1. Process Air Inlet 2. Process Air Outlet 3. Reactivation Air Inlet 4. Reactivation Air Outlet

Note : All dimensions in mm.

MODELUNIT DIMENSIONAL DATA

Inlet Outlet

Process DuctConnection

Reactivation DuctConnection

F

125

150

250

250

352

352

G

125

150

250

250

352

352

Inlet

H

75

125

150

150

200

200

Outlet

I

75

125

150

150

200

200

A

665

665

774

774

1118

1118

B

630

670

878

878

1180

1180

C

400

460

664

664

911

911

D

410

450

654

654

500

500

E

150

150

150

150

600

600

TM VICTORY PLUS 200TM VICTORY PLUS 420TM VICTORY PLUS 700TM VICTORY PLUS 1000TM VICTORY PLUS 1500TM VICTORY PLUS 2000

Due to constant upgradation, data subject to change without notice

DATA & DUCT CONNECTION DIMENSIONS (mm)

1. Process Air Inlet2. Process Air Outlet3. Reactivation Air Inlet4. Reactivation Air Outlet

Victory Plus 1500 & 2000TM

1

3

2

4

B

F

H

G

A C

D

E

Victory Plus 200 to 1000TM

Technical Data Sheet

TM

series

Compact Dehumidifier

* The performance chart shown is for 100 mm deep rotor

Performance charts are for nominal process airflow within the TMoperating range each Victory Plus series with the assumption

WPI = WRI. Please consult Bry-Air for other specific condition.

PERFORMANCE CHART

Example :-

Conditions:Process inlet w PI = 12g/kgProcess inlet T PI. = 20 °C

Chart Data :-Process outlet w PO = 4.4g/kgProcess outlet T PO. = 42 °C

PR

OC

ES

S O

UT

LE

T A

IR M

OIS

TU

RE

CO

NT

EN

T w

PO

(g/k

g)

PROCESS INLET AIR MOISTURE CONTENT wPI(g/kg)

0P

RO

CE

SS

OU

TL

ET

AIR

DB

TE

MP

ER

AT

UR

E T

PO

(C

)

Due to constant upgradation, data subject to change without notice

TECHNICALDATA SHEET

Bulletin: BAA : D0060Effective: SEP. 13, 2016Supercedes: BAA : D0060 Dated: MAR. 30, 2016

Reach us at:Contact: +91 8130237917

Email: [email protected]

www.bryair.com

©, ® & ‘TM’ of Bry-Air (Asia) Pvt. Ltd.TM

Corporate Office & Plant II 21C, Sector-18, Gurgaon 122015, INDIAPhone: +91-124-4091111Fax: +91-124-4091100E-mail: [email protected]

Int’l. Sales Office & Plant I419-420, Udyog Vihar, Phase-III, Gurgaon 122016, INDIAPhone: +91-124-4184444Fax: +91-124-4184400E-mail: [email protected].: www.bryair.com

BRY-AIR (USA)E-mail: [email protected] (MALAYSIA)Email: [email protected] (CHINA)E-mail: [email protected] PROKON GmbH (EUROPE) E-mail: [email protected] (BRAZIL)E-mail: [email protected] (NIGERIA)E-mail: [email protected]


Recommended