+ All Categories
Home > Documents > TOPFLEX -EMV-UV-2XSLCH-J Climatização... · 2020. 10. 2. · TOPFLEX®-EMV-UV-2XSLCH-J for power...

TOPFLEX -EMV-UV-2XSLCH-J Climatização... · 2020. 10. 2. · TOPFLEX®-EMV-UV-2XSLCH-J for power...

Date post: 07-May-2021
Category:
Upload: others
View: 4 times
Download: 0 times
Share this document with a friend
2
TOPFLEX ® -EMV-UV-2XSLCH-J for power supply connections to frequency converters, 0,6/1 kV, halogen-free, double screened, higher current carrying capacity, meter marking Properties Cable structure Technical data Bare copper conductor, fine wire acc. to DIN VDE 0295 cl.5 / IEC 60228 cl.5 Special motor power supply cable for frequency converters adapted to DIN VDE 0250 Halogen-free Low mutual capacitance Low coupling resistance for high electromagnetic compatibility Temperature range flexing -15°C to +90°C fixed installation -40°C to +90°C Core insulation of cross-linked polyethylene (XLPE) This screened motor supply cable with low mutual capacitance of the single cores be- cause of the special XLPE core insulation and low screen capacitance enable a low- loss transmission of the power Core cidentification: BN, BK, GY GN-YE conductor Permissible operating temperature at conductor +90°C Cores stranded in concentric layers • Nominal voltage U0/U 600/1000 V 1. Screen with special aluminium film 2. Tinned copper braided screen, approx. 85% coverage Due to the optimal screening an interference-free operation of frequency converters is obtained Max. permissible operating voltage - 3-Phase and single phase operation 700/1200 V - DC operation 900/1800 V Outer sheath of special polyolefin compound The materials used during manufacturing are cadmium-free, contain no silicone and are free from substances harmful to the wetting properties of lacquers Sheath colour: black (RAL 9005) With meter marking • Test voltage 4000 V Tests • Coupling resistance acc. to different cross sections max. 250 Ohm/km Flame test acc. to DIN VDE 0482-332-3-24 / DIN EN 60332-3-24 / IEC 60332-3-24 Note **) The current carrying capacity for permanent operation at ambient temperature of 30°C. For deviating ambient temperatures the conversion factors should be used and for further see the indication in DIN VDE 0298-4. Flame retardant acc. to DIN VDE 0482-332-1-2 / DIN EN 60332-1-2 / IEC 60332-1-2 • Minimum bending radius flexing for outer Ø: up to 12 mm: 10x outer Ø > 12-20 mm: 15x outer Ø > 20 mm: 20x outer Ø fixed installation for outer Ø: up to 12 mm: 5x outer Ø > 12-20 mm: 7,5x outer Ø > 20 mm: 10x outer Ø Corrosiveness of combustion gases acc. to DIN VDE 0482-754-2 / DIN EN 60754-2 / IEC 60754-2 The conductor is metrically constructed (mm²). The AWG designation is approximate and purely informative. Smoke density acc. to DIN VDE 0482-1034-1+2 / DIN EN 61034-1+2 / IEC 61034-1+2 UV-resistant acc. to DIN EN ISO 4892-2 Meets EMC requirements acc. to EN 55011 and DIN VDE 0875-11 Application This TOPFLEX ® -EMV-UV-2XSLCH-J motor power supply cable for the frequency converters assures electromagnetic compatibility in plants and buildings, facilities with units and operating equipment where the fields of electromagnetic interference might cause adverse effects on the surroundings. Respecting the permissible operating temperature at the conductor of +90°C permits a higher current carrying capacity than PE insulated power distribution cables. As a supply and connecting cable for medium mechanical stresses in fixed installations and forced movements in dry, moist and wet environments and for outdoor applications. Used in the automotive and food industries, environmental technology, packaging industry, machine tools. Handling equipment, for SIMOVERT drives, they are particularly suitable for use with industrial pumps, ventilators, conveyor belts and air-conditioning installations and similar applications. EMC = Electromagnetic compatibility To optimize the EMC features we recommend a large round contact of the copper braiding on both ends. = Product conforms with Low-Voltage Directive 2014/35/EU. Continuation 17.04.2020 / Dimensions and specifications may be changed without prior notice.
Transcript
Page 1: TOPFLEX -EMV-UV-2XSLCH-J Climatização... · 2020. 10. 2. · TOPFLEX®-EMV-UV-2XSLCH-J for power supply connections to frequency converters, 0,6/1 kV, halogen-free, double screened,

TOPFLEX®-EMV-UV-2XSLCH-Jfor power supply connections to frequency converters, 0,6/1 kV, halogen-free,double screened, higher current carrying capacity, meter marking 

 

PropertiesCable structureTechnical data• Bare copper conductor,fine wire acc. toDIN VDE 0295 cl.5 / IEC 60228 cl.5

• •Special motor power supply cable forfrequency converters adapted toDIN VDE 0250

Halogen-free• Low mutual capacitance• Low coupling resistance for highelectromagnetic compatibility• •Temperature range

flexing -15°C  to  +90°Cfixed installation -40°C  to  +90°C

Core insulation of cross-linkedpolyethylene (XLPE) • This screened motor supply cable with low

mutual capacitance of the single cores be-cause of the special XLPE core insulationand low screen capacitance enable a low-loss transmission of the power

• Core cidentification: BN, BK, GY• GN-YE conductor• Permissible operating temperature

at conductor  +90°C • Cores stranded in concentric layers• Nominal voltageU0/U 600/1000 V

• 1. Screen with special aluminium film2. Tinned copper braided screen,    approx. 85% coverage

• Due to the optimal screening aninterference-free operation offrequency converters is obtained

• Max. permissible operating voltage- 3-Phase and single phase  operation  700/1200 V- DC operation  900/1800 V

• Outer sheath of special polyolefin compound• The materials used during manufacturingare cadmium-free, contain no siliconeand are free from substances harmfulto the wetting properties of lacquers

• Sheath colour: black (RAL 9005)• With meter marking • Test voltage

4000 V Tests • Coupling resistance

acc. to different cross sectionsmax. 250 Ohm/km

• Flame test acc. toDIN VDE 0482-332-3-24 /DIN EN 60332-3-24 / IEC 60332-3-24

Note• **) The current carrying capacity forpermanent operation at ambient temperatureof 30°C. For deviating ambient temperaturesthe conversion factors should be used andfor further see the indication inDIN VDE 0298-4.

• Flame retardant acc. toDIN VDE 0482-332-1-2 /DIN EN 60332-1-2 / IEC 60332-1-2

• Minimum bending radiusflexing for outer Ø:up to 12 mm: 10x outer Ø> 12-20 mm: 15x outer Ø> 20 mm: 20x outer Øfixed installation for outer Ø:up to 12 mm: 5x outer Ø> 12-20 mm: 7,5x outer Ø> 20 mm: 10x outer Ø

• Corrosiveness of combustion gasesacc. to DIN VDE 0482-754-2 /DIN EN 60754-2 / IEC 60754-2 • The conductor is metrically constructed

(mm²).  The AWG designation isapproximate and purely informative.

• Smoke density acc. toDIN VDE 0482-1034-1+2 /DIN EN 61034-1+2 / IEC 61034-1+2

• UV-resistant acc. to DIN EN ISO 4892-2• Meets EMC requirements acc. toEN 55011 and DIN VDE 0875-11

 

ApplicationThis TOPFLEX®-EMV-UV-2XSLCH-J motor power supply cable for the frequency converters assures electromagnetic compatibility in plants andbuildings, facilities with units and operating equipment where the fields of electromagnetic interference might cause adverse effects on the surroundings.Respecting the permissible operating temperature at the conductor of +90°C permits a higher current carrying capacity than PE insulated powerdistribution cables. As a supply and connecting cable for medium mechanical stresses in fixed installations and forced movements in dry, moist andwet environments and for outdoor applications. Used in the automotive and food industries, environmental technology, packaging industry, machinetools. Handling equipment, for SIMOVERT drives, they are particularly suitable for use with industrial pumps, ventilators, conveyor belts andair-conditioning installations and similar applications.EMC = Electromagnetic compatibilityTo optimize the EMC features we recommend a large round contact of the copper braiding on both ends.= Product conforms with Low-Voltage Directive 2014/35/EU.

 

 

Continuation 

17.04.2020 / Dimensions and specifications may be changed without prior notice.

Page 2: TOPFLEX -EMV-UV-2XSLCH-J Climatização... · 2020. 10. 2. · TOPFLEX®-EMV-UV-2XSLCH-J for power supply connections to frequency converters, 0,6/1 kV, halogen-free, double screened,

TOPFLEX®-EMV-UV-2XSLCH-Jfor power supply connections to frequency converters, 0,6/1 kV, halogen-free,double screened, higher current carrying capacity, meter marking 

AWG-No.Weightapp. kg / km

Cop.weightkg / km

Power ratings **)with 3 loaded coresin Amperes

Coupling resistanceMutual capacitanceOuter Øapp. mm

No.cores xcross-sec.mm²

Part no.at 30 MHzOhm/km

at 1 MHzOhm/km

Core / Screenapp. nF / km

Core / Coreapp. nF / km

16164,095,0231107010,14 G 1,524522 

14211,0150,032210181308011,24 G 2,524523 

12303,0235,042210111509012,84 G 424524 

10428,0320,05415061509014,94 G 624525 

8673,0533,075180720012017,74 G 1024526 

61000,0789,0100190921012020,94 G 1624527 

41505,01236,012795423014025,34 G 2524528 

21934,01662,016885326015028,04 G 3524529 

12724,02345,019240232019032,34 G 5024530 

2/03674,03196,024645232019037,64 G 7024531 

3/04583,04316,029850141025041,64 G 9524532 

4/06061,05435,034643027044,84 G 12024533 

300 kcmil7443,06394,039945028052,34 G 15024534 

350 kcmil8727,07639,045647029058,74 G 18524535 

Dimensions and specifications may be changed without prior notice. (RD01)

17.04.2020 / Dimensions and specifications may be changed without prior notice.