www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional Emergi-Lite Orbis detectors Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofire systems. Non-addressable (conventional) smoke and heat sensors respond to fire situations within a given zone, sending a signal to the fire panel, which will indicate a fire condition and sound the alarm. Orbis provides valuable core features, with high reliability, a marked reduction in unwanted false alarms, complemented by operational and maintenance enhancements. Features: StartUp: Correct installation – a flashing red LED Continuity link: Zone wiring can be voltage tested before commissioning Wide-angle optics: Responsive to fires with black or white smoke Drift Compensation: Calibrated sensitivity levels are maintained despite contamination DustDefy: Dust ingress prevented while airflow is unimpeded Transient Rejection: Abnormal readings are filtered out to reduce false alarms DirtAlert: A flashing yellow LED will indicate when the drift compensation limit has been reached SensAlert: A flashing yellow LED indicates incorrect sensor operation Fast Test: A 4 second test confirms correct detector operation E-Z Fit slots: Remove and refit the base without dismounting the fixing screws Detector base with diode FAPO-TDB The standard detector base has a diode fitted beneath the connectors. A link feature enables voltage testing of zone wiring before commissioning. The base is a five terminal unit – positive IN, positive OUT, Negative IN & OUT, remote LED negative and functional earth (screen) wire. Two fixing centre positions are provided at 51 and 60mm. SPECIFICATION Construction White moulded polycarbonate Termination Connectors accept up to 2.5mm 2 cables Dimensions ø d (mm) 100 x 15 Weight g 60 Detector relay base FAPO-TRB The relay base has a single pole voltage free changeover contact for use to switch ancillary equipment. When the detector goes to alarm the relay is energised and changes state. Contacts rated at 30Vdc, 1A. SPECIFICATION Termination Connectors accept up to 2.5mm 2 cables Construction White moulded polycarbonate Dimensions ø d (mm) 100 x 15 Weight g 60 FAPO-TDB FAPO-TRB 57
Transcript
  • www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional

    Emergi-Lite Orbis detectors

    Emergi-Lite Orbis brings the latest in fire detector microprocessor technology to the Firetec and Eurofiresystems. Non-addressable (conventional) smoke and heat sensors respond to fire situations within agiven zone, sending a signal to the fire panel, which will indicate a fire condition and sound the alarm.

    Orbis provides valuable core features, with high reliability, a marked reduction in unwanted false alarms,complemented by operational and maintenance enhancements.

    Features:

    � StartUp: Correct installation – a flashing red LED

    � Continuity link: Zone wiring can be voltagetested before commissioning

    � Wide-angle optics: Responsive to fires with blackor white smoke

    � Drift Compensation: Calibrated sensitivity levelsare maintained despite contamination

    � DustDefy: Dust ingress prevented while airflow isunimpeded

    � Transient Rejection: Abnormal readings arefiltered out to reduce false alarms

    � DirtAlert: A flashing yellow LED will indicatewhen the drift compensation limit has beenreached

    � SensAlert: A flashing yellow LED indicatesincorrect sensor operation

    � Fast Test: A 4 second test confirms correct detector operation

    � E-Z Fit slots: Remove and refit the base without dismounting the fixing screws

    Detector base with diode FAPO-TDBThe standard detector base has a diode fitted beneath the connectors. Alink feature enables voltage testing of zone wiring before commissioning.

    The base is a five terminal unit – positive IN, positive OUT, Negative IN &OUT, remote LED negative and functional earth (screen) wire. Two fixingcentre positions are provided at 51 and 60mm.

    SPECIFICATION

    Construction White moulded polycarbonate

    Termination Connectors accept up to 2.5mm2 cables

    Dimensions ø d (mm) 100 x 15

    Weight g 60

    Detector relay base FAPO-TRBThe relay base has a single pole voltage free changeover contact for use toswitch ancillary equipment. When the detector goes to alarm the relay isenergised and changes state.

    Contacts rated at 30Vdc, 1A.

    SPECIFICATION

    Termination Connectors accept up to 2.5mm2 cables

    Construction White moulded polycarbonate

    Dimensions ø d (mm) 100 x 15

    Weight g 60

    FAPO-TDB

    FAPO-TRB

    57

  • www.emergi-lite.co.ukConventional | Emergi-Lite Orbis detectors

    58

    Optical smoke detector FAPO-OPTThe optical detector measures the level of smoke particles using lightscatter, going to alarm at a pre-set threshold. New optics help reduce falsealarms while stability is strengthened by using internal software control.

    Recommended for general purpose use to give early warning of fire.

    SPECIFICATION

    Voltage range 8.5 – 33Vdc

    Average quiescent current at 24V 65µA

    Alarm current at 12V24V

    20mA40mA

    Wiring & polarity 2 wire supply, polarity sensitive

    Construction White moulded polycarbonate

    Dimensions ø d (mm) 97 x 31 (100 x 46 inc base)

    Weight g 75, 135 with base

    Standards EN54-7: 2000

    Optical smoke and thermally FAPO-MUSenhanced detectorThe detector uses optical and heat sensing technology in deciding when totrigger an alarm condition. The unit is designed as a smoke detector andcannot be switched from smoke to heat detection.

    This detector is more sensitive to fast burning, flaming fires than theoptical model. Ideal for where heat is prevalent at an early stage inthe fire.

    SPECIFICATION

    Voltage range 8.5 – 33Vdc

    Average quiescent current at 24V 65µA

    Alarm current at 12V24V

    20mA40mA

    Wiring & polarity 2 wire supply, polarity sensitive

    Construction White moulded polycarbonate

    Dimensions ø d (mm) 97 x 42 (100 x 57 inc base)

    Weight g 80, 140 with base

    Standards EN54-7: 2000

    Emergi-Lite Orbis detectors

    FAPO-OPT

    FAPO-MUS

  • 59

    www.emergi-lite.co.uk Emergi-Lite Orbis detectors | Conventional

    Emergi-Lite Orbis detectors

    Heat detectors – FAPO-HR1, FAPO-HR2, FAPO-HR3Fixed temperatureThe fixed (static) heat detector will trigger when a pre-set uppertemperature threshold is exceeded at the sensor.

    Classification – maximum application temperature: HR1 = 50ºC, HR2 = 65ºC,HR3 = 80ºC

    SPECIFICATION

    Voltage range 8.5 – 33Vdc

    Average quiescent current at 24V 65µA

    Alarm current at 12V24V

    20mA40mA

    Wiring & polarity 2 wire supply, polarity sensitive

    Construction White moulded polycarbonate

    Dimensions ø d (mm) 100 x 42

    Weight g 100

    Standards EN54-5: 2000

    STANDARD ORDER CODE DESCRIPTION

    FAPO-HR1 Heat detector – Fixed upper threshold 50ºC, A2S

    FAPO-HR2 Heat detector – Fixed upper threshold 65ºC, BS

    FAPO-HR3 Heat detector – Fixed upper threshold 80ºC, CS

    Heat detectors – FAPO-RR1, FAPO-RR2 , FAPO-RR3Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.

    Readings are taken every 2 seconds, the stored values are compared againsta preset value to decide if an alarm level has been reached.

    Classification – maximum application temperature: RR1= 50ºC, RR2 = 65ºC,RR3 = 80ºC

    SPECIFICATION

    Voltage range 8.5 – 33Vdc

    Average quiescent current at 24V 65µA

    Alarm current at 12V24V

    20mA40mA

    Wiring & polarity 2 wire supply, polarity sensitive

    Construction White moulded polycarbonate

    Dimensions ø d (mm) 97 x 36 (100 x 51 inc base)

    Weight g 70, 130 with base

    Standards EN54-7: 2000

    STANDARD ORDER CODE DESCRIPTION

    FAPO-RR1 Heat detector -Rate of rise with fixed upper threshold 50ºC, A1R

    FAPO-RR2 Heat detector -Rate of rise with fixed upper threshold 65ºC, BR

    FAPO-RR3 Heat detector -Rate of rise with fixed upper threshold 80ºC, CR

    FAPO-HR1

    FAPO-RR1

  • Conventional 4-wire detectors

    www.emergi-lite.co.ukConventional | Conventional 4-wire detectors

    60

    Detector base with diode FAP6-STBThe standard detector base has a diode fitted beneath the connectors.

    SPECIFICATION

    Termination Connectors accept up to 2.5mm2 cables

    Construction White moulded polycarbonate

    Dimensions ø d (mm) 100 x 15

    Weight g 60

    Relay base FAP6-RLBThe relay base incorporates a set of volt-free changeover contacts, whichwill latch when the detector registers an alarm.

    FAP6-STB

    FAP6-RLB

    Conventional 4-wire detection: The FAP6 rangeIntroducing the FAP6 range of detectors, for use with the Firetec and Eurofire 4-wire panels. FAP6provides proven technology in a slim package, the concise range comprises optical and heat detectors(fixed and rate of rise temperature). In conjunction with Firetec the range is suited to small to mediumsized buildings.

    FAP6 is based on series 65technology from Apollo FireDetectors Ltd

    SPECIFICATION

    Voltage range 9 – 33Vdc

    Relay base alarm current at 24V 17mA

    Modes Latching

    Operating temperature -20 to +70ºC

    Termination Connectors accept up to 2.5mm2 cables

    Construction White moulded polycarbonate

    Dimensions ø d (mm) 100, 25

    Weight g 100

  • 61

    www.emergi-lite.co.uk Conventional 4-wire detectors | Conventional

    Conventional 4-wire detectors

    Relay base, 12 volt FAP6-RLB12The low voltage relay base incorporates a set of volt-free changeovercontacts that can be used for either latching or non-latching (securitysystem) purposes. To enable control of an automatic door closer,for example.

    SPECIFICATION

    Voltage range 9 – 15Vdc

    Average quiescent current at 12V

  • www.emergi-lite.co.uk

    62

    Conventional 4-wire detectors

    Conventional | Conventional 4-wire detectors

    Heat detector – FAP6-RR6, FAP6-RR75, FAP6-RR90Rate of riseThe heat detector will monitor the rate of temperature increase in thevicinity and will also be triggered when a fixed upper thresholdtemperature level is exceeded.

    Classification – maximum application temperature: RR6= 50ºC, RR75 = 65ºC,RR90 = 80ºC

    SPECIFICATION

    Voltage range 9 – 33Vdc

    Quiescent current at 24V

  • 63

    www.emergi-lite.co.uk Conventional 4-wire call points | Conventional

    Conventional 4-wire call points

    Call point FMC-200RSurface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:

    � Secure clip-fix front cover

    � A single key for test, reset and removal of cover

    SPECIFICATION

    Voltage range 24Vdc

    Impedance 470R series resistor

    Alarm indication Red LED

    Operating temperature -25 to +55ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination 4 way terminal block

    Construction ABS plastic in red

    Ingress rating IP42

    Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)

    Weight g 190

    Standards EN54-11

    OPTIONS

    FMC-200RS Call point with re-settable plastic element

    FMC-10G Spare glass (pack of 10)

    FMC-10GRS Spare re-settable element (pack of 10)

    Weatherproof call point FMC-200RWPSurface mounted manually operated call point with LED indicator,providing a switch closure to the panel when operated. Features:

    � Secure clip-fix front cover

    � One key for test, reset and removal of cover

    � Weatherproof to IP67

    SPECIFICATION

    Voltage range 24Vdc

    Impedance 470R series resistor

    Alarm indication Red LED

    Operating temperature –25 to +55ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination 4 way terminal block

    Construction ABS plastic in red

    Ingress rating IP67

    Dimensions lwd (mm) 110 x 110 x 65

    Weight g 290

    Standards EN54-11

    OPTION

    FMC-200RSWP Weatherproof call point with re-settable plastic element

    ACCESSORIES FOR FMC CALL POINTS

    FMC-KEY Spare test key (pack of 10)

    FMC-10G Spare glass (pack of 10)

    FMC-10GRS Spare re-settable element (pack of 10)

    FMC-PC Polycarbonate cover

    FMC-PCS Polycarbonate cover with security tie

    RSL800 Fire call point notice sticker

    SPARES FOR FMC INDOOR CALL POINTS

    FMC-BBR Back box in red

    FMC-BBW Back box in green

    FMC-200R

    FMC-200RWP

    For standard and weatherproofprotective call point covers, seepage 88.

    RSL800

  • www.emergi-lite.co.uk

    64

    Conventional 4-wire call points

    Conventional | Conventional 4-wire call points

    Call point FMC-800RSurface mounted manually operated call point, providing a switch closureto the panel when operated. Features:

    � Secure clip-fix front cover

    � A single key for test, reset and removal of cover

    SPECIFICATION

    Voltage range 24Vdc

    Impedance 470R series resistor

    Operating temperature –25 to +55ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination 4 way terminal block

    Construction ABS plastic in red

    Ingress rating IP42

    Dimensions lwd (mm) 87 x 87 x 53 (20 without back box)

    Weight g 190

    Standards EN54-11

    OPTION

    FMC-800RS Call point with re-settable plastic element

    Weather resistant call point FMC-800RWPSurface mounted manually operated call point, providing a switch closureto the panel when operated. Features:

    � Secure clip-fix front cover

    � One key for test, reset and removal of cover

    � Weatherproof to IP67

    SPECIFICATION

    Voltage range 24Vdc

    Impedance 470R series resistor

    Operating temperature –25 to +55ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination 4 way terminal block

    Construction ABS plastic in red

    Ingress rating IP67

    Dimensions lwd (mm) 110 x 110 x 65

    Weight g 290

    Standards EN54-11

    OPTION

    FMC-800RSWP Weatherproof call point with re-settable plastic element

    ACCESSORIES FOR FMC CALL POINTS

    FMC-KEY Spare test key (pack of 10)

    FMC-10G Spare glass (pack of 10)

    FMC-10GRS Spare re-settable element (pack of 10)

    FMC-PC Polycarbonate cover

    FMC-PCS Polycarbonate cover with security tie

    RSL800 Fire call point notice sticker

    SPARES FOR FMC INDOOR CALL POINTS

    FMC-BBR Back box in red

    FMC-BBW Back box in green

    FMC-800R

    FMC-800RWP

    For standard and weatherproofprotective call point covers, seepage 88.

    RSL800

  • 65

    www.emergi-lite.co.uk Conventional 4-wire call points/ancillary | Conventional

    Conventional 4-wirecall points/ancillary

    Key-switch operated call point FMC-2KSWA key-switch operated call point for use in secure premises where restrictedaccess is needed.

    � Suitable for use with 230Vac systems

    SPECIFICATION

    Voltage range 24Vdc

    Operation 2 position keyswitch with 1 NO contact and 1 NC contact

    Switch rating 10A, 24Vdc 2A, 230Vac

    Operating temperature –25 to +55ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination Flying lead connections

    Construction ABS plastic in red

    Ingress rating IP42, when fitted to a standard back box

    Dimensions lwd (mm) 87 x 87 x 20

    Weight g 190

    Standards EN54-11

    Fitting The 2KSW can be used with either a standard or a weatherresistant back box.

    FMC-2KSW

    Remote Indicator unit FAP6-P10A remote indicator is used to help an investigator quickly identify thelocation where a device has registered a fire, without having to gain entryto every room or inaccessible space. Features:

    � Fire detector operated text

    SPECIFICATION

    LED indicator Red

    Termination Terminal block

    IP rating IP42

    Dimensions lwd (mm) 86.5 x 86.5 x 9

    Weight g 38

    Ceiling tile mounting box FAP-MBCTThe fixture is used to fit a detector or sounder into a false ceiling matrix.The devices can be pre-wired and tested before the ceiling is fitted. Withthe ceiling tiles in place, the MBCT assemblies can be slotted into place.

    FAP6-P10

    FAP-MBCT-FD

    STANDARD ORDER CODE DESCRIPTION

    FAP-MBCT-FD Ceiling tile mounting box for detectors

    FAP-MBCT-SO Ceiling tile mounting box for sounders

    o o

    Remote indicator

    Closed roomspace

    Normaldetection:

    Indicator visible

    Illustration: Use of remote indicatorin conventional fire system

    Corridor

    Vision panel in doorSolid door

    L1 in

    L1 out

    - RZone+

    Zone -

    End of linedevice

    Example: Connecting a remote indicator to anFAP6 detector base (shown common across

    two detectors) in a zone

    L2Earth

    L1 in

    L1 out

    L2

    - R

    Note: A diode is normallyfitted between L1 in & L1 out

    LED-

    COM-

    IN+

    OUT+LED-

    COM-

    IN+

    OUT+

    Connection of remote LED unitto FAPO Orbis detector

    EO

    L

    Zone

    Zone -ve

    Zone +ve

    Note: A diode is normallyfitted between IN+ & OUT-

    Remote LEDindicator

  • 66

    www.emergi-lite.co.uk

    Conventional 4-wire alarms

    Conventional | Conventional 4-wire alarms

    FACS Conventional 4-wire sounders,beacons and alarm bellsEmergi-Lite Safety Systems offers a range of sounderand alarm options, for use with Firetec and Eurofire4-wire panels.

    The table below highlights the key features ofindividual alarms to assist with planning and selection,when preparing a fire detection and evacuationsystem.

    PRODUCT CODE DESCRIPTION

    FACS-5W Sounder base � W � 67

    FACS-5TPR Sounder base cap R � 67

    FACS-5TPW Sounder base cap W � 67

    FACS-1R Sounder � � R 67

    FACS-1RL Sounder � � R � 67

    FACS-1W Sounder � � W 67

    FACS-1WL Sounder � � W � 67

    FACS-BBR Back box for FACS1R R � 67

    FACS-BBW Back box for FACS1W W � 67

    FACS-4R Sounder � R � 68

    FACS-4RDB Sounder � R 65 � 68

    FACS-4W Sounder � W � 68

    FACS-4WDB Sounder � W 65 � 68

    FACS-8R Sounder-beacon � R R � � 68

    FACS-8RDB Sounder-beacon � R R 65 � � 68

    FACS-8RDB-A Sounder-beacon � A R 65 � � 68

    FACS-8W Sounder-beacon � R W � � 68

    FACS-8WDB Sounder-beacon � R W 65 � � 68

    FACS-BEA-R Beacon � R R 69

    FACS-BEA-RDB Beacon � R R 65 69

    FACB-624 Bell � R 69

    FACB-624-G Bell � G 69

    FAAB-624-WP Bell � R 55 70

    Feat

    ure

    s:

    Bell

    6in

    diam

    Beac

    on

    Soun

    der

    Soun

    der:

    room

    /be

    dhea

    d

    Soun

    der

    beac

    on

    Am

    ber,

    Cle

    aror

    Red

    lens

    Red.

    Whi

    teor

    Gre

    ybo

    dy

    Vis

    ualL

    ED

    IPra

    ting

    100

    dB(A

    )

    Inte

    grat

    edba

    se

    Acc

    esso

    ries

    32To

    nera

    nge

    Page

    refe

    renc

    e

  • 67

    www.emergi-lite.co.uk

    Conventional 4-wire alarms

    Conventional 4-wire alarms | Conventional

    Low profile sounder FACS-5WA low height sounder that can be used standalone with an optional coveror as a platform for a smoke/heat detector with a detector base. Features:

    � Four selectable tones including warble, pips and sweep

    SPECIFICATION

    Voltage range 8 – 35Vdc

    Current draw @ 24Vdc 11mA

    Sound output, at 1m (dBA) 91 (94 with cover plate)

    No. of tones 4

    Operating frequency 800Hz to 1Khz

    Operating temperature –20 to +70ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination Terminal block

    Cable entry Rear

    Construction ABS plastic

    Ingress rating IP43 (DB version - IP65)

    Dimensions ø h (mm) 106 x 25 (35 with cover)

    Weight g 121

    OPTIONS

    FACS-5TPW White cover

    FACS-5TPR Red cover

    Room sounder FACS-1RA room sounder, suitable for bedroom and passageway use. Features:

    � Low profile with a small footprint

    � Audio/visual version with flashing LEDs on alarm

    � Four selectable tones including warble, pips and sweep

    SPECIFICATION

    Voltage range 8 – 35Vdc

    Current draw @ 24Vdc 11mA

    Sound output, at 1m (dBA) 97

    No. of tones 4

    Volume control -50dBA

    Operating frequency 800Hz to 1Khz

    Operating temperature -20 to +70ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination Terminal block

    Cable entry Rear (or side entry with surface box)

    Construction ABS plastic

    Ingress rating IP43

    Dimensions lwd (mm) 86.5 x 86.5 x 9 (+25.2 back box or recessed)

    Weight g 103

    OPTIONS

    FACS-1RL Room sounder, red, with two flashing hi-intensity LEDs

    FACS-1W Room sounder, white

    FACS-1WL Room sounder, white, with two flashing hi-intensity LEDs

    FACS-BBR Back box for FACS-1R

    FACS-BBW Back fox for FACS-1W

    FACS-5W

    FACS-5TPW

    FACS-1R

  • www.emergi-lite.co.uk

    68

    Conventional 4-wire alarms

    Conventional | Conventional 4-wire alarms

    Open area sounder FACS-4RA multi-tone sounder for open area use, operating across a range offrequencies. Features:

    � Quick fit installation

    � 32 tones, selectable by DIL switch

    � High, medium and low outputs can be selected to fit in with a localsound pattern requirement

    � Side grub screw for security locking

    SPECIFICATION

    Voltage range 15 – 35Vdc

    Sound level Low Med Hi

    Current draw @ 24Vdc

  • 69

    www.emergi-lite.co.uk Conventional 4-wire alarms | Conventional

    Conventional 4-wire alarms

    Alarm beacon FACS-BEA-RA bright output flashing beacon to augment sounders, particularly in areasof higher ambient noise. LED light source with low power requirement.

    SPECIFICATION

    Voltage range 20 – 35Vdc

    Set up Standard Low

    Current draw @ 24Vdc 5mA 3mA

    Light output (equiv) @24Vdc 0.7w 0.4w

    Operating frequency 1Hz

    Operating temperature –20 to +70ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination 6 way angled terminal block

    Cable entry Rear (DB - rear or side entry)

    Construction ABS plastic in red

    Ingress rating IP43 (DB version - IP65)

    Dimensions ø h (mm) 93.6 (DB-93) x 60.2 (DB-77.1)

    Weight g 145

    OPTION

    FACS-BEA-RDB Alarm beacon, deep base

    FACS-BEA-R

    FACS-BEA-RDB

    Alarm fire bell FACB-624A wall mountable motorised fire bell for fire alarm or class change.The gong is secured by a tamper resistant bolt.

    SPECIFICATION

    Voltage range 18 – 28Vdc

    Current draw @ 24Vdc 25mA

    Sound output, at 1m (dBA) 96

    Operating temperature –10 to +55ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination 4 way terminal block

    Cable entry Rear (or side entry with surface box)

    Construction Metal gong in red

    Ingress rating IP42

    Dimensions ø h (mm) 150 x 54

    Weight g 527

    OPTION

    FACB-624-G Alarm fire bell with grey gong

    FACB-624

  • www.emergi-lite.co.uk

    70

    Conventional 4-wire alarms

    Conventional | Conventional 4-wire alarms

    Alarm fire bell FAAB-624-WPA wall mountable fire bell for fire alarm or class change applications.Weather resistant rating achieved with a rubber gasket.

    SPECIFICATION

    Voltage range 18 – 30Vdc

    Current draw @ 24Vdc 30mA

    Sound output, at 1m (dBA) 93 – 95

    Operating temperature –10 to +55ºC

    Wiring & polarity 2 wire supply, polarity sensitive

    Termination 4 way terminal block

    Cable entry Rear (or side entry with surface box)

    Construction Metal gong in red, base in polycarbonate

    Ingress rating IP55

    Dimensions ø h (mm) 150 x 85

    Weight g 1,100

    FAAB-624-WP