Governor and AGC Control of System Frequency TRE Technical Workshop March 31, 2009 Bob Green Garland Power and Light
Transcript
  • Governor and AGC Controlof System Frequency

    TRE Technical WorkshopMarch 31, 2009Bob GreenGarland Power and Light

  • Two generators equipped withgovernors having output feedback

  • Schematic of a governor with output feedback

  • Response of governor with output feedback

  • Steady-state speed characteristic (droop) curve

  • R(per unit), the slope of the droop curve, is defined as f(p.u.)/ P(p.u.), where f(p.u.)= f(HZ) / 60.0,and P(p.u.)= P(MW) / Unit Capacity.For a 600 MW unit that has a governor response of 20 MW for a frequency excursion that settles out at 59.9 HZ, R=f(p.u.) / P(p.u.) = (0.1/60)/(20/600)=0.05 or 5% droop.

    Once the droop is known, the MW response to frequency deviation can be determined by (P/f)=(1/R), or P=(1/R) X f.For the 600 MW unit with 5% droop, (P/600)=(1/0.05) X (f/60), or P=200MW/HZCalculation of steady-state speed characteristic

  • So, how do governors with the steady-state speed characteristic interact when there are multiple generators in a power system?

    What determines the steady state system frequency after a load is added to the system?

  • Multiple Generator Governor ResponseConsider an isolated power system with three generators on-line and operating at 60HZ. The load is 360 MW and the generator outputs for units #1, #2 and #3 are 80MW, 120MW and 160MW, respectively.A load of 21MW (P) is added. What frequency does the system settle at? How much does each unit pick-up (MW)?Since R(p.u.)=( f(HZ)/60)/( P(MW)/Capacity), then (P/f)=(1/R) X Capacity/60).

    UNITCAPACITYR (DROOP)P/f#1300MW0.100 (10%)50MW/HZ#2450MW0.075 (7.5%)100MW/HZ#3600MW0.050 (5%)200MW/HZSolution:Unit #1: P1=50 X fUnit #2: P2=100 X fUnit #3: P3=200 X fPi=350f=21MW,and f=21/350=0.06HZFrequency=60-0.06=59.94HZP1=50 X 0.06=3MWP2=100 X 0.06=6MWP3=200 X 0.06=12MW check: Pi=21MW

  • Three generators serving 360MW

  • Three generators serving 367MW

  • Three generators serving 374MW

  • Three generators serving 381MW

  • The system frequency reaches steady-state at a value that causes the sum of the on-line generator output MW to be equal to the system load MW.With this type of governor, when the system load increases, the system frequency decreases and visa versa.How do we control frequency to 60HZ, no matter what the load is?

  • Power system equipped for supplemental control

  • Addition of a speed changer

  • Steady-state speed characteristic with speed changer

  • Power output as a function of frequency

  • How does the addition of the speed changer to the governor facilitate the control of frequency? Hint: The system frequency reaches steady-state at a value that causes the sum of the on-line generator output MW to be equal to the system load MW.

  • From a central site, you increase or decrease the 60HZ set-points until the sum of the 60HZ set-points is equal to the system load. Then the frequency will stabilize at 60HZ.This form of supplemental control is called Automatic Generation Control (AGC) and more specifically, Load Frequency Control (LFC).

  • Load of 367MW and 60HZ SPs increased by 7 MW

  • Load as a function of frequency (load damping)

  • Governor and load characteristic curve intersection

  • Illustration of typical governor dead band

  • Generation oscillations at the dead band frequency

  • Primary ControlSecondary or Supplementary ControlCommon NameGovernor Control/ResponseAGC Control/ResponseFunction-GenericHolds the system together as load changes occur and also as un-commanded generation excursions occurShifts generation between units to achieve security and economic objectives plus restores frequency to the rated value.Function-TechnicalProvides the correct amount of mechanical input to turbines to match the electrical output of the corresponding generatorsChanges the 60HZ governor set-points of the units to achieve scheduled values established by the market.Control InputFrequency/rotational speed of the turbineIn ERCOT, the SCE for the portfolio of unitsControl Time ConstantFast - SecondsSlower - Tens of seconds and minutesStyle of ControlLocal within the Units/PGCsA QSE has no direct control over governor response.Centralized from ERCOT to Units via QSEsPerformance OptimizationHaving more governors on-line (with a given droop characteristic) will minimize the magnitude of frequency deviationsHaving more units being controlled by AGC will minimize the duration of frequency deviationsKey ParametersSteady state speed characteristic (droop), governor dead-band, first stage boiler pressure (steam units) and head (hydro units)Base power schedule plus deployments of balancing energy, regulation energy, responsive and non-spinning reserve. AGC dead-band, gains and frequency bias term.Market CharacteristicsIf there ever is a governor response market, there will probably be bids, awards and settlement, but the market will never deploy the governor response.Bids, awards, deployments and settlement through the Ancillary Service Market. Performance monitoring of individual Services is approximate and complicated.Disturbance TimelineInitial governor response (to point B) is over completely by the time units start receiving secondary control signals in response to the disturbance.There needs to be recognition of governor response and coordination between RRS and RegUp deployments to insure smooth , rapid and sustained frequency recovery.