Application technology, 5th edition
Volume III:Fonterra radiant heating and cooling
Regulation components, manifolds and manifold cabinets
Fonterra Smart Control
System descriptionFonterra Smart Control is a completely new type of single room regulation in radiant heating and cooling; it carries out the hydraulic calibration required by law in a fully automated process, ensuring agreeable temperatures and opti-mum calibration of the heat distribution systems at all times.
The Fonterra Smart Control components are mounted ready-to-plug at the manifold in the concealed manifold cabinet.The owner can operate them via any WLAN-capable end device by means of the browser-based user interface.
Fig. 244: Operation via smartphone Fig. 245: Fonterra Smart Control components
Easy operation provides for maximum user comfort, for example quick-action heating for priority rooms, temperature preservation at floor level, or absence mode for energy saving.
Fig. 246: Temperature regulation Fig. 247: Individual heating profiles
Regulation components, manifolds and manifold cabinets | Fonterra Smart Control
297
Application technology: Fonterra radiant heating and cooling
Features ■ WLAN-capable complete system, can be parameterised from any lo-cation world-wide via smartphone, tablet or laptop (remote diagnosis available).
■ Easy mounting (ready to plug) and installation (plug & play); clean instal-lation without any cable laying.
■ Perfect for refurbishment and reconstruction ■ Automatic adjustment of the system to the prevailing conditions (floor covering, heating circuit lengths, screed heights and external heat sour-ces)
■ Individual demand-driven heat output with special functions, allowing for energy savings of up to 20%
■ Very fast reaction time without over- and undershooting ■ Five regulation parameters for permanent hydraulic calibration of the system
■ Attractive subsidies available from funding programs offered by German institutions Bafa and KfW
Fonterra Smart Control regulation strategyVia five regulation parameters, continuous precise compensation is perfor-med for each individual heating circuit, avoiding over- and undershooting of the regulation and the loss of energy and comfort. In addition to the supply temperature, the return temperature in every heating circuit and the three room temperature values are measured.
Fig. 248:
12
3
t Fast reaction time without over- and undershooting
Key① Fonterra Smart Control② Standard regulation③ Time advantage due to Fonterra Smart Control
Fast reaction time without over- and undershooting
298
System components
Main components
Fonterra Smart Control room thermostat
Fonterra Smart Control basic unit
Fonterra Smart Control temperature measuring
point
Fonterra Smart Control actuator module
Fonterra Smart Control actuator
Fonterra Smart Control WLAN module
Fonterra Smart Control radio amplifier
Accessories
Fonterra Smart Control power pack
Fonterra Smart Control connection line window contact
Fonterra Smart Control connection line RS 232
Fonterra Smart Control ribbon cable
Fonterra Smart Control Sensor
Fonterra Smart Control dewpoint sensor
Regulation components, manifolds and manifold cabinets | Fonterra Smart Control
299
Application technology: Fonterra radiant heating and cooling
Name Article number
Fonterra Smart Control room thermostat 734022 (black) / 734527 (white)
Fonterra Smart Control basic unit 734039
Fonterra Smart Control temperature measuring point 734459
Fonterra Smart Control actuator module 734046
Fonterra Smart Control actuator 734466
Fonterra Smart Control WLAN module 734473
Fonterra Smart Control radio amplifier 734480 (black) / 736453 (white)
Fonterra Smart Control power pack 734503
Fonterra Smart Control dewpoint sensor 734510
Fonterra Smart Control connection line window contact 741136
Fonterra Smart Control connection line RS 232 736460
Fonterra Smart Control ribbon cable 741204
Fonterra Smart Control sensor 741211
Tab. 119 System components
System compon-ents
300
Standard regulations
To meet the high requirements in function, residential comfort, cosiness and ease of operation of surface heating systems, the Viega system portfolio pro-vides a variety of regulation and control units.
Overview of regulation components
Room thermostats
Room thermostat 230 V
Art. no. 610 401
Room thermostat 24 V
Art. no. 610 418
Room thermostat 230 V
Art. no. 759 025
Basic units
Basic unit 230 V / 24 V
Art. no. 759 001
Basic unit 230 V with pump module
Art no. 759018
Actuators
Actuator 230 V Art. no. 696214
Actuator 24 V Art. no. 708887
Regulation components, manifolds and manifold cabinets | Standard regulations
301
Application technology: Fonterra radiant heating and cooling
Control stations
Compact control station Preset value
Art. no. 704889
Manifold control station Preset value
Art. no. 704896
Small surface control stationArt. no.684112
Multibox combi RTL
Art. no. 639310
Return temperature Limiter set
Art. no. 685171
Differential pressure regula-tor
Art. no. 719562
manifold
Manifold mod. 1005
Industry manifold mod. 1007
Manifold cabinets
Manifold cabinets, con-cealed
Installation depth 110-150 mm
mod. 1294
Manifold cabinets, con-cealed
Installation depth 80-110 mm mod. 1294.3
Manifold cabinets, wall-mounted
mod. 1294.1
302
Room thermostats
§ 14 (2) EnEV specifies that when installing heating systems using water as a heat carrier in buildings, devices for automatically controlling the temperature separately for each room must be provided.
Room thermostat 230 V / 24 V
Fig. 249: Room thermostat 230 V / 24 V
Electronic room thermostats in 230 V and 24 V versions detect the room tem-perature and control the supply of heat to the room.
Room thermostat 230 V 24 V
Operating voltage 230 V, 50 / 60 Hz 24 V AC, 50 / 60 Hz
Switching current 1.8 A (resistive load) 1.0 A (resistive load)
Switching capacity max. 10 actuators max. 5 actuators
Switching output Relay Triac
Normal operation 10–28 °C
Deviation from setpoint max. ± 0.5 K
Lowering through external switching signal approx. 2 K / 20 °C
IP Code IP 30
Protection class II III
Ambient temperature 0–50 °C
relative humidity max. 80 %
Dimensions H / W / D (mm) 82 / 82 / 26
Weight 69 g 62 g
CE conformity EN 60730
Casing colour Signal white
Terminal 5-pole
usable line cross-sections 5-wire 0.25–1.5 mm²
Mounting type Wall-mounted on socket
Art. no. room thermostat 610401 610418
Tab. 120 Technical data room thermostat
Room thermostat 230 V / 24 V
Technical data room thermostat
Regulation components, manifolds and manifold cabinets | Room thermostats
303
Application technology: Fonterra radiant heating and cooling
Clock thermostat 230 V
Fig. 250: Clock thermostat 230 V
Whereas room thermostats interrupt the power supply when the set room temperature is reached, clock thermostats furthermore allow the user to as-sign different heating intervals to individual rooms.
Clock thermostat 230 V
Operating voltage 230 V AC 50 Hz
Power supply via basic unit
Fuse T1AH
Contact element Relay
Switching capacity 1 A resistive load
Nominal current without drives ≤2 mA
Power consumption in idle state < 0.3 W
Setting range target temperature 5–30 °C
Temperature measurement 0–40 °C
Ambient temperature 0–50 °C
Lowering balance Can be set for night and day temperature
Correction actual-setpoint temperature measurement ± 2 °C
Change-Over input electronic/potential-free
Block cooling yes
Valve protection function every 14 days for 10 minutes
Ambient temperature: 0–50 °C
Storage temperature -20–70 °C
Admissible ambient humidity: 80% not condensed
CE conformity according to EN 60730
IP Code IP 20
Protection class II
Degree of contamination 2
Dimensions H / W / D 86 / 86 / 31 mm
Casing colour Signal white
Terminal 8 clamps 0.22–1.5 mm²
Weight 105 g
Mounting type Wall-mounted on socket
Art. no. room thermostat 759 025
Tab. 121 Technical data clock thermostat
a1 2 1 2
b c1 2 1 2
d
N/L
2
ext.
1ex
t. 2
CON
‘/L2‘
=>L/L1
N/L2
°C
L/L1>>>
Clock thermostat 230 V
Technical data Clock thermostat
304
Basic units
Basic units simplify mounting and wiring of the regulation components for comfortable single room regulation. They serve as interface and communica-tion point between actuator and room thermostat.
Basic unit 230 V / 24 V
Fig. 251: Basic unit 230 V / 24 V
Basic unit 230 V 24 V
Operating voltage 230 V, 50 Hz 24 V, 50 Hz
Power supply Euro plug via external voltage supply source
max. power consumption 50 VA 36 VA
Fuse T4AH T2A
Number of heating zones 6
No. of room thermostats max. 6
No. of actuators max. 15
Switch-on current per actuator max. 500 mA –
Nominal load of all drives max. 24 W
Direction of operation NC
Storage temperature -20–70 °C
Ambient temperature 0–50 °C
relative humidity 1) max. 80 %
Degree of contamination 2
ErP class acc. to EU 811/2013 1=1 %
Protection class II III
IP Code IP 20
Terminals screwless terminal technology 0.2–1.5 mm²
Connection line massive: YM-J / NYM-o (max. 5 x 1.5 mm²)flexible: H03V2V2H2-F / H05V2V2H2-F
Dimensions (H / L / D) 90 x 326.5 x 52 mm
CE conformity in acc. with EN 60730
Art. no. basic unit 759 001
Tab. 122: Technical data basic unit1) non-condensing
Basic unit 230 V / 24 V
Technical data basic unit
Regulation components, manifolds and manifold cabinets | Basic units
305
Application technology: Fonterra radiant heating and cooling
Fig. 252: Selection fuse 24 V or 230 V,
depending on operating mode.
Connection diagram
Fig. 253: Connection diagram for the basic units model 1246
~ Voltage source External system clock
Analogue controller Heating
Actuator
24 V
T2A T4AH
230 V
Selection 24 V or 230 V fuse
BA
HZ 1L/L1
=> => => => => =>N/L2
CO
L/L1
NC
0min 5min
TB
N/L2
NachlaufzeitShut-down delay
24V => T2A 230V => T4A H
CO
CO
90mm
8..9mm
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
HZ 2 HZ 3 HZ 4 HZ 5 HZ 6 HZ 7 HZ 8 HZ 9 HZ 10
L1‘24V L2‘ L1 L2230V N‘L‘ L N
NO
10min 15min
2 32 3
2 32 3
A
=>
N/L
2
A
A A A
=> =>
A B
=> =>
B B B B%H
L/L1
N/L
2L/
L1
~
viegaConnection dia-gram
306
Basic unit 230 V with pump module
Fig. 254: Basic unit heating/cooling
An existing changeover contact provides for external changeover between heating and cooling modes.
Basic unit 230 V with pump module
Operating voltage 230 V, 50 Hz
Power supply Euro plug via external power source
max. power consumption 50 VA
Fuse T4AH
Number of heating zones 6
No. of room thermostats max. 6
No. of actuators max. 15
Max. switch-on current per actuator 500 mA
Max. nominal load of all drives max. 24 W
Direction of operation NC
Storage temperature -20–70 °C
Ambient temperature 0–50 °C
relative humidity 1) max. 80 %
Degree of contamination 2
ErP class acc. to EU 811/2013 1=1 %
Protection class II
IP Code IP 20
Terminals screwless terminal technology 0.2–1.5 mm²
Connection line massive: YM-J / NYM-o (max. 5 x 1.5 mm²)flexible: H03V2V2H2-F / H05V2V2H2-F
Dimensions (H / L / D) 90 x 326.5 x 52 mm
CE conformity in acc. with EN 60730
Art. no. basic unit 759 001
Pump control yes
Tab. 123: Technical data basic unit heating/cooling1) Pump module with potential-free contact, via relay2) non-condensing
Basic unit heating/cooling
Technical data basic unit 230 V with pump module
Regulation components, manifolds and manifold cabinets | Basic units
307
Application technology: Fonterra radiant heating and cooling
Connection diagram
Fig. 255: Connection diagram for the basic unit model 1246.1
Digital controller Temperature limiter
Analogue controller System clock
Actuator CO Changeover contact
pump Cooling
~ Voltage source Heating
BA
HZ 1L/L1
=> => => => => =>N/L2
CO
L/L1
NC
0min 5min
TB
N/L2
NachlaufzeitShut-down delay
24V => T2A 230V => T4A H
CO
CO
90mm
8..9mm
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
L/L1
N/L2
CO
HZ 2 HZ 3 HZ 4 HZ 5 HZ 6 HZ 7 HZ 8 HZ 10
L1‘24V L2‘ L1 L2230V N‘L‘ L N
NO
10min 15min
2 32 3
2 32 3
A
=>
N/L
2
COA
A A A
=> =>
A B
=> =>
B B B B%H
L/L1
=>
N/L
2
AL/L1
%H
Mo Tu We Th Fr Sa Su
0 6 12 18 24
N/L
2L/
L1
CO
NL
~
viega
PE
N/L
2
L/L1
PE
Connection dia-gram
308
ActuatorsThermal actuators are available in the versions 230 V or 24 V, closed in de-energised state.
Fig. 256: Actuators
Actuator 230 V 24 V
Operating voltage 230 V AC 24 V AC
Switch-on current max. 200 mA 230 mA
Operating capacity 2 W
Opening and closing time < 5 minDisplacement > 3.5 mm
Pulling load 80 N +15 / -10 N
Ambient temperature max. 60 °C
Protection class 1) / IP Code IP 54/IICE conformity EN 60335
Casing colour RAL 9010
Version Closed in de-energized state
Weight approx. 100 g
Connection line 1 m 2 x 0.75 mm²Article no. 696214 708887
Tab. 124: Technical data
1) in all installation situations
Actuators
Technical data ac-tuators
Regulation components, manifolds and manifold cabinets | Basic units
309
Application technology: Fonterra radiant heating and cooling
Manifold control stations
Compact control station preset value The compact control station is used in heating systems whose heat output takes place on the one hand via consumers with a high supply temperature (e. g. radiators) and on the other hand via low-temperature heating surfaces (e. g. underfloor or wall heating).It has a mixer valve for regulating preset values without auxiliary energy and is used centrally to a maximum power requirement of 15 kW.
Fig. 257: Compact control station preset value
System benefits ■ High-efficiency pump ■ Thermometer in supply and return flow ■ Compact control station incl. insulating shell, ready for assembly ■ Three-way valve with preset value regulation without auxiliary energy ■ Maximum temperature limiter ■ With gravity brake
Compact control station preset value
310
Dimension DN25
Wilo high-efficiency pump Yonos PARA RS 25 / 6 RKA
Maximum permitted operating tempera-ture 95 °C
Minimum permitted operating tempera-ture 1) -20 °C
Maximum permitted operating pressure 1 MPa (10 bar)
Nominal heating capacity 15 kW
Power consumption pump 3–45 W
Delivery height pump max. 6.2 m
Flow volume pump max. 3.3 m³ / h
Height incl. insulating shell 355 mm
Width incl. insulating shell 250 mm
Depth incl. insulating shell with wall bracket
190 mm235 mm
Screw fitting flat sealing R 1½ inch
Art. no. control station 704889
Tab. 125: Technical data
1) With fluid temperatures below 20 °C, take potential condensation into consideration. Furthermore, use suitable cooling brines if the temperature of the fluid drops below the water freezing point.
Fig. 258: Pump diagram compact control station
Technical data
-c (constant)
00
011
022
033
044
055
066
0 0,5 1,0 1,5 2,0 2,5 3,0
H/m
Q/m³/h
p/kPaPump diagram compact control station
Regulation components, manifolds and manifold cabinets | Manifold control stations
311
Application technology: Fonterra radiant heating and cooling
Manifold control station preset value
Since the maximum floor surface temperature is limited by standards and by building physics (to 29 °C in living rooms, 33 °C in bathrooms and 40 °C for wall heatings), the supply temperature must be kept at a correspondingly low value. In systems with high supply temperatures, this can for example be achieved by so-called manifold control stations. They monitor the supply temperature and prevent overheating of the heating surface by closing a valve. To achieve the nominal heating capacity, the pressure difference between the boiler cir-cuit and the surface heating must be minimum 200 hPa.
Fig. 259: Manifold control station ‒ preset value
System benefits ■ Compact preset value manifold station incl. ball valve and 1-inch double nipple set, ready for assembly
■ High-efficiency pump and maximum temperature limiter are factory wi-red.
■ Can be mounted to the manifold on the left or right side
Fig. 260: Mounting to the manifold model 1005
When installing the preset value control station, ensure that the supply/return flow manifold bars are mounted according to the enclosed mounting instructions (return flow bottom position/sup-ply flow top position).
Manifold control station preset value
Mounting to the manifold model 1005
312
Dimension DN 20
Maximum permitted operating tempera-ture 1) 80 °C
Minimum permitted operating tempera-ture 2) -10 °C
Maximum permitted operating pressure 0.6 MPa (6 bar)
Control range 20–70 °C
Power consumption pump 3–45 W
Delivery height pump max. 6.2 m
Flow volume pump max. 3.3 m³ / h
Height 328 mm
Width 192 mm
Connections, flat sealing R 1 inch
Nominal heating capacity approx. 14 kW
Wilo high-efficiency pump Yonos PARA RS15 / 6 RKA FS130
Art. no. constant temperature control sta-tion 704896
Tab. 126: Technical data
1) boiler side2) With use of suitable anti-freeze. For the permissible minimum operating temperatures of
the circulation pumps, see the manufacturer's information.
Fig. 261: Pump diagram preset value control station
Technical data
-c (constant)
00
011
022
033
044
055
066
0 0,5 1,0 1,5 2,0 2,5 3,0
H/m
Q/m³/h
p/kPaPump diagram preset value con-trol station
Regulation components, manifolds and manifold cabinets | Manifold control stations
313
Application technology: Fonterra radiant heating and cooling
Small surface control station
Fig. 262: Small surface control station
The small surface control station is intended for regulating the supply tempe-rature of surface heating systems at a preselected fixed target value.The target value can be set continuously between 20 and 70 °C at the ther-mostat head. The small surface control station is used in systems whose con-sumers (e. g. radiators) are replaced by low-temperature heating surfaces.The supply temperature of the heating circuits is kept constant in the small surface control station by controlled addition of hot water from the heat ge-nerator. The target value for the supply temperature is set at the thermostat head. In case of malfunction, an additional temperature limiter switches the pump off when overtemperature of the fluid is present, thus preventing dama-ge to the surface heating.If the small surface control station is to be regulated additionally via a target value (room temperature), we recommend to use a thermostat valve in combi-nation with a basic unit.
System benefits ■ Readily mounted and wired in the built-in cabinet ■ For heating areas up to 40 m² ■ Suitable for up to 4 heating circuits ■ Incl. Wilo high-efficiency pump ■ Temperature regulation for an individual room can be connected via room thermostat and actuator.
■ Concealed manifold cabinet for pre-wall systems
Small surface con-trol station
314
Dimension DN15
Maximum permitted operating tempera-ture 80 °C
Maximum permitted operating pressure 0.6 MPa (6 bar)
Control range 20–70 °C
Height approx. 480 mm
Width approx. 430 mm
Depth approx. 115 mm
Euro cone connections R ¾ inch
Wilo high-efficiency pump Yonos PARA RS15 / 6 RKA FS130
Pump capacity 9–63 W
Nominal heating capacity max. 3 kW
Art. no. small surface control station 684112
Tab. 127: Technical data
Fig. 263: Performance diagram small surface control station
Key① Residual delivery height② Flow volumeLevels (residual delivery height): a = level 1 b = level 2 c = level 3 d = level 4 e = level 5 f = level 6 g = level 7
Technical data
[hPa]
1
2
ab
c
d
e
f
g
Residual deli-very height small surface control station Kvs = 2.47 m3/h
Regulation components, manifolds and manifold cabinets | Manifold control stations
315
Application technology: Fonterra radiant heating and cooling
Differential pressure regulator
Fig. 264: Differential pressure regulator
The intactness of the hydraulics of the system is an important precondition for its regulation behaviour. A decentralised dynamic differential pressure re-gulation is required because the mass flows vary due to the constantly chan-ging conditions.The differential pressure regulator is a high-performance differential pressure regulator which keeps the differential pressure constant via the load. Thanks to the pressure-relieved valve cone, an accurate differential pressure regulati-on is possible; the integrated locking function makes maintenance easy.Please observe the enclosed instructions for use regarding flow direction, ins-tallation situation etc.
Differential pressure regulator
Lockable yes
Dimension DN25
Pressure class PN 16
Max. differential pressure (∆pv) 250 kPa
Setting range (∆p) 10*–60 kPa
Permitted operating temperature -20–120 °C
Height 141 mm
Length 93 mm
Diameter of pipe connection G1
Tab. 128: Technical data, differential pressure regulator (*factory setting)
Circulation regulation valve
Lockable yes
Dimension DN25
Pressure class PN 20
Permitted operating temperature -20–120 °C
Height 105 mm
Length 110 mm
Diameter of pipe connection G1
Tab. 129:Technical data, circulation regulation valve
Differential pres-sure regulator
Technical data, differential pres-sure regulator
Technical data, circulation regula-tion valve
316
Installation situationsThe circulation regulation valve is installed in the supply line, the differential pressure regulator in the return flow in the specified flow direction. The top of the differential pressure regulator is rotatable.
Fig. 265: Installation position A
Fig. 266: Installation position B
Installation posi-tion A
Installation posi-tion B
Regulation components, manifolds and manifold cabinets | Manifold control stations
317
Application technology: Fonterra radiant heating and cooling
Heat meter set
Fig. 267: Heat meter set, vertical
Fig. 268: Heat meter set, vertical Fig. 269: Heat meter set, horizontal
To record the quantities of heat used, heat flow meters must be installed in larger housing units.They are adjusted for use in surface heating manifolds and suitable for com-mercially available heat flow meters with installation lengths 110 or 130 mm.
Heat meter set
Installation length G ¾ inch 110 mm
Installation length G 1 inch 130 mm
max operating pressure 1 MPa
max. operating temperature 95 °C
External thread G1 inch
Connection of measuring probe Ø 5.6 mm, M10
Tab. 130: Technical data, heat meter set
109
35
G1
G1
23
3
10
8
Heat meter set
194
69
G1
G1
Technical data
318
Manifold
Manifold DN25
Fig. 270: Manifold DN25 (model 1005)
Features ■ Stainless steel with union nut DN25 ■ Connection can be made on left or right side ■ Flow sensor in supply line, can be locked individually and adjusted from 0 to 5 l/min
■ Suitable for actuators M 30 x 1.5 ■ Manifold incl. fan, plug, and KFE taps ■ Heating circuit connection ¾ inch euro cone ■ incl. wall brackets ■ End cap ¾ inch
Fig. 271: Stainless steel manifold 1 inch, with flow sensor, without thermometer
Manifold DN25
Stainless steel ma-nifold 1 inch with flow sensor, wit-hout thermometer
Regulation components, manifolds and manifold cabinets | Manifold
319
Application technology: Fonterra radiant heating and cooling
Manifold lengths
HC [number] 2 3 4 5 6 7 8 9 10 11 12
L1 [mm] 50
L2 [mm] 242 242 292 342 392 442 492 542 592 642 692
Tab. 131: Dimensions model 1005
As accessory to a manifold outlet, an extension set model 1005.2 is available. Please take the larger installation length in the conce-aled manifold cabinet into consideration.
industry manifold
Viega industry manifolds are suitable for use in heating systems according to DIN EN 12828 for connection of heating circuits under the specified operating conditions.The manifold can be mounted in vertical position, with outlet facing up or down, or in horizontal position at a storey floor.
Fig. 272: Industry manifold 1½ inch with regulating spindle (model 1007)
Features ■ Stainless steel manifold trunk 1½ inch flat sealing ■ Heating circuit connection ¾ inch Rp thread ■ Regulation valves with locking function in the supply line ■ Return flow locking for each heating circuit ■ Including KFE taps
Dimensions model 1005
Industry manifold 1½ inch with regu-lating spindle
320
Fig. 273: Dimensions of industry manifolds
Art. no. Outlets L (mm)
L1 (mm)
Kvs value (m³ / h)
620806 4 395 380 6,52
620813 5 475 460 7,74
620820 6 555 540 8,95
620837 7 635 620 10,14
620844 8 715 700 11,33
621957 9 795 780 12,52
921964 10 875 860 13,7
621971 11 955 940 14,87
621988 12 1035 1020 15,93
621995 13 1115 1100 16,98
622008 14 1195 1180 17,95
622015 15 1275 1260 18,83
622022 16 1355 1340 19,66
Tab. 132: Dimensions
Dimensions of industry manifolds
Dimensions
Regulation components, manifolds and manifold cabinets | Manifold
321
Application technology: Fonterra radiant heating and cooling
Kv value (m³ / h) Kvs value
(m³ / h)Number of revolutions (U)
0,25 0,5 1 1,5 2 2,5 3 3,5
0,22 0,37 0,62 0,92 1,27 1,55 1,72 1,85 1,93
Tab. 133: Target values of the valves
Fig. 274: Flowthrough diagram
Key ① Pressure loss ∆p [kPa]② Mass flow m [kg/h]③ Pressure loss ∆p [hPa]④ Number of revolutions [U]
Target values of the valves
4 [U]
1[kPa]
2 [kg/h]
3[hPa]
Flow diagram
322
Manifold cabinets
The manifold cabinets house not only the manifolds but also actuators, ball valves, basic units or other regulation devices. The cabinet allows for quick mounting of and easy access to the compo-nents.
Wall-mounted manifold cabinetMade of galvanised sheet steel, frame and door painted (colour pure white RAL 9016) with an installation depth of 140 mm, five cabinet widths available.
Features ■ Suitable for manifold DN25 ■ Height-adjustable from 630-790 mm ■ incl. universal bracket for manifold
Fig. 275: Wall-mounted manifold cabinet Fig. 276: Dimensions
Type T L2
460
140 mm
490 mm
560 575 mm
700 725 mm
1000 1025 mm
1200 1175 mm
Tab. 134: Dimensions model 1294.1
Dimensions model 1294.1
Regulation components, manifolds and manifold cabinets | Manifold cabinets
323
Application technology: Fonterra radiant heating and cooling
Mo
del
129
4.1
Man
ifold
co
nnec
tio
n ve
rtic
al
Hea
t flo
w m
eter
ve
rtic
al
Diff
eren
tial
pre
ssur
e re
gu-
lato
r +
heat
flo
w m
eter
ver
tica
l
Diff
eren
tial
pre
ssur
e re
gu-
lato
r +
vert
ical
co
nnec
tio
n
Man
ifold
co
nnec
tio
n +
zo
ne v
alve
Man
ifold
co
nnec
tio
n +
co
ntro
l sta
tio
n m
od
el
1254
.2
Type
460 ≤ 3 ≤ 3
560 ≤ 5 ≤ 5 ≤ 4 ≤ 4 ≤ 4
700 ≤ 8 ≤ 8 ≤ 4 ≤ 7 ≤ 7 ≤ 7
1000 ≤ 12 ≤ 12 ≤ 10 ≤ 12 ≤ 12 ≤ 12
1200 ≤ 12
Tab. 135: Manifold selection table model 1294.1
Concealed manifold cabinetMade of galvanised steel sheet, frame and door painted (colour: traffic white RAL 9016), with an installation depth of 110 to 150 mm, in five cabinet widths.
Features ■ Suitable for manifold DN25 ■ Height-adjustable from 675 to 855 mm ■ incl. universal bracket for manifold
Fig. 277: Concealed manifold cabinet Fig. 278: Dimensions
Manifold selection table model 1294.1
324
Type T L1 L2
460
110–150mm
450 mm 510 mm
560 535 mm 595 mm
700 685 mm 745 mm
1000 985 mm 1045 mm
1200 1135 mm 1195 mm
Tab. 136: Dimensions model 1294
Mo
del
129
4
Man
ifold
co
nnec
tio
n ho
rizo
n-ta
l
Man
ifold
co
nnec
tio
n ve
rtic
al
Man
ifold
co
nnec
tio
n +
zone
va
lve
hori
zont
al
Man
ifold
co
nnec
tio
n +
he
at f
low
met
er h
ori
zont
al
Man
ifold
co
nnec
tio
n +
d
iffer
enti
al p
ress
ure
reg
ulat
or
hori
zont
al
Man
ifold
co
nnec
tio
n +
diff
e-re
ntia
l pre
ssur
e re
gul
ato
r +
heat
flo
w m
eter
ho
rizo
ntal
Man
ifold
co
nnec
tio
n +
cont
rol s
tati
on
mo
del
125
4.2
Type
460 ≤ 5 ≤ 3 ≤ 4 ≤ 2
560 ≤ 7 ≤ 5 ≤ 6 ≤ 4 ≤ 5 ≤ 3
700 ≤ 10 ≤ 8 ≤ 9 ≤ 7 ≤ 7 ≤ 3 ≤ 6
1000 ≤ 12 ≤ 12 ≤ 12 ≤ 12 ≤ 12 ≤ 9 ≤ 12
1200 ≤ 12
Tab. 137: Manifold selection table model 1294
Dimensions model 1294
Manifold selection table model 1294
Regulation components, manifolds and manifold cabinets | Manifold cabinets
325
Application technology: Fonterra radiant heating and cooling
Concealed manifold cabinet 80 mm
Made of galvanised steel sheet, frame and door painted (colour: pure white RAL 9016), with an installation depth of 80 to 110 mm, in five cabinet widths.
Features ■ Suitable for manifold DN25 ■ Height-adjustable from 675 to 855 mm ■ incl. universal bracket for manifold
The concealed box model 1294.3 with an adjustable installation depth of 80-110 mm is suitable for use in drywalls.
Fig. 279: Concealed manifold cabinet Fig. 280: Dimensions
Type T L1 L2
460
80–110 mm
450 mm 510
560 535 mm 595
700 685 mm 745
1000 985 mm 1045
1200 1135 mm 1195
Tab. 138: Dimensions model 1294.3
Model 1294.3Type
Manifold connec-tion
horizontal
Manifold connec-tion
vertical
Manifold connec-tion + zone valve
horizontal
460 ≤ 5 ≤ 3 ≤ 4
560 ≤ 7 ≤ 5 ≤ 6
700 ≤ 10 ≤ 8 ≤ 9
1000 ≤ 12 ≤ 12 ≤ 12
1200
Tab. 139: Manifold selection table model 1294.3
Dimensions model 1294.3
Manifold selection table model 1294.3
326
INT ∙ 709 365 ∙ 2018-05 ∙ VPN 170369
Viega Technology GmbH & Co. KGViega Platz 157439 AttendornGermany
Phone +49 (0) 2722 61-0