2
TYPICAL APPLICATIONS • Inboard/Outboard Switching • Multiple Load Control • Control Lights and Fan • Private Offices • Individual Bathrooms (no stalls) • Storage rooms SENSOR HIGHLIGHTS • Patented Bi-Polar Wiring • Replaces 2 Switches at once • Small Motion Detection up to 20 Feet • No Minimum Load • Optional Vandal-Resistant • Optional Photocell/Daylight Override FEATURES • Time Delay: 30 sec. to 20 mins (each pole independently) • Two pole operation • Green LED Activity Indicator SPECIFICATIONS • Size: 4.2”H x 1.8”W x 1.4” Deep • Sensor Weight: 5 Ounces • Sensor Colors: Ivory, White, Gray, and Almond • Mounting Height: 30 to 48 inches • 1/2” inch Fresnel Lens • Relative Humidity: 20 to 90% non-condensing • Operating Temp: 14° to 85° F • Storage Temp: -14° to 160° F • Load Rating: Each Pole • 120 VAC @ 800 W, 60 Hz • 277 VAC @ 1200 W, 60 Hz • 347 VAC @1500 W, 60 Hz Note: 347 Volt, 1 Phase Only • 1/4 HP Motor Load each pole • Frequency: 60 Hz • UL and CUL Listed • 5-Year Warranty • Made In USA LOW TEMP/HI HUMIDITY (-LT) • Conformally Coated PCB • Operates down to -40º F • Corrosion resistant from moisture Part Numbering System: WSD-2P-[LENS]-[PHOTOCELL]-[PHOTOCELL]-[COLOR*]-[TEMP/HUMIDITY] *Must specify color MODEL# LENS PHOTOCELL VOLTAGE COLOR LO TEMP/HI HUMIDITY WSD-2P TECHNICAL DATA WSD 2 Pole Series- Programmable Edition! 2 POLE PASSIVE INFRARED DECORATOR WALL SWITCH SENSOR Blank -V = = Standard Lens Vandal Resistant Blank -3 = = 120-277 VAC 347 VAC** Blank -P No Photocell w/Photocell -I -W -G -A = = = = Ivory White Gray Almond = = STANDARD VS. VANDAL RESISTANT LENS The Standard lens provides maximum PIR detection sensing small movements up to 20 feet. This lens should be used in typical offices and rooms where occupants work for extended periods of time. The Vandal Resistant lens should be used in high abuse or public areas, where occupants simply come and go and make larger types of motions. Copy rooms, small public restrooms, storage or janitor’s closets are ideal applications. The PIR detection is reduced by 50%. PHOTOCELL/BI-LEVEL DAYLIGHT OVERRIDE OPTION (WSD-2P-P) The WSD-2P sensor offers a Photocell Override option of both poles separately. Ideal for Automatic Bi-Level Lighting Control for spaces where abundant natural light is available. Once the sensor turns “On” (each pole respectively), the photocell is overridden so that the lights will not cycle from the artificial light source. F inally a Decorator Style Sensor that handles inboard/ outboard switching! Utilizing two isolated power relays, the WSD-2P provides: Full “On”, Load A only, Load B only, or All “Off”. Perfect for private offices with A-B switching. Additionally, the WSD-2P handles multiple loads and voltages. SENSOR OPERATIONS These sensors use PIR detection to sense occupancy in a space and initiate the lights to an “On” condition. The 2 pole design allows 2 switching functions for multi- level lighting control thru inboard/outboard control of 3 lamp fixtures or the switching of multiple fixtures. Once the sensor turns the load to “On”, the built in time delay (typically 10 minutes) keeps the lights “On” during brief periods of inactivity. Once the timer expires, the lights turn “Off”. The electronic frequency response and sensitivity to movement is factory calibrated for maximum performance. This-state-of-the-art design allows the sensor to adapt to it’s environment, eliminating the need for manual field adjustments. Blank -LT = = 14º to 85º F -40º to 85º F **347 V: Plate not provided TWO POLES-TWO LEVELS OF FUNCTION Each pole may be programmed separately. For example, the first pole can be set to automatically turn “On” upon occupancy, and the 2nd pole to be a “Manual On”. Or the 1st pole set at a 10 minute delay on the lights, with a 20 minute delay on the exhaust fan. Photocell control can also be set at different levels per pole. Auto On - Auto Off Manual On - Auto Off Reduced Turn On
Transcript
Page 1: WSD 2 Pole Series- Programmable Edition! · WSD-2P SERIES 0 5 10 15 20 4‘ 4‘ 5.6’ 2.4’ TOP VIEW SIDE VIEW 20 15 10 5 5 10 15 20 AREA OF COVERAGE: The PIR collector beams view

TYPICAL APPLICATIONS• Inboard/Outboard Switching• Multiple Load Control• Control Lights and Fan• Private Offices• Individual Bathrooms (no stalls)• Storage roomsSENSOR HIGHLIGHTS• Patented Bi-Polar Wiring• Replaces 2 Switches at once• Small Motion Detection up to 20 Feet• No Minimum Load• Optional Vandal-Resistant• Optional Photocell/Daylight OverrideFEATURES• Time Delay: 30 sec. to 20 mins (each pole independently)• Two pole operation• Green LED Activity IndicatorSPECIFICATIONS• Size: 4.2”H x 1.8”W x 1.4” Deep• Sensor Weight: 5 Ounces• Sensor Colors: Ivory, White, Gray, and Almond• Mounting Height: 30 to 48 inches• 1/2” inch Fresnel Lens• Relative Humidity: 20 to 90% non-condensing• Operating Temp: 14° to 85° F• Storage Temp: -14° to 160° F• Load Rating: Each Pole• 120 VAC @ 800 W, 60 Hz• 277 VAC @ 1200 W, 60 Hz• 347 VAC @1500 W, 60 Hz Note: 347 Volt, 1 Phase Only• 1/4 HP Motor Load each pole• Frequency: 60 Hz• UL and CUL Listed• 5-Year Warranty• Made In USALOW TEMP/HI HUMIDITY (-LT)• Conformally Coated PCB• Operates down to -40º F• Corrosion resistant from moisture

Part Numbering System: WSD-2P-[LENS]-[PHOTOCELL]-[PHOTOCELL]-[COLOR*]-[TEMP/HUMIDITY]

*Must specify color

MODEL# LENS PHOTOCELL VOLTAGE COLOR LO TEMP/HI HUMIDITYWSD-2P

TECHNICAL DATA WSD 2 Pole Series- Programmable Edition!

2 POLE PASSIVE INFRAREDDECORATOR WALL SWITCH SENSOR

Blank -V

==

Standard LensVandal Resistant

Blank -3

==

120-277 VAC347 VAC**

Blank -P

No Photocellw/Photocell

-I

-W -G -A

====

IvoryWhiteGrayAlmond

==

STANDARD VS. VANDAL RESISTANT LENSThe Standard lens provides maximum PIR detection sensing small movements up to 20 feet. This lens should be used in typical offices and rooms w h e r e occupants work for extended

periods of time. The Vandal Resistant lens should be used in high abuse or public areas, where occupants simply come and go and make larger types of motions. Copy rooms, small public restrooms, storage or janitor’s closets are ideal applications. The PIR detection is reduced by 50%.PHOTOCELL/BI-LEVEL DAYLIGHT OVERRIDE OPTION (WSD-2P-P)The WSD-2P sensor offers a Photocell Override option of both poles separately. Ideal for Automatic Bi-Level Lighting Control for spaces where abundant natural light is available. Once the sensor turns “On” (each pole respectively), the photocell is overridden so that the lights will not cycle from the artificial light source.

Finally a Decorator Style Sensor that handles inboard/outboard switching! Utilizing two isolated power relays, the

WSD-2P provides: Full “On”, Load A only, Load B only, or All “Off”. Perfect for private offices with A-B switching. Additionally, the WSD-2P handles multiple loads and voltages. SENSOR OPERATIONSThese sensors use PIR detection to sense occupancy in a space and initiate the lights to an “On” condition. The 2 pole design allows 2 switching functions for multi-level lighting control thru inboard/outboard control of 3 lamp fixtures or the switching of multiple fixtures. Once the sensor turns the load to “On”, the built in time delay (typically 10 minutes) keeps the lights “On” during brief periods of inactivity. Once the timer expires, the lights turn “Off”. The electronic frequency response and sensitivity to movement is factory calibrated for maximum performance. This-state-of-the-art design allows the sensor to adapt to it’s environment, eliminating the need for manual field adjustments.

Blank -LT

==

14º to 85º F-40º to 85º F

**347 V: Plate not provided

TWO POLES-TWO LEVELS OF FUNCTIONEach pole may be programmed separately. For example, the first pole can be set to automatically turn “On” upon occupancy, and the 2nd pole to be a “Manual On”.

Or the 1st pole set at a 10 minute delay on the lights, with a 20 minute delay on the exhaust fan. Photocell control can also be set at different levels per pole.

Auto On - Auto OffManual On - Auto Off

Reduced Turn On

Page 2: WSD 2 Pole Series- Programmable Edition! · WSD-2P SERIES 0 5 10 15 20 4‘ 4‘ 5.6’ 2.4’ TOP VIEW SIDE VIEW 20 15 10 5 5 10 15 20 AREA OF COVERAGE: The PIR collector beams view

revised 01/18/2005copyright Sensor Switch, Inc. 2004

SENSOR SWITCH, INC.900 Northrop Rd., Wallingford, CT 06492(203) 265-2842 [email protected] www.sensorswitch.com

WARRANTY: Sensor Switch, Inc. warrants these products to be free of defects in manufacture and workmanship for a period of sixty months. Sensor Switch, Inc., upon prompt notice of such defect will, at its option, provide a Returned Material Authorization number and a replacement product.LIMITATIONS AND EXCLUSIONS: This Warranty is in full lieu of all other representation and expressed and implied warranties (including the implied warranties of merchantability and fitness for use) and under no circumstances shall Sensor Switch, Inc. be liable for any incidental or consequential property damages or losses.

WSD-2P SERIES

0 5 10 15 20

4‘ 4‘

5.6’

2.4’

SIDE VIEWTOP VIEW

� 5 10 15 20 20 15 10 5

AREA OF COVERAGE:The PIR collector beams view out horizontally in a wall-to-wall pattern. The beams will see out to 50 feet, however, their effectiveness in the Standard product is 20 feet for small hand or body motions and 10 feet for the Vandal Resisitant products.

���

���

���

���

���

���� ����

������������

��

TIME DELAY SETTINGThe sensor is factory set with a 10 minute Time Delay. This Delay may be changed to 30 seconds for Test Mode, or set up to 20 minutes in 2.5 minute increments.

OPTION: DISABLE OVERRIDE OFF SWITCHIf desired to prevent the user from being able to manually turn off the lights, the Override “Off” function may be disabled. You cannot disable this feature when in the Semi-Auto mode.

3 MINUTE WARM-UP

TYPICAL WIRING DIAGRAM (DO NOT WIRE HOT)

OPTIONAL SEMI-AUTO OR MANUAL ON MODEThe Semi-Auto feature allows the user to determine if the lights are needed or not. This maximizes energy savings as well as lamp life. An alternative to this is to use the fully automatic mode with a built-in photocell. It’s a matter of preference. If the sensor is installed in such a location that it can view outside the room, a person walking by will trigger the sensor. Program sensor for Manual On. Note: When the Sensor Times Out, turning “Off” the lights, the PIR detector remains active for 10 seconds to allow the occupant to move and automatically turn the lights back On. After 10 seconds, the manual button must be pushed to activate the lights.

OPTIONAL REDUCED TURN ONPassive Infrared cannot “see through glass”, however, the reflection of PIR can bounce off glass, mirrors, or even high gloss doors and view outside the room. The sensor may be set to only detect large motions at Turn On, which will avoid “reflected signals”, however still sense the occupant when they enter the room. Once On, the sensor maintains maximum sensitivity for small desk top activity.

Reduced Turn On• No false “Ons” from reflected surface - Tinted windows - High Gloss Doors - Mirrors or Paintings

Semi-Auto• Manual On desired• Sensor views outside the space• A/B Switching -Auto A -Manual B

Note: Black wire is replaced with a Red wire for 347 VAC.