1
UNREINFORCED MASONRY EXAMPLES
© 2013 by International Masonry Institute
All rights reserved.
This program is intended as a preliminary design tool for design professionals who are experienced and competent
in masonry design. This program is not intended to replace sound engineering knowledge, experience, and
judgment. Users of this program must determine the validity of the results. The International Masonry Institute
assumes no responsibility for the use or application of this program.
2
EXAMPLE A:
Given:
8 inch medium weight hollow CMU
Type N masonry cement
12 ft vertical span (simple support)
Design load is 5 psf out‐of‐plane
Seismic Design Category A
Use the 2012 IBC Required: Determine if the wall is adequate. Solution: Load Combination A (0.6D + wL) will control. The maximum moment will occur at mid‐height of the wall.
ftlbftftpsfhw
M L /908
125
8
22
The axial force (wall weight is 36 psf) is:
ftlbft
psfh
wP wall /6.1292
12366.0
26.0
Calculate the flexural tension stress.
psiftin
ftlbft
ftin
ftlb
S
M
A
P
nn
01.9/0.81
/9012
/0.30
/6.1291232
The allowable stress, Ft, is 12 psi, so the wall is adequate. If the 2009 IBC had been used, the allowable flexural tension stress is 9 psi, so the wall would not be adequate. Many designers would say that 9.01 psi is close enough to 9 psi that the wall would be OK. The program rounds to the nearest 0.1 psi, so 9.01 psi would round to 9.0 psi, and the program would indicate the wall is adequate. If Type S masonry cement were used, the allowable flexural tension stress would be 15 psi, and the wall would be adequate. The reaction at the top of the wall, Rtop, is:
ftlb
ftpsfhwR L
top /302
125
2
A sufficient anchorage would need to be provided at the top of the wall to carry this out‐of‐plane reaction force.
3
EXAMPLE B:
Given:
8 inch medium weight hollow CMU
Type N masonry cement
12 ft vertical span (simple support)
Design load is a horizontal load of 50 lb/ft at a height of 3’‐6” from the floor
Seismic Design Category A
Use the 2012 IBC Required: Determine if the wall is adequate. Solution: Load Combination D (0.6D + HL) will control. The maximum moment will occur at the location of the horizontal load.
ftlbftftftft
ftftlbhh
h
hHM L
LL /0.1245.312
12
5.3/50
The axial force (wall weight is 36 psf) is:
ftlbftftpsfhhwP Lwall /6.1835.312366.06.0
Calculate the flexural tension stress.
psiftin
ftlbft
ftin
ftlb
S
M
A
P
nn
2.12/0.81
/12412
/0.30
/6.1831232
The allowable stress, Ft, is 12 psi, so the wall is not adequate. Using a Type S masonry cement would increase the allowable stress to 20 psi, and the wall would be OK. The 50 lb/ft at 3’‐6” above the floor is a typical handrail load. The IBC and ASCE 7 are unclear as to whether a handrail load should be combined with a 5 psf out‐of‐plane load. Our interpretation is that the 5 psf out‐of‐plane load is a minimum load, and that it does not need to be combined with the handrail load.
The reaction at the top of the wall, Rtop, is:
ftlb
ft
ftftlb
h
hHR LL
top /6.1412
5.3/50
This force is smaller than the 30 lb/ft anchorage force from a 5 psf uniform lateral load (see Example A). A sufficient anchorage would need to be provided at the top of the wall to carry 30 lb/ft.
4
EXAMPLE C:
Given:
8 inch medium weight hollow CMU
Type N masonry cement
12 ft vertical span (simple support)
Design load is a vertical load of 40 lb/ft at an eccentricity of 4 inches outside the wall
Seismic Design Category A
Use the 2012 IBC Required: Determine if the wall is adequate. Solution: Load Combination B (0.6D + PL) and C (D + PL) will be checked. The maximum moment will be Pe.
ftlbftin
ftin
inftlbPeM /0.26
12
14
2
625.7/40
The eccentric load is assumed to occur at the top of the wall; hence the wall weight is 0. The axial force will just be the applied vertical load. Calculate the flexural tension stress.
psiftin
ftlbft
ftin
ftlb
S
M
A
P
nn
5.2/0.81
/2612
/0.30
/401232
The allowable stress, Ft, is 12 psi, so the wall is not adequate. Although tension almost always controls with unreinforced masonry, the unity equation will be checked for completeness. The value of r is 3.21 in., making h/r = 144in/3.21in. = 44.8
psiftin
ftlb
A
Pf
na 3.1
0.30
/402
psiin
inpsi
r
hfF m
a 8.302.21.3
.1441401
4
13501401
4
22
psi
ftin
ftlbft
S
Mf
nb 8.3
0.81
/2612123
psipsif
F mb 450
3
1350
3
0.1013.0450
8.3
8.302
3.1
psi
psi
psi
psi
F
f
F
f
b
b
a
a OK
The TMS 402 Code also requires that when using allowable stress design the following equations be checked:
ePP 41
3
2
2
577.01
r
e
h
IEP m
e
5
For this wall, / =3.21in. With e = 7.81in., 1‐0.577e/r = ‐0.405. Thus, the wall does not meet this
code requirement. However, given the relatively light load, many designers would accept the wall as adequate. The eccentric vertical load is typical of a large monitor that is attached to the wall. The IBC and ASCE 7 are unclear as to whether this load should be combined with a 5 psf out‐of‐plane load. Our interpretation is that the 5 psf out‐of‐plane load is a minimum load, and that it does not need to be combined with the handrail load. The 5 psf out‐of‐plane load should also be checked (see Example A), and would control in this case.
6
EXAMPLE D:
Given:
8 inch medium weight hollow CMU
Type N masonry cement
12 ft horizontal span (simple support)
Design load is 5 psf out‐of‐plane
Seismic Design Category A
Use the 2012 IBC Required: Determine if the wall is adequate. Solution: Load Combination A (0.6D + wL) will control. The maximum moment will occur at mid‐length of the wall (h is used for length).
ftlbftftpsfhw
M L /908
125
8
22
There is no axial force on the wall. Calculate the flexural tension stress.
psiftin
ftlbft
S
M
n
3.13/0.81
/9012123
The allowable stress, Ft, is 25 psi, so the wall is adequate. By trial and error changing of the wall length, it can be determined that the maximum horizontal span for this wall is 16 ft for a 5 psf out‐of‐plane load.
7
EXAMPLE E:
Given:
8 inch medium weight hollow CMU
Type N masonry cement
5 ft high cantilever
Design load is 5 psf out‐of‐plane
Seismic Design Category A
Use the 2012 IBC Required: Determine if the wall is adequate. Solution: Load Combination A (0.6D + wL) will control. The maximum moment will occur at the base of the wall.
ftlbftftpsfhw
M L /5.622
55
2
22
The axial force (wall weight is 36 psf) is:
ftlbftpsfhwP wall /1085366.06.0
Calculate the flexural tension stress.
psiftin
ftlbft
ftin
ftlb
S
M
A
P
nn
66.5/0.81
/5.6212
/0.30
/1081232
The allowable stress, Ft, is 12 psi, so the wall is adequate.
8
EXAMPLE F:
Given:
8 inch medium weight hollow CMU
Type N Portland cement lime mortar
12 ft vertical span (simple support)
Minimum design load is 5 psf out‐of‐plane
SDS = 0.5; Seismic Design Category C
Use the 2012 IBC Required: Determine if the wall is adequate. Solution: Check Load Combination G (0.6D + 0.7E). Wall weight is 36 psf, and R = 1.5 for unreinforced masonry.
The seismic load is
psfpsf
I
R
WSw
p
p
pDSE 4.14
0.1
5.1
365.02.12.1
Since 0.7(14.4psf) = 10.1 psf, seismic will control. The maximum moment will occur at mid‐height of the wall.
ftlbftftpsfhw
M E /1818
124.147.0
8
7.0 22
The axial force is:
ftlbft
psfh
wSP wallDS /5.1142
12365.02.07.06.0
22.07.06.0
Calculate the flexural tension stress.
psiftin
ftlbft
ftin
ftlb
S
M
A
P
nn
1.23/0.81
/18112
/0.30
/5.1141232
The allowable stress, Ft, is 25 psi, so the wall is adequate. Partition walls in SDC are required to have prescriptive seismic reinforcement in either the horizontal OR vertical direction in accordance with the following:
(a) Horizontal reinforcement — Two longitudinal wires of W1.7 (9 gage) bed joint reinforcement
spaced not more than 16 in. on center, or No. 4 bars spaced not more than 48 in. on center. Horizontal
reinforcement needs to be provided within 16 in. of the top and bottom of the wall.
(b) Vertical reinforcement —No. 4 bars spaced not more than 120 in. on center. Vertical
reinforcement needs to be provided within 16 in. of the ends of the wall.
It is recommended that W1.7 (9 gage) bed joint reinforcement at 16 in. (every other course) be provided to meet the prescriptive seismic requirements. Due to the permitted one‐third stress increase in the 2009 IBC (2008 MSJC), the allowable flexural tension stress would be the same, and this wall would be adequate using the 2009 IBC. The reaction at the top of wall, Rt, is:
9
ftlbft
psfh
wR Et /5.602
124.147.0
27.0
Sufficient anchors need to be provided at the top of wall to carry this force. If this partition wall were part of an egress stairway, the importance factor would be 1.5, which increases the seismic load, wE, to 21.6 psf, the moment to 272 ft‐lb/ft, and the flexural tensile stress to 36.5 psi. Unreinforced, ungrouted masonry will no longer work, even with Type S Portland cement lime mortar.
VERIFICAT The followunder varThe maximAll of the the result CASE A: mh = 12 ft HL = 40 lb/hL = 10 ft PL = 100 lbe = 6 in wE = 14.4
Rb
7.0
7.0
Is Rb < 0.7
Yes, 53.5l
hx0
Maximum
RM
5
max
TION OF STRU
wing examplerious loading mum momenother load cots are compar
maximum mom
/ft
b/ft
psf
p
hwE
2
4.147.05
2
7.05
75*0.7wEhL?
b/ft < 75.6 lb
w
R
E
b
7.075.0m moment occ
ftlb
xhRb
12/5.53
0
UCTURAL AN
es are verificaconditions. Tnt and the locombinations ared to a mom
ment occurs
ftpsf
h
hhH LL
4012
wE7.075.0/ft. Case A c
ft7.0
12
curs at 4.92 f
ftft
hwE
92.42
2
7.075.0
NALYSIS
tion of the stThe loads are ation of the mare subsets o
ment diagram.
below HL.
ft
ftftlb
h
ePL
12
12/0
hLE 075.0controls.
p
ftlb
4.147.075
/5.53
ft below top o
xh
17.075.0
2
10
tructural analnot necessarmaximum mof this. For ea
ft 1010
psf4.147.0
fpsf
92.4
of wall, or 7.0
fpsf
2
124.4
ysis of the simrily representoment are cheach of the fou
ft
fftlb
12
5.0/00
ft .7510
ft
08 ft up from t
ftft 92.4 2
mply supporttative of typicecked for Loaur cases of Loa
lb
ft5.53
ftlb /6
the bottom o
lbft189
ted vertical wcal partition load Combinatioad Combinati
ftb /
of the wall.
ftb /
all oads. on L. ion L,
CASE B: mh = 12 ft HL = 40 lb/hL = 5 ft PL = 100 lbe = 6 in wE = 14.4
Rb
7.0
7.0
Is 0.75*0.
7.075.0
w7.075.0Yes, 37.8l
hhx Maximum
RM
6
max
maximum mom
/ft
b/ft
psf
p
hwE
2
4.147.05
2
7.05
7wEhL ≤ Rb < 0
hw LE 75.0Hhw LLE
b/ft ≤ 66.0lb
fthL 512 m moment occ
fftlb
hR Lb
5/0.66
075.0
ment occurs a
ftpsf
h
hhH LL
4012
0.75(0.7wEhL+
p4.147.05
17.075.0/ft < 67.8 lb/f
ftft 7
curs at 7 ft be
ft
hw LE
7.075.0
2
7.0 2
at HL.
ft
ftftlb
h
ePL
12
12/0
+HL)?
ftpsf 375 ftpsf 54.14
ft. Case B co
elow top of w
psf
2
54.147
11
ft 1005
ftlb /8.7
ftlbt /40ontrols.
wall, or 5 ft up
f
ft235
2
ft
ftftlb
12
5.0/0
ftlb /8.67
p from the bo
ftlbft /
lb /0.66
ft
ottom of the w
ft/
wall.
CASE C: mh = 12 ft HL = 40 lb/hL = 3 ft PL = 100 lbe = 6 in wE = 14.4
Rb
7.0
7.0
Is 0.75(0.7
w7.075.0
w7.075.0Yes, 52.7l
Rhx
0
Maximum
ft
lb
RM
201
0.71
max
maximum mom
/ft
b/ft
psf
p
hwE
2
4.147.05
2
7.05
7wEhL+HL) <Rb
Hhw LLE Hhw LE
b/ft ≤ 71.0lb
w
HR
E
Lb
7.075.0
75.0
m moment occ
ftlb
ftft
xhRb
/
612/
0
ment occurs a
ftpsf
h
hhH LL
4012
b ≤ 0.75(0.7w
17.075.0 147.075.0
/ft < 120.7lb/
ft71
12
curs at 6.58 f
ft
wE
75.058.
2
7.075.0
above HL, but
ft
ftftlb
h
ePL
12
12/0
wEh+HL)?
ftpsf 34.14
ftpsf 124.4/ft. Case C co
ftlb
17.075.0
.0/0.1
ft below top o
ps
Hxh
L
4.147.05
2
2
12
t below top.
ft 1003
ftlbt /40 ftlbt /40ontrols.
psf
ftlb
4.14
/4075
of wall, or 5.4
ftsf
hxh LL
2
.612
ft
ftftlb
12
5.0/0
ftlb /7.52 flb /7.120
ft58.6
42 ft up from t
l
ft40
58 2
lb /0.71
ft
ft
the bottom o
ftftlb 12/
ft/
of the wall.
fft 358.6 ft
CASE D: mh = 12 ft HL = 20 lb/hL = 3 ft PL = 200 lbe = 48 in wE = 14.4
Rb
7.0
7.0
Is Rb > 0.7
w7.075.0Yes, 106.6Maximum
M 0max
maximum mo
/ft
b/ft
psf
p
hwE
2
4.147.05
2
7.05
75(0.7wEh+HL)
Hhw LE 6lb/ft > 105.7m moment occ
Pe 7.075.0
ment occurs
ftpsf
h
hhH LL
2012
)?
147.075.07lb/ft. Case Dcurs at top of
ftlb /20075
at top.
ft
ftftlb
h
ePL
12
12/0
ftpsf 124.4D controls. xf wall.
fft 6004
13
ft 2003
ftlbt /20x = 0
ftlbft /
ft
ftftlb
12
4/0
flb /7.105
lb /6.106
ft
ft