The right ITK UPS.
raDOG
Line InteractiveAiO All-in-OneAiO 600 & AiO 800
The AiO All-in-One UPS series, featured with smart microprocessor control design, AVR boost and Buck, Smart USB communication interface and cold start function, is an ideal solution for protecting household and small office systems. In addition the UPS is built-in USB charger, which may charge your mobile, PAD, etc. alone.
Features:• Boost and Buck AVR corrects either under-voltage or over-voltage condition to minimize the
usage of battery energy, hence to extend the life of the battery.
• Built-in USB charger supplies feasible access to recharge your mobile or PAD alone.
• With ergonomic cable management design, all the access of the cables is from top only.
• Cold Start Function aids user to tudn on the UPS without connecting the Utility.
• Smart USB Interface for Power Management supports real-time powerrand UPS status monitoring. Automatic shutdown, schedule and many other advance power management functions.
• Auto-restart Function enables the UPS may be automatically re-started when Utility recovers.
3
AIO ALL-IN-ONEMODEL
600 800CAPACITY 600VA / 360W 800VA / 480W
INPUTVoltage 110/120 VAC or 220/230/240 VACVoltage range 81-145 VAC or 162-290 VACFrequency range 50/60Hz ±10% auto-sensing
OUTPUT
Voltage Regulation ±10% for both AC mode and Battery modeFrequency Range (Batt. Mode) 60Hz or 50Hz ±1HzTransfer Time Typical: 2-6ms, 10ms maxWaveform (Batt. Mode) Simulated sine wave
BATTERYBattery Type & Number 12V/7AH × 1 12V/9AH × 1Typical Recharge Time 6-8 hours recover to 90% capacity
INDICATORSAC Mode Green LED lightningBattery Mode Amber LED lightningFault Red LED lightning
PROTECTION Full Protection Overload and overcharge protection
ALARM
Battery Mode Sounding every 10 secondsLow Battery Sounding every secondOverload Sounding every 0,5 secondBattery Replacement Alarm Sounding every 2 secondsFault Continuously sounding
PHYSICAL
Dimensions D×W×H (mm) 270 × 190 × 90
Details
Net Weight 3,55 4,9OPERATING ENVI-RONMENT
Humidity 0-90% RH @ 0~40ºC (non condensing)Noise Level Less than 40dB
MANAGEMENT Optional USB Port Supports Windows®, Linux, Unix and MACUSB CHARGER for mobile & PAD charging
Line Interactive
4
Line Interactive
The Micropower LCD series, featured with smart microprocessor control design, AVR boost and buck, smart USB interface and cold start function, is a cost effective solution to your mission critical PC valuble peripherals.
The AVR Boost and Buck automatically corrects either undervoltage or overvoltage condition without unnecessary drain and extends the life of the battery.
• Line-interactive technology (VI)
• Automatic Voltage Regulator (AVR, “Boost and Buck”)
• Transfer to battery at under and overvoltage
• Big LCD display
• Self-diagnostic function
• Battery cold start
• Genset-compatible
• Auto-charging in Off-mode
• Auto-restart function
• Automatic computer shutdown
• Audible and visible alarm
• Surge protection
• RJ45/11 protection (EMI/RFI filtering)
• USB interface includin software
• 2 years warranty
MICROPOWER600 - 3000VA
5
MICROPOWERMODEL
600 800 1000 1500 2000 3000Nominal capacity (VA) 600 800 1000 1500 2000 3000Power (Watt) 360 480 600 900 1200 1800Voltage 220/230/240Vac / 110/120VacInput voltage range 162-290Vac / 81-145VacVoltage stabilizer-AVR Boost & BuckInput frequency 50/60Hz (auto-sensing)Output voltage (AC/battery mode) +/- 10HzOutput frequency (battery mode) 50/60Hz ±1HzTransfer time to battery Typical: 2-6ms / maximum: 10msWaveform Simulated sine waveBattery (voltage and quantity) 1 × 12V7Ah 1 × 12V9Ah 2 × 12V7Ah 2 × 12V9Ah 4 × 12V9AhBackup time 5 - 10 minutes at 70% of nominal loadTypical recharge time 6-8 hours recover to 90% capacityOutlets IEC (Schuko on request) 4 outlets (650-1300VA) / 6 outlets (1600-2200VA) IEC320 C13Interface USB-portProtection Overvoltage, short-circuit, overload, battery deep dischargeLCD information Big LCD displayAcoustic information Battery mode - low battery - overload - battery replacement alarm - faultHumidity / Noise level 0-90% at 0-40ºC (non-condensing) / less than 40dB
Dimensions W×D×H (mm) 101 × 302 × 142 149 × 338 × 160 158 × 380 × 196 150 × 430 ×
210Weight 4,3kg 4,9kg 7,8kg 11,1kg 11,5kg 23,2kgWarranty 2 yearsSoftware For Windows, Mac, Linux
On-LineMEMOPOWER III1 - 3kVA, PF 1,0
6
The Memopower III PF 1.0 double conversion true on-line series, superior input voltage window for energy saving, ECO mode, super powerful charger, is an ideal solution to your computer center, network center, communication system, automatic control system or other critical systems.
Features:
• True Online Double Conversion
• Mimic LCD Display with Multifunction Parameter Settings & Operational status
• Wide input voltage range for the harshest environment
• Support Generator Input
• Super Powerful Charger for battery backup extension
• Support Economic Operation Mode
• Emergency power off function (EPO)
• Cold stard Function is built-in
• Bundled Communication Software supports Windows application, etc.
• Matching Battery Pack
• Smart Battery Charging Design for Optimizing Battery Performance
• Output Power Factor 1.0
• >92% High Efficiency Models Avalible
• Input power factor 0.99 (With PFC)
7
MEMOPOWER IIIMODEL
1000 2000 3000CAPACITY (VA/WATTS) 1000VA / 1000W 2000VA / 2000W 3000VA / 3000W
INPUT
Phase Single phase with groundNominal Voltage 200 / 208 / 220 / 230 / 240 Vac
Operating voltage range
Low line transfer
160Vac±5% at 100%~80% load; 140Vac±5% at 80%~70% load; 120Vac±5% at 70%~60% load; 110Vac±5% at 60%~0% load (Ambient temp.<35ºC)
Low line comback
175Vac±5% at 100%~80% load; 155Vac±5% at 80%~70% load; 135Vac±5% at 70%~60% load; 125Vac±5% at 60%~0% load (Ambient temp.<35ºC)
High line transfer 300Vac ±5%
High line comback 290Vac ±5%
Input Voltage Range 55~150Vac or 110-300Vac at 60% load, 80~145Vac or 160~300Vac at 100% loadOperating frequency range 40~70HzPower Factor 0,99Generator input Support
OUTPUT
Output Voltage 200 / 208 / 220 / 230 / 240VacPower Factor 1.0Voltage Regulation ±1%
FrequencyLine mode (Sync. mode) 47~53Hz or 57~63Hz
Battery mode (50/60±0,1) HzCrest Factor 3:1
Harmonic Distortion (THDv)≤2% THD (Linear load)
≤4% THD (Non-linear load)Waveform 2 Pure Sinewave
Transfer Time
AC mode <-> Batt. Mode Zero
Inverter <-> Bypass 4ms (Typical)
EFFICIENCYAC Mode 88% 92%Battery Mode 85% 86% 87% 88% 89% 90%
BATTERY
Battery Type 12V9Ah N/ANumbers 2 3 4 6 8Backup time Long run depends on the capacity of external batteriesTypical recharging time (Standard model) 4 hours recover to 90% capacity
Charging voltage 27,4VDC±1% 41,1VDC±1% 54,7VDC±1% 82,1VDC±1% 109,4VDC±1%Charging current (max.) 1A 12A 1A 12A 1A 12A
SYSTEM FEA-TURES
Line modeAmbient temp. <35ºC
105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal 110%~130%: UPS transfer to bypass after 1 minute when the utility is normal
35ºC<ambient temp.<40ºC105%~110%: UPS transfer to bypass after 1 minute when the utility is normal
110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal>130%: UPS transfer to bypass immediately when the utility is normal
Battery mode
Short circuit Hold whole system
Overheat Line mode: Switch to bypass Backup mode: Shut down UPS immediately
Battery low Alarm and switch offEPO (optional) Shut down UPS immediatelyAudible & Visual alarms Line failure, Battery low, Overload, System faultCommunication interface USB, RS232, SNMP Card, Relay Card (Optional)
PHYSICALDimensions W×H×D (mm) 144×209×293 144×209×309 191×337×460 144×209×309Net Weight (kg) 9,8 4,1 17 6,8 27,6 7,4
ENVIRONMENT
Operating temperature 0 ~ 40ºCStorage temperature -25ºC ~ 55ºCHumidity range 20~90% RH at 0~40ºC (non-condensing)Altitude <1500mNoise Level Less than 50dBA at 1 meter
STANDARDSSafety IEC/EN6204-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-8
On-LineMEMOPOWER RT III1 - 3kVA, PF 1,0
8
The Memopower RT III convertible double conversion true on-line series, superior input voltage window for energy saving, ECO mode, super powerful charger, is an ideal solution to your computer center, network center, communication system, automatic control system or other critical systems.
Features
• True Online Double Conversion
• Mimic LCD display with Multifunction Parameter Settings & operational status
• Wide input voltage range for the harshest envvironment
• Support Generator input
• Super Powerful Charger for Battery backup eytension
• Support Economic Operation Mode
• Power Shedding Function
• Hot-Swappable Battery
• Cold Start Function is built-in
• Bundled Communication Software supports Windows application, etc.
• Matching Battery Pack
• Output Power Factor 1.0
• Up to 92% High Efficiency Models Available
9
MEMOPOWER RT III, PF 1.0MODEL
1KVA 2KVA 3KVACAPACITY (VA/WATTS) 1000VA / 1000W 2000VA / 2000W 3000VA / 3000W
INPUT
Phase Single phase & GroundRelated Voltage 200* / 208* / 220 / 230 / 240 Vac
Voltage range
160Vac±5% at 100%~80% load; 140Vac±5% at 80%~70% load; 120Vac±5% at 70%~60% load; 110Vac±5% at 60%~0% load (Ambient temp.<35ºC)
175Vac±5% at 100%~80% load; 155Vac±5% at 80%~70% load; 135Vac±5% at 70%~60% load; 125Vac±5% at 60%~0% load (Ambient temp.<35ºC)
300Vac ±5%290Vac ±5%
Frequency Range 40Hz ~70Hz (auto detect)Power Factor ≥0.99
Bypass Voltage Range230-264: setting the high voltage point in LCD from 230Vac to 264Vac (Default: 264Vac)
170-220: setting to low voltage point in LCD from 170Vac to 220Vac (Default: 170Vac)
ECO Range Same as the bypassGeneral Input Support
OUTPUT
Phase Single phase & GroundRated Voltage 200 / 208 / 220 / 230 / 240VacPower Factor 1Voltage Regulation ±1%
Frequency Utility Mode 47~53Hz (for 50Hz) or 57~63Hz (for 60Hz)Battery Mode 50/60±0,01 Hz
Crest Factor 3:1
Harmonic Distortion (THDv) ≤3% THD with linear load ≤6% THD with non-linear load
Waveform Pure SinewaveEFFICIENCY AC Mode (full load) >88% >92%
BATTERY
Voltage 24Vdc 36Vdc 48Vdc 72Vdc 96VdcQuantity 2 3 4 6 8Capacity (standard unit) 12V/9Ah N/A 12V/9Ah N/A 12V/9Ah N/ABackup Long run unit depends on the capacity of external batteriesRecharge time to 90% 4 hoursCharging Current (Built-in/Max) 2A Max. 12A 2A Max. 12A 2A Max. 12A
TRANSFER TIME Utility to Battery: 0ms, Utillity to bypass <4ms
PROTECTION
Overload
AC mode Ambient Temp. <35ºC105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal
110%~130%: UPS transfer to bypass after 1 minute when the utility is normal130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal
>150%: UPS transfer to bypass immediately when the utility is normal<35ºC < Ambient Temp. <40ºC
105%~110%: UPS transfer to bypass after 1 minute when the utility is normal110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal
>130%: UPS transfer to bypass immediately when the utility is normal
Battery Mode
Bypass Mode 10A (Input breaker) 16A (Input breaker) 20A (Input breaker)Short circuit Hold whole system
Overheat Line mode: Switch to bypass Backup mode: Shut down UPS immediately
Battery low Alarm and switch offEPO (optional) Shut down UPS immediatelyBattery Advanced Battery Management
ALARMS Audible & Visual Line failure, Battery low, Overload, System fault
COMMUNICATION INTERFACE
Status LED & LCD Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Reading on the LCD Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage
PHYSICAL Dimensions W×H×D (mm) 440×86,5×305 440×86,5×460 440×86,5×435 440×86,5×600(2U)440×131×460(3U) 440×86,5×435
Net Weight (kg) 11,3 5,6 19,1 8,3 26,2 / 25,8 8,6COMMUNICATION INTERFACE
Communication Port RS232 or USBCommunication Slot SNMP Card, Relay Card, etc.
ENVIRONMENT
Operating temperature 0 ~ 40ºCStorage temperature -25ºC ~ 55ºCHumidity 20~90% RH non-condensingAltitude <1500m (derating while >1500m)Noise < 50dB at 1 meter
SAFETY CONFORMANCE IEC/EN62040-1-1, IEC/EN62040-2
*Derate to 80% of capacity when the output voltage is adjusted to 200/208VAC
On-LineMEMOPOWER III6 - 10kVA, PF 1,0
10
The Memopower III 6-10kVA 1.0 PF Parallel Redundancy on-line series, featured with N+X Parallel Redundancy, DSP-controlled technology, high input & output power factors, superior input voltage window for energy saving ECO mode, is an ideal solution to your server, bank, industrial equipment, IT equipment, communication system and other networking equipment, whic is demanding for thorough protection.
Features
• N+X Parallel Redundancy
• Online Double Conversion with DSP Control
• Built--in Power Charger can be set from 1A to 10A
• Unity Input Power Factor with low input current distortion
• High Input Power Factor at 1.0 PF
• Low Input Current Distortion <3%
• Green Concept design with Superior Input Voltage Window for Energy Saving
• Support Generator Input
• Estimated Remaining Time displayed on the LCD
• Support Evonomic (ECO) Operation Mode
• Settable Battery Voltage
• Automatic Battery Test Settable from LCD
• Load - controlled fan
• Matching Battery Pack with Powerful Charger Built-in
• Common Battery When UPS in Parallel Mode
• Versatile Communication Interfaces Available
• Cold Start
• Communicaton Software
• Frequency Converter Mode
• Settable Charge Current
• De-rating Operation Available
11
MEMOPOWER III, PF 1.0MODEL
6KVA 10KVACAPACITY (VA/WATTS) 6kVA/6kW 10kVA/10kW
INPUT
Nominal Voltage 220 / 230 / 240 VacOperating Voltage Range 120 ~ 276 VacFrequency Range 50Hz: 45~55Hz; 60Hz: 54~66Hz (auto sensing)Power Factor ≥0.99
Bypass voltage range
Max. voltage 220V: +25% (optional +10%, +15%, +20%)Bypass voltage
230V: +20% (optional +10%, +15%)240V: +15% (optional +10%)
Min. voltage -45% (optional -20%, -30%)Bypass frequency Range Frewuency protection range ±10%ECO range Same as the bypassHarmonic distortion (THDi) <3% (100% linear load)Generator input Support
OUTPUT
Output Voltage 220 / 230 / 240 VacPower Factor 1Voltage Regulation ±1%
Frequency Line Mode ±1% / ±2% / ±4% / ±5% / ±10% of rated frequency (optional)Battery Mode 50/60 (±0,01) Hz
Crest Factor 3:1
Harmonic Distortion (THDv) ≤2% THD with linear load ≤5% THD with non-linear load
Efficiency >93%
BATTERY
Voltage ±96 / 108 / 120Vdc (Settable)Capacity (standard unit) 12V/7Ah or 12V/9AhTypical recharging time 6 ~ 8 hours (to 90% of full capacity)Charging Current 1A 10A 1A 10A
SYSTEM FEATURES
Transfer time Mains to battery: 0msMains to bypass: 0ms
Overload Line modeLoad ≤110%: last 10minLoad ≤130%: last 1min
>130% turn to bypass mode immediatelyBypass mode 63A (Breaker) 80A (Breaker)
Short Circuit Hold whole system
Overheat Line mode Turn to bypassBat. mode Shut down UPS immediately
Battery low Alarm and switch offSelf-diagnostics Upon power on and software controlBattery Advanced battery managementAudible and visual alarms Line failure, Battery low, Overload, System fault
LED & LCD display Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS fault
LCD displayInput voltage, Input frequency, Output voltage, Output frequency, Load
percentage, Battery voltage, Inner temperature & Remaining battery backup time
Communication interface RS232, USB, SNMP card (optional), Parallel card (optional), Relay card (optional)
ENVIRONMENT
Operating temperature 0ºC ~ 40ºCStorage temperature -25ºC ~ 55ºCHumidity range 0~95% (non-condensing)Altitude <1500mNoise level < 50dB
PHYSICAL Dimension W×H×D (mm) 191×660×460 191×330×405 191×660×460 191×330×405Net weight (kg) 65 18 69 20
STANDARDSSafety IEC/EN62040-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8
On-LineMEMOPOWER RT III6 - 10kVA, PF 1.0
12
The Memopower RT III on-line UPS series, featured with up to 93,5% efficiency, rack/tower convertible, N+X Parallel Redundancy, DSP-controlled technology, high input & output power factors, superior input voltage window for energy saving, ECO mode, is an ideal solution to your server, bank, industrial equipment, IT equipment, communication system and other networking equipment, which is demanding for thorough protection.
Features
• Rack/Tower Convertible
• Graphic LCD Display with Multifunction Parameter Settings & Mimic Diagram
• Hot Swappable Battery
• N+X Parallel Redundancy
• Online Double Conversion with DSP Control
• High Output Power Factor at 1.0PF
• Low Input Current Distortion
• Green Concept design with Superior Input Voltage Window for Energy Saving
• Efficiency up to 93,5%
• Emergency Power Off
• Support Economic (ECO) Operation Mode
• Settable Battery Voltage
• Temperature-controlled Fan
• Matching Battery Pack
• Common Battery When UPS in Parallel Mode
• Versatile Communication Interfaces Availiable
• Cold start
• Communication Software
• Settable Charge Current
• Optional Frequency Converter Mode Supported
• Transformer Module for Galvanic Isolation
13
MEMOPOWER RT III, PF 1.0MODEL
6kVA 10kVACAPACITY (VA/WATTS) 6kVA/6kW 10kVA/10kW
INPUT
Nominal Voltage 208 / 220 / 240 VacOperating Voltage Range 110 ~ 300 VacFrequency Range 45~55Hz / 54~66HzPower Factor ≥0.99 at Nominal voltage (100%)
Bypass voltage range Max. voltage
220Vac: 10%, 15%, 20% or 25%; default: 25%230Vac: 10%, 15% or 20%; default: 20%
240Vac: 10% or 15%; default: 15%)Bypass frequency Range ±1%, ±2%, ±4%, ±5%, ±10%, ECO range Same as the bypassHarmonic distortion (THDi) ≤3% (100% linear load), ≤5% (100% non linear load)Generator input Support
OUTPUT
Output Voltage 208/ 220 / 230 / 240 VacPower Factor 1.0Voltage Regulation ±1%
Frequency Line Mode Synchronize to MainsBattery Mode 50/60 (±0,01) Hz
Crest Factor 3:1Harmonic Distortion (THDv) ≤3% THD with linear load, ≤5% THD with non-linear loadEfficiency >93,5%
BATTERY
Voltage ±96 / 108 / 120VdcCapacity (standard unit) 12V/5Ah or 12V/7Ah or 12V/9AhTypical recharging time 6 ~ 8 hours (to 90% of full capacity)
Charging Current 1A (Standard Unit); Max. Current: 10A (Long run unit); Charging current can be set according to battery capacity installed
SYSTEM FEATURES
Transfer time Mains to battery: 0ms Mains to bypass: 0ms
Overload Line mode Load ≤110%: last 60min, Load ≤125%: last 1minLoad ≤150%: last 200ms turn to bypass mode immediately
Bypass mode 40A (Breaker) 63A (Breaker)Short Circuit Hold whole systemBattery low Alarm and switch offSelf-diagnostics Upon power on and software controlBattery Advanced battery managementAudible and visual alarms Line failure, Battery low, Overload, System fault
LED & LCD display Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS fault
LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature, etc.
Communication interface RS232, USB, Parallel card, EPO and communication slot for optional SNMP card, Relay card or Modbus card
ENVIRONMENT
Operating temperature 0ºC ~ 40ºCStorage temperature 25ºC ~ 55ºCHumidity range 0~95% (non-condensing)Altitude <1500mNoise level (at 1m) < 50dB
PHYSICAL Dimension W×H×D (mm) 440×88×585Net weight (kg) 14 18
STANDARDSSafety IEC/EN62040-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8
On-LineMEMOPOWER PLUS 3/1 Phase6 - 10kVA
14
Up to 4 Memopower Plus 3/1 Phase systems can be connected in parallel to get maximum power capacity. Only one battery is necessary in the parallel redundancy mode.
Features
• On-line “double conversion” technology (VFI)
• DSP (Digital Signal Processor) technology
• Internal static and manual bypass
• Input power factor up to 0.99
• Wide input voltage range
• Up to 4 units in parallel
• Battery (DC) cold start
• Common or separate battery in parallel mode
• Charging current 1-10A
• Selectable battery voltage (16/18/20 batteries)
• ECO mode for energy saving
• Site wiring fault indication
• Self testing at UPS startup
• Intelligent management through ES485, USB, DB9
• Backfeed protection
Options
• SNMP card adapter
• Relay card (dry contacts)
• Additional / external battery packs
• 2 years warranty
15
MEMOPOVER PLUS 3/1 PHASEMODEL
6kVA 10kVAPOWER (kW) 5,4 9
INPUT
Nominal Voltage 220 / 230 / 240 Vac, optional 380 / 400 / 415 VacInput Voltage Range 120-276Vac (1/1), 208-478Vac (3/1)Frequency range 45-55Hz for 50Hz, 55Hz-65Hz for 60Hz (auto-sensing)Input power factor ≥ 0,99Bypass voltage range -45% / +15%Harmonic distortion (THDi) ≤ 5% at 100% non-linear load
OUTPUT
Voltage 208/220/230/240Vac selectableWaveform Pure sine waveHarmonic distortion (THD) ≤ 2 THD at 100% linear loadFrequency 50/60Hz ±2%Voltage regulation ±2% at nominal voltageCrest factor 3:1Efficiency at 75-100% load >92% (AC mode) / >95% (battery mode) / >97% (ECO mode)
BATTERY(INTERNAL)
Type VRLA, AGMVoltage 240Vdc (selectable 192/210/240Vdc)Standard backup time 6-8min at nominal load 3-5min at nominal loadPower of the internal charger 1-10A adjustable
PROTECTIONInput/Output Overvoltage, short-circuit, battery deep discharge, thermal protecionOverload capability AC/Battery mode
≤110% load 3min/30sec, ≤125% load 30sec/3sec, ≤150% load 1sec/200ms
ALARMS - INFOR-MATIONS
Audible Battery backup, battery low, overload status, fault statusLED Mains, inverter, bypass, fault, battery levelLCD Input and output voltage, load, battery voltage, error codes
BYPASS Type Internal static bypass (automatic) and manual bypass / External bypass optional
ENVIRONMNETTemperature / altitude / humidity 0-40ºC / less than 1500m / 0-95% non-condensing
Audible noise at 1m < 50dB
INTERFACEStandard USB, RS232, EPOOptions SNMP, relay card, parallel card
DIMENSIONSDimension W×H×D (mm) 250×510×620 (UPS), 250×600×620 (battery cabinet)Weight (with internal batteries) kg 70 80
STANDARDS CE-certificate, EN/IEC 62040-2, EN/IEC 62040-1, GOST
On-LineMEMOPOWER PLUS RT 3/1 Phase6 - 10kVA
16
Up to 4 MP RT II systems can be connected in parallel to get maximum power capacity. Only one battery is necessary in the parallel redundancy mode.
Features
• On-line “double conversion” technology (VFI)
• DSP (Digital Signal Processor) technology
• Wide input voltage range (120-276V or 208-478V)
• Wide frequency range 40-70Hz ±0,5Hz
• Input power factor up to 0.99 and high output power factor 0.9
• Parallel connection up to 4 units (N+1)
• Rack/Tower design with convertible display
• Input power factor correction (PFC)
• Battery (DC) cold start
• Genset compatible
• ECO mode for energy saving
• Self testing at UPS startup
• Internal static and manual bypass
• Selectable amount of batteries : 16/18/20pcs
• Common or separate battery in parallel mode
• Backup-time indication on the display
• Adjustable charger 1-10A
• Fixing for tower and rackmount included
• EPO contact (Emergency Power off)
• Intelligent management trough RS232 slot, USB
• Including monitoring software
• Backfeed protection
Options
• SNMP card, relay card
• External maintenance bypass
• Galvanic isolaion transformer
• 2 years warranty
Up to 4 units in parallel
Common battery in parallel mode
17
MEMOPOVER PLUS 3/1 PHASEMODEL
6kVA 10kVAPOWER (kW) 5,4 9
INPUT
Connection L-N (single phase), optional: 3L-N 4 wires (three phase)Nominal voltage 220/230/240Vac, optional 380/400/415VacInput voltage range 120-276Vac (1/1), optional 208-478Vac (3/1)Frequency range 45-55Hz for 50Hz, 55Hz-65Hz for 60Hz (auto-sensing)Power factor > 0,99Harmonic distortion (THDi) ≤ 3% at 100% non-linear load
Bypass voltage range +25% (+10%, +20% -option), -45% (-20%,-30% -option), frequency range: ±10%
OUTPUT
Output connection 2 × IEC-C13Voltage 208/220/230/240VacType of wave Pure sine waveHarmonic distortion (THD) ≤ 2 THD (linear load), ≤ 5% THD (no-linear load)Frequency 50/60Hz ±0,02HzVoltage regulation ±2% at nominal voltageCrest factor 3:1Efficiency at 75-100% laod >92% (AC mode) / >94% (battery mode) / 97% (ECO mode)
BATTERY (EXTER-NAL)
Voltage 16/18/20pcs 12V - only external batteries (modules)Charge current 1-10A adjustableParallel systems Common or separate battery possible
PROTECTION
Input/Output Overvoltage, short-circuit, battery deep discharge, thermal protecion
Overload capability
AC mode Load ≤110% : 3min, ≤125% : 30sec, ≤150% : 1sec, >150 : switching to bypass
battery mode Load ≤110% : 30sec, ≤125% : 1sec, ≤150% : 200msec, >150 : shut down of the UPS
bypass Input fuse 40A Input fuse 63A
Type Internal static bypass (automatic) and manual bypass / External bypass optional
ALARMS - INFOR-MATIONS
Audible Battery backup, battery low, overload, short-circuit, fault and error modeLED AC, battery, bypass, working modes, overload, error
LCD Voltage / frequency, load %, battery voltage, temperature, remaining backup time
Audible noise at 1m <55dBBYPASS Type Internal static bypass / external maintenance bypass (option)
CERTIFICATESEMC protection CE, EN/IEC 62040-2, EN/IEC 62040-1-1Protection class IP20 (up to IP55 on option)
INTERFACEStandard USB, parallel port, EPO, RS232, intelligent slotOptions SNMP, relay card
DIMENSIONSDimensions W×D×H (mm) 440×580×130 (3U)Weight (kg) 23 25
EXTERNAL BAT-TERY MODULES
Battery 16/18/20pcs per 12V/9AhDimensions W×D×H (mm) / weight 440×720×132 (3U) / 67kg
Connections input/output/battery modules Terminals
On-LineMEMOPOWER PLUS 3/1 Phase10 - 20kVA, PF 0,9
18
Features
• N+X parallel redundancy
• Online double conversion with DSP control
• Input current harmonic: <5%
• Optimization battery group, the quantity of battery: 16/18/20 pieces (optional)
• Factor can change when selection different battery quantity 16pcs: 0,7PF; 18pcs: 0,8PF; 20pcs: 0,9PF
• Wide input voltage range: 208 ~ 478Vac
• Wide input frequency range (50Hz: 45 ~ 55Hz / 60Hz: 54 ~ 66Hz)
• Support genereator input
• Support economic (ECO) operation mode
• Self-testing when UPS startup
• Options: SNMP card / Relay card / Parallel board
• Cold start
Control panel
Relay card
SNMP
Parallel board
Battery cabinets (optional)
19
MEMOPOVER PLUS 3/1 PHASEMODEL
10kVA 15kVA 20kVACAPACITY (VA / WATTS) 10k/ 9k 15k / 13,5k 20k / 18k
INPUT
Nominal voltage 380/400/415Vac; (3Ph+N+PE)Operating voltage range 208 ~ 478VacOperating frequency range 45~55Hz for 50Hz, 54Hz~66Hz for 60Hz (auto-sensing)Power factor ≥ 0,99
Bypass voltage range
Max. voltage; 220V: +25% (optional +10%, +15%, +20%)230V: +20% (optional +10%, +15%)
240V: +15% (optional +10%)Min. voltage: -45% (optional -20%, -30%)
Bypass frequency range Frequency protection range: ±10%ECO range Same as the bypassHarmonic distortion (THDi) <5% (100% linear load)Generator input Support
OUTPUT
Rated Voltage 220 / 230 / 240 VacPower factor 0,9Voltage regulation ±1%
FrequencyLine mode ±1% / ±2% / ±4% / ±5% / ±10% of the rated frequency (optional)Batt. mode 50 / 60 (±0,1)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load≤5% with non-linear load
Efficiency >93,5% <94,5
BATTERY
Battery voltage ± 96 / 108 / 120Vdc (optional)Capacity (Standard unit) 12V / 7Ah / 9AhTypical recharging time 6 ~ 8 hours (to 90% of full capacity)Charging current 1A (10kVA standard unit); max current 10A (Long run unit)
SYSTEM FEATURES
Transfer time Mains to battery; 0ms; Mains to bypass: 0ms
OverloadLine mode Load ≤110%: 60min, ≤125%: last 10min, ≤150%: last 1min, >150 turn to
bypass mode immediatelyBypass mode 63A (Breaker) 100A (Breaker) 125A (Breaker)
Short circuit Hold whole systemOverheat Line mode: Turn to bypass, Bat. mode: Shut down UPS immediatelyBattery low Alarm and switch offSelf-diagnostics Upon power on and software controlBattery Advanced battery managementAudible & Visual alarms Line failure, Battery under voltage, Overload & UPS fault
LED & LCD display Line mode, Battery mode, ECO mode, Bypass mode, Battery under voltage, Overload & UPS fault
LCD displayInput voltage, Input frequency, Output voltage, Output frequency, Load
percentage, Battery voltage, Inner temperature & Remaining battery backup time
Communication interface RS232, USB, SNMP card (optional), Parallel board (optional), Relay card (optional)
ENVIRONMENT
Operating temperature 0 ~ 40ºCStorage temperature -25 ~ 55ºCHumidity range 0 ~ 95% (Non-condensing)Altitude < 1500mNoise level <55dB <58dB
PHYSICALDimension D×W×H (mm) 597×250×655(S)/502×250×616(H) 502×250×616Net weight (kg) 76(S) / 35(H) 45 46
STANDARDS Safety IEC/EN62040-1, IEC/EN60950-1
EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4,IEC61000-4-5, IEC61000-4-6, IEC61000-4-8
BATTERY BANKModel MP-BT SeriesBattery type & max. quantity 2×20pcs / 7Ah (9Ah)
PHYSICAL OF BAT-TERY BANK
Dimension D×W×H (mm) 597×250×616Net weight (kg) 122 / 134
On-LineMEGAPOWER 3/3 Phase10 - 40kVA, PF 1,0
20
The Megapower 3/3 Phase 1,0PF parallel redundancy online UPS series, featured with 7" color Monitor display, smallest footprint cabinet, built-in batteries up to 40kVA, DSP Control, Common Battery, Programmable battery voltage, 3-lvel intelligent charge mode with powerful battery charges, is an ideal budget-concerned solution to your server, bank, industrial equipment, internet data center, telecom, IT equipment and other mission-critical application.
Features
• Built-in Batteries supports 4 ~ 30min autonomy at 60% load.
• Parallel Redundancy up to 4 units
• Wide Input Voltage and Frequency Windows
• Unity Power Factor and Low Input Distrotion
• Output Power Factor 1,0
• ECO Mode for Energy Saving
• Common Battery
• Programmable Battery Voltage Reduces unnecessary investment and increases your competition
• Module-type design speeds up maintenance work & reduces MTTR
• Highest Efficiency up to 94,5%
• Matching Batttery Packs
• 3-level Intelligent Charge Modes with Smart Charge Current Adjustment
• Powerful Charger up to 15A
• Versatile Communication Interfaces Provided for different applications
• Superior Overload Capability
• Programmable Control and Monitoring Software via RS232 port
• Emergency Power Off
• DC Start
• 7" Color Monitor display supports up to 9 different languages.
MEGAPOWER 3/3 PHASEMODEL
10kVA 15kvA 20kVA 30kVA 40kVACAPACITY (VA / WATTS) 10k / 10k 15k / 15k 20k / 20k 30k / 30k 40k / 40k
INPUT
Rectifer input
Rated AC Input Voltage 380 / 400 / 415Vac, (3PH+N+PE)Input Voltage Range 305 ~ 478Vac (Full load); 208 ~ 478Vac (50% load)Frequency 50 or 60Hz (40 ~ 70Hz Range)Power factor 0,99Harmonic distortion (THDi) ≤2% (100% nonlinear load)
Bypass input
Bypass voltage rangeMax. voltage; 220V: +25% (optional +10%, +15%, +20%), 230V: +20% (optional +10%, +15%), 240V:
+15% (optional +10%)Min. voltage: -45% (optional -20%, -30%)
Bypass frequency range ±10%Synchronization - Window ±1% / ±2% / ±4% / ±5% / ±10% optional (default ±10%)Max current Breaker 20A Breaker 32A Breaker 40A Breaker 63A Breaker 80AUpstream protection, bypass line
Thermomagnethic circuit-breaker, rated up to 125% of nominal ouput current. IEC 60947-2 curve C
Current rating of neutral cable (A) 1,7 × In
Generator input Support
OUTPUTInverter Output
Power factor 1,0Rated AC Voltage 1 300 / 400 / 415 Vac, (3Ph+N+PE)Voltage Regulation ± 1%Transient Voltage Response ±5% (linear load)
Phase Balance 120˚ ±1˚ (100% unbalanced load)
Frequ-ency
Line mode synchronize with input; when input frequency > ±10% (±1% / ±2% / ±4% / ±5% optional),output (50/60±0,1%) Hz
Battery mode 50/60±0,1%) HzCrest factor 3:1Harmonic distortion (THD) <1% (linear load), <3% (non-linear load)Overload capacity
AC mode Load ≤110%: last 60min, ≤125% last 10min, ≤150% last 1min, >150% turn to bypass immediatelyBattery mode Load ≤110%: last 10min, ≤125% last 1min, ≤150% last 5s, >150% shut down UPS immediately
Efficiency Normal mode 93,5% 94,5
BATTERY
Battery voltage
Standard unit
±120Vdc (20pcs 12V9Ah); (2×20pcs 12V9Ah; 3×20pcs 12V9Ah optional)
±120Vdc (2×20pcs 12V9Ah); (3×20pcs 12V9Ah optional)
±120Vdc (3×20pcs 12V9Ah)
±180Vdc (2×30pcs 12V9Ah)
Long run unit ±96 / 108 / 120 /132 / 144Vdc
±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/5
0pcs optional)Float voltage 2,25V/cell (selectable from 2,20~2,29V/cell) Constant current and constant voltage charge mode Boost Charge Voltage 2,30V/cell (selectable from 2,30~2,40V/cell) Constant current and constant voltage charge mode End of Discharge 1,75V/cell (selectable from 1,60 or 1,90V/cell)Charge Current (A) (charge current can be set according to battery capacity installed)
Standard unit 1,35A (2,7; 4,05A optional)
2,7A (4,05A optional) 4,05A 2,7A
Long run unit max. current 15A (limited by input current)
SYSTEM FEATURES
Transfer TimeSynchronous Utility to Battery: 0ms / Utility to bypass: 0msAsynchronous 15ms (50Hz), 13,3ms (60Hz)
Alarms Overload, utility abnormal, UPS fault, battery low, etc.Protection short circuit, overload, over temperature, battery low, fan fault alarm
Communication Interface USB, RS232, Paralel port, Dry contact, Intelligent slotOptional: SNMP card, Relay card, Battery temperature sensor
ENVIRON-MENTAL
Operating Temperature 0ºC ~ 40ºCStorage Temperature -25ºC ~ 55ºC (no battery)Humidity 0 ~ 95% non condensingAcoustical Noise (from 1m distance) <55dB <58dBAltitude < 1500m De-rating when >1500m
STAND-ARDS
Safety certifications IEC/EN62040-1, IEC/EN60950-1EMC IEC/EN62040-2, IEC/EN61000-4-4, IEC/EN61000-4-5, IEC/EN61000-4-6, IEC/EN61000-4-8
21