+ All Categories
Home > Documents > TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ......

TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ......

Date post: 18-Jun-2018
Category:
Upload: tranthien
View: 212 times
Download: 0 times
Share this document with a friend
26
Scope: 1. 1.1 This protocol covers the determination of the resistance to uplift pressure of newly installed, adhered, built-up, bituminous roofing systems over mechanically at- tached or adhered rigid board insulation over various deck types. 1.2 The test procedures outlined herein are in- tended to determine the performance of a new roof system assembly when installed over an existing roof system assembly or directly over a roofing substrate. 1.3 The test procedures outlined herein are in- tended to determine whether the uplift re- sistance performance of a newly installed Roof System Assembly meets the design pressure requirements of ASCE 7, as re- quired in Section 1606 of the Florida Building Code, Building. The design pressure requirements for the building in question are listed on Section II of the Uniform Building Permit. 1.4 Tests shall be conducted prior to full-scale test assemblies to ensure that the specific maximum pressures set forth in the built-up roofing manufacturer’s Product Approval can be achieved utilizing the specified components (i.e., fasteners, in- sulation, etc.). 1.5 When insulation boards are mechanically attached or adhered to the deck, the test shall be conducted not less than 7 days af- ter roofing work is complete. Systems containing cold adhesive shall be in place not less than 14 days prior to conducting the test. 1.6 All testing shall be conducted by an ap- proved testing agency and all test reports shall be signed by a Registered Design Professional per F.S., Section 471 or 481 or Registered Roof Consultant. 1.7 Design pressures calculated in accor- dance with ASCE 7 are permitted to be multiplied by 0.6 for the purposes of com- paring to tested pressures in TAS 124. Referenced Documents: 2. 2.1 ASTM Standards D 41 Standard Specification for As- phalt Primer used in Roofing, Damp proofing, and water proofing D 1079 Definitions and Terms Related to Roofing, Waterproofing and Bituminous Materials E 380 Excerpts from Standard Practice for Use of the International Sys- tem of Units (SI) (the Modern- ized Metric System) E 575 Practice for Reporting Data from Structural Tests of Build- ing Constructions, Elements, Connections and Assemblies. E 907 Test Method for Field Testing Uplift Resistance of Roofing Systems Employing Steel Deck, Rigid Insulation and Bitumi- nous Built-Up Roofing 2.2 Factory Mutual Engineering Corpora- tion: Loss Prevention Data Sheet 1-28(S), No- vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention Data Sheet 1-52, Febru- ary, 1986 2.3 National Roofing Contractors Associa- tion: NRCA/ARMA Manual of Roof Mainte- nance and Repair NRCA Roofing and Waterproofing Manual 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.1 TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE FOR FIELD UPLIFT RESISTANCE OF EXISTING MEMBRANE ROOF SYSTEMS AND IN SITU TESTING FOR REROOF AND NEW CONSTRUCTION APPLICATIONS
Transcript
Page 1: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

Scope:1.

1.1 This protocol covers the determination ofthe resistance to uplift pressure of newlyinstalled, adhered, built-up, bituminousroofing systems over mechanically at-tached or adhered rigid board insulationover various deck types.

1.2 The test procedures outlined herein are in-tended to determine the performance of anew roof system assembly when installedover an existing roof system assembly ordirectly over a roofing substrate.

1.3 The test procedures outlined herein are in-tended to determine whether the uplift re-sistance performance of a newly installedRoof System Assembly meets the designpressure requirements of ASCE 7, as re-quired in Section 1606 of the FloridaBuilding Code, Building. The designpressure requirements for the building inquestion are listed on Section II of theUniform Building Permit.

1.4 Tests shall be conducted prior to full-scaletest assemblies to ensure that the specificmaximum pressures set forth in thebuilt-up roofing manufacturer’s ProductApproval can be achieved utilizing thespecified components (i.e., fasteners, in-sulation, etc.).

1.5 When insulation boards are mechanicallyattached or adhered to the deck, the testshall be conducted not less than 7 days af-ter roofing work is complete. Systemscontaining cold adhesive shall be in placenot less than 14 days prior to conductingthe test.

1.6 All testing shall be conducted by an ap-proved testing agency and all test reportsshall be signed by a Registered DesignProfessional per F.S., Section 471 or 481or Registered Roof Consultant.

1.7 Design pressures calculated in accor-dance with ASCE 7 are permitted to bemultiplied by 0.6 for the purposes of com-paring to tested pressures in TAS 124.

Referenced Documents:2.

2.1 ASTM Standards

D 41 Standard Specification for As-phalt Primer used in Roofing,Damp proofing, and waterproofing

D 1079 Definitions and Terms Relatedto Roofing, Waterproofing andBituminous Materials

E 380 Excerpts from Standard Practicefor Use of the International Sys-tem of Units (SI) (the Modern-ized Metric System)

E 575 Practice for Reporting Datafrom Structural Tests of Build-ing Constructions, Elements,Connections and Assemblies.

E 907 Test Method for Field TestingUplift Resistance of RoofingSystems Employing Steel Deck,Rigid Insulation and Bitumi-nous Built-Up Roofing

2.2 Factory Mutual Engineering Corpora-tion:Loss Prevention Data Sheet 1-28(S), No-vember, 1991Loss Prevention Data Sheet 1-49, June,1985Loss Prevention Data Sheet 1-52, Febru-ary, 1986

2.3 National Roofing Contractors Associa-tion:NRCA/ARMA Manual of Roof Mainte-nance and RepairNRCA Roofing and WaterproofingManual

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.1

TESTING APPLICATION STANDARD (TAS) 124-11

TEST PROCEDURE FOR FIELD UPLIFT RESISTANCE OF EXISTINGMEMBRANE ROOF SYSTEMS AND IN SITU TESTING FOR REROOF AND NEW

CONSTRUCTION APPLICATIONS

Page 2: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

2.4 The Florida Building Code, Building:Chapter 16 (High-Velocity HurricaneZones) Design LoadsChapter 19 (High-Velocity HurricaneZones)Reinforced Gypsum Concrete and Insu-lating ConcreteChapter 21 (High-Velocity HurricaneZones) MasonryChapter 22 (High-Velocity HurricaneZones) Steel and IronChapter 23 (High-Velocity HurricaneZones) WoodChapter 15 (High-Velocity HurricaneZones) Roof Covering and Application

2.5 Application Standards:

TAS 105 Test Procedure for Field With-drawal Resistance Testing

TAS 114 Test Procedures for Roof Sys-tem Assemblies in the High-Velocity Hurricane Zone Juris-diction

2.6 Application Standards:

RAS 111 Standard Requirements for At-tachment of Perimeter Wood-blocking and Perimeter Flash-ing

RAS 117 Standard Requirements forBonding or Mechanical At-tachment of Insulation Panelsto and Mechanical Attachmentof Anchor or Base Sheets toVarious Substrates

2.7 Roof Consultants Institute:Glossary of Terms

Terminology & Units:3.

3.1 Definitions–For definitions of terms usedin this Protocol, refer ASTM D 1079;Chapter 2 and Section 1513 of the FloridaBuilding Code; Building and/or the RCIGlossary of Terms. Definitions from theFlorida Building Code, Building shalltake precedence.

3.2 Units –For conversion of U.S. customaryunits to SI units, refer to ASTM E 380.

Significance and Use:4.

4.1 The field test procedures specified hereinprovide a means for determining the upliftresistance of a new, adhered, built-up, bi-tuminous roof system assembly, as statedin applicable specification bid docu-ments, installed on a building within thehigh-velocity hurricane zone. The testprocedures are intended to confirm andsupplement the uplift resistance perfor-mance of roofing systems as determinedunder laboratory conditions and confirmthat a given installation meets the designpressure requirements under ASCE 7, asrequired in Section 1606 of the FloridaBuilding Code, Building.

4.1.1 Field testing of an assembly maybe used to support the uplift resis-tance performance of a specificroof system assembly when therequired number of samples notedin Section 7.1 and 7.2 have beentested, and averaged. A margin ofsafety of 1.45:1 shall be applied tothe sample average.

4.1.2 Laboratory conditions may en-able uplift investigations to in-clude:

• examination of the criticalcomponents and their orienta-tion within the roof system as-sembly;

• examination of the roof sys-tem assembly’s long-term up-lift resistance; and

• examination of the roof sys-tem assembly’s uplift resis-tance from the dynamic affectof variable wind velocities.

4.2 A contractor licensed to install roofing inthe high-velocity hurricane zone shall bepresent during all tests should roof repairsbe necessary. Any roofing componentdamaged during testing shall be repairedimmediately subsequent to test comple-tion.

4.3 When new construction will require a tearoff of the existing roof system assembly,areas of existing roofing shall be removedto deck level. Sample assemblies shall beapplied including a lifting panel, as de-tailed in Section 5.2 when the bonded pull

(TAS) 124-11.2 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

Page 3: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

test procedure is utilized. Sample panelsshall be covered and waterproofed with amembrane roof covering to return the ex-isting assembly to a waterproof condition.

Apparatus:5.

5.1 Bell chamber tests:

5.1.1 Square Uplift Chamber

• The square pressure chambershall be 60 + 1/2 inch (1500 ±15 mm) in size with a maxi-mum height in the center ofthe bell of 18 inches.

• The chamber shall be of suffi-cient strength to withstand notless than 125 pounds persquare feet without collaps-ing.

5.1.2 Pressure measurement device:

• The pressure within thesquare uplift chamber shall bemeasured with a manometerwhich is calibrated to indicatenegative pressures in incre-ments of 15 ± 0.5 pound footper square foot (720 ± 20 Pa).

5.1.3 Vacuum pump:

• Negative pressures shall becreated within the pressurechamber with a vacuum pumpof sufficient capacity to createthe negative pressures speci-fied in Section 8.9.

• The vacuum pump shall alsobe equipped with controls tomaintain a constant pressureat each test pressure incre-ment, as noted in Section 8.9.

5.1.4 Dial indicator:

• Membrane deflections shallbe measured using an analogdial indicator with a reset facegraduated in units not greaterthan 0.002 inch (0.05 mm)and having a range not lessthan 2 inches (50 mm).

• The analog dial indicator shallbe mounted at the center of a 2

inch by 2 inch (50 mm by 50mm) aluminum (or materialof equivalent stiffness) barhaving a length of 60 inches(1500 mm). The bar shall besupported with support legswhich clear the roof mem-brane by not less than 2 inches(50 mm).

5.2 Bonded pull test:

5.2.1 Load transfer device:

• The load transfer device shallconsist of two pieces of 2 feetsquare, 7/8 inch thick plywoodfastened together using 12each, 11/4 inch long woodscrews to form a 2 feet by 2feet by 13/4 inch panel. Screwplacement shall be as noted inFigure 1, below.

• Alternatively the top plywoodpanel may be substituted witha 3/8 inch thick steel panel rein-forced with two 2 inch sec-tions of angle iron welded tothe top face of the panel. Thesteel panel shall have 7/16 inchdiameter holes drilled at loca-tions noted in Figure 1, above,through which 3/8 inch coun-tersunk machine screws shall

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.3

(TAS) No. 124-11

FIGURE 1SCREW AND EYE-BOLT LOCATIONS

Page 4: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

be installed through the baseof the plywood panel and se-cured to the steel plate with awasher and wing nut. (SeeFigure 2, below.)

• One 1/2 inch diameter eye-boltshall be installed in the centerof the test panel and shall besecured to the underside witha lock nut and washers, asnoted in Figure 1, above. Al-ternatively a ring shall bewelded to the steel panel.

• A block and tackle or chainhoist shall be attached to theeye-bolt or welded ring withthe opposite end attached tothe top of a tripod, or equiva-lent support system, capableof withstanding a minimum of1200 lbf downward load. Thehoist assembly shall be capa-ble of an incremental rise of 1/4

inch.

5.2.2 Load cell:

• A load cell, or equivalent loadmeasurement device, capableof recording loads up to 2000lbf to an accuracy of 0.5 lbf,shall be attached between thehois t assembly and theeye-bolt or welded ring tomeasure the applied load.

Test Limitations and Precautions:6.

6.1 General:

6.1.1 Conduct tests when the roof’s sur-face temperature is within a rangeof 40°F to 100ºF (4°C to 38ºC) asmeasured by a surface thermome-ter. The surface temperature shallbe noted on the test report.

6.1.2 For safety considerations, it is rec-ommended that tests not be con-ducted when the wind speed at theroof level is greater than 15 milesper hour (6.5 m/s). (A portable an-emometer to measure wind speedmay be utilized.)

6.2 Bell chamber tests:

6.2.1 The manometer shall serve as asafety device to prevent negativepressures that could cause theplastic or fiberglass dome to shat-ter. The maximum negative pres-sure for the dome shall be clearlymarked on the manometer. Alter-natively other safety features shallbe added to the test chamber toeliminate negative pressuregreater than the design capabili-ties of the dome.

6.2.2 Safety goggles or face shield shallbe worn by persons operating theequipment or observing its opera-tion as a precaution against injurythat could be caused by suddenfailure of the test chamber or roof-ing system.

6.2.3 Care shall be taken to ensure thatmovement of persons and/orequipment during the test does notlead to movement of the analogdial indicator. During the test, allpersons not involved shall stay farenough away from the test area tonot influence the analog dial indi-cators.

6.2.4 Testing under this protocol shallbe conducted on mechanically at-tached roof system assemblies.

6.3 Bonded pull test:

(TAS) 124-11.4 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

FIGURE 2ALTERNATE LOAD TRANSFER DEVICE

Page 5: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

6.3.1 Testing shall only be conductedon fully adhered roof coverings.

6.3.2 Proper safety equipment shall beutilized and proper safety proce-dures followed during the applica-tion of hot asphalt or coal tar pitch.Application of roofing productsshall be in compliance with thesafety guidelines published andrecommended by the roof mem-brane manufacturer and by theNational Roofing Contractors As-sociation.

Sampling:7.

7.1 The total number of tests to be conductedwhen testing over an existing roof assem-bly is listed in Table 1, below. Of thesetests, half shall be conducted at selectedlocations within the perimeter area of theroof and half shall be conducted at se-lected locations within the field area of theroof.

TABLE 1NUMBER OF BELL CHAMBER OR BONDED PULL TESTS

TO BE CONDUCTED PER ROOF AREA

Roof Area (A) Number of Tests

10 squares < A < 50 squares(100 m2 < A < 450 m2) 2

50 squares < A < 100 squares(450 m2 < A < 1000 m2) 4

A > 100 squares(A > 1000 m2)

4 plus 1 additional test foreach additional 100 squares(1000 m2) or portion thereof

1 1 square = 100 ft2 = 9.3 m2

7.2 Three test samples are required for all as-semblies tested on any size roof deckwhen the test assembly is applied directlyto the substrate for confirmation of designpressure performance. (See Section4.1.1.)

Acceptable Roof Deck Constructions:8.

8.1 Acceptable deck types for testing underthis protocol are as follows:

• minimum 15/32 inch plywood orwood plank;

• cementitious wood fiber;

• poured gypsum concrete;

• structural poured concrete;

• structural concrete plank;

• aggregate lightweight insulatingconcrete;

• cellular insulating lightweight con-crete;

• aggregate/cellular insulating light-weight;

• 18-22 gage steel;

• > 22 gage steel; and

• composite deck system (e.g. loadmaster)

Procedure:9.

9.1 Bell chamber tests over an existing roofsystem assembly:

9.1.1 The test area’s membrane surfaceshall be clean, smooth and dry toprovide a continuous contact sur-face for the edges of the pressurechamber. For roof surfaces whichcontain surfacing such as gravel,slag or granules, the test areasshall be prepared as follows:

• Remove the loose gravelsurfacing; sweeping a 12 inch(300 mm) wide square inwhich the chamber perimeterwill be placed.

• Apply a heavy pouring of hotasphalt over the swept areaand allow to completely cool.

• This test area preparation isintended to provide a continu-ous, smooth surface to whichthe edges of the test chambermake contact such that accu-rate pressure measurementsare taken.

9.1.2 Place the bar with attached dial in-dicator such that the tip of the dialindicator is in contact with theroof membrane at the center of thetest area.

9.1.3 Place the assembled chamber overthe roof test area such that the barwith attached dial indicator is cen-tered within the chamber and is

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.5

(TAS) No. 124-11

Page 6: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

perpendicular to the sides of thechamber. The edges of the cham-ber shall be in complete contactwith the roof surface. Position thechamber such that its edges areparallel with the direction of thestructural framing of the building.

9.1.4 Install the pressure measurementdevice to the uplift pressure cham-ber and calibrate to zero pressure.

9.1.5 Position the vacuum pump overthe hole provided in the chamber,insuring that the bypass valve onthe pump is open before startingthe pump or, if a rheostat is used,that it is in the OFF position.

9.1.6 Raise the pressure within thechamber to 15 + 0.5 lbf/ft2 (720 +20 Pa) and hold this pressure levelfor one minute.

9.1.7 Continuously observe the deflec-tion and pressure measurementdevice throughout the vacuumpumping process for sudden orvariable rates of movement.

9.1.8 At the end of the first one minuteinterval, increase the pressurewithin the chamber in incrementsof 15 + 0.5 lbf/ft2 (720 + 20 Pa),holding each pressure level for aperiod of one minute, until:

• the roof system assemblyfails, as noted in Section 10.1;or,

• the pressure within the cham-ber is held at the design pres-sure for the particular roofarea (i.e., field, perimeter orcorner area) for a period ofone minute. These designpressures are determined incompliance with ASCE 7-98,as specified in Section 1606of the Florida Building Code,Building and are listed onSection II of the UniformBuilding Permit.

9.1.9 If “failure,” as defined in Section10.1, occurs, record the appliedload and time.

9.2 Bell chamber test for a new roof systemassembly applied directly to the substrate:

9.2.1 Remove the existing roofingmembrane to the deck in an areaof 8 feet by 8 feet, thoroughlycleaning the deck of all existingroofing material.

9.2.2 If the new assembly is to be ad-hered, prime the deck with ASTMD 41 primer and allow to com-pletely dry.

9.2.3 Install the proposed roof systemassembly utilizing the precise ma-terials proposed for the reroof ap-pl icat ion. Insta l l the tes tassemblies in strict compliancewith published application rec-ommendations.

9.2.4 Provide the testing agency withtwo copies of manufacturer’s lit-erature and application instruc-tions.

9.2.5 Allow the test panel to cure for 48hours if applied in hot asphalt or28 days if solvent or waterbasedadhesives are employed.

9.2.6 Do not apply aggregate surfacingto the test assembly. If an aggre-gate surface or coating is to be ap-plied to the final assembly finishthe test assembly with a flood coatof asphalt at an application rate of384 pounds ± 10 pounds.

9.2.7 Seal the test assembly by stripflashing the test panel to the exist-ing roof system assembly.

9.2.7.1 If the test assembly islower than the existingroof system assemblythe test assembly areashall be filled with aloose insulation mate-rial and the test areashall be covered for thecure period.

9.2.8 Testing of the panel shall be asnoted in Section 9.1

(TAS) 124-11.6 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

Page 7: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

9.3 Bonded pull test over existing roof systemassemblies:

9.3.1 The test area’s membrane surfaceshall be clean, smooth and dry toprovide a continuous contact sur-face for test panel adhesion.

9.3.2 Cut an indentation in the center ofthe test area to accommodate thenut and washer on the undersideof the test panel where a doubleplywood panel is used. Outlinethe test area perimeter, assign areference number and photo-graph.

9.3.3 Suspend the wood or wood andsteel test panel, with eye-bolt orwelded ring installed, from theload application apparatus and re-cord the downward load.

9.3.4 Apply a flood coat of hot steep as-phalt or coal tar pitch over themarked test area at an applicationrate of 4 lb/ft2 and float the testpanel into place. Allow a curingtime of 24 hours for hot asphaltand 48 hours for coal tar pitch ap-plications. Curing time may varydue to atmospheric conditions.

9.3.4.1 Report any variation incure time.

9.3.4.2 The flood coat applica-tion rate may be in-creased for unusualconditions to ensure acomplete bond of thetest assembly.

9.3.4.3 Report any variation inthe adhesive applica-tion rate.

9.3.5 Determine the required upliftforce (F) to be applied using infor-mation determined in Section9.3.3 and the following equation:

where,F = (4 by P) + W

F = required uplift force (lbf);

P = design pressure (lbf/ft2);and

W = weight of test panel (lbf).

9.3.6 When the flood coat, noted in Sec-tion 9.3.4, has fully cured, cut a 2inch to 3 inch wide strip throughthe roof covering around the testpanel down to deck level. The in-tent is to fully isolate the test sam-ple from surrounding roofingmaterials.

9.3.7 Position the support system overthe test panel and attach the loadapplication and measurement de-vices to the eye-bolt or weldedring.

9.3.8 Apply an initial load of 40 lbf plusthe weight of the test panel (W +40) and hold for 1 minute. Afterthe initial 1 minute, increase theapplied load by 40 lbf incrementsin 1 minute time intervals until thedesign pressure (P) is attained, asnoted in Table 2, below.

TABLE 2APPLIED LOAD INCREMENTS

Load (lbf) Pressure (psf) Hold Time (min)

W + 80 20 1

W + 120 30 1

W + 160 40 1

W + 200 50 1

F P 1

9.3.9 If “failure,” as defined in Section10.2, occurs, record the appliedload and time.

Interpretation of Results:10.

10.1 Bell chamber test:

10.1.1 Most roof system assemblies sub-jected to a negative pressure willexhibit an upward deflection thatwill increase as the negative pres-sure increases. Poorly adheredsystems will exhibit relativelylarge increases in upward deflec-tions with relatively small in-creases in applied pressure. Forroof system assemblies that arewell adhered, the increase in de-

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.7

(TAS) No. 124-11

Page 8: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

flection will be gradual and at arelatively constant rate up to apoint at or near failure. The up-ward deflection may slowly in-crease while maintaining thepressure within the chamber.When failure occurs due to lack ofadhesive or cohesive resistance ofthe roof system assembly, therewill be a sudden increase in theupward deflection, and mostlikely the deflection will exceedthe capacity of the dial indicator.

10.1.2 Any roof system assembly whichexhibits an upward deflectiongreater than or equal to 1 inch (25mm) during any of the tests shallbe considered as failing at thepoint where 1 inch (25 mm) of de-flection is recorded.

10.1.3 An upward deflection in excess of1/4 inch (6 mm) or a sudden in-crease in deflection, as measuredby the dial indicator, may indicatean attachment and/or adhesionproblem in the roof system assem-bly and may require further inves-tigation.

10.1.4 Upward deflection of the roof sys-tem assembly due to negativepressure may vary at different lo-cations due to varying stiffness ofthe roof system assembly. Stiff-ness of a roof system assembly isinfluenced by the thickness of in-sulation; stiffness of decking; andby the type, proximity and rigidityof connections between the deck-ing and framing system.

10.2 Bonded pull test:

10.2.1 Any roof system assembly whichexhibits delamination of any por-tion of the test sample prior to thefull 1 minute duration at an ap-plied load equal to the design load(F) shall be considered as failingthe bonded pull test.

10.2.2 If delamination occurs betweenthe plywood test panel and theroof covering, the test panel shall

be re-adhered to the test area, in-creasing the curing period of thehot steep asphalt coal tar pitch orsuch other adhesive material thatmay better adhere the test panel tothe roof membrane.

Report:11.

11.1 Refer to ASTM E 575 for general use inreporting structural performance tests ofbuilding assemblies.

11.2 For either bell chamber tests or bondedpull tests, the final report shall include thefollowing:

11.2.1 A copy of the roof system assem-bly manufacturer’s Product Ap-proval, indicating the maximumdesign pressure for the system,product data sheets and publishedapplication instructions.

11.2.2 A copy of Section II of the Uni-form Building Permit for the pro-ject in question indicating designpressures for the field area, perim-eter area, and if applicable, cornerand extended corner areas of thestructure.

11.2.3 The area, height, and plan view ofthe roof showing the location ofthe test areas, numbered to corre-spond with the test report.

11.2.4 A complete detailed descriptionof the roof system assembly con-struction being tested. Include thetype of steel roof deck and methodof attachment, deck support spac-ing, vapor retarder and adhesive(if any), types and thicknesses ofinsulation and methods of attach-ment, and the type of adhered roofmembrane including surfacing.

11.2.5 Dates of tests, air and roof surfacetemperatures, wind velocity.

11.2.6 Names, signatures and affiliationsof all persons observing the tests.

(TAS) 124-11.8 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

Page 9: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

11.2.7 Photographs documenting all per-tinent aspects of the test, includingtest assembly construction, actualtesting, failure examination (if ap-plicable), and repair procedures(if applicable).

11.3 For bell chamber tests, the final reportshall include the following:

11.3.1 A brief description of the test pro-cedure, including the negativepressure increments, hold timesfor each pressure increment andthe maximum applied pressure.

11.3.2 Tabulated results recorded at eachpressure increment including ob-servations and deflection mea-surements. Deflection shall berecorded at the start and end ofeach pressure increment.

11.3.3 If “failure” occurs during any ofthe bell chamber tests, the test areashall be cut and thoroughly exam-ined and the complete recordshould include:

• the negative pressure at whichthe failure occurred;

• the type of failure and its loca-tion within the roof system as-sembly; and,

• other observations of the roofsystem assembly conditionsthat may be attributed to thefailure.

The cut area of roofing should berepaired after examination of thefailed area or where roofing hasbeen removed to deck level for thepurpose of testing. Insulated as-semblies shall be filled with likeinsulation prior to membrane re-pair.

11.3.4 The attached “Bell Chamber TestResults” sheet completed in full.Make photocopies of the “DataRecording Sheet” and indicate oneach sheet the “Level #” and the“Test #.”

11.4 For bonded pull tests, the final report shallinclude the following:

11.4.1 A brief description of the test pro-cedure, including the applied loadincrements, hold times for eachload increment, the maximum ap-plied load and the calculated max-imum applied pressure.

11.4.2 Tabulated results recorded at eachapplied load increment includingobservations.

11.4.3 If “failure” occurs during any ofthe bonded pull tests, the test areashall be cut and thoroughly exam-ined and the complete recordshould include:

• the applied load and calcu-lated applied pressure atwhich the failure occurred;

• the type of failure and its loca-tion within the roof system as-sembly; and

• other observations of the roofsystem assembly conditionsthat may be attributed to thefailure.

The cut area of roofing should berepaired after examination of thefailed area or where roofing hasbeen removed to deck level for thepurpose of testing. Insulated as-semblies shall be filled with likeinsulation prior to membrane re-pair.

11.4.4 The attached “Bonded Pull TestResults” sheet completed in full.Make photocopies of the “DataRecording Sheet” and indicate oneach sheet the “Level #” and the“Test #.”

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.9

(TAS) No. 124-11

Page 10: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

(TAS) 124-11.10 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

Page 11: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

GENERAL INFORMATION

Job Name: ______________________________________________________________

Job Address: ______________________________________________________________

______________________________________________________________

Job Contact Person: ______________________________________________________________

TESTING AGENCY/EQUIPMENT INFORMATION:Note: The undersigned representative agrees that all testing has been conducted and results have

been reported in compliance with TAS 124.

Testing Agency Name: ______________________________________________________________

Address: ______________________________________________________________

Telephone: ( ) __________ ___________

Fax: ( ) __________ ___________

Representative Name: ______________________________________________________________

Title: ______________________________________________________________

Signature: ______________________________________________________________

Uplift Chamber (General Description):

____________________________________________________________________________________

____________________________________________________________________________________

____________________________________________________________________________________

BUILDING/ROOF SYSTEM INFORMATION:

Building Height: height = _____________________ft

Building Dimensions: length = _____________________ft

second largest dimension = _____________________ft

total roof area = _____________________ft2

= _____________________sqs,

Deck Type: plywood or wood plank cementitious wood fiber

poured gypsum concrete aggregate l/w insulating concrete

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.11

TESTING APPLICATION STANDARD (TAS) 124-11

BELL CHAMBER TEST RESULTS

Page 12: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

structural poured concrete cellular l/w insulating concrete

structural concrete plank aggregate/cellular insulating concrete

18 - 22 ga. steel > 22 ga. steel

composite (e.g. Load Master)

Insulation: polyisocyanurate wood fiber

glass fiber perlite

cellular glass rockwool

extruded polystyrene expanded polystyrene

none other: _____________________

combination: ____________ & _______________________________

Attachment: mechanically attached ( fasteners per ft2)

in hot asphalt ( lbs per square)

cold applied

Provide a brief description of the built-up roof system:

____________________________________________________________________________________

____________________________________________________________________________________

____________________________________________________________________________________

____________________________________________________________________________________

(TAS) 124-11.12 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

Page 13: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

TEST INFORMATION:

Number of Tests: n = ____________(see Section 7.1 of TAS 124)(note the locations of all tests on“Building Information” Detail #2, attached)

Maximum Uplift Pressure: Pmax = ____________ psf(as noted on the roof system manufacturer’s Product Approval)

Design Pressures: Level #1:Field Area: Pfl = ___________ psf

Perimeter Area: Ppl = ___________ psf

Corner Areas: Pcl = ___________ psf

Extended Corner: Pecl = ___________ psf

Design Pressures: Level #2:Field Area: Pf2 =__________ psf

Perimeter Area: Pp2 = ___________ psf

Corner Areas: Pcl2 = ___________ psf

Extended Corner: Pec2 =__________ psf

Design Pressures: Level #3:Field Area: Pff3 = ___________ psf

Perimeter Area: Pp3 = ___________ psf

Corner Areas: Pc3 = ___________ psf

Extended Corner: Pec3 = ___________ psf

Note: If the number of levels on the building/project exceeds three (3), record design pressures for additionallevels in a similar format.

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.13

(TAS) No. 124-11

Page 14: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

(TAS) 124-11.14 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

DATA RECORDING SHEET: Level # _________

Bell Chamber Test Test # _________

Check the appropriate box for field, perimeter, corner or extended corner.

Field Area Perimeter Area

Corner Area Extended Corner Area

Uplift Pressure (psf) Starting Deflection (inch) Ending Deflection (inch)

15 psf 0.00" _________"

30 psf _______" _________"

________ psf _______" _________ "

________ psf _______" _________ "

________ psf _______" _________ "

________ psf _______" _________ "

________ psf _______" _________ "

________ psf _______" _________ "

________ psf _______" _________ "

Check either “pass” or “fail:” pass fail

If the test resulted in failure, complete the following:

Suspected mode of failure: ______________________________________________________________

____________________________________________________________________________________

____________________________________________________________________________________

Was a test cut taken to confirm the mode of failure? yes no

____________________________________________________________________________________

____________________________________________________________________________________

Notes: Provide one of these “Data Recording Sheets” for each Bell Chamber Test conducted on each roof level.Multiple deck types shall be treated as separate roof levels. Stair towers, mechanical penthouses and me-chanical rooms shall have a minimum of one (1) test conducted.

Page 15: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.15

(TAS) No. 124-11

ROOF SYSTEM INFORMATION - DETAIL #1

Page 16: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

(TAS) 124-11.16 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

BUILDING INFORMATION - DETAIL #2

Page 17: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.17

(TAS) No. 124-11

___ INCH___ INCH

___ INCH___ INCH

___ INCH___ INCH

ROOF SYSTEM ASSEMBLY. FILL IN WITH "N/A")ROOF SYSTEM ASSEMBLY. FILL IN WITH "N/A")

INSULATION LAYER(S) (WHERE ROOFING COMPONENT NOT USED ININSULATION LAYER(S) (WHERE ROOFING COMPONENT NOT USED IN

UP ROOF SYSTEM ASSEMBLY AND THICKNESS OF DECK ANDUP ROOF SYSTEM ASSEMBLY AND THICKNESS OF DECK AND

FILL IN EXISTING ROOFING COMPONENTS WHICH MAKEFILL IN EXISTING ROOFING COMPONENTS WHICH MAKE

DENSITY, IF CONCRETE DECK _____DENSITY, IF CONCRETE DECK _____

GAGE OR THICKNESS ____________GAGE OR THICKNESS ____________

TYPE: __________________________TYPE: __________________________

DECKDECK

(IF APPLICABLE)(IF APPLICABLE)

PRIMER: _________________________PRIMER: _________________________

(IF APPLICABLE)(IF APPLICABLE)

VAPOR RETARDED: ________________VAPOR RETARDED: ________________

(IF INSULATION BONDED)(IF INSULATION BONDED)

BONDING MATERIAL: _______________BONDING MATERIAL: _______________

INSULATION: ______________________INSULATION: ______________________

MECH ATTACHED)MECH ATTACHED)

(IF INSULATION(IF INSULATION

FASTENER: _______________________FASTENER: _______________________

LAYER BONDED)LAYER BONDED)

(IF TOP INSULATION(IF TOP INSULATION

BONDING MATERIAL: _______________BONDING MATERIAL: _______________

(IF APPLICABLE)(IF APPLICABLE)

TOP INSULATION LAYER: ___________TOP INSULATION LAYER: ___________

MECH. ATTACHED)MECH. ATTACHED)

(IF TOP INSULATION LAYER(IF TOP INSULATION LAYER

FASTENER: _______________________FASTENER: _______________________

(IF BASE SHEET BONDED)(IF BASE SHEET BONDED)

BONDING MATERIAL: _______________BONDING MATERIAL: _______________

BASE SHEET: _____________________BASE SHEET: _____________________

(IF BASE SHEET MECH. ATTACHED)(IF BASE SHEET MECH. ATTACHED)

FASTENERS: _____________________FASTENERS: _____________________

__________________________________________________________________

BONDING MATERIAL: ______________BONDING MATERIAL: ______________

PLY SHEET(S): ____________________PLY SHEET(S): ____________________

BONDING MATERIAL: ______________BONDING MATERIAL: ______________

TOP PLY: _________________________TOP PLY: _________________________

IF APPLICABLE)IF APPLICABLE)

(BRIEFLY DESCRIBE.(BRIEFLY DESCRIBE.

SURFACING: _____________________SURFACING: _____________________

ROOF SYSTEM INFORMATION - DETAIL #3

Page 18: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

(TAS) 124-11.18 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

Page 19: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

TESTING APPLICATION STANDARD (TAS) 124-11

BONDED PULL TEST RESULTSGENERAL INFORMATION

Job Name: ______________________________________________________________

Job Address: ______________________________________________________________

______________________________________________________________

Job Contact Person: ______________________________________________________________

TESTING AGENCY/EQUIPMENT INFORMATION:Note: The undersigned representative agrees that all testing has been conducted and results have been re-

ported in compliance with TAS 124.

Testing Agency Name: ______________________________________________________________

Address: ______________________________________________________________

Telephone: ( ) __________ ___________

Fax: ( ) __________ ___________

Representative Name: ______________________________________________________________

Title: ______________________________________________________________

Signature: ______________________________________________________________

Test Apparatus (General Description):

____________________________________________________________________________________

____________________________________________________________________________________

____________________________________________________________________________________

BUILDING/ROOF SYSTEM INFORMATION:

Building Height: height = _____________________ft

Building Dimensions: length = _____________________ft

second largest dimension = _____________________ft

total roof area = _____________________ft2

= _____________________sqs,

Deck Type: plywood or wood plank cementitious wood fiber

poured gypsum concrete aggregate l/w insulating concrete

structural poured concrete cellular l/w insulating concrete

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.19

Page 20: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

structural concrete plank aggregate/cellular insulating concrete

18 - 22 ga. steel > 22 ga. steel

composite (e.g. Load Master)

Insulation: polyisocyanurate wood fiber

glass fiber perlite

cellular glass rockwool

extruded polystyrene expanded polystyrene

none ____________ other: __________________________

combination: ____________ & _______________________________

Attachment: mechanically attached ( fasteners per ft2)

in hot asphalt ( lbs per square)

cold applied

Provide a brief description of the built-up roof system:

____________________________________________________________________________________

____________________________________________________________________________________

____________________________________________________________________________________

(TAS) 124-11.20 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

Page 21: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

TEST INFORMATION:

Number of Tests: n = ____________(see Section 7.1 of TAS 124)(note the locations of all tests on“Building Information” Detail #2, attached)

Maximum Uplift Pressure: Pmax = ____________psf(as noted on the roof system manufacturer’sProduct Approval)

Design Pressures: Level #1:Field Area: Pfl = ___________psf

Perimeter Area: Ppl = ___________psf

Corner Areas: Pcl = ___________psf

Extended Corner: Pecl = ___________psf

Design Pressures: Level #2:Field Area: Pf2 = ___________psf

Perimeter Area: Pp2 = ___________psf

Corner Areas: Pcl2 = ___________psf

Extended Corner: Pec2 = ___________psf

Design Pressures: Level #3:Field Area: Pff3 = ___________psf

Perimeter Area: Pp3 = ___________psf

Corner Areas: Pc3 = ___________psf

Extended Corner: Pec3 =__________psf

Note: If the number of levels on the building/project exceeds three (3), record design pressures for additionallevels in a similar format.

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.21

(TAS) No. 124-11

Page 22: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

(TAS) 124-11.22 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

DATA RECORDING SHEET: Level # _________

Bonded Pull Test Test # _________

Check the appropriate box for field, perimeter, corner or extended corner.

Field Area Perimeter Area

Corner Area Extended Corner Area

Applied Load (lbf) Applied Pressure (psf) Pass 1 minute Hold(“yes” or “no”)

80 lbf 20 psf _________

110 lbf 30 psf _________

________lbf _______psf _________

________lbf _______psf _________

________lbf _______psf _________

________lbf _______psf _________

________lbf _______psf _________

________lbf _______psf _________

________lbf _______psf _________

Check either “pass” or “fail:” pass fail

If the test resulted in failure, complete the following:Suspected mode of failure: ______________________________________________________________

____________________________________________________________________________________

____________________________________________________________________________________

Was a test cut taken to confirm the mode of failure? yes no

____________________________________________________________________________________

____________________________________________________________________________________

Notes: Provide one of these “Data Recording Sheets” for each Bonded Pull Test conducted on each roof level.Multiple deck types shall be treated as separate roof levels. Stair towers, mechanical penthouses and me-chanical rooms shall have a minimum of one (1) test conducted.

Page 23: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.23

(TAS) No. 124-11

ROOF SYSTEM INFORMATION - DETAIL #1

Page 24: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

(TAS) 124-11.24 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ

(TAS) No. 124-11

BUILDING INFORMATION - DETAIL #2

Page 25: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ (TAS) 124-11.25

(TAS) No. 124-11

___ INCH___ INCH

___ INCH___ INCH

___ INCH___ INCH

ROOF SYSTEM ASSEMBLY. FILL IN WITH "N/A")ROOF SYSTEM ASSEMBLY. FILL IN WITH "N/A")

INSULATION LAYER(S) (WHERE ROOFING COMPONENT NOT USED ININSULATION LAYER(S) (WHERE ROOFING COMPONENT NOT USED IN

UP ROOF SYSTEM ASSEMBLY AND THICKNESS OF DECK ANDUP ROOF SYSTEM ASSEMBLY AND THICKNESS OF DECK AND

FILL IN EXISTING ROOFING COMPONENTS WHICH MAKEFILL IN EXISTING ROOFING COMPONENTS WHICH MAKE

DENSITY, IF CONCRETE DECK _____DENSITY, IF CONCRETE DECK _____

GAGE OR THICKNESS ____________GAGE OR THICKNESS ____________

TYPE: __________________________TYPE: __________________________

DECKDECK

(IF APPLICABLE)(IF APPLICABLE)

PRIMER: _________________________PRIMER: _________________________

(IF APPLICABLE)(IF APPLICABLE)

VAPOR RETARDED: ________________VAPOR RETARDED: ________________

(IF INSULATION BONDED)(IF INSULATION BONDED)

BONDING MATERIAL: _______________BONDING MATERIAL: _______________

INSULATION: ______________________INSULATION: ______________________

MECH ATTACHED)MECH ATTACHED)

(IF INSULATION(IF INSULATION

FASTENER: _______________________FASTENER: _______________________

LAYER BONDED)LAYER BONDED)

(IF TOP INSULATION(IF TOP INSULATION

BONDING MATERIAL: _______________BONDING MATERIAL: _______________

(IF APPLICABLE)(IF APPLICABLE)

TOP INSULATION LAYER: ___________TOP INSULATION LAYER: ___________

MECH. ATTACHED)MECH. ATTACHED)

(IF TOP INSULATION LAYER(IF TOP INSULATION LAYER

FASTENER: _______________________FASTENER: _______________________

(IF BASE SHEET BONDED)(IF BASE SHEET BONDED)

BONDING MATERIAL: _______________BONDING MATERIAL: _______________

BASE SHEET: _____________________BASE SHEET: _____________________

(IF BASE SHEET MECH. ATTACHED)(IF BASE SHEET MECH. ATTACHED)

FASTENERS: _____________________FASTENERS: _____________________

__________________________________________________________________

BONDING MATERIAL: ______________BONDING MATERIAL: ______________

PLY SHEET(S): ____________________PLY SHEET(S): ____________________

BONDING MATERIAL: ______________BONDING MATERIAL: ______________

TOP PLY: _________________________TOP PLY: _________________________

IF APPLICABLE)IF APPLICABLE)

(BRIEFLY DESCRIBE.(BRIEFLY DESCRIBE.

SURFACING: _____________________SURFACING: _____________________

ROOF SYSTEM INFORMATION - DETAIL #3

Page 26: TESTING APPLICATION STANDARD (TAS) 124-11 TEST PROCEDURE ... · 2.2 Factory Mutual Engineering ... vember, 1991 Loss Prevention Data Sheet 1-49, June, 1985 Loss Prevention ... (TAS)

(TAS) 124-11.26 2010 FLORIDA BUILDING CODE — TEST PROTOCOLS HVHZ


Recommended