Bruker EST Technology and design of inductive HTS shielded fault current limiter: German demonstration project. A. Henning 1 , H.-U. Klein 1 , A. Usoskin 1 , K. Bäuml 2 , T. Janetschek 3 1 Bruker EST; 2 Schneider Electric Sachsenwerk GmbH, 3 Stadtwerke Augsburg GmbH
Transcript
Page 1: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Technology and design of inductive HTS

shielded fault current limiter: German

demonstration project.

A. Henning1, H.-U. Klein1, A. Usoskin1, K. Bäuml2, T. Janetschek3

1 Bruker EST; 2 Schneider Electric Sachsenwerk GmbH, 3 Stadtwerke Augsburg GmbH

Page 2: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Content

• Why a (superconducting) fault current limiter?

• Project overview

• Electro-Magnetic Design

• Cryogenic technology

• Summary

Page 3: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Why a (superconducting) fault current limiter?

3

inductive Shielded core Fault Current Limiter

iSFCL

Page 4: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

The Power Grid Today

4

Transmission

Residential Areas

Distribution

Industry

Data Center

Buildings

Centralised

Production

Page 5: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

5

Transmission

Residental Areas

Distribution

Centralised

Production

Industrial Customer

Buildings

Data Center

E-Mobility and Energy Storage

Renewable Energies

Decentral

Production

The Power Grid in the future

Page 6: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Aftermath of a Severe Faultif the safety systems fail

Page 7: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Solution

Rebuilding of the local power gridReplacement of transformers, switchgear, cables, ...

Intelligent Limitation of Fault Currents Use of Fault Current Limiting (FCL) Systems

Page 8: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Project Overview

8

inductive Shielded core Fault Current Limiter

iSFCL

Page 9: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Schneider Electric

Overview

• Turnover: €19,6 Milliarden in 2010

• More than 110.000 employees in

more than 100 countries

Activity

• Devices for energy distribution in

medium and low voltage range

• Industrial automation

• Building automation & security

• Energy management

• Uninteruptable power supplies und cooling systems

• Services

Fig: Schneider Electric Sachsenwerk GmbH

Page 10: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Stadtwerke Augsburg

10

Facts

The utility „Stadtwerke Augsburg“ is the third-largest municipal energy supplier

in Bavaria / Germany. It supplies energy, natural gas, drinking water and

communal heating as well as easy public transport to it‘s customer.

Energy 997,9 Mio. kWh

Natural gas 3.846,9 Mio. kWh

Community heating 463,6 Mio. kWh

Drinking water 16,8 Mio m³

Data: 31.12.2009

Power grid data

Peak load power grid 300 MW

Length of transmission

lines 2400 km

Page 11: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Bruker CorporationGlobal Company with Diversified Markets

11

Page 12: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

• Bruker EAS & Bruker HTS

Low and High Temperature Superconductors (LTS, HTS)

• Bruker ASC

Superconducting Magnets and Devices for Research, Energy /

Power, and Industry, Beamlines, Synchrotron Instrumentation / XUV

• RI Research Instruments

(51% Bruker) cavities, RF systems, linacs, special projects

• Hydrostatic Extrusions

Bruker Energy and

Supercon Technologies (BEST)Bruker EST

Page 13: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Before Fault:

• Iron core is inductivly shielded by the HTS against the primary coil

”invisible“ in the grid.

• Primary coil smaller than a comparable shunt reactor small impedance.

After Fault:

• HTS get„s normalconducting iron core and screened part of the primary coil

becomes ”visible“ large impedance in the grid, which results in current limitation.

iSFCL in the Power Grid

CB

Primary coilLoad

CryostatSuperconducting short-circuited

secondary

CB

Primary coilLoad

CryostatSuperconducting short-circuited

secondary

Page 14: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Function of the iSFCL

Limitation of the fault current in the grid of the utility

Stadtwerke Augsburg between a transformer station and

the factory of MTU onsite Energy GmbH.

MTU Onsite Energy is a producer of block heat and power

plants. These plants are tested extensively, therefore MTU

is a consumer as well as a supplier of electrical energy.

Partners:

Joint project „iSFCL“

Partners and Project

Bruker EST

Intended location of the iSFCL (green), of the substation (blue) and of MTU onsite (yellow).

Page 15: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

G~iSFCL

G~

110 kV

10 kV

Transformer:

40 MVA

10/110 kV

Circuit breaker:

IN=2500 A

release time 1s

Customer site:

MTU onsite Energy

UN=10.6 kV

IN= 1250 A

IP=25.1 kA

Ik”=10.25 kA

Iop=817 A

Sr=15 MVA

IE 1300 A / 200 ms

10 kV-cable

2x400 mm² Cu

N2XS(F)2Y

R=0.0064 m

X=0.0113 m

230m 130m

Grid Layout

Grid connection:

UN=10.6 kV

SK“= 380 MVA

IK“=20.7 kA

R=0.021

X=0.366

R/X=0.059

=1.84

Circuit breaker IN=1250 A; release time 0,5 s

Page 16: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Maximum Voltage Drop and Impedance in

non-fault Operation

According to IEC 60038 10% voltage drop allowed

based on the nominal voltage of 10.6 kV

Z = Udiff / IN = 1100 V / 817 A = 1.34

iSFCL Znom < 1

iSFCL estimated total active losses incl. cooling 45 - 50 kW

15 MVA Reactor for comparison with the iSFCL

Rated inductance at fault 8.6 mH per phase

Impedance (per phase) = 2.7 Results in ≈ 20% voltage drop

Total active losses = 95 kW

Page 17: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Specifications

-20

-10

0

10

20

30

40

0 0,05 0,1 0,15 0,2 0,25

Cu

rre

nt

in k

A /

Vo

lta

ge

in

kV

Time in s

Grid Voltage

Current without iSFCL2

√2

I k"

Maximum aperiodic

short-circuit current (25 kA)

Operational current (817 A rms)

Specifications

• Operating voltage 10 kV

• Power rating 15 MVA

• Operating current (rms) 817 A

• Fault current

• Limited maximum aperiodic

short-circuit current (1st peak) <5 kA

• Limited steady state fault current 2 kA

• Maximum aperiodic

short-circuit current (1st peak) 25.1 kA

• Initial symmetrical

short circuit current Ik“ 10.25 kA

• Tripping time ~1 ms

• Fault duration max. 500 ms

Page 18: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Advantages of the iSFCL

Reduction of the voltage drop during normal (non-fault) operation compared the an equivalent air core reactor.

Reduction of active (ohmic) losses in comparison with other inductive solutions.

Self-triggering compared to other conventional FCL (e.g. Is-Limiter)No active trigger / control unit needed.

Fail safe compared to resistive type FCL.No interruption of the main current path during failure of the HTS or

cooling system.

Short reaction time and autonomous recooling after fault / quench.

Only small lengths of HTS tape necessary compared to other superconducting types of FCL.

Page 19: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Electromagnetic Design

19

inductive Shielded core Fault Current Limiter

iSFCL

Page 20: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Schematic Design iSFCL

Primary coil

12 HTS modules stacked vertically

(8 HTS tapes with shunts)

GFRP cryostat

Iron core

Safety valves for blow-off during

quench

Support structure

Page 21: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

General Design HTS-Shunt Combination

HTS tapes with protection layer

Metallic support structure

Rod for mech. connection of modules

Schematic, not drawn to scale

External shunts

Support

ing b

asis

Page 22: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Limitation Behavior

-20

-15

-10

-5

0

5

10

15

20

25

30

0 0,05 0,1 0,15 0,2 0,25 0,3 0,35 0,4 0,45 0,5

Cu

rre

nt

in k

A

Time in s

Limited current Unlimited fault current

Limited current 1st peak < 5 kA)

Limitation Steady state < 2kA

Page 23: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Current Distribution in Coaxial Arranged HTS Rings

-1000

-800

-600

-400

-200

0

200

400

600

800

1000

-2,5

-2

-1,5

-1

-0,5

0

0,5

1

1,5

2

2,5

0 5 10 15 20

Cu

rre

nt

in H

TS

in

A

Cu

rre

nt

in P

rim

ary

in

kA

Time in ms

Primary HTS 1 HTS 2

HTS 3 HTS 4

Page 24: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Current Distribution in Coaxial Systems of HTS

Rings stacked along z-axis

PrimaryIron Core

HTS 1-6

z

r

Page 25: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

-800

-600

-400

-200

0

200

400

600

800

1000

-2

-1,5

-1

-0,5

0

0,5

1

1,5

2

2,5

0 5 10 15 20

Cu

rre

nt

in H

TS

in

A

Cu

rre

nt

in P

rim

ary

in

kA

Time in ms

Primary HTS top out HTS middle out

HTS bottom out HTS top inn HTS middle inn

HTS bottom inn

Current Distribution in Coaxial Systems of HTS

Rings stacked along z-axis

Page 26: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

-2,00E-06

0,00E+00

2,00E-06

4,00E-06

6,00E-06

8,00E-06

1,00E-05

1,20E-05

1,40E-05

0 20 40 60 80 100

Ma

gn

. F

lux

De

ns

ity i

n T

Path in mm

Br @ 7.5 ms

Bz @ 7.5 ms

Br @ 5 ms

Bz @ 5 ms

HTS 1 HTS 2 Primary

z

r

Current Distribution in Coaxial Systems of HTS

Rings stacked along z-axis

Page 27: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Cryosystem

27

inductive Shielded core Fault Current Limiter

iSFCL

Page 28: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Cooling – General Design

Design: ILK Dresden

Recooling in

normal operation

Blow off during quench

Refilling of volume losses

via N2 tanks.

(Gas will be liquefied by cooling system)

Only one reservoir tank per system,

Coolers are integrated in the tank.

LN2

Insulation

Gas

Coldheads

Page 29: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Summary

• The grid layout and the specifications are typical for MV

grids

system should be easily adaptable for other locations /

grids

• Novel HTS rings structure used which consists of several

independent HTS rings

easy to adapt to grid power level via change of # of HTS

rings

• Current distribution / sharing between HTS rings is studied

• Cryosystem designed for easy use

no handling of LN2 necessary by customer

Page 30: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Project Team

Bruker ASC GmbH

A. Henning, P. Komorowski, S. Schmidt, D. Krischel, H.-U. Klein

Bruker HTS GmbH

A. Usoskin, T. Withnell, A. Rutt

Schneider Electric Sachsenwerk GmbH

K. Bäuml, R. Summer, P. Novak, U. Kaltenborn

Stadtwerke Augsburg

T. Janetschek

Bruker EST

Page 31: Technology and design of inductive HTS shielded fault ...mydocs.epri.com/docs/publicmeetingmaterials/1110/7TNRSL46577/… · Bruker EST Technology and design of inductive HTS shielded

Bruker EST

Thank you for your attention!