+ All Categories
Home > Documents > Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection...

Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection...

Date post: 08-Aug-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
32
Application technology, 5th edition Volume III: Fonterra radiant heating and cooling
Transcript
Page 1: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology, 5th edition

Volume III:Fonterra radiant heating and cooling

Page 2: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Regulation components, manifolds and manifold cabinets

Fonterra Smart Control

System descriptionFonterra Smart Control is a completely new type of single room regulation in radiant heating and cooling; it carries out the hydraulic calibration required by law in a fully automated process, ensuring agreeable temperatures and opti-mum calibration of the heat distribution systems at all times.

The Fonterra Smart Control components are mounted ready-to-plug at the manifold in the concealed manifold cabinet.The owner can operate them via any WLAN-capable end device by means of the browser-based user interface.

Fig. 244: Operation via smartphone Fig. 245: Fonterra Smart Control components

Easy operation provides for maximum user comfort, for example quick-action heating for priority rooms, temperature preservation at floor level, or absence mode for energy saving.

Fig. 246: Temperature regulation Fig. 247: Individual heating profiles

Regulation components, manifolds and manifold cabinets | Fonterra Smart Control

297

Page 3: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Features ■ WLAN-capable complete system, can be parameterised from any lo-cation world-wide via smartphone, tablet or laptop (remote diagnosis available).

■ Easy mounting (ready to plug) and installation (plug & play); clean instal-lation without any cable laying.

■ Perfect for refurbishment and reconstruction ■ Automatic adjustment of the system to the prevailing conditions (floor covering, heating circuit lengths, screed heights and external heat sour-ces)

■ Individual demand-driven heat output with special functions, allowing for energy savings of up to 20%

■ Very fast reaction time without over- and undershooting ■ Five regulation parameters for permanent hydraulic calibration of the system

■ Attractive subsidies available from funding programs offered by German institutions Bafa and KfW

Fonterra Smart Control regulation strategyVia five regulation parameters, continuous precise compensation is perfor-med for each individual heating circuit, avoiding over- and undershooting of the regulation and the loss of energy and comfort. In addition to the supply temperature, the return temperature in every heating circuit and the three room temperature values are measured.

Fig. 248:

12

3

t Fast reaction time without over- and undershooting

Key① Fonterra Smart Control② Standard regulation③ Time advantage due to Fonterra Smart Control

Fast reaction time without over- and undershooting

298

Page 4: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

System components

Main components

Fonterra Smart Control room thermostat

Fonterra Smart Control basic unit

Fonterra Smart Control temperature measuring

point

Fonterra Smart Control actuator module

Fonterra Smart Control actuator

Fonterra Smart Control WLAN module

Fonterra Smart Control radio amplifier

Accessories

Fonterra Smart Control power pack

Fonterra Smart Control connection line window contact

Fonterra Smart Control connection line RS 232

Fonterra Smart Control ribbon cable

Fonterra Smart Control Sensor

Fonterra Smart Control dewpoint sensor

Regulation components, manifolds and manifold cabinets | Fonterra Smart Control

299

Page 5: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Name Article number

Fonterra Smart Control room thermostat 734022 (black) / 734527 (white)

Fonterra Smart Control basic unit 734039

Fonterra Smart Control temperature measuring point 734459

Fonterra Smart Control actuator module 734046

Fonterra Smart Control actuator 734466

Fonterra Smart Control WLAN module 734473

Fonterra Smart Control radio amplifier 734480 (black) / 736453 (white)

Fonterra Smart Control power pack 734503

Fonterra Smart Control dewpoint sensor 734510

Fonterra Smart Control connection line window contact 741136

Fonterra Smart Control connection line RS 232 736460

Fonterra Smart Control ribbon cable 741204

Fonterra Smart Control sensor 741211

Tab. 119 System components

System compon-ents

300

Page 6: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Standard regulations

To meet the high requirements in function, residential comfort, cosiness and ease of operation of surface heating systems, the Viega system portfolio pro-vides a variety of regulation and control units.

Overview of regulation components

Room thermostats

Room thermostat 230 V

Art. no. 610 401

Room thermostat 24 V

Art. no. 610 418

Room thermostat 230 V

Art. no. 759 025

Basic units

Basic unit 230 V / 24 V

Art. no. 759 001

Basic unit 230 V with pump module

Art no. 759018

Actuators

Actuator 230 V Art. no. 696214

Actuator 24 V Art. no. 708887

Regulation components, manifolds and manifold cabinets | Standard regulations

301

Page 7: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Control stations

Compact control station Preset value

Art. no. 704889

Manifold control station Preset value

Art. no. 704896

Small surface control stationArt. no.684112

Multibox combi RTL

Art. no. 639310

Return temperature Limiter set

Art. no. 685171

Differential pressure regula-tor

Art. no. 719562

manifold

Manifold mod. 1005

Industry manifold mod. 1007

Manifold cabinets

Manifold cabinets, con-cealed

Installation depth 110-150 mm

mod. 1294

Manifold cabinets, con-cealed

Installation depth 80-110 mm mod. 1294.3

Manifold cabinets, wall-mounted

mod. 1294.1

302

Page 8: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Room thermostats

§ 14 (2) EnEV specifies that when installing heating systems using water as a heat carrier in buildings, devices for automatically controlling the temperature separately for each room must be provided.

Room thermostat 230 V / 24 V

Fig. 249: Room thermostat 230 V / 24 V

Electronic room thermostats in 230 V and 24 V versions detect the room tem-perature and control the supply of heat to the room.

Room thermostat 230 V 24 V

Operating voltage 230 V, 50 / 60 Hz 24 V AC, 50 / 60 Hz

Switching current 1.8 A (resistive load) 1.0 A (resistive load)

Switching capacity max. 10 actuators max. 5 actuators

Switching output Relay Triac

Normal operation 10–28 °C

Deviation from setpoint max. ± 0.5 K

Lowering through external switching signal approx. 2 K / 20 °C

IP Code IP 30

Protection class II III

Ambient temperature 0–50 °C

relative humidity max. 80 %

Dimensions H / W / D (mm) 82 / 82 / 26

Weight 69 g 62 g

CE conformity EN 60730

Casing colour Signal white

Terminal 5-pole

usable line cross-sections 5-wire 0.25–1.5 mm²

Mounting type Wall-mounted on socket

Art. no. room thermostat 610401 610418

Tab. 120 Technical data room thermostat

Room thermostat 230 V / 24 V

Technical data room thermostat

Regulation components, manifolds and manifold cabinets | Room thermostats

303

Page 9: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Clock thermostat 230 V

Fig. 250: Clock thermostat 230 V

Whereas room thermostats interrupt the power supply when the set room temperature is reached, clock thermostats furthermore allow the user to as-sign different heating intervals to individual rooms.

Clock thermostat 230 V

Operating voltage 230 V AC 50 Hz

Power supply via basic unit

Fuse T1AH

Contact element Relay

Switching capacity 1 A resistive load

Nominal current without drives ≤2 mA

Power consumption in idle state < 0.3 W

Setting range target temperature 5–30 °C

Temperature measurement 0–40 °C

Ambient temperature 0–50 °C

Lowering balance Can be set for night and day temperature

Correction actual-setpoint temperature measurement ± 2 °C

Change-Over input electronic/potential-free

Block cooling yes

Valve protection function every 14 days for 10 minutes

Ambient temperature: 0–50 °C

Storage temperature -20–70 °C

Admissible ambient humidity: 80% not condensed

CE conformity according to EN 60730

IP Code IP 20

Protection class II

Degree of contamination 2

Dimensions H / W / D 86 / 86 / 31 mm

Casing colour Signal white

Terminal 8 clamps 0.22–1.5 mm²

Weight 105 g

Mounting type Wall-mounted on socket

Art. no. room thermostat 759 025

Tab. 121 Technical data clock thermostat

a1 2 1 2

b c1 2 1 2

d

N/L

2

ext.

1ex

t. 2

CON

‘/L2‘

=>L/L1

N/L2

°C

L/L1>>>

Clock thermostat 230 V

Technical data Clock thermostat

304

Page 10: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Basic units

Basic units simplify mounting and wiring of the regulation components for comfortable single room regulation. They serve as interface and communica-tion point between actuator and room thermostat.

Basic unit 230 V / 24 V

Fig. 251: Basic unit 230 V / 24 V

Basic unit 230 V 24 V

Operating voltage 230 V, 50 Hz 24 V, 50 Hz

Power supply Euro plug via external voltage supply source

max. power consumption 50 VA 36 VA

Fuse T4AH T2A

Number of heating zones 6

No. of room thermostats max. 6

No. of actuators max. 15

Switch-on current per actuator max. 500 mA –

Nominal load of all drives max. 24 W

Direction of operation NC

Storage temperature -20–70 °C

Ambient temperature 0–50 °C

relative humidity 1) max. 80 %

Degree of contamination 2

ErP class acc. to EU 811/2013 1=1 %

Protection class II III

IP Code IP 20

Terminals screwless terminal technology 0.2–1.5 mm²

Connection line massive: YM-J / NYM-o (max. 5 x 1.5 mm²)flexible: H03V2V2H2-F / H05V2V2H2-F

Dimensions (H / L / D) 90 x 326.5 x 52 mm

CE conformity in acc. with EN 60730

Art. no. basic unit 759 001

Tab. 122: Technical data basic unit1) non-condensing

Basic unit 230 V / 24 V

Technical data basic unit

Regulation components, manifolds and manifold cabinets | Basic units

305

Page 11: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Fig. 252: Selection fuse 24 V or 230 V,

depending on operating mode.

Connection diagram

Fig. 253: Connection diagram for the basic units model 1246

~ Voltage source External system clock

Analogue controller Heating

Actuator

24 V

T2A T4AH

230 V

Selection 24 V or 230 V fuse

BA

HZ 1L/L1

=> => => => => =>N/L2

CO

L/L1

NC

0min 5min

TB

N/L2

NachlaufzeitShut-down delay

24V => T2A 230V => T4A H

CO

CO

90mm

8..9mm

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

HZ 2 HZ 3 HZ 4 HZ 5 HZ 6 HZ 7 HZ 8 HZ 9 HZ 10

L1‘24V L2‘ L1 L2230V N‘L‘ L N

NO

10min 15min

2 32 3

2 32 3

A

=>

N/L

2

A

A A A

=> =>

A B

=> =>

B B B B%H

L/L1

N/L

2L/

L1

~

viegaConnection dia-gram

306

Page 12: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Basic unit 230 V with pump module

Fig. 254: Basic unit heating/cooling

An existing changeover contact provides for external changeover between heating and cooling modes.

Basic unit 230 V with pump module

Operating voltage 230 V, 50 Hz

Power supply Euro plug via external power source

max. power consumption 50 VA

Fuse T4AH

Number of heating zones 6

No. of room thermostats max. 6

No. of actuators max. 15

Max. switch-on current per actuator 500 mA

Max. nominal load of all drives max. 24 W

Direction of operation NC

Storage temperature -20–70 °C

Ambient temperature 0–50 °C

relative humidity 1) max. 80 %

Degree of contamination 2

ErP class acc. to EU 811/2013 1=1 %

Protection class II

IP Code IP 20

Terminals screwless terminal technology 0.2–1.5 mm²

Connection line massive: YM-J / NYM-o (max. 5 x 1.5 mm²)flexible: H03V2V2H2-F / H05V2V2H2-F

Dimensions (H / L / D) 90 x 326.5 x 52 mm

CE conformity in acc. with EN 60730

Art. no. basic unit 759 001

Pump control yes

Tab. 123: Technical data basic unit heating/cooling1) Pump module with potential-free contact, via relay2) non-condensing

Basic unit heating/cooling

Technical data basic unit 230 V with pump module

Regulation components, manifolds and manifold cabinets | Basic units

307

Page 13: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Connection diagram

Fig. 255: Connection diagram for the basic unit model 1246.1

Digital controller Temperature limiter

Analogue controller System clock

Actuator CO Changeover contact

pump Cooling

~ Voltage source Heating

BA

HZ 1L/L1

=> => => => => =>N/L2

CO

L/L1

NC

0min 5min

TB

N/L2

NachlaufzeitShut-down delay

24V => T2A 230V => T4A H

CO

CO

90mm

8..9mm

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

L/L1

N/L2

CO

HZ 2 HZ 3 HZ 4 HZ 5 HZ 6 HZ 7 HZ 8 HZ 10

L1‘24V L2‘ L1 L2230V N‘L‘ L N

NO

10min 15min

2 32 3

2 32 3

A

=>

N/L

2

COA

A A A

=> =>

A B

=> =>

B B B B%H

L/L1

=>

N/L

2

AL/L1

%H

Mo Tu We Th Fr Sa Su

0 6 12 18 24

N/L

2L/

L1

CO

NL

~

viega

PE

N/L

2

L/L1

PE

Connection dia-gram

308

Page 14: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

ActuatorsThermal actuators are available in the versions 230 V or 24 V, closed in de-energised state.

Fig. 256: Actuators

Actuator 230 V 24 V

Operating voltage 230 V AC 24 V AC

Switch-on current max. 200 mA 230 mA

Operating capacity 2 W

Opening and closing time < 5 minDisplacement > 3.5 mm

Pulling load 80 N +15 / -10 N

Ambient temperature max. 60 °C

Protection class 1) / IP Code IP 54/IICE conformity EN 60335

Casing colour RAL 9010

Version Closed in de-energized state

Weight approx. 100 g

Connection line 1 m 2 x 0.75 mm²Article no. 696214 708887

Tab. 124: Technical data

1) in all installation situations

Actuators

Technical data ac-tuators

Regulation components, manifolds and manifold cabinets | Basic units

309

Page 15: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Manifold control stations

Compact control station preset value The compact control station is used in heating systems whose heat output takes place on the one hand via consumers with a high supply temperature (e. g. radiators) and on the other hand via low-temperature heating surfaces (e. g. underfloor or wall heating).It has a mixer valve for regulating preset values without auxiliary energy and is used centrally to a maximum power requirement of 15 kW.

Fig. 257: Compact control station preset value

System benefits ■ High-efficiency pump ■ Thermometer in supply and return flow ■ Compact control station incl. insulating shell, ready for assembly ■ Three-way valve with preset value regulation without auxiliary energy ■ Maximum temperature limiter ■ With gravity brake

Compact control station preset value

310

Page 16: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Dimension DN25

Wilo high-efficiency pump Yonos PARA RS 25 / 6 RKA

Maximum permitted operating tempera-ture 95 °C

Minimum permitted operating tempera-ture 1) -20 °C

Maximum permitted operating pressure 1 MPa (10 bar)

Nominal heating capacity 15 kW

Power consumption pump 3–45 W

Delivery height pump max. 6.2 m

Flow volume pump max. 3.3 m³ / h

Height incl. insulating shell 355 mm

Width incl. insulating shell 250 mm

Depth incl. insulating shell with wall bracket

190 mm235 mm

Screw fitting flat sealing R 1½ inch

Art. no. control station 704889

Tab. 125: Technical data

1) With fluid temperatures below 20 °C, take potential condensation into consideration. Furthermore, use suitable cooling brines if the temperature of the fluid drops below the water freezing point.

Fig. 258: Pump diagram compact control station

Technical data

-c (constant)

00

011

022

033

044

055

066

0 0,5 1,0 1,5 2,0 2,5 3,0

H/m

Q/m³/h

p/kPaPump diagram compact control station

Regulation components, manifolds and manifold cabinets | Manifold control stations

311

Page 17: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Manifold control station preset value

Since the maximum floor surface temperature is limited by standards and by building physics (to 29 °C in living rooms, 33 °C in bathrooms and 40 °C for wall heatings), the supply temperature must be kept at a correspondingly low value. In systems with high supply temperatures, this can for example be achieved by so-called manifold control stations. They monitor the supply temperature and prevent overheating of the heating surface by closing a valve. To achieve the nominal heating capacity, the pressure difference between the boiler cir-cuit and the surface heating must be minimum 200 hPa.

Fig. 259: Manifold control station ‒ preset value

System benefits ■ Compact preset value manifold station incl. ball valve and 1-inch double nipple set, ready for assembly

■ High-efficiency pump and maximum temperature limiter are factory wi-red.

■ Can be mounted to the manifold on the left or right side

Fig. 260: Mounting to the manifold model 1005

When installing the preset value control station, ensure that the supply/return flow manifold bars are mounted according to the enclosed mounting instructions (return flow bottom position/sup-ply flow top position).

Manifold control station preset value

Mounting to the manifold model 1005

312

Page 18: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Dimension DN 20

Maximum permitted operating tempera-ture 1) 80 °C

Minimum permitted operating tempera-ture 2) -10 °C

Maximum permitted operating pressure 0.6 MPa (6 bar)

Control range 20–70 °C

Power consumption pump 3–45 W

Delivery height pump max. 6.2 m

Flow volume pump max. 3.3 m³ / h

Height 328 mm

Width 192 mm

Connections, flat sealing R 1 inch

Nominal heating capacity approx. 14 kW

Wilo high-efficiency pump Yonos PARA RS15 / 6 RKA FS130

Art. no. constant temperature control sta-tion 704896

Tab. 126: Technical data

1) boiler side2) With use of suitable anti-freeze. For the permissible minimum operating temperatures of

the circulation pumps, see the manufacturer's information.

Fig. 261: Pump diagram preset value control station

Technical data

-c (constant)

00

011

022

033

044

055

066

0 0,5 1,0 1,5 2,0 2,5 3,0

H/m

Q/m³/h

p/kPaPump diagram preset value con-trol station

Regulation components, manifolds and manifold cabinets | Manifold control stations

313

Page 19: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Small surface control station

Fig. 262: Small surface control station

The small surface control station is intended for regulating the supply tempe-rature of surface heating systems at a preselected fixed target value.The target value can be set continuously between 20 and 70 °C at the ther-mostat head. The small surface control station is used in systems whose con-sumers (e. g. radiators) are replaced by low-temperature heating surfaces.The supply temperature of the heating circuits is kept constant in the small surface control station by controlled addition of hot water from the heat ge-nerator. The target value for the supply temperature is set at the thermostat head. In case of malfunction, an additional temperature limiter switches the pump off when overtemperature of the fluid is present, thus preventing dama-ge to the surface heating.If the small surface control station is to be regulated additionally via a target value (room temperature), we recommend to use a thermostat valve in combi-nation with a basic unit.

System benefits ■ Readily mounted and wired in the built-in cabinet ■ For heating areas up to 40 m² ■ Suitable for up to 4 heating circuits ■ Incl. Wilo high-efficiency pump ■ Temperature regulation for an individual room can be connected via room thermostat and actuator.

■ Concealed manifold cabinet for pre-wall systems

Small surface con-trol station

314

Page 20: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Dimension DN15

Maximum permitted operating tempera-ture 80 °C

Maximum permitted operating pressure 0.6 MPa (6 bar)

Control range 20–70 °C

Height approx. 480 mm

Width approx. 430 mm

Depth approx. 115 mm

Euro cone connections R ¾ inch

Wilo high-efficiency pump Yonos PARA RS15 / 6 RKA FS130

Pump capacity 9–63 W

Nominal heating capacity max. 3 kW

Art. no. small surface control station 684112

Tab. 127: Technical data

Fig. 263: Performance diagram small surface control station

Key① Residual delivery height② Flow volumeLevels (residual delivery height): a = level 1 b = level 2 c = level 3 d = level 4 e = level 5 f = level 6 g = level 7

Technical data

[hPa]

1

2

ab

c

d

e

f

g

Residual deli-very height small surface control station Kvs = 2.47 m3/h

Regulation components, manifolds and manifold cabinets | Manifold control stations

315

Page 21: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Differential pressure regulator

Fig. 264: Differential pressure regulator

The intactness of the hydraulics of the system is an important precondition for its regulation behaviour. A decentralised dynamic differential pressure re-gulation is required because the mass flows vary due to the constantly chan-ging conditions.The differential pressure regulator is a high-performance differential pressure regulator which keeps the differential pressure constant via the load. Thanks to the pressure-relieved valve cone, an accurate differential pressure regulati-on is possible; the integrated locking function makes maintenance easy.Please observe the enclosed instructions for use regarding flow direction, ins-tallation situation etc.

Differential pressure regulator

Lockable yes

Dimension DN25

Pressure class PN 16

Max. differential pressure (∆pv) 250 kPa

Setting range (∆p) 10*–60 kPa

Permitted operating temperature -20–120 °C

Height 141 mm

Length 93 mm

Diameter of pipe connection G1

Tab. 128: Technical data, differential pressure regulator (*factory setting)

Circulation regulation valve

Lockable yes

Dimension DN25

Pressure class PN 20

Permitted operating temperature -20–120 °C

Height 105 mm

Length 110 mm

Diameter of pipe connection G1

Tab. 129:Technical data, circulation regulation valve

Differential pres-sure regulator

Technical data, differential pres-sure regulator

Technical data, circulation regula-tion valve

316

Page 22: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Installation situationsThe circulation regulation valve is installed in the supply line, the differential pressure regulator in the return flow in the specified flow direction. The top of the differential pressure regulator is rotatable.

Fig. 265: Installation position A

Fig. 266: Installation position B

Installation posi-tion A

Installation posi-tion B

Regulation components, manifolds and manifold cabinets | Manifold control stations

317

Page 23: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Heat meter set

Fig. 267: Heat meter set, vertical

Fig. 268: Heat meter set, vertical Fig. 269: Heat meter set, horizontal

To record the quantities of heat used, heat flow meters must be installed in larger housing units.They are adjusted for use in surface heating manifolds and suitable for com-mercially available heat flow meters with installation lengths 110 or 130 mm.

Heat meter set

Installation length G ¾ inch 110 mm

Installation length G 1 inch 130 mm

max operating pressure 1 MPa

max. operating temperature 95 °C

External thread G1 inch

Connection of measuring probe Ø 5.6 mm, M10

Tab. 130: Technical data, heat meter set

109

35

G1

G1

23

3

10

8

Heat meter set

194

69

G1

G1

Technical data

318

Page 24: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Manifold

Manifold DN25

Fig. 270: Manifold DN25 (model 1005)

Features ■ Stainless steel with union nut DN25 ■ Connection can be made on left or right side ■ Flow sensor in supply line, can be locked individually and adjusted from 0 to 5 l/min

■ Suitable for actuators M 30 x 1.5 ■ Manifold incl. fan, plug, and KFE taps ■ Heating circuit connection ¾ inch euro cone ■ incl. wall brackets ■ End cap ¾ inch

Fig. 271: Stainless steel manifold 1 inch, with flow sensor, without thermometer

Manifold DN25

Stainless steel ma-nifold 1 inch with flow sensor, wit-hout thermometer

Regulation components, manifolds and manifold cabinets | Manifold

319

Page 25: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Manifold lengths

HC [number] 2 3 4 5 6 7 8 9 10 11 12

L1 [mm] 50

L2 [mm] 242 242 292 342 392 442 492 542 592 642 692

Tab. 131: Dimensions model 1005

As accessory to a manifold outlet, an extension set model 1005.2 is available. Please take the larger installation length in the conce-aled manifold cabinet into consideration.

industry manifold

Viega industry manifolds are suitable for use in heating systems according to DIN EN 12828 for connection of heating circuits under the specified operating conditions.The manifold can be mounted in vertical position, with outlet facing up or down, or in horizontal position at a storey floor.

Fig. 272: Industry manifold 1½ inch with regulating spindle (model 1007)

Features ■ Stainless steel manifold trunk 1½ inch flat sealing ■ Heating circuit connection ¾ inch Rp thread ■ Regulation valves with locking function in the supply line ■ Return flow locking for each heating circuit ■ Including KFE taps

Dimensions model 1005

Industry manifold 1½ inch with regu-lating spindle

320

Page 26: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Fig. 273: Dimensions of industry manifolds

Art. no. Outlets L (mm)

L1 (mm)

Kvs value (m³ / h)

620806 4 395 380 6,52

620813 5 475 460 7,74

620820 6 555 540 8,95

620837 7 635 620 10,14

620844 8 715 700 11,33

621957 9 795 780 12,52

921964 10 875 860 13,7

621971 11 955 940 14,87

621988 12 1035 1020 15,93

621995 13 1115 1100 16,98

622008 14 1195 1180 17,95

622015 15 1275 1260 18,83

622022 16 1355 1340 19,66

Tab. 132: Dimensions

Dimensions of industry manifolds

Dimensions

Regulation components, manifolds and manifold cabinets | Manifold

321

Page 27: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Kv value (m³ / h) Kvs value

(m³ / h)Number of revolutions (U)

0,25 0,5 1 1,5 2 2,5 3 3,5

0,22 0,37 0,62 0,92 1,27 1,55 1,72 1,85 1,93

Tab. 133: Target values of the valves

Fig. 274: Flowthrough diagram

Key ① Pressure loss ∆p [kPa]② Mass flow m [kg/h]③ Pressure loss ∆p [hPa]④ Number of revolutions [U]

Target values of the valves

4 [U]

1[kPa]

2 [kg/h]

3[hPa]

Flow diagram

322

Page 28: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Manifold cabinets

The manifold cabinets house not only the manifolds but also actuators, ball valves, basic units or other regulation devices. The cabinet allows for quick mounting of and easy access to the compo-nents.

Wall-mounted manifold cabinetMade of galvanised sheet steel, frame and door painted (colour pure white RAL 9016) with an installation depth of 140 mm, five cabinet widths available.

Features ■ Suitable for manifold DN25 ■ Height-adjustable from 630-790 mm ■ incl. universal bracket for manifold

Fig. 275: Wall-mounted manifold cabinet Fig. 276: Dimensions

Type T L2

460

140 mm

490 mm

560 575 mm

700 725 mm

1000 1025 mm

1200 1175 mm

Tab. 134: Dimensions model 1294.1

Dimensions model 1294.1

Regulation components, manifolds and manifold cabinets | Manifold cabinets

323

Page 29: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Mo

del

129

4.1

Man

ifold

co

nnec

tio

n ve

rtic

al

Hea

t flo

w m

eter

ve

rtic

al

Diff

eren

tial

pre

ssur

e re

gu-

lato

r +

heat

flo

w m

eter

ver

tica

l

Diff

eren

tial

pre

ssur

e re

gu-

lato

r +

vert

ical

co

nnec

tio

n

Man

ifold

co

nnec

tio

n +

zo

ne v

alve

Man

ifold

co

nnec

tio

n +

co

ntro

l sta

tio

n m

od

el

1254

.2

Type

460 ≤ 3 ≤ 3

560 ≤ 5 ≤ 5 ≤ 4 ≤ 4 ≤ 4

700 ≤ 8 ≤ 8 ≤ 4 ≤ 7 ≤ 7 ≤ 7

1000 ≤ 12 ≤ 12 ≤ 10 ≤ 12 ≤ 12 ≤ 12

1200 ≤ 12

Tab. 135: Manifold selection table model 1294.1

Concealed manifold cabinetMade of galvanised steel sheet, frame and door painted (colour: traffic white RAL 9016), with an installation depth of 110 to 150 mm, in five cabinet widths.

Features ■ Suitable for manifold DN25 ■ Height-adjustable from 675 to 855 mm ■ incl. universal bracket for manifold

Fig. 277: Concealed manifold cabinet Fig. 278: Dimensions

Manifold selection table model 1294.1

324

Page 30: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Type T L1 L2

460

110–150mm

450 mm 510 mm

560 535 mm 595 mm

700 685 mm 745 mm

1000 985 mm 1045 mm

1200 1135 mm 1195 mm

Tab. 136: Dimensions model 1294

Mo

del

129

4

Man

ifold

co

nnec

tio

n ho

rizo

n-ta

l

Man

ifold

co

nnec

tio

n ve

rtic

al

Man

ifold

co

nnec

tio

n +

zone

va

lve

hori

zont

al

Man

ifold

co

nnec

tio

n +

he

at f

low

met

er h

ori

zont

al

Man

ifold

co

nnec

tio

n +

d

iffer

enti

al p

ress

ure

reg

ulat

or

hori

zont

al

Man

ifold

co

nnec

tio

n +

diff

e-re

ntia

l pre

ssur

e re

gul

ato

r +

heat

flo

w m

eter

ho

rizo

ntal

Man

ifold

co

nnec

tio

n +

cont

rol s

tati

on

mo

del

125

4.2

Type

460 ≤ 5 ≤ 3 ≤ 4 ≤ 2

560 ≤ 7 ≤ 5 ≤ 6 ≤ 4 ≤ 5 ≤ 3

700 ≤ 10 ≤ 8 ≤ 9 ≤ 7 ≤ 7 ≤ 3 ≤ 6

1000 ≤ 12 ≤ 12 ≤ 12 ≤ 12 ≤ 12 ≤ 9 ≤ 12

1200 ≤ 12

Tab. 137: Manifold selection table model 1294

Dimensions model 1294

Manifold selection table model 1294

Regulation components, manifolds and manifold cabinets | Manifold cabinets

325

Page 31: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

Application technology: Fonterra radiant heating and cooling

Concealed manifold cabinet 80 mm

Made of galvanised steel sheet, frame and door painted (colour: pure white RAL 9016), with an installation depth of 80 to 110 mm, in five cabinet widths.

Features ■ Suitable for manifold DN25 ■ Height-adjustable from 675 to 855 mm ■ incl. universal bracket for manifold

The concealed box model 1294.3 with an adjustable installation depth of 80-110 mm is suitable for use in drywalls.

Fig. 279: Concealed manifold cabinet Fig. 280: Dimensions

Type T L1 L2

460

80–110 mm

450 mm 510

560 535 mm 595

700 685 mm 745

1000 985 mm 1045

1200 1135 mm 1195

Tab. 138: Dimensions model 1294.3

Model 1294.3Type

Manifold connec-tion

horizontal

Manifold connec-tion

vertical

Manifold connec-tion + zone valve

horizontal

460 ≤ 5 ≤ 3 ≤ 4

560 ≤ 7 ≤ 5 ≤ 6

700 ≤ 10 ≤ 8 ≤ 9

1000 ≤ 12 ≤ 12 ≤ 12

1200

Tab. 139: Manifold selection table model 1294.3

Dimensions model 1294.3

Manifold selection table model 1294.3

326

Page 32: Volume III: Fonterra radiant heating and cooling · ErP class acc. to EU 811/2013 1=1 % Protection class II III IP Code IP 20 Terminals screwless terminal technology 0.2–1.5mm ...

INT ∙ 709 365 ∙ 2018-05 ∙ VPN 170369

Viega Technology GmbH & Co. KGViega Platz 157439 AttendornGermany

Phone +49 (0) 2722 61-0

viega.com


Recommended