Coordination of Protection to IEC 60947-4-1 Coordination Tables 1SBC 0097 00 R1001 edition Dec 2001
Transcript
Page 1: Type Selection Tables

Coordinationof Protectionto IEC 60947-4-1

Coordination Tables

1SBC 0097 00 R1001 edition Dec 2001

Page 2: Type Selection Tables

ABB is providing a large offer of coordination tables needed for any motor supply feeder for which protection against overload and short circuit are mandatory in industrial applications. Choice GuidanceFor instance, a table given for 80kA is covering the intermediate short circuit leveel i.e. 70, 60,...kA at the same voltage. However, you may find some cheaper solution for lower short circuit levels in the database : the SCPD upstream is calibrated to give the cheapest solution for the whole combination starter according to the highest shor circuit level. General Remarks- to read before using the coordination tables Please read those remarks before you start using the coordination. They will give you the general data and help you use the tables properly.

Following basic functions are achieved : overload protection, motor control, short circuit protection, isolation. These functions are applied here for standard starters : direct-on-line (DOL), reverser, star-delta, softstarters.

Coordination TypesAny table is in conformity with the standard IEC 60947-4-1 which defines two types of coodinations : - Type 1 : there is not any risk for the operator and assets, damage to the starter is acceptable, its replacement for re-starting is generally necessary. - Type 2 : the single acceptable risk is a light welding of the contactor, that means the contacts shall be easily separated either by electrical control or using a tool. After a short circuit, whatever its level, re-starting is allowed after a few verifications : all the protection device functions are still operational.

Short Circuit Protection DevicesThe starters given in the tables are protected starters or combination starters i.e. the SCPD (Short Circuit Protection Device) and the starter are mounted in the same compartment or enclosure. Various SPCDs are proposed : Moulded-Case Circuit Breaker (MCCB), Manual Motor Starter (MMS), Switch-Disconnector-Fuse or Switch-Fuse. Circuit Breakers or fuses coordinated with starters cannot be determined directly : tests in Power Laboratories shall be carried out to qualify the coordination type at low fault and high fault currents. ABB has got a large knowledge about short circuit protection in its qualified Laboratories in Europe (Low Voltage Agreement Group : LOVAG). Use of a SCPD not in compliance with the manufacturers' recommandations (type, settings) may invalidate the coordination.

>> Coordination Tables - choose your type of protection- Fuses- MCCBs- MMS- MCBs- Softstarters- UL Combination Starters

Page 3: Type Selection Tables

General Remarks

Motor Current Magnetic Tripping CurrentTables are based on 4-pole, 3-phase motor currents. Indicative currents are given.

Magnetic tripping current is everytime indicated and chosen to withstand the sub transient current at the starting phase

Ambient Temperature Safety PerimeterTables are given for 40°C ambient temperature. For higher temperature a derating factor must be applied : Fuses : 0.8 to In when ambient temperature is 70°C MCCBs : 0.8 to In when ambient temperature is 60°C Thermal Overload Relay without derating up to 55°C, 0.9 In at 70°C

It indicates the minimum distances of any metallic plates from the components in order to avoid any breakdown during short circuit.

Starting Reverser TableNormal starting means up to 5s (cold state) at full speed (class 10) and up to 2s (warm state) Long starting or heavy duty means starting time between 5 to 30s (class 30)Thermal overload relays DU type and MMS are class 10AThermal overload relays SU type are class 30

A "reverser" (two identical contactors) table is given by the corresponding "DOL" table

Heavy duty star-delta startersHeavy duty star-delta starters are star-delta starters for which : - the motor speed reached at the end of the star period is less than 85% of the nominal one, mainly due to the incertainty of the load inertia - the connecting diagram to the motor is not in accordance with the one described in Main catalogue 1SBC0004 99 R1001 (p 8/10) - the dwelling time (transition between star and delta connection) is longer than 80msNote : one only of the above conditions leads to "heavy duty" class.

.

Page 4: Type Selection Tables

FUSE

UeV

IqkA

Coor.type

Startingtype

SCPDtype

SCPDcurve

SizekW

Table Last Update

400 50 1 Normal Din Fuse gG 0.37 ... 7.5 FG4050NS1,1a/b 04/02/002 Normal Din Fuse gG 0.37 ... 7.5 FG4050NS2.1a/b 04/02/00

80 2 Normal Din Fuse gG 0.37 ... 355 FG4080NS2.1af 29/08/01aM 0.37 ... 290 FM4080NS2.1af 29/08/01

2 Normal Din Fuse gG 0.37 ... 250 FG4080NSIN2.1 04/02/00aM 0.37 ... 290 FM4080NSIN2.1 04/02/00

2 HD Din Fuse gG 0.37 ... 200 FG4080HDIN2.1 04/02/00aM 0.37 ... 200 FM4080HDIN2.1 04/02/00

2 HD Din Fuse gG 0.37... 200 FG4080HD2.1 04/02/00aM 0.37 ... 250 FM4080HD2.1af 12/11/01

1 SD Din Fuse aM 4 ... 355 FM4080SD1.1 27/09/00gG 4 ... 355 FG4080SD1.1 27/09/00

2 SD Din Fuse aM 4 ... 355 FM4080SD2.1 05/04/00gG 4 ... 355 FG4080SD2.1 05/04/00

100 1 Normal Din Fuse gG 0.37 ... 55 FG4000NS1.1 04/02/00aM 0.37 ... 55 FM4000NS1.1 04/02/00

415 80 2 Normal BS Fuse gM 0.37 ... 355 FGB4180NS2.1 04/02/00440 80 2 Normal Din Fuse gG 0.37 ... 55 FG4480NS2.1 04/02/00

aM 0.37 ... 55 FM4480NS2.1 04/02/00500 80 2 Normal Din Fuse gG 0.37 ... 315 FG5080NS2.1af 29/08/01

aM 0.37 ... 315 FM5080NS2.1af 29/08/012 Normal Din Fuse gG 0.37 ... 355 FG5080NSIN2.1 04/02/00

aM 0.37 ... 355 FM5080NSIN2.1 04/02/002 HD Din Fuse gG 0.37 ... 200 FG5080HDIN2.1 04/02/00

aM 0.37 ... 200 FM5080HDIN2.1 04/02/002 HD Din Fuse gG 0.37 ... 200 FG5080HD2.1 04/02/00

aM 0.37 ... 200 FM5080HD2.1 04/02/001 SD Din Fuse aM 4 ... 400 FM5080SD1.1 27/09/00

gG 4 ... 355 FG5080SD1.1 27/09/002 SD Din Fuse gG 4 ... 355 FG5080SD2.1 05/04/00

aM 4 ... 400 FM5080SD2.1 05/04/00690 35 1 Normal Din Fuse gG 0.37 ... 11 FG6935NS1.1 04/02/00

2 Normal Din Fuse gG 0.37 ...11 FG6935NS2.1 04/02/0050 2 Normal Din Fuse gG 1.1 ... 500 FG6950NS2.1af 29/08/01

aM 1.1 ... 500 FM6950NS2.1af 29/08/012 Normal Din Fuse gG 0.37 ... 355 FG6950NSIN2.1 04/02/00

aM 0.37 ... 355 FM6950NSIN2.1 04/02/002 HD Din Fuse gG 0.37 ... 200 FG6950HDIN2.1 04/02/00

aM 0.37 ... 200 FM6950HDIN2.1 04/02/002 HD Din Fuse gG 0.37 ... 200 FG6950HD2.1 04/02/00

aM 0.37 ... 315 FM6950HD2.1 04/02/001 SD Din Fuse aM 4 ... 560 FM6950SD1.1 27/09/00

gG 4 ... 400 FG6950SD1.1 27/09/002 SD Din Fuse gG 4 ... 400 FG6950SD2.1 05/04/00

aM 4 ... 400 FM6950SD2.1 05/04/00Glossary SCPD Short Circuit Protection Device gG Fuselink for general protectionHDNS

Heavy DutyNormal start

aM Fuselink for motor starter protection

SD Star Delta IN INSUM Motor Protection

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 5: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 1Note : FG4050NS1.1a/b

gG

Fuse type gG

Direct-on-line starters with Switch - fuse400 V, 50 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse type gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 OS32D 10 00 B6 15 E16DU2.7 0.9 - 2.7 2.70.55 1.5 OS32D 10 00 B6 15 E16DU2.7 0.9 - 2.7 2.70.75 2 OS32D 10 00 B6 15 E16DU2.7 0.9 - 2.7 2.71.1 2.6 OS32D 10 00 B6 15 E16DU2.7 0.9 - 2.7 2.71.5 3.5 OS32D 20 00 B6 15 E16DU6.3 2 - 6.3 2.72.2 5 OS32D 20 00 B6 15 E16DU6.3 2 - 6.3 6.33 6.6 OS32D 25 00 B7 15 E16DU18.9 5.7 - 18.9 94 8.5 OS32D 25 00 B7 15 E16DU18.9 5.7 - 18.9 9

5.5 11.5 OS32D 25 00 B7 15 E16DU18.9 5.7 - 18.9 127.5 15.2 OS32D 40 00 A16 15 E16DU18.9 5.7 - 18.9 16

FG4050NS1.1bFuse type gG

Direct-on-line starters with Switch - fuse400 V, 50kA, Normal start - up, type 1

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse type gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 OS32D 10 00 A9 15 E16DU2.7 0.9 - 2.7 2.70.55 1.5 OS32D 10 00 A9 15 E16DU2.7 0.9 - 2.7 2.70.75 2 OS32D 10 00 A9 15 E16DU2.7 0.9 - 2.7 2.71.1 2.6 OS32D 10 00 A9 15 E16DU2.7 0.9 - 2.7 2.71.5 3.5 OS32D 20 00 A9 15 E16DU6.3 2,0 - 6.3 2.72.2 5 OS32D 20 00 A9 15 E16DU6.3 2,0 - 6.3 6.33 6.6 OS32D 25 00 A9 15 E16DU18.9 5.7 - 18.9 94 8.5 OS32D 35 00 A9 15 E16DU18.9 5.7 - 18.9 9

5.5 11.5 OS32D 40 00 A12 15 E16DU18.9 5.7 - 18.9 127.5 15.2 OS32D 40 00 A16 15 E16DU18.9 5.7 - 18.9 16

FG4050NS1.1a

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2000 by Jean-Paul Guitton

Page 6: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 2Note : FG4050NS2.1a/b

gG

Fuse type gG

Direct-on-line starters with Switch - fuse400 V, 50 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse type gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 OS32D 10 00 B7 15 E16DU2.7 0.9 - 2.7 2.70.55 1.5 OS32D 10 00 B7 15 E16DU2.7 0.9 - 2.7 2.70.75 2 OS32D 10 00 B7 15 E16DU2.7 0.9 - 2.7 2.71.1 2.6 OS32D 10 00 B7 15 E16DU2.7 0.9 - 2.7 2.71.5 3.5 OS32D 20 00 B7 15 E16DU6.3 2 - 6.3 6.32.2 5 OS32D 20 00 B7 15 E16DU6.3 2 - 6.3 6.33 6.6 OS32D 20 00 B7 15 E16DU18.9 5.7 - 18.9 94 8.5 OS32D 20 00 B7 15 E16DU18.9 5.7 - 18.9 9

5.5 11.5 OS32D 20 00 B7 15 E16DU18.9 5.7 - 18.9 127.5 15.2 OS32D 25 00 A16 15 E16DU18.9 5.7 - 18.9 16

FG4050NS2.1bFuse type gG

Direct-on-line starters with Switch - fuse400 V, 50kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse type gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 OS32D 10 00 A9 15 E16DU2,7 0,9 - 2,7 2.70.55 1.5 OS32D 10 00 A9 15 E16DU2,7 0,9 - 2,7 2.70.75 2 OS32D 10 00 A9 15 E16DU2,7 0,9 - 2,7 2.71.1 2.6 OS32D 10 00 A9 15 E16DU2,7 0,9 - 2,7 2.71.5 3.5 OS32D 20 00 A9 15 E16DU6,3 2 - 6,3 2.72.2 5 OS32D 20 00 A9 15 E16DU6,3 2 - 6,3 6.33 6.6 OS32D 20 00 A9 15 E16DU18,9 5,7 - 18,9 94 8.5 OS32D 20 00 A9 15 E16DU18,9 5,7 - 18,9 9

5.5 11.5 OS32D 20 00 A12 15 E16DU18,9 5,7 - 18,9 127.5 15.2 OS32D 25 00 A16 15 E16DU18,9 5,7 - 18,9 16

FG4050NS2.1a

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2000 by Jean-Paul Guitton

Page 7: Type Selection Tables

Direct-on-line starters 400 V - 80 kA - Normal start - up, type : 2Note : FG4080NS2.1af

gG

Fuse type gG

Direct-on-line starters with Switch - fuse400 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse type*gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] max [A]0.37 1.2 OS32D 4 OFAA00H A9 15 TA25DU1.4 1 - 1.4 1.40.55 1.5 OS32D 6 OFAA00H A9 15 TA25DU1.8 1.3 - 1.8 1.80.75 2 OS32D 6 OFAA00H A9 15 TA25DU2.4 1.7 - 2.4 2.41.1 2.6 OS32D 10 OFAA00H A9 15 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 OS32D 10 OFAA00H A9 15 TA25DU4 2.8 - 4 4

OS32D 10 OFAA00H A9 15 TA25DU5 3.5 - 5 52.2 5 OS32D 16 OFAA00H A9 15 TA25DU6.5 4.5 - 6.5 6.53 6.6 OS32D 16 OFAA00H A9 15 TA25DU8.5 6 - 8.5 8.54 8.5 OS32D 25 OFAA00H A9 15 TA25DU11 7.5 - 11 9

5.5 11.5 OS32D 32 OFAA00H A12 15 TA25DU14 10 - 14 127.5 15.5

19OS32DOS32D

3240

OFAA00HOFAA00H

A16A26

1520

TA25DU19TA25DU19

13 - 1913 - 19

1619

11 2225

OS32DOS32D

5063

OFAA00HOFAA00H

A26A26

2020

TA25DU25TA25DU25

18 - 2518 - 25

2225

15 3032

OS32DOS32D

6380

OFAA00HOFAA00H

A30A30

2020

TA25DU32TA25DU32

24 - 3224 - 32

3032

18.5 37 OS63D 100 OFAA00H A40 20 TA42DU42 29 - 42 4022 44

50OS63D

OS125D100125

OFAA00HOFAA00H

A50A50

2020

TA75DU52TA75DU52

36 - 5236 - 52

4450

30 6063

OS125DOESA250D

125160

OFAA00HOFAA1H

A63A63

2020

TA75DU63TA75DU63

45 - 6345 - 63

6063

37 72 OESA250D 160 OFAA1H A75 20 TA75DU80 60 - 80 7545 85 OESA250D 200 OFAA1H A95 30 TA110DU90 65 - 90 9055 105 OESA250D 200 OFAA1H A110 30 TA110DU110 80 - 110 11075 135 OESA250D 250 OFAA1H A145 10 TA200DU150 110 - 150 13590 165 OESA400D 315 OFAA2H A185 10 TA200DU175 130 - 175 175110 200 OESA400D 400 OFAA2H A210 10 TA450DU235 165 - 235 210132 240 OESA400D 400 OFAA2H A260 10 TA450DU310 220 - 310 240160 290 OESA630D 500 OFAA3H AF400 10 E500DU(10) 150 - 500 290200 350 OESA630D 630 OFAA3H AF400 10 E500DU(10) 150 - 500 400250 420 OESA630D 630 OFAA3H AF460 10 E500DU(10) 150 - 500 430290 520 OESA800D 800 3 AF580 10 E800DU(10) 250 - 800 580315 545 OESA800D 800 3 AF580 10 E800DU(10) 250 - 800 580355 610 OESA800D 800 3 AF750 10 E800DU(10) 250 - 800 610

FG4080NS2.1af

* : tested with ABB fuses. To use such fuses or fuses with similar characteristics

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 29/08/2001 by Jean-Paul Guitton

Page 8: Type Selection Tables

Direct-on-line starters400 V - 80 kA - Normal start - up, type : 2Note : FM4080NS2.1af

aM

Fuse type aM

Direct-on-line starters with Switch - fuse400 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse* type aM

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 OS32D 2 OFAM00aM A9 15 TA25DU1.4 1 - 1.4 1.40.55 1.5 OS32D 2 OFAM00aM A9 15 TA25DU1.8 1.3 - 1.8 1.80.75 2 OS32D 4 OFAM00aM A9 15 TA25DU2.4 1.7 - 2.4 2.41.1 2.6 OS32D 4 OFAM00aM A9 15 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 OS32D 6 OFAM00aM A9 15 TA25DU4 2.8 - 4 4

OS32D 6 OFAM00aM A9 15 TA25DU5 3.5 - 5 52.2 5 OS32D 6 OFAM00aM A9 15 TA25DU6.5 4.5 - 6.5 6.53 6.6 OS32D 10 OFAM00aM A9 15 TA25DU8.5 6 - 8.5 8.54 8.5 OS32D 16 OFAM00aM A9 15 TA25DU11 7.5 - 11 9

5.5 11.5 OS32D 16 OFAM00aM A12 15 TA25DU14 10 - 14 127.5 15.5 OS32D 20 OFAM00aM A16 15 TA25DU19 13 - 19 1711 22

25OS32DOS32D

2532

OFAM00aMOFAM00aM

A26A26

2020

TA25DU25TA25DU25

18 - 2518 - 25

2225

15 3032

OS32DOS32D

3240

OFAM00aMOFAM00aM

A30A30

2020

TA25DU32TA25DU32

24 - 3224 - 32

3032

18.5 3740

OS63DOS63D

4050

OFAM00aMOFAM00aM

A40A40

2020

TA42DU42TA42DU42

29 - 4229 - 42

3740

22 4450

OS63DOS63D

5063

OFAM00aMOFAM00aM

A50A50

2020

TA75DU52TA75DU52

36 - 5236 - 52

4550

30 6063

OS63DOS63D

6380

OFAM00aMOFAM00aM

A63A63

2020

TA75DU63TA75DU63

45 - 6345 - 63

6063

37 7275

OS125DOS125D

80100

OFAM00aMOFAM00aM

A75A75

2020

TA75DU80TA75DU80

60 - 8060 - 80

7275

45 8595

OS125DOS125D

100125

OFAM00aMOFAM00aM

A95A95

3030

TA110DU90TA110DU110

65 - 9080 - 110

8595

55 105 OS125D 160 OFAM00aM A110 30 TA110DU110 80 - 110 11075 135

145OS160D

OESA250D160200

OFAM00aMOFAM1aM

A145A145

1010

TA200DU150TA200DU150

110 - 150110 - 150

135145

90 165 OESA250D 200 OFAM1aM A185 10 TA200DU175 130 - 175 175110 200 OESA250D 250 OFAM1aM A210 10 TA450DU235 165 - 235 200132 240 OESA400D 315 OFAM2aM A260 10 TA450DU310 220 - 310 250160 280

305OESA400DOESA400D

315355

OFAM2aMOFAM2aM

A300A300

1010

TA450DU310TA450DU310

220 - 310220 - 310

280305

200 350400

OESA400DOESA630D

400500

OFAM2aMOFAM3aM

AF400AF400

1010

E500DU(10)E500DU(10)

150 - 500150 - 500

350400

250 430460

OESA630DOESA630D

500500

OFAM3aMOFAM3aM

AF460AF460

1010

E500DU(10)E500DU(10)

150 - 500150 - 500

430460

290 520 OESA630D 630 OFAM3aM AF580 10 E800DU(10) 250 - 800 520

FM4080NS2.1af

* : tested with ABB fuses. To use such fuses or fuses with similar characteristics

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 29/08/2001 by Jean-Paul Guitton

Page 9: Type Selection Tables

Direct-on-line starters protected by INSUM 2400 V - 80 kA - Normal start - up, type : 2Note : FG4080NSIN2.1[INSUM 2]

gG, INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2400 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 1.1 OS32D 4 OFAA 00 H A9 15 7 1.30.55 1.5 OS32D 6 OFAA 00 H A9 15 7 1.80.75 1.9 OS32D 10 OFAA 00 H A9 15 7 3.41.1 2.8 OS32D 10 OFAA 00 H A9 15 7 3.41.5 3.5 OS32D 16 OFAA 00 H A9 15 7 6.52.2 5.0 OS32D 16 OFAA 00 H A9 15 7 6.53 6.6 OS32D 20 OFAA 00 H A9 15 7 7.54 8.6 OS32D 25 OFAA 00 H A9 15 7 9

5.5 11.5 OS32D

OS32D

32

32

OFAA 00 H

OFAA 00 H

A12

A16

15

15

7

5

13

15

7.5 15.2 OS32D

OS32D

40

50

OFAA 00 H

OFAA 00 H

A26

A26

20

20

7

7

16.5

19.5

11 22 OS32D 63 OFAA 00 H A26 20 7 2615 28.5 OS32D 80 OFAA 00 H A30 20 7 32

18.5 36 OS63D

OS63D

100

100

OFAA 00 H

OFAA 00 H

A40

A50

20

20

7

7

37

40

22 42 0S125D 125 OFAA 00 H A50 20 7 5030 56 OS125D

OESA250D

125

160

OFAA 00 H

OFAA 1 H

A63

A75

20

20

7

7

58

66

37 68 OESA250D 160 OFAA 1 H A75 20 5 7545 83 OESA250D 200 OFAA 1 H A95 20 7 9055 98 OESA250D 250 OFAA 1 H A145 10 7 11575 135 OESA400D 315 OFAA 2 H A145 10 7 14590 158 OESA400D 315 OFAA 2 H A185 10 7 168

110 193 OESA400D 400 OFAA 2 H A260 10 7 210132 232 OESA400D 400 OFAA 2 H A260 10 7 235160 282 OESA630D 500 OFAA 3 H EH370 40 7 290200 349 OESA630D 630 OFAA 3 H EH370 40 7 400250 420 OESA630D

OESA630D

630

630

OFAA 3 H

OFAA 3 H

EH550

EH550

40

40

7

5

440

480

FG4080NSIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Page 10: Type Selection Tables

Direct-on-line starters protected by INSUM 2400 V - 80 kA - Normal start - up, type : 2Note : FM4080NSIN2.1[INSUM 2]

aM , INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2400 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 1.1 OS32D 2 OFAM 00 aM A9 15 7 1.70.55 1.5 OS32D 2 OFAM 00 aM A9 15 7 1.70.75 1.9 OS32D 4 OFAM 00 aM A9 15 7 3.21.1 2.8 OS32D 4 OFAM 00 aM A9 15 7 3.21.5 3.5 OS32D 6 OFAM 00 aM A9 15 7 4.92.2 5 OS32D 10 OFAM 00 aM A9 15 7 7.23 6.6 OS32D 10 OFAM 00 aM A9 15 7 7.24 8.6 OS32D 16 OFAM 00 aM A9 15 7 9

5.5 11.5 OS32D 16 OFAM 00 aM A12 15 7 127.5 15.2 OS32D 20 OFAM 00 aM A16 15 7 1611 22 OS32D

OS32D2532

OFAM 00 aMOFAM 00 aM

A26A26

2020

77

2226

15 28.5 OS32D 40 OFAM 00 aM A30 20 7 3018.5 36 OS63D 50 OFAM 00 aM A40 20 7 3722 42 OS63D 63 OFAM 00 aM A50 20 7 5030 56 OS63D 80 OFAM 00 aM A63 20 7 6537 68 OS125D 100 OFAM 00 aM A75 20 7 7545 83 OS125D 125 OFAM 00 aM A95 20 7 9655 98 OS125D 160 OFAM 00 aM A145 10 7 12575 135 OS160D

OESA250D160200

OFAM 00 aMOFAM 1 aM

A145A145

1010

57

135145

90 158 OESA250D 200 OFAM 1 aM A185 10 7 162110 193 OESA250D 250 OFAM 1 aM A210 10 7 200132 232 OESA400D

OESA400D315355

OFAM 2 aMOFAM 2 aM

A260EH370

1040

77

245275

160 282 OESA400D 400 OFAM 2 aM EH370 40 7 315200 349 OESA630D

OESA630D500500

OFAM 3 aMOFAM 3 aM

EH370EH550

4040

77

400415

250 420 OESA630DOESA630D

500630

OFAM 3 aMOFAM 3 aM

EH550EH550

4040

57

450500

290 520 OESA630D 630 OFAM 3 aM EH550 40 5 520FM4080NSIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 11: Type Selection Tables

Direct-on-line starters protected by INSUM 2400 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FG4080HDIN2.1[INSUM 2]

gG , INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2400 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/ MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 1.1 OS32D 6 OFAA 00 H A9 15 28 1.50.55 1.5 OS32D 10 OFAA 00 H A9 15 28 2.70.75 1.9 OS32D 10 OFAA 00 H A9 15 28 2.71.1 2.8 OS32D 16 OFAA 00 H A9 15 28 51.5 3.5 OS32D 16 OFAA 00 H A9 15 28 52.2 5.0 OS32D 20 OFAA 00 H A9 15 28 63 6.6 OS32D 25 OFAA 00 H A9 15 28 7.14 8.6 OS32D 32 OFAA 00 H A12 15 28 10.5

5.5 11.5 OS32D 40 OFAA 00 H A26 15 28 137.5 15.2 OS32D 50 OFAA 00 H A26 20 28 1611 22 OS32D

OS32D6380

OFAA 00 HOFAA 00 H

A30A30

2020

2828

2226.5

15 28,5 OS32D 100 OFAA 00 H A40 20 28 3218.5 36 OS125D 125 OFAA 00 H A50 20 28 4622 42 OS125D

OESA250D125160

OFAA 00 HOFAA 1 H

A50A63

2020

2828

4651

30 56 OESA250D 200 OFAA 1 H A95 20 28 7037 68 OESA250D 200 OFAA 1 H A95 20 28 7045 83 OESA250D 250 OFAA 1 H A145 10 28 9255 98 OESA400D 315 OFAA 1 H A185 10 28 13075 135 OESA400D 400 OFAA 2 H A210 10 28 15090 158 OESA400D 400 OFAA 2 H A260 10 28 175

110 193 OESA630D 500 OFAA 3 H EH370 40 28 210132 232 OESA630D 630 OFAA 3 H EH370 40 28 328160 282 OESA630D 630 OFAA 3 H EH370 40 28 328200 349 OESA630D 630 OFAA 3 H EH370 40 21 350

FG4080HDIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 12: Type Selection Tables

Direct-on-line starters protected by INSUM 2400 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FM4080HDIN2.1[INSUM 2]

aM , INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2400 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/ MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 1.1 OS32D 2 OFAM 00 aM A9 15 28 1.50.55 1.5 OS32D 4 OFAM 00 aM A9 15 28 2.60.75 1.9 OS32D 4 OFAM 00 aM A9 15 28 2.61.1 2.8 OS32D 6 OFAM 00 aM A9 15 28 41.5 3.5 OS32D 6 OFAM 00 aM A9 15 28 42.2 5.0 OS32D 10 OFAM 00 aM A9 15 28 63 6.6 OS32D 16 OFAM 00 aM A12 15 28 114 8.6 OS32D 16 OFAM 00 aM A12 15 28 11

5.5 11.5 OS32D 20 OFAM 00 aM A16 15 28 137.5 15.2 OS32D

OS32D2532

OFAM 00 aMOFAM 00 aM

A26A30

2020

2828

1820

11 22 OS32D 40 OFAM 00 aM A30 20 28 2515 28.5 OS32D 50 OFAM 00 aM A30 20 28 31

18.5 36 OS63D 63 OFAM 00 aM A50 20 28 4022 42 OS63D 80 OFAM 00 aM A50 20 28 5030 56 OS125D 100 OFAM 00 aM A63 20 28 6037 68 OS125D 125 OFAM 00 aM A95 20 28 7545 83 OS125D 160 OFAM 00 aM A145 20 28 9555 98 OESA250D

OESA250D200200

OFAM 1 aMOFAM 1 aM

A145A185

2020

2828

110125

75 135 OESA250D 250 OFAM 1 aM A210 20 28 15590 158 OESA400D 315 OFAM 2 aM A260 20 28 190

110 193 OESA400D 355 OFAM 2 aM EH370 40 28 215132 232 OESA400D 400 OFAM 2 aM EH370 40 28 245160 282 OESA630D 500 OFAM 3 aM EH370 40 28 320200 349 OESA630D 630 OFAM 3 aM EH550 40 28 380

FM4080HDIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 13: Type Selection Tables

Direct on line starters400 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FG4080HD2.1

gG

Fuse type gG

Direct-on-line starters with Switch - fuse400 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse type gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.1 OS32D 6 00 A9 15 E16DU2.7 30* 0.8 - 2.7 1.50.55 1.5 OS32D 10 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.70.75 1.9 OS32D 10 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.1 2.8 OS32D 16 00 A9 15 E16DU6.3 30* 1.9 - 6.3 4.51.5 3.5 OS32D 16 00 A9 15 E16DU6.3 30* 1.9 - 6.3 4.52.2 5 OS32D 25 00 A9 15 E16DU6.3 30* 1.9 - 6.3 6.33 6.6 OS32D 32 00 A12 15 E16DU18.9 30* 5.7 - 18.9 94 8.6 OS32D 40 00 A26 20 E16DU18.9 30* 5.7 - 18.9 11

5.5 11.5 OS32D 50 00 A26 20 E16DU18.9 30* 5.7 - 18.9 147.5 15.2 OS32D 63 00 A30 20 E16DU18.9 30* 5.7 - 18.9 18.911 22 OS32D 80 00 A30 20 TA450SU80(3) 18.3 - 26.7 2415 28.5 OS32D

OS125D100125

0000

A40A50

2020

TA450SU60(2)TA450SU80(2)

20 - 3027.5 - 40

3035

18.5 36 OS125D 125 00 A50 20 TA450SU105(2) 35 - 52.5 4322 42 OS125D

OESA250D125160

001

A50A63

2020

TA450SU105(2)TA450SU60

35 - 52.540 - 60

4350

30 56 OESA250D 200 1 A95 20 TA450SU60 40 - 60 6037 68 OESA250D 200 1 A95 20 TA450SU80 55 - 80 6845 83 OESA250D 250 1 A145 10 TA450SU105 70 - 105 9055 98 OESA400D 315 2 A185 10 TA450SU105 70 - 105 10575 135 OESA400D 400 2 A210 10 TA450SU140 95 -1 40 14090 158 OESA400D 400 2 A260 10 TA450SU185 130 - 185 165110 193 OESA630D 500 3 EH370 40 T450SU235 165 - 235 205132 232 OESA630D 630 3 EH370 40 T450SU235 165 - 235 235160 290 OESA630D 630 3 EH370 40 T450SU310 220 - 310 300

* : trip class of E16DU (x) : number of primary turns

FG4080HD2.1

Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 14: Type Selection Tables

Direct on line starters400 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FM4080HD2.1af

aM

Fuse type aM

Direct-on-line starters with Switch - fuse400 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Overload Relay

Group

Rated Output

Rated Current

Type FusetypeaM

Size Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 1.1 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.70.55 1.5 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.70.75 1.9 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.1 2.8 OS32D 6 00 A9 15 E16DU6.3 30* 1.9 - 6.3 3.71.5 3.5 OS32D 10 00 A9 15 E16DU6.3 30* 1.9 - 6.3 5.52.2 5 OS32D 10 00 A9 15 E16DU6.3 30* 1.9 - 6.3 5.53 6.6 OS32D 16 00 A12 15 E16DU18.9 30* 5.7 - 18.9 8.54 8.6 OS32D 20 00 A16 15 E16DU18.9 30* 5.7 - 18.9 12

5.5 11.5 OS32D 25 00 A26 20 E16DU18.9 30* 5.7 - 18.9 177.5 15.2 OS32D 32 00 A30 20 E16DU18.9 30* 5.7 - 18.9 18.911 22 OS32D

OS32D4050

0000

A30A30

2020

TA450SU80(3)TA450SU80(3)

18.3 - 26.718.3 - 26.7

2326.7

15 28.5 OS32DOS63D

5063

0000

A40A50

2020

TA450SU80(2)TA450SU80(2)

27.5 - 4027.5 - 40

3035

18.5 36 OS63D 80 00 A63 20 TA450SU80(2) 27.5 - 40 4022 42 OS63D

OS125D80

1000000

A63A95

2020

TA450SU105(2)TA450SU60

35 - 52.540 - 60

4655

30 56 OS125D 100 00 A95 20 TA450SU80 55 - 80 5837 68 OS125D 125 00 A95 10 TA450SU80 55 - 80 7045 83 OS125D 160 00 A145 10 TA450SU105 70 - 105 8855 98 OESA250D

OESA250D200200

11

A145A185

1010

TA450SU105TA450SU140

70 - 10595 - 140

105120

75 135 OESA250D 250 1 A210 10 TA450SU140 95 - 140 14090 158 OESA400D 315 2 A260 10 TA450SU185 130 - 185 170110 210 OESA400D 355 2 A300 10 TA450SU235 165 - 235 230132 250 OESA400D 400 2 AF400 10 E500 30* 150 - 500 260160 320 OESA630D 500 3 AF400 10 E500 30* 150 - 500 330200 380 OESA630D 630 3 AF400 40 E500 30* 150 - 500 400250 470 OESA630D 800 3 AF580 40 E500 30* 150 - 500 500

* : trip class (x) : number of primary turns

FM4080HD2.1af

Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 12/11/2001 by Jean-Paul Guitton

Page 15: Type Selection Tables

Star delta starters with separate TOR400 V - 80 kA - Normal start - up, type : 1Note : FM4080SD1.1

aM

Fuse type aM

Star-Delta starters with Switch - fuse400 V, 80 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Overload Relay

Group

Rated Output

Rated Current

Type Fuserating aM

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 8.6 OS32D 10 OFAM 00 aM A9 A9 A9 TA25DU6.5 4.5 - 6.5 10

5.5 11.5 OS32D 16 OFAM 00 aM A9 A9 A9 TA25DU8.5 5 - 8.5 147.5 15.2 OS32D 20 OFAM 00 aM A9 A9 A9 TA25DU11 7.5 - 11 1811 22 OS32D 25 OFAM 00 aM A12 A12 A9 TA25DU14 10 - 14 2415 28.5 OS32D 32 OFAM 00 aM A16 A16 A12 TA25DU19 13 - 19 32

18.5 36 OS63D 40 OFAM 00 aM A26 A26 A16 TA25DU25 18 - 25 4022 42 OS63D 50 OFAM 00 aM A26 A26 A16 TA25DU32 24 - 32 5030 56 OS63D 63 OFAM 00 aM A40 A40 A26 TA42DU42 29 - 42 6337 68 OS125D 80 OFAM 00 aM A40 A40 A26 TA75DU52 36 - 52 8045 83 OS125D 100 OFAM 00 aM A50 A50 A30 TA75DU63 45 - 63 9555 98 OS125D 125 OFAM 00 aM A63 A63 A40 TA75DU63 45 - 63 10875 135 OS160D 160 OFAM 00 aM A95 A95 A75 TA110DU90 65 - 90 14590 158 OESA250D 200 OFAM 1 aM A110 A110 A95 TA110U110 80 - 110 188110 193 OESA250D 200 OFAM 1 aM A145 A145 A95 TA200DU135 100 - 135 200132 232 OESA250D 250 OFAM 1 aM A145 A145 A110 TA200DU150 110 - 150 250160 282 OESA400D 315 OFAM 2 aM A185 A185 A145 TA200DU175 130 - 175 315200 349 OESA400D

OESA400D

355

400

OFAM 2 aM

OFAM 2 aM

A210

A210

A210

A210

A185

A185

TA450DU235

TA450DU235

165 - 235

165 - 235

355

400

250 430 OESA630D 500 OFAM 3 aM A260 A260 A210 TA450DU310 220 - 310 500290 520 OESA630D 630 OFAM 3 aM AF400 AF400 A300 E500DU500 165 - 500 630315 545 OESA630D 630 OFAM 3 aM AF400 AF400 A300 E500DU500 165 - 500 630355 610 OESA630D 630 OFAM 3 aM AF400 AF400 A300 E500DU500 165 - 500 630

FM4080SD1.1

Created 11/04/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 27/09/2000 by Jean-Paul Guitton

Page 16: Type Selection Tables

Star delta starters with separate TOR400 V - 80 kA - Normal start - up, type : 1Note : FG4080SD1.1

gG

Fuse type gG

Star-Delta starters with Switch - fuse400 V, 80 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 8.6 OS32D 20 OFAA 00 H A9 A9 A9 TA25DU6.5 4.5 - 6.5 10

5.5 11.5 OS32D 25 OFAA 00 H A9 A9 A9 TA25DU8.5 5 - 8.5 137.5 15.2 OS32D 32 OFAA 00 H A9 A9 A9 TA25DU11 7.5 - 11 1811 22 OS32D 40 OFAA 00 H A12 A12 A9 TA25DU14 10 - 14 2415 28.5 OS32D 50 OFAA 00 H A16 A16 A12 TA25DU19 13 - 19 32

18.5 36 OS63D 63 OFAA 00 H A26 A26 A16 TA25DU25 18 - 25 4022 42 OS63D 80 OFAA 00 H A26 A26 A16 TA25DU32 24 - 32 5030 56 OS63D 100 OFAA 00 H A40 A40 A26 TA42DU42 29 - 42 6337 68 OS125D 125 OFAA 00 H A40 A40 A26 TA75DU52 36 - 52 8045 83 OS125D 125 OFAA 00 H A50 A50 A30 TA75DU63 45 - 63 9055 98 OESA250D 160 OFAA 1 H A63 A63 A40 TA75DU63 45 - 63 10875 135 OESA250D 200 OFAA 1 H A95 A95 A75 TA110DU90 65 - 90 14590 158 OESA250D 250 OFAA 1 H A110 A110 A95 TA110DU110 80 - 110 188

110 193 OESA250D 250 OFAA 1 H A145 A145 A110 TA200DU135 100 - 135 200132 232 OESA400D 315 OFAA 2 H A145 A145 A110 TA200DU150 110 - 150 235160 282 OESA400D

OESA400D

315

400

OFAA 2 H

OFAA 2 H

A185

A185

A185

A185

A145

A145

TA200DU175

TA200DU175

130 - 175

130 - 175

285

300

200 349 OESA630D 500 OFAA 3 H A210 A210 A185 TA450DU235 165 - 235 400250 430 OESA630D 500 OFAA 3 H A260 A260 A210 TA450DU310 220 - 310 450290 520 OESA630D 630 OFAA 3 H EH370 EH370 EH260 T450DU400 285 - 400 540315 545 OESA630D 630 OFAA 3 H EH370 EH370 EH260 T450DU400 285 - 400 610355 610 OESA630D 630 OFAA 3 H EH370 EH370 EH260 T450DU400 285 - 400 610

FG4080SD1.1

Created 11/04/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 27/09/2000 by Jean-Paul Guitton

Page 17: Type Selection Tables

Star-delta starters with TOR400 V - 80 kA - Normal start - up, type : 2Note : FM4080SD2.1

aM

Fuse type aM

Star-Delta starters with Switch - fuse400 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating aM

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 8.6 OS32D 10 OFAM 00 aM A9 A9 A9 TA25DU6.5 4.5 - 6.5 10

5.5 11.5 OS32D 16 OFAM 00 aM A12 A12 A9 TA25DU8.5 5 - 8.5 147.5 15.2 OS32D 20 OFAM 00 aM A16 A16 A9 TA25DU11 7.5 - 11 1811 22 OS32D 25 OFAM 00 aM A26 A26 A9 TA25DU14 10 - 14 2415 28.5 OS32D 32 OFAM 00 aM A26 A26 A12 TA25DU19 13 - 19 32

18.5 36 OS63D 40 OFAM 00 aM A26 A26 A16 TA25DU25 18 - 25 4022 42 OS63D 50 OFAM 00 aM A30 A30 A16 TA25DU32 24 - 32 5030 56 OS63D 63 OFAM 00 aM A40 A40 A26 TA42DU42 29 - 42 6337 68 OS125D 80 OFAM 00 aM A50 A50 A26 TA75DU52 36 - 52 8045 83 OS125D 100 OFAM 00 aM A63 A63 A30 TA75DU63 45 - 63 9555 98 OS125D 125 OFAM 00 aM A75 A75 A40 TA75DU63 45 - 63 10875 135 OS160D 160 OFAM 00 aM A145 A145 A75 TA200DU90 65 - 90 14590 158 OESA250D 200 OFAM 1 aM A145 A145 A95 TA200U110 80 - 110 188110 193 OESA250D 200 OFAM 1 aM A145 A145 A95 TA200DU135 100 - 135 200132 232 OESA250D 250 OFAM 1 aM A210 A210 A110 TA450DU185 130 - 185 250160 282 OESA400D 315 OFAM 2 aM A210 A210 A145 TA450DU185 130 - 185 315200 349 OESA400D

OESA400D

355

400

OFAM 2 aM

OFAM 2 aM

EH370

EH370

EH370

EH370

A210

A210

T450DU235

T450DU235

165 - 235

165 - 235

355

400

250 430 OESA630D 500 OFAM 3 aM EH370 EH370 A260 T450DU310 220 - 310 500290 520 OESA630D 630 OFAM 3 aM EH550 EH550 A300 T450DU400 285 - 400 630315 545 OESA630D 630 OFAM 3 aM EH550 EH550 A300 T450DU400 285 - 400 630355 610 OESA630D 630 OFAM 3 aM EH550 EH550 A300 T450DU400 285 - 400 630

FM4080SD2.1

Created 22/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 04/04/2000 by Jean-Paul Guitton

Page 18: Type Selection Tables

Star delta starters with TOR400 V - 80 kA - Normal start - up, type : 2Note : FG4080SD2.1

gG

Fuse type gG

Star-Delta starters with Switch - fuse400 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 8.6 OS32D 20 OFAA 00 H A9 A9 A9 TA25DU6.5 4.5 - 6.5 10

5.5 11.5 OS32D 25 OFAA 00 H A12 A12 A9 TA25DU8.5 5 - 8.5 137.5 15.2 OS32D 32 OFAA 00 H A16 A16 A9 TA25DU11 7.5 - 11 1811 22 OS32D 40 OFAA 00 H A26 A26 A9 TA25DU14 10 - 14 2415 28.5 OS32D 50 OFAA 00 H A26 A26 A12 TA25DU19 13 - 19 32

18.5 36 OS63D 63 OFAA 00 H A26 A26 A16 TA25DU25 18 - 25 4022 42 OS63D 80 OFAA 00 H A30 A30 A16 TA25DU32 24 - 32 5030 56 OS63D 100 OFAA 00 H A40 A40 A26 TA42DU42 29 - 42 6337 68 OS125D 125 OFAA 00 H A50 A50 A26 TA75DU52 36 - 52 8045 83 OS125D 125 OFAA 00 H A63 A63 A30 TA75DU63 45 - 63 9055 98 OESA250D 160 OFAA 1 H A75 A75 A40 TA75DU63 45 - 63 10875 135 OESA250D 200 OFAA 1 H A95 A95 A75 TA110DU90 65 - 90 14590 158 OESA250D 250 OFAA 1 H A145 A145 A95 TA200DU110 80 - 110 188

110 193 OESA250D 250 OFAA 1 H A145 A145 A95 TA200DU135 100 - 135 200132 232 OESA400D 315 OFAA 2 H A145 A145 A110 TA200DU175 130 - 175 235160 282 OESA400D

OESA400D

315

400

OFAA 2 H

OFAA 2 H

A185

A210

A185

A210

A145

A145

TA200DU175

TA450DU185

130 - 175

130 - 185

285

315

200 349 OESA630D 500 OFAA 3 H EH370 EH370 A210 TA450DU235 165 - 235 400250 430 OESA630D 500 OFAA 3 H EH370 EH370 A210 T450DU310 220 - 310 450290 520 OESA630D 630 OFAA 3 H EH370 EH370 A260 T450DU400 285 - 400 540315 545 OESA630D 630 OFAA 3 H EH370 EH370 A300 T450DU400 285 - 400 610355 610 OESA630D 630 OFAA 3 H EH370 EH370 A300 T450DU400 285 - 400 610

FG4080SD2.1

Created 22/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 04/04/2000 by Jean-Paul Guitton

Page 19: Type Selection Tables

Direct-on-line starters400 V - 100 kA - Normal start - up, type : 1Note : FG4000NS1.1

gG

Fuse type gG

Direct-on-line starters with Switch - fuse400 V, 100 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse typegG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] max [A]0.37 1.2 OS32D 6 00 A9 15 TA25DU1.4 1 - 1.4 1.40.55 1.5 OS32D 10 00 A9 15 TA25DU1.8 1.3 - 1.8 1.80.75 2 OS32D 10 00 A9 15 TA25DU2.4 1.7 - 2.4 2.41.1 2.6 OS32D 16 00 A9 15 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 OS32D 16 00 A9 15 TA25DU4.0 2.8 - 4 4

OS32D 16 00 A9 15 TA25DU5.0 3.5 - 5 52.2 5 OS32D 25 00 A9 15 TA25DU6.5 4.5 - 6.5 6.53 6.6 OS32D 25 00 A9 15 TA25DU8.5 6 - 8.5 8.54 8.5 OS32D 32 00 A9 15 TA25DU11 7.5 - 11 9

5.5 11.5 OS32D 40 00 A12 15 TA25DU14 10 - 14 127.5 15.5 OS32D 40 00 A16 15 TA25DU19 13 - 19 1611 22 OS32D 63 00 A26 20 TA25DU25 18 - 25 2515 30 OS32D 80 00 A30 20 TA25DU32 24 - 32 30

18.5 37 OS63D 100 00 A40 20 TA42DU42 29 - 42 3722 44 OESA00 125 00 A50 20 TA75DU52 36 - 52 5030 60 OESA250D 160 1 A63 20 TA75DU63 45 - 63 6337 72 OESA250D 200 1 A75 20 TA75DU80 60 - 80 7545 85 OESA250D 200 1 A95 20 TA110DU90 65 - 90 9055 105 OESA250D 250 1 A110 20 TA110DU110 80 - 110 110

FG4000NS1.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 20: Type Selection Tables

Direct-on-line starters400 V - 100 kA - Normal start - up, type : 1Note : FM4000NS1.1

aM

Fuse type aM

Direct-on-line starters with Switch - fuse 400 V, 100 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse typeaM

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 OS32D 4 00 A9 15 TA25DU1.4 1 - 1.4 1.40.55 1.5 OS32D 4 00 A9 15 TA25DU1.8 1.3 - 1.8 1.80.75 2 OS32D 6 00 A9 15 TA25DU2.4 1.7 - 2.4 2.41.1 2.6 OS32D 6 00 A9 15 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 OS32D 8 00 A9 15 TA25DU4.0 2.8 - 4 4

OS32D 8 00 A9 15 TA25DU5.0 3.5 - 5 52.2 5 OS32D 8 00 A9 15 TA25DU6.5 4.5 - 6.5 6.53 6.6 OS32D 10 00 A9 15 TA25DU8.5 6 - 8.5 8.54 8.5 OS32D 16 00 A9 15 TA25DU11 7.5 - 11 9

5.5 11.5 OS32D 20 00 A12 15 TA25DU14 10 - 14 127.5 15.5 OS32D 25 00 A16 15 TA25DU19 13 - 19 1611 22 OS32D 32 00 A26 20 TA25DU25 18 - 25 2515 30 OS32D 40 00 A30 20 TA25DU32 24 - 32 30

18.5 37 OS63D 50 00 A40 20 TA42DU42 29 - 42 3722 44 OS63D 63 00 A50 20 TA75DU52 36 - 52 5030 60 OESA00 100 1 A63 20 TA75DU63 45 - 63 6337 72 OESA00 100 1 A75 20 TA75DU80 60 - 80 7545 85 OESA00 125 1 A95 20 TA110DU90 65 - 90 9055 105 OESA00 160 1 A110 20 TA110DU110 80 - 110 110

FM4000NS1.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 21: Type Selection Tables

Direct-on-line starters415 V - 80 kA - Normal start - up, type : 2Note : FGB4180NS2.2

BS Fuse

Fuse type BS Direct-on-line starters with Switch - fuse

415 V, 80 kA, Normal start - up, type 2Motor Switch-fuse Contactor Thermal Overload

RelayGroup

RatedOutput

RatedCurrent

415

Type Fuse typeBS Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] max [A]0.37 1.15 OESA20P3A1 NIT4 A1 A9 15 TA25DU1.4 1 - 1.4 1.40.55 1.5 OESA20P3A1 NIT6 A1 A9 15 TA25DU1.8 1.3 - 1.8 1.80.75 2 OESA20P3A1 NIT6 A1 A9 15 TA25DU2.4 1.7 - 2.4 2.41.1 2.5 OESA20P3A1 NIT16 A1 A9 15 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 OESA20P3A1 NIT16 A1 A9 15 TA25DU4 2.8 - 4 42.2 5 OESA20P3A1 NIT16 A1 A9 15 TA25DU5 3.5 - 5 53 6.5 OESA20P3A1 NIT20 A1 A9 15 TA25DU6.5 4.5 - 6.5 8.54 8.4 OESA20P3A1 NIT20 A1 A9 15 TA25DU8.5 6 - 8.5 8.5

5.5 11 OESA20P3A1 NIT20M25 A1 A12 15 TA25DU11 7.5 - 11 11OESA20P3A1 NIT20M25 A1 A16 15 TA25DU14 10 - 14 14

7.5 14 OESA20P3A1 NIT20M32 A1 A16 15 TA25DU19 13 - 19 15.511 21 OESA32P3A2 TIA32M50 A2 A26 20 TA25DU25 18 - 25 2515 28 OESA32P3A2 TIA32M63 A2 A30 20 TA25DU32 24 - 32 30

18.5 35 OS63B3(OESA 63)

TIS63M80 A3 A50 20 TA75DU42 29 - 42 42

22 42 OS63B3 TIS63M80 A3 A50 20 TA75DU52 36 - 52 4530 55 OS63B3 TIS63M100 A3 A63 20 TA75DU63 45 - 63 6337 66 OESA100G1 TC100M125 A4 A75 20 TA75DU80 60 - 80 7045 81 OESA200B3PL1 TC100M160 B1 A95 20 TA110DU90 65 - 90 9055 96 OESA200B3PL1 TC100M200 B1 A110 20 TA110DU110 80 - 110 10075 127 OESA 200 DEO200M250 - A145 10 TA200DU135 100 - 135 13590 156 OESA200 DEO200M250 - A185 10 TA200DU175 130 - 175 175

110 188 OESA315 DEO200M315 - A210 10 TA450DU235 165 - 235 210132 225 OESA315 DEO200M315 - A260 10 TA450DU235 165 - 235 210160 276 OESA400 ED315M355 - A300 10 TA450DU310 220 - 310 270200 339 OESA630 ED400M450 - EH370 40 T450DU400 285 - 400 370250 435 OESA630 630R11/FF630 - EH550 40 T900DU500 355 - 500 500290 475 OESA630 630R11/FF630 - EH550 40 T900DU500 355 - 500 500315 530 OESA630 630R11/FF630 - EH550 40 T900DU650 465 - 650 550355 582 OESA800 800S11/GF800 - EH700 40 T900DU650 465 -650 650

FGB4180NS2.2

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 22: Type Selection Tables

Direct-on-line starters440 V - 80 kA - Normal start - up, type : 2Note : FG4480NS2.1

gG

Fuse type gG

Direct-on-line starters with Switch - fuse440 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse type gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.06 OS32D 4 00 A9 15 TA25DU1.4 1 - 1.4 1.40.55 1.25 OS32D 6 00 A9 15 TA25DU1.4 1- 1.4 1.40.75 1.67 OS32D 6 00 A9 15 TA25DU1.8 1.3 - 1.8 1.8

OS32D 6 00 A9 15 TA25DU2.4 1.7 - 2.4 2.41.1 2.26 OS32D 10 00 A9 15 TA25DU3.1 2.2 - 3.1 3.11.5 3.03 OS32D 10 00 A9 15 TA25DU4.0 2.8 - 4 42.2 4.31 OS32D 16 00 A9 15 TA25DU6.5 3.5 - 5 53 5.8 OS32D 16 00 A9 15 TA25DU6.5 4.5 - 6.5 6.54 7.6 OS32D 25 00 A9 15 TA25DU8.5 6 - 8.5 8.5

5.5 10.3 OS32D 32 00 A12 15 TA25DU11 7.5 - 11 11OS32D 32 00 A16 15 TA25DU19 10 - 14 14

7.5 13.5 OS32D 40 00 A16 15 TA25DU19 13 - 19 1611 19.3 OS32D 50 00 A26 20 TA25DU25 18 - 25 2515 26.3 OS32D 63 00 A30 20 TA25DU32 24 - 32 30

18.5 32 OS63D 80 00 A40 20 TA42DU42 29 - 42 4022 37.1 OS63D 100 00 A50 20 TA75DU42 29 - 42 42

OS63D 100 00 A63 20 TA75DU52 36 - 52 5230 50.1 OESA00 125 00 A63 20 TA75DU63 45 - 63 6337 61.9 OESA250D 160 1 A75 20 TA75DU80 60 - 80 7045 73.9 OESA250D 160 1 A95 20 TA110DU90 65 - 90 9055 90.3 OESA250D 200 1 A110 20 TA110DU110 80 - 110 100

FG4480NS2.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 23: Type Selection Tables

Direct-on-line starters440 V - 80 kA - Normal start - up, type : 2Note : FM4480NS2.1

aM

Fuse type aM

Direct-on-line starters with Switch - fuse 440 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse typeaM

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.06 OS32D 2 00 A9 15 TA25DU1.4 1 - 1.4 1.40.55 1.25 OS32D 2 00 A9 15 TA25DU1.4 1 - 1.4 1.40.75 1.67 OS32D 4 00 A9 15 TA25DU1.8 1.3 - 1.8 1.8

OS32D 4 00 A9 15 TA25DU2.4 1.7 - 2.4 2.41.1 2.26 OS32D 4 00 A9 15 TA25DU3.1 2.2 - 3.1 3.11.5 3.03 OS32D 6 00 A9 15 TA25DU4 2.8 - 4 42.2 4.31 OS32D 6 00 A9 15 TA25DU5 3.5 - 5 53 5.8 OS32D 8 00 A9 15 TA25DU6.5 4.5 - 6.5 6.54 7.6 OS32D 10 00 A9 15 TA25DU8.5 6 - 8.5 8.5

5.5 10.3 OS32D 16 00 A12 15 TA25DU11 7.5 - 11 11OS32D 16 00 A16 15 TA25DU19 10 - 14 11

7.5 13.5 OS32D 20 00 A16 15 TA25DU19 13 - 19 1611 19.3 OS32D 25 00 A26 20 TA25DU25 18 - 25 2515 26.3 OS32D 32 00 A30 20 TA25DU32 24 - 32 30

18.5 32 OS63D 50 00 A40 20 TA42DU42 29 - 42 4022 37.1 OS63D 50 00 A50 20 TA75DU42 29 - 42 42

OS63D 63 00 A63 20 TA75DU52 36 - 52 5230 50.1 OS63D 63 00 A63 20 TA75DU63 45 - 63 6337 61.9 OESA00 100 00 A75 20 TA75DU80 60 - 80 7045 73.9 OESA00 100 00 A95 20 TA110DU90 65 - 90 9055 90.3 OESA00 125 00 A110 20 TA110DU110 80 - 110 100

FM4480NS2.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 24: Type Selection Tables

Direct on line starters500 V - 80 kA - Normal start - up, type : 2Note : FG5080NS2.1af

gG

Fuse type gG

Direct-on-line starters with Switch - fuse 500 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse* typegG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 0.85 OS32D 4 OFAA00H A9 15 TA25DU1 0.63 - 1 10.55 1.2 OS32D 6 OFAA00H A9 15 TA25DU1.4 1 - 1.4 1.40.75 1.48 OS32D 6 OFAA00H A9 15 TA25DU1.8 1.3 - 1.8 1.81.1 2.1 OS32D 10 OFAA00H A9 15 TA25DU2.4 1.7 - 2.4 2.41.5 2.6 OS32D 10 OFAA00H A9 15 TA25DU3.1 2.2 - 3.1 3.12.2 3.8 OS32D 16 OFAA00H A9 15 TA25DU4 2.8 - 4 4

OS32D 16 OFAA00H A9 15 TA25DU5 3.5 - 5 53 5.5 OS32D 16 OFAA00H A9 15 TA25DU6.5 4.5 - 6.5 6.54 8 OS32D 25 OFAA00H A9 15 TA25DU8.5 6 - 8.5 8.5

5.5 911

OS32DOS32D

2532

OFAA00HOFAA00H

A9A12

1515

TA25DU11TA25DU11

7.5 - 117.5 - 11

911

7.5 1214

OS32DOS32D

3232

OFAA00HOFAA00H

A12A16

1515

TA25DU14TA25DU14

10 - 1410 - 14

1214

11 19 OS32D 40 OFAA00H A26 20 TA25DU19 13 - 19 1915 22

25OS32DOS32D

6363

OFAA00HOFAA00H

A26A30

2020

TA25DU25TA25DU25

18 - 2518 - 25

2225

18.5 2832

OS63DOS63D

6380

OFAA00HOFAA00H

A30A40

2020

TA25DU32TA42DU32

24 - 3224 - 32

2832

22 3340

OS63DOS63D

80100

OFAA00HOFAA00H

A40A50

2020

TA42DU42TA75DU42

29 - 4229 - 42

3340

30 4552

OS63DOS125D

100125

OFAA00HOFAA00H

A50A63

2020

TA75DU52TA75DU52

36 - 5236 - 52

4552

37 5560

OS125DOS125D

125125

OFAA00HOFAA00H

A63A75

2020

TA75DU63TA75DU63

45 - 6345 - 63

5560

45 6570

OS125DOESA250D

125160

OFAA00HOFAA1H

A75A95

2030

TA75DU80TA80DU80

60 - 8060 - 80

6570

55 80100

OESA250DOESA250D

160200

OFAA1HOFAA1H

A95A110

3030

TA110DU90TA110DU110

65 - 9080 - 110

80100

75 110 OESA250D 200 OFAA1H A145 10 TA200DU135 100 - 135 11090 135 OESA250D 250 OFAA1H A145 10 TA200DU150 110 - 150 135110 160 OESA400D 315 OFAA2H A185 10 TA200DU175 130 - 175 170132 190 OESA400D 355 OFAA2H A210 10 TA450DU235 165 - 235 200160 230 OESA400D 400 OFAA2H A260 10 TA450DU310 220 - 310 240200 280 OESA630D 500 OFAA3H AF400 10 E500DU(10) 150 - 500 290250 335 OESA630D 630 OFAA3H AF400 10 E500DU(10) 150 - 500 400290 420 OESA630D 630 OFAA3H AF460 10 E500DU(10) 150 - 500 430315 430

580OESA800DOESA800D

800800

33

AF580AF580

1010

E500DU(10)**E800DU(10)

150 - 500250 - 800

500580

FG5080NS2.1af

* : tested with ABB fuses. To use such fuses or fuses with similar characteristics** : mounting kit between contactor and relay is not available

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 29/08/2001 by Jean-Paul Guitton

Page 25: Type Selection Tables

Direct on line starters500 V - 80 kA - Normal start - up, type : 2Note : FM5080NS2.1af

aM

Fuse type aM

Direct-on-line starters with Switch - fuse 500 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse* typeaM

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 0.85 OS32D 2 OFAM00aM A9 15 TA25DU1 0.63 - 1 10.55 1.2 OS32D 2 OFAM00aM A9 15 TA25DU1.4 1 - 1.4 1.40.75 1.48 OS32D 4 OFAM00aM A9 15 TA25DU1.8 1.3 - 1.8 1.81.1 2.1 OS32D 4 OFAM00aM A9 15 TA25DU2.4 1.7 - 2.4 2.41.5 2.6 OS32D 4 OFAM00aM A9 15 TA25DU3.1 2.2 - 3.1 3.12.2 3.8 OS32D 4 OFAM00aM A9 15 TA25DU4 2.8 - 4 4

OS32D 6 OFAM00aM A9 15 TA25DU5 3.5 - 5 53 5.5 OS32D 6 OFAM00aM A9 15 TA25DU6.5 4.5 - 6.5 6.54 8 OS32D 10 OFAM00aM A9 15 TA25DU8.5 6 - 8.5 8.5

5.5 911

OS32DOS32D

1616

OFAM00aMOFAM00aM

A9A12

1515

TA25DU11TA25DU11

7.5 - 117.5 - 11

911

7.5 1214

OS32DOS32D

1616

OFAM00aMOFAM00aM

A12A16

1515

TA25DU14TA25DU14

10 - 1410 - 14

1214

11 19 OS32D 25 OFAM00aM A26 20 TA25DU19 13 - 19 1915 22

25OS32DOS32D

3232

OFAM00aMOFAM00aM

A26A30

2020

TA25DU25TA25DU25

18 - 2518 - 25

2225

18.5 2832

OS63DOS63D

4040

OFAM00aMOFAM00aM

A30A40

2020

TA25DU32TA42DU32

24 - 3224 - 32

2832

22 3340

OS63DOS63D

5050

OFAM00aMOFAM00aM

A40A50

2020

TA42DU42TA75DU42

29 - 4229 - 42

3340

30 4552

OS63DOS63D

6363

OFAM00aMOFAM00aM

A50A63

2020

TA75DU52TA75DU52

36 - 5236 - 52

4552

37 5563

OS63DOS63D

8080

OFAM00aMOFAM00aM

A63A75

2020

TA75DU63TA75DU63

45 - 6345 - 63

5563

45 6570

OS125DOS125D

100100

OFAM00aMOFAM00aM

A75A95

2030

TA75DU80TA80DU80

60 - 8060 - 80

6570

55 80100

OS125DOS125D

125125

OFAM00aMOFAM00aM

A95A110

3030

TA110DU90TA110DU110

65 - 9080 - 110

80100

75 110125

OS125DOS125D

125160

OFAM00aMOFAM00aM

A145A145

1010

TA200DU135TA200DU135

100 - 135100 - 135

110125

90 135145

OS160DOESA250D

160200

OFAM00aMOFAM1aM

A145A145

1010

TA200DU135TA200DU150

100 - 135110 - 150

135145

110 160 OESA250D 200 OFAM1aM A185 10 TA200DU200 150 - 200 165132 190 OESA250D 250 OFAM1aM A210 10 TA450DU235 165 - 235 200160 220

240OESA250DOESA400D

250315

OFAM1aMOFAM2aM

A260A260

1010

TA450DU235TA450DU310

165 - 235220 - 310

220240

200 275300

OESA400DOESA400D

315355

OFAM2aMOFAM2aM

A300AF400

1010

TA450DU310E500DU(10)

220 - 310150 - 500

275300

250 335370

OESA400DOESA630D

400500

OFAM2aMOFAM3aM

AF400AF400

1010

E500DU(10)E500DU(10)

150 - 500150 - 500

335370

290 420 OESA630D 500 OFAM3aM AF460 10 E500DU(10) 150 - 500 420315 430

500500

OESA630DOESA630DOESA630D

500630630

OFAM3aMOFAM3aMOFAM3aM

AF460AF580AF580

101010

E500DU(10)E500DU(10)**E800DU(10)

150 - 500150 - 500250 - 800

430500500

FM5080NS2.1af

* : tested with ABB fuses. To use such fuses or fuses with similar characteristics** : mounting kit between contactor and relay is not available

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 29/08/2001 by Jean-Paul Guitton

Page 26: Type Selection Tables

Direct-on-line starters protected by INSUM 2500 V - 80 kA - Normal start - up, type : 2Note : FG5080NSIN2.1[INSUM 2]

gG /INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2500 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/ MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.88 OS32D 4 OFAA 00 H A9 15 7 1.30.55 1.2 OS32D 6 OFAA 00 H A9 15 7 1.80.75 1.5 OS32D 6 OFAA 00 H A9 15 7 1.81.1 2.2 OS32D 10 OFAA 00 H A9 15 7 3.41.5 2.8 OS32D 10 OFAA 00 H A9 15 7 3.42.2 4 OS32D 16 OFAA 00 H A9 15 7 6.53 5.2 OS32D 16 OFAA 00 H A9 15 7 6.54 6.9 OS32D 20 OFAA 00 H A9 15 7 7.5

5.5 9.1 OS32D 32 OFAA 00 H A12 15 7 127.5 12.2 OS32D

OS32D

32

40

OFAA 00 H

OFAA 00 H

A16

A26

15

15

7

7

13

16.5

11 17.5 OS32D 50 OFAA 00 H A26 20 7 19.515 23 OS32D 63 OFAA 00 H A30 20 7 26

18.5 29 OS32D 80 OFAA 00 H A40 20 7 3322 34 OS63D 100 OFAA 00 H A50 20 7 4030 45 OS125D

OS125D

125

125

OFAA 00 H

OFAA 00 H

A50

A63

20

20

7

7

45

55

37 56 OESA250D 160 OFAA 1 H A75 20 7 6545 67 OESA250D 200 OFAA 1 H A95 20 7 8055 82 OESA250D 200 OFAA 1 H A110 20 7 8875 110 OESA250D 250 OFAA 1 H A145 10 7 11590 132 OESA400D 315 OFAA 2 H A145 10 7 145

110 158 OESA400D 315 OFAA 2 H A185 10 7 168132 192 OESA400D 400 OFAA 2 H A210 10 7 210160 230 OESA400D 400 OFAA 2 H A260 10 7 235200 279 OESA630D 500 OFAA 3 H EH370 40 7 290250 335 OESA630D 630 OFAA 3 H EH370 40 7 370290 394 OESA630D 630 OFAA 3 H EH550 40 7 440315 440 OESA630D

OESA630D

630

630

OFAA 3 H

OFAA 3 H

EH550

EH550

40

40

7

5

440

480

FG5080NSIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 27: Type Selection Tables

Direct-on-line starters protected by INSUM 2500 V - 80 kA - Normal start - up, type : 2Note : FM5080NSIN2.1[INSUM 2]

aM/ INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2500 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [s] Imax [A]0.37 0.88 OS32D 2 OFAM 00 aM A9 15 7 1.70.55 1.2 OS32D 2 OFAM 00 aM A9 15 7 1.70.75 1.5 OS32D 2 OFAM 00 aM A9 15 7 1.71.1 2.2 OS32D 4 OFAM 00 aM A9 15 7 3.21.5 2.8 OS32D 4 OFAM 00 aM A9 15 7 3.22.2 4 OS32D 6 OFAM 00 aM A9 15 7 4.93 5.2 OS32D 10 OFAM 00 aM A9 15 7 7.24 6.9 OS32D 10 OFAM 00 aM A9 15 7 7.2

5.5 9.1 OS32D 16 OFAM 00 aM A12 15 7 127.5 12.2 OS32D 20 OFAM 00 aM A16 15 7 1411 17.5 OS32D 25 OFAM 00 aM A26 20 7 2215 23 OS32D 32 OFAM 00 aM A30 20 7 26

18.5 29 OS32D 40 OFAM 00 aM A40 20 7 3022 34 OS63D 50 OFAM 00 aM A50 20 7 3830 45 OS63D

OS63D6363

OFAM 00 aMOFAM 00 aM

A50A63

2020

77

4550

37 56 OS63D 80 OFAM 00 aM A75 20 7 6345 67 OS125D 100 OFAM 00 aM A95 20 7 7555 82 OS125D 125 OFAM 00 aM A110 20 7 9675 110 OS125D 160 OFAM 00 aM A145 10 7 12590 132 OS160D

OESA250D160200

OFAM 00 aMOFAM 1 aM

A145A145

1010

57

135145

110 158 OESA250D 200 OFAM 1 aM A185 10 7 162132 192 OESA250D 250 OFAM 1 aM A210 10 7 200160 230 OESA400D

OESA400D315355

OFAM 2 aMOFAM 2 aM

A260EH370

1040

77

240275

200 279 OESA400D 400 OFAM 2 aM EH370 40 7 315250 335 OESA400D

OESA630D400500

OFAM 2 aMOFAM 3 aM

EH370EH550

4040

57

340415

290 394 OESA630D 500 OFAM 3 aM EH550 40 7 415315 440 OESA630D 500 OFAM 3 aM EH550 40 5 450355 483 OESA630D 630 OFAM 3 aM EH550 40 7 500

FM5080NSIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 28: Type Selection Tables

Direct-on-line starters protected by INSUM 2500 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FG5080HDIN2.1[INSUM 2]

gG/ INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2500 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/ MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.88 OS32D 6 OFAA 00 H A9 15 28 1.50.55 1.2 OS32D 6 OFAA 00 H A9 15 28 1.50.75 1.5 OS32D 10 OFAA 00 H A9 15 28 2.71.1 2.2 OS32D 10 OFAA 00 H A9 15 28 2.71.5 2.8 OS32D 16 OFAA 00 H A9 15 28 52.2 4 OS32D 16 OFAA 00 H A9 15 28 53 5.2 OS32D 20 OFAA 00 H A9 15 28 64 6.9 OS32D 25 OFAA 00 H A9 15 28 7.1

5.5 9.1 OS32D 32 OFAA 00 H A12 15 28 10.57.5 12.2 OS32D

OS32D

40

50

OFAA 00 H

OFAA 00 H

A26

A26

20

20

28

28

13

16

11 17.5 OS32D 63 OFAA 00 H A30 20 28 2215 23 OS32D 80 OFAA 00 H A30 20 28 26.5

18.5 29 OS32D 100 OFAA 00 H A40 20 28 3222 34 OS125D 125 OFAA 00 H A50 20 28 4530 45 OS125D

OESA250D

125

160

OFAA 00 H

OFAA 1 H

A63

A63

20

20

28

28

46

51

37 56 OESA250D 200 OFAA 1 H A95 20 28 7045 67 OESA250D 200 OFAA 1 H A95 20 28 7055 82 OESA250D 250 OFAA 1 H A145 10 28 9275 110 OESA400D 315 OFAA 2 H A185 10 28 13090 132 OESA400D 400 OFAA 2 H A210 10 28 150

110 158 OESA400D 400 OFAA 2 H A260 10 28 175132 192 OESA630D 500 OFAA 3 H EH370 40 28 210160 230 OESA630D 630 OFAA 3 H EH370 40 28 328200 279 OESA630D 630 OFAA 3 H EH370 40 28 328

FG5080HDIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 29: Type Selection Tables

Direct-on-line starters protected by INSUM 2500 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FM5080HDIN2.1[INSUM 2]

aM /INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2500 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/ MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.88 OS32D 2 OFAM 00 aM A9 15 28 1.50.55 1.2 OS32D 2 OFAM 00 aM A9 15 28 1.50.75 1.5 OS32D 4 OFAM 00 aM A9 15 28 2.61.1 2.2 OS32D 4 OFAM 00 aM A9 15 28 2.61.5 2.8 OS32D 6 OFAM 00 aM A9 15 28 42.2 4 OS32D 6 OFAM 00 aM A9 15 28 43 5.2 OS32D 10 OFAM 00 aM A9 15 28 64 6.9 OS32D 16 OFAM 00 aM A12 15 28 11

5.5 9.1 OS32D 16 OFAM 00 aM A12 15 28 117.5 12.2 OS32D 20 OFAM 00 aM A16 15 28 1311 17.5 OS32D

OS32D

25

32

OFAM 00 aM

OFAM 00 aM

A26

A30

20

20

28

28

18

20

15 23 OS32D 40 OFAM 00 aM A30 20 28 2518.5 29 OS32D 50 OFAM 00 aM A40 20 28 3122 34 OS63D 63 OFAM 00 aM A50 20 28 4030 45 OS63D

OS63D

80

80

OFAM 00 aM

OFAM 00 aM

A50

A63

20

20

28

28

45

50

37 56 OS125D 100 OFAM 00 aM A75 20 28 6045 67 OS125D 125 OFAM 00 aM A110 20 28 7555 82 OS125D 160 OFAM 00 aM A145 10 28 9675 110 OESA250D 200 OFAM 1 aM A185 10 28 12590 132 OESA250D 250 OFAM 1 aM A210 10 28 155

110 158 OESA400D 315 OFAM 2 aM A260 10 28 190132 192 OESA400D 355 OFAM 2 aM EH370 40 28 215160 230 OESA400D 400 OFAM 2 aM EH370 40 28 245200 279 OESA630D 500 OFAM 3 aM EH370 40 28 320250 335 OESA630D 630 OFAM 3 aM EH550 40 28 380

FM5080HDIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 30: Type Selection Tables

Direct on line starters500 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FG5080HD2.1

gG

Fuse type gG

Direct-on-line starters with Switch - fuse500 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type FusetypegG

Size Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.88 OS32D 4 00 A9 15 E16DU1.0 30* 0.3 - 1.0 1.00.55 1.2 OS32D 6 00 A9 15 E16DU2.7 30* 0.8 - 2.7 1.50.75 1,5 OS32D 10 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.1 2.2 OS32D 10 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.5 2.8 OS32D 16 00 A9 15 E16DU6.3 30* 1.9 - 6.3 4.52.2 4 OS32D 20 00 A9 15 E16DU6.3 30* 1.9 - 6.3 5.53 5.2 OS32D 25 00 A9 15 E16DU6.3 30* 1.9 - 6.3 6.34 6.8 OS32D 32 00 A12 15 E16DU18.9 30* 5.7 - 18.9 9

5.5 9.1 OS32D 40 00 A26 20 E16DU18.9 30* 5.7 - 18.9 117.5 12.2 OS32D 50 00 A26 20 E16DU18.9 30* 5.7 - 18.9 1411 17.5 OS32D 63 00 A30 20 E16DU18.9 30* 5.7 - 18.9 18.915 23 OS32D 80 00 A30 20 TA450SU80(3) 18.3 - 26.7 24

18.5 29 OS32D 100 00 A40 20 TA450SU60(2) 20 - 30 3022 34 OS125D

OS125D125125

0000

A50A50

2020

TA450SU80(2)TA450SU105(2)

27.5 - 4035 - 52.5

3543

30 45 OESA250D 160 1 A63 20 TA450SU60 40 - 60 5037 56 OESA250D 200 1 A95 20 TA450SU60 40 - 60 6045 67 OESA250D 200 1 A95 20 TA450SU80 55 - 80 6855 82 OESA250D 250 1 A145 10 TA450SU105 70 - 105 9075 110 OESA400D 315 1 A185 10 TA450SU140 95 - 140 12090 132 OESA400D 400 2 A210 10 TA450SU185 130 - 185 170110 158 OESA400D 400 2 A260 10 T450SU185 130 - 185 185132 192 OESA630D 500 3 EH370 40 T450SU235 185 - 235 205160 230 OESA630D 630 3 EH370 40 T450SU235 185 - 235 235200 279 OESA630D 630 3 EH370 40 T450SU310 220 - 310 300

* : trip class of E16DU (x) : number of primary turns

FG5080HD2.1

Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/04/2000 by Jean-Paul Guitton

Page 31: Type Selection Tables

Direct on line starters500 V - 80 kA - Long starting (heavy duty) start - up, type : 2Note : FM5080HD2.1

aM

Fuse type aM

Direct-on-line starters with Switch - fuse500 V, 80 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type FusetypeaM

Size Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.88 OS32D 2 00 A9 15 E16DU1 30* 0.3 - 1 10.55 1.2 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.70.75 1.5 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.1 2.2 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.5 2.8 OS32D 6 00 A9 15 E16DU6.3 30* 1.9 - 6.3 3.72.2 4 OS32D 10 00 A9 15 E16DU6.3 30* 1.9 - 6.3 5.53 5.2 OS32D 10 00 A9 15 E16DU6.3 30* 1.9 - 6.3 5.54 6,9 OS32D 16 00 A12 15 E16DU18.9 30* 5.7 - 18.9 8,5

5.5 9.1 OS32D 20 00 A16 15 E16DU18.9 30* 5.7 - 18.9 127.5 12,2 OS32D 25 00 A26 15 E16DU18.9 30* 5.7 - 18.9 1711 17,5 OS32D 32 00 A30 20 E16DU18.9 30* 5.7 - 18.9 18.915 23 OS32D 40 00 A30 20 TA450SU80(3) 18.3 - 26.7 23

18.5 29 OS32D 50 00 A40 20 TA450SU80(2) 27.5 - 40 3022 34 OS63D 63 00 A50 20 TA450SU(80)2 27.5 - 40 3530 45 OS63D

OS125D80

1000000

A63A95

2020

TA450SU105(2)TA450SU60

35 - 52.540 - 60

4655

37 56 OS125D 100 00 A95 20 TA450SU80 55 - 80 5845 67 OS125D 125 00 A110 10 TA450SU80 55 - 80 7055 82 OS125D

OESA250160200

001

A145A185

1010

TA450SU105TA450SU105

70 - 10570 - 105

88105

75 110 OESA250D 200 1 A185 10 TA450SU140 95 - 140 12090 132 OESA250D 250 1 A210 10 TA450SU140 95 - 140 140

110 158 OESA400D 315 2 A260 10 TA450SU185 130 - 185 170132 192 OESA400D

OESA400D355400

22

EH370EH370

4040

T450SU235T450SU235

165 - 235165 - 235

200220

160 230 OESA400D 400 2 EH370 40 T450SU310 220 - 310 240200 279 OESA630D

OESA630D500630

33

EH370EH550

4040

T450SU310T450SU310

220 - 310220 - 310

285310

250 335 OESA630D 630 3 EH550 40 T450SU400 285 - 400 350

* : trip class of E16DU(x) : number of primary turns FM5080HD2.1

Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/02/2000 by Jean-Paul Guitton

Page 32: Type Selection Tables

Star Delta Starters with separate TOR500 V - 80 kA - Normal start - up, type : 1Note : FM5080SD1.1

aM

Fuse type aM

Star-Delta starters with Switch - fuse500 V, 80 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 6.9 OS32D 10 OFAM 00 aM A9 A9 A9 TA25DU5 3.5 - 5 8.6

5.5 9.1 OS32D 10 OFAM 00 aM A9 A9 A9 TA25DU6.5 4.5 - 6.5 107.5 12.2 OS32D 16 OFAM 00 aM A12 A12 A9 TA25DU8.5 5 - 8.5 1411 17.5 OS32D 20 OFAM 00 aM A16 A16 A12 TA25DU11 7.5 - 11 18.915 23 OS32D 25 OFAM 00 aM A16 A16 A12 TA25DU14 10 - 14 24

18.5 29 OS32D 32 OFAM 00 aM A26 A26 A16 TA25DU19 13 - 19 3222 34 OS63D 40 OFAM 00 aM A26 A26 A16 TA25DU25 18 - 25 4030 45 OS63D 50 OFAM 00 aM A40 A40 A26 TA42DU32 22 - 32 5037 56 OS63D 63 OFAM 00 aM A40 A40 A26 TA42DU42 29 - 42 6345 67 OS125D 80 OFAM 00 aM A50 A50 A30 TA75DU52 36 - 52 8055 82 OS125D 100 OFAM 00 aM A63 A63 A40 TA75DU63 45 - 63 9575 110 OS125D 125 OFAM 00 aM A75 A75 A50 TA75DU80 60 - 80 11590 132 OS160D 160 OFAM 00 aM A95 A95 A75 TA110DU90 65 - 90 145

110 158 OESA250D 200 OFAM 1 aM A110 A110 A95 TA110DU110 80 - 110 188132 192 OESA250D 200 OFAM 1 aM A145 A145 A110 TA200DU135 100 - 135 200160 230 OESA250D 250 OFAM 1 aM A145 A145 A110 TA200DU185 110 - 150 250200 279 OESA400D 315 OFAM 2 aM A185 A185 A145 TA200DU175 130 - 175 315250 335 OESA400D 355 OFAM 2 aM A260 A260 A210 TA450DU235 165 - 235 355290 394 OESA400D 400 OFAM 2 aM A300 A300 A260 TA450DU235 165 - 235 400315 440 OESA630D 500 OFAM 3 aM A300 A300 A260 TA450DU310 220 - 310 500355 483 OESA630D 500 OFAM 3 aM A300 A300 A260 TA450DU310 220 - 310 500400 538 OESA630D 630 OFAM 3 aM AF400 AF400 A300 E500DU500 165 - 500 630

FM5080SD1.1

Created 02/05/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 27/09/2000 by Jean-Paul Guitton

Page 33: Type Selection Tables

Star-delta starters with TOR500 V - 80 kA - Normal start - up, type : 2Note : FG5080SD2.1

gG

Fuse type gG

Star-Delta starters with Switch - fuse500 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 6.9 OS32D 16 OFAA 00 H A9 A9 A9 TA25DU5 3.5 - 5 8.6

5.5 9.1 OS32D 20 OFAA 00 H A12 A12 A9 TA25DU6.5 4.5 - 6.5 107.5 12.2 OS32D 25 OFAA 00 H A16 A16 A9 TA25DU8.5 5 - 8.5 1411 17.5 OS32D 32 OFAA 00 H A16 A16 A12 TA25DU11 7.5 - 11 18.915 23 OS32D 40 OFAA 00 H A26 A26 A12 TA25DU14 10 - 14 24

18.5 29 OS32D 50 OFAA 00 H A26 A26 A16 TA25DU19 13 - 19 3222 34 OS63D 63 OFAA 00 H A30 A30 A16 TA42DU25 18 - 25 4030 45 OS63D 80 OFAA 00 H A40 A40 A26 TA42DU32 22 - 32 5037 56 OS63D 100 OFAA 00 H A50 A50 A26 TA42DU42 29 - 42 6345 67 OS125D 125 OFAA 00 H A63 A63 A30 TA75DU52 36 - 52 8055 82 OS125D 125 OFAA 00 H A75 A75 A40 TA75DU63 45 - 63 9075 110 OESA250D 160 OFAA 1 H A95 A95 A50 TA80DU80 60 - 80 11090 132 OESA250D 200 OFAA 1 H A145 A145 A75 TA110DU90 65 - 90 145

110 158 OESA250D 250 OFAA 1 H A145 A145 A95 TA200DU110 80 - 110 188132 192 OESA250D 250 OFAA 1 H A145 A145 A110 TA200DU135 100 - 135 200160 230 OESA400D 315 OFAA 2 H A185 A185 A110 TA200DU175 130 - 175 245200 279 OESA400D

OESA400D

315

400

OFAA 2 H

OFAA 2 H

A185

A210

A185

A210

A145

A185

TA200DU175

TA450DU185

130 - 175

130 - 185

285

315

250 335 OESA400D 400 OFAA 2 H A210 A210 A185 T450DU235 165 - 235 340290 394 OESA630D 500 OFAA 3 H EH370 EH370 A210 T450DU235 165 - 235 405315 440 OESA630D 500 OFAA 3 H EH370 EH370 A260 T450DU310 220 - 310 450355 483 OESA630D 630 OFAA 3 H EH370 EH370 A300 T450DU310 220 - 310 530

FG5080SD2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 04/04/2000 by Jean-Paul Guitton

Page 34: Type Selection Tables

Star-delta starters with TOR500 V - 80 kA - Normal start - up, type : 2Note : FM5080SD2.1

aM

Fuse type aM

Star-Delta starters with Switch - fuse500 V, 80 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 6.9 OS32D 10 OFAM 00 aM A9 A9 A9 TA25DU5 3.5 - 5 8.6

5.5 9.1 OS32D 10 OFAM 00 aM A12 A12 A9 TA25DU6.5 4.5 - 6.5 107.5 12.2 OS32D 16 OFAM 00 aM A16 A16 A9 TA25DU8.5 5 - 8.5 1411 17.5 OS32D 20 OFAM 00 aM A16 A16 A12 TA25DU11 7.5 - 11 18.915 23 OS32D 25 OFAM 00 aM A26 A26 A12 TA25DU14 10 - 14 24

18.5 29 OS32D 32 OFAM 00 aM A26 A26 A16 TA25DU19 13 - 19 3222 34 OS63D 40 OFAM 00 aM A30 A30 A16 TA42DU25 18 - 25 4030 45 OS63D 50 OFAM 00 aM A40 A40 A26 TA42DU32 22 - 32 5037 56 OS63D 63 OFAM 00 aM A50 A50 A26 TA75DU42 29 - 42 6345 67 OS125D 80 OFAM 00 aM A63 A63 A30 TA75DU52 36 - 52 8055 82 OS125D 100 OFAM 00 aM A75 A75 A40 TA75DU63 45 - 63 9575 110 OS125D 125 OFAM 00 aM A95 A95 A50 TA80DU80 60 - 80 11590 132 OS160D 160 OFAM 00 aM A145 A145 A75 TA200DU90 65 - 90 145

110 158 OESA250D 200 OFAM 1 aM A145 A145 A95 TA200DU110 80 - 110 188132 192 OESA250D 200 OFAM 1 aM A145 A145 A110 TA200DU135 100 - 135 200160 230 OESA250D 250 OFAM 1 aM A210 A210 A110 TA450DU185 130 - 185 250200 279 OESA400D 315 OFAM 2 aM A210 A210 A145 TA450DU185 130 - 185 315250 335 OESA400D 355 OFAM 2 aM EH370 EH370 A210 TA450DU235 165 - 235 355290 394 OESA400D 400 OFAM 2 aM EH370 EH370 A210 T450DU235 165 - 235 400315 440 OESA630D 500 OFAM 3 aM EH370 EH370 A260 T450DU310 220 - 310 500355 483 OESA630D 500 OFAM 3 aM EH370 EH370 A260 T450DU310 220 - 310 500400 538 OESA630D 630 OFAM 3 aM EH550 EH550 A300 T450DU400 285 - 400 630

FM5080SD2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 04/04/2000 by Jean-Paul Guitton

Page 35: Type Selection Tables

Direct-on-line starters690 V - 35 kA - Normal start - up, type : 1Note : FG6935NS1.1

gG

Fuse type gG

Direct-on-line starters with Switch - fuse 690 V, 35 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse typegG

Size Type Safetyclearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 0.6 OS32D 6 00 A9 15 E16DU1 0.3 - 1 10.55 0.9 OS32D 6 00 A9 15 E16DU2.7 0.9 - 2.7 2.70.75 1.1 OS32D 6 00 A9 15 E16DU2.7 0.9 - 2.7 2.71.1 1.6 OS32D 6 00 A9 15 E16DU2.7 0.9 - 2.7 2.71.5 2 OS32D 20 00 A9 15 E16DU6.3 2 - 6.3 6.32.2 2.9 OS32D 20 00 A9 15 E16DU6.3 2 - 6.3 6.33 3.8 OS32D 20 00 A9 15 E16DU6.3 2 - 6.3 6.34 5 OS32D 25 00 A9 15 E16DU18.9 5.7 - 18.9 7

5.5 6.7 OS32D 25 00 A9 15 E16DU18.9 5.7 - 18.9 77.5 8.8 OS32D 32 00 A12 15 E16DU18.9 5.7 - 18.9 911 13 OS32D 50 00 A26 15 E16DU18.9 5.7 - 18.9 17

FG6935NS1.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 36: Type Selection Tables

Direct-on-line starters690 V - 35 kA - Normal start - up, type : 2Note : FG6935NS2.1

gG

Fuse type gG

Direct-on-line starters with Switch - fuse690 V, 35 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Electronic Overload Relay

Group

Rated Output

Rated Current

Type FusetypegG

Size Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.6 OS32D 4 00 A9 15 E16DU 1 0.3 - 1 10.55 0.9 OS32D 6 00 A9 15 E16DU 2.7 0.9 - 2.7 2.70.75 1.1 OS32D 6 00 A9 15 E16DU 2.7 0.9 - 2.7 2.71.1 1.6 OS32D 6 00 A9 15 E16DU 2.7 0.9 - 2.7 2.71.5 2 OS32D 16 00 A9 15 E16DU 6.3 2 - 6.3 6.32.2 2.9 OS32D 16 00 A9 15 E16DU 6.3 2 - 6.3 6.33 3.8 OS32D 20 00 A9 15 E16DU 6.3 2 - 6.3 6.34 5 OS32D 20 00 A9 15 E16DU 18.9 5.7 - 18.9 7

5.5 6.7 OS32D 25 00 A12 15 E16DU 18.9 5.7 - 18.9 97.5 8.8 OS32D 32 00 A16 15 E16DU 18.9 5.7 - 18.9 1011 13 OS32D 40 00 A26 15 E16DU 18.9 5.7 - 18.9 17

FG6935NS2.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/02/2000 by Jean-Paul Guitton

Page 37: Type Selection Tables

Direct-on-line starters690 V - 50 kA - Normal start - up, type : 2Note : FG6950NS2.1af

gG

Fuse type gG

Direct-on-line starters with Switch - fuse690 V, 50 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse* type gG

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] max [A]1.1 1.5 OS32D 4 OFAA00H A9 15 TA25DU1.8 1.3 - 1.8 1.81.5 2 OS32D 6 OFAA00H A9 15 TA25DU2.4 1.7 - 2.4 2.42.2 2.9 OS32D 6 OFAA00H A9 15 TA25DU3.1 2.2 - 3.1 3.13 3.5 OS32D 10 OFAA00H A9 15 TA25DU4 2.8 - 4 44 4.9 OS32D 16 OFAA00H A9 15 TA25DU5 3.5 - 5 5

OS32D 16 OFAA00H A9 15 TA25DU6.5 4.5 - 6.5 6.55.5 6.7 OS32D 16 OFAA00H A9 15 TA25DU8.5 6 - 8.5 77.5 9 OS32D 25 OFAA00H A26 20 TA25DU11 7.5 - 11 1111 13 OS32D 32 OFAA00H A26 20 TA25DU14 10 - 14 1415 17

19OS32DOS32D

3240

OFAA00HOFAA00H

A26A30

2020

TA25DU19TA25DU19

13 - 1913 - 19

1719

18.5 21 OS32D 50 OFAA00H A30 20 TA42DU25 18 - 25 2122 25 OS32D 63 OFAA00H A40 20 TA42DU32 22 - 32 2530 35 OS63D 80 OFAA00H A50 20 TA75DU42 29 - 42 3537 40

4346

OS63DOS63DOS63D

100100100

OFAA00HOFAA00HOFAA00H

A63A63A75

202020

TA75DU42TA75DU52TA75DU52

29 - 4236 - 5236 - 52

404346

45 52 OESA250D 125 OFAA1H A95 30 TA80DU52 36 - 52 5255 63 OESA250D 125 OFAA1H A95 30 TA80DU63 45 - 63 63

OESA250D 125 OFAA1H A95 30 TA80DU80 60 - 80 8075 82 OESA250D 200 OFAA1H A110 30 TA110DU90 65 - 90 8290 95 OESA250D 200 OFAA1H A145 10 TA200DU110 80 - 110 100110 115 OESA400D 250 OFAA2H A145 10 TA200DU135 100 - 135 120132 140 OESA400D 315 OFAA2H A185 10 TA200DU175 130 - 175 140160 170 OESA400D 315 OFAA2H A210 10 TA450DU185 130 - 185 170200 205

235OESA630DOESA630D

400400

OFAA3HOFAA3H

A210A300

1010

TA450DU235TA450DU235

165 - 235165 - 235

210235

250 245 OESA630D 500 OFAA3H AF400 10 E500DU(10) 150 - 500 270290 305 - 630 4 AF400 10 E500DU(10) 150 - 500 310315 315 - 630 4 AF400 10 E500DU(10) 150 - 500 350355 370 - 630 4 AF460 10 E500DU(10) 150 - 500 400400 420

420--

630630

44

AF580AF580

1010

E500DU(10)**E500DU(10)

150 - 500250 - 800

420420

450 470470

--

800800

44

AF580AF580

1010

E500DU(10)**E500DU(10)

150 - 500250 - 800

480480

500 500500

--

800800

44

AF580AF580

1010

E500DU(10)**E500DU(10)

150 - 500250 - 800

500500

FG6950NS2.1af* : tested with ABB fuses. To use such fuses or fuses with similar characteristics** : mounting kit between contactor and relay is not available

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 29/08/2001 by Jean-Paul Guitton

Page 38: Type Selection Tables

Direct-on-line starters690 V - 50 kA - Normal start - up, type : 2Note : FM6950NS2.1af

aM

Fuse type aM

Direct-on-line starters with Switch - fuse690 V, 50 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Fuse* type aM

Size Type Safety clearance

Type Currentsetting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] max [A]1.1 1.5 OS32D 4 OFAM00aM A9 15 TA25DU1.8 1.3 - 1.8 1.81.5 2 OS32D 4 OFAM00aM A9 15 TA25DU2.4 1.7 - 2.4 2.42.2 2.9 OS32D 4 OFAM00aM A9 15 TA25DU3.1 2.2 - 3.1 3.13 3.5 OS32D 6 OFAM00aM A9 15 TA25DU4.0 2.8 - 4 44 4.9 OS32D 10 OFAM00aM A9 15 TA25DU5.0 3.5 - 5 5

OS32D 10 OFAM00aM A9 15 TA25DU6.5 4.5 - 6.5 6.55.5 6.7 OS32D 10 OFAM00aM A9 15 TA25DU8.5 6 - 8.5 77.5 9 OS32D 16 OFAM00aM A26 20 TA25DU11 7.5 - 11 1111 13 OS32D 20 OFAM00aM A26 20 TA25DU14 10 - 14 1415 17

19OS32DOS32D

2025

OFAM00aMOFAM00aM

A26A30

2020

TA25DU19TA25DU19

13 - 1913 - 19

1719

18.5 21 OS32D 25 OFAM00aM A30 20 TA25DU25 18 - 25 2122 25 OS32D 32 OFAM00aM A40 20 TA42DU32 22 - 32 2530 35 OS63D 40 OFAM00aM A50 20 TA75DU42 29 - 42 3537 40

4346

OS63DOS63DOS63D

506363

OFAM00aMOFAM00aMOFAM00aM

A63A63A75

202020

TA75DU42TA75DU52TA75DU52

29 - 4236 - 5236 - 52

404346

45 52 OS63D 63 OFAM00aM A95 30 TA80DU52 36 - 52 5255 63 OS63D 80 OFAM00aM A95 30 TA80DU63 45 - 63 63

OS63D 80 OFAM00aM A95 30 TA80DU80 60 - 80 8075 82 OS125D 100 OFAM00aM A110 30 TA110DU90 65 - 90 8290 95 OS125D 125 OFAM00aM A145 10 TA200DU110 80 - 110 100110 115 OESA250D 160 OFAM1aM A145 10 TA200DU135 100 - 135 120132 140 OESA250D 200 OFAM1aM A185 10 TA200DU150 110 - 150 150160 170 OESA250D 250 OFAM1aM A210 10 TA450DU185 130 - 185 170200 205

220OESA250DOESA400D

250315

OFAM1aMOFAM2aM

A210A260

1010

TA450DU235TA450DU235

165 - 235165 - 235

205220

250 245 OESA400D 315 OFAM2aM A300 10 TA450DU310 220 - 310 270290 305 OESA400D 400 OFAM2aM AF400 10 E500DU(10) 150 - 500 310315 315

350OESA400DOESA630D

400500

OFAM2aMOFAM3aM

AF400AF400

1010

E500DU(10)E500DU(10)

150 - 500150 - 500

320350

355 370 OESA630D 500 OFAM3aM AF460 10 E500DU(10) 150 - 500 400400 420

350OESA630DOESA630D

630630

OFAM3aMOFAM3aM

AF580AF580

1010

E500DU(10)*E800DU(10)

150 - 500250 - 800

430430

450 470470

OESA630DOESA630D

630630

OFAM3aMOFAM3aM

AF580AF580

1010

E500DU(10)*E800DU(10)

150 - 500250 - 800

480480

500 500500

OESA630DOESA630D

630630

OFAM3aMOFAM3aM

AF580AF580

1010

E500DU(10)*E800DU(10)

150 - 500250 - 800

500500

FM6950NS2.1af* : tested with ABB fuses. To use such fuses or fuse with similar characteristics** : mounting kit between contactor and relay is not available

Created 23/06/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 29/08/2001 by Jean-Paul Guitton

Page 39: Type Selection Tables

Direct-on-line starters protected by INSUM 2690 V - 50 kA - Normal start - up, type : 2Note : FG6950NSIN2.1[INSUM2]

gG /INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2690 V, 50 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.6 OS32D 4 OFAA 00 H A9 15 7 1.30.55 0.9 OS32D 4 OFAA 00 H A9 15 7 1.30.75 1.1 OS32D 4 OFAA 00 H A9 15 7 1.31.1 1.6 OS32D 6 OFAA 00 H A9 15 7 1.81.5 2 OS32D 10 OFAA 00 H A9 15 7 3.42.2 2.9 OS32D 10 OFAA 00 H A9 15 7 3.43 3.8 OS32D 16 OFAA 00 H A9 15 7 6.54 5 OS32D 16 OFAA 00 H A9 15 7 6.5

5.5 6.7 OS32D 20 OFAA 00 H A12 15 7 7.57.5 8.8 OS32D 25 OFAA 00 H A26 20 7 911 13 OS32D

OS32D3240

OFAA 00 HOFAA 00 H

A26A30

2020

77

1316.5

15 18 OS32D 50 OFAA 00 H A30 20 7 19.518.5 21 OS32D 63 OFAA 00 H A30 20 7 2122 25 OS32D 63 OFAA 00 H A40 20 7 2530 33 OS63D

OS63D80

100OFAA 00 HOFAA 00 H

A50A63

2020

77

3340

37 41 OS63D 100 OFAA 00 H A75 20 7 4245 49 OESA250D 125 OFAA 1 H A95 20 7 5555 60 OESA250D 160 OFAA 1 H A95 20 7 6575 80 OESA250D

OESA250D200200

OFAA 1 HOFAA 1 H

A110A145

2010

77

8288

90 95 OESA400D 250 OFAA 2 H A145 10 7 115110 115 OESA400D 250 OFAA 2 H A145 10 7 115132 139 OESA400D 315 OFAA 2 H A185 10 7 155160 167 OESA400D 315 OFAA 2 H A210 10 7 168200 202 OESA630D

OESA630D400400

OFAA 3 HOFAA 3 H

A210A260

1010

77

210235

250 242 OESA630D 500 OFAA 3 H EH370 40 7 290290 301 OESA630D 500 OFAA 3 H EH370 40 5 315

FG6950NSIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 40: Type Selection Tables

Direct-on-line starters protected by INSUM 2690 V - 50 kA - Normal start - up, type : 2Note : FM6950NSIN2.1[INSUM2]

aM/ INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2690 V, 50 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.6 OS32D 2 OFAM 00 aM A9 15 7 1.70.55 0.9 OS32D 2 OFAM 00 aM A9 15 7 1.70.75 1.1 OS32D 2 OFAM 00 aM A9 15 7 1.71.1 1.6 OS32D 4 OFAM 00 aM A9 15 7 3.21.5 2 OS32D 4 OFAM 00 aM A9 15 7 3.22.2 2.9 OS32D 4 OFAM 00 aM A9 15 7 3.23 3.8 OS32D 6 OFAM 00 aM A9 15 7 4.94 5 OS32D 10 OFAM 00 aM A9 15 7 7

5.5 6.7 OS32D 10 OFAM 00 aM A9 15 7 77.5 8.8 OS32D 16 OFAM 00 aM A26 20 7 1311 13 OS32D 20 OFAM 00 aM A26 20 7 1615 18 OS32D 25 OFAM 00 aM A30 20 7 21

18.5 21 OS32D 25 OFAM 00 aM A30 20 7 2122 25 OS32D

OS32D3240

OFAM 00 aMOFAM 00 aM

A40A50

2020

77

2530

30 33 OS63D 50 OFAM 00 aM A63 20 7 3837 41 OS63D 63 OFAM 00 aM A75 20 7 4645 49 OS63D 63 OFAM 00 aM A95 20 7 5055 60 OS63D

OS125D80

100OFAM 00 aMOFAM 00 aM

A95A110

2020

77

6375

75 80 OS125D 125 OFAM 00 aM A110 20 7 8290 95 OS125D 125 OFAM 00 aM A145 10 7 96

110 115 OESA250D 160 OFAM 1 aM A145 10 7 120132 139 OESA250D 200 OFAM 1 aM A185 10 7 162160 167 OESA250D 250 OFAM 1 aM A210 10 7 200200 202 OESA400D 315 OFAM 2 aM A260 10 7 240250 242 OESA400D

OESA400D315355

OFAM 2 aMOFAM 2 aM

A300EH370

1040

77

245275

290 301 OESA400D 400 OFAM 2 aM EH370 40 7 315315 313 OESA400D 400 OFAM 2 aM EH370 40 7 315355 370 OESA630D 500 OFAM 3 aM EH370 40 7 370400 405 OESA630D 500 OFAM 3 aM EH550 40 7 415450 460 OESA630D 630 OFAM 3 aM EH550 40 7 500

FM6950NSIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 41: Type Selection Tables

Direct-on-line starters protected by INSUM 2690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : FG6950HDIN2.1[INSUM2]

gG/ INSUM2

Fuse type gG

Direct-on-line starters with Switch - fuse + INSUM 2690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/ MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.6 OS32D 4 OFAA 00 H A9 15 28 1.20.55 0.9 OS32D 4 OFAA 00 H A9 15 28 1.20.75 1.1 OS32D 6 OFAA 00 H A9 15 28 1.51.1 1.6 OS32D 10 OFAA 00 H A9 15 28 2.71.5 2 OS32D 10 OFAA 00 H A9 15 28 2.72.2 2.9 OS32D 16 OFAA 00 H A9 15 28 53 3.8 OS32D 16 OFAA 00 H A9 15 28 54 5 OS32D 20 OFAA 00 H A9 15 28 6

5.5 6.7 OS32D 25 OFAA 00 H A26 20 28 7.17.5 8.8 OS32D 32 OFAA 00 H A26 20 28 10.511 13 OS32D

OS32D

40

50

OFAA 00 H

OFAA 00 H

A26

A26

20

20

28

28

13

16

15 18 OS32D 63 OFAA 00 H A30 20 28 2118.5 21 OS32D 63 OFAA 00 H A40 20 28 2222 25 OS32D

OS32D

80

80

OFAA 00 H

OFAA 00 H

A40

A50

20

20

28

28

25

26.5

30 33 OS63D 100 OFAA 00 H A50 20 28 3337 41 OESA250D 125 OFAA 1 H A75 20 28 4645 49 OESA250D 160 OFAA 1 H A95 20 28 5155 60 OESA250D 200 OFAA 1 H A110 20 28 7075 80 OESA400D 250 OFAA 2 H A145 10 28 9290 95 OESA400D 315 OFAA 2 H A185 10 28 120

110 115 OESA400D 315 OFAA 2 H A185 10 28 130132 139 OESA630D 400 OFAA 3 H A260 10 28 175160 167 OESA630D 400 OFAA 3 H A300 10 28 175200 202 OESA630D 500 OFAA 3 H EH370 40 28 210

FG6950HDIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 28/01/2000 by Jean-Paul Guitton

Page 42: Type Selection Tables

Direct-on-line starters protected by INSUM 2690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : FM6950HDIN2.1[INSUM2]

aM/ INSUM2

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseTypeandSize

Type Safety clearance

Type

INSUM 2MCU1/ MCU2

t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.6 OS32D 2 OFAM 00 aM A9 15 28 1.50.55 0.9 OS32D 2 OFAM 00 aM A9 15 28 1.50.75 1.1 OS32D 2 OFAM 00 aM A9 15 28 1.51.1 1.6 OS32D 4 OFAM 00 aM A9 15 28 2.61.5 2 OS32D 4 OFAM 00 aM A9 15 28 2.62.2 2.9 OS32D 6 OFAM 00 aM A9 15 28 43 3.8 OS32D 6 OFAM 00 aM A9 15 28 44 5 OS32D 10 OFAM 00 aM A9 15 28 6

5.5 6.7 OS32D 16 OFAM 00 aM A26 20 28 117.5 8.8 OS32D 16 OFAM 00 aM A26 20 28 1111 13 OS32D 20 OFAM 00 aM A26 20 28 1315 18 OS32D 25 OFAM 00 aM A30 20 28 18

18.5 21 OS32D 32 OFAM 00 aM A30 20 28 2122 25 OS32D

OS32D4050

OFAM 00 aMOFAM 00 aM

A40A50

2020

2828

2531

30 33 OS63DOS63D

6363

OFAM 00 aMOFAM 00 aM

A50A63

2020

2828

3540

37 41 OS63D 80 OFAM 00 aM A75 20 28 4645 49 OS63D 80 OFAM 00 aM A95 20 28 5055 60 OS125D

OS125D100125

OFAM 00 aMOFAM 00 aM

A95A110

2020

2828

6075

75 80 OESA250D 160 OFAM 1 aM A145 10 28 9690 95 OESA250D 160 OFAM 1 aM A185 10 28 96

110 115 OESA250D 200 OFAM 1 aM A185 10 28 120132 139 OESA250D

OESA250D250250

OFAM 1 aMOFAM 1 aM

A185A210

1010

2828

140155

160 167 OESA400D 315 OFAM 2 aM A300 10 28 190200 202 OESA400D 355 OFAM 2 aM EH370 40 28 215250 242 OESA400D 400 OFAM 2 aM EH370 40 28 245290 301 OESA630D 500 OFAM 3 aM EH370 40 28 320315 313 OESA630D 500 OFAM 3 aM EH370 40 28 320355 370 OESA630D 630 OFAM 3 aM EH550 40 28 380

FM6950HDIN2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 43: Type Selection Tables

Direct on line starters690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : FG6950HD2.1

gG

Fuse type gG Direct-on-line starters with Switch - fuse

690 V, 50 kA, Long starting (heavy duty) start - up, type 2Motor Switch-fuse Contactor Thermal Overload

RelayGroup

Rated Output

Rated Current

Type Fuserating

gG

FuseTypeandSize

Type Safety clearance

Type t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s ] Imax [A]0.37 0.6 OS32D 4 00 A9 15 E16DU1 30* 0.3 - 1 10.55 0.9 OS32D 4 00 A9 15 E16DU1 30* 0.3 - 1 10.75 1.1 OS32D 6 00 A9 15 E16DU2.7 30* 0.8 - 2.7 1.51.1 1.6 OS32D 10 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.5 2 OS32D 10 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.72.2 2.9 OS32D 16 00 A9 15 E16DU6.3 30* 1.9 - 6.3 4.53 3.8 OS32D 16 00 A9 15 E16DU6.3 30* 1.9 - 6.3 4.54 5.0 OS32D 25 00 A26 20 E16DU6.3 30* 1.9 - 6.3 6.3

5.5 6.7 OS32D 32 00 A26 20 E16DU18.9 30* 5.7 - 18.9 97.5 8.8 OS32D 40 00 A26 20 E16DU18.9 30* 5.7 - 18.9 1111 13 OS32D 50 00 A26 20 E16DU18.9 30* 5.7 - 18.9 1415 18 OS32D 63 00 A30 20 E16DU18.9 30* 5.7 - 18.9 18.9

18.5 21 OS32D 80 00 A50 20 TA450SU80(3) 18.3 - 26.7 2422 25 OS32D 100 00 A63 20 TA450SU60(2) 20 - 30 3030 33 OESA250D 125 1 A95 20 TA450SU80(2) 27.5 - 40 3537 41 OESA250D 125 1 A95 20 TA450SU105(2) 35 - 52,5 4345 49 OESA250D

OESA250D160200

11

A95A110

2010

TA450SU60TA450SU60

40 - 6040 - 60

5060

55 60 OESA250D 200 1 A110 10 TA450SU80 55 - 80 6875 80 OESA400D 250 2 A145 10 TA450SU105 70 - 105 9090 95 OESA400D 315 2 A185 10 TA450SU105 70 - 105 105

110 115 OESA400DOESA630D

315400

23

A185A210

1010

TA450SU140TA450SU140

95 - 14095 - 140

120140

132 139 OESA630D 400 3 A260 10 TA450SU185 130 - 185 165160 167 OESA630D 500 3 EH370 40 TA450SU185 130 - 185 185200 202 OESA630D 500 3 EH370 40 T450SU235 165 - 235 205

* : trip class of E16DU (x) : number of primary turns

FG6950HD2.1

Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/02/2000 by Jean-Paul Guitton

Page 44: Type Selection Tables

Direct on line starters690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : FM6950HD2.1

aM

Fuse type aM

Direct-on-line starters with Switch - fuse + INSUM 2690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseTypeandSize

Type Safety clearance

Type t6 settingmax

for starter

Max. Current

Pe [kW] Ie [A] [A] [mm] [ s] Imax[ A]0.37 0.6 OS32D 2 00 A9 15 E16DU1 30* 0.3 - 1 10.55 0.9 OS32D 2 00 A9 15 E16DU1 30* 0.3 - 1 10.75 1.1 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.1 1.6 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.71.5 2 OS32D 4 00 A9 15 E16DU2.7 30* 0.8 - 2.7 2.72.2 2.9 OS32D 6 00 A9 15 E16DU6.3 30* 1.9 - 6.3 3.73 3.8 OS32D 10 00 A9 15 E16DU6.3 30* 1.9 - 6.3 5.54 5 OS32D 10 00 A9 15 E16DU6.3 30* 1.9 - 6.3 5.5

5.5 6.7 OS32D 16 00 A26 20 E16DU18.9 30* 5.7 - 18.9 8.57.5 8,8 OS32D 20 00 A26 20 E16DU18.9 30* 5.7 - 18.9 1211 13 OS32D 25 00 A30 20 E16DU18.9 30* 5.7 - 18.9 1715 18 OS32D 32 00 A30 20 E16DU18.9 30* 5.7 - 18.9 18.9

18.5 21 OS32D 40 00 A30 20 TA450SU80(3) 18.3 - 26.7 2122 25 OS32D

OS32D5050

0000

A40A50

2020

TA450SU60(2)TA450SU60(2)

20 - 3020 - 30

2528

30 33 OS63D 63 00 A50 20 TA450SU80(2) 27.5 - 40 3537 41 OS63D

OS63D8080

0000

A63A75

2020

TA450SU105(2)TA450SU105(2)

35 - 52.535 - 52.5

4346

45 49 OS125DOS125D

100125

0000

A95A95

2020

TA450SU60TA450SU60

40 - 6040 - 60

5560

55 60 OS125DOS125D

125125

0000

A95A110

2020

TA450SU80TA450SU80

55 - 8055 - 80

6570

75 80 OESA250D 160 1 A145 10 TA450SU105 70 - 105 8890 95 OESA250D 200 1 A185 10 TA450SU105 70 - 105 105

110 115 OESA250DOESA250D

200250

11

A185A210

1010

TA450SU140TA450SU140

95 - 14095 - 140

120140

132 139 OESA250D 250 1 A210 10 TA450SU185 130 - 185 145160 167 OESA400D

OESA400D315355

22

A300EH370

1040

TA450SU185TA450SU185

130 - 185130 - 185

170185

200 202 OESA400DOESA400D

400400

22

EH370EH370

4040

T450SU235T450SU310

165 - 235220 - 310

220240

250 242 OESA630D 500 3 EH370 40 T450SU310 220 - 310 285290 301 OESA630D 630 3 EH550 40 T450SU310 220 - 310 310315 313 OESA630D 630 3 EH550 40 T450SU400 285 - 400 350

* : trip class of E16DU (x) : number of primary turns

FM6950HD2.1

Created 20/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/02/2000 by Jean-Paul Guitton

Page 45: Type Selection Tables

Star delta starters with separate TOR690 V - 50 kA - Normal start - up, type : 1Note : FM6950SD1.1

aMFuse type aM

Star-Delta starters with Switch - fuse690 V, 50 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 5 OS32D

OS32D

6

6

OFAM 00 aM

OFAM 00 aM

A9

A9

A9

A9

A9

A9

TA25DU3.1

TA25DU4

2.2 - 3.1

2.8 - 4

5.3

6

5.5 6.7 OS32D 10 OFAM 00 aM A9 A9 A9 TA25DU5 3.5 - 5 8.67.5 8.8 OS32D 10 OFAM 00 aM A12 A12 A9 TA25DU6.5 4.5 - 6.5 1011 13 OS32D 16 OFAM 00 aM A16 A16 A12 TA25DU8.5 5 - 8.5 1415 18 OS32D 20 OFAM 00 aM A26 A26 A16 TA25DU11 7.5 - 11 18.9

18.5 21 OS32D 25 OFAM 00 aM A30 A30 A26 TA25DU14 10 - 14 2422 25 OS32D 32 OFAM 00 aM A40 A40 A26 TA25DU19 13 - 19 3030 33 OS63D 40 OFAM 00 aM A40 A40 A26 TA42DU25 18 - 25 4037 41 OS63D 50 OFAM 00 aM A40 A40 A26 TA42DU25 18 - 25 4345 49 OS63D 50 OFAM 00 aM A50 A50 A30 TA75DU32 22 - 32 5055 60 OS63D 63 OFAM 00 aM A63 A63 A40 TA75DU42 29 - 42 6375 80 OS125D 80 OFAM 00 aM A95 A95 A50 TA80DU52 36 - 52 8090 95 OS125D 100 OFAM 00 aM A95 A95 A75 TA80DU63 45 - 63 100

110 115 OS125D 125 OFAM 00 aM A110 A110 A95 TA80DU80 60 - 80 125132 139 OESA250D 160 OFAM 1 aM A110 A110 A95 TA200DU90 65 - 90 155160 167 OESA250D 200 OFAM 1 aM A145 A145 A110 TA200DU110 80 - 110 189200 202 OESA250D 250 OFAM 1 aM A185 A185 A145 TA200DU150 110 - 150 250250 242 OESA250D 250 OFAM 1 aM A185 A185 A145 TA450DU185 130 - 185 250290 301 OESA400D 315 OFAM 2 aM A210 A210 A185 TA450DU185 130 - 185 315315 313 OESA400D 355 OFAM 2 aM A210 A210 A185 T450DU235 165 - 235 355355 370 OESA400D 400 OFAM 2 aM AF400 AF400 A300 E500DU500 165 - 500 400450 445 OESA630D 500 OFAM 3 aM AF400 AF400 A300 E500DU500 165 - 500 500560 540 OESA630D 630 OFAM 3 aM AF460 AF460 AF400 E500DU500 165 - 500 630

FM6950SD1.1

Created 19/05/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 27/09/2000 by Jean-Paul Guitton

Page 46: Type Selection Tables

Star delta starters with separate TOR690 V - 50 kA - Normal start - up, type : 1Note : FG6950SD1.1

gG

Fuse type gG

Star-Delta starters with Switch - fuse690 V, 50 kA, Normal start - up, type 1

Motor Switch-fuse Contactor Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 5 OS32D

OS32D

10

10

OFAA 00 H

OFAA 00 H

A9

A9

A9

A9

A9

A9

TA25DU3.1

TA25DU4

2.2 - 3.1

2.8 - 4

5.3

6

5.5 6.7 OS32D 16 OFAA 00 H A9 A9 A9 TA25DU5 3.5 - 5 8.67.5 8.8 OS32D 20 OFAA 00 H A12 A12 A9 TA25DU6.5 4.5 - 6.5 1011 13 OS32D 25 OFAA 00 H A16 A16 A12 TA25DU8.5 5 - 8.5 1415 18 OS32D 32 OFAA 00 H A26 A26 A16 TA25DU11 7.5 - 11 18.9

18.5 21 OS32D 40 OFAA 00 H A30 A30 A26 TA25DU14 10 - 14 2422 25 OS32D 50 OFAA 00 H A40 A40 A26 TA42DU19 13 - 19 3230 33 OS63D 63 OFAA 00 H A40 A40 A26 TA42DU25 18 - 25 4337 41 OS63D 63 OFAA 00 H A40 A40 A26 TA42DU25 18 - 25 4345 49 OS63D 80 OFAA 00 H A50 A50 A30 TA75DU32 22 - 32 5255 60 OS63D 100 OFAA 00 H A63 A63 A40 TA42DU42 29 - 42 6375 80 OESA250D 125 OFAA 1 H A95 A95 A50 TA80DU52 36 - 52 8590 95 OESA250D 160 OFAA 1 H A95 A95 A75 TA80DU63 45 - 63 108

110 115 OESA250D 200 OFAA 1 H A110 A110 A95 TA80DU80 60 - 80 135132 139 OESA250D 200 OFAA 1 H A110 A110 A95 TA200DU90 65 - 90 145160 167 OESA400D 250 OFAA 2 H A145 A145 A110 TA200DU110 80 - 110 188200 202 OESA400D 315 OFAA 2 H A185 A185 A110 TA200DU150 110 - 150 206250 242 OESA400D 315 OFAA 2 H A185 A185 A145 TA200DU175 130 - 175 285290 301 OESA630D 400 OFAA 3 H A210 A210 A185 TA450DU185 130 - 185 318315 313 OESA630D 400 OFAA 3 H A210 A210 A185 TA450DU235 165 - 235 340355 370 OESA630D 500 OFAA 3 H AF400 AF400 A300 E500DU500 165 - 500 405400 410 OESA630D 500 OFAA 3 H AF400 AF400 A300 E500DU500 165 - 500 450

FG6950SD1.1

Created 12/05/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 27/09/2000 by Jean-Paul Guitton

Page 47: Type Selection Tables

Star-delta starters with TOR690 V - 50 kA - Normal start - up, type : 2Note : FG6950SD2.1

gG

Fuse type gG

Star-Delta starters with Switch - fuse690 V, 50 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

gG

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 5 OS32D

OS32D

10

10

OFAA 00 H

OFAA 00 H

A9

A9

A9

A9

A9

A9

TA25DU3.1

TA25DU4

2.2 - 3.1

2.8 - 4

5.3

6

5.5 6.7 OS32D 16 OFAA 00 H A12 A12 A9 TA25DU5 3.5 - 5 8.67.5 8.8 OS32D 20 OFAA 00 H A16 A16 A9 TA25DU6.5 4.5 - 6.5 1011 13 OS32D 25 OFAA 00 H A26 A26 A12 TA25DU8.5 5 - 8.5 1415 18 OS32D 32 OFAA 00 H A26 A26 A16 TA25DU11 7.5 - 11 18.9

18.5 21 OS32D 40 OFAA 00 H A26 A26 A26 TA25DU14 10 - 14 2422 25 OS32D 50 OFAA 00 H A30 A30 A26 TA42DU19 13 - 19 3230 33 OS63D 63 OFAA 00 H A40 A40 A26 TA42DU25 18 - 25 4337 41 OS63D 63 OFAA 00 H A40 A40 A26 TA42DU25 18 - 25 4345 49 OS63D 80 OFAA 00 H A50 A50 A30 TA75DU32 22 - 32 5255 60 OS63D 100 OFAA 00 H A63 A63 A40 TA42DU42 29 - 42 6375 80 OESA250D 125 OFAA 1 H A95 A95 A50 TA80DU52 36 - 52 8590 95 OESA250D 160 OFAA 1 H A95 A95 A75 TA80DU63 45 - 63 108

110 115 OESA250D 200 OFAA 1 H A110 A110 A95 TA80DU80 60 - 80 135132 139 OESA250D 200 OFAA 1 H A145 A145 A95 TA200DU90 65 - 90 145160 167 OESA400D 250 OFAA 2 H A145 A145 A110 TA200DU110 80 - 110 188200 202 OESA400D 315 OFAA 2 H A145 A145 A110 TA200DU150 110 - 150 206250 242 OESA400D 315 OFAA 2 H A185 A185 A145 TA200DU175 130 - 175 285290 301 OESA630D 400 OFAA 3 H A210 A210 A185 TA450DU185 130 - 185 318315 313 OESA630D 400 OFAA 3 H A210 A210 A185 TA450DU235 165 - 235 340355 370 OESA630D 500 OFAA 3 H EH370 EH370 A210 T450DU235 165 - 235 405400 410 OESA630D 500 OFAA 3 H EH370 EH370 A260 T450DU310 220 - 310 450

FG6950SD2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 04/04/2000 by Jean-Paul Guitton

Page 48: Type Selection Tables

Star-delta starters with TOR690 V - 50 kA - Normal start - up, type : 2Note : FM6950SD2.1

aM

Fuse type aM

Star-Delta starters with Switch - fuse690 V, 50 kA, Normal start - up, type 2

Motor Switch-fuse Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Fuserating

aM

FuseType andSize

K1Line

K3Delta

K2Star

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [A] [A]4 5 OS32D

OS32D

6

6

OFAM 00 aM

OFAM 00 aM

A9

A9

A9

A9

A9

A9

TA25DU3.1

TA25DU4

2.2 - 3.1

2.8 - 4

5.3

6

5.5 6.7 OS32D 10 OFAM 00 aM A12 A12 A9 TA25DU5 3.5 - 5 8.67.5 8.8 OS32D 10 OFAM 00 aM A16 A16 A9 TA25DU6.5 4.5 - 6.5 1011 13 OS32D 16 OFAM 00 aM A26 A26 A12 TA25DU8.5 5 - 8.5 1415 18 OS32D 20 OFAM 00 aM A26 A26 A16 TA25DU11 7.5 - 11 18.9

18.5 21 OS32D 25 OFAM 00 aM A26 A26 A26 TA25DU14 10 - 14 2422 25 OS32D 32 OFAM 00 aM A30 A30 A26 TA25DU19 13 - 19 3030 33 OS63D 40 OFAM 00 aM A40 A40 A26 TA42DU25 18 - 25 4037 41 OS63D 50 OFAM 00 aM A40 A40 A26 TA42DU25 18 - 25 4345 49 OS63D 50 OFAM 00 aM A50 A50 A30 TA75DU32 22 - 32 5055 60 OS63D 63 OFAM 00 aM A63 A63 A40 TA75DU42 29 - 42 6375 80 OS125D 80 OFAM 00 aM A95 A95 A50 TA80DU52 36 - 52 8090 95 OS125D 100 OFAM 00 aM A95 A95 A75 TA80DU63 45 - 63 100

110 115 OS125D 125 OFAM 00 aM A110 A110 A95 TA80DU80 60 - 80 125132 139 OESA250D 160 OFAM 1 aM A145 A145 A95 TA200DU90 65 - 90 155160 167 OESA250D 200 OFAM 1 aM A145 A145 A110 TA200DU110 80 - 110 189200 202 OESA250D 250 OFAM 1 aM A210 A210 A145 TA200DU150 110 - 150 250250 242 OESA250D 250 OFAM 1 aM A210 A210 A145 TA450DU185 130 - 185 250290 301 OESA400D 315 OFAM 2 aM A210 A210 A185 TA450DU185 130 - 185 315315 313 OESA400D 355 OFAM 2 aM EH370 EH370 A210 T450DU235 165 - 235 355355 370 OESA400D 400 OFAM 2 aM EH370 EH370 A210 T450DU235 165 - 235 400450 445 OESA630D 500 OFAM 3 aM EH370 EH370 A260 T450DU310 220 - 310 500560 540 OESA630D 630 OFAM 3 aM EH550 EH550 A300 T450DU400 285 - 400 630

FM6950SD2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 04/04/2000 by Jean-Paul Guitton

Page 49: Type Selection Tables

MCCB

UeV

IqkA

Coor.type

Startingtype

SCPDtype

Overloadmean

kWMotor

Table lastupdate

400 35 2 S-D MCCB TOR 5.5 ... 355 MB4035SD2.1af 24/08/01

2 DOL/HD MCCB TOR 0.37 ... 355 MB4035HD2.1af 24/08/012 DOL MCCB TOR 0.37 ... 355 MB4035NS2.1af 11/07/012 DOL/HD MCCB MP 30 ... 355 MP4035HD2.1af 11/07/012 S-D MCCB MP 45 ... 355 MP4035SD2.1af 24/08/012 S-D/HD MCCB TOR 45 ... 355 MB4035SDHD2.1af 30/08/012 S-D MCCB INSUM 45 ... 355 MB4035SDIN2.1af 31/08/012 DOL MCCB INSUM 0.37 ... 355 MB4035NSIN2.1af 14/11/012 DOL / HD MCCB INSUM 0.37 ... 355 MB4035HDIN2.1af 14/11/012 S-D/HD MCCB MP 45 ... 355 MP4035SDHD2.1af 30/08/01

50 2 SD MCCB TOR 5.5 ... 355 MB4050SD2.1af 24/08/01

2 DOL/HD MCCB MP 30 ... 355 MP4050HD2.1af 11/07/012 DOL MCCB TOR 0.37 ... 355 MB4050NS2.1af 11/07/012 DOL MCCB INSUM 0.37 ... 355 MB4050NSIN2.1af 14/11/012 DOL / HD MCCB INSUM 0.37 ... 355 MB4050HDIN2.1af 14/11/012 S-D MCCB MP 45 ... 355 MP4050SD2.1af 24/08/012 DOL/HD MCCB TOR 0.37 ... 355 MB4050HD2.1af 24/08/012 S-D/HD MCCB TOR 45 ... 355 MB4050SDHD2.1af 30/08/012 S-D MCCB INSUM 45 ... 355 MB4050SDIN2.1af 31/08/012 S-D/HD MCCB MP 45 ... 355 MP4050SDHD2.1af 30/08/01

65 2 DOL MCCB TOR 0.37 ... 355 MB4065NS2.1 25/02/00

415 80 2 DOL MCCB TOR 0.37 ... 355 MB4180NS2.1 25/02/00

440 50 2 DOL/HD MCCB MP 30 ... 355 MP4450HD2.1af 11/07/012 DOL MCCB TOR 0.37 ... 355 MB4450NS2.1af 19/09/012 DOL MCCB INSUM 0.37 ... 355 MB4450NSIN2.1af 14/11/012 DOL/HD MCCB INSUM 0.37 ... 355 MB4450HDIN2.1af 14/11/012 S-D MCCB TOR 5.5 ... 355 MB4450SD2.1af 19/09/012 S-D MCCB MP 45 ... 355 MP4450SD2.1af 24/08/012 DOL/HD MCCB TOR 0.37 ... 355 MB4450HD2.1af 19/09/012 S-D/HD MCCB TOR 45 ... 355 MB4450SDHD2.1af 30/08/012 S-D MCCB INSUM 45 ... 355 MB4450SDIN2.1af 31/08/012 S-D/HD MCCB MP 45 ... 355 MP4450SDHD2.1af 30/08/01

500 50 2 S-D MCCB TOR 5.5 ... 355 MB5050SD2.1af 24/0801

2 DOL/HD MCCB MP 30 ... 355 MP5050HD2.1af 11/07/012 DOL MCCB TOR 0.37 ... 355 MB5050NS2.1af 11/07/012 DOL MCCB INSUM 0.37 ... 355 MB5050NSIN2.1af 14/11/012 DOL /HD MCCB INSUM 0.37 ... 355 MB5050HDIN2.1af 14/11/012 S-D MCCB MP 45 ... 355 MP5050SD2.1af 24/08/012 DOL/HD MCCB TOR 0.37 ... 355 MB5050HD2.1af 24/08/012 S-D/HD MCCB TOR 45 ... 355 MB5050SDHD2.1af 30/08/012 S-D MCCB INSUM 45 ... 355 MB5050SDIN2.1af 31/08/012 S-D/HD MCCB MP 45 ... 355 MP5050SDHD2.1af 30/08/01

690 50 2 DOL/HD MCCB TOR 0.37 ... 500 MB6950HD2.1af 24/08/01

2 DOL MCCB INSUM 5.5 ... 500 MB6950NSIN2.1af 14/11/012 DOL/HD MCCB INSUM 5.5 ... 500 MB6950HDIN2.1af 14/11/012 S-D MCCB TOR 5.5 ...500 MB6950SD2.1af 27/08012 DOL MCCB TOR 0.37 ... 500 MB6950NS2.1af 11/07/012 DOL/HD MCCB MP 45 ... 500 MP6950HD2.1af 11/07/012 S-D MCCB MP 45 ... 500 MP6950SD2.1af 24/08/012 S-D/HD MCCB TOR 45 ... 500 MB6950SDHD2.1af 30/08/012 S-D MCCB INSUM 45 ... 355 MB6950SDIN2.1af 31/08/012 S-D/HD MCCB MP 45 ... 500 MP6950SDHD2.1af 30/08/01

Glossary SCPD Short Circuit Protection Device M Magnetic only

Page 50: Type Selection Tables

HDNS

Heavy DutyNormal Start

ProlimIsomax

Current limiterSACE isomax S

SD Star Delta MP MCCB + Electronic Motor Protection

MCCBINTOR

Moulded Case Circuit BreakerINSUM Motor ProtectionThermal Overload Relay

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 51: Type Selection Tables

STAR-DELTA STARTERS400 V - 35 kA - Normal start - up, type : 2Note : MB4035SD2.1af

mccb+AF contactorStar-delta starters with MCCB

400V, 35 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors Thermal OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type**

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]5.5 11.5 S2X80 In16 210 A 30 A 30 A 9 10 10 TA25DU14** 10-147.5 15.2 S2X80 In20 260 A 30 A 30 A 9 10 10 TA25DU19** 13-1911 22 S2X80 In25 325 A 30 A 30 A 9 10 10 TA42DU25** 18-2515 28.5 S2X80 In32 415 A 50 A 50 A 16 10 10 TA75DU32** 22-32

18.5 36 S2X80 In42 540 A 50 A 50 A 26 10 10 TA75DU42** 29-4222 42 S2X80 In52 680 A 50 A 50 A 26 10 10 TA75DU52** 36-5230 56 S2X80 In63 820 A 63 A 63 A 30 10 10 TA75DU63** 45-6337 68 S2X80 In80 1040 A 75 A 75 A 30 10 10 TA75DU80** 60-80

68 S3N160 In125 * 900 A95 A95 A30 20 10 TA80DU52 36 - 5245 83 S3N160 In125 * 1050 A95 A95 A30 20 10 TA80DU52 36 - 5255 98 S3N160 In125 * 1250 A95 A95 A40 20 10 TA80DU63 45 - 6375 135 S3N250 In200 * 1700 A95 A95 A75 20 10 TA110DU90 66 - 9090 158 S3N250 In200 * 2000 A110 A110 A95 20 20 TA110DU110 80 - 110

110 193 S4N250 PR211-I In250

2500 A145 A145 A95 15 20 TA200DU135 100 - 135

132 232 S4N250 PR211-I In250

3000 A145 A145 A110 15 20 TA200DU175 130 - 175

160 282 S5N400 PR211-I In400

4000 A210 A210 A145 15 15 TA200DU175 130 - 175

200 349 S5N400 PR211-I In400

4800 A210 A210 A185 15 15 TA450DU235 165 - 235

250 430 S6N630 PR211-I In630

6300 AF400 AF400 A210 10 15 E500DU500 150 - 500

290 520 S6N630 PR211-I In630

7560 AF400 AF400 A260 10 15 E500DU500 150 - 500

315 545 S6N630 PR211-I In630

7560 AF400 AF400 A260 10 15 E500DU500 150 - 500

355 610 S6N800 PR211-I In800

8000 AF400 AF400 A260 10 15 E500DU500 150 - 500

* : magnetic only adjustable release** : TOR to be connected between MCCB and Line/Delta node MB4035SD2.1af

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/08/2001 by Jean-Paul Guitton

Page 52: Type Selection Tables

DOL STARTERS400 V - 35 kA - Long starting (heavy duty) start - up, type : 2Note : MB4035HD2.1af

Isomax+AF+EOLDirect-on-line starters with MCCB

400 V, 35 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.1 S2X80 In1.6 21 A9 10 TA25DU1.4 ** 1 -1.4 1.40.55 1.5 S2X80 In2 26 A9 10 TA25DU1.8 ** 1.3 - 1.8 1.80.75 1.9 S2X80 In2.5 33 A9 10 TA25DU2.4 ** 1.7 - 2.4 2.41.1 2.8 S2X80 In3.2 42 A9 10 TA25DU3.1 ** 2.2 - 3.1 3.11.5 3.5 S2X80 In5 65 A16 10 TA25DU4.0 ** 2.8 - 4 4

S2X80 ln5 65 A26 10 TA25DU5.0** 3.5 - 5 52.2 5 S2X80 In6.5 84 A26 10 TA25DU6.5 ** 4.5 - 6.5 6.53 6.6 S2X80 In8.5 110 A26 10 TA25DU8.5 ** 6 - 8.5 8.54 8.6 S2X80 In11 145 A30 10 TA25DU11 ** 7.5 - 11 11

5.5 11.5 S2X80 In16 210 A30 10 TA 450SU60 (4) 10 - 15 157.5 15.2 S2X80 In20 260 A30 10 TA 450SU60 (3) 13 - 20 2011 22 S2X80 In25 325 A30 10 TA 450SU60 (2) 20 - 30 2515 28.5 S2X80 In32 415 A50 10 TA 450SU80 (2) 23 - 40 40

18.5 36 S2X80 In42 540 A50 10 TA 450SU80 (2) 23 - 40 4022 42 S2X80 In52 680 A50 10 TA 450SU60 (1) 40 - 60 5030 56 S2X80 In63 820 A63 10 TA 450SU80 (1) 55 - 80 6337 68 S2X80 In80 1040 A95 20 TA 450SU80 (1) 55 - 80 8045 83 S3N160 In160 * 1250 A110 20 TA 450SU105 (1) 70 - 105 10555 98 S3N160 In160 * 1500 A145 15 TA 450SU140 (1) 95 - 140 14075 135 S3N250 In200 * 2150 A185 15 TA 450SU185 (1) 130 - 185 18590 158 S3N250 In200 * 2400 A210 15 TA 450SU185 (1) 130 - 185 185

110 193 S4N250 PR211-I In250

3000 A260 15 TA 450SU235 (1) 165 - 235 235

132 232 S5N400 PR211-I In320

3840 A300 15 TA 450SU310 (1) 220 - 310 300

160 282 S5N400 PR211-I In400

4800 AF 400 10 E 500DU 150 - 500 400

200 349 S6N630 PR211-I In630

6300 AF 460 10 E 500DU 150 - 500 460

250 430 S6N630 PR211-I In630

S6N630 PR211-I In630

7560

7560

AF 750

AF 750

10

10

E 500DU***

E 800DU

150 - 500

250 - 800

500

630

290 520 S6N800 PR211-I In800

8000 AF 750 10 E 800DU 250 - 800 750

315 545 S6N800 PR211-I In800

9600 AF 750 10 E 800DU 250 - 800 750

355 610 S6N800 PR211-I In800

9600 AF 750 10 E 800DU 250 - 800 750

MB4035HD2.1af* : magnetic only adjustable release.** : by pass contactor on the TOR during starting, same size as the line contactor*** Mounting kit between Contactor and Relay is not available. (x) : number of primary turns on CT

Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/08/2001 by Jean-Paul Guitton

Page 53: Type Selection Tables

DIRECT ON LINE STARTERS400 V - 35 kA - Normal start - up, type : 2Note : MB4035NS2.1af

MCCB+AF-contactor

Direct-on-line starters with MCCB 400V, 35 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.1 S2X80 In1.6 21 A9 10 TA25DU1.4 1 - 1.4 1.40.55 1.5 S2X80 In2 26 A9 10 TA25DU1.8 1.3 - 1.8 1.80.75 1.9 S2X80 In2.5 33 A9 10 TA25DU2.4 1.7 - 2.4 2.41.1 2.8 S2X80 In3.2 42 A9 10 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 S2X80 ln5 65 A16 10 TA25DU4.0 2.8 - 4 4

S2X80 ln5 65 A26 10 TA25DU5.0 3.5 - 5 52.2 5 S2X80 In6.5 84 A26 10 TA25DU6.5 4.5 - 6.5 6.53 6.6 S2X80 In8.5 110 A26 10 TA25DU8.5 6 - 8.5 8.54 8.6 S2X80 In11 145 A30 10 TA25DU11 7.5 - 11 11

5.5 11.5 S2X80 In16 210 A30 10 TA25DU14 10 -1 4 147.5 15.2 S2X80 In20 260 A30 10 TA25DU19 13 -19 1911 22 S2X80 In25 325 A30 10 TA42DU25 18 - 25 2515 28.5 S2X80 In32 415 A50 10 TA75DU32 22 - 32 32

18.5 36 S2X80 In42 540 A50 10 TA75DU42 29 - 42 4222 42 S2X80 In52 680 A50 10 TA75DU52 36 - 52 5030 56 S2X80 In63 820 A63 10 TA75DU63 45 - 63 6337 68 S2X80 In80 1040 A75 10 TA75DU80 60 - 80 7545 83 S3N160 In160 * 1250 A95 20 TA110DU90 66 - 90 9055 98 S3N160 In160 * 1500 A110 20 TA110DU110 80 - 110 11075 135 S3N250 In200 * 2150 A145 15 TA200DU150 110 - 150 14590 158 S3N250 In200 * 2400 A185 15 TA200DU175 130 - 175 175

110 193 S4N250 PR211-I In250

3000 A210 15 TA450DU235 165 - 235 210

132 232 S5N400 PR211-I In320

3840 A260 15 TA450DU310 220 - 310 260

160 282 S5N400 PR211-I In400

4800 A300 15 TA450DU310 220 - 310 300

200 349 S6N630 PR211-I In630

6300 AF400 10 E500DU 150 - 500 400

250 430 S6N630 PR211-I In630

S6N630 PR211-I In630

7560

7560

AF580

AF580

10

10

E500DU**

E800DU

150 - 500

250 - 800

500

580

290 520 S6N800 PR211-I In800

8000 AF580 10 E800DU 250 - 800 580

315 545 S6N800 PR211-I In800

9600 AF580 10 E800DU 250 - 800 580

355 610 S6N800 PR211-I In800

9600 AF750 10 E800DU 250 - 800 750

MB4035NS2.1af* Magnetic only adjustable release.** Mounting kit between Contactor and Relay is not available

Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 54: Type Selection Tables

DIRECT-ON-LINE STARTERS 400 V - 35 kA - Long starting (heavy duty) start - up, type : 2Note : MP4035HD2-1af

MCCB+PR212MP+AF-contDirect-on-line starters with MCCB

400 V, 35 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type I1 range Current setting

PR 212 / MPrelease I3 *

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [A] [mm] Imax [A]30 56 S4N160 PR212-MP In100 50 - 100 600 A145 15 10037 68 S4N160 PR212-MP In100 50 - 100 700 A145 15 10045 83 S4N160 PR212-MP In100 50 - 100 900 A145 15 10055 98 S4N160 PR212-MP In160 80 - 160 1120 A145 15 14575 135 S4N160 PR212-MP In160 80 - 160 1440 A145 15 14590 158 S4N250 PR212-MP In200 100 - 200 1800 A185 15 185

110 193 S5N400 PR212-MP In320 160 - 320 2240 A210 15 210132 232 S5N400 PR212-MP In320 160 - 320 2560 A260 15 260160 282 S5N400 PR212-MP In320 160 - 320 2880 AF400** 10 320200 349 S6N800 PR212-MP In630 315 - 630 3780 AF400 10 400250 430 S6N800 PR212-MP In630 315 - 630 5040 AF460 10 460290 520 S6N800 PR212-MP In630 315 - 630 5670 AF580 10 580315 545 S6N800 PR212-MP In630 315 - 630 5670 AF580 10 580355 610 S6N800 PR212-MP In630 315 - 630 5670 AF750 10 630

MP4035HD2-1af

* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes whenthe motor is starting-up.** : A300 in case of Normal StartNORMAL and HEAVY-DUTY START

For smaller motor powers, please refer to MMS tables or MCCB / MCB tables

Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 55: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY400 V - 35 kA - Normal start - up, type : 2Note : MP4035SD2.1af

PR212/MP+AF contactorStar-delta starters with MCCB

400 V, 35 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactors

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 83 S4S160 PR212-MP In100 50 - 100 800 A145 A145 A30 15 1055 98 S4S160 PR212-MP In160 80 - 160 960 A145 A145 A40 15 1075 135 S4S160 PR212-/MP In160 80 - 160 1280 A145 A145 A75 15 1090 158 S4S250 PR212-MP In200 100 - 200 1600 A145 A145 A95 15 20

110 193 S5S400 PR212-MP In320 160 - 320 1920 A210 A210 A95 15 20132 232 S5S400 PR212-MP In320 160 - 320 2240 A210 A210 A110 15 20160 282 S5S400 PR212-MP In320 160 - 320 2560 A210 A210 A145 15 15200 349 S6S800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15250 430 S6S800 PR212-MP In630 315 - 630 4410 AF400 AF400 A210 10 15290 520 S6S800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15315 545 S6S800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15355 610 S6S800 PR212-MP In630 315 - 630 5670 AF400 AF400 A260 10 15

MP4035SD2.1af* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes whenthe motor is starting-up.

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/08/2001 by Jean-Paul Guitton

Page 56: Type Selection Tables

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY400 V - 35 kA - Long starting (heavy duty) start - up, type : 2Note : MB4035SDHD2.1af

MCCB PR211+AFStar-delta starters with MCCB

400 V, 35 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors Thermal OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]45 83 S3N160 In160 * 1280 A95 A95 A50 20 10 TA450SU60 40 - 6055 98 S3N160 In160 * 1600 A95 A95 A50 20 10 TA450SU60 40 - 6075 135 S3N250 In200 * 2200 A145 A145 A75 15 10 TA450SU80 55 - 8090 158 S3N250 In200 * 2400 A145 A145 A95 15 20 TA450SU105 70 - 105

110 193 S4N250 PR211-I In250

3000 A145 A145 A95 15 20 TA450SU140 95 - 140

132 232 S5N400 PR211-I In320

3840 A210 A210 A145 15 15 TA450SU140 95 - 140

160 282 S5N400 PR211-I In400

4800 A210 A210 A145 15 15 TA450SU185 130 - 185

200 349 S6N630 PR211-I In630

6300 AF400 AF400 A185 10 15 E500DU 150 - 500

250 430 S6N630 PR211-I In630

7560 AF400 AF400 A260 10 15 E500DU 150 - 500

290 520 S6N800 PR211-I In800

8000 AF400 AF400 A260 10 15 E500DU 150 - 500

315 545 S6N800 PR211-I In800

9600 AF400 AF400 A260 10 15 E500DU 150 - 500

355 610 S6N800 PR211-I In800

9600 AF400 AF400 AF400 10 10 E500DU 150 - 500

MB4035SDHD2.1af

* : Magnetic only adjustable release

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 57: Type Selection Tables

STAR-DELTA STARTERS + INSUM400 V - 35 kA - Normal start - up, type : 2Note : MB4035SDIN2.1af

INSUM PR211+AFStar-delta starters with MCCB

400 V, 35 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type**

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [mm] [mm]45 83 S3N160 In125 * 1050 A95 A95 A30 20 1055 98 S3N160 In125 * 1250 A95 A95 A40 20 1075 135 S3N250 In200 * 1700 A95 A95 A75 20 1090 158 S3N250 In200 * 2000 A110 A110 A95 20 10

110 193 S4N250 PR211-I In250 2500 A145 A145 A95 15 20132 232 S4N250 PR211-I In250 3000 A145 A145 A110 15 20160 282 S5N400 PR211-I In400 4000 A210 A210 A145 15 15200 349 S5N400 PR211-I In400 4800 A210 A210 A185 15 15250 430 S6N630 PR211-I In630 6300 AF400 AF400 A210 10 15290 520 S6N630 PR211-I In630 7560 AF400 AF400 A260 10 15315 545 S6N630 PR211-I In630 7560 AF400 AF400 A260 10 15355 610 S6N800 PR211-I In800 8000 AF400 AF400 A260 10 15

MB4035SDIN2.1af

* : Magnetic only adjustable release.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 31/08/2001 by Jean-Paul Guitton

Page 58: Type Selection Tables

DIRECT ON LINE STARTERS +INSUM400 V - 35 kA - Normal start - up, type : 2Note : MB4035NSIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2400 V, 35 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 1.1 S2X80 In1.6 21 A9 10 1.60.55 1.5 S2X80 In2 26 A9 10 20.75 1.9 S2X80 In2.5 33 A16 10 2.51.1 2.8 S2X80 In3.2 42 A26 10 3.21.5 3.5 S2X80 In5 65 A26 10 52.2 5 S2X80 In6.5 84 A26 10 6.53 6.6 S2X80 In8.5 110 A26 10 8.54 8.6 S2X80 In11 145 A30 10 11

5.5 11.5 S2X80 In16 210 A30 10 167.5 15.2 S2X80 In20 260 A30 10 2011 22 S2X80 In25 325 A30 10 2515 28.5 S2X80 In32 415 A50 10 32

18.5 36 S2X80 In42 540 A50 10 4222 42 S2X80 In52 680 A50 10 5030 56 S2X80 In63 820 A63 10 6337 68 S2X80 In80 1040 A75 10 7545 83 S3N160 In160 * 1250 A95 20 9555 98 S3N160 In160 * 1500 A110 20 11075 135 S3N250 In200 * 2150 A145 15 14590 158 S3N250 In200 * 2400 A185 15 175

110 193 S4N250 PR211-I In250 3000 A210 15 210132 232 S5N400 PR211-I In320 3840 A260 15 260160 282 S5N400 PR211-I In400 4800 A300 15 300200 349 S6N630 PR211-I In630 6300 AF400 10 400250 430 S6N630 PR211-I In630 7560 AF580 10 580290 520 S6N800 PR211-I In800 8000 AF580 10 580315 545 S6N800 PR211-I In800 9600 AF580 10 580355 610 S6N800 PR211-I In800 9600 AF750 10 750

MB4035NSIN2.1af* Magnetic only adjustable release

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 59: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM400 V - 35 kA - Long starting (heavy duty) start - up, type : 2Note : MB4035HDIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2400 V, 35 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 1.1 S2X80 In1.6 21 A9 10 1.60.55 1.5 S2X80 In2 26 A9 10 20.75 1.9 S2X80 In2.5 33 A16 10 2.51.1 2.8 S2X80 In3.2 42 A26 10 3.21.5 3.5 S2X80 In5 65 A26 10 52.2 5 S2X80 In6.5 84 A26 10 6.53 6.6 S2X80 In8.5 110 A26 10 8.54 8.6 S2X80 In11 145 A30 10 11

5.5 11.5 S2X80 In16 210 A30 10 167.5 15.2 S2X80 In20 260 A30 10 2011 22 S2X80 In25 325 A30 10 2515 28.5 S2X80 In32 415 A50 10 32

18.5 36 S2X80 In42 540 A50 10 4222 42 S2X80 In52 680 A50 10 5030 56 S2X80 In63 820 A63 10 6337 68 S2X80 In80 1040 A95 20 8045 83 S3N160 In160 * 1250 A110 20 11055 98 S3N160 In160 * 1500 A145 15 14575 135 S3N250 In200 * 2150 A185 15 18590 158 S3N250 In200 * 2400 A210 15 200

110 193 S4N250 PR211-I In250 3000 A260 15 250132 232 S5N400 PR211-I In320 3840 A300 15 300160 282 S5N400 PR211-I In400 4800 AF400 10 400200 349 S6N630 PR211-I In630 6300 AF460 10 460250 430 S6N630 PR211-I In630 7560 AF750 10 630290 520 S6N800 PR211-I In800 8000 AF750 10 750315 545 S6N800 PR211-I In800 9600 AF750 10 750355 610 S6N800 PR211-I In800 9600 AF750 10 750

* : magnetic only adjustable release. MB4035HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 60: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY400 V - 35 kA - Long starting (heavy duty) start - up, type : 2Note : MP4035SDHD2.1af

MCCB PR212/MP+AF

Star-delta starters with MCCB400 V, 35 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range** Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactors

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 83 S4N160 PR212-MP In100 50 - 100 900 A145 A145 A50 15 1055 98 S4N160 PR212-MP In160 80 - 160 1120 A145 A145 A50 15 1075 135 S4N160 PR212-MP In160 80 - 160 1440 A145 A145 A75 15 1090 158 S4N250 PR212-MP In200 100 - 200 1800 A145 A145 A95 15 20

110 193 S5N400 PR212-MP In320 160 - 320 2240 A210 A210 A95 15 20132 232 S5N400 PR212-MP In320 160 - 320 2560 A210 A210 A145 15 15160 282 S5N400 PR212-MP In320 160 - 320 2880 A210 A210 A145 15 15200 349 S6N800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15250 430 S6N800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15290 520 S6N800 PR212-MP In630 315 - 630 5670 AF400 AF400 A260 10 15315 545 S6N800 PR212-MP In630 315 - 630 5670 AF400 AF400 A260 10 15355 610 S6N800 PR212-/MP In630 315 - 630 5670 AF400 AF400 AF400 10 10

MP4035SDHD2.1af

* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes whenthe motor is starting-up.** The protection against overload (L function) of the MP release, must be set with class 30 starting class.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 61: Type Selection Tables

STAR-DELTA STARTERS400 V - 50 kA - Normal start - up, type : 2Note : MB4050SD2.1af

mccb+AF contactorStar-delta starters with MCCB

400V, 50 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors Thermal OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type**

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]5.5 11.5 S2X80 In16 210 A 30 A 30 A 9 10 10 TA25DU14** 10-147.5 15.2 S2X80 In20 260 A 30 A 30 A 9 10 10 TA25DU19** 13-1911 22 S2X80 In25 325 A 30 A 30 A 9 10 10 TA42DU25** 18-2515 28.5 S2X80 In32 415 A 50 A 50 A 16 10 10 TA75DU32** 22-32

18.5 36 S2X80 In42 540 A 50 A 50 A 26 10 10 TA75DU42** 29-4222 42 S2X80 In52 680 A 50 A 50 A 26 10 10 TA75DU52** 36-5230 56 S2X80 In63 820 A 63 A 63 A 30 10 10 TA75DU63** 45-6337 68 S2X80 In80 1040 A 75 A 75 A 30 10 10 TA75DU80** 60-80

68 S3H160 In125 * 900 A95 A95 A30 20 10 TA80DU52 36 - 5245 83 S3H160 In125 * 1050 A95 A95 A30 20 10 TA80DU52 36 - 5255 98 S3H160 In125 * 1250 A95 A95 A40 20 10 TA80DU63 45 - 6375 135 S3H250 In200 * 1700 A95 A95 A75 20 10 TA110DU90 66 - 9090 158 S3H250 In200 * 2000 A110 A110 A95 20 20 TA110DU110 80 - 110

110 193 S4H250 PR211-I In250

2500 A145 A145 A95 15 20 TA200DU135 100 - 135

132 232 S4H250 PR211-I In250

3000 A145 A145 A110 15 20 TA200DU175 130 - 175

160 282 S5H400 PR211-I In400

4000 A210 A210 A145 15 15 TA200DU175 130 - 175

200 349 S5H400 PR211-I In400

4800 A210 A210 A185 15 15 TA450DU235 165 - 235

250 430 S6S630 PR211-I In630

6300 AF400 AF400 A210 10 15 E500DU500 150 - 500

290 520 S6S630 PR211-I In630

7560 AF400 AF400 A260 10 15 E500DU500 150 - 500

315 545 S6S630 PR211-I In630

7560 AF400 AF400 A260 10 15 E500DU500 150 - 500

355 610 S6S800 PR211-I In800

8000 AF400 AF400 A260 10 15 E500DU500 150 - 500

* : magnetic only adjustable release** : TOR to be connected between MCCB and Line/Delta node MB4050SD2.1af

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/08/2001 by Jean-Paul Guitton

Page 62: Type Selection Tables

DIRECT-ON-LINE STARTERS400 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP4050HD2-1af

MCCB+PR212MP+AF-contDirect-on-line starters with MCCB

400 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type I1 range Current setting

PR 212 / MPrelease I3 *

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [A] [mm] Imax [A]30 56 S4H160 PR212-MP In100 50 - 100 600 A145 15 10037 68 S4H160 PR212-MP In100 50 - 100 700 A145 15 10045 83 S4H160 PR212-MP In100 50 - 100 900 A145 15 10055 98 S4H160 PR212-MP In160 80 - 160 1120 A145 15 14575 135 S4H160 PR212-MP In160 80 - 160 1440 A145 15 14590 158 S4H250 PR212-MP In200 100 - 200 1800 A185 15 185110 193 S5H400 PR212-MP In320 160 - 320 2240 A210 15 210132 232 S5H400 PR212-MP In320 160 - 320 2560 A260 15 260160 282 S5H400 PR212-MP In320 160 - 320 2880 AF400** 10 320200 349 S6H800 PR212-MP In630 315 - 630 3780 AF400 10 400250 430 S6H800 PR212-MP In630 315 - 630 5040 AF460 10 460290 520 S6H800 PR212-MP In630 315 - 630 5670 AF580 10 460315 545 S6H800 PR212-MP In630 315 - 630 5670 AF580 10 580355 610 S6H800 PR212-MP In630 315 - 630 5670 AF580 10 630

MP4050HD2-1af

* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes whenthe motor is starting-up.** : A300 in case of Normal Start.NORMAL and HEAVY-DUTY START

For smaller motor powers, please refer to MMS tables or MCCB / MCB tables

Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 63: Type Selection Tables

DIRECT ON LINE STARTERS400 V - 50 kA - Normal start - up, type : 2Note : MB4050NS2.1af

MCCB+AF-contactorDirect-on-line starters with MCCB

400 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type Safety clearance

Type Current settingrange

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 S2X80 In1.6 21 A 9 10 TA25DU1.4 1 - 1.4 1.40.55 1.5 S2X80 In2 26 A 9 10 TA25DU1.8 1.3 - 1.8 1.80.75 1.9 S2X80 In2.5 33 A 9 10 TA25DU2.4 1.7 - 2.4 2.41.1 2.8 S2X80 In3.2 42 A 9 10 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 S2X80 In5 65 A 16 10 TA25DU4 2.8 - 4 4

S2X80 ln5 65 A26 10 TA25DU5 3.5 - 5 52.2 5 S2X80 In6.5 84 A 26 10 TA25DU6.5 4.5 - 6.5 6.53 6.6 S2X80 In8.5 110 A 26 10 TA25DU8.5 6 - 8.5 8.54 8.6 S2X80 In11 145 A 30 10 TA25DU11 7.5 - 11 11

5.5 11.5 S2X80 In16 210 A 30 10 TA25DU14 10 - 14 147.5 15.2 S2X80 In20 260 A 30 10 TA25DU19 13 - 19 1911 22 S2X80 In25 325 A 30 10 TA25DU25 18 - 25 2515 28.5 S2X80 In32 415 A 50 10 TA75DU32 22 - 32 32

18.5 36 S2X80 In42 540 A 50 10 TA75DU42 29 - 42 4222 42 S2X80 In52 680 A 50 10 TA75DU52 36 - 52 5030 56 S2X80 In63 820 A 63 10 TA75DU63 45 - 63 6337 68 S2X80 In80 1040 A 75 10 TA75DU80 60 - 80 7545 83 S3H160 In160 * 1250 A 95 20 TA110DU90 65 - 90 9055 98 S3H160 In160 * 1500 A 110 20 TA110DU110 80 - 110 11075 135 S3H250 In200 * 2150 A 145 15 TA200DU150 110 - 150 14590 158 S3H250 In200 * 2400 A 185 15 TA200DU175 130 - 175 175110 193 S4H250 PR211-I

In2503000 A 210 15 TA450DU235 165 - 235 210

132 232 S5H400 PR211-I In320

3840 A 260 15 TA450DU310 220 - 310 260

160 282 S5H400 PR211-I In400

4800 A 300 15 TA450DU310 220 - 310 300

200 349 S6S630 PR211-I In630

6300 AF 400 10 E 500DU 150 - 500 400

250 430 S6S630 PR211-I In630

S6S630 PR211-I In630

7560

7560

AF 580

AF 580

10

10

E 500DU**

E 800DU

150 - 500

250 - 800

500

580

290 520 S6S800 PR211-I In800

8000 AF 580 10 E 800DU 250 - 800 580

315 545 S6S800 PR211-I In800

9600 AF 580 10 E 800DU 250 - 800 580

355 610 S6S800 PR211-I In800

9600 AF 750 10 E 800DU 250 - 800 750

MB4050NS2.1af* : Magnetic only adjustable release. ** Mounting kit between Contactor and Relay is not available

Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 64: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM400 V - 50 kA - Normal start - up, type : 2Note : MB4050NSIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2400 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 1.1 S2X80 In1.6 21 A9 10 1.60.55 1.5 S2X80 In2 26 A9 10 20.75 1.9 S2X80 In2.5 33 A16 10 2.51.1 2.8 S2X80 In3.2 42 A26 10 3.21.5 3.5 S2X80 In5 65 A26 10 52.2 5 S2X80 In6.5 84 A26 10 6.53 6.6 S2X80 In8.5 110 A26 10 8.54 8.6 S2X80 In11 145 A30 10 11

5.5 11.5 S2X80 In16 210 A30 10 167.5 15.2 S2X80 In20 260 A30 10 2011 22 S2X80 In25 325 A30 10 2515 28.5 S2X80 In32 415 A50 10 32

18.5 36 S2X80 In42 540 A50 10 4222 42 S2X80 In52 680 A50 10 5030 56 S2X80 In63 820 A63 10 6337 68 S2X80 In80 1040 A75 10 7545 83 S3H160 In160 * 1250 A95 20 9555 98 S3H160 In160 * 1500 A110 20 11075 135 S3H250 In200 * 2150 A145 15 14590 158 S3H250 In200 * 2400 A185 15 175

110 193 S4H250 PR211-I In250 3000 A210 15 210132 232 S5H400 PR211-I In320 3840 A260 15 260160 282 S5H400 PR211-I In400 4800 A300 15 300200 349 S6S630 PR211-I In630 6300 AF400 10 400250 430 S6S630 PR211-I In630 7560 AF580 10 580290 520 S6S800 PR211-I In800 8000 AF580 10 580315 545 S6S800 PR211-I In800 9600 AF580 10 580355 610 S6S800 PR211-I In800 9600 AF750 10 750

* Magnetic only adjustable MB4050NSIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 65: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM400 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB4050HDIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2400 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 1.1 S2X80 In1.6 21 A9 10 1.60.55 1.5 S2X80 In2 26 A9 10 20.75 1.9 S2X80 In2.5 33 A16 10 2.51.1 2.8 S2X80 In3.2 42 A26 10 3.21.5 3.5 S2X80 In5 65 A26 10 52.2 5 S2X80 In6.5 84 A26 10 6.53 6.6 S2X80 In8.5 110 A26 10 8.54 8.6 S2X80 In11 145 A30 10 11

5.5 11.5 S2X80 In16 210 A30 10 167.5 15.2 S2X80 In20 260 A30 10 2011 22 S2X80 In25 325 A30 10 2515 28.5 S2X80 In32 415 A50 10 32

18.5 36 S2X80 In42 540 A50 10 4222 42 S2X80 In52 680 A50 10 5030 56 S2X80 In63 820 A63 10 6337 68 S2X80 In80 1040 A95 20 8045 83 S3H160 In160 * 1250 A110 20 11055 98 S3H160 In160 * 1500 A145 15 14575 135 S3H250 In200 * 2150 A185 15 18590 158 S3H250 In200 * 2400 A210 15 200

110 193 S4H250 PR211-I In250 3000 A260 15 250132 232 S5H400 PR211-I In320 3840 A300 15 300160 282 S5H400 PR211-I In400 4800 AF400 10 400200 349 S6S630 PR211-I In630 6300 AF460 10 460250 430 S6S630 PR211-I In630 7560 AF750 10 630290 520 S6S800 PR211-I In800 8000 AF750 10 750315 545 S6S800 PR211-I In800 9600 AF750 10 750355 610 S6S800 PR211-I In800 9600 AF750 10 750

* : magnetic only adjustable release. MB4050HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 66: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY400 V - 50 kA - Normal start - up, type : 2Note : MP4050SD2.1af

PR212/MP+AF contactorStar-delta starters with MCCB

400 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactors

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 83 S4H160 PR212-MP In100 50 - 100 800 A145 A145 A30 15 1055 98 S4H160 PR212-MP In160 80 - 160 960 A145 A145 A40 15 1075 135 S4H160 PR212-/MP In160 80 - 160 1280 A145 A145 A75 15 1090 158 S4H250 PR212-MP In200 100 - 200 1600 A145 A145 A95 15 20

110 193 S5H400 PR212-MP In320 160 - 320 1920 A210 A210 A95 15 20132 232 S5H400 PR212-MP In320 160 - 320 2240 A210 A210 A110 15 20160 282 S5H400 PR212-MP In320 160 - 320 2560 A210 A210 A145 15 15200 349 S6H800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15250 430 S6H800 PR212-MP In630 315 - 630 4410 AF400 AF400 A210 10 15290 520 S6H800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15315 545 S6H800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15355 610 S6H800 PR212-MP In630 315 - 630 5670 AF400 AF400 A260 10 15

MP4050SD2.1af* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes whenthe motor is starting-up.

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/08/2001 by Jean-Paul Guitton

Page 67: Type Selection Tables

DOL STARTERS400 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB4050HD2.1af

Isomax+AF+EOLDirect-on-line starters with MCCB

400 V, 50 kA, long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.1 S2X80 In1.6 21 A9 10 TA25DU1.4 ** 1 - 1.4 1.40.55 1.5 S2X80 In2 26 A9 10 TA25DU1.8 ** 1.3 - 1.8 1.80.75 1.9 S2X80 In2.5 33 A9 10 TA25DU2.4 ** 1.7 - 2.4 2.41.1 2.8 S2X80 In3.2 42 A9 10 TA25DU3.1 ** 2.2 - 3.1 3.11.5 3.5 S2X80 In5 65 A16 10 TA25DU4 ** 2.8 - 4 4

S2X80 ln5 65 A26 10 TA25DU5** 3.5 - 5 52.2 5 S2X80 In6.5 84 A26 10 TA25DU6.5 ** 4.5 - 6.5 6.53 6.6 S2X80 In8.5 110 A26 10 TA25DU8.5 ** 6 - 8.5 8.54 8.6 S2X80 In11 145 A30 10 TA25DU11 ** 7.5 - 11 11

5.5 11.5 S2X80 In16 210 A30 10 TA 450SU60 (4) 10 - 15 157.5 15.2 S2X80 In20 260 A30 10 TA 450SU60 (3) 13 - 20 2011 22 S2X80 In25 325 A30 10 TA 450SU60 (2) 20 - 30 2515 28.5 S2X80 In32 415 A50 10 TA 450SU80 (2) 23 - 40 32

18.5 36 S2X80 In42 540 A50 10 TA 450SU80 (2) 23 - 40 4022 42 S2X80 In52 680 A50 10 TA 450SU60 (1) 40 - 60 5030 56 S2X80 In63 820 A63 10 TA 450SU80 (1) 55 - 80 6337 68 S2X80 In80 1040 A95 20 TA 450SU80 (1) 55 - 80 8045 83 S3H160 In160 * 1250 A110 20 TA 450SU105 (1) 70 - 105 10555 98 S3H160 In160 * 1500 A145 15 TA 450SU140 (1) 95 - 140 14075 135 S3H250 In200 * 2150 A185 15 TA 450SU185 (1) 130 - 185 18590 158 S3H250 In200 * 2400 A210 15 TA 450SU185 (1) 130 - 185 185

110 193 S4H250 PR211-I In250 3000 A260 15 TA 450SU235 (1) 165 - 235 235132 232 S5H400 PR211-I In320 3840 A300 15 TA 450SU310 (1) 220 - 310 300160 282 S5H400 PR211-I In400 4800 AF 400 10 E 500DU 150 - 500 400200 349 S6S630 PR211-I In630 6300 AF 460 10 E 500DU 150 - 500 460250 430 S6S630 PR211-I In630

S6S630 PR211-I In630

7560

7560

AF 750

AF 750

10

10

E 500DU***

E 800DU

150 - 500

250 - 800

500

630

290 520 S6S800 PR211-I In800 8000 AF 750 10 E 800DU 250 - 800 750315 545 S6S800 PR211-I In800 9600 AF 750 10 E 800DU 250 - 800 750355 610 S6S800 PR211-I In800 9600 AF 750 10 E 800DU 250 - 800 750

MB4050HD2.1af* : Magnetic only adjustable release.** : by pass contactor on the TOR during starting, same size as the line contactor*** Mounting kit between Contactor and Relay is not available. (x) : number of primary turns on CT

Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/08/2001 by Jean-Paul Guitton

Page 68: Type Selection Tables

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY400 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB4050SDHD2.1af

MCCB PR211+AF

Star-delta starters with MCCB400 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors Thermal OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]45 83 S3H160 In160 * 1280 A95 A95 A50 20 10 TA450SU60 40 - 6055 98 S3H160 In160 * 1600 A95 A95 A50 20 10 TA450SU60 40 - 6075 135 S3H250 In200 * 2200 A145 A145 A75 15 10 TA450SU80 55 - 8090 158 S3H250 In200 * 2400 A145 A145 A95 15 20 TA450SU105 70 - 105

110 193 S4H250 PR211-I In250

3000 A145 A145 A95 15 20 TA450SU140 95 - 140

132 232 S5H400 PR211-I In320

3840 A210 A210 A145 15 15 TA450SU140 95 - 140

160 282 S5H400 PR211-I In400

4800 A210 A210 A145 15 15 TA450SU185 130 - 185

200 349 S6S630 PR211-I In630

6300 AF400 AF400 A185 10 15 E500DU 150 - 500

250 430 S6S630 PR211-I In630

7560 AF400 AF400 A260 10 15 E500DU 150 - 500

290 520 S6S800 PR211-I In800

8000 AF400 AF400 A260 10 15 E500DU 150 - 500

315 545 S6S800 PR211-I In800

9600 AF400 AF400 A260 10 15 E500DU 150 - 500

355 610 S6S800 PR211-I In800

9600 AF400 AF400 AF400 10 10 E500DU 150 - 500

MB4050SDHD2.1af* : Magnetic only adjustable release.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 69: Type Selection Tables

STAR-DELTA STARTERS + INSUM400 V - 50 kA - Normal start - up, type : 2Note : MB4050SDIN2.1af

INSUM PR211+AF

Star-delta starters with MCCB400 V, 50 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type**

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [mm] [mm]45 83 S3H160 In125 * 1050 A95 A95 A30 20 1055 98 S3H160 In125 * 1250 A95 A95 A40 20 1075 135 S3H250 In200 * 1700 A95 A95 A75 20 1090 158 S3H250 In200 * 2000 A110 A110 A75 20 10

110 193 S4H250 PR211-I In250 2500 A145 A145 A95 15 20132 232 S4H250 PR211-I In250 3000 A145 A145 A110 15 20160 282 S5H400 PR211-I In400 4000 A210 A210 A145 15 15200 349 S5H400 PR211-I In400 4800 A210 A210 A185 15 15250 430 S6S630 PR211-I In630 6300 AF400 AF400 A210 10 15290 520 S6S630 PR211-I In630 7560 AF400 AF400 A260 10 15315 545 S6S630 PR211-I In630 7560 AF400 AF400 A260 10 15355 610 S6S800 PR211-I In800 8000 AF400 AF400 A260 10 15

MB4050SDIN2.1af* : Magnetic only adjustable release.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 31/08/2001 by Jean-Paul Guitton

Page 70: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY400 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP4050SDHD2.1af

MCCB PR212/MP+AFStar-delta starters with MCCB

400 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range** Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW]

Ie [A] [A] [A] [mm] [mm]

45 83 S4H160 PR212-MP In100 50 - 100 900 A145 A145 A50 15 1055 98 S4H160 PR212-MP In160 80 - 160 1120 A145 A145 A50 15 1075 135 S4H160 PR212-MP In160 80 - 160 1440 A145 A145 A75 15 1090 158 S4H250 PR212-MP In200 100 - 200 1800 A145 A145 A95 15 20110 193 S5H400 PR212-MP In320 160 - 320 2240 A210 A210 A95 15 20132 232 S5H400 PR212-MP In320 160 - 320 2560 A210 A210 A145 15 15160 282 S5H400 PR212-MP In320 160 - 320 2880 A210 A210 A145 15 15200 349 S6H800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15250 430 S6H800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15290 520 S6H800 PR212-MP In630 315 - 630 5670 AF400 AF400 A260 10 15315 545 S6H800 PR212-MP In630 315 - 630 5670 AF400 AF400 A260 10 15355 610 S6H800 PR212-MP In630 315 - 630 5670 AF400 AF400 AF400 10 10

MP4050SDHD2.1af* In order to avoid untimely tripping during motor star-up transient, the PR212/MP release recognizes whenthe motor is starting-up.** The protection against overload (L function) of the MP release, must be set with class 30 starting class.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 71: Type Selection Tables

Direct-on-line starters400 V - 65 kA - Normal start - up, type : 2Note : MB4065NS2.1

MCCB+TOR

Direct-on-line starters with MCCB400 V, 65 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.1 S2X80 In1.6 21 A 9 10 TA25DU1.4 1 - 1.4 1.40.55 1.5 S2X80 In2 26 A 9 10 TA25DU1.8 1.3 - 1.8 1.80.75 1.9 S2X80 In2.5 33 A 9 10 TA25DU2.4 1.7 - 2.4 2.41.1 2.8 S2X80 In3.2 42 A 9 10 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 S2X80 In5 65 A 16

A 16

10

10

TA25DU4

TA25DU5

2.8 - 4

3.5 - 5

4

5

2.2 5 S2X80 In6.5 84 A 26 10 TA25DU6.5 4.5 - 6.5 6.53 6.6 S2X80 In8.5 110 A 26 10 TA25DU8.5 6 - 8.5 8.54 8.6 S2X80 In11 145 A 30 10 TA25DU11 7.5 - 11 11

5.5 11.5 S2X80 In16 210 A 50 10 TA25DU14 10 - 14 147.5 15.2 S2X80 In20 260 A 50 10 TA25DU19 13 - 19 1911 22 S2X80 In25 325 A 50 10 TA42DU25 18 - 25 2515 28.5 S2X80 In32 415 A 50 10 TA75DU32 22 - 32 32

18.5 36 S2X80 In42 540 A 50 10 TA75DU42 29 - 42 4222 42 S2X80 In52 680 A 50 10 TA75DU52 36 - 52 5030 56 S2X80 In63 820 A 63 10 TA75DU63 45 - 63 6337 68 S2X80 In80 1040 A 75 10 TA75DU80 60 - 80 7545 83 S3H160 In160 * 1250 A 145 15 TA200DU110 80 - 110 11055 98 S3H160 In160 * 1500 A 145 15 TA200DU110 80 - 110 11075 135 S3H250 In200 * 2150 A 145 15 TA200DU150 110 - 150 14590 158 S3H250 In200 * 2400 A 185 15 TA200DU175 130 - 175 175

110 193 S4H250 PR211-I In250

3000 A 210 15 TA450DU235 165 - 235 210

132 232 S5H400 PR211-I In320

3840 A 260 15 TA450DU310 220 - 310 260

160 282 S5H400 PR211-I In400

4800 A 300 15 TA450DU310 220 - 310 300

200 349 S6H630 PR211-I In630

6300 EH 370 40 T450DU400 285 - 400 400

250 430 S6H630 PR211-I In630

7560 EH 550 40 T900DU500 355 - 500 500

290 520 S6H800 PR211-I In800

8000 EH 550 40 T900DU650 465 - 650 550

315 545 S6H800 PR211-I In800

9600 EH 700 40 T900DU650 465 - 650 650

355 610 S6H800 PR211-I In800

9600 EH 700 40 T900DU650 465 - 650 650

MB4065NS2.1* : Magnetic only adjustable release.

Created 14/01/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 25/02/2000 by Jean-Paul Guitton

Page 72: Type Selection Tables

Direct-on-line Starters415 V - 80 kA - Normal start - up, type : 2Note : MB4180NS2.1

MCCB+TOR

Direct-on-line starters with MCCB415 V, 80 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.1 S2X80 In1.6 21 A 9 10 TA25DU1.4 1 - 1.4 1.40.55 1.5 S2X80 In2 26 A 9 10 TA25DU1.8 1.3 - 1.8 1.80.75 1.9 S2X80 In2.5 33 A 9 10 TA25DU2.4 1.7 - 2.4 2.41.1 2.8 S2X80 In3.2 42 A 16 10 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 S2X80 In5 65 A 26

A 26

10

10

TA25DU4

TA25DU5

2.8 - 4

3.5 - 5

4

5

2.2 5 S2X80 In6.5 84 A 26 10 TA25DU6.5 4.5 - 6.5 6.53 6.6 S2X80 In8.5 110 A 26 10 TA25DU8.5 6 - 8.5 8.54 8.6 S2X80 In11 145 A 30 10 TA25DU11 7.5 - 11 11

5.5 11.5 S2X80 In16 210 A 50 10 TA25DU14 10 - 14 147.5 15.2 S2X80 In20 260 A 50 10 TA25DU19 13 - 19 1911 22 S2X80 In25 325 A 50 10 TA42DU25 18 - 25 2515 28.5 S2X80 In32 415 A 50 10 TA75DU32 22 - 32 32

18.5 36 S2X80 In42 540 A 50 10 TA75DU42 29 - 42 4222 42 S2X80 In52 680 A 50 10 TA75DU52 36 - 52 5030 56 S2X80 In63 820 A 63 10 TA75DU63 45 - 63 6337 68 S2X80 In80 1040 A 75 10 TA75DU80 60 - 80 7545 83 S3L160 In160 * 1250 A 145 15 TA200DU110 80 - 110 11055 98 S3L160 In160 * 1500 A 145 15 TA200DU110 80 - 110 11075 135 S3L250 In200 * 2150 A 145 15 TA200DU150 110 - 150 14590 158 S3L250 In200 * 2400 A 185 15 TA200DU175 130 - 175 175

110 193 S4L250 PR211-I In250 3000 A 210 15 TA450DU235 165 - 235 210132 232 S5L400 PR211-I In320 3840 A 260 15 TA450DU310 220 - 310 260160 282 S5L400 PR211-I In400 4800 A 300 15 TA450DU310 220 - 310 300200 349 S6L630 PR211-I In630 6300 EH 370 40 T450DU400 285 - 400 400250 430 S6L630 PR211-I In630 7560 EH 550 40 T900DU500 355 - 500 500290 520 S6L800 PR211-I In800 8000 EH 550 40 T900DU650 465 - 650 550315 545 S6L800 PR211-I In800 9600 EH 700 40 T900DU650 465 - 650 650355 610 S6L800 PR211-I In800 9600 EH 700 40 T900DU650 465 - 650 650

MB4180NS2.1* : Magnetic only adjustable release.

Created 24/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 25/02/2000 by Jean-Paul Guitton

Page 73: Type Selection Tables

DIRECT-ON-LINE STARTERS440 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP4450HD2-1af

MCCB+PR212MP+AF-contDirect-on-line starters with MCCB

440 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type I1 range Current setting

PR 212 / MPrelease I3 *

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [A] [mm] Imax [A]30 52 S4H160 PR212-MP In100 50 - 100 600 A145 15 10037 63 S4H160 PR212-MP In100 50 - 100 700 A145 15 10045 75 S4H160 PR212-MP In100 50 - 100 800 A145 15 10055 90 S4H160 PR212-MP In160 80 - 160 960 A145 15 14575 120 S4H160 PR212-MP In160 80 - 160 1280 A145 15 14590 147 S4H250 PR212-MP In200 100 - 200 1600 A185 15 185

110 177 S5H400 PR212-MP In320 160 - 320 1920 A210 15 210132 212 S5H400 PR212-MP In320 160 - 320 2240 A260 15 260160 260 S5H400 PR212-MP In320 160 - 320 2880 AF400** 10 320200 320 S6H800 PR212-MP In630 315 - 630 3780 AF400 10 400250 370 S6H800 PR212-MP In630 315 - 630 4410 AF460 10 460290 436 S6H800 PR212-MP In630 315 - 630 5040 AF460 10 460315 500 S6H800 PR212-MP In630 315 - 630 5040 AF580 10 580355 549 S6H800 PR212-MP In630 315 - 630 5670 AF580 10 580

MP4450HD2-1af

* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes whenthe motor is starting-up.**: A300 in case of Normal Starter.

NORMAL and HEAVY-DUTY START

For smaller motor powers, please refer to MMS tables or MCCB / MCB tables

Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 74: Type Selection Tables

DIRECT ON LINE STARTERS440 V - 50 kA - Normal start - up, type : 2Note : MB4450NS2.1af

MCCB+AF-contactor

Direct-on-line starters with MCCB440 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1 S2X80 In1.6 21 A9 10 TA25DU1.4 1 - 1.4 1.40.55 1.4 S2X80 In2 26 A9 10 TA25DU1.8 1.3 - 1.8 1.80.75 1.7 S2X80 In2.5 33 A9 10 TA25DU2.4 1.7 - 2.4 2.41.1 2.2 S2X80 In3.2 42 A9 10 TA25DU3.1 2.2 - 3.1 3.11.5 3.0 S2X80 In4 52 A16 10 TA25DU4 2.8 - 4 42.2 4.4 S2X80 In5 65 A26 10 TA25DU5 3,5 - 5 53 5.7 S2X80 In6.5 84 A26 10 TA25DU6.5 4.5 - 6.5 6.5

S2X80 In6.5 84 A26 10 TA25DU8.5 6 - 8.5 6.54 7.8 S2X80 In11 145 A30 10 TA25DU11 7.5 - 11 11

5.5 10.5 S2X80 In16 210 A30 10 TA25DU14 10 - 14 147.5 13.5 S2X80 In16 210 A30 10 TA25DU14 10 - 14 14

S2X80 In16 210 A30 10 TA25DU19 13 - 19 1611 19 S2X80 In25 325 A30 10 TA42DU25 18 - 25 2515 26 S2X80 In32 415 A50 10 TA75DU32 22 - 32 32

18,5 32 S2X80 In42 540 A50 10 TA75DU42 29 - 42 4222 38 S2X80 In52 680 A50 10 TA75DU52 36 - 52 4530 52 S2X80 In63 820 A63 10 TA75DU63 45 - 63 6337 63 S2X80 In80 1040 A75 10 TA75DU80 60 - 80 7045 75 S3H160 In125 * 1150 A95 20 TA110DU90 65 - 90 9055 90 S3H160 In125 * 1400 A110 20 TA110DU110 80 - 110 10075 120 S3H250 In200 * 1920 A145 15 TA200DU135 100 - 135 13590 147 S3H250 In200 * 2300 A185 15 TA200DU175 130 - 175 175110 177 S4H250 PR211-I

In2503000 A210 15 TA450DU235 165 - 235 210

132 212 S5H400 PR211-I In320

3200 A260 15 TA450DU235 165 - 235 235

160 260 S5H400 PR211-I In400

4000 A300 15 TA450DU310 220 - 310 300

200 320 S5H400 PR211-I In400

4800 AF 400 10 E 500DUTA450DU400

150 - 500285 - 400

400400

250 410 S6H630 PR211-I In630

S6H630 PR211-I In630

63006300

AF 580AF 580

1010

E 500DU**E 800DU

TA900DU500

150 - 500250 - 800355 - 500

500580500

290 448 S6H630 PR211-I In630

S6H630 PR211-I In630

75607560

AF 580AF 580

1010

E 500DU**E 800DU

TA900DU500

150 - 500250 - 800355 - 500

500580500

315 500 S6H800 PR211-I In800

8000 AF 580 10 E 800DUTA900DU650

250 - 800465 - 650

580580

355 549 S6H800 PR211-I In800

9600 AF 580 10 E 800DUTA900DU650

250 - 800465 - 650

580580

MB4450NS2.1af* Magnetic only adjustable release.** Mounting kit between Contactor and Relay is not available

Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 19/09/2001 by Jean-Paul Guitton

Page 75: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM440 V - 50 kA - Normal start - up, type : 2Note : MB4450NSIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2440 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 1 S2X80 In1.6 21 A9 10 1.60.55 1.4 S2X80 In2 26 A9 10 20.75 1.7 S2X80 In2.5 33 A16 10 2.51.1 2.2 S2X80 In3.2 42 A26 10 3.21.5 3 S2X80 In4 52 A26 10 42.2 4.4 S2X80 In5 65 A26 10 53 5.7 S2X80 In6.5 84 A26 10 6.54 7.8 S2X80 In11 145 A30 10 11

5.5 10.5 S2X80 In16 210 A30 10 167.5 13.5 S2X80 In16 210 A30 10 1611 19 S2X80 In25 325 A30 10 2515 26 S2X80 In32 415 A50 10 32

18.5 32 S2X80 In42 540 A50 10 4222 38 S2X80 In52 680 A63 10 4530 52 S2X80 In63 820 A63 10 6337 63 S2X80 In80 1040 A75 10 7045 75 S3H160 In125 * 1150 A95 20 9355 90 S3H160 In125 * 1400 A110 20 10075 120 S3H250 In200 * 1920 A145 15 14590 147 S3H250 In200 * 2300 A185 15 185

110 177 S4H250 PR211-I In250 3000 A210 15 210132 212 S5H400 PR211-I In320 3200 A260 15 240160 260 S5H400 PR211-I In400 4000 A300 15 280200 320 S5H400 PR211-I In400 4800 AF400 10 400250 410 S6H630 PR211-I In630 6300 AF580 10 580290 448 S6H630 PR211-I In630 7560 AF580 10 580315 500 S6H800 PR211-I In800 8000 AF580 10 580355 549 S6H800 PR211-I In800 9600 AF580 10 580

* : Magnetic only adjustable release MB4450NSIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 76: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM440 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB4450HDIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM440 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 1 S2X80 In1.6 21 A9 10 1.60.55 1.4 S2X80 In2 26 A9 10 20.75 1.7 S2X80 In2.5 33 A16 10 2.51.1 2.2 S2X80 In3.2 42 A26 10 3.21.5 3 S2X80 In4 52 A26 10 42.2 4.4 S2X80 In5 65 A26 10 53 5.7 S2X80 In6.5 84 A26 10 6.54 7.8 S2X80 In11 145 A30 10 11

5.5 10.5 S2X80 In16 210 A30 10 167.5 13.5 S2X80 In16 210 A30 10 1611 19 S2X80 In25 325 A30 10 2515 26 S2X80 In32 415 A50 10 32

18.5 32 S2X80 In42 540 A50 10 4222 38 S2X80 In52 680 A63 10 4530 52 S2X80 In63 820 A63 10 6337 63 S2X80 In80 1040 A95 20 8045 75 S3H160 In125 * 1150 A110 20 10055 90 S3H160 In125 * 1400 A145 15 12575 120 S3H250 In200 * 1920 A185 15 18590 147 S3H250 In200 * 2300 A210 15 200

110 177 S4H250 PR211-I In250 3000 A260 15 240132 212 S5H400 PR211-I In320 3200 A300 15 280160 260 S5H400 PR211-I In400 4000 AF400 10 400200 320 S5H400 PR211-I In400 4800 AF460 10 400250 410 S6H630 PR211-I In630 6300 AF580 10 580290 448 S6H630 PR211-I In630 7560 AF750 10 630315 500 S6H800 PR211-I In800 8000 AF750 10 750355 549 S6H800 PR211-I In800 9600 AF750 10 750

* : Magnetic only adjustable release. MB4450HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 77: Type Selection Tables

STAR-DELTA STARTERS440 V - 50 kA - Normal start - up, type : 2Note : MB4450SD2.1af

mccb+AF contactorStar-delta starters with MCCB

440 V, 50 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]5.5 10.5 S2X80 In16 210 A 30 A 30 A 9* 10 10 TA25DU14*** 10-147.5 13.5 S2X80 In16 210 A 30 A 30 A 9* 10 10 TA25DU14^*** 10-1411 19 S2X80 In25 325 A 30 A 30 A 9* 10 10 TA42DU25*** 18-2515 26 S2X80 In32 415 A 50 A 50 A 16* 10 10 TA75DU32*** 22-32

18.5 32 S2X80 In42 540 A 50 A 50 A 16* 10 10 TA75DU42*** 29-4222 38 S2X80 In52 680 A 50 A 50 A 26* 10 10 TA75DU52*** 36-5230 52 S2X80 In63 820 A 63 A 63 A 26* 10 10 TA75DU63*** 45-6337 63 S2X80 In80 1040 A 75 A 75 A 30* 10 10 TA75DU80*** 60-8045 75 S3H160 In125 ** 950 A95 A95 A30* 20 10 TA80DU52 36 - 5255 90 S3H160 In125 ** 1150 A95 A95 A40* 20 10 TA80DU63 45 - 6375 120 S3H250 In200 ** 1600 A145 A145 A75* 15 10 TA80DU80 60 - 8090 147 S3H250 In200 ** 1850 A145 A145 A75* 15 10 TA200DU110 80 - 110

110 177 S4H250 PR211-I In250 2500 A145 A145 A95 15 20 TA200DU110 80 - 110132 212 S4H250 PR211-I In250 3000 A145 A145 A110 15 20 TA200DU135 100 - 135160 260 S5H400 PR211-I In400 4000 A210 A210 A145 15 15 TA200DU175 130 - 175200 320 S5H400 PR211-I In400 4800 A210 A210 A185 15 15 TA450DU235 165 - 235250 410 S6H630 PR211-I In630 6300 AF400 AF400 A210 10 15 E500DU500

TA450DU310

150 - 500

220 - 310

290 448 S6H630 PR211-I In630 6300 AF400 AF400 A260 10 15 E500DU500

TA450DU310

150 - 500

220 - 310

315 500 S6H630 PR211-I In630 6300 AF400 AF400 A260 10 15 E500DU500

TA450DU310

150 - 500

220 - 310

355 549 S6H630 PR211-I In630 7560 AF400 AF400 A260 10 15 E500DU500

TA450DU400

150 - 500

285 - 400

MB4450SD2.1af * : Using mounting kits, use Star-contactor size same as Delta-contactor size.** : Magnetic only adjustable release** : Connect the OR between the MCCB and the Line-Delta node.

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 19/09/2001 by Jean-Paul Guitton

Page 78: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY440 V - 50 kA - Normal start - up, type : 2Note : MP4450SD2.1af

PR212/MP+AF contactorStar-delta starters with MCCB

440 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 75 S4H160 PR212-MP In100 50 - 100 700 A145 A145 A30 15 1055 90 S4H160 PR212-MP In160 80 - 160 960 A145 A145 A40 15 1075 120 S4H160 PR212-MP In160 80 - 160 1120 A145 A145 A75 15 1090 147 S4H160 PR212-MP In160 80 - 160 1440 A145 A145 A75 15 10110 177 S4H250 PR212-MP In200 100 - 200 1600 A145 A145 A95 15 20132 212 S5H400 PR212-MP In320 160 - 320 1920 A210 A210 A110 15 20160 260 S5H400 PR212-MP In320 160 - 320 2560 A210 A210 A145 15 15200 320 S6H800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15250 410 S6H800 PR212-MP In630 315 - 630 3780 AF400 AF400 A210 10 15290 448 S6H800 PR212-MP In630 315 - 630 4410 AF400 AF400 A260 10 15315 500 S6H800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15355 549 S6H800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15

MP4450SD2.1af

* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the motor is starting-up

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/08/2001 by Jean-Paul Guitton

Page 79: Type Selection Tables

DOL STARTERS440 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB4450HD2.1af

Isomax+AF+EOLDirect-on-line starters with MCCB

440 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1 S2X80 In1.6 21 A9 10 TA25DU1.4 ** 1 - 1.4 1.40.55 1.4 S2X80 In2 26 A9 10 TA25DU1.8 ** 1.3 - 1.8 1.80.75 1.7 S2X80 In2.5 33 A9 10 TA25DU2.4 ** 1.7 - 2.4 2.41.1 2.2 S2X80 In3.2 42 A9 10 TA25DU3.1 ** 2.2 - 3.1 3.11.5 3 S2X80 In4 52 A16 10 TA25DU4 ** 2.8 - 4 42.2 4.4 S2X80 In5 65 A26 10 TA25DU5 ** 3.5 - 5 53 5.7 S2X80 In6.5 84 A26 10 TA25DU6.5 ** 4.5 - 6.5 6.5

S2X80 In6.5 84 A30 10 TA25DU8.5 ** 6 - 8.5 6.54 7.8 S2X80 In11 145 A30 10 TA25DU11 ** 7.5 - 11 11

5.5 10.5 S2X80 In16 210 A30 10 TA25DU14 ** 10 - 14 147.5 13.5 S2X80 In16 210 A30 10 TA 450SU60 (4) 10 - 15 1511 19 S2X80 In25 325 A30 10 TA 450SU80 (3) 18 - 27 2515 26 S2X80 In32 415 A50 10 TA 450SU60 (2) 20 - 30 30

18.5 32 S2X80 In42 540 A50 10 TA 450SU80 (2) 28 - 40 4022 38 S2X80 In52 680 A50 10 TA 450SU80 (2) 28 - 40 4030 52 S2X80 In63 820 A63 10 TA 450SU60 40 - 60 6037 63 S2X80 In80 1040 A95 20 TA 450SU80 55 - 80 8045 75 S3H160 In125 * 1150 A110 20 TA 450SU105 70 - 105 10055 90 S3H160 In125 * 1400 A145 15 TA 450SU105 70 - 105 10575 120 S3H250 In200 * 1920 A185 15 TA 450SU140 95 - 140 14090 147 S3H250 In200 * 2300 A210 15 TA 450SU185 130 - 185 185110 177 S4H250 PR211-I

In2503000 A260 15 TA 450SU235 165 - 235 235

132 212 S5H400 PR211-I In320

3200 A300 15 TA 450SU235 165 - 235 235

160 260 S5H400 PR211-I In400

4000 AF 400 10 E 500DUTA450SU310

150 - 500220 - 310

400310

200 320 S5H400 PR211-I In400

4800 AF 460 10 E 500DUTA450SU400

150 - 500285 - 400

400400

250 410 S6H630 PR211-I In630

S6H630 PR211-I In630

63006300

AF 580AF 580

1010

E 500DU***E 800DU

TA900SU500

150 - 500250 - 800355 - 500

500580500

290 448 S6H630 PR211-I In630

S6H630 PR211-I In630

75607560

AF 750AF 750

1010

E 500DU***E 800DU

TA900SU500

150 - 500250 - 800355 - 500

500630500

315 500 S6H800 PR211-I In800

8000 AF 750 10 E 800DUTA900SU650

250 - 800465 - 650

750650

355 549 S6H800 PR211-I In800

9600 AF 750 10 E 800DUTA900SU650

250 - 800465 - 650

750650

MB4450HD2.1af* : Magnetic only adjustable release. ** : by pass contactor on the TOR during starting, same size as the line contactor *** Mounting kit between Contactor and Relay is not available. (x) : number of primary turns on CT

Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 19/09/2001 by Jean-Paul Guitton

Page 80: Type Selection Tables

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY440 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB4450SDHD2.1af

MCCB PR211+AFStar-delta starters with MCCB

440 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]45 75 S3H160 In125 * 1150 A95 A95 A50** 20 10 TA450SU60 40 - 6055 90 S3H160 In125 * 1400 A95 A95 A50** 20 10 TA450SU60 40 - 6075 120 S3H250 In200 * 2000 A145 A145 A50** 15 10 TA450SU80 55 - 8090 147 S3H250 In200 * 2400 A145 A145 A95 15 10 TA450SU105 70 - 105

110 177 S4H250 PR211-I In250

3000 A145 A145 A95 15 20 TA450SU140 95 - 140

132 212 S5H400 PR211-I In320

3200 A210 A210 A145 15 15 TA450SU140 95 - 140

160 260 S5H400 PR211-I In400

4000 A210 A210 A145 15 15 TA450SU185 130 - 185

200 320 S5H400 PR211-I In400

4800 A210 A210 A185 15 15 TA450SU235 165 - 235

250 410 S6H630 PR211-I In630

6300 AF400 AF400 A260 10 15 E500DU500

TA450SU310

150 - 500

220 - 310

290 448 S6H630 PR211-I In630

7560 AF400 AF400 A260 10 15 E500DU500

TA450SU310

150 - 500

220 - 310

315 500 S6H800 PR211-I In800

8000 AF400 AF400 A260 10 15 E500DU500

TA450SU310

150 - 500

220 - 310

355 549 S6H800 PR211-I In800

9600 AF580 AF580 A260 10 15 E500DU500

TA450SU400

150 - 500

285 - 400

MB4450SDHD2.1af* : Magnetic only adjustable release.** : using mounting kits, use star contactor size same as delta contactor size

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/09/2001 by Jean-Paul Guitton

Page 81: Type Selection Tables

STAR-DELTA STARTERS + INSUM440 V - 50 kA - Normal start - up, type : 2Note : MB4450SDIN2.1af

INSUM PR211+AF

Star-delta starters with MCCB440 V, 50 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type**

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [mm] [mm]45 75 S3H160 In125 * 950 A95 A95 A30 20 1055 90 S3H160 In125 * 1150 A95 A95 A40 20 1075 120 S3H250 In200 * 1600 A145 A145 A50 15 1090 147 S3H250 In200 * 1850 A145 A145 A75 15 10

110 177 S4H250 PR211-I In250 2500 A145 A145 A95 15 20132 212 S4H250 PR211-I In250 3000 A145 A145 A110 15 20160 260 S5H400 PR211-I In400 4000 A210 A210 A110 15 20200 320 S5H400 PR211-I In400 4800 A210 A210 A185 15 15250 410 S6H630 PR211-I In630 6300 AF400 AF400 A210 10 15290 448 S6H630 PR211-I In630 6300 AF400 AF400 A260 10 15315 500 S6H630 PR211-I In630 6300 AF400 AF400 A260 10 15355 549 S6H630 PR211-I In630 7560 AF400 AF400 A260 10 15

MB4450SDIN2.1af

* : Magnetic only adjustable release.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 31/08/2001 by Jean-Paul Guitton

Page 82: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY440 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP4450SDHD2.1af

MCCB PR212/MP+AF

Star-delta starters with MCCB440 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range** Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 75 S4H160 PR212-MP In100 50 - 100 800 A145 A145 A50 15 1055 90 S4H160 PR212-MP In160 80 - 160 960 A145 A145 A50 15 1075 120 S4H160 PR212-MP In160 80 - 160 1280 A145 A145 A50 15 1090 147 S4H250 PR212-MP In200 100 - 200 1600 A145 A145 A95 15 20110 177 S5H400 PR212-MP In320 160 - 320 1920 A210 A210 A95 15 20132 212 S5H400 PR212-MP In320 160 - 320 2240 A210 A210 A145 15 15160 260 S5H400 PR212-MP In320 160 - 320 2880 A210 A210 A145 15 15200 320 S6H800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15250 410 S6H800 PR212-MP In630 315 - 630 4410 AF400 AF400 A260 10 15290 448 S6H800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15315 500 S6H800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15355 549 S6H800 PR212-MP In630 315 - 630 5670 AF400 AF400 A260 10 15

MP4450SDHD2.1af * In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the motor is starting-up. ** The protection against overload (L function) of the MP release, must be set with class 30 starting class.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 83: Type Selection Tables

STAR-DELTA STARTER500 V - 50 kA - Normal start - up, type : 2Note : MB5050SD2.1af

mccb+AF contactorStar-delta starters with MCCB

500 V, 50 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors Thermal OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type*

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]5.5 9.1 S2X80 In11 145 A 30 A 30 A 9 10 10 TA25DU11** 7.5-117.5 12.2 S2X80 In16 210 A 30 A 30 A 9 10 10 TA25DU14** 10-1411 17.5 S2X80 In25 325 A 30 A 30 A 9 10 10 TA42DU19** 13-1915 23 S2X80 In32 415 A 50 A 50 A 12 10 10 TA75DU25** 18-25

18.5 29 S2X80 In42 540 A 50 A 50 A 16 10 10 TA75DU42** 29-4222 34 S2X80 In42 540 A 50 A 50 A 16 10 10 TA75DU42** 29-4230 45 S2X80 In52 680 A 63 A 63 A 26 10 10 TA75DU52** 36-5237 56 S2X80 In63 800 A 75 A 75 A 30 10 10 TA75DU63** 45-6345 67 S3L160 In125 * 900 A145 A145 A30 15 10 TA80DU52 36 - 5255 82 S3L160 In125 * 1050 A145 A145 A30 15 10 TA80DU52 36 - 5275 110 S3L160 In125 * 1400 A145 A145 A50 15 10 TA80DU80 60 - 8090 132 S3L250 In200 * 1700 A145 A145 A75 15 10 TA110DU90 65 - 90

110 158 S3L250 In200 * 2000 A145 A145 A95 15 20 TA200DU110 80 - 110132 192 S3L250 In200 * 2500 A145 A145 A95 15 20 TA200DU135 100 - 135160 230 S4L250 PR211-I In250 3000 A145 A145 A110 15 20 TA200DU150 110 - 150200 279 S5L400 PR211-I In400 4000 A210 A210 A145 15 15 TA200DU175 130 - 175250 335 S5L400 PR211-I In400 4800 A210 A210 A185 15 15 TA450DU235 165 - 235290 394 S6L630 PR211-I In630 5040 AF400 AF400 A210 10 15 E500DU500 150 - 500315 440 S6L630 PR211-I In630 6300 AF400 AF400 A210 10 15 E500DU500 150 - 500355 483 S6L630 PR211-I In630 6300 AF400 AF400 A260 10 15 E500DU500 150 - 500

MB5050SD2.1af *: Using mounting kits, use Star-contactor size same as Delta-contactor size. **: Connect the TOL between the MCCB and the Line-Delta node.

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/08/2001 by Jean-Paul Guitton

Page 84: Type Selection Tables

DIRECT-ON-LINE STARTERS500 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP5050HD2-1af

MCCB+PR212MP+AF-contDirect-on-line starters with MCCB

500 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type I1 range Current setting

PR 212 / MPrelease I3 *

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [A] [mm] Imax [A]30 45 S4L160 PR212-MP In100 50 - 100 600 A145 15 10037 56 S4L160 PR212-MP In100 50 - 100 600 A145 15 10045 67 S4L160 PR212-MP In100 50 - 100 700 A145 15 10055 82 S4L160 PR212-MP In100 50 - 100 800 A145 15 10075 110 S4L160 PR212-MP In160 80 - 160 1280 A145 15 14590 132 S4L160 PR212-MP In160 80 - 160 1440 A145 15 145

110 158 S4L250 PR212-MP In200 100 - 200 1800 A185 15 170132 192 S5L400 PR212-MP In320 160 - 320 2240 A210 15 210160 230 S5L400 PR212-MP In320 160 - 320 2560 A260 15 240200 279 S5L400 PR212-MP In320 160 - 320 2880 AF400** 10 320250 335 S6L800 PR212-MP In630 315 - 630 3780 AF400 10 400290 395 S6L800 PR212-MP In630 315 - 630 4410 AF460 10 460315 415 S6L800 PR212-MP In630 315 - 630 4410 AF460 10 460355 451 S6L800 PR212-MP In630 315 - 630 5040 AF580 10 580

MP5050HD2-1af

* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes whenthe motor is starting-up.** : A300 in case of Normal Starter.

NORMAL and HEAVY-DUTY START

For smaller motor powers, please refer to MMS tables or MCCB / MCB tables

Created 04/05/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 85: Type Selection Tables

DIRECT ON LINE STARTERS500 V - 50 kA - Normal start - up, type : 2Note : MB5050NS2.1af

MCCB+AF-contactorDirect-on-line starters with MCCB

500 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safetyclearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 O.88 S2X80 In1.6 21 A9 10 TA25DU1.0 0.63 - 1 10.55 1.2 S2X80 In1.6 21 A9 10 TA25DU1.4 1 - 1.4 1.40.75 1.5 S2X80 In2 26 A9 10 TA25DU1.8 1.3 - 1.8 1.81.1 2.2 S2X80 In3.2 42 A9 10 TA25DU2.4 1.7 - 2.4 2.41.5 2.8 S2X80 In3.2 42 A16 10 TA25DU3.1 2.2 - 3.1 3.1

S2X80 In3.2 42 A26 10 TA25DU4 2.8 - 4 3.22.2 4 S2X80 In5 65 A26 10 TA25DU5 3.5 - 5 53 5.2 S2X80 In6.5 84 A26 10 TA25DU6.5 4.5 - 6.5 6.54 6.9 S2X80 In8.5 110 A30 10 TA25DU8.5 6 - 8.5 8.5

5.5 9.1 S2X80 In11 145 A30 10 TA25DU11 7.5 - 11 117.5 12.2 S2X80 In16 210 A30 10 TA25DU14 10 - 14 1411 17.5 S2X80 In25 325 A30 10 TA25DU19 13 - 19 1915 23 S2X80 In32 415 A50 10 TA75DU25 18 - 25 25

S2X80 In32 415 A50 10 TA75DU32 22 - 32 3218,5 29 S2X80 In42 540 A50 10 TA75DU42 29 - 42 4222 34 S2X80 In42 540 A50 10 TA75DU42 29 - 42 4230 45 S2X80 In52 680 A63 10 TA75DU52 36 - 52 5237 56 S2X80 In63 800 A75 10 TA75DU63 45 - 63 6345 67 S3L160 In125 * 1050 A145 15 TA80DU80 60 - 80 8055 82 S3L160 In125 * 1250 A145 15 TA110DU90 65 - 90 90

S3L160 In125 * 1250 A145 15 TA110DU110 80 - 110 11075 110 S3L250 In200 * 1700 A145 15 TA200DU135 100 - 135 13590 132 S3L250 In200 * 2050 A145 15 TA200DU150 110 - 150 145110 158 S3L250 In200 * 2400 A185 15 TA200DU175 130 - 175 170132 192 S4L250 PR211-I In250 3000 A210 15 TA 450DU235 165 - 235 210160 230 S5L400 PR211-I In320 3840 A260 15 TA 450DU310 220 - 310 240200 279 S5L400 PR211-I In400 4800 A300 15 TA 450DU310 220 - 310 280250 335 S6L630 PR211-I In630 5040 AF 400 10 E 500DU 150 - 500 400290 394 S6L630 PR211-I In630

S6L630 PR211-I In630

6300

6300

AF 580

AF 580

10

10

E 500DU**

E 800DU

150 - 500

250 - 800

500

580

315 440 S6L630 PR211-I In630

S6L630 PR211-I In630

7560

7560

AF 580

AF 580

10

10

E 500DU**

E 800DU

150 - 500

250 - 800

500

580

355 483 S6L630 PR211-I In630

S6L630 PR211-I In630

7560

7560

AF 580

AF 580

10

10

E 500DU**

E 800DU

150 - 500

250 - 800

500

580

MB5050NS2.1af

* : Magnetic only adjustable release.** Mounting kit between Contactor and Relay is not available

Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 86: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM500 V - 50 kA - Normal start - up, type : 2Note : MB5050NSIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2500 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 O.88 S2X80 In1.6 21 A9 10 1.60.55 1.2 S2X80 In1.6 21 A9 10 1.60.75 1.5 S2X80 In2 26 A16 10 21.1 2.2 S2X80 In3.2 42 A26 10 3.21.5 2.8 S2X80 In3.2 42 A26 10 3.22.2 4 S2X80 In5 65 A26 10 53 5.2 S2X80 In6.5 84 A26 10 6.54 6.9 S2X80 In8.5 110 A30 10 8.5

5.5 9.1 S2X80 In11 145 A30 10 117.5 12.2 S2X80 In16 210 A50 10 1611 17.5 S2X80 In25 325 A50 10 2515 23 S2X80 In32 415 A50 10 32

18.5 29 S2X80 In42 540 A63 10 4222 34 S2X80 In42 540 A63 10 4230 45 S2X80 In52 680 A63 10 5237 56 S2X80 In63 800 A75 10 6345 67 S3L160 In125 * 1050 A145 15 12555 82 S3L160 In125 * 1250 A145 15 12575 110 S3L250 In200 * 1700 A145 15 14590 132 S3L250 In200 * 2050 A145 15 145

110 158 S3L250 In200 * 2400 A185 15 170132 192 S4L250 PR211-I In250 3000 A210 15 210160 230 S5L400 PR211-I In320 3840 A260 15 240200 279 S5L400 PR211-I In400 4800 A300 15 280250 335 S6L630 PR211-I In630 5040 AF400 10 400290 394 S6L630 PR211-I In630 6300 AF580 10 580315 440 S6L630 PR211-I In630 7560 AF580 10 580355 483 S6L630 PR211-I In630 7560 AF580 10 580

* : Magnetic only adjustable release MB5050NSIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 87: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM500 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB5050HDIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2500 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]0.37 O.88 S2X80 In1.6 21 A9 10 1.60.55 1.2 S2X80 In1.6 21 A9 10 1.60.75 1.5 S2X80 In2 26 A16 10 21.1 2.2 S2X80 In3.2 42 A26 10 3.21.5 2.8 S2X80 In3.2 42 A26 10 3.22.2 4 S2X80 In5 65 A26 10 53 5.2 S2X80 In6.5 84 A26 10 6.54 6.9 S2X80 In8.5 110 A30 10 8.5

5.5 9.1 S2X80 In11 145 A30 10 117.5 12.2 S2X80 In16 210 A50 10 1611 17.5 S2X80 In25 325 A50 10 2515 23 S2X80 In32 415 A50 10 32

18.5 29 S2X80 In42 540 A63 10 4222 34 S2X80 In42 540 A63 10 4230 45 S2X80 In52 680 A63 10 5237 56 S2X80 In63 800 A75 10 6345 67 S3L160 In125 * 1050 A145 15 12555 82 S3L160 In125 * 1250 A145 15 12575 110 S3L250 In200 * 1700 A145 15 14590 132 S3L250 In200 * 2050 A185 15 170

110 158 S3L250 In200 * 2400 A210 15 200132 192 S4L250 PR211-I In250 3000 A260 15 240160 230 S5L400 PR211-I In320 3840 A300 15 280200 279 S5L400 PR211-I In400 4800 AF400 10 400250 335 S6L630 PR211-I In630 5040 AF460 10 460290 394 S6L630 PR211-I In630 6300 AF750 10 630315 440 S6L630 PR211-I In630 7560 AF750 10 630355 483 S6L630 PR211-I In630 7560 AF750 10 630

* : Magnetic only adjustable release. MB5050HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 88: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY500 V - 50 kA - Normal start - up, type : 2Note : MP5050SD2.1af

PR212/MP+AF contactorsStar-delta starters with MCCB

500 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 67 S4L160 PR212-MP In100 50 - 100 700 A145 A145 A30 15 1055 82 S4L160 PR212-MP In100 50 - 100 800 A145 A145 A30 15 1075 110 S4L160 PR212-MP In160 80 - 160 1120 A145 A145 A50 15 1090 132 S4L160 PR212-MP In160 80 - 160 1280 A145 A145 A75 15 10110 158 S4L250 PR212-MP In200 100 - 200 1600 A145 A145 A95 15 20132 192 S5L400 PR212-MP In320 160 - 320 1920 A210 A210 A95 15 20160 230 S5L400 PR212-MP In320 160 - 320 2240 A210 A210 A110 15 20200 279 S5L400 PR212-MP In320 160 - 320 2560 A210 A210 A145 15 15250 335 S6L800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15290 394 S6L800 PR212-MP In630 315 - 630 3780 AF400 AF400 A210 10 15315 440 S6L800 PR212-MP In630 315 - 630 4410 AF400 AF400 A210 10 15355 483 S6L800 PR212-MP In630 315 - 630 4410 AF400 AF400 A260 10 15

MP5050SD2.1af * In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the motor is starting-up

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/08/2001 by Jean-Paul Guitton

Page 89: Type Selection Tables

DOL STARTERS500 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB5050HD2.1af

Isomax+AF+EOLDirect-on-line starters with MCCB

500 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safetyclearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 O.88 S2X80 In1.6 21 A9 10 TA25DU1.0** 0.63 - 1 10.55 1.2 S2X80 In1.6 21 A9 10 TA25DU1.4** 1 - 1.4 1.40.75 1.5 S2X80 In2 26 A9 10 TA25DU1.8** 1.3 - 1.8 1.81.1 2.2 S2X80 In3.2 42 A9 10 TA25DU2.4** 1.7 - 2.4 2.41.5 2.8 S2X80 In3.2 42 A16 10 TA25DU3.1** 2.2 - 3.1 3.1

S2X80 In3.2 42 A26 10 TA25DU4** 2.8 - 4 3.22.2 4 S2X80 In5 65 A26 10 TA25DU5** 3.5 - 5 53 5.2 S2X80 In6.5 84 A26 10 TA25DU6.5** 4.5 - 6.5 6.54 6.9 S2X80 In8.5 110 A30 10 TA25DU8.5** 6 - 8.5 8.5

5.5 9.1 S2X80 In11 145 A30 10 TA25DU11** 7.5 - 11 117.5 12.2 S2X80 In16 210 A30 10 TA 450SU60 (4) 10 - 15 1511 17.5 S2X80 In25 325 A30 10 TA 450SU60 (3) 13 - 20 2015 23 S2X80 In32 415 A50 10 TA 450SU60 (2) 20 - 30 30

18.5 29 S2X80 In42 540 A50 10 TA 450SU80 (2) 27.5 - 40 4022 34 S2X80 In42 540 A50 10 TA 450SU80 (2) 27.5 - 40 4030 45 S2X80 In52 680 A63 10 TA 450SU60 (1) 40 - 60 5237 56 S2X80 In63 800 A75 10 TA 450SU60 (1) 40 - 60 6045 67 S3L160 In125 * 1050 A145 15 TA 450SU80 (1) 55 - 80 8055 82 S3L160 In125 * 1250 A145 15 TA 450SU105 (1) 70 - 105 10575 110 S3L250 In200 * 1700 A145 15 TA 450SU140 (1) 95 - 140 14090 132 S3L250 In200 * 2050 A185 15 TA 450SU185 (1) 130 - 185 170110 158 S3L250 In200 * 2400 A210 15 TA 450SU185 (1) 130 - 185 185132 192 S4L250 PR211-I In250 3000 A260 15 TA 450SU235 (1) 165 - 235 235160 230 S5L400 PR211-I In320 3840 A300 15 TA 450SU310 (1) 220 - 310 280200 279 S5L400 PR211-I In400 4800 AF 400 10 E 500DU 150 - 500 400250 335 S6L630 PR211-I In630 5040 AF 460 10 E 500DU 150 - 500 460290 394 S6L630 PR211-I In630

S6L630 PR211-I In630

6300

6300

AF 750

AF 750

10

10

E 500DU***

E 800DU

150 - 500

250 - 800

500

630

315 440 S6L630 PR211-I In630

S6L630 PR211-I In630

7560

7560

AF 750

AF 750

10

10

E 500DU***

E 800DU

150 - 500

250 - 800

500

630

355 483 S6L630 PR211-I In630

S6L630 PR211-I In630

7560

7560

AF 750

AF 750

10

10

E 500DU***

E 800DU

150 - 500

250 - 800

500

630

MB5050HD2.1af

* : Magnetic only adjustable release. ** : provide by-pass contactor on the TOR during starting, same size as the line contactor*** Mounting kit between Contactor and Relay is not available. (x) : number of primary turns on the CT

Created 20/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/08/2001 by Jean-Paul Guitton

Page 90: Type Selection Tables

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY500 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB5050SDHD2.1af

MCCB PR211+AFStar-delta starters with MCCB

500 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors Thermal OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]45 67 S3L160 In125 * 1150 A145 A145 A50 15 10 TA450SU80** 27.5 - 4055 82 S3L160 In125 * 1250 A145 A145 A50 15 10 TA450SU60 40 - 6075 110 S3L250 In200 * 1800 A145 A145 A50 15 10 TA450SU80 55 - 8090 132 S3L250 In200 * 2200 A145 A145 A75 15 10 TA450SU105 70 - 105

110 158 S3L250 In200 * 2400 A145 A145 A95 15 20 TA450SU105 70 - 105132 192 S4L250 PR211-I In250 3000 A145 A145 A95 15 20 TA450SU140 95 - 140160 230 S5L400 PR211-I In320 3840 A210 A210 A145 15 15 TA450SU140 95 - 140200 279 S5L400 PR211-I In400 4000 A210 A210 A145 15 15 TA450SU185 130 - 185250 335 S6L630 PR211-I In630 5040 AF400 AF400 A185 10 15 E500DU 150 - 500290 394 S6L630 PR211-I In630 6300 AF400 AF400 A210 10 15 E500DU 150 - 500315 440 S6L630 PR211-I In630 6300 AF400 AF400 A260 10 15 E500DU 150 - 500355 483 S6L630 PR211-I In630 7560 AF400 AF400 A260 10 15 E500DU 150 - 500

MB5050SDHD2.1af

* : Magnetic only adjustable release.

** : 2 cable turns on CT.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 91: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY500 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP5050SDHD2.1af

MCCB PR212/MP+AFStar-delta starters with MCCB

500 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range** Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 67 S4L160 PR212-MP In100 50 - 100 700 A145 A145 A50 15 1055 82 S4L160 PR212-MP In100 50 - 100 900 A145 A145 A50 15 1075 110 S4L160 PR212-MP In160 80 - 160 1280 A145 A145 A50 15 1090 132 S4L160 PR212-MP In160 80 - 160 1440 A145 A145 A75 15 10

110 158 S4L250 PR212-MP In200 100 - 200 1800 A145 A145 A95 15 20132 192 S5L400 PR212-MP In320 160 - 320 2240 A210 A210 A95 15 20160 230 S5L400 PR212-MP In320 160 - 320 2560 A210 A210 A145 15 15200 279 S5L400 PR212-MP In320 160 - 320 2880 A210 A210 A145 15 15250 335 S6L800 PR212-MP In630 315 - 630 3780 AF400 AF400 A185 10 15290 394 S6L800 PR212-MP In630 315 - 630 4410 AF400 AF400 A210 10 15315 440 S6L800 PR212-MP In630 315 - 630 4410 AF400 AF400 A260 10 15355 483 S6L800 PR212-MP In630 315 - 630 5040 AF400 AF400 A260 10 15

MP5050SDHD2.1af

* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the motor is starting-up. ** The protection against overload (L function) of the MP release, must be set with class 30 starting class.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 92: Type Selection Tables

DOL STARTERS690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB6950HD2.1af

Isomax+AF+EOLDirect-on-line starters with MCCB

690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactor Overload Relay Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type N° of primary turns on CT

Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 0.6 S2X80 In1 13 A9 10 TA25DU0.63*** 0.4 - 0.63 0.630.55 0.9 S2X80 In1 13 A9 10 TA25DU1*** 0.63 - 1 10.75 1.1 S2X80 In1.6 21 A9 10 TA25DU1.4*** 1 - 1.4 1.41.1 1.6 S2X80 In2 26 A9 10 TA25DU1.8*** 1.3 - 1.8 1.81.5 2 S2X80 In2.5 33 A16 10 TA25DU2.4*** 1.7 - 2.4 2.42.2 2.9 S2X80 In4 52 A26 10 TA25DU4*** (a) 2.8 - 4 43 3.8 S2X80 In5 65 A26 10 TA25DU5*** (a) 3.5 - 5 54 5 S2X80 In6.5 84 A30 10 TA25DU6.5***(a) 4.5 - 6.5 6.5

5.5 6.7 S3X125 In25 * 110 A95 20 TA 450SU60 7** 5.7 - 8.6 8.67.5 8.8 S3X125 In25 * 140 A95 20 TA 450SU60 5** 8 - 12 1211 13 S3X125 In25 * 200 A95 20 TA 450SU60 4** 10 - 15 1515 18 S3X125 In25 * 280 A95 20 TA 450SU60 3** 13 - 20 20

18.5 21 S3X125 In50 * 320 A145 15 TA 450SU80 3 18 - 27 2722 25 S3X125 In50 * 380 A145 15 TA 450SU60 2 20 - 30 3030 33 S3X125 In50 * 500 A145 15 TA 450SU80 2 27.5 - 40 4037 41 S3X125 In100 * 620 A145 15 TA 450SU60 1 40 - 60 6045 49 S3X125 In100 * 740 A145 15 TA 450SU60 1 40 - 60 6055 60 S3X125 In100 * 920 A145 15 TA 450SU80 1 55 - 80 8075 80 S3X125 In125 * 1250 A145 15 TA 450SU105 1 70 - 105 10590 95 S3X125 In125 * 1450 A145 15 TA 450SU105 1 70 - 105 105

110 115 S3X200 In200 * 1750 A185 15 TA 450SU140 1 95 - 140 140132 139 S3X200 In200 * 2100 A210 15 TA 450SU185 1 130 - 185 185160 167 S4X250 PR211-I

In2502500 A210 15 TA 450SU185 1 130 - 185 185

200 202 S4X250 PR211-I In250

3000 A260 15 TA 450SU235 1 165 - 235 220

250 242 S6X400 PR211-I In320

3840 AF 400 10 E 500DUTA450SU310

1 150 - 500220 - 310

320310

290 301 S6X400 PR211-I In400

4800 AF 400 10 E 500DUTA450SU310

1 150 - 500220 - 310

350310

315 313 S6X400 PR211-I In400

4800 AF 460 10 E 500DUTA450SU400

1 150 - 500285 - 400

400400

355 370 S6X630 PR211-I In630

S6X630 PR211-I In630

63006300

AF 580AF 580

1010

E 500DU (X)E 800DU

TA450SU400

11

150 - 500250 - 800285 - 400

500500400

400 420 S6X630 PR211-I In630

S6X630 PR211-I In630

63006300

AF 580AF 580

1010

E 500DU (X)E 800DU

TA900SU500

11

150 - 500250 - 800355 - 500

500500500

450 470 S6X630 PR211-I In630

S6X630 PR211-I In630

75607560

AF 750AF 750

1010

E 500DU (X)E 800DU

TA900SU500

11

150 - 500250 - 800355 - 500

500630500

500 500 S6X630 PR211-I In630

7560 AF 750 10 E 800DUTA900SU650

1 250 - 800465 - 650

630650

MB6950HD2.1af* : Magnetic only adjustable release. ** : Cable cross section 4.0 mm2 *** : Use by-pass contactor during motor start-up : A9 < 1.1kW / A16 < 4kW (X) Mounting kit between Contactor and Relay is not available.(a) : type 1 coordination, type 2 by the relevant MCB (MO325) table

Page 93: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM690 V - 50 kA - Normal start - up, type : 2Note : MB6950NSIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2690 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]5.5 6.7 S3X125 In25* 110 A95 20 257.5 8.8 S3X125 In25 * 140 A95 20 2511 13 S3X125 In25 * 200 A95 20 2515 18 S3X125 In25 * 280 A95 20 25

18.5 21 S3X125 In50 * 320 A145 15 5022 25 S3X125 In50 * 380 A145 15 5030 33 S3X125 In50 * 500 A145 15 5037 41 S3X125 In100 * 620 A145 15 10045 49 S3X125 In100 * 740 A145 15 10055 60 S3X125 In100 * 920 A145 15 10075 80 S3X125 In125 * 1250 A145 15 12090 95 S3X125 In125 * 1450 A145 15 120110 115 S3X200 In200 * 1750 A145 15 120132 139 S3X200 In200 * 2100 A185 15 170160 167 S4X250 PR211-I In250 2500 A185 15 170200 202 S4X250 PR211-I In250 3000 A210 15 210250 242 S6X400 PR211-I In320 3840 AF400 10 320290 301 S6X400 PR211-I In400 4800 AF400 10 350315 313 S6X400 PR211-I In400 4800 AF400 10 350355 370 S6X630 PR211-I In630 6300 AF580 10 500400 420 S6X630 PR211-I In630 6300 AF580 10 500450 470 S6X630 PR211-I In630 7560 AF580 10 500500 500 S6X630 PR211-I In630 7560 AF750 10 630

* : Magnetic only adjustable release. **: From 0.37kW up to 15kW, the cable section must be equal to 4.0 mm2. MB6950NSIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 94: Type Selection Tables

DIRECT ON LINE STARTERS + INSUM690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB6950HDIN2.1af

MCCB-INSUM

Direct-on-line starters with MCCB + INSUM2690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [mm] Imax [A]5.5 6.7 S3X125 In25* 110 A95 20 257.5 8.8 S3X125 In25 * 140 A95 20 2511 13 S3X125 In25 * 200 A95 20 2515 18 S3X125 In25 * 280 A95 20 25

18.5 21 S3X125 In50 * 320 A145 15 5022 25 S3X125 In50 * 380 A145 15 5030 33 S3X125 In50 * 500 A145 15 5037 41 S3X125 In100 * 620 A145 15 10045 49 S3X125 In100 * 740 A145 15 10055 60 S3X125 In100 * 920 A145 15 10075 80 S3X125 In125 * 1250 A145 15 12090 95 S3X125 In125 * 1450 A145 15 120110 115 S3X200 In200 * 1750 A185 15 170132 139 S3X200 In200 * 2100 A210 15 200160 167 S4X250 PR211-I In250 2500 A210 15 210200 202 S4X250 PR211-I In250 3000 A260 15 220250 242 S6X400 PR211-I In320 3840 AF400 10 320290 301 S6X400 PR211-I In400 4800 AF400 10 350315 313 S6X400 PR211-I In400 4800 AF460 10 400355 370 S6X630 PR211-I In630 6300 AF580 10 500400 420 S6X630 PR211-I In630 6300 AF580 10 500450 470 S6X630 PR211-I In630 7560 AF750 10 630500 500 S6X630 PR211-I In630 7560 AF750 10 630

* : Magnetic only adjustable release. **: From 0.37kW up to 15kW, the cable section must be equal to 4.0 mm2. MB6950HDIN2.1af

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 95: Type Selection Tables

STAR DELTA STARTERS690 V - 50 kA - Normal start - up, type : 2Note : MB6950SD2.1af

mccb+AF contStar-delta starters with MCCB

690 V, 50 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactortype***

KORC type

turnsonC T

TOLtype

Current setting range

Pe [kW] Ie [A] [A] 4 L n [A]5.5 6.7** S3X125 In25 * 110 A 95 A 95 A 26 185R/4 13 TA25DU2.4**** 6-8.57.5 8.8** S3X125 In25 * 140 A 95 A 95 A 26 185R/4 10 TA25DU2.4**** 7.9-11.111 13** S3X125 In25 * 200 A 95 A 95 A 26 185R/4 7 TA25DU2.4**** 11.2-15.915 18** S3X125 In25 * 280 A 95 A 95 A 26 185R/4 7 TA25DU3.1**** 15.2-20.5

18.5 21 S3X125 In50 * 320 A 145 A 145 A 30 185R/4 6 TA25DU3.1**** 17.7-23.922 25 S3X125 In50 * 380 A 145 A 145 A 30 185R/4 6 TA25DU4**** 21.6-30.830 33 S3X125 In50 * 500 A 145 A 145 A 30 185R/4 6 TA25DU5**** 27-38.537 41 S3X125 In100 * 620 A 145 A 145 A 30 185R/4 4 TA25DU4**** 32.4-46.345 49 S3X125 In125 * 620 A145 A145 A30 - - TA75DU32 22 - 3255 60 S3X125 In125 * 750 A145 A145 A40 - - TA75DU42 29 - 4275 80 S3X125 In125 * 1000 A145 A145 A50 - - TA75DU52 36 - 5290 95 S3X125 In125 * 1200 A145 A145 A75 - - TA75DU63 45 - 63

110 115 S3X125 In125 * 1440 A145 A145 A75 - - TA75DU80 60 - 80132 139 S3X200 In200 * 1750 A145 A145 A95 - - TA200DU110 80 - 110160 167 S3X200 In200 * 2100 A145 A145 A110 - - TA200DU110 80 - 110200 202 S4X250 PR211-I

In2502550 A185 A185 A110 - - TA200DU135 100 - 135

250 242 S6X400 PR211-I In400

3200 AF400 AF400 A145 - - E500DU500TA200DU150

150 - 500110 - 150

290 301 S6X400 PR211-I In400

4000 AF400 AF400 A145 - - E500DU500TA200DU200

150 - 500150 - 200

315 313 S6X400 PR211-I In400

4000 AF400 AF400 A185 - - E500DU500TA200DU200

150 - 500150 - 200

355 370 S6X630 PR211-I In630

5040 AF400 AF400 A210 - - E500DU500TA450DU235

150 - 500165 - 235

400 420 S6X630 PR211-I In630

6300 AF460 AF460 A210 - - E500DU500TA450DU310

150 - 500220 - 310

450 470 S6X630 PR211-I In630

6300 AF460 AF460 A260 - - E500DU500TA450DU310

150 - 500220 - 310

500 500 S6X630 PR211-I In630

6300 AF460 AF460 A260 - - E500DU500TA450DU310

150 - 500220 - 310

MB6950SD2.1af

* : Magnetic only adjustable release. ** : Cable section equal to 4 mm2 ***: Using mounting kits, use Star-contactor size same as Delta-contactor size.****: Connect the TOL between the MCCB and the Line-Delta node.

Created 29/06/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/09/2001 by Jean-Paul Guitton

Page 96: Type Selection Tables

DIRECT ON LINE STARTERS690 V - 50 kA - Normal start - up, type : 2Note : MB6950NS2.1af

MCCB+AF-contactorDirect-on-line starters with MCCB

690 V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor KORC(Current transfo)

Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type N° ofprimary turns on CT

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 0.6 S2X80 In1 13 A9 10 TA25DU0.63 0.4 - 0.63 0.630.55 0.9 S2X80 In1 13 A9 10 TA25DU1 0.63 - 1 10.75 1.1 S2X80 In1.6 21 A9 10 TA25DU1.4 1 - 1.4 1.41.1 1.6 S2X80 In2 26 A9 10 TA25DU1.8 1.3 - 1.8 1.81.5 2 S2X80 In2.5 33 A16 10 TA25DU2.4 1,7 - 2.4 2.42.2 2.9 S2X80 In4 52 A26 10 TA25DU4 ** 2.8 - 4 43 3.8 S2X80 In5 65 A26 10 TA25DU5 ** 3.5 - 5 54 5 S2X80 In6.5 84 A30 10 TA25DU6.5 ** 4.5 - 6,5 6.5

5.5 6.7 S3X125 In25* 110 A95 20 4L185R/4 13*** TA25DU2.4 6 - 8.5 8.57.5 8.8 S3X125 In25 * 140 A95 20 4L185R/4 10*** TA25DU2.4 7.9 - 11.1 11.111 13 S3X125 In25 * 200 A95 20 4L185R/4 7*** TA25DU2.4 11.2 - 15.9 15.915 18 S3X125 In25 * 280 A95 20 4L185R/4 7*** TA25DU3.1 15.2 - 20.5 20.5

18.5 21 S3X125 In50 * 320 A145 15 4L185R/4 6 TA25DU3.1 17.7 - 23.9 23.922 25 S3X125 In50 * 380 A145 15 4L185R/4 6 TA25DU4 21.6 - 30.8 30.830 33 S3X125 In50 * 500 A145 15 4L185R/4 6 TA25DU5 27 - 38.5 38.537 41 S3X125 In100 * 620 A145 15 4L185R/4 4 TA25DU4 32.4 - 46.3 46.345 49 S3X125 In100 * 740 A145 15 4L185R/4 4 TA25DU5 40.5 - 57.8 57.855 60 S3X125 In100 * 920 A145 15 4L185R/4 3 TA25DU5 54 - 77.1 77.175 80 S3X125 In125 * 1250 A145 15 4L185R/4 2 TA25DU4 64.8 - 92.5 92.590 95 S3X125 In125 * 1450 A145 15 4L185R/4 2 TA25DU5 81 - 115.6 115.6110 115 S3X200 In200 * 1750 A145 15 4L235R/4 2 TA25DU5 103 - 147 120132 139 S3X200 In200 * 2100 A185 15 TA 450DU185 130 - 185 170160 167 S4X250 PR211-I In250 2500 A185 15 TA 450DU185 130 - 185 170200 202 S4X250 PR211-I In250 3000 A210 15 TA 450DU235 165 - 235 210250 242 S6X400 PR211-I In320 3840 AF 400 10 E 500DU

TA450DU310150 - 500220 - 310

320310

290 301 S6X400 PR211-I In400 4800 AF 400 10 E 500DUTA450DU310

150 - 500220 - 310

350310

315 313 S6X400 PR211-I In400 4800 AF 400 10 E 500DUTA450DU400

150 - 500285 - 400

350400

355 370 S6X630 PR211-I In630S6X630 PR211-I In630

63006300

AF 580AF 580

1010

E 500DU (X)E 800DU

TA450DU400

150 - 500250 - 800285 - 400

500500400

400 420 S6X630 PR211-I In630S6X630 PR211-I In630

63006300

AF 580AF 580

1010

E 500DU (X)E 800DU

TA900DU500

150 - 500250 - 800355 - 500

500500500

450 470 S6X630 PR211-I In630S6X630 PR211-I In630

75607560

AF 580AF 580

1010

E 500DU (X)E 800DU

TA900DU500

150 - 500250 - 800355 - 500

500500500

500 500 S6X630 PR211-I In630 7560 AF 750 10 E 800DUTA900DU650

250 - 800465 - 650

630650

MB6950NS2.1af * : Magnetic only adjustable release. ** : Type 1 coordination, type 2 by the relevant MCB (MO325) table***: Cable section equal to 4.0 mm2.(X) Mounting kit between Contactor and Relay is not available.

Created 07/09/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/09/2001 by Jean-Paul Guitton

Page 97: Type Selection Tables

DIRECT-ON-LINE STARTERS690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP6950HD2-1af

MCCB+PR212MP+AF-contDirect-on-line starters with MCCB

690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker Contactor GroupRatedOutput

RatedCurrent

Type I1 range Current setting

PR 212 / MPrelease I3 *

Type Safety clearance

Max.Current

Pe [kW] Ie [A] [A] [A] [mm] Imax [A]45 49 S4X250 PR212-MP In100 50 - 100 600 A145 15 10055 60 S4X250 PR212-MP In100 50 - 100 600 A145 15 10075 80 S4X250 PR212-MP In100 50 - 100 900 A145 15 10090 95 S4X250 PR212-MP In160 80 - 160 1120 A145 15 120

110 115 S4X250 PR212-MP In160 80 - 160 1280 A145 15 120132 139 S4X250 PR212-MP In160 80 - 160 1440 A185 15 160160 167 S4X250 PR212-MP In200 100 - 200 1800 A185 15 170200 202 S6X400 PR212-MP In320 160 - 320 2240 AF400 10 320250 242 S6X400 PR212-MP In320 160 - 320 2560 AF400 10 320290 301 S6X400 PR212-MP In320 160 - 320 2880 AF400 10 320315 313 S6X630 PR212-MP In400 200 - 400 3200 AF400 10 350355 370 S6X630 PR212-MP In400 200 - 400 3600 AF460 10 400400 420 S6X630 PR212-MP In630 315 - 630 4410 AF580 10 500450 470 S6X630 PR212-MP In630 315 - 630 5040 AF580 10 500500 500 S6X630 PR212-MP In630 315 - 630 5040 AF750 10 650

MP6950HD2-1af

* In order to avoid tripping during motor start-up transient, the PR212/MP release recognizes whenthe motor is starting-up.X To be defined by further tests.

NORMAL and HEAVY-DUTY START

For smaller motor powers, please refer to MMS tables or MCCB / MCB tables

Created 07/05/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 10/07/2001 by Jean-Paul Guitton

Page 98: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY690 V - 50 kA - Normal start - up, type : 2Note : MP6950SD2.1af

PR212/MP+AF contactorStar-delta starters with MCCB

690V, 50 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 49 S4X250 PR212-MP In100 50 - 100 600 A145 A145 A30 15 1055 60 S4X250 PR212-MP In100 50 - 100 600 A145 A145 A40 15 1075 80 S4X250 PR212-MP In100 50 - 100 800 A145 A145 A50 15 1090 95 S4X250 PR212-MP In160 80 - 160 960 A145 A145 A75 15 10110 115 S4X250 PR212-MP In160 80 - 160 1120 A145 A145 A75 15 10132 139 S4X250 PR212-MP In160 80 - 160 1280 A145 A145 A95 15 20160 167 S4X250 PR212-MP In200 100 - 200 1600 A145 A145 A110 15 20200 202 S6X400 PR212-MP In320 160 - 320 1920 AF400 AF400 A110 10 20250 242 S6X400 PR212-MP In320 160 - 320 2240 AF400 AF400 A145 10 15290 301 S6X630 PR212-MP In400 200 - 400 2800 AF400 AF400 A145 10 15315 313 S6X630 PR212-MP In400 200 - 400 3200 AF400 AF400 A185 10 15355 370 S6X630 PR212-MP In630 315 - 630 3780 AF400 AF400 A210 10 15400 420 S6X630 PR212-MP In630 315 - 630 4410 AF460 AF460 A210 10 15450 470 S6X630 PR212-MP In630 315 - 630 4410 AF460 AF460 A260 10 15500 500 S6X630 PR212-MP In630 315 - 630 5040 AF460 AF460 A260 10 15

MP6950SD2.1af

* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the motor is starting-upIn case of smaller motor powers, please refer to MMS tables.

Created 27/07/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 24/08/2001 by Jean-Paul Guitton

Page 99: Type Selection Tables

STAR-DELTA STARTERS WITH SEPARATE OVERLOAD RELAY690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MB6950SDHD2.1af

MCCB PR211+AFStar-delta starters with MCCB

690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors OverloadRelay

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Type Current setting range

Pe [kW] Ie [A] [A] [mm] [mm] [A]45 49 S3X125 In125 * 750 A145 A145 A30 15 10 TA450SU60** 20 - 3055 60 S3X125 In125 * 1000 A145 A145 A40 15 10 TA450SU80** 27.5 - 4075 80 S3X125 In125 * 1250 A145 A145 A50 15 10 TA450SU60 40 - 6090 95 S3X125 In125 * 1500 A145 A145 A75 15 10 TA450SU60 40 - 60

110 115 S3X200 In200 * 1800 A145 A145 A75 15 10 TA450SU80 55 - 80132 139 S3X200 In200 * 2200 A145 A145 A95 15 20 TA450SU105 70 - 105160 167 S4X250 PR211-I In250 2500 A145 A145 A110 15 20 TA450SU105 70 - 105200 202 S4X250 PR211-I In250 3000 A185 A185 A145 15 15 TA450SU140 95 - 140250 242 S6X400 PR211-I In320 3840 AF400 AF400 A145 10 15 E500DU500

TA450SU185

150 - 500

130 - 185

290 301 S6X400 PR211-I In400 4800 AF400 AF400 A185 10 15 E500DU500

TA450SU185

150 - 500

130 - 185

315 313 S6X400 PR211-I In400 4800 AF400 AF400 A185 10 15 E500DU500

TA450SU235

150 - 500

165 - 235

355 370 S6X630 PR211-I In630 6300 AF400 AF400 A210 10 15 E500DU500

TA450SU235

150 - 500

165 - 235

400 420 S6X630 PR211-I In630 6300 AF460 AF460 A260 10 15 E500DU500

TA450SU310

150 - 500

220 - 310

450 470 S6X630 PR211-I In630 7560 AF580 AF580 A260 10 15 E800DU500

TA450SU310

250 - 800

220 - 310

500 500 S6X630 PR211-I In630 7560 AF580 AF580 AF400 10 10 E800DU800

TA450SU310

250 - 800

220 - 310

MB6950SDHD2.1af

* : Magnetic only adjustable release.** : 2 cable turns on CT

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Page 100: Type Selection Tables

STAR-DELTA STARTERS + INSUM690 V - 50 kA - Normal start - up, type : 2Note : MB6950SDIN2.1af

INSUM PR211+AF

Star-delta starters with MCCB690 V, 50 kA, Normal start - up, type 2

Motor Moulded CaseCircuit-Breaker

Contactors

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Linecontactor

type

Deltacontactor

type

Starcontactor

type**

Safety clearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [mm] [mm]45 49 S3X125 In125 * 620 A145 A145 A30 15 1055 60 S3X125 In125 * 750 A145 A145 A40 15 1075 80 S3X125 In125 * 1000 A145 A145 A50 15 1090 95 S3X125 In125 * 1200 A145 A145 A75 15 10

110 115 S3X125 In125 * 1440 A145 A145 A75 15 10132 139 S3X200 In200 * 1750 A145 A145 A95 15 20160 167 S3X200 In200 * 2100 A145 A145 A110 15 20200 202 S4X250 PR211-I In250 2550 A185 A185 A110 15 20250 242 S6X400 PR211-I In400 3200 AF400 AF400 A145 10 15290 301 S6X400 PR211-I In400 4000 AF400 AF400 A145 10 15315 313 S6X400 PR211-I In400 4000 AF400 AF400 A185 10 15355 370 S6X630 PR211-I In630 5040 AF400 AF400 A210 10 15400 420 S6X630 PR211-I In630 6300 AF460 AF460 A210 10 15450 470 S6X630 PR211-I In630 6300 AF460 AF460 A260 10 15500 500 S6X630 PR211-I In630 6300 AF460 AF460 A260 10 15

MB6950SDIN2.1af

* : Magnetic only adjustable release.

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 31/08/2001 by Jean-Paul Guitton

Page 101: Type Selection Tables

STAR-DELTA STARTERS WITHOUT SEPARATE OVERLOAD RELAY690 V - 50 kA - Long starting (heavy duty) start - up, type : 2Note : MP6950SDHD2.1af

MCCB PR212/MP+AF

Star-delta starters with MCCB690 V, 50 kA, Long starting (heavy duty) start - up, type 2

Motor Moulded Case Circuit-Breaker ContactorsRatedOutput

RatedCurrent

Type I1 range** Currentsetting

PR212 / MP

release I3 *

Linecontactor

type

Deltacontactor

type

Starcontactor

type

SafetyclearanceLine-Deltacontactor

Safetyclearance

Starcontactor

Pe [kW] Ie [A] [A] [A] [mm] [mm]45 49 S4X250 PR212-MP In100 50 - 100 600 A145 A145 A30 15 1055 60 S4X250 PR212-MP In100 50 - 100 700 A145 A145 A40 15 1075 80 S4X250 PR212-MP In100 50 - 100 900 A145 A145 A50 15 1090 95 S4X250 PR212-MP In160 80 - 160 1120 A145 A145 A75 15 10

110 115 S4X250 PR212-MP In160 80 - 160 1280 A145 A145 A75 15 10132 139 S4X250 PR212-MP In160 80 - 160 1440 A145 A145 A95 15 20160 167 S4X250 PR212-MP In200 100 - 200 1800 A145 A145 A110 15 20200 202 S6X400 PR212-MP In320 160 - 320 2240 AF400 AF400 A145 10 15250 242 S6X400 PR212-MP In320 160 - 320 2560 AF400 AF400 A145 10 15290 301 S6X630 PR212-MP In400 200 - 400 3200 AF400 AF400 A185 10 15315 313 S6X630 PR212-MP In400 200 - 400 3200 AF400 AF400 A185 10 15355 370 S6X630 PR212-MP In630 315 - 630 3780 AF400 AF400 A210 10 15400 420 S6X630 PR212-MP In630 315 - 630 4410 AF460 AF460 A260 10 15450 470 S6X630 PR212-MP In630 315 - 630 5040 AF460 AF460 A260 10 15500 500 S6X630 PR212-MP In630 315 - 630 5040 AF460 AF460 AF400 10 10

MP6950SDHD2.1af

* In order to avoid untimely tripping during motor starting-up transient, the PR212/MP recognizes when the motor is starting-up. ** The protection against overload (L function) of the MP release, must be set with class 30 starting class. In case of smaller motor powers, please refer to MMS tables

Created 28/08/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 30/08/2001 by Jean-Paul Guitton

Page 102: Type Selection Tables

MMS

UeV

IqkA

Coor.type

Startingtype

SCPDtype

SizekW

Table Last Update

400 16 1 Normal MMS 0.06 ... 7.5 MM4016NS1.1 22/11/012 Normal MMS 0.06 ... 7.5 MM4016NS2.1 22/11/01

400 50 1 Normal MMS 0.37 ... 55 MM4050NS1.1 04/02/00

212

NormalNormalNormal

MMS/DLAMMSMMS

0.37 ... 110.12 ... 220.12 ... 22

MM4050NS2.1aMM4050NS1.1KMM4050NS2.1K

04/02/0023/10/0023/10/00

1 SD MMS 1.1 ... 55 MM4050SD1.1 04/02/00 2 SD MMS 1.1 ... 55 MM4050SD2.1 04/02/00 1 Normal MMS/DLA 0.37 ... 11 MM4050NS1.1a 04/02/00

2 Normal MMS 0.06 ... 55 MM4050NS2.1 04/02/00100 1 Normal MMS 0.06 ... 18.5 MM4000NS2.1 04/02/00

440 25 2 Normal MMS 0.06 ... 22 MM4430NS2.1 04/02/0050 2 Normal MMS 0.06 ... 22 MM4450NS2.1 04/02/00

100 2 Normal MMS 0.06 ... 22 MM4400NS2.1 04/02/00500 25

2512

NormalNormal

MMSMMS

0.12 .. 220.12 .. 22

MM5025NS1.1KMM5025NS2.1K

25/02/0025/02/00

50 2 Normal MMS 0.06 ... 22 MM5050NS2.1 04/02/00100 2 Normal MMS 0.06 ... 22 MM5000NS2.1 04/02/00

Glossary SCPD Short Circuit Protection Device Prolim Current limiterNS Normal Start DLA MS325 + A-ContactorsSD Star Delta MMS Manual Motor Starter

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 22/11/2001 by Jean-Paul Guitton

Page 103: Type Selection Tables

Direct on line starters400 V - 16 kA - Normal start - up, type : 1Note : MM4016NS1.1

MS116

Manual Motors Starter MS116400 V, 16 kA, Normal start - up, type 1

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 MS116-0.25 3.0 A9/B6 40/10 - 0.16 - 0.25 0.250.09 0.33 MS116-0.4 4.8 A9/B6 40/10 - 0.25 - 0.4 0.40.12 0.42 MS116-0.63 7.56 A9/B6 40/10 - 0.40 - 0.63 0.630.18 0.72 MS116-1 12 A9/B6 40/10 - 0.63 - 1 10.25 0.83 MS116-1 12 A9/B6 40/10 - 0.63 - 1 10.37 1.2 MS116-1.6 19.2 A9/B6 40/10 - 1 - 1.6 1.60.55 1.5 MS116-1.6 19.2 A9/B6 40/10 - 1 - 1.6 1.60.75 2 MS116-2.5 30 A9/B6 40/10 - 1.6 - 2.5 2.51.1 2.6 MS116-4 48 A9/B6 40/10 - 2.5 - 4 41.5 3.5 MS116-4 48 A9/B6 40/10 - 2.5 - 4 42.2 5 MS116-6.3 75.6 A9/B6 40/10 - 4 - 6.3 6.33 6.6 MS116-10 120 A9/B6 40/10 - 6.3 - 10 104 8.5 MS116-10 120 A9/B6 40/10 - 6.3 - 10 10

5.5 11.5 MS116-16 192 A12 40/10 - 10 - 16 127.5 15.5 MS116-16 192 A16 40/10 - 10 - 16 16

MM4016NS1.1

Safety perimeter : 40/10 x 15 x 5 means : 40mm above MS xxx, 10mm below the contactor15mm in front of each component, 5mm on each side

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 22/11/2001 by Jean-Paul Guitton

Page 104: Type Selection Tables

Direct on line starters400 V - 16 kA - Normal start - up, type : 2Note : MM4016NS2.1

MS116Manual Motors Starter MS116

400 V, 16 kA, Normal start - up, type 2

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 MS116-0.25 3.0 A9/B6 40/10 - 0.16 - 0.25 0.250.09 0.33 MS116-0.4 4.8 A9/B6 40/10 - 0.25 - 0.4 0.40.12 0.42 MS116-0.63 7.56 A9/B6 40/10 - 0.40 - 0.63 0.630.18 0.72 MS116-1 12 A9/B6 40/10 - 0.63 - 1 10.25 0.83 MS116-1 12 A9/B6 40/10 - 0.63 - 1 10.37 1.2 MS116-1.6 19.2 A9/B6 40/10 - 1 - 1.6 1.60.55 1.5 MS116-1.6 19.2 A9/B6 40/10 - 1 - 1.6 1.60.75 2 MS116-2.5 30 A9/BB6 40/10 - 1.6 - 2.5 2.51.1 2.6 MS116-4 48 A12/B6 40/10 - 2.5 - 4 41.5 3.5 MS116-4 48 A12/B6 40/10 - 2.5 - 4 42.2 5 MS116-6.3 75.6 A16 40/10 - 4 - 6.3 6.33 6.6 MS116-10 120 A16 40/10 - 6.3 - 10 104 8.5 MS116-10 120 A16 40/10 - 6.3 - 10 10

5.5 11.5 MS116-16 192 ** - 10 - 16 127.5 15.5 MS116-16 192 ** - 10 - 16 16

MM4016NS2.1

Safety perimeter : 40/10 x 15 x 5 means : 40mm above MS xxx, 10mm below the contactor15mm in front of each component, 5mm on each side

** : under consideration

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 22/11/2001 by Jean-Paul Guitton

Page 105: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 1Note : MM4050NS1.1

MS325/495Manual Motors Starter MS325

400 V, 50 kA, Normal start - up, type 1

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type<br>

Safety clearance

Type<br>

Current setting range

Max. Current

Pe [kW] Ie [A] [A]r> [mm] [A] Imax [A]0.37 1.2 MS325-1.6 18.4 A9 25/5x15x5 - 1 - 1.6 1.60.55 1.5 MS325-1.6 18.4 A9 25/5x15x5 - 1 - 1.6 1.60.75 2 MS325-2.5 29 A9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.6 MS325-4 48 A9 25/5x15x5 - 2.5 - 4 41.5 3.5 MS325-4 48 A9 25/5x15x5 - 2.5 - 4 42.2 5 MS325-6.3 94.5 A9 25/5x15x5 - 4 - 6.3 6.33 6.6 MS325-9 135 A9 25/5x15x5 - 6.3 - 9 94 8,5 MS325-9 135 A9 25/5x15x5 - 6.3 - 9 9

5.5 11.5 MS325-12.5 187.5 A12 25/5x15x5 - 9 - 12.5 127.5 15.5 MS325-16

MS450-20

240

240

A16

A16

25/5x15x5

50/5x15x10

-

-

12.5 - 16

14 - 20

16

16

9 18.3 MS325-20 300 A26 25/5x15x5 - 16 - 20 2011 22 MS325-25

MS450-25

375

300

A26

A26

25/5x15x5

50/5x15x10

-

-

20 - 25

18 - 25

25

25

15 30 MS450-32 384 A30 50/5x15x10 - 22 - 32 3018.5 37 MS450-40 480 A40 50/5x15x10 - 28 - 40 4022 45 MS450-50 540 A50 50/5x15x10 - 40 - 50 5030 60 MS495-63 756 A63 70/5x15x10 - 45 - 63 6037 72 MS495-75 900 A75 70/5x15x10 - 57 - 75 7245 85 MS495-90 1080 A95 70/5x15x10 - 70 - 90 9055 98 MS495-100 1200 A110 70/5x15x10 - 80 - 100 100

MM4050NS1.1

Safety perimeter : 25/5x15x5 means : 25mm above MS325, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 106: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 2Note : MM4050NS2.1

MS325/DLAManual Motors Starter MS325

400 V, 50 kA, Normal start - up, type 2

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 MS325-1.6 18.4 DLA9 25/5x15x5 - 1 - 1.6 1.60.55 1.5 MS325-1.6 18.4 DLA9 25/5x15x5 - 1 - 1.6 1.60.75 2 MS325-2.5 29 DLA9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.6 MS325-4 50 DLA9 25/5x15x5 - 2.5 - 4 41.5 3.5 MS325-4 50 DLA12 25/5x15x5 - 2.5 - 4 42.2 5 MS325-6.3 79 DLA12 25/5x15x5 - 4 - 6.3 6.33 6.6 MS325-9 112.5 DLA26 25/5x15x5 - 6.3 - 9 94 8.5 MS325-9 112.5 DLA26 25/5x15x5 - 6.3 - 9 9

5.5 11.5 MS325-12.5 156 DLA26 25/5x15x5 - 9 - 12.5 12.57.5 15.5 MS325-16 200 DLA26 25/5x15x5 - 12.5 - 16 1611 22 MS325-25 300 DLA26 25/5x15x5 - 20 - 25 25

MM4050NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 107: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 1Note : MM4050NS1.1K

S503KManual Motor Starter S503-K

400 V, 50 kA, Normal start - up, type 1

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.12 0.44 S503-K 0.58 7 A9-30-10 20 - 0.38 - 0.58 0.550.18 0.72 S503-K 0.8 10 A9-30-10 20 - 0.53 - 0.8 0.760.25 0.83 S503-K 1.1 13 A9-30-10 20 - 0.73 - 1.1 1.050.37 1.12 S503-K 1.5 18 A9-30-10 20 - 1 - 1.5 1.450.55 1.5 S503-K 2.1 25 A9-30-10 20 - 1.4 - 2.1 2.050.75 2 S503-K 2.1 25 A9-30-10 20 - 1.4 - 2.1 2.051.1 2.6 S503-K 3 36 A9-30-10 20 - 2 - 3 2.91.5 3.5 S503-K 4.2 50 A9-30-10 20 - 2.8 - 4.2 4

1.85 4.4 S503-K 5.8 69 A9-30-10 20 - 3.8 - 5.8 5.552.2 5 S503-K 5.8 69 A9-30-10 20 - 3.8 - 5.8 5.553 6.6 S503-K 8 96 A9-30-10 20 - 5.3 - 8 7.654 8.5 S503-K11 132 A9-30-10 35 - 7.3 - 11 10.5

5.5 11.5 S503-K 15 180 A12-30-10 35 - 10 - 15 14.57.5 15.5 S503-K 20 240 A16-30-10 35 - 14 - 20 1911 22 S503-K 26 312 A26-30-10 35 - 18 - 26 24.515 30 S503-K 32 384 A30-30-10 35 - 23 - 32 30.5

18.5 37 S503-K 37 444 A40-30-00 35 - 29 - 37 3722 44 S503-K 45 540 A50-30-00 35 - 38 - 45 45

MM4050NS1.1K

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/10/2000 by Jean-Paul Guitton

Page 108: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 2Note : MM4050NS2.1K

S503KManual Motor Starter S503-K

400 V, 50 kA, Normal start - up, type 2

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.12 0.44 S503-K 0.58 7 A9-30-10 20 - 0.38 - 0.58 0,550.18 0.72 S503-K 0.8 10 A9-30-10 20 - 0.53 - 0.8 0,760.25 0.83 S503-K 1.1 13 A9-30-10 20 - 0.73 - 1.1 1,050.37 1.2 S503-K 1.5 18 A9-30-10 20 - 1 - 1.5 1,450.55 1.5 S503-K 2.1 25 A9-30-10 20 - 1.4 - 2.1 2,050.75 2 S503-K 2.1 25 A9-30-10 20 - 1.4 - 2.1 2,051.1 2.6 S503-K 3 36 A12-30-10 20 - 2 - 3 2.91.5 3.5 S503-K 4.2 50 A12-30-10 20 - 2.8 - 4.2 41.85 4.4 S503-K 5.8 69 A16-30-10 20 - 3.8 - 5.8 5,552.2 5 S503-K 5.8 69 A16-30-10 20 - 3.8 - 5.8 5.553 6.6 S503-K 8 96 A16-30-10 20 - 5.3 - 8 7.654 8.5 S503-K11 132 A26-30-10 35 - 7.3 - 11 10.5

5.5 11.5 S503-K 15 180 A26-30-10 35 - 10 - 15 14.57.5 15.5 S503-K 20 240 A26-30-10 35 - 14 - 20 1911 22 S503-K 26 312 A26-30-10 35 - 18 - 26 24.515 30 S503-K 32 384 A30-30-10 35 - 23 - 32 30.5

18.5 37 S503-K 37 444 A40-30-00 35 - 29 - 37 3722 44 S503-K 45 540 A50-30-00 35 - 38 - 45 45

MM4050NS2.1K

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/10/2000 by Jean-Paul Guitton

Page 109: Type Selection Tables

Star Delta Starters400 V - 50 kA - Normal start - up, type : 1Note : MM4050SD1.1

MS325/495

MMS Up-stream

Star-Delta starters with Manual Motor Starter400 V, 50 kA, Normal start - up, type 1

Motor Manual Motor Starter

Contactor Thermal TrippingSetting Range

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

K1Line

K2Delta

K3Star

Type Current setting range

Max. starting

timePe [kW] Ie [A] Irm (A) [A] (s)

1.1

1.5

2.8

3.5

MS325-4.0 48 A9 A9 A9 - 2.5 - 4 15

2.2 5 MS325-6.3 94.5 A9 A9 A9 - 4 - 6.3 153 6.6 MS325-9.0 135 A9 A9 A9 - 6.3 - 9 154 8.5 MS325-9.0 135 A9 A9 A9 - 6.3 - 9 15

5.5 11.5 MS325-12.5 187.5 A9 A9 A9 - 9 - 12.5 157.5 15.5 MS325-16 240 A9 A9 A9 - 12.5 - 16 1511 22 MS325-25 375 A12 A12 A9 - 20 - 25 1515 30 MS450-32 384 A16 A16 A12 - 22 - 32 15

18.5 37 MS450-40 480 A26 A26 A16 - 28 - 40 1522 44 MS450-50 600 A26 A26 A16 - 40 - 50 3030 60 MS495-63 756 A40 A40 A26 - 45 - 63 3037 72 MS495-75 900 A40 A40 A26 - 57 - 75 3045 85 MS495-90 1080 A50 A50 A30 - 70 - 90 3055 100 MS495-100 1200 A63 A63 A40 - 80 - 100 30

MM4050SD1.1

Created 07/04/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 02/05/2000 by Jean-Paul Guitton

Page 110: Type Selection Tables

Star - Delta Starters400 V - 50 kA - Normal start - up, type : 2Note : MM4050SD2.1

MS325/495

MMS Up-stream

Star-Delta starters with Manual Motor Starter400 V, 50 kA, Normal start - up, type 2

Motor Manual Motor Starter

Contactor Thermal Tripping Setting Range

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

K1Line

K2Delta

K3Star

Type Current setting range

Max.starting

timePe [kW] Ie [A] Irm (A) [A] (s)

1.1

1.5

2.8

3.5

MS325-4.0 48 A9 A9 A9 - 2.5 - 4 15

2.2 5 MS325-6.3 94.5 A12 A12 A9 - 4 - 6.3 153 6.6 MS325-9.0 135 A26 A26 A12 - 6.3 - 9 154 8.5 MS325-9.0 135 A26 A26 A12 - 6.3 - 9 15

5.5 11.5 MS325-12.5 187.5 A26 A26 A12 - 9 - 12.5 157.5 15.5 MS325-16 240 A26 A26 A12 - 12.5 - 16 1511 22 MS325-25 375 A26 A26 A12 - 20 - 25 1515 30 MS450-32 384 A30 A30 A26 - 22 - 32 15

18.5 37 MS450-40 480 A40 A40 A26 - 28 - 40 3022 44 MS450-50 600 A50 A50 A30 - 40 - 50 3030 60 MS495-63 756 A63 A63 A40 - 45 - 63 3037 72 MS495-75 900 A95 A95 A75 - 57 - 75 3045 85 MS495-90 1080 A95 A95 A75 - 70 - 90 3055 100 MS495-100 1200 A110 A110 A95 - 80 - 100 30

MM4050SD2.1

Created 07/04/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 02/05/2000 by Jean-Paul Guitton

Page 111: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 1Note : MM4050NS1.1

MS325/DLAManual Motors Starter MS325

400 V, 50 kA, Normal start - up, type 1

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.37 1.2 MS325-1.6 18.4 DLA9 25/5x15x5 - 1 - 1.6 1.60.55 1.5 MS325-1.6 18.4 DLA9 25/5x15x5 - 1 - 1.6 1.60.75 2 MS325-2.5 29 DLA9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.6 MS325-4 50 DLA9 25/5x15x5 - 2.5 - 4 41.5 3.5 MS325-4 50 DLA9 25/5x15x5 - 2.5 - 4 42.2 5 MS325-6.3 79 DLA9 25/5x15x5 - 4 - 6.3 6.33 6.6 MS325-9 112.5 DLA9 25/5x15x5 - 6.3 - 9 94 8.5 MS325-9 112.5 DLA9 25/5x15x5 - 6.3 - 9 9

5.5 11.5 MS325-12.5 156 DLA12 25/5x15x5 - 9 - 12.5 127.5 15.5 MS325-16 200 DLA16 25/5x15x5 - 12.5 - 16 1611 22 MS325-25 300 DLA26 25/5x15x5 - 20 - 25 25

MM4050NS1.1

Safety perimeter : 25/5x15x5 means : 25mm above MS325, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 112: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 2Note : MM4050NS2.1

MS325/495

Manual Motors Starter MS325400 V, 50 kA, Normal start - up, type 2

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 MS325-0.25 2.44 A9 25/5x15x5 - 0.16 - 0.25 0.250.09 0.33 MS325-0.4 3.9 A9 25/5x15x5 - 0.25 - 0.4 0.40.12 0.42 MS325-0.63 6.14 A9 25/5x15x5 - 0.40 - 0.63 0.630.18 0.72 MS325-1 11.5 A9 25/5x15x5 - 0.63 - 1 10.25 0.83 MS325-1 11.5 A9 25/5x15x5 - 0.63 - 1 10.37 1.2 MS325-1.6 18.4 A9 25/5x15x5 - 1 - 1.6 1.60.55 1.5 MS325-1.6 18.4 A9 25/5x15x5 - 1 - 1.6 1.60.75 2 MS325-2.5 28.7 A9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.6 MS325-4 48 A9 25/5x15x5 - 2.5 - 4 41.5 3.5 MS325-4 48 A12 25/5x15x5 - 2.5 - 4 42.2 5 MS325-6.3 94.5 A12 25/5x15x5 - 4 - 6.3 6.33 6.6 MS325-9 135 A26 25/5x15x5 - 6.3 - 9 94 8.5 MS325-9 135 A26 25/5x15x5 - 6.3 - 9 9

5.5 11.5 MS325-12.5 187.5 A26 25/5x15x5 - 9 - 12.5 12.57.5 15.5 MS325-16

MS450-20

240

240

A26

A26

25/5x15x5

50/5x15x10

-

-

12.5 - 16

14 - 20

16

16

9 18.3 MS325-20 300 A26 25/5x15x5 - 16 - 20 2011 22 MS325-25

MS450-25

375

300

A30

A30

25/5x15x5

50/5x15x10

-

-

20 - 25

18 - 25

25

25

15 30 MS450-32 384 A30 50/5x15x10 - 22 - 32 3018.5 37 MS450-40 480 A40 50/5x15x10 - 28 - 40 4022 44 MS450-50 600 A50 50/5x15x10 - 40 - 50 5030 60 MS495-63 756 A63 70/5x15x10 - 45 - 63 6337 72 MS495-75 900 A95 70/5x15x10 - 57 - 75 7545 85 MS495-90 1080 A95 70/5x15x10 - 70 - 90 9055 98 MS495-100 1200 A110 70/5x15x10 - 80 - 100 100

MM4050NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 113: Type Selection Tables

Direct-on-line starters with current limiter400 V - 100 kA - Normal start - up, type : 2Note : MM4000NS2.1

MS325/450

MS 325 & MS 450

Direct-on-line starters with Current limiter400 V, 100 kA, Normal start - up, type 2

Motor Manual Motor Starter Protection Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Limitertype

Prolim

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 MS325-0.25 2.44 - A9 25/5x15x5 - 0.16 - 0.25 0.250.09 0.33 MS325-0.40 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.400.12 0.42 MS325-0.63 6.14 - A9 25/5x15x5 - 0.40 - 0.63 0.630.18 0.72 MS325-1 11.5 - A9 25/5x15x5 - 0.63 - 1 10.25 0.83 MS325-1 11.5 - A9 25/5x15x5 - 0.63 - 1 10.37 1.2 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.55 1.5 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.75 2 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.6 MS325-4 48 - A9 25/5x15x5 - 2.5 - 4 41.5 3.5 MS325-4 48 - A12 25/5x15x5 - 2.5 - 4 42.2 5 MS325-6.3 94.5 - A12 25/5x15x5 - 4 - 6.3 6.33 6.6 MS325-9 135 - A26 25/5x15x5 - 6.3 - 9 94 8.5 MS325-9 135 - A26 25/5x15x5 - 6.3 - 9 9

5.5 11.5 MS325-12.5 187.5 PLM 36-A A26 25/5x15x5 - 9 - 12.5 12.57.5 15.5 MS325-16 240 PLM 36-A A26 25/5x15x5 - 12.5 - 16 169 18.3 MS325-20 300 PLM 36-A A26 25/5x15x5 - 16 - 20 20

11 22 MS325-25 375 PLM 63-A A30 25/5x15x5 - 20 - 25 2515 30 MS450-32

S 503 K32

384

416

PLM 63-A

PLM 63-A

A30

A30

50/5x15x10

20

- 22 - 32

23 - 32

30

30.5

18.5 37 S 503 K37 481 PLM 63-A A50 20 - 29 - 37 37MM4000NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 17/08/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 114: Type Selection Tables

Direct on line Starters440 V - 25 kA - Normal start - up, type : 2Note : MM4430NS2.1

MS325/450

Direct-on-line starters440 V, 25 kA, Normal start - up, type 2

Motor Manual Motor Starter Protection Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Limitertype

Prolim

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.19 MS325-0.25 2.44 - A9 25/5x15x5 - 0.16 - 0.25 0.250.09 0.28 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.40.12 0.37 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.40.18 0.55 MS325-0.63 6.14 - A9 25/5x15x5 - 0.4 - 0.63 10.25 0.76 MS325-1 11.5 - A9 25/5x15x5 - 0.63 - 1 10.37 1.06 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.55 1.25 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.75 1.67 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.26 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.5 3.03 MS325-4 48 - A12 25/5x15x5 - 2.5 - 4 42.2 4.31 MS325-6.3 94.5 - A26 25/5x15x5 - 4 - 6.3 6.33 5.8 MS325-6.3 94.5 - A26 25/5x15x5 - 4 - 6.3 6.34 7.6 MS325-9 135 - A26 25/5x15x5 - 6.3 - 9 9

5.5 10.3 MS325-12.5 187.5-

A26 25/5x15x5 - 9 - 12.5 12.5

7.5 13.5 MS325-16 240 - A26 25/5x15x5 - 12.5 - 16 169 15.8 MS325-16 240 - A26 25/5x15x5 - 12.5 - 16 1611 19.3 MS325-20 300 - A26 25/5x15x5 - 16 - 20 20

12.5 21.9 MS325-25 375 - A30 25/5x15x5 - 20 - 25 2515 26.3 S 503K 32

MS450-32

416

384

-

-

A30

A30

35

50/5x15x10

-

-

23 - 32

22 - 32

30.5

30

18.5 32 S 503K 37 481 - A50 35 - 29 - 37 3722 37 S 503K 37 481 - A50 35 - 29 - 37 37

MM4430NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 115: Type Selection Tables

Direct on line Starters440 V - 50 kA - Normal start - up, type : 2Note : MM4450NS2.1

MS325/450

Direct-on-line starters440 V, 50 kA, Normal start - up, type 2

Motor Manual Motor Starter Protection Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Limitertype

Prolim

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.19 MS325-0,25 2.44 - A9 25/5x15x5 - 0.16 - 0.25 0.250.09 0.28 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.40.12 0.37 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.40.18 0.55 MS325-0.63 6.14 - A9 25/5x15x5 - 0.4 - 0.63 10.25 0.76 MS325-1 11.5 - A9 25/5x15x5 - 0.63 - 1 10.37 1.06 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.55 1.25 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.75 1.67 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.26 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.5 3.03 MS325-4 48 - A12 25/5x15x5 - 2.5 - 4 42,2 4.31 MS325-6.3 94.5 - A26 25/5x15x5 - 4 - 6.3 6.33 5.8 MS325-6.3 94.5 - A26 25/5x15x5 - 4 - 6.3 6.34 7.6 MS325-9 135 - A26 25/5x15x5 - 6.3 - 9 9

5.5 10.3 MS325-12.5 187.5PLM 36-A

A26 25/5x15x5 - 9 - 12.5 12.5

7.5 13.5 MS325-16 240 PLM 36-A A26 25/5x15x5 - 12.5 - 16 169 15.8 MS325-16 240 PLM 36-A A26 25/5x15x5 - 12.5 - 16 1611 19.3 MS325-20 300 PLM 36-A A26 25/5x15x5 - 16 - 20 20

12.5 21.9 MS325-25 375 PLM 63-A A30 25/5x15x5 - 20 - 25 2515 26.3 S 503K 32

MS450-32

416

384

PLM 63-A

PLM 63-A

A30

A30

35

50/5x15x10

-

-

23 - 32

22 - 32

30.5

30

18.5

22

32

37

S 503K 37

S 503K 37

481

481

PLM 63-A

PLM 63-A

A50

A50

35

35

-

-

29 - 37

29 - 37

37

37

MM4450NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 116: Type Selection Tables

Direct-on-line starters with current limiter440 V - 100 kA - Normal start - up, type : 2Note : MM4400NS2.1

MS325Direct-on-line starters with current limiter

440 V, 100 kA, Normal start - up, type 2

Motor Manual Motor Starter Protection Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Limitertype

Prolim

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.19 MS325-0.25 2.44 - A9 25/5x15x5 - 0.16 - 0,25 0.250.09 0.28 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.40.12 0.37 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.40.18 0.55 MS325-0.63 6.14 - A9 25/5x15x5 - 0.4 - 0.63 10.25 0.76 MS325-1 11.5 - A9 25/5x15x5 - 0.63 - 1 10.37 1.06 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.55 1.25 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.75 1.67 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.1 2.26 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.5 3.03 MS325-4 50 - A12 25/5x15x5 - 2.5 - 4 42.2 4.31 MS325-6.3

MS325-6.3

78.7

78.7

PLM 36-A

MO325-6.3

A26

A26

25/5x15x5

25/5x15x5

-

-

4 - 6.3

4 - 6.3

6.3

6.3

3 5.8 MS325-6.3

MS325-6.3

78.7

78.7

PLM 36-A

MO325-6.3

A26

A26

25/5x15x5

25/5x15x5

-

-

4 - 6.3

4 - 6.3

6.3

6.3

4 7.6 MS325-9

MS325-9

135

135

PLM 36-A

MO325-9

A26

A26

25/5x15x5

25/5x15x5

-

-

6.3 - 9

6.3 - 9

9

9

5.5 11.3 MS325-12.5

MS325-12.5

187.5

187.5

PLM 36-A

MO325-12.5

A26

A26

25/5x15x5

25/5x15x5

-

-

9 - 12.5

9 - 12.5

12.5

12.5

7.5 13.5 MS325-16

MS325-16

240

240

PLM 36-A

MO325-16

A26

A26

25/5x15x5

25/5x15x5

-

-

12.5 - 16

12.5 - 16

16

16

9 15.8 MS325-16

MS325-16

240

240

PLM 36-A

MO325-16

A26

A26

25/5x15x5

25/5x15x5

-

-

12.5 - 16

12.5 - 16

16

16

11 19.3 MS325-20

MS325-20

300

300

PLM 36-A

MO325-20

A26

A26

25/5x15x5

25/5x15x5

-

-

16 - 20

16 - 20

20

20

12.5 21.9 MS325-25

MS325-25

375

375

PLM 63-A

MO325-25

A26

A26

25/5x15x5

25/5x15x5

-

-

20 - 25

20 - 25

25

25

Page 117: Type Selection Tables

15 26.3 S 503K 32

MS450-32

416

384

PLM 63-A

PLM 63-A

A30

A30

35

50/5x15x10

-

-

23 - 32

22 - 32

30

30

18.5 32 S 503K 37 481 PLM 63-A A50 35 - 29 - 37 3722 37 S 503K 37 481 PLM 63-A A50 35 - 29 - 37 37

MM4400NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 30/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 118: Type Selection Tables

Direct-on-line starters500 V - 25 kA - Normal start - up, type : 1Note : MM5025NS1.1K

S503KManual Motor Starter S503-K

500 V, 25 kA, Normal start - up, type 1

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Current setting Magnetic release

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [mm] [A] Imax [A]0.12 0.35 S503-K0.42 5 A9-30-10 20 - 0.28 - 0.42 0.420.18 0.58 S503-K0.8 10 A9-30-10 20 - 0.53 - 0.8 0.770.25 0.68 S503-K0.8 10 A9-30-10 20 - 0.53 - 0.8 0.770.37 0.9 S503-K1.1 13 A9-30-10 20 - 0.73 - 1.1 1.050.55 1.2 S503-K1.5 18 A9-30-10 20 - 1 - 1.5 1.450.75 1.5 S503-K2.1 25 A9-30-10 20 - 1.4 - 2.1 2.051.1 2.1 S503-K3 36 A9-30-10 20 - 2 - 3 2.91.5 2.7 S503-K3 36 A9-30-10 20 - 2 - 3 2.92.2 3.8 S503-K4.2 50 A9-30-10 20 - 2.8 - 4.2 43 5.1 S503-K5.8 69 A9-30-10 20 - 3.8 - 5.8 5,554 6.5 S503-K8 96 A9-30-10 20 - 5.3 - 8 7.65

5.5 8.9 S503-K11 132 A12-30-10 35 - 7.3 - 11 10.57.5 11.9 S503-K15 180 A16-30-10 35 - 10 - 15 14.511 17 S503-K20 240 A26-30-10 35 - 14 - 20 1915 22.5 S503-K26 312 A30-30-10 35 - 18 - 26 24.5

18.5 28.5 S503-K32 384 A40-30-10 35 - 23 - 32 30.522 33 S503-K37 444 A50-30-00 35 - 29 - 37 37

MM5025NS1.1K

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 05/04/2000 by Jean-Paul Guitton

Page 119: Type Selection Tables

Direct-on-line starters500 V - 25 kA - Normal start - up, type : 2Note : MM5025NS2.1K

S503KManual Motor Starter S503-K

500 V, 25 kA, Normal start - up, type 2

Motor Manual Motor Starter Contactor Overload Release

Group

Rated Output

Rated Current

Type Current setting Magnetic release

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [mm] [A] Imax [A]0.12 0.35 S503-K 0.42 5 A9-30-10 20 - 0.28 - 0.42 0.420.18 0.58 S503-K 0.80 10 A9-30-10 20 - 0.53 - 0.8 0.770.25 0.68 S503-K 0.80 10 A9-30-10 20 - 0.53 - 0.8 0.770.37 0.9 S503-K 1.10 13 A9-30-10 20 - 0.73 - 1.1 1.050.55 1.2 S503-K 1.50 18 A9-30-10 20 - 1 - 1.5 1.450.75 1.5 S503-K 2.10 25 A9-30-10 20 - 1.4 - 2.1 2.051.1 2.1 S503-K 3.00 36 A12-30-10 20 - 2 - 3 2.91.5 2.7 S503-K 3.00 36 A12-30-10 20 - 2 - 3 2.92.2 3.8 S503-K 4.20 50 A12-30-10 20 - 2.8 - 4.2 43 5.1 S503-K 5.80 69 A12-30-10 20 - 3.8 - 5.8 5.554 6.5 S503-K 8.00 96 A16-30-10 20 - 5.3 - 8 7.65

5.5 8.9 S503-K 11.0 132 A16-30-10 35 - 7.3 - 11 10.57.5 11.9 S503-K 15.0 180 A26-30-10 35 - 10 - 15 14.511 17 S503-K 20.0 240 A26-30-10 35 - 14 - 20 1915 22.5 S503-K 26.0 312 A30-30-10 35 - 18 - 26 24.5

18.5 28.5 S503-K 32.0 384 A40-30-10 35 - 23 - 32 30.522 33 S503-K 37.0 444 A50-30-00 35 - 29 - 37 37

MM5025NS2.1K

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 05/04/2000 by Jean-Paul Guitton

Page 120: Type Selection Tables

Direct-on-line Starters500 V - 50 kA - Normal start - up, type : 2Note : MM5050NS2.1

MS325/450Direct-on-line starters

500 V, 50 kA, Normal start - up, type 2

Motor Manual Motor Starter Protection Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Limitertype

Prolim

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.16 MS325-0.25 2.44 - A9 25/5x15x5 - 0.16 - 0.25 0.250.09 0.24 MS325-0.25 2.44 - A9 25/5x15x5 - 0.16 - 0.25 0.250.12 0.33 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.40.18 0.46 MS325-0.63 6.14 - A9 25/5x15x5 - 0.4 - 0.63 0.630.25 0.59 MS325-0.63 6.14 - A9 25/5x15x5 - 0.40 - 0.63 0.630.37 0.85 MS325-1 11.5 - A9 25/5x15x5 - 0.63 - 1 1.60.55 1.2 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.75 1.48 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.61.1 2.1 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.5 2.6 MS325-4 48 - A12 25/5x15x5 - 2.5 - 4 42.2 3.8 MS325-4 48 - A12 25/5x15x5 - 2.5 - 4 43 5.1 MS325-6.3 94.5 PLM 36-B A26 25/5x15x5 - 4.0 - 6.3 6.34 6.5 MS325-9 135 PLM 36-B A26 25/5x15x5 - 6.3 - 9 9

5.5 8.9 MS325-9 135 PLM 36-B A26 25/5x15x5 - 6.3 - 9 97.5 11.9 MS325-12.5 187.5 PLM 36-B A26 25/5x15x5 - 9 - 12.5 12.59 13.9 MS325-16 240 PLM 36-B A26 25/5x15x5 - 12.5 - 16 1611 16.7 MS325-20 300 PLM 63-B A26 25/5x15x5 - 16 - 20 2015 22.5 MS325-25 375 PLM 63-B A30 25/5x15x5 - 20 - 25 25

18.5 28.5 S 503K 32

MS450-32

416

384

PLM 63-B

PLM 63-B

A30

A30

35

50/5x15x10

-

-

23 - 32

22 - 32

30.5

30

22 33 S 503K 37 481 PLM 63-B A50 35 - 29 - 37 37

MM5050NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 11/10/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 121: Type Selection Tables

Direct-on-line starters with current limiter500 V - 100 kA - Normal start - up, type : 2Note : MM5000NS2.1

MS325Direct-on-line starters with current limiter

500 V, 100 kA, Normal start - up, type 2

Motor Manual Motor Starter Protection Contactor Overload Release

Group

Rated Output

Rated Current

Type Magnetic trippingcurrent

Limitertype

Prolim

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.16 MS325-0.25 2.44 - A9 25/5x15x5 - 0.16 - 0.25 0,250.09 0.24 MS325-0.25 2.44 - A9 25/5x15x5 - 0.16 - 0.25 0.250.12 0.33 MS325-0.4 3.9 - A9 25/5x15x5 - 0.25 - 0.4 0.400.18 0.46 MS325-0.63 6.14 - A9 25/5x15x5 - 0.4 - 0.63 0.630.25 0.59 MS325-0.63 6.14 - A9 25/5x15x5 - 0.4 - 0.63 0.630.37 0.85 MS325-1 11.5 - A9 25/5x15x5 - 0.63 - 1 1.60.55 1.2 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.60.75 1.48 MS325-1.6 18.4 - A9 25/5x15x5 - 1 - 1.6 1.61.1 2.1 MS325-2.5 28.75 - A9 25/5x15x5 - 1.6 - 2.5 2.51.5 2.6 MS325-4

MS325-4

50

50

PLM 36-B

MO325-4

A12

A12

25/5x15x5

25/5x15x5

-

-

2.5 - 4

2.5 - 4

4.0

4.0

2.2 3.8 MS325-4

MS325-4

50

50

PLM 36-B

MO325-4

A12

A12

25/5x15x5

25/5x15x5

-

-

2.5 - 4

2.5 - 4

4.0

4.0

3 5.1 MS325-6.3

MS325-6.3

78.7

78.7

PLM 36-B

MO325-6.3

A26

A26

25/5x15x5

25/5x15x5

-

-

4 - 6.3

4 - 6.3

6.3

6.3

4 6.5 MS325-9

MS325-9

135

135

PLM 36-B

MO325-9

A26

A26

25/5x15x5

25/5x15x5

-

-

6.3 - 9

6.3 - 9

9.0

9.0

5.5 8.9 MS325-9

MS325-9

135

135

PLM 36-B

MO325-9

A26

A26

25/5x15x5

25/5x15x5

-

-

6.3 - 9

6.3 - 9

9.0

9.0

7.5 11.9 MS325-12.5

MS325-12.5

187.5

187.5

PLM 36-B

MO325-12.5

A26

A26

25/5x15x5

25/5x15x5

-

-

9 - 12.5

9 - 12.5

12.5

12.5

9 13.9 MS325-16

MS325-16

240

240

PLM 36-B

MO325-16

A26

A26

25/5x15x5

25/5x15x5

-

-

12.5 - 16

12.5 - 16

16

16

11 16.7 MS325-20

MS325-20

300

300

PLM 36-B

MO325-20

A26

A26

25/5x15x5

25/5x15x5

-

-

16 - 20

16 - 20

20

20

Page 122: Type Selection Tables

15 22.5 MS325-25

MS325-25

375

375

PLM 63-B

MO325-25

A26

A26

25/5x15x5

25/5x15x5

-

-

20 - 25

20 - 25

25

25

18.5 28.5 S 503K 32

MS450-32

416

384

PLM 63-B

PLM 63-B

A30

A30

35

50/5x15x10

-

-

23 - 32

22 - 32

30,5

30

22 33 S 503K 37 481 PLM 63-B A50 35 - 29 - 37 37MM5000NS2.1

Safety perimeter : 25/5 x 15 x 5 means : 25mm above MS xxx, 5mm below the contactor15mm in front of each component, 5mm on each side

Created 30/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 123: Type Selection Tables

SOFTSTARTERS

UeV

IqkA

Coor.type

Startingtype

SCPDtype

SizekW

Table Last Update

400 50 1 Normal MMS 0.06 ... 50 MMPS4050LIN40-1 13/11/01Normal MMS 15 ... 50 MMPD4050LIN40-1 13/11/01Normal MCCB 0.37 ... 400 MBPS4050LIN40-1 13/11/01

400 65 2 Normal Fuse 1.5 ... 160 PSS4065LINE40 14/11/01Normal Fuse 1.5 ... 55 PSS4065LINE50 20/11/00Normal Fuse 30 ... 450 PSD4065LINE40 14/11/01Normal Fuse 25 ... 400 PSD4065LINE50 20/11/00Normal Fuse 7.5 ... 132 PSS4065DELTA40 20/11/00Normal Fuse 7.5 ... 110 PSS4065DELTA50 20/11/00

415 65 2 Normal Fuse 1.5 ... 75 PSS4165LINE40 20/11/00Normal Fuse 1.5 .... 55 PSS4165LINE50 20/11/00Normal Fuse 30 ... 500 PSD4165LINE40 20/11/00Normal Fuse 30 ... 400 PSD4165LINE50 20/11/00Normal Fuse 7.5 ... 132 PSS4165DELTA40 20/11/00Normal Fuse 8 ... 110 PSS4165DELTA50 20/11/00

440 50 1 Normal MCCB 0.37 ... 400 MBPS4450LIN40-1 13/11/01500 50 1 Normal MCCB 0.37 ... 355 MBPS5050LIN40-1 13/11/01

65 2 Normal Fuse 2.2 ... 90 PSS5065LINE40 20/11/00Normal Fuse 2.2 .. 75 PSS5065LINE50 20/11/00Normal Fuse 45 ... 550 PSD5065LINE40 20/11/00Normal Fuse 45 ... 500 PSD5065LINE50 20/11/00Normal Fuse 11 ... 160 PSS5065DELTA40 20/11/00Normal Fuse 11 ... 160 PSS5065DELTA50 20/11/00

690 50 1 Normal MCCB 0.25 ... 600 MBPS6950LIN40-1 13/11/01

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 124: Type Selection Tables

SOFTSTARTERS WITH MMS400 V - 50 kA - Normal start - up, type : 1Note : MMPS4050LIN40-1

SoftMMSSOFTSTARTERS PS S 03 ... 105

400 V, 50 kA (up to 40°C) IEC 947-4-2, type 1, AC-53a,bStarter and MMS in line

Motor Softstarter Manual Motor Starter Linecontactor

By-passcontactor

RatedOutput

[kW]

Maxcurrent

[A]

Type Type Current settingrange

[A]

Type Type

0.16 PS S 03-400B MS225-0.16 0.1 - 0.16 A9 Integrated0.06 0.25 PS S 03-400B MS225-0.25 0.16 - 0.25 A9 Integrated

0.4 PS S 03-400B MS225-0.4 0.25 - 0.4 A9 Integrated0.63 PS S 03-400B MS225-0.63 0.4 - 0.63 A9 Integrated

1 PS S 03-400B MS225-1 0.63 - 1 A9 Integrated0.55 1.6 PS S 03-400B MS225-1.6 1 - 1.6 A9 Integrated

2.5 PS S 03-400B MS225-2.5 1.6 - 2.5 A9 Integrated1.5 3.5 PS S 03-400B MS225-4 2.5 - 4 A9 Integrated2.5 6.3 PS S 12-400B MS225-6.3 4 - 6.3 A9 Integrated4 9 PS S 12-400B

PS S 18/30-500MS225-9

MS325-106.3 - 96 - 10

A9A9

IntegratedA9

10 PS S 18/30-500 MS325-10 6 – 10 A12 A95.5 12 PS S 18/30-500

PS S 12-400BMS325-12.5MS325-12.5

9 – 12.59 - 12.5

A12A12

A9Integrated

7.5 16 PS S 18/30-500PS S 25-400B

MS325-16MS325-16

12.5 - 1612.5 - 16

A16A16

A9Integrated

8 17 PS S 18/30-500PS S 25-400B

MS325-20MS325-20

16 – 2016 - 20

A16A16

A9Integrated

18 PS S 18/30-500 MS325-20 16 – 20 A26 A912.5 25 PS S 30/52-500

PS S 25-400BMS325-25MS325-25

18 – 2518 - 25

A26A26

A9Integrated

26 PS S 30/52-500 MS450-32 22 – 32 A26 A1227 PS S 30/52-500 MS450-32 22 – 32 A30 A12

15 30 PS S 30/52-500 MS450-32 22 – 32 A30 A1632 PS S 37/64-500 MS450-40 28 - 40 A30 A26

18,5 37 PS S 37/64-500 MS450-40 28 - 40 A40 A2622 44 PS S 44/76-500 MS450-50 40 - 50 A50 A26

45 PS S 50/85-500 MS450-50 40 - 50 A50 A2625 50 PS S 50/85-500 MS450-50 40 - 50 A50 A30

55 PS S 60/105-500 MS495-63 45 - 63 A63 A3030 60 PS S 60/105-500 MS495-63 45 - 63 A63 A4037 72 PS S 72/124-500 MS495-75 57 - 75 A75 A50

75 PS S 72/124-500 MS495-75 57 - 75 A75 A5045 85 PS S 85/147-500 MS495-90 70 - 90 A95 A50

96 PS S 105/181-500 MS495-100 80-100 A95 A5051 100 PS S 105/181-500 MS495-100 80-100 A110 A50

MMPS4050LIN40-1

Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 13/11/2001 by Jean-Paul Guitton

Page 125: Type Selection Tables

SOFTSTARTERS WITH MMS400 V - 50 kA - Normal start - up, type : 1Note : MMPD4050LINE40-1

SoftPSDMMSSOFTSTARTERS PS D 75 ... 110

400 V, 50 kA (up to 40°C) IEC 947-4-2, type 1, AC-53a,bStarter and MMS in line

Motor Softstarter Manual Motor Starter Linecontactor

By-passcontactor

RatedOutput

[kW]

Maxcurrent

[A]

Type Type Current settingrange

[A]

Type Type

15 30 PS D 75 MS450-40 28 - 40 A30 A1632 PS D 75 MS450-40 28 - 40 A30 A26

18.5 37 PS D 75 MS450-40 28 - 40 A40 A2620 40 PS D 75 MS450-40 28 - 40 A50 A2622 45 PS D 75 MS450-45 36 - 45 A50 A2625 50 PS D 75 MS450-50 36 - 50 A50 A4030 60 PS D 75 MS495-63 45 - 63 A63 A40

65 PS D 75 MS495-75 57 - 75 A63 A5037 72 PS D 75 MS495-75 57 - 75 A75 A50

75 PS D 75 MS495-75 57 - 75 A75 A5045 85 PS D 110 MS495-100 70 - 90 A95 A50

90 PS D 110 MS495-100 70 - 90 A95 A5096 PS D 110 MS495-100 80 - 100 A95 A50

51 100 PS D 110 MS495-100 80 - 100 A110 A50

MMPD4050LINE40-1

Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 13/11/2001 by Jean-Paul Guitton

Page 126: Type Selection Tables

SOFTSTARTERS WITH MCCB400 V - 50 kA - Normal start - up, type : 1Note : MBPS4050LIN40-1

SoftMCCBSOFTSTARTERS PS S 03 ... PS D840

400 V, 50 kA (up to 40°C) IEC 947-4-2, type 1, AC-53bStarter and MCCB in line

Motor Softstarter Moulded CaseCircuit-Breaker

OverloadRelay

Linecontactor

By-passcontactor

RatedOutput

[kW]

Maxcurrent

[A]

Type Type Magnetictrippingcurrent

[A]

Type Settingrange

[A]

Type Type

0.37 1.4 PS S 03-400B S2X80 In1.6 21 TA25DU1.4 1 - 1.4 A9 Integrated0.55 1.8 PS S 03-400B S2X80 In2 26 TA25DU1.8 1.3 - 1.8 A9 Integrated

2.4 PS S 03-400B S2X80 In2.5 33 TA25DU2.4 1.7 - 2.4 A9 Integrated1.1 3.1 PS S 12-400B S2X80 In3.2 42 TA25DU3.1 2.2 - 3.1 A9 Integrated1.5 4 PS S 12-400B S2X80 In5 65 TA25DU4 2.8 - 4 A16 Integrated2.2 5 PS S 12-400B S2X80 ln5 65 TA25DU5 3.5 - 5 A26 Integrated

6.5 PS S 12-400B S2X80 In6.5 84 TA25DU6.5 4.5 - 6.5 A26 Integrated4 8.5 PS S 12-400B S2X80 In8.5 110 TA25DU8.5 6 - 8.5 A26 Integrated5 11 PS S 12-400B S2X80 In11 145 TA25DU11 7.5 - 11 A30 Integrated

6.5 14 PS S 25-400B S2X80 In16 210 TA25DU14 10-14 A30 Integrated9 19 PS S 25-400B S2X80 In20 260 TA25DU19 13 - 19 A30 Integrated

12.5 25 PS S 25-400B S2X80 In25 325 TA25DU25 18 - 25 A30 Integrated15 32 PS S 37/64-500 S2X80 In32 415 TA75DU32 22 - 32 A50 A2620 42 PS S 44/76-500 S2X80 In42 540 TA75DU42 29 - 42 A50 A2625 50 PS S 50/85-500 S2X80 In52 680 TA75DU52 36 - 52 A50 A30

63 PS S 72/124-500 S2X80 In63 820 TA75DU63 45 - 63 A63 A5040 75 PS S 85/147-500 S2X80 In80 1040 TA75DU80 60 - 80 A75 A5045 90 PS S 105/181-500 S3H160 In160 * 1250 TA110DU90 65 - 90 A95 A5055 110 PS S 142/245-500 S3H160 In160 * 1500 TA110DU110 80 - 110 A110 A6375 145 PS S 175/300-500 S3H250 In200 * 2150 TA200DU150 110 - 150 A145 A9590 175 PS S 175/300-500 S3H250 In200 * 2400 TA200DU175 130 - 175 A185 A145

210 PS S 250/430-500 S4H250 PR211-I In250 3000 TA450DU235 165 - 235 A210 A145140 260 PS S 300/515-500 S5H400 PR211-I In320 3840 TA450DU310 220 - 310 A260 A185160 300 PS S 300/515-500 S5H400 PR211-I In400 4800 TA450DU310 220 - 310 A300 A210200 400 PS D 470 S6S630 PR211-I In630 6300 E 500DU 150 - 500 AF400 A260257 500 PS D 570 S6S630 PR211-I In630 7560 E 500DU** 150 - 500 AF580 A300315 580 PS D 720 S6S630 PR211-I In630 7560 E 800DU 250 - 800 AF580 AF400

580 PS D 720 S6S800 PR211-I In800 9600 E 800DU 250 - 800 AF580 AF400400 750 PS D 840 S6S800 PR211-I In800 9600 E 800DU 250 - 800 AF750 AF580

* magnetic only adjustable release** mounting kit between contactor and relay is not available MBPS4050LIN40-1

Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 13/11/2001 by Jean-Paul Guitton

Page 127: Type Selection Tables

SOFTSTARTERS WITH FUSES400 V - 65 kA - Normal start - up, type : 2Note : PSS4065LINE40

PSS40/40SOFTSTARTERS PS S 03 ... 142

400 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

1.5 3.5 PS S 03-400B 16 170M1359 OS 160RD0380 TA25DU4.0 2.8 - 4.0 A9 Built-in2.2 5 PS S 12-400B 20 170M1360 OS 160RD0380 TA25DU5 3.5 - 5 A9 Built-in2.5 6.5 PS S 12-400B 25 170M1361 OS 160RD0380 TA25DU6.5 4.5 - 6.5 A9 Built-in4 8.5 PS S 12-400B 32 170M1362 OS 160RD0380 TA25DU8.5 6 - 8.5 A9 Built-in5 11 PS S 12-400B 40 170M1363 OS 160RD0380 TA25DU11 7.5 - 11 A12 Built-in

5.5 12 PS S 12-400B 40 170M1363 OS 160RD0380 TA25DU14 10 - 14 A12 Built-in8 17 PS S 18/30-500

PS S 25-400B5050

170M1364170M1364

OS 160RD0380OS 160RD0380

TA25DU19TA25DU19

13 - 1913 - 19

A16A16

A9Built-in

18 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A26 A912,5 25 PS S 30/52-500

PS S 25-400B8050

170M1366170M1364

OS 160RD0380OS 160RD0380

TA25DU25TA25DU25

18 - 2518 - 25

A26A26

A9Built-in

26 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1227 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A12

15 30 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1618,5 37 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A2622 44 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A26

45 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2625 50 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

55 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A3030 60 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A40

65 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A5037 72 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5040 75 PS S 85/147-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5045 85 PS S 85/147-500 250 170M1371 OS 160RD0380 TA110DU90 65 - 90 A95 A50

96 PS S 105/181-500 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A5051 100 PS S 105/181-500 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A5055 105 PS S 105/181-500 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A63

110 PS S 142/245-500 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A6359 115 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A6375 125 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

142 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A9580 145 PS S 175/300-500 500 170M3021 OESA 250R03D80 TA200DU175 130 - 175 A145 A9590 160 PS S 175/300-500 500 170M3021 OESA 250R03D80 TA200DU175 130 - 175 A185 A110

175 PS S 175/300-500 500 170M3021 OESA 250R03D80 TA200DU175 130 - 175 A185 A145185 PS S 250/430-500 630 170M4016 OESA 250R03D80 TA200DU200 150 - 200 A185 A145

100 210 PS S 250/430-500 630 170M4016 OESA 250R03D80 TA450DU235 165 - 235 A210 A145132 250 PS S 250/430-500 700 170M4017 OESA 250R03D80 TA450DU310 220 - 310 A260 A145140 260 PS S 300/515-500 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A185147 275 PS S 300/515-500 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A185160 300 PS S 300/515-500 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210

PSS4065LINE40

Created 13/10/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 128: Type Selection Tables

SOFTSTARTERS WITH FUSES400 V - 65 kA - Normal start - up, type : 2Note : PSS4065LINE50

PSS40/50SOFTSTARTERS PS S 03 ... 142

400 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

1.5 3.5 PS S 03-400B 16 170M1359 OS 160RD0380 TA25DU4.0 2.8 - 4.0 A9 Built-in9 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5 - 11 A9 A9

5.5 12 PS S 18/30-500PS S 12-400B

5040

170M1364170M1363

OS 160RD0380OS 160RD0380

TA25DU14TA25DU14

10 - 1410 - 14

A12A12

A9Built-in

7.5 15,5 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A16 A91617

PS S 18/30-500PS S 25-400B

5050

170M1364170M1364

OS 160RD0380OS 160RD0380

TA25DU19TA25DU19

13 - 1913 - 19

A16A16

A9Built-in

11 22 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A912.5 25 PS S 30/52-500

PS S 25-400B8050

170M1366170M1364

OS 160RD0380OS 160RD0380

TA25DU25TA25DU25

18 - 2518 - 25

A26A26

A12Built-in

26 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1627 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A16

15 30 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU32 22 - 32 A30 A2632 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU32 22 - 32 A30 A2634 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A26

18.5 37 PS S 44/76-500 160 170M1369 OS 160RD0380 TA42DU42 36 - 52 A40 A2640 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 36 - 52 A50 A26

22 44 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3046 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

25 50 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU52 36 - 52 A50 A3055 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A30

30 60 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A4065 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50

37 72 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A5075 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A5078 PS S 85/147-500 315 170M1372 OS 160RD0380 TA80DU80 60 - 80 A95 A50

45 85 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A5095 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A6396 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A75

55 110 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A75110 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A95130 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95

PSS4065LINE50

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 129: Type Selection Tables

SOFTSTARTERS WITH FUSES400 V - 65 kA - Normal start - up, type : 2Note : PSD4065LINE40

PSD40/40SOFTSTARTERS PS D 75 ... 840

400 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

30 60 PS D 75 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A4065 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50

37 75 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5045 96 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A5051 100 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A5055 110 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A6359 115 PS D 145 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A145 A63

125 PS D 145 400 170M3019 OESA 250R03D80 TA200DU150 110 - 150 A145 A7575 145 PS D 145 400 170M3019 OESA 250R03D80 TA200DU175 130 - 175 A145 A9590 175 PS D 175 450 170M3020 OESA 250R03D80 TA200DU200 150 - 200 A185 A145

185 PS D 210 500 170M3021 OESA 250R03D80 TA200DU200 150 - 200 A185 A145110 210 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145132 250 PS D 250 630 170M4016 OESA 250R03D80 TA450DU310 220 - 310 A260 A145140 260 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A185147 275 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A185160 300 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210

305 PS D 370 900 170M5015 OESA 400R03D80 E500DU 150 - 500 AF400 A210180 350 PS D 370 900 170M5015 OESA 400R03D80 E500DU 150 - 500 AF400 A210200 370 PS D 370 900 170M5015 OESA 400R03D80 E500DU 150 - 500 AF400 A260

400 PS D 470 1250 170M5018 OESA 630R03D80 E500DU 150 - 500 AF400 A260250 460 PS D 470 1250 170M5018 OESA 630R03D80 E500DU 150 - 500 AF460 A300

470 PS D 470 1250 170M5018 OESA 630R03D80 E800DU 250 - 800 AF580 A300257 500 PS D 570 1500 170M6018 OESA 630R03D80 E800DU 250 - 800 AF580 A300295 570 PS D 570 1500 170M6018 OESA 630R03D80 E800DU 250 - 800 AF580 AF400315 580 PS D 720 1800 170M6020 OESA 630R03D80 E800DU 250 - 800 AF580 AF400

600 PS D 720 1800 170M6020 OESA 630R03D80 E800DU 250 - 800 AF750 AF400355 700 PS D 720 1800 170M6020 OESA 800R03D80 E800DU 250 - 800 AF750 AF460400 720 PS D 720 1800 170M6020 OESA 800R03D80 E800DU 250 - 800 AF750 AF580

750 PS D 840 1800 170M6020 1) E800DU 250 - 800 AF750 AF580450 800 PS D 840 1800 170M6020 1) T900DU850 610 - 850 IOR1000 AF580

1) Use Bussmann fuseholder 170H 3004PSD4065LINE40

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 130: Type Selection Tables

SOFTSTARTERS WITH FUSES400 V - 65 kA - Normal start - up, type : 2Note : PSD4065LINE50

PSD40/50SOFTSTARTERS PS D 75 ... 840

400 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

25 50 PS D 75 250 170M1371 OS 160RD0380 TA75DU52 36 - 52 A50 A3055 PS D 75 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A53 A30

30 60 PS D 75 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A4065 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A5069 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A50

37 72 PS D 110 315 170M1372 OS 160RD0380 TA80DU80 65 - 80 A75 A5075 PS D 110 315 170M1372 OS 160RD0380 TA80DU80 65 - 80 A75 A50

45 85 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A5095 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A6396 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A75101 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A75

55 105 PS D 145 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A75110 PS D 145 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A95133 PS D 145 400 170M3019 OESA 250R03D80 TA200DU150 110 - 150 A145 A95135 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95

75 140 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A110145 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A110161 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A185 A145

90 170 PS D 210 500 170M3021 OESA 250R03D80 TA200DU175 130 - 175 A185 A145185 PS D 210 500 170M3021 OESA 250R03D80 TA200DU200 150 - 200 A185 A145193 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145

110 205 PS D 250 630 170M4016 OESA 400R03D80 TA450DU235 165 - 235 A210 A185230 PS D 250 630 170M4016 OESA 400R03D80 TA450DU235 165 - 235 A260 A185

132 245 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A210250 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A210260 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A210276 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A260

160 295 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 A300 A260300 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 A300 A260305 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 A300 A260340 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260350 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 400 EH370 A300

200 370 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 500 EH370 A300400 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 500 EH370 A300432 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370

250 460 PS D 570 1500 170M6018 OESA 800R03D80 T900DU500 355 - 500 EH550 EH370470 PS D 570 1500 170M6018 OESA 800R03D80 T900DU500 355 - 500 EH550 EH370524 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550550 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550

315 580 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550355 636 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550

650 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550662 PS D 720 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH700700 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH700

400 710 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH800 EH700720 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH800 EH700

PSD4065LINE50

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 131: Type Selection Tables

SOFTSTARTERS WITH FUSES400 V - 65 kA - Normal start - up, type : 2Note : PSS4065DELTA40

PSS40/40DELSOFTSTARTERS PS S 18 ... 142

400 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter inside delta and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

insidedelta

By-passcontactor

insidedelta

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

7.5 15 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5 - 11 A9 A920 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A12 A9

11 22 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A16 A929 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A16 A9

15 30 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A26 A918.5 37 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A9

40 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A943 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A9

22 44 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1246 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A12

25 50 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1651 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1655 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A30 A26

30 60 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A2663 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A2664 PS S 37/64-500 125 170M1368 OS 160RD0380 TA75DU42 29 - 42 A40 A26

37 72 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2676 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2677 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A26

45 85 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3086 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A50 A3094 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A30103 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A40

55 105 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A50112 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50124 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A50129 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A50

75 140 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50147 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50165 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A50

90 170 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50173 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50181 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A63189 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A63198 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A63

110 205 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75215 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

132 245 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95PSS4065DELTA40

Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 132: Type Selection Tables

SOFTSTARTERS WITH FUSES400 V - 65 kA - Normal start - up, type : 2Note : PSS4065DELTA50

PSS40/50DELSOFTSTARTERS PS S 18 ... 142

400 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter inside delta and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

insidedelta

By-passcontactor

insidedelta

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

7.5 15 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5 - 11 A9 A920 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A12 A9

11 22 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A16 A929 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU19 13 - 19 A16 A9

15 30 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU19 13 - 19 A26 A918.5 37 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A9

43 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1244 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1646 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1647 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A26

25 50 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A2655 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A26

30 60 PS S 44/76-500 160 170M1369 OS 160RD0380 TA42DU42 29 - 42 A40 A2663 PS S 44/76-500 160 170M1369 OS 160RD0380 TA42DU42 29 - 42 A40 A2668 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29 - 42 A50 A2670 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

37 72 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3078 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

45 85 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A50 A3086 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A50 A3094 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A30103 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A40

55 105 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50112 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50114 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A50129 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A50135 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50

75 140 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A50146 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A50163 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A63165 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A75166 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A75

90 170 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A75181 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A75189 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A95

110 205 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95225 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95

PSS4065DELTA50

Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 133: Type Selection Tables

SOFTSTARTERS WITH FUSES415 V - 65 kA - Normal start - up, type : 2Note : PSS4165LINE40

PSS41/40SOFTSTARTERS PS S 03 ... 142

415 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

3.5 PS S 03-400B 16 170M1359 OS 160RD0380 TA25DU4.0 2.8 - 4.0 A9 Built-in12 PS S 18/30-500

PS S 12-400B4040

170M1364170M1363

OS 160RD0380OS 160RD0380

TA25DU14TA25DU14

10 - 1410 - 14

A12A12

A9Built-in

7.5 14 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A16 A917 PS S 18/30-500

PS S 25-400B5050

170M1364170M1364

OS 160RD0380OS 160RD0380

TA25DU19TA25DU19

13 - 1913 - 19

A16A16

A9Built-in

18 PS S 18/30-500PS S 25-400B

5050

170M1364170M1364

OS 160RD0380OS 160RD0380

TA25DU19TA25DU19

13 - 1913 - 19

A26A26

A9Built-in

11 21 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A926 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1227 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A12

15 28 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1630 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1632 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU32 22 - 32 A30 A26

18.5 35 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A2637 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A26

22 40 PS S 44/76-500 160 170M1369 OS 160RD0380 TA42DU42 29 - 42 A50 A2644 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2645 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A26

25 47 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3050 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

30 55 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A3060 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A4065 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50

37 66 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5072 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5075 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A95 A50

45 80 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A5085 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50

55 96 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A50100 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50105 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A63110 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A63115 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A63125 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

75 135 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95142 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95

PSS4165LINE40

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 134: Type Selection Tables

SOFTSTARTERS WITH FUSES415 V - 65 kA - Normal start - up, type : 2Note : PSS4165LINE50

PSS41/50SOFTSTARTERS PS S 03 ... 142

415 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

3.5 PS S 03-400B 16 170M1359 OS 160RD0380 TA25DU4.0 2.8 - 4.0 A9 Built-in9 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5 - 11 A9 A912 PS S 18/30-500

PS S 12-400B5040

170M1364170M1363

OS 160RD0380OS 160RD0380

TA25DU14TA25DU14

10 - 1410 - 14

A12A12

A9Built-in

7.5 14 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A16 A91617

PS S 18/30-500PS S 25-400B

5050

170M1364170M1364

OS 160RD0380OS 160RD0380

TA25DU19TA25DU19

13 - 1913 - 19

A16A16

A9Built-in

11 21 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A922 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A9

12.5 23 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1225 PS S 30/52-500

PS S 25-400B8050

170M1366170M1364

OS 160RD0380OS 160RD0380

TA25DU32TA25DU25

24 - 3218 - 25

A26A26

A12Built-in

26 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1627 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A16

15 28 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A2630 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A2632 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU32 22 - 32 A30 A2634 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A26

18.5 35 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29 - 42 A40 A2637 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29 - 42 A40 A26

22 40 PS S 44/76-500 160 170M1369 OS 160RD0380 TA42DU42 29 - 42 A50 A2645 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

25 47 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU52 36 - 52 A50 A3050 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU52 36 - 52 A50 A30

30 55 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A3060 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A4065 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50

37 66 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A5072 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A5078 PS S 85/147-500 315 170M1372 OS 160RD0380 TA80DU80 60 - 80 A95 A50

45 80 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A5085 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A5095 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A63

55 96 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A75105 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A75110 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A95130 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95

PSS4165LINE50

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 135: Type Selection Tables

SOFTSTARTERS WITH FUSES415 V - 65 kA - Normal start - up, type : 2Note : PSD4165LINE40

PSD41/40SOFTSTARTERS PS D 75 ... 840

415 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

60 PSD 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A4065 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50

37 66 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5072 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A50

45 80 PS D 110 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A5055 96 PS D 110 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50

100 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A50110 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A63115 PS S 145 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A63125 PS S 145 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

75 135 PS D 145 400 170M3019 OESA 250R03D80 TA200DU150 110 - 150 A145 A95145 PS D 145 400 170M3019 OESA 250R03D80 TA200DU150 110 - 150 A145 A95160 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A185 A110

90 165 PS D 175 450 170M3020 OESA 250R03D80 TA200DU200 150 - 200 A185 A145175 PS D 175 450 170M3020 OESA 250R03D80 TA200DU200 150 - 200 A185 A145185 PS D 210 500 170M3021 OESA 250R03D80 TA200DU200 150 - 200 A185 A145

110 200 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145210 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145

132 242 PS D 250 630 170M4016 OESA 250R03D80 TA450DU310 220 - 310 A260 A185250 PS D 250 630 170M4016 OESA 400R03D80 TA450DU310 220 - 310 A260 A185260 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A185275 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210

160 285 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210300 PS D 300 700 170M4017 OESA 400R03D80 TA450DU400 285 - 400 A300 A210

200 340 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260350 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260370 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260400 PS D 470 1250 170M5018 OESA 400R03D80 T900DU500 355 - 500 EH370 A260

250 425 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 A300450 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370470 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370

315 535 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH550 EH370550 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH550 EH370570 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550

400 650 PS D 720 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH550700 PS D 720 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH550720 PS D 720 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH800 EH550

450 740 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 IOR1000 EH550800 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 IOR1000 EH550

500 830 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 IOR1000 EH700840 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 IOR1000 EH700

PSD4165LINE40

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 136: Type Selection Tables

SOFTSTARTERS WITH FUSES415 V - 65 kA - Normal start - up, type : 2Note : PSD4165LINE50

PSD41/50SOFTSTARTERS PS D 75 ... 840

415 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

60 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A4065 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50

37 66 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5072 PS D 110 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A50

45 80 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A5055 96 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A75

105 PS D 145 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A75110 PS D 145 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A95133 PS D 145 400 170M3019 OESA 250R03D80 TA200DU150 110 - 150 A145 A95

75 135 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95145 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A110161 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A185 A145

90 165 PS D 210 500 170M3021 OESA 250R03D80 TA200DU200 150 - 200 A185 A145185 PS D 210 500 170M3021 OESA 250R03D80 TA200DU200 150 - 200 A185 A145193 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145

110 200 PS D 250 630 170M4016 OESA 250R03D80 TA450DU235 165 - 235 A210 A145230 PS D 250 630 170M4016 OESA 250R03D80 TA450DU235 165 - 235 A260 A185

132 242 PS D 300 700 170M4017 OESA 250R03D80 TA450DU310 220 - 310 A260 A210250 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A210260 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A260 A210276 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A260

160 280 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 A300 A260300 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 A300 A260

200 340 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260350 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 400 EH370 A300400 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 400 EH370 EH370

250 425 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370432 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370470 PS D 570 1500 170M6018 OESA 800R03D80 T900DU500 355 - 500 EH550 EH370524 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550

315 535 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550550 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550

355 580 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550650 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550662 PS D 720 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH700700 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH700720 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH800 EH700

PSD4165LINE50

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 137: Type Selection Tables

SOFTSTARTERS WITH FUSES415 V - 65 kA - Normal start - up, type : 2Note : PSS4165DELTA40

PSS41/40DELSOFTSTARTERS PS S 18 ... 142

415 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter inside delta and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

insidedelta

By-passcontactor

insidedelta

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

15 PS S 18/30-500 50 170M364 OS 160RD0380 TA25DU11 7.5 - 11 A9 A920 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A12 A9

15 28 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A16 A929 PS S 37/64-500 80 170M1368 OS 160RD0380 TA25DU19 13 - 19 A16 A9

18.5 35 PS S 37/64-500 80 170M1368 OS 160RD0380 TA25DU25 18 - 25 A26 A922 40 PS S 37/64-500 80 170M1368 OS 160RD0380 TA25DU25 18 - 25 A26 A9

43 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A26 A946 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A12

25 47 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A1651 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A16

30 55 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A2663 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU32 29 - 42 A40 A2664 PS S 37/64-500 125 170M1368 OS 160RD0380 TA75DU32 29 - 42 A40 A26

37 66 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2676 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2677 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A26

45 80 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3085 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3086 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU63 45 - 63 A50 A3094 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A30

55 96 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A40103 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A40105 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A50112 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50124 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A50

75 135 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50147 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50

90 165 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A50173 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50

100 181 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A63189 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A63198 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A63

110 200 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75215 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

132 242 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU1505 100 - 150 A145 A95245 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU1505 100 - 150 A145 A95

PSS4165DELTA40

Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 138: Type Selection Tables

SOFTSTARTERS WITH FUSES415 V - 65 kA - Normal start - up, type : 2Note : PSS4165DELTA50

PSS41/50DELSOFTSTARTERS PS S 18 ... 142

415 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter inside delta and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

insidedelta

By-passcontactor

insidedelta

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

8 15 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5 - 11 A9 A920 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A12 A9

11 21 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A16 A915 28 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A16 A9

29 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU19 13 - 19 A16 A918.5 35 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A9

37 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A922 40 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A12

43 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1244 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A26 A1646 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1647 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A26

30 55 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A2663 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A26

37 66 PS S 37/64-500 125 170M1368 OS 160RD0380 TA75DU42 29 - 42 A50 A2668 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29 - 42 A50 A2670 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3078 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

45 80 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A50 A3086 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A50 A3094 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A30

55 96 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A40103 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A40112 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A63 A50114 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A50124 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A75 A50

75 135 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50146 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A50163 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A63

90 165 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A75166 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A95 A75

100 181 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A75189 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A95

110 200 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95225 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95

PSS4165DELTA50

Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 139: Type Selection Tables

SOFTSTARTERS WITH MCCB440 V - 50 kA - Normal start - up, type : 1Note : MBPS4450LIN40-1

SoftMCCBSOFTSTARTERS PS S 03 ... PS D840

440 V, 50 kA (up to 40°C) IEC 947-4-2, type 1, AC-53bStarter and MCCB in line

Motor Softstarter Moulded CaseCircuit-Breaker

OverloadRelay

Linecontactor

By-passcontactor

RatedOutput

[kW]

Maxcurrent

[A]

Type Type Magnetictrippingcurrent

[A]

Type Settingrange

[A]

Type Type

0.37 1.4 PS S 03-400B S2X80 In1.6 21 TA25DU1.4 1 - 1.4 A9 Integrated0.55 1.8 PS S 03-400B S2X80 In2 26 TA25DU1.8 1.3 - 1.8 A9 Integrated

2.4 PS S 03-400B S2X80 In2.5 33 TA25DU2.4 1.7 - 2.4 A9 Integrated1.1 3.1 PS S 12-400B S2X80 In3.2 42 TA25DU3.1 2.2 - 3.1 A9 Integrated1.5 4 PS S 12-400B S2X80 In5 65 TA25DU4 2.8 - 4 A16 Integrated2.2 5 PS S 12-400B S2X80 ln5 65 TA25DU5 3.5 - 5 A26 Integrated

6.5 PS S 12-400B S2X80 In6.5 84 TA25DU6.5 4.5 - 6.5 A26 Integrated4 8.5 PS S 12-400B S2X80 In8.5 110 TA25DU8.5 6 - 8.5 A26 Integrated5 11 PS S 12-400B S2X80 In11 145 TA25DU11 7.5 - 11 A30 Integrated

6.5 14 PS S 25-400B S2X80 In16 210 TA25DU14 10-14 A30 Integrated9 19 PS S 25-400B S2X80 In20 260 TA25DU19 13 - 19 A30 Integrated

12.5 25 PS S 25-400B S2X80 In25 325 TA25DU25 18 - 25 A30 Integrated15 32 PS S 37/64-500 S2X80 In32 415 TA75DU32 22 - 32 A50 A2620 42 PS S 44/76-500 S2X80 In42 540 TA75DU42 29 - 42 A50 A2625 50 PS S 50/85-500 S2X80 In52 680 TA75DU52 36 - 52 A50 A30

63 PS S 72/124-500 S2X80 In63 820 TA75DU63 45 - 63 A63 A5040 75 PS S 85/147-500 S2X80 In80 1040 TA75DU80 60 - 80 A75 A5045 90 PS S 105/181-500 S3H160 In160 * 1250 TA110DU90 65 - 90 A95 A5055 110 PS S 142/245-500 S3H160 In160 * 1500 TA110DU110 80 - 110 A110 A6375 145 PS S 175/300-500 S3H250 In200 * 2150 TA200DU150 110 - 150 A145 A9590 175 PS S 175/300-500 S3H250 In200 * 2400 TA200DU175 130 - 175 A185 A145

210 PS S 250/430-500 S4H250 PR211-I In250 3000 TA450DU235 165 - 235 A210 A145140 260 PS S 300/515-500 S5H400 PR211-I In320 3840 TA450DU310 220 - 310 A260 A185160 300 PS S 300/515-500 S5H400 PR211-I In400 4800 TA450DU310 220 - 310 A300 A210200 400 PS D 470 S6S630 PR211-I In630 6300 E 500DU 150 - 500 AF400 A260257 500 PS D 570 S6S630 PR211-I In630 7560 E 500DU** 150 - 500 AF580 A300315 580 PS D 720 S6S800 PR211-I In800 9600 E 800DU 250 - 800 AF580 AF400400 750 PS D 840 S6S800 PR211-I In800 9600 E 800DU 250 - 800 AF750 AF580

* magnetic only adjustable release** mounting kit between contactor and relay is not available MBPS4450LIN40-1

Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 13/11/2001 by Jean-Paul Guitton

Page 140: Type Selection Tables

SOFTSTARTERS WITH MCCB500 V - 50 kA - Normal start - up, type : 1Note : MBPS5050LIN40-1

SoftMCCBSOFTSTARTERS PS S 03 ... PS D840

500 V, 50 kA (up to 40°C) IEC 947-4-2, type 1, AC-53bStarter and MCCB in line

Motor Softstarter Moulded CaseCircuit-Breaker

OverloadRelay

Linecontactor

By-passcontactor

RatedOutput

[kW]

Maxcurrent

[A]

Type Type Magnetictrippingcurrent

[A]

Type Settingrange

[A]

Type Type

0.37 1 PS S 03-480B S2X80 In1.6 21 TA25DU1.0 0.63 - 1 A9 Integrated1.4 PS S 03-480B S2X80 In1.6 21 TA25DU1.4 1 - 1.4 A9 Integrated1.8 PS S 03-480B S2X80 In2 26 TA25DU1.8 1.3 - 1.8 A9 Integrated

1.1 2.4 PS S 03-480B S2X80 In3.2 42 TA25DU2.4 1.7 - 2.4 A9 Integrated1.5 3.1 PS S 12-480B S2X80 In3.2 42 TA25DU3.1 2.2 - 3.1 A16 Integrated

3.2 PS S 12-480B S2X80 In3.2 42 TA25DU4 2.8 - 4 A26 Integrated5 PS S 12-480B S2X80 In5 65 TA25DU5 3.5 - 5 A26 Integrated

4 6.5 PS S 12-480B S2X80 In6.5 84 TA25DU6.5 4.5 - 6.5 A26 Integrated5 8.5 PS S 12-480B S2X80 In8.5 110 TA25DU8.5 6 - 8.5 A30 Integrated

6.5 11 PS S 12-480B S2X80 In11 145 TA25DU11 7.5 - 11 A30 Integrated9 14 PS S 25-480B S2X80 In16 210 TA25DU14 10-14 A30 Integrated

12.5 19 PS S 25-480B S2X80 In25 325 TA25DU19 13 - 19 A30 Integrated25 PS S 25-480B S2X80 In32 415 TA75DU25 18 - 25 A50 Integrated

20 32 PS S 37/64-500 S2X80 In32 415 TA75DU32 22 - 32 A50 A2642 PS S 44/76-500 S2X80 In42 540 TA75DU42 29 - 42 A50 A2642 PS S 44/76-500 S2X80 In42 540 TA75DU42 29 - 42 A50 A2652 PS S 72/124-500 S2X80 In52 680 TA75DU52 36 - 52 A63 A30

40 63 PS S 72/124-500 S2X80 In63 800 TA75DU63 45 - 63 A75 A5055 80 PS S 105/181-500 S3L160 In125 * 1050 TA80DU80 60 - 80 A145 A50

90 PS S 105/181-500 S3L160 In125 * 1250 TA110DU90 65 - 90 A145 A5075 110 PS S 142/245-500 S3L160 In125 * 1250 TA110DU110 80 - 110 A145 A6390 135 PS S 142/245-500 S3L250 In200 * 1700 TA200DU135 100 - 135 A145 A95

100 145 PS S 175/300-500 S3L250 In200 * 2050 TA200DU150 110 - 150 A145 A95170 PS S 175/300-500 S3L250 In200 * 2400 TA200DU175 130 - 175 A185 A145

147 210 PS S 250/430-500 S4L250 PR211-I In250 3000 TA 450DU235 165 - 235 A210 A146160 240 PS S 250/430-500 S5L400 PR211-I In320 3840 TA 450DU310 220 - 310 A260 A147200 280 PS S 300/515-500 S5L400 PR211-I In400 4800 TA 450DU310 220 - 310 A300 A210

400 PS D 470 S6L630 PR211-I In630 5040 E 500DU 150 - 500 AF400 A260355 500 PS D 570 S6L630 PR211-I In630 7560 E 500DU** 150 - 500 AF580 A300355 500 PS D 570 S6L630 PR211-I In630 7560 E 500DU** 150 - 500 AF580 A300

580 PS D 720 S6L630 PR211-I In630 7560 E 800DU 250 - 800 AF580 AF400* magnetic only adjustable release** mounting kit between contactor and relay is not available MBPS5050LIN40-1

Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 13/11/2001 by Jean-Paul Guitton

Page 141: Type Selection Tables

SOFTSTARTERS WITH FUSES500 V - 65 kA - Normal start - up, type : 2Note : PSS5065LINE40

PSS50/40SOFTSTARTERS PS S 03 ... 142

500 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

3.5 PS S 03-480B 16 170M1359 OS 160RD0380 TA25DU4.0 2.8 - 4.0 A9 Built-in5.5 9 PS S 12-480B 40 170M1363 OS 160RD0380 TA25DU14 10 - 14 A9 Built-in7.5 12 PS S 18/30-500

PS S 12-480B4040

170M1364170M1363

OS 160RD0380OS 160RD0380

TA25DU14TA25DU14

10 - 1410 - 14

A12A12

A9Built-in

14 PS S 18/30-500PS S 25-480B

5050

170M1364170M1364

OS 160RD0380OS 160RD0380

TA25DU14TA25DU14

10 - 1410 - 14

A16A16

A9Built-in

11 17 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A26 A918 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A26 A9

15 2223

PS S 25-480BPS S 30/52-500

5080

170M1364170M1366

OS 160RD0380OS 160RD0380

TA25DU25TA25DU32

18 - 2524 - 32

A26A30

Built-inA9

2526

PS S 25-480BPS S 30/52-500

5080

170M1364170M1366

OS 160RD0380OS 160RD0380

TA25DU25TA25DU32

18 - 2524 - 32

A30A30

Built-inA12

27 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1218.5 28 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A16

30 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A40 A1622 33 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A26

37 PS S 37/64-500 125 170M1368 OS 160RD0380 TA75DU42 29 - 42 A50 A2625 38 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2630 44 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A26

45 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2650 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A63 A30

37 54 PS S 60105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A3055 PS S 60105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A3060 PS S 60105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A75 A40

45 65 PS S 72124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5072 PS S 72124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A95 A50

55 79 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A95 A5080 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A95 A5085 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A110 A50100 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50105 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A63

75 106 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A63115 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A63125 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

90 128 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95142 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95

PSS5065LINE40

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 142: Type Selection Tables

SOFTSTARTERS WITH FUSES500 V - 65 kA - Normal start - up, type : 2Note : PSS5065LINE50

PSS50/50SOFTSTARTERS PS S 03 ... 142

500 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

2.2 3.5 PS S 03-480B 16 170M1359 OS 160RD0380 TA25DU4.0 2.8 - 4.0 A9 Built-in5.5 9 PS S 12-480B 40 170M1363 OS 160RD0380 TA25DU11 7.5 - 11 A9 Built-in7.5 12 PS S 12-480B 40 170M1363 OS 160RD0380 TA25DU14 10 - 14 A12 Built-in

14 PS S 18/30-500PS S 25-480B

5050

170M1364170M1364

OS 160RD0380OS 160RD0380

TA25DU14TA25DU14

10 - 1410 - 14

A16A16

A9Built-in

16 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU19 13 - 19 A26 A922 PS S 30/52-500

PS S 25-480B8050

170M1366170M1364

OS 160RD0380OS 160RD0380

TA25DU25TA25DU25

18 - 2518 - 25

A26A26

A9Built-in

15 23 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A30 A1225 PS S 30/52-500

PS S 25-480B8050

170M1366170M1364

OS 160RD0380OS 160RD0380

TA25DU25TA25DU25

18 - 2518 - 25

A30A30

A12Built-in

27 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1618.5 28 PS S 37/52-500 80 170M1368 OS 160RD0380 TA25DU32 24 - 32 A30 A2622 33 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A26

34 PS S 37/64-500 125 170M1368 OS 160RD0380 TA75DU42 29 - 42 A50 A2625 38 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29 - 42 A50 A26

40 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29 - 42 A50 A2630 44 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A30

45 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A3046 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A63 A30

37 54 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A3055 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A30

45 65 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5066 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A95 A5078 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A95 A50

55 79 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA75DU80 60 - 80 A95 A5080 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA80DU80 60 - 80 A95 A5085 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A5095 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A6396 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A75100 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80 - 110 A110 A75105 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

75 106 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95130 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95

PSS5065LINE50

Created 16/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 143: Type Selection Tables

SOFTSTARTERS WITH FUSES500 V - 65 kA - Normal start - up, type : 2Note : PSD5065LINE40

PSD50/40SOFTSTARTERS PS D 75 ... 840

500 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

45 65 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5075 PS D 75 250 170M1371 OS 160RD0380 TA110DU110 80 - 110 A95 A50

55 79 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A5080 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A95 A50100 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A50

75 106 PS D 110 315 170M1372 OS 160RD0380 TA200DU135 100 - 135 A145 A63110 PS D 110 315 170M1372 OS 160RD0380 TA200DU135 100 - 135 A145 A63

90 128 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A145 A95145 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A145 A95

110 156 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A185 A110160 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A185 A110170 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A185 A145175 PS D 175 450 170M3020 OESA 250R03D80 TA450DU235 165 - 235 A210 A145

132 186 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145210 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145

160 220 PS D 250 630 170M4016 OESA 250R03D80 TA450DU310 220 - 310 A260 A145240 PS D 250 630 170M4016 OESA 250R03D80 TA450DU310 220 - 310 A260 A185250 PS D 250 630 170M4016 OESA 250R03D80 TA450DU310 220 - 310 A300 A185275 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210

200 278 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210280 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210300 PS D 300 700 170M4017 OESA 400R03D80 T450DU310 220 - 310 EH370 A210350 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A210

250 353 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260370 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260400 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 A260

315 445 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 A300450 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370470 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370

400 538 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH550 EH370550 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH550 EH370570 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550

500 680 PS D 720 1800 170M6020 OESA 800R03D80 T900DU810 610 - 810 EH700 EH550700 PS D 720 1800 170M6020 OESA 800R03D80 T900DU810 610 - 810 EH700 EH550720 PS D 720 1800 170M6020 OESA 800R03D80 T900DU810 610 - 810 EH800 EH550800 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 IOR1000 EH550840 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 IOR1000 EH700

PSD5065LINE40

Created 15/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 144: Type Selection Tables

SOFTSTARTERS WITH FUSES500 V - 65 kA - Normal start - up, type : 2Note : PSD5065LINE50

PSD50/50SOFTSTARTERS PS D 75 ... 840

500 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

By-passcontactor

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

55 PS D 75 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A63 A3060 PS D 75 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A75 A40

45 65 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A5069 PS D 75 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A95 A50

55 79 PS D 110 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A95 A5080 PS D 110 315 170M1372 OS 160RD0380 TA75DU80 60 - 80 A95 A5085 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A5095 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A63100 PS D 110 315 170M1372 OS 160RD0380 TA110DU110 80 - 110 A110 A75101 PS D 110 315 170M1372 OS 160RD0380 TA200DU135 100 - 135 A145 A75105 PS D 145 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

75 106 PS D 145 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A9590 128 PS D 145 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A95

133 PS D 145 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A95135 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95145 PS D 175 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A110

110 156 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A185 A145161 PS D 175 450 170M3020 OESA 250R03D80 TA200DU175 130 - 175 A185 A145170 PS D 210 500 170M3021 OESA 250R03D80 TA200DU200 150 - 200 A185 A145

132 186 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145193 PS D 210 500 170M3021 OESA 250R03D80 TA450DU235 165 - 235 A210 A145210 PS D 250 630 170M4016 OESA 250R03D80 TA450DU235 165 - 235 A210 A185

160 220 PS D 250 630 170M4016 OESA 250R03D80 TA450DU235 165 - 235 A260 A185230 PS D 250 630 170M4016 OESA 250R03D80 TA450DU235 165 - 235 A260 A185240 PS D 300 700 170M4017 OESA 250R03D80 TA450DU310 220 - 310 A260 A210250 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A210276 PS D 300 700 170M4017 OESA 400R03D80 TA450DU310 220 - 310 A300 A260

200 278 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 A300 A260280 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 A300 A260300 PS D 370 900 170M5015 OESA 400R03D80 TA450DU310 220 - 310 EH370 A260340 PS D 370 900 170M5015 OESA 400R03D80 T450DU400 285 - 400 EH370 A260350 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 400 EH370 A300

250 353 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 400 EH370 A300370 PS D 470 1250 170M5018 OESA 400R03D80 T450DU400 285 - 400 EH370 A300400 PS D 470 1250 170M5018 OESA 400R03D80 T900DU500 355 - 500 EH550 EH370432 PS D 470 1250 170M5018 OESA 630R03D80 T900DU500 355 - 500 EH550 EH370

315 445 PS D 570 1500 170M6018 OESA 800R03D80 T900DU500 355 - 500 EH550 EH370470 PS D 570 1500 170M6018 OESA 800R03D80 T900DU500 355 - 500 EH550 EH370524 PS D 570 1500 170M6018 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550

400 538 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550550 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH550 EH550

450 608 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550650 PS D 720 1800 170M6020 OESA 800R03D80 T900DU650 465 - 650 EH700 EH550662 PS D 720 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH700

500 680 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH700700 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH700 EH700720 PS D 840 1800 170M6020 OESA 800R03D80 T900DU850 610 - 850 EH800 EH700

PSD5065LINE50

Created 16/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 145: Type Selection Tables

SOFTSTARTERS WITH FUSES500 V - 65 kA - Normal start - up, type : 2Note : PSS5065DELTA40

PSS50/40DELSOFTSTARTERS PS S 18 ... 142

500 V, 65 kA (up to 40°C) IEC 947-4-2, type 2, AC-53a,bStarter inside delta and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

insidedelta

By-passcontactor

insidedelta

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

15 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5 - 11 A9 A911 17 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A12 A9

20 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A12 A924 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10 - 14 A16 A9

18.5 28 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU25 18 - 25 A26 A922 33 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A9

37 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A925 38 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A26 A9

43 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18 - 25 A30 A930 44 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A12

46 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1248 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A30 A1651 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU32 24 - 32 A40 A16

37 54 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24 - 32 A40 A2656 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29 - 42 A40 A2664 PS S 37/64-500 125 170M1368 OS 160RD0380 TA75DU42 29 - 42 A50 A26

45 65 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29 - 42 A50 A2676 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A2677 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A50 A26

55 79 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A63 A3085 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36 - 52 A63 A3094 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A63 A30103 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A75 A40105 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45 - 63 A75 A50

75 106 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45 - 63 A75 A50112 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60 - 80 A75 A50124 PS S 72/124-500 250 170M1371 OS 160RD0380 TA80DU80 60 - 80 A95 A50

90 128 PS S 85/147-500 315 170M1372 OS 160RD0380 TA80DU80 60 - 80 A95 A50137 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A95 A50147 PS S 85/147-500 315 170M1372 OS 160RD0380 TA110DU90 65 - 90 A110 A50

110 156 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50172 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50173 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80 - 110 A110 A50181 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA200DU135 100 - 135 A145 A63

132 186 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A63198 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A63215 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A75

160 220 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100 - 135 A145 A95245 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110 - 150 A145 A95

PSS5065DELTA40

Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 146: Type Selection Tables

SOFTSTARTERS WITH FUSES500 V - 65 kA - Normal start - up, type : 2Note : PSS5065DELTA50

PSS50/50DELSOFTSTARTERS PS S 18 ... 142

500 V, 65 kA (up to 50°C) IEC 947-4-2, type 2, AC-53a,bStarter inside delta and fuses in line

Motor Softstarter Semi-conductorfuses

Switch Fuse Thermal OverloadRelay

Linecontactor

insidedelta

By-passcontactor

insidedelta

RatedOutput[kW]

Maxcurrent

[A]

Type Ratedcurrent

[A]

Bussmannref.

Type Type Settingrange

[A]

Type Type

15 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5-11 A9 A911 17 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU11 7.5-11 A12 A9

20 PS S 18/30-500 50 170M1364 OS 160RD0380 TA25DU14 10-14 A12 A915 23 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU14 10-14 A16 A9

24 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU14 10-14 A16 A918.5 28 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18-25 A26 A922 33 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18-25 A26 A9

37 PS S 30/52-500 80 170M1366 OS 160RD0380 TA25DU25 18-25 A26 A925 38 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU25 18-25 A26 A9

43 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU25 18-25 A30 A1230 44 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24-32 A30 A16

46 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24-32 A30 A1648 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24-32 A30 A26

37 54 PS S 37/64-500 125 170M1368 OS 160RD0380 TA25DU32 24-32 A40 A2656 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29-42 A40 A2658 PS S 37/64-500 125 170M1368 OS 160RD0380 TA42DU42 29-42 A50 A26

45 65 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29-42 A50 A2668 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29-42 A50 A2670 PS S 44/76-500 160 170M1369 OS 160RD0380 TA75DU42 29-42 A50 A3077 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36-52 A50 A3078 PS S 50/85-500 160 170M1369 OS 160RD0380 TA75DU52 36-52 A50 A30

55 79 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45-63 A63 A3094 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45-63 A63 A3096 PS S 60/105-500 200 170M1370 OS 160RD0380 TA75DU63 45-63 A75 A40103 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45-63 A75 A40

75 106 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU63 45-63 A75 A50112 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60-80 A75 A50114 PS S 72/124-500 250 170M1371 OS 160RD0380 TA75DU80 60-80 A95 A50

90 128 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60-80 A95 A50135 PS S 85/147-500 315 170M1372 OS 160RD0380 TA75DU80 60-80 A95 A50137 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA75DU80 60-80 A95 A50146 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80-110 A110 A50

110 156 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80-110 A110 A63163 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80-110 A110 A63166 PS S 105/181-500 400 170M3019 OESA 250R03D80 TA110DU110 80-110 A110 A75172 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA110DU110 80-110 A110 A75181 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100-135 A145 A75

132 186 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100-135 A145 A95160 220 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU135 100-135 A145 A95

225 PS S 142/245-500 450 170M3020 OESA 250R03D80 TA200DU150 110-150 A145 A95PSS5065DELTA50

Created 20/11/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 20/11/2000 by Jean-Paul Guitton

Page 147: Type Selection Tables

SOFTSTARTERS WITH MCCB690 V - 50 kA - Normal start - up, type : 1Note : MBPS6950LIN40-1

SoftMCCBSOFTSTARTERS PS S 03 ... PS D840

690 V, 50 kA (up to 40°C) IEC 947-4-2, type 1, AC-53bStarter and MCCB in line

Motor Softstarter Moulded CaseCircuit-Breaker

OverloadRelay

KORCCurrent

Transformer

Linecontactor

By-passcontactor

RatedOutput

[kW]

Maxcurrent

[A]

Type Type Magnetictrippingcurrent

[A]

Type Settingrange

[A]

Type Primary turnson CT

Type Type

0.63 PS S 18/30-690 S2X80 In1 13 TA25DU0.63 0.4 - 0.63 A9 A90.55 1 PS S 18/30-690 S2X80 In1 13 TA25DU1 0.63 - 1 A9 A9

1.4 PS S 18/30-690 S2X80 In1.6 21 TA25DU1.4 1 - 1.4 A9 A91.5 1.8 PS S 18/30-690 S2X80 In2 26 TA25DU1.8 1.3 - 1.8 A9 A9

2.4 PS S 18/30-690 S2X80 In2.5 33 TA25DU2.4 1,7 - 2.4 A16 A94 PS S 18/30-690 S2X80 In4 52 TA25DU4 2.8 - 4 A26 A9

4 5 PS S 18/30-690 S2X80 In5 65 TA25DU5 3.5 - 5 A26 A96.5 PS S 18/30-690 S2X80 In6.5 84 TA25DU6.5 4.5 - 6,5 A30 A9

6.5 8.5 PS S 18/30-690 S3X125 In25* 110 TA25DU2.4 6 - 8.5 4L185R/4 13*** A95 A99 11.1 PS S 18/30-690 S3X125 In25 * 140 TA25DU2.4 7.9 - 11.1 4L185R/4 10*** A95 A9

12.5 15.9 PS S 18/30-690 S3X125 In25 * 200 TA25DU2.4 11.2 - 15.9 4L185R/4 7*** A95 A920.5 PS S 30/52-690 S3X125 In25 * 280 TA25DU3.1 15.2 - 20.5 4L185R/4 7*** A95 A9

20 23.9 PS S 30/52-691 S3X125 In50 * 320 TA25DU3.1 17.7 - 23.9 4L185R/4 6 A145 A925 30.8 PS S 37/64-690 S3X125 In50 * 380 TA25DU4 21.6 - 30.8 4L185R/4 6 A145 A26

38.5 PS S 44/76-690 S3X125 In50 * 500 TA25DU5 27 - 38.5 4L185R/4 6 A145 A2640 46.3 PS S 50/85-690 S3X125 In100 * 620 TA25DU4 32.4 - 46.3 4L185R/4 4 A145 A3051 57.8 PS S 60/105-690 S3X125 In100 * 740 TA25DU5 40.5 - 57.8 4L185R/4 4 A145 A40

77.1 PS S 85/147-690 S3X125 In100 * 920 TA25DU5 54 - 77.1 4L185R/4 3 A145 A5092.5 PS S 105/181-690 S3X125 In125 * 1250 TA25DU4 64.8 - 92.5 4L185R/4 2 A145 A50

100 115.6 PS S 142/245-690 S3X125 In125 * 1450 TA25DU5 81 - 115.6 4L185R/4 2 A145 A75120 PS S 142/245-690 S3X200 In200 * 1750 TA25DU5 103 - 147 4L235R/4 2 A145 A75170 PS S 175/300-690 S3X200 In200 * 2100 TA 450DU185 130 - 185 A185 A145

160 170 PS S 175/300-690 S4X250 PR211-I In250 2500 TA 450DU185 130 - 185 A185 A145200 210 PS S 250/430-690 S4X250 PR211-I In250 3000 TA 450DU235 165 - 235 A210 A145

310 PS D 370 S6X400 PR211-I In320 3840 TA450DU310 220 - 310 AF400 A210310 PS D 370 S6X400 PR211-I In400 4800 TA450DU310 220 - 310 AF400 A210320 PS D 370 S6X400 PR211-I In320 3840 E 500DU 150 - 500 AF400 A210350 PS D 370 S6X400 PR211-I In400 4800 E 500DU 150 - 500 AF400 A210400 PS D 470 S6X630 PR211-I In630 6300 TA450DU400 285 - 400 AF580 A260

475 500 PS D 570 S6X630 PR211-I In630 6300 TA900DU500 355 - 500 AF580 A300500 PS D 570 S6X630 PR211-I In630 7560 TA900DU500 355 - 500 AF580 A300500 PS D 570 S6X630 PR211-I In630 6300 E 800DU 250 - 800 AF580 A300500 PS D 570 S6X630 PR211-I In630 7560 E 800DU 250 - 800 AF580 A300500 PS D 570 S6X630 PR211-I In630 6300 E 500DU ** 150 - 500 AF580 A300500 PS D 570 S6X630 PR211-I In630 7560 E 500DU ** 150 - 500 AF580 A300

600 630 PS D 720 S6X630 PR211-I In630 7560 E 800DU 250 - 800 AF750 AF460650 PS D 720 S6X630 PR211-I In630 7560 TA900DU650 465 - 650 AF750 AF460

* magnetic only adjustable release** mounting kit between contactor and relay is not available MBPS6950LIN40-1

Created 09/11/2001 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 13/11/2001 by Jean-Paul Guitton

Page 148: Type Selection Tables

UL Combination Starters acc. to UL 508

UeV

IqkA

Coor.type

Startingtype

SCPDtype

hp Table Last Update

240 200 1 DOL J Fuse 2 ... 100 FUL2400NS1.1 08-11-00480 200

3585

111

DOLDOLDOL

J FuseMCCBMCCB

5 ... 2005 ... 25

25 ... 200

FUL4800NS1.1MB4835NS1.1MB4885NS1.1

08-11-0008-11-0008-11-00

600 200 1 DOL J Fuse 7.5 ... 300 FUL6000NS1.1 08-11-00

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 149: Type Selection Tables

Direct on line starters240 V - 200 kA - start - up, type : Under Construction :No On Internet :No

Note : FUL2400NS1.1

COMBINATION MOTOR CONTROLLERS - TYPE A - Normal start-upJ FUSES - 240V / 200kA

Motor Disconnectingmean

Fuse Contactor Thermal OverloadProtection

Minimumenclosure

[hp] type Amp/Type type type [in.]2 OESA-CF30J6S 30J A9 TA25DU14 14 x 12 x 83 OESA-CF30J6S 30J A12 TA25DU14 14 x 12 x 85 OESA-CF30J6S 30J A16 TA25DU19 14 x 12 x 8

10 OESA-CF30J6S

OEAS-F60J6A

30J

60J

A26

A26

TA25DU32

TA25DU32

14 x 12 x 8

14 x 12 x 8

10 OEAS-F60J6A 60J A30 TA25DU32 14 x 12 x 810 OESA-F100JT6A 100J A40 TA42DU42 20 x 16 x 820 OESA-F100JT6A 100J A50 TA75DU63 20 x 16 x 825 OES200JT6A 200J A63 TA75DU80 20 x 16 x 830 OES200JT6A 200J A75 TA75DU80 20 x 16 x 830 OES200JT6A 200J A95 TA110DU110 24 x 20 x 1040 OES200JT6A 200J A110 TA110DU110 24 x 20 x 1050 OES200JT6A 200J A145 TA200DU135 24 x 20 x 1060 OES400JT6

OES400JT6

250J

300J

A185

A185

TA200DU150

TA200DU175

24 x 20 x 10

24 x 20 x 10

75 OES400JT6 350J A210 TA450DU200 30 x 30 x 10100 OES400JT6 400J A260 TA450DU235 30 x 30 x 10100 OES600JT6 600J A300 TA450DU310 30 x 30 x 10

FUL2400NS1.1ULFuse

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 08/11/2000 by Jean-Paul Guitton

Page 150: Type Selection Tables

Direct on line starters480 V - 200 kA - start - up, type : Under Construction :No On Internet :No

Note : FUL4800NS1.1

COMBINATION MOTOR CONTROLLERS - TYPE A - Normal start-upJ FUSES - 480V / 200kA

Motor Disconnectingmean

Fuse Contactor Thermal OverloadProtection

Minimumenclosure

[hp] type Amp/Type type type [in.]5 OESA-CF30J6S 30J A9 TA25DU14 14 x 12 x 8

7.5 OESA-CF30J6S 30J A12 TA25DU14 14 x 12 x 810 OESA-CF30J6S 30J A16 TA25DU19 14 x 12 x 820 OESA-CF30J6S

OEAS-F60J6A

30J

60J

A26

A26

TA25DU32

TA25DU32

14 x 12 x 8

14 x 12 x 8

25 OEAS-F60J6A 60J A30 TA25DU32 14 x 12 x 830 OESA-F100JT6A 100J A40 TA42DU42 20 x 16 x 840 OESA-F100JT6A 100J A50 TA75DU63 20 x 16 x 860 OES200JT6A

OES200JT6A

200J

200J

A63

A75

TA75DU80

TA75DU80

20 x 16 x 8

20 x 16 x 8

60 OES200JT6A 200J A95 TA110DU110 24 x 20 x 1075 OES200JT6A 200J A110 TA110DU110 24 x 20 x 10

100 OES200JT6A 200J A145 TA200DU135 24 x 20 x 10125 OES400JT6

OES400JT6

250J

300J

A185

A185

TA200DU150

TA200DU175

24 x 20 x 10

24 x 20 x 10

150 OES400JT6 350J A210 TA450DU200 30 x 30 x 10200 OES400JT6 400J A260 TA450DU235 30 x 30 x 10200 OES600JT6 600J A300 TA450DU310 30 x 30 x 10

FUL4800NS1.1ULFuse

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/10/2000 by Jean-Paul Guitton

Page 151: Type Selection Tables

UL STARTERS480 V - 35 kA - start - up, type : Under Construction :No On Internet :No

Note : MB4835NS1.1

COMBINATION MOTOR CONTROLLERS - TYPE C* - Normal start-upMCCB - 480V / 35kA

Motor Disconnectingmean

Contactor Thermal OverloadProtection

Minimumenclosure

[hp] type type type [in.]5 S3L010MW A9 TA25DU14 14 x 12 x 8

7.5 S3L050MW A12 TA25DU14 14 x 12 x 810 S3L050MW A16 TA25DU19 14 x 12 x 820 S3L100MW A26 TA25DU32 14 x 12 x 825 S3L150MW A30 TA42DU32 14 x 12 x 8

* : UL listed Moulded Case Circuit BreakerMB4835NS1.1

UL/MCCB

Created 06/12/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 06/12/2000 by Jean-Paul Guitton

Page 152: Type Selection Tables

UL STARTERS480 V - 85 kA - start - up, type : Under Construction :No On Internet :No

Note : MB4885NS1.1

COMBINATION MOTOR CONTROLLERS - TYPE C* - Normal start-upMCCB - 480V / 85kA

Motor Disconnectingmean

Contactor Thermal OverloadProtection

Minimumenclosure

[hp] type type type [in.]25 S3L150MW A30** TA42DU42 14 x 12 x 830 S3L150MW A40** TA42DU42 14 x 12 x 840 S3L150MW A50 TA75DU63 14 x 12 x 860 S3L250MW A63

A75

TA75DU80

TA75DU80

14 x 12 x 8

14 x 12 x 8

75 S3L250MW A110 TA110DU110 20 x 16 x 8100 S4N250MW A145** TA200DU135 24 x 20 x 10125 S4N250MW A185

A185

TA200DU150

TA200DU175

24 x 20 x 10

24 x 20 x 10

150 S4N250MW A210 TA450DU200 30 x 30 x 10200 S5N400MW A260

A260

TA450DU235

TA450DU310

30 x 30 x 10

30 x 30 x 10

200 S5N400MW A300 TA450DU310 30 x 30 x 10

* : UL listed Moulded Case Circuit Breaker** : 65kA limitation MB4885NS1.1

UL/MCCB

Created 06/12/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 06/12/2000 by Jean-Paul Guitton

Page 153: Type Selection Tables

Direct on line starters600 V - 200 kA - start - up, type : Under Construction :No On Internet :No

Note : FUL6000NS1.1

COMBINATION MOTOR CONTROLLERS - TYPE A - Normal start-upJ FUSES - 600V / 200kA

Motor Disconnectingmean

Fuse Contactor Thermal OverloadProtection

Minimumenclosure

[hp] type Amp/Type type type [in.]7.5 OESA-CF30J6S 30J A9 TA25DU14 14 x 12 x 810 OESA-CF30J6S 30J A12 TA25DU14 14 x 12 x 815 OESA-CF30J6S 30J A16 TA25DU19 14 x 12 x 825 OESA-CF30J6S

OEAS-F60J6A

30J

60J

A26

A26

TA25DU32

TA25DU32

14 x 12 x 8

14 x 12 x 8

30 OEAS-F60J6A 60J A30 TA25DU32 14 x 12 x 840 OESA-F100JT6A 100J A40 TA42DU42 20 x 16 x 850 OESA-F100JT6A 100J A50 TA75DU63 20 x 16 x 875 OES200JT6A

OES200JT6A

200J

200J

A63

A75

TA75DU80

TA75DU80

20 x 16 x 8

20 x 16 x 8

75 OES200JT6A 200J A95 TA110DU110 24 x 20 x 10100 OES200JT6A 200J A110 TA110DU110 24 x 20 x 10125 OES200JT6A 200J A145 TA200DU135 24 x 20 x 10150 OES400JT6

OES400JT6

250J

300J

A185

A185

TA200DU150

TA200DU175

24 x 20 x 10

24 x 20 x 10

200 OES400JT6 350J A210 TA450DU200 30 x 30 x 10250 OES400JT6 400J A260 TA450DU235 30 x 30 x 10300 OES600JT6 600J A300 TA450DU310 30 x 30 x 10

FUL6000NS1.1UL Fuse

Created 23/10/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 23/10/2000 by Jean-Paul Guitton

Page 154: Type Selection Tables

MCB

UeV

IqkA

Coor.type

Startingtype

SCPDtype

Overloadmean

SizekW

Table Last Update

400 10 12

NormalNormal

MCBMCB

TORTOR

0.06 ... 220.06 ... 22

MC4010NS1.1MC4010NS2.1

04/02/0004/02/00

16 12

NormalNormal

MCBMCB

TORTOR

0.06 ... 150.06 ... 15

MC4016NS1.1MC4016NS2.1

04/02/0004/02/00

35 12

NormalNormal

MCBMCB

TORTOR

0.06 ... 110.06 ... 11

MC4035NS1.1MC4035NS2.1

04/02/0004/02/00

2 HD MCB EOR 0.06 ... 9 MC4035HD2.1 04/02/0050 1 Normal MCB TOR 0.12 ... 30 MC4050NS1.1 04/02/00

2 Normal MCB TOR 0.12 ... 30 MC4050NS2.1 04/02/00100 1 Normal MCB TOR 0.06 ... 11 MC4000NS1.1 04/02/00

2 Normal MCB TOR 0.06 ... 11 MC4000NS2.1 04/02/00500 25 1 Normal MCB TOR 0.12 ... 37 MC5025NS1.1 04/02/00

2 Normal MCB TOR 0.12 ... 37 MC5025NS2.1 04/02/00100 1 Normal MCB TOR 0.25 ... 15 MC5000NS1.1 04/02/00

2 Normal MCB TOR 0.25 ... 15 MC5000NS2.1 04/02/00690 100 1 Normal MCB TOR 0.18 ... 11 MC6900NS1.1 04/02/00

2 Normal MCB TOR 0.18 ... 11 MC6900NS2.1 04/02/00

Glossary SCPD Short Circuit Protection Device Prolim Current limiter HD

NS Heavy Duty

Normal StartTOREOR

Thermal Overload RelayElectronic Overload Relay

SD Star Delta MCB Miniature Circuit Breaker

Created 01/12/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 14/11/2001 by Jean-Paul Guitton

Page 155: Type Selection Tables

Direct-on-line starters400 V - 10 kA - Normal start - up, type : 1Note : MC4010NS1.1

S273

Direct-on-line starters with S 273-K circuit-breaker 400V, 10 kA, Normal start - up, type 1

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 S 273-K1 12 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 S 273-K1 12 A9 15 TA25DU0.40 0.25 - 0.4 0.40.12 0.44 S 273-K1 12 A9 15 TA25DU0.63 0.4 - 0.63 0.630.18 0.6 S 273-K1.6 19.2 A9 15 TA25DU0.63 0.4 - 0.63 10.25 0.83 S 273-K1.6 19.2 A9 15 TA25DU1.0 0.63 - 1 10.37 1.12 S 273-K2 24 A9 15 TA25DU1.4 1 - 1.4 1.350.55 1.45 S 273-K3 36 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 S 273-K3 36 A9 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 S 273-K4 48 A9 15 TA25DU3.1 2.3 - 3.1 2.751.5 3.5 S 273-K6 72 A9 15 TA25DU4.0 2.8 - 4 3.752.2 4.8 S 273-K8 96 A9 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 S 283-K10 140 A16 15 TA25DU8.5 6 - 8.5 84 8.5 S 283-K13 182 A26 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 S 283-K16 224 A26 15 TA25DU14 10 - 14 13.57.5 15 S 283-K20 280 A26 15 TA25DU19 13 - 19 18.511 22 S 283-K32 448 A26 15 TA25DU25 18 - 25 2415 28.5 S 283-K40 560 A40 15 TA42DU32 24 - 32 30

18.5 37 S 283-K50 700 A40 15 TA42DU42 29 - 42 4022 44 S283-K63 882 A50 15 TA75DU52 35 - 52 50

MC4010NS1.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 156: Type Selection Tables

Direct-On-Line Starters400 V - 10 kA - Normal start - up, type : 2Note : MC4010NS2.1

S273

Direct-on-line starters with S 273/S283-K circuit-breaker 400V, 10 kA, Normal start - up, type 2

Motor Miniature Circuit-Breaker Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 S 273-K1 12 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 S 273-K1 12 A9 15 TA25DU0.40 0.25 - 0.4 0.40.12 0.44 S 273-K1 12 A9 15 TA25DU0.63 0.4 - 0.63 0.630.18 0.6 S 273-K1.6 19.2 A9 15 TA25DU0.63 0.4 - 0.63 0,630.25 0.83 S 273-K1.6 19.2 A9 15 TA25DU1 0.63 - 1 10.37 1.12 S 273-K2 24 A9 15 TA25DU1.4 1 - 1.4 1.350.55 1.45 S 273-K3 36 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 S 273-K3 36 A9 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 S 273-K4 48 A9 15 TA25DU3.1 2.3 - 3.1 2.951.5 3.5 S 273-K6 72 A16 15 TA25DU4

TA25DU5

2.8 - 4

3,5 - 5

3.75

4.75

2.2 4.8 S 273-K8 96 A26 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 S 283-K10 140 A26 15 TA25DU8.5 6 - 8.5 84 8.5 S 283-K13 182 A26 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 S 283-K16 224 A26 15 TA25DU14 10 - 14 13.57.5 15 S 283-K20 280 A30 15 TA25DU19 13 - 19 18.511 22 S 283-K32 448 A30 15 TA25DU25 18 - 25 24.515 28.5 S 283-K40 560 A40 15 TA42DU32 24 - 32 30.5

18.5 37 S 283-K50 700 A50 15 TA42DU42 29 - 42 38.522 44 S283-K63 882 A50 15 TA75DU52 35 - 52 50

MC40101NS2.1

Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 18/02/2000 by Jean-Paul Guitton

Page 157: Type Selection Tables

Direct-on-line starters400 V - 16 kA - Normal start - up, type : 1Note : MC4016NS1.1

S273Direct-on-line starters with S 273-K circuit-breaker

400 V, 16 kA, Normal start - up, type 1

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 S 273-K1 12 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 S 273-K1 12 A9 15 TA25DU0.40 0.25 - 0.4 0.40.12 0.44 S 273-K1 12 A9 15 TA25DU0.63 0.4 - 0.63 0.630.18 0.60 S 273-K1.6 19.2 A9 15 TA25DU0.63 0.4 - 0.63 10.25 0.83 S 273-K1.6 19.2 A9 15 TA25DU1.0 0.63 - 1 10.37 1.12 S 273-K2 24 A9 15 TA25DU1.4 1 - 1.4 1.350.55 1.45 S 273-K3 36 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 S 273-K3 36 A9 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 S 273-K4 48 A9 15 TA25DU3.1 2.3 - 3.1 2.751.5 3.5 S 273-K6 72 A9 15 TA25DU4.0 2.8 - 4 3.752.2 4.8 S 273-K8 96 A9 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 S 283-K10 140 A16 15 TA25DU8.5 6 - 8.5 84 8.5 S 283-K13 182 A26 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 S 283-K16 224 A26 15 TA25DU14 10-14 13.57.5 15 S 283-K20 280 A26 15 TA25DU19 13-19 18.511 22 S 283-K32 448 A40 15 TA42DU25 18-25 2415 28.5 S 283-K40 560 A40 15 TA42DU32 24-32 30

MC4016NS1.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 158: Type Selection Tables

Direct-On-Line Starters400 V - 16 kA - Normal start - up, type : 2Note : MC4016NS2.1

S273Direct-on-line starters with S 273/S283-K circuit-breaker

400 V, 16 kA, Normal start - up, type 2

Motor Miniature Circuit-Breaker Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 S 273-K1 12 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 S 273-K1 12 A9 15 TA25DU0.40 0.25 - 0.4 0.40.12 0.44 S 273-K1 12 A9 15 TA25DU0.63 0.4 - 0.63 0.630.18 0.60 S 273-K1.6 19.2 A9 15 TA25DU0.63 0.4 - 0.63 0,630.25 0.83 S 273-K1.6 19.2 A9 15 TA25DU1 0.63 - 1 10.37 1.12 S 273-K2 24 A9 15 TA25DU1.4 1 - 1.4 1.350.55 1.45 S 273-K3 36 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 S 273-K3 36 A12 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 S 273-K4 48 A16 15 TA25DU3.1 2.3 - 3.1 2.951.5 3.5 S 273-K6 72 A26 15 TA25DU4

TA25DU5

2.8 - 4

3,5 - 5

3.75

4.75

2.2 4.8 S 273-K8 96 A26 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 S 283-K10 140 A26 15 TA25DU8.5 6 - 8.5 84 8.5 S 283-K13 182 A30 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 S 283-K16 224 A30 15 TA25DU14 10 - 14 13.57.5 15 S 283-K20 280 A30 15 TA25DU19 13 - 19 18.511 22 S 283-K32 448 A40 15 TA42DU25 18 - 25 24.515 28.5 S 283-K40 560 A40 15 TA42DU32 24 - 32 30

MC4016NS2.1

Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 18/02/2000 by Jean-Paul Guitton

Page 159: Type Selection Tables

Direct-on-line starters400 V - 35 kA - Normal start - up, type : 1Note : MC4035NS1.1

S273Direct-on-line starters with S 273-K circuit-breaker

400 V, 35 kA, Normal start - up, type 1

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 S 273-K1 12 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 S 273-K1 12 A9 15 TA25DU0.4 0.25 - 0.4 0.40.12 0.44 S 273-K1 12 A9 15 TA25DU0.63 0.4 - 0.63 0.630.18 0.60 S 273-K1.6 19.2 A9 15 TA25DU0.63 0.4 - 0.63 10.25 0.83 S 273-K1.6 19.2 A9 15 TA25DU1 0.63 - 1 10.37 1.12 S 273-K2 24 A9 15 TA25DU1.4 1 - 1.4 1.350.55 1.45 S 273-K3 36 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 S 273-K3 36 A9 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 S 273-K4 48 A9 15 TA25DU3.1 2.3 - 3.1 2.751.5 3.5 S 273-K6 72 A9 15 TA25DU4 2.8 - 4 3.752.2 4.8 S 273-K8 96 A9 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 S 283-K10 140 A16 15 TA25DU8.5 6 - 8.5 84 8.5 S 283-K13 182 A26 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 S 283-K16 224 A26 15 TA25DU14 10 - 14 13.57,5 15 S 283-K20 280 A26 15 TA25DU19 13 - 19 18.511 22 S 283-K32 448 A40 15 TA42DU25 18 - 25 24

MC4035NS1.1

Created 26/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 160: Type Selection Tables

Direct-On-Line Starters400 V - 35 kA - Normal start - up, type : 2Note : MC4035NS2.1

S273Direct-on-line starters with S 273/S283-K circuit-breaker

400 V, 35 kA, Normal start - up, type 2

Motor Miniature Circuit-Breaker Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 S 273-K1 12 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 S 273-K1 12 A9 15 TA25DU0.4 0.25 - 0.4 0.40.12 0.44 S 273-K1 12 A9 15 TA25DU0.63 0.4 - 0.63 0.630.18 0.60 S 273-K1.6 19.2 A9 15 TA25DU0.63 0.4 - 0.63 0,630.25 0.83 S 273-K1.6 19.2 A9 15 TA25DU1 0.63 - 1 10.37 1.12 S 273-K2 24 A9 15 TA25DU1.4 1 - 1.4 1.350.55 1.45 S 273-K3 36 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 S 273-K3 36 A16 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 S 273-K4 48 A26 15 TA25DU3.1 2.3 - 3.1 2.951.5 3.5 S 273-K6 72 A26 15 TA25DU4

TA25DU5

2.8 - 4

3,5 - 5

3.75

4.75

2.2 4.8 S 273-K8 96 A26 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 S 283-K10 140 A26 15 TA25DU8.5 6 - 8.5 84 8.5 S 283-K13 182 A30 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 S 283-K16 224 A30 15 TA25DU14 10 - 14 13.57,5 15 S 283-K20 280 A30 15 TA25DU19 13 - 19 18.511 22 S 283-K32 448 A40 15 TA42DU25 18 - 25 24

MC4035NS2.1

Created 10/02/2000 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 18/02/2000 by Jean-Paul Guitton

Page 161: Type Selection Tables

Direct-on-line starters, heavy duty class 20400 V - 35 kA - Long starting (heavy duty) start - up, type : 2Note : MC4035HD2.1

MO325Direct-on-line starters with MO 325 circuit-breaker, class 20 heavy-duty

400 V, 35 kA, long starting (heavy duty), type2

Motor Moulded Case Circuit-Breaker

Contactor Overload relay Groupstarter

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Separatemounting

Max.Current

Tmaxstart.

Pe [kW] Ie [A] [A] [mm] [A] Imax [A] (s)0.06 0.22 MO325-0.25 2.44 A9 15 E16DU0.32 (10) 0.1 - 0.32 - 0.25 200.09 0.34 MO325-0.4 3.9 A9 15 E16DU1.0 (10) 0.3 - 1 - 0.4 200.12 0.44 MO325-0.63 6.14 A9 15 E16DU1.0 (10) 0.3 - 1 - 0.63 200.18 0.72 MO325-1 11.5 A9 15 E16DU1.0 (10) 0.3 - 1 - 0.95 200.25 0.83 MO325-1 11.5 A9 15 E16DU1.0 (10) 0.3 - 1 - 0.95 200.37 1.12 MO325-1.6 16 A9 15 E16DU2.7 (20) 0.9 - 2.7 - 1.45 200.55 1.45 MO325-1.6 16 A9 15 E16DU2.7 (20) 0.9 - 2.7 - 1.45 200.75 1.9 MO325-2.5 27.5 A9 15 E16DU2.7 (20) 0.9 - 2.7 - 2.2 201.1 2.6 MO325-4 40 A9 15 E16DU6.3 (20) 2 - 6.3 - 3.5 201.5 3.5 MO325-4 40 A12 15 E16DU6.3 (20) 2 - 6.3 - 3.5 202.2 4.8 MO325-6.3 67.7 A12 15 E16DU6.3 (20) 2 - 6.3 - 5.4 203 6.5 MO325-9 112.5 A26 15 E16DU18.9 (20) 5.7 - 18.9 AB16 7.3 204 8.5 MO325-16 200 A26 15 E16DU18.9 (20) 5.7 - 18.9 AB16 10.5 20

5.5 11.5 MO325-20 250 A26 15 E16DU18.9 (20) 5.7 - 18.9 AB16 13 207,5 15 MO325-25 312.5 A26 15 E16DU18.9 (20) 5.7 - 18.9 AB16 16 209 18.3 S503X-AG0074-32 352 A30 10 E16DU18.9 (20) 5.7 - 18.9 AB16 18.9 20

MC4035HD2.1

Created 19/08/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 162: Type Selection Tables

Direct-on-line starters400 V - 50 kA - Normal start - up, type : 1Note : MC4050NS1.1KM

S503KMMiniature Circuit Breaker S503-KM

400 V, 50 kA, Normal start - up, type 1

Motor Manual Motor Starter Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.12 0.44 S503-KM 1.6 16 A9-30-10 20 TA25DU0.63 0.4 - 0.63 0.630.18 0.72 S503-KM 1.6 16 A9-30-10 20 TA25DU1 0.63 - 1 10.25 0.83 S503-KM 1.6 16 A9-30-10 20 TA25DU1 0.63 - 1 10.37 1.2 S503-KM 1.6 16 A9-30-10 20 TA25DU1.4 1 - 1.4 1.40.55 1.5 S503-KM 2.5 25 A9-30-10 20 TA25DU1.8 1.3 - 1.8 1.80.75 2 S503-KM 2.5 25 A9-30-10 20 TA25DU2.4 1.7 - 2.4 2.41.1 2.6 S503-KM 4.0 45 A9-30-10 20 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 S503-KM 6.0 55 A9-30-10 20 TA25DU4 2.8 - 4 4

1.85 4.4 S503-KM 6.0 55 A9-30-10 20 TA25DU5 3.5 - 5 52.2 5 S503-KM 6.0 55 A9-30-10 20 TA25DU6.5 4.5 - 6.5 63 6.6 S503-KM 9.0 100 A9-30-10 20 TA25DU8.5 6 - 8.5 8.54 8.5 S503-KM 20 200 A9-30-10 35 TA25DU11 7.5 - 11 9

5.5 11.5 S503-KM 20 200 A12-30-10 35 TA25DU14 10 - 14 127.5 15.5 S503-KM 20 200 A16-30-10 35 TA25DU19 13 - 19 1611 22 S503-KM 32 400 A26-30-10 35 TA25DU25 18 - 25 2515 30 S503-KM 32 400 A30-30-10 35 TA25DU32 24 - 32 32

18.5 37 S503-KM 52 580 A40-30-00 35 TA42DU42 29 - 42 4022 44 S503-KM 63 800 A50-30-00 35 TA75DU52 36 - 52 5030 60 S503-KM 75 840 A63-30-00 35 TA75DU63 45 - 63 63

MC4050NS1.1KM

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 18/02/2000 by Jean-Paul Guitton

Page 163: Type Selection Tables

Direct-on line starters400 V - 50 kA - Normal start - up, type : 2Note : MC4050NS2.1KM

S503KMMiniature Circuit Breaker S503-KM

400 V, 50 kA, Normal start - up, type 2

Motor Manual Motor Starter Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.12 0.44 S503-KM1.6 16 A9-30-10 20 TA25DU0.63 0.4 - 0.63 0.50.18 0.72 S503-KM1.6 16 A9-30-10 20 TA25DU1 0.63 - 1 0.80.25 0.83 S503-KM1.6 16 A9-30-10 20 TA25DU1 0.63 - 1 10.37 1.2 S503-KM1.6 16 A9-30-10 20 TA25DU1.4 1 - 1.4 1.40.55 1.5 S503-KM2.5 25 A9-30-10 20 TA25DU1.8 1.3 - 1.8 1.40.75 2 S503-KM2.5 25 A9-30-10 20 TA25DU2.4 1.7 - 2.4 2.21.1 2.6 S503-KM4 45 A12-30-10 20 TA25DU3.1 2.2 - 3.1 3.11.5 3.5 S503-KM6 55 A12-30-10 20 TA25DU4 2.8 - 4 41.85 4.4 S503-KM6 55 A16-30-10 20 TA25DU5 3.5 - 5 52.2 5 S503-KM6 55 A16-30-10 20 TA25DU6.5 4.5 - 6.5 6.53 6.6 S503-KM9 100 A16-30-10 20 TA25DU8.5 6 - 8.5 8.54 8.5 S503-KM20 200 A26-30-10 35 TA25DU11 7.5 - 11 11

5.5 11.5 S503-KM20 200 A26-30-10 35 TA25DU14 10 - 14 147.5 15.5 S503-KM20 200 A26-30-10 35 TA25DU19 13 - 19 1911 22 S503-KM32 400 A26-30-10 35 TA25DU25 18 - 25 2515 30 S503-KM32 400 A30-30-10 35 TA25DU32 24 - 32 32

18.5 37 S503-KM52 580 A40-30-00 35 TA42DU42 29 - 42 4222 44 S503-KM63 800 A50-30-00 35 TA75DU52 36 - 52 5230 60 S503-KM75 840 A63-30-00 35 TA75DU63 45 - 63 63

MC4050NS2.1KM

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 18/02/2000 by Jean-Paul Guitton

Page 164: Type Selection Tables

Direct-on-line starters400 V - 100 kA - Normal start - up, type : 1Note : MC4000NS1.1

MO325

Direct-on-line starters with MO 325 circuit-breaker400 V, 100 kA, Normal start - up, type 1

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.06 0.22 MO325-0.25 2.44 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 MO325-0.4 3.9 A9 15 TA25DU0.4 0.25 - 0.4 0.40.12 0.44 MO325-0.63 6.14 A9 15 TA25DU0.63 0.40 - 0.63 0.630.18 0.72 MO325-1 11.5 A9 15 TA25DU1 0.63 - 1 10.25 0.83 MO325-1 11.5 A9 15 TA25DU1 0.63 - 1 10.37 1.12 MO325-1.6 16 A9 15 TA25DU1.4 1 - 1.4 1.350.55 1.45 MO325-1.6 16 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 MO325-2.5 27.5 A9 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 MO325-2.5 27.5 A9 15 TA25DU3.1 2.3 - 3.1 2.751.5 3.5 MO325-4.0 40 A9 15 TA25DU4.0 2.8 - 4 3.752.2 4.8 MO325-6.3 67.7 A9 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 MO325-9.0 112.5 A9 15 TA25DU8.5 6 - 8.5 84 8.5 MO325-12.5 156 A12 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 MO325-16 200 A16 15 TA25DU14 10 - 14 13.57.5 15 MO325-20 250 A26 15 TA25DU19 13 - 19 18.511 22 MO325-25 312.5 A26 15 TA25DU25 18 - 25 24

MC4000NS1.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 165: Type Selection Tables

Direct-on-line starters400 V - 100 kA - Normal start - up, type : 2Note : MC4000NS2.1

MO325Direct-on-line starters with MO 325 circuit-breaker

400 V, 100 kA, Normal start - up, type 2

Motor Moulded Case Circuit-Breaker

Contactor Thermal Overload Relay

Group

RatedOutput

RatedCurrent

Type Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A0.06 0.22 MO325-0.25 2.44 A9 15 TA25DU0.25 0.16 - 0.25 0.250.09 0.34 MO325-0.4 3.9 A9 15 TA25DU0.4 0.25 - 0.4 0.40.12 0.44 MO325-0.63 6.14 A9 15 TA25DU0.63 0.40 - 0.63 0.630.18 0.72 MO325-1.0 11.5 A9 15 TA25DU1.0 0.63 - 1 10.25 0.83 MO325-1.0 11.5 A9 15 TA25DU1.0 0.63 - 1 10.37 1.12 MO325-1.6 16 A9 15 TA25DU1.4 1.0 - 1.4 1.350.55 1.45 MO325-1.6 16 A9 15 TA25DU1.8 1.3 - 1.8 1.750.75 1.9 MO325-2.5 27.5 A9 15 TA25DU2.4 1.7 - 2.4 2.351.1 2.6 MO325-2.5 27.5 A9 15 TA25DU3.1 2.3 - 3.1 2.751.5 3.5 MO325-4.0 40 A12 15 TA25DU4 2.8 - 4 3.752.2 4.8 MO325-6.3 67.7 A12 15 TA25DU6.5 4.5 - 6.5 6.253 6.5 MO325-9.0 112.5 A26 15 TA25DU8.5 6 - 8.5 84 8.5 MO325-12.5 156 A26 15 TA25DU11 7.5 - 11 10.5

5.5 11.5 MO325-16 200 A26 15 TA25DU14 10 - 14 13.57.5 15 MO325-20 250 A26 15 TA25DU19 13 - 19 18.511 22 MO325-25 312.5 A26 15 TA25DU25 18 - 25 24

MC4000NS2.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 166: Type Selection Tables

500 V - 25 kA - Normal start - up, type : 1Note : MC5025NS1.1

S503KMMiniature Circuit Breaker S503-KM

500 V, 25 kA, Normal start - up, type 1

Motor Manual Motor Starter Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Current setting Magnetic release

Type Safety clearance

Type Current setting range

Max.Current

Pe [kW] Ie [A] [mm] [A] Imax [A]0.12 0.35 S503-KM 1.6 16 A9-30-10 20 TA 25DU0.4 0.25 - 0.4 0.40.18 0.58 S503-KM 1.6 16 A9-30-10 20 TA 25DU0.93 0.4 - 0.63 0.630.25 0.68 S503-KM 1.6 16 A9-30-10 20 TA 25DU1 0.63 - 1 10.37 0.9 S503-KM 1.6 16 A9-30-10 20 TA 25DU1 0.63 - 1 10.55 1.2 S503-KM 1.6 16 A9-30-10 20 TA 25DU1.4 1 - 1.4 1.350.75 1.5 S503-KM 2.5 25 A9-30-10 20 TA 25DU1.8 1.3 - 1.8 1.751.1 2.1 S503-KM 2.5 25 A9-30-10 20 TA 25DU2.4 1.7 - 2.4 2.31.5 2.7 S503-KM 4 45 A9-30-10 20 TA 25DU3.1 2.2 - 3.1 2.952.2 3.8 S503-KM 6 55 A9-30-10 20 TA 25DU4 2.8 - 4 43 5.1 S503-KM 9 100 A9-30-10 35 TA 25DU6.5 4.5 - 6.5 6.254 6.5 S503-KM 9 100 A9-30-10 35 TA 25DU8.5 6 - 8.5 8.1

5.5 8.9 S503-KM 20 200 A12-30-10 35 TA 25DU11 7.5 - 11 10.57.5 11.9 S503-KM 20 200 A16-30-10 35 TA 25DU14 10 - 14 13.511 17 S503-KM 20 200 A26-30-10 35 TA 25DU19 13 - 19 18.515 22.5 S503-KM 32 400 A30-30-10 35 TA 25DU25 18 - 25 24.5

18.5 28.5 S503KM 32 400 A40-30-10 35 TA 25DU32 24 - 32 30.522 33 S503-KM 52 580 A50-30-00 35 TA 75DU42 29 - 42 3930 44 S503-KM 63 800 A63-30-00 35 TA 75DU52 36 - 52 48.537 54 S503-KM 75 840 A95-30-00 35 TA 80DU63 45 - 63 63

MC5025NS1.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 167: Type Selection Tables

500 V - 25 kA - Normal start - up, type : 2Note : MC5025NS2.1

S503KMMiniature Circuit Breaker S503-KM

500 V, 25 kA, Normal start - up, type 2

Motor Manual Motor Starter Contactor Thermal Overload Relay

Group

Rated Output

Rated Current

Type Current setting Magnetic release

Type Safety clearance

Type Current setting range

Max. Current

Pe [kW] Ie [A] [mm] [A] Imax [A]0.12 0.35 S503-KM1.6 16 A9-30-10 20 TA25DU0.4 0.25 - 0.4 0.40.18 0.58 S503-KM1.6 16 A9-30-10 20 TA25DU0.93 0.4 - 0.63 0.630.25 0.68 S503-KM1.6 16 A9-30-10 20 TA25DU1 0.63 - 1 10.37 0.9 S503-KM1.6 16 A9-30-10 20 TA25DU1 0.63 - 1 10.55 1.2 S503-KM1.6 16 A9-30-10 20 TA25DU1.4 1 - 1.4 1.350.75 1.5 S503-KM2.5 25 A9-30-10 20 TA25DU1.8 1.3 - 1.8 1.751.1 2.1 S503-KM2.5 25 A9-30-10 20 TA25DU2.4 1.7 - 2.4 2.31.5 2.7 S503-KM4 45 A12-30-10 20 TA25DU3.1 2.2 - 3.1 2.952.2 3.8 S503-KM6 55 A12-30-10 20 TA25DU4 2.8 - 4 43 5.1 S503-KM9 100 A16-30-10 35 TA25DU6.5 4.5 - 6.5 6.254 6.5 S503-KM9 100 A16-30-10 35 TA25DU8.5 6 - 8.5 8.1

5.5 8.9 S503-KM20 200 A16-30-10 35 TA25DU11 7.5 - 11 10.57.5 11.9 S503-KM20 200 A16-30-10 35 TA25DU14 10 - 14 13.511 17 S503-KM20 200 A26-30-10 35 TA25DU19 13 - 19 18.515 22.5 S503-KM32 400 A30-30-10 35 TA25DU25 18 - 25 24.5

18.5 28.5 S503KM32 400 A40-30-10 35 TA25DU32 24 - 32 30.522 33 S503-KM52 580 A50-30-00 35 TA75DU42 29 - 42 3930 44 S503-KM63 800 A63-30-00 35 TA75DU52 36 - 52 48.537 54 S503-KM75 840 A95-30-00 35 TA80DU63 45 - 63 63

MC5025NS2.1

Created 29/11/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 01/02/2000 by Jean-Michel Eymery

Page 168: Type Selection Tables

Direct-on-line starters500 V - 100 kA - Normal start - up, type : 1Note : MC5000NS1.1

MO325

MO 325 circuit-breaker with Prolim current limiter500 V, 100 kA, Normal start - up, type1

Motor Circuit-Breakerand Current Limitor

Contactor Thermal Overload Relay Group

Rated Output

Rated Current

Type Limiter type

PROLIM

Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.25 0.66 MO325-1 - 11.5 A9 15 TA25DU1 0.63 - 1 10.37 0.88 MO325-1 - 11.5 A9 15 TA25DU1 0.63 - 1 10.55 1.2 MO325-1.6 - 16 A9 15 TA25DU1.4 1 - 1.4 1.350.75 1.5 MO325-1.6 - 16 A9 15 TA25DU1.8 1.3 - 1.8 1.751.1 2.1 MO325-2.5 - 27.5 A9 15 TA25DU2.4 1.7 - 2.4 2.31.5 2.8 MO325-4

MO325-4

-

-

40

40

A9

A9

15

15

TA25DU3.1

TA25DU4

2.2 - 3.1

2.8 - 4

2.95

3.75

2.2 3.8 MO325-4 - 40 A9 15 TA25DU5 3.5 - 5 4.22.5 4.3 MO325-6.3 - 67.7 A9 15 TA25DU5 3.5 - 5 4.753 5.2 MO325-6.3 - 67.7 A12 15 TA25DU6.5 4.5 - 6.5 6.254 6.9 MO325-9 - 112.5 A12 15 TA25DU8.5 6 - 8.5 8

5.5 9.1 MO325-12.5 - 156 A16 15 TA25DU11 7.5 - 11 10.57.5 12.2 MO325-12.5

MO325-16

-

PLM 36-B*

156

200

A26

A26

15

15

TA25DU14

TA25DU14

10 - 14

10 - 14

12.5

13.5

11 17.5 MO325-20 PLM 36-B 250 A26 15 TA25DU19 13 - 19 18.515 22.8 MO325-25 PLM 36-B 312.5 A26 15 TA25DU25 18 - 25 23

* : PLM 36-B only needed for Iq > 100 kAMC5000NS1.1

Created 30/04/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 03/02/2000 by Jean-Paul Guitton

Page 169: Type Selection Tables

Direct-on-line starters500 V - 100 kA - Normal start - up, type : 2Note : MC5000NS2.1

MO325MO 325 circuit-breaker with Prolim current limiter

500V, 100 kA, Normal start - up, type 2

Motor Circuit-Breakerand Current Limitor

Contactor Thermal Overload Relay Group

Rated Output

Rated Current

Type Limiter type

PROLIM

Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.25 0.66 MO325-1 - 11.5 A9 15 TA 25DU1 0.63 - 1 10.37 0.88 MO325-1 - 11.5 A9 15 TA 25DU1 0.63 - 1 10.55 1.2 MO325-1.6 - 16 A9 15 TA 25DU1.4 1 - 1.4 1.350.75 1.5 MO325-1.6 - 16 A9 15 TA 25DU1.8 1.3 - 1.8 1.751.1 2.1 MO325-2.5 - 27.5 A12 15 TA 25DU2.4 1.7 - 2.4 2.31.5 2.8 MO325-4

MO325-4

-

-

40

40

A12

A16

15

15

TA 25DU3.1

TA 25DU4

2.2 - 3.1

2.8 - 4

2.95

3.75

2.2 3.8 MO325-4 - 40 A26 15 TA 25DU5 3.5 - 5 4.22.5 4.3 MO325-6.3 - 67.7 A26 15 TA 25DU5 3.5 - 5 4.753 5.2 MO325-6.3 - 67.7 A26 15 TA 25DU6.5 4.5 - 6.5 6.254 6.9 MO325-9 - 112.5 A26 15 TA 25DU8.5 6 - 8.5 8

5.5 9.1 MO325-12.5 - 156 A26 15 TA 25DU11 7.5 - 11 10.57.5 12.2 MO325-12.5

MO325-16

-

PLM 36-B*

156

200

A26

A26

15

15

TA 25DU14

TA 25DU14

10 - 14

10 - 14

12.5

13.5

11 17.5 MO325-20 PLM 36-B 250 A26 15 TA 25DU19 13 - 19 18.515 22.8 MO325-25 PLM 36-B 312.5 A26 15 TA 25DU25 18 - 25 23

* : PLM 36-B only needed for Iq > 100 kA MC5000NS2.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 25/02/2000 by Jean-Michel Eymery

Page 170: Type Selection Tables

Direct-on-line starters690 V - 100 kA - Normal start - up, type : 1Note : MC6900NS1.1

MO325MO 325 circuit-breaker with Prolim current limiter

690 V, 100 kA, Normal start - up, type 1

Motor Circuit Breakerand Current Limiter

Contactor Thermal Overload Relay Group

Rated Output

Rated Current

Type Limiter type

PROLIM

Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.12 0.26 MO325-0.40 - 3.9 A9 15 TA 25DU0.40 0.25 - 0.40 0.400.18 0.42 MO325-0.63 - 6.14 A9 15 TA 25DU0.63 0.4 - 0.63 0.630.25 0.48 MO325-0.63 - 6.14 A9 15 TA 25DU0.63 0.4 - 0.63 0.630.37 0.65 MO325-1 - 11.5 A9 15 TA 25DU1 0.63 - 1 10.55 0.84 MO325-1 - 11.5 A9 15 TA 25DU1 0.63 - 1 10.75 1.1 MO325-1.6 - 18.4 A9 15 TA 25DU1.4 1.0 - 1.4 1.351.1 1.5 MO325-1.6 - 18.4 A9 15 TA25DU1.8 1.3 - 1.8 1.751.5 1.99 MO325-2.5 - 28.75 A9 15 TA 25DU2.4 1.7 - 2.4 2.35

1.85 2.54 MO325-2.5 - 28.75 A9 15 TA 25DU3.1 2.3 - 3.1 2.62.2 2.77 MO325-4 - 50 A9 15 TA 25DU3.1 2.3 - 3.1 33 3.74 MO325-4

MO325-4

-

-

50

50

A9

A9

15

15

TA 25DU4

TA 25DU5

2.8 - 4.0

3.5 - 5.0

3.75

4.5

4 4.97 MO325-6.3 - 78.75 A9 15 TA 25DU6.5 4.5 - 6.5 6.255.5 6.41 MO325-6.3 PLM 20-C 78.75 A9 15 TA 25DU8.5 6 - 8.5 6.77.5 8.54 MO325-9

MO325-12.5

PLM 20-C

PLM 20-C

135

187.5

A12

A16

15

15

TA 25DU11

TA25DU11

7.5 - 11

7.5 - 11

9

10

11 12.4 MO325-12.5 PLM 20-C 187.5 A26 15 TA 25DU14 10 - 14 13.5

MC6900NS1.1

Created 30/04/99 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 27/09/2000 by Jean-Paul Guitton

Page 171: Type Selection Tables

Direct-on-line starters690 V - 100 kA - Normal start - up, type : 2Note : MC6900NS2.1

MO325MO 325 circuit-breaker with Prolim current limiter

690 V, 100 kA, Normal start - up, type 2

Motor Circuit Breakerand Current Limiter

Contactor Thermal Overload Relay Group

Rated Output

Rated Current

Type Limiter type

PROLIM

Magnetictrippingcurrent

Type Safety clearance

Type Current setting range

Max Current

Pe [kW] Ie [A] [A] [mm] [A] Imax [A]0.12 0.26 MO325-0.40 - 3.9 A9 15 TA 25DU0.40 0.25 - 0.40 0.400.18 0.42 MO325-0.63 - 6.14 A9 15 TA 25DU0.63 0.4 - 0.63 0.630.25 0.48 MO325-0.63 - 6.14 A9 15 TA 25DU0.63 0.4 - 0.63 0.630.37 0.65 MO325-1 - 11.5 A9 15 TA 25DU1 0.63 - 1 10.55 0.84 MO325-1 - 11.5 A9 15 TA 25DU1 0.63 - 1 10.75 1.1 MO325-1.6 - 18.75 A9 15 TA 25DU1.4 1 - 1.4 1.351.1 1.5 MO325-1.6 - 18.75 A9 15 TA25DU1.8 1.3 - 1.8 1.751.5 1.99 MO325-2.5 - 28.75 A9 15 TA 25DU2.4 1.7 - 2.4 2.35

1.85 2.54 MO325-2.5 - 28.75 A12 15 TA 25DU3.1 2.3 - 3.1 2.62.2 2.77 MO325-4 - 50 A12 15 TA 25DU3.1 2.3 - 3.1 33 3.74 MO325-4

MO325-4

-

-

50

50

A12

A26

15

15

TA 25DU4

TA 25DU5

2.8 - 4

3.5 - 5

3.75

4.75

4 4.97 MO325-6.3 - 78.75 A26 15 TA 25DU6.5 4.5 - 6.5 6.255.5 6.41 MO325-6.3 PLM 20-C 78.75 A26 15 TA 25DU8.5 6 - 8.5 8.07.5 8.54 MO325-9

MO325-12.5

PLM 20-C

PLM 20-C

135

187.5

A26

A26

15

15

TA 25DU11

TA25DU11

7.5 - 11

7.5 - 11

9

10.5

11 12.4 MO325-12.5 PLM 20-C 187.5 A26 15 TA 25DU14 10 - 14 13.5

MC6900NS2.1

Created 24/09/98 by Jean-Paul Guitton/FRCTL/ABB

Coordination TableLatest changed 06/07/2001 by Jean-Paul Guitton


Recommended