+ All Categories
Home > Documents > U-Charge® U1-12RT...U-Charge® RT is a perfect choice when lower voltage and intrinsic safety are...

U-Charge® U1-12RT...U-Charge® RT is a perfect choice when lower voltage and intrinsic safety are...

Date post: 18-Feb-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
2
U-Charge® U1-12RT 12V Battery Module www.valence.com *under recommended conditions Providing twice the run-time at approximately half the weight of a comparatively sized lead-acid battery, U-Charge® RT is a perfect choice when lower voltage and intrinsic safety are prerequisites. Thousands of U-Charge® RT modules are currently in service within numerous industrial products. Excellent float and cycle life results in low operating costs, providing high investment returns for end user applications. Overview U-Charge® RT offers a simple ‘plug-and-play’ replacement for typical lead-acid battery applications. The Lithium Iron Magnesium Phosphate module offers 40Ah with a peak load capability of up to 80A incorporating built-in automatic protection. Specifications U1-12RT Voltage 12.8 V Nominal Capacity (C/5, 23°C) 40 Ah Weight (approximate) kg 6.5 kg Weight (approximate) Ibs 14.3 Ibs Dimension incl. Terminals LxWxH (mm) 197 x 131 x 183 Dimension incl. Terminals LxWxH (inches) 7.76 x 5.12 x 7.20 BCI Group Number U1R Terminals, Female-Threaded M6x1.0 Specific Energy 79 Wh/kg Energy Density 110 Wh/l Standard Discharge @ 23°C Max. Cont Current 30 A Max. 30 sec. Pulse 80 A Cut-off Voltage 10 V Run-time @ 10A 240 min Run-time @ 30A 80 min Standard Charge Charge Voltage 14.6 V Float 13.8 V Recommended 20 A Charge Time* 2.5 hrs DC Internal Resistance (Max) 15 mΩ Equivalent Lithium Content Per Module (g) 48.6 Part Number 1004461 Features Built-in automatic protection for over-charge, over- discharge and over-temperature conditions No battery management system required Series connection up to four (4) batteries (48 V) Intra-module balancing LED battery status indicator Maintenance-free Flame retardant plastics Thousands of cycles, under normal conditions Can be charged using most standard lead-acid chargers Optional battery discharge indicator ( U-BDI ) for SOC display and fault indication
Transcript
Page 1: U-Charge® U1-12RT...U-Charge® RT is a perfect choice when lower voltage and intrinsic safety are prerequisites. Thousands of U-Charge® RT modules are currently in service within

U-Charge® U1-12RT 12V Battery Module

www.valence.com

*under recommended conditions

Providing twice the run-time at approximately half the weight of a comparatively sized lead-acid battery, U-Charge® RT is a perfect choice when lower voltage and intrinsic safety are prerequisites.

Thousands of U-Charge® RT modules are currently in service within numerous industrial products. Excellent float and cycle life results in low operating costs, providing high investment returns for end user applications.

Overview

U-Charge® RT offers a simple ‘plug-and-play’ replacement for typical lead-acid battery applications.

The Lithium Iron Magnesium Phosphate module offers 40Ah with a peak load capability of up to 80A incorporating built-in automatic protection.

Specifications U1-12RT

Voltage 12.8 V

Nominal Capacity (C/5, 23°C) 40 Ah

Weight (approximate) kg 6.5 kg

Weight (approximate) Ibs 14.3 Ibs

Dimension incl. Terminals LxWxH (mm) 197 x 131 x 183

Dimension incl. Terminals LxWxH (inches) 7.76 x 5.12 x 7.20

BCI Group Number U1R

Terminals, Female-Threaded M6x1.0

Specific Energy 79 Wh/kg

Energy Density 110 Wh/l

Standard Discharge @ 23°C

Max. Cont Current 30 A

Max. 30 sec. Pulse 80 A

Cut-off Voltage 10 V

Run-time @ 10A 240 min

Run-time @ 30A 80 min

Standard Charge

Charge Voltage 14.6 V

Float 13.8 V

Recommended 20 A

Charge Time* 2.5 hrs

DC Internal Resistance (Max) 15 mΩ

Equivalent Lithium Content Per Module (g) 48.6

Part Number 1004461

Features

Built-in automatic protection for over-charge, over-discharge and over-temperature conditionsNo battery management system requiredSeries connection up to four (4) batteries (48 V)Intra-module balancingLED battery status indicatorMaintenance-free Flame retardant plasticsThousands of cycles, under normal conditionsCan be charged using most standard lead-acid chargers

Optional battery discharge indicator ( U-BDI ) for SOC display and fault indication

Page 2: U-Charge® U1-12RT...U-Charge® RT is a perfect choice when lower voltage and intrinsic safety are prerequisites. Thousands of U-Charge® RT modules are currently in service within

Common specifications

Operating temperature -10°C to +50°C

Storage temperature -40°C to +50°C

Operating humidity 5% to 95%, non-condensing

Water/dust resistance IP56

Shock and vibration IEC 62133, DIN VG96 924

Certifications FCC Class B, CE,IEC 62133 UL 1642 & UL 2054

Shipping classification UN 3480, Class 9

Accessories

U-BDI – a wired, remote U-Charge® Battery Discharge Indicator displaying a 10 segment State-of-Charge (SOC).

LED indication bar and battery status indicators. The U-BDI also monitors and controls battery-to-battery balance within a battery string.

Corporate HeadquartersNorth America Sales12303 Technology Blvd.Suite 950Austin, Texas 78727USA

Tel (888) VALENCE or +1 (512) 527-2900Fax +1 (512) 527-2910Email [email protected]

EMEA SalesUnit 63 Mallusk Enterprise ParkMallusk Co.AntrimNorthern IrelandBT36 4GN

Tel +44(0) 28 9084 5400Fax +44(0) 28 9083 8912Email [email protected]

Performance may vary depending on, but not limited to cell usage and application. If cell is used outside specifications, performance will diminish. All specifications are subject to change without notice. All information provided herein is believed, but not guaranteed, to be current and accurate. Copyright © 2005-2012 Valence Technology, Inc.

Tell us about your application at: www.valence.com Aug 2012U1-12RT

Datasheet

Capacity %

Cycles

U1-12RT Discharge Capacity Performance at 23°CCharged CC 20A to 14.6V, CV @14.6 to 1A ; Discharged 20A to 10.5V; Cycled 42 Months

Cap

acit

y (%

rat

ed)

100

90

80

60

40

20

70

50

30

10

00 5,0004,0002,000 3,5001,500500 1,000 2,500 3,000 4,500

Capacity (%)

U1-12XP Discharge Voltage Profiles at C/2 Discharge Rate and Various Ambient Temperatures

Volt

age

(V)

13.5

13

12

11

12.5

11.5

10.5

100 80 6020 40 10070 5010 30 90

50°C40°C30°C20°C10°C0°C-10°C

Cycles

Volta

ge V

U-Charge® Discharge Voltage Profiles at C/2 Discharge Rate Various Ambient Temperatures

Volta

ge (V

)

Charging Time (min)

Capacity (%)

UCharge Voltage Profiles at Various Rates and 23°C Ambient Temperature

Volt

age

(V)

14

13

12

11

13.5

12.5

11.5

10.5

100 80 6020 40 100

C/8C/5C/3C/21C2C

Time (min.)

Typical UCharge C/2 Charging Voltage and SOC Profiles at 23°C Ambient Temperature

Volt

age

(V)

Sta

te o

f C

harg

e (%

)

15

14

13

14.5

13.5

12.5

12

100

80

20

90

70

50

40

30

60

10

00 1209030 60 150

U-Charge® Voltage Profiles at Various Rates 23°C Ambient Temperature

Capacity %

State O

f Charge (S

OC

)

Typical U-Charge® C/2 Charging Voltage and SOC Profiles 23°C Ambient Temperature

U-Charge® Discharge Capacity Performance at 23°CCharged CC 20A to 14.6V, CV @14.6 to 1A Discharged 20A to 10.5V; Cycled 42 Months

Cap

acity

(% R

ated

)Vo

ltage


Recommended