Catalogue 2011
a Nexans company
1
01/2
011
While every care is taken to ensure that the information contained in this publication is correct, no legal responsibility can be accepted for any inaccuracy. Nexans Network Solutions N.V. - Div. Euromold reserves the right to alter or modify the characteristics of its products described in this catalogue as standards and technology evolve.
EUROMOLDEuromold is the leading European specialised designer, manufacturer and distributor of prefabricated cable accessories for medium voltage energy distribution. Euromold provides a complete range of accessories for underground cables: premoulded EPDM rubber connectors for cables and epoxy bushings for transformers and switchgear, as well as a large range of cold-shrinkable terminations and joints from 12 to 42 kV.Euromold is also the manufacturer of electrical components for the high voltage accessories of the Nexans group.
ISO 9001 CertificateSince 1992, Euromold’s commitment to quality is demonstrated by its ISO 9001 certification.
Laboratory accreditationSince June 2000, Euromold’s independent ELAB laboratory obtained the BELAC accreditation no.144-TEST conform with the European standards for laboratories ISO 17025 for electrical testing of low and medium voltage cable accessories according to the international standards HD 623 and HD 629.
International standardsAll our products meet the International standards like CENELEC HD 629.1, CENELEC EN 50180, IEC 60137, IEC 60502-4… or country speci-fications. Official certificates, CESI, KEMA, ATEX… prove the conformity of our products. Long duration tests of existing or new products are con-tinuously performed in our test fields.
Nexans Network SolutionsDiv. Euromold
COMPANY PRESENTATION
2
01/2
011
SEPARABLE CONNECTORSAND BUSHINGS
INTERFACE C
Interface CDimensions according to European CENELEC EN 50180 and 50181 (in mm).
Table of contents400LB - elbow connector430TB - tee connector400TB - tee connector434TB - tee connector440TB - tee connector300PBM - coupling connector430TBM-P2/P3 - dual/triple cable arrangement440PBM - coupling connector434TBM-P2 - dual cable arrangement400AR-3 - equipment bushing400AR-4 - equipment bushing400AR-5 - equipment bushing400AR-6 - equipment bushing400SFR-B - equipment bushing400A-24B - in-air bushing300SA - surge arrester400PB-XSA - surge arrester400TR & 400TR-LB - test rod400TK-400SW installation toolsAccessoriesPossible arrangements
90±0.2
Dia. 46±0.2
Dia. 56±0.2
Dia. 70±0.2
0-0.51.5M16 x 2 - 6H
29min
11min
Dia. 22 min for C1Dia. 32 nominal for C2
3 01/2
011
Connecting possibilities
CONNECTIONBUSHINGS /ACCESSORIES
CONNECTORS /ACCESSORIES
(K)(M)300PBM/GCoupling connector
300SASurge arrester
dead-endingof equipment (K)(M)400DR-B
Dead-end receptacle
cableearthing
tap-off630/250A
in-linejunction
in-linejunction
(K)400LB/GElbow connector
(K)(M)(P)400TB/GTee connector
(K)(M)(P)440TB/GTee connector
(K)(M)430TB/GTee connector
Equipmentinterface
(K)(M)400AR-3Equipment bushing
400A-24BIn-air bushing
(K)(M)400SOP-BStand-off plug
400GP-BEarthing plug
(K)400RTPAReducing tap plug
(K)(M)440CPConnecting plug
(K)(M)400CP-SCConnecting plug
(K)(M)400SFR-BEquipment bushing
(K)(M)400AR-6Equipment bushing
(K)(M)400AR-4Equipment bushing
(K)(M)400AR-5Equipment bushing
cable toequipment
cableisolation
400PB-XSASurge arrester
(K)(M)440PBM/GCoupling connector
(K)(M)434TB/GTee connector
4
01/2
011
Specifications and standardsThe 400LB separable connector meets the requirements of CENELEC HD 629.1.
Up to 24 kV - 630 A
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Conductor sizes (mm2)
min max
400LB/G
K400LB/G
12
24
630
630
25
25
300
300
DesignSeparable connector comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Type C - 630 A interface as described by CENELEC EN 50180 and 50181.5. Conductor connector (not included in the standard kit).6. Insulating plug.7. Cable reducer.8. Earthing lead.9. Transition contact M10/M16.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
400LBINTERFACE C
ELBOW CONNECTOR
ApplicationSeparable elbow connector designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors...).Also connects cable to cable, using the appropriate mating part.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
Technical characteristics ������������ �����������
jacket provides a total safe to touch screen which ensures safety for personnel.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
330 mm
205 mm
9
4
1
5
2
38
7
6
5
Kit contentsThe complete (K)400LB/G elbow connector kit comprises 3 x the following components:
Ordering instructionsSelect the part numberwhich gives the best centring to the cable core insulation diameter.Add a 'K' for use up to 24 kV.
Orderingpart number
Dia. over core insulation (mm)
min max
3 x 400LB/G-11
3 x 400LB/G-15
3 x 400LB/G-19
3 x 400LB/G-22
3 x 400LB/G-25
3 x 400LB/G-27
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5Example:The copper wire screened cables are 24 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 32.2 mm.Order 3 x K400LB/G-27 elbow connector kit.
Can be suppliedwith cable lugs.
For applicationsoutdoors and in humid climate.
Order: +MWS.
Components can be ordered individually.
For use withcopper tape
screened cables. Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact our representative.
For use with fabric tape (graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).
3 x (K)400LB/G-W(-X)connector kit
Table W
Notes:We do not supply the compression lugs in the standard kit. All types of cable lugs can be used. The lugs must be within the dimensions specified and the palm of the lug must be copper or any equivalent alloy.
Transitioncontact +
screw assembly400LTS
Insulatingplug
400LBPCable reducer
411CA-WConnector housing
(K)400BLB
2 max
Dia. 10.2 or 13
24 max
112 max 135 max
38max
Dia. 36max
10.5max
The kit also comprises silicone grease, field control mastic and installation instructions.
6
01/2
011
ApplicationSeparable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...).Also connects cable to cable when using the appropriate mating parts.
Technical characteristics���������� �����������
jacket provides a total safe to touch screen.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
Specifications and standardsThe 430TB separable connector meets the requirements of CENELEC HD 629.1.
Up to 36 kV630 A (800 A)
430TBINTERFACE C
TEE CONNECTOR
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
185 mm
290 mm
(350 mmfor 36 kV)
4 9
6
1
2
3
10
7
5
8
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Current Ir (A)Conductor sizes (mm2)
When installed on an appropriate equipment bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact min max
430TB/GK430TB/GM430TB/G
122436
630630630
800800800
353550
300300240
7
3 x (K)(M)430TB/G-W-X connector kit
When installed on an appropriate equipment
bushing: 800 A continuously
Kit contentsThe complete (K)(M)430TB/G tee connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
Table W
Table X
Connector housing(K)(M)430BT/G
Cable reducer430CA-W
(411CA-Wfor 36 kV)
Clamping screw
430TCS
For use withcopper tape
screened cables. Order: Kit MT.
Orderingpart number
Voltage(Um)(kV)
Dia. over core insulation (mm)
min max
3 x 430TB/G-11-X3 x 430TB/G-16-X3 x 430TB/G-18-X
3 x K430TB/G-11-X3 x K430TB/G-16-X3 x K430TB/G-18-X
3 x M430TB/G-11-X3 x M430TB/G-15-X3 x M430TB/G-19-X3 x M430TB/G-22-X3 x M430TB/G-25-X3 x M430TB/G-27-X
121212
242424
363636363636
12.017.019.0
12.017.019.0
12.016.020.023.526.528.5
17.523.532.6
17.523.532.6
17.522.026.531.032.537.5
Ordering instructionsTo order the tee connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.
Example:The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm.Order 3 x K430TB/G-18-95.240-14-5 tee connector kit.
Conductorcontact TMBC-X
Conductor contact TBC-X
For use with Alupe orC 33-226 cables.
Please contact our representative.
For use withother cable types.
Please contact our representative.
For applicationsoutdoors and in humid climate.
Order: +MWS.
For use witheasy strip semi-conductive screened cables. Order: Field control mastic
(type MFC).
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
35 35(K)M-10-2 35KM-10-1 35(K)M-11-250 50(K)M-10-2 50(K)M-10-1 50(K)M-11-270 70(K)M-10-2 70(K)M-10-1 70(K)M-11-295 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2300 300(K)M-10-2 – 300(K)M-11-2
16.9
5-14
-5
95.2
40-1
4-5
50.1
50-1
4-5
120.
300-
12-5
16.9
5-14
-5
50.1
50-1
4-5
95.2
40-1
4-5
120.
300-
12-5
Basic insulatingplug
(K)(M)300BIPA +rubber cap
8
01/2
011
Up to 41.5 kV630 A (800 A)
400TBINTERFACE C
TEE CONNECTOR
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
20.8/36 (41.5) kV
Technical characteristics ������������ �����������
jacket provides a total safe to touch screen which ensures safety for personnel.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
ApplicationSeparable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...).Also connects cable to cable when using the appropriate mating parts.
DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer. 4. Type C - 630 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
Specifications and standardsThe 400TB separable connector meets the requirements of CENELEC HD 629.1 S1.
220 mm
350 mm
8
4 9
1
2
3
10
7
56
255 mm
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Current Ir (A)Conductor sizes (mm2)
When installed on an appropriate equipment bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact min max
400TB/GK400TB/GM400TB/GP400TB/G
122436
41.5
630630630630
800800800800
35353535
300300240240
9
For use withcopper tape
screened cables. Order: Kit MT.
For use in potentiallyexplosive atmospheres
(for 12 kV max). Add -/ATEX to part number.
Kit contentsThe complete (K)(M)(P)400TB/G tee connector kit comprises the following components:
Ordering instructionsTo order the tee connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 41.5 kV.
Orderingpart number
Dia. over core insulation (mm)
min max
400TB/G-11-X400TB/G-15-X400TB/G-19-X400TB/G-22-X400TB/G-25-X400TB/G-27-X
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
Example:The copper wire screened cable is 36 kV, 150 mm2 stranded copper with a diameter over core insulation of 32.5 mm.Order a M400TB/G-27-150(K)M-11-2 tee connector kit.
Table W
Table X
(K)(M)(P)400TB/G-W-Xconnector kit
Connector housing(K)(M)(P)400BT/G
Clampingscrew
400TCS
Basic insulatingplug
(K)(M)(P)400BIPA+ rubber cap
Cable reducer411CA-W
Conductorcontact TMBC-X
Conductor contact TBC-X
For use withother cable types.
Please contact our representative.
Components can be ordered individually.
For applicationsoutdoors and in humid climate.
Order: +MWS.
When installed on an appropriate equipment
bushing: 800 A continuously
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
35 35(K)M-10-2 35KM-10-1 35(K)M-11-250 50(K)M-10-2 50(K)M-10-1 50(K)M-11-270 70(K)M-10-2 70(K)M-10-1 70(K)M-11-295 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2300 300(K)M-10-2 – 300(K)M-11-2
16.9
5-14
-5
95.2
40-1
4-5
50.1
50-1
4-5
120.
300-
12-5
16.9
5-14
-5
50.1
50-1
4-5
95.2
40-1
4-5
120.
300-
12-5
The kit also comprises silicone grease, field control mastic, installation instructions and crimp chart.
10
01/2
011
Up to 36 kVUp to 1250 A
434TBINTERFACE C
TEE CONNECTOR
Technical characteristics ������������ �����������
jacket provides a total safe to touch screen which ensures safety for personnel.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
ApplicationSeparable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...).Also connects cable to cable when using the appropriate mating parts.
DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
Specifications and standardsThe 434TB separable connector meets the test requirements of CENELEC HD 629.1.
Separable connector
type
VoltageUm(kV)
CurrentIr (A)
When installed on anappropriate equipment bushing
Conductor sizes (mm2)
Cable with reducedcore insulation thickness
Cable with unreducedcore insulation thickness
min max min max434TB/GK434TB/GM434TB/G
122436
up to 1250up to 1250up to 1250
185185185
800800800
185185185
800800630
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
185 mm
84 9
1
2
3
10
7
355 mm
5
6
11
Kit contentsThe complete (K)(M)434TB/G tee connector kit comprises the following components:
The kit also comprises silicone grease, field control mastic, installation instructions and crimp chart.
Ordering instructionsTo order the tee connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV.
Example:The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm.Order a M434TB/G-32-240(K)M-12-2 tee connector kit.
Orderingpart number
Dia. over core insulation (mm)min max
434TB/G-22-X434TB/G-27-X434TB/G-32-X434TB/G-37-X434TB/G-43-X
23.5
28.5
34.0
39.0
45.5
31.0
37.5
42.5
48.5
56.0
When installed on an appropriate equipment
bushing: 1250 A continuously
For use withcopper tape
screened cables. Order: Kit MT.
Table W
Table X
For use withother cable types.
Please contact our representative.
Components can be ordered individually.
(K)(M)434TB/G-W-Xconnector kit
Connector housing(K)(M)434BT/G
Basic insulatingplug
(K)(M)300BIPA +rubber cap
Cable reducer611CA-W
Conductorcontact TMBC-X
Conductor contact TBC-X
For applicationsoutdoors and in humid climate.
Order: +MWS.
Clampingscrew
430TCS
For use with Alupe orC 33-226 cables.
Please contact our representative.
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
185 185(K)M-12-2 185(K)M-12-1
–
185(K)M-11-2
240 240(K)M-12-2 240(K)M-12-1 240(K)M-11-2
300 300(K)M-12-2 300(K)M-12-1 300(K)M-11-2
400 400(K)M-12-2 400(K)M-12-1 400(K)M-11-2
500 500(K)M-12-2 500(K)M-12-1 500(K)M-11-2
630 630(K)M-12-2 630(K)M-12-1 630(K)M-11-2 –
800 800(K)M-12-2 800(K)M-12-1 – 800(K)M-11-2 –
400.
630-
14-5
12
01/2
011
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
20.8/36 (41.5) kV
Up to 41.5 kV630 A (1250 A)
440TBINTERFACE C
TEE CONNECTOR
Technical characteristics ������������ �����������
jacket provides a total safe to touch screen which ensures safety for personnel.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
ApplicationSeparable tee shape connector (bolted type) designed to connect polymeric insulated cable to equipment (transformers, switchgear, motors, ...).Also connects cable to cable when using the appropriate mating parts.
DesignSeparable connector comprising: 1. Conductive EPDM insert. 2. Conductive EPDM jacket. 3. Insulating EPDM layer moulded between the insert and the jacket. 4. Type C - 630 A interface as described by CENELEC EN 50180 and 50181. 5. Conductor connector. 6. Basic insulating plug (with VD point). 7. Cable reducer. 8. Conductive rubber cap. 9. Clamping screw. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
Specifications and standardsThe 440TB separable connector meets the requirements of CENELEC HD 629.1.
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
CurrentIr (A)
When installed on anappropriate equipment bushing
Conductor sizes (mm2)
min max440TB/GK440TB/GM440TB/GP440TB/G
122436
41.5
630630630630
1250125012501250
185185185185
630630630630
4 9
1
2
3
10
7
5 8
255 mm
220 mm
355 mm
6
13
Ordering instructionsTo order the tee connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV, add a 'P' for use up to 41.5 kV.
Example:The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm.Order a M440TB/G-32-240(K)M-12-2 tee connector kit.
Orderingpart number
Dia. over core insulation (mm)
min max
440TB/G-22-X440TB/G-27-X440TB/G-32-X440TB/G-37-X440TB/G-43-X
23.5
28.5
34.0
39.0
45.5
31.0
37.5
42.5
48.5
56.0
When installed on an appropriate equipment
bushing: 1250 A continuously
Table W
Table X
Components can be ordered individually.
Kit contentsThe complete (K)(M)(P)440TB/G tee connector kit comprises the following components:
The kit also comprises silicone grease, field control mastic, installation instructions and crimp chart.
(K)(M)(P)440TB/G-W-Xconnector kit
Connector housing(K)(M)(P)440BT/G
Clampingscrew
430TCSCable reducer
611CA-W
Conductorcontact TMBC-X
Conductor contact TBC-X
Basic insulatingplug
(K)(M)(P)400BIPA+ rubber cap
For use withcopper tape
screened cables. Order: Kit MT.
For use in potentiallyexplosive atmospheres
(for 12 kV max). Add -/ATEX to part number.
For use withother cable types.
Please contact our representative.
For applicationsoutdoors and in humid climate.
Order: +MWS.
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
185
240
300
400
500
630
185(K)M-12-2
240(K)M-12-2
300(K)M-12-2
400(K)M-12-2
500(K)M-12-2
–
185KM-12-1
240KM-12-1
300KM-12-1
400KM-12-1
500KM-12-1
630KM-12-1
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
400(K)M-11-2
500(K)M-11-2
630(K)M-11-2
400.
630-
14-5
14
01/2
011
ApplicationSeparable coupling connector (bolted type) for dual cable arrangement. It has been designed to be used with 430TB separable Tee connector.
Technical characteristics���������� �����������
jacket provides a total safe to touch screen.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
Up to 36 kV630 A (1250 A)
300PBMCOUPLING CONNECTOR
FOR 430TB/G
Specifications and standardsThe 300PBM coupling connector meets the requirements of CENELECHD 629.1.
Design 1. Interface designed to fit 430TB connector. 2. Bus for 300PBM. 3. Conductive EPDM insert. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Conductive EPDM jacket. 6. Conductive EPDM cap. 7. Basic insulating plug (with VD point). 8. Conductor connector (hexagonal crimping, deep indent crimping or bolted). 9. Cable reducer. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
290 mm(350 mmfor 36 kV)
105 mm
300PBMcouplingconnector
290 mm
1
2
8
3
4
5
9
7
6
10
430TBconnector
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Current Ir (A)Conductor sizes (mm2)
When installed on an appropriate equipment bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact min max
300PBM/GK300PBM/GM300PBM/G
122436
630630630
125012501250
353550
300300240
15
Kit contentsThe complete (K)(M)300PBM/G coupling connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
For use withcopper tape
screened cables. Order: Kit MT.
For use witheasy strip semi-conductive screened cables. Order: Field control mastic
(type MFC).
For use with copperwire screened cables.
No earthingdevice is
necessary.
For use withother cable types.
Please contact our representative.
For outdoorapplications.
Order: +MWS.
Connector housing(K)(M)300BP/G
For use with fabric tape (graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).
Contact rod 300PB-CR
3 x (K)(M)300PBM/G-W-X coupling connector kit
Cable reducer430CA-W
(411CA-Wfor 36 kV)
Conductorcontact TMBC-X
Conductor contact TBC-X
Table W
Table X
Orderingpart number
Voltage(Um)(kV)
Dia. over core insulation (mm)
min max
3 x 300PBM/G-11-X3 x 300PBM/G-16-X3 x 300PBM/G-18-X
3 x K300PBM/G-11-X3 x K300PBM/G-16-X3 x K300PBM/G-18-X
3 x M300PBM/G-11-X3 x M300PBM/G-15-X3 x M300PBM/G-19-X3 x M300PBM/G-22-X3 x M300PBM/G-25-X3 x M300PBM/G-27-X
121212
242424
363636363636
12.017.019.0
12.017.019.0
12.016.020.023.526.528.5
17.523.532.6
17.523.532.6
17.522.026.531.032.537.5
Ordering instructionsTo order the coupling connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.
Example:The cable is 24 kV, 150 mm2 compact stranded copper with a diameter over core insulation of 27.5 mm.Order 3 x K300PBM/G-18-95.240-14-5 coupling connector kit.
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
35 35(K)M-10-2 35KM-10-1 35(K)M-11-250 50(K)M-10-2 50(K)M-10-1 50(K)M-11-270 70(K)M-10-2 70(K)M-10-1 70(K)M-11-295 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2300 300(K)M-10-2 – 300(K)M-11-2
16.9
5-14
-5
95.2
40-1
4-5
50.1
50-1
4-5
120.
300-
12-5
16.9
5-14
-5
50.1
50-1
4-5
95.2
40-1
4-5
120.
300-
12-5
16
01/2
011
ApplicationSeparable connectors (bolted type) for dual (P2) and triple (P3) cable arrangements.
Technical characteristics���������� �����������
jacket provides a total safe to touch screen.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
Specifications and standardsThe 430TBM-P2/P3 connectors meet the requirements of CENELEC HD 629.1.
Up to 36 kV630 A (1250 A)
Design 1. Type C interface as described by CENELEC EN 50180 and 50181. 2. Bus for 300PBM. 3. Conductive EPDM insert. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Conductive EPDM jacket. 6. Conductive EPDM cap. 7. Basic insulating plug (with VD point). 8. Conductor connector. 9. Cable reducer. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
430TBM-P2/P3DUAL/TRIPLE CABLE ARRANGEMENT
FOR 430TB CONNECTOR
Non-sizesensitive:290 mm
Sizesensitive:350 mm
105 mm
430TBMconnector
300PBMcouplingconnector
290 mm
1 2
8
3
4
5
9
7
6
10
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Current Ir (A)Conductor sizes (mm2)
When installed on an appropriate equipment bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact min max
430TBM-P2/P3K430TBM-P2/P3M430TBM-P2/P3
122436
630630630
125012501250
353550
300300240
17
Kit contentsThe complete (K)(M)430TBM-P2 connector kit comprises 3 x the following components:
Ordering instructionsTo order the separable connectors for dual cable arrangement, use the tables beside to substitute for W and X in the formula:3 x 430TBM-P2-W-X,for use up to 12 kV.Add a 'K' for use up to 24 kV:3 x K430TBM-P2-W-X.Add an 'M' for use up to 36 kV:3 x M430TBM-P2-W-X.
For triple cable arrangement:3 x 430TBM-P3-W-X,for use up to 12 kV.Add a 'K' for use up to 24 kV:3 x K430TBM-P3-W-X.Add an 'M' for use up to 36 kV:3 x M430TBM-P3-W-X.
Example:The two cables are 24 kV, 150 mm2 stranded aluminium with a diameter over core insulation of 27.5 mm.Order 3 x K430TBM-P2-22-150(K)M-10-2.
Table W
Dia. over coreinsulation (mm) W
min max
12.0
16.0
20.0
23.5
26.5
28.5
17.5
22.0
26.5
31.0
32.5
37.5
11
15
19
22
25
27
1. From table W: select the symbol which gives the best centring of your core insulation diameter.
2. From table X: according to your conductor size and type, select the designation which completes the part number.
The complete (K)(M)430TBM-P3 connector kit comprises 3 x the following components:
In mm.
Table X
When installed on an appropriate equipment
bushing: 1250 A continuously
For use withother cable types.
Please contact our representative.
For use withcopper tape
screened cables. Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact our representative.
For applicationsoutdoors and in humid climate.
Order: +MWS.
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
35 35(K)M-10-2 35KM-10-1 35(K)M-11-250 50(K)M-10-2 50(K)M-10-1 50(K)M-11-270 70(K)M-10-2 70(K)M-10-1 70(K)M-11-295 95(K)M-10-2 95(K)M-10-1 95(K)M-11-2120 120(K)M-10-2 120(K)M-10-1 120(K)M-11-2150 150(K)M-10-2 150(K)M-10-1 150(K)M-11-2185 185(K)M-10-2 185(K)M-10-1 185(K)M-11-2240 240(K)M-10-2 240(K)M-10-1 240(K)M-11-2300 300(K)M-10-2 – 300(K)M-11-2
16.9
5-14
-5
95.2
40-1
4-5
50.1
50-1
4-5
120.
300-
12-5
16.9
5-14
-5
50.1
50-1
4-5
95.2
40-1
4-5
120.
300-
12-5
For use witheasy strip semi-conductive screened cables. Order: Field control mastic
(type MFC).
110 105
430TB teeconnector
300PBMcouplingconnector
290
300BIPAbasicinsulatingplug
300BIPAbasicinsulatingplug
300PBMcouplingconnectors
430TB teeconnector
18
01/2
011
ApplicationSeparable coupling connector (bolted type) for dual cable arrangement. It has been designed to be used with 440TB separable Tee connector.
Technical characteristics���������� �����������
jacket provides a total safe to touch screen.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
Up to 36 kV630 A (1250 A)
440PBMCOUPLING CONNECTOR
FOR 440TB
Specifications and standardsThe 440PBM coupling connector meets the requirements of CENELECHD 629.1.
Design 1. Interface designed to fit 440TB connector. 2. Bus for 440PBM. 3. Conductive EPDM insert. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Conductive EPDM jacket. 6. Conductive EPDM cap. 7. Basic insulating plug. 8. Conductor connector (hexagonal crimping, deep indent crimping or bolted). 9. Cable reducer. 10. Earthing lead.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
CurrentIr (A)
When installed on anappropriate equipment bushing
Conductor sizes (mm2)
min max
440PBM/GK440PBM/GM440PBM/G
122436
630630630
125012501250
185185185
630630630
400 mm
155 mm
440TBconnector
410 mm
440PBMcouplingconnector
1
2
8
3
4
5
9
7
6
10
19
Kit contentsThe complete(K)(M)440PBM/G coupling connector kit comprises 3 x the following components:
The kit also comprises silicone grease, field control mastic, installation rod, installation instructions and crimp chart.
For use withcopper tape
screened cables. Order: Kit MT.
For use witheasy strip semi-conductive screened cables. Order: Field control mastic
(type MFC).
For use with copperwire screened cables.
No earthingdevice is
necessary.
For use withother cable types.
Please contact our representative.
For outdoorapplications.
Order: +MWS.
Connector housing(K)(M)440BP/G
For use with fabric tape (graphite) screened cables.
Order additionalsemi-conductive tape
(type TSC).
3 x (K)(M)440PBM/G-W-X coupling connector kit
Conductorcontact TMBC-X
Conductor contact TBC-X
Ordering instructionsTo order the coupling connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV.
Example:The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm.Order 3 x M440PBM/G-32-240(K)M-12-2 coupling connector kit.
Orderingpart number
Dia. over core insulation (mm)
min max
3 x 440PBM/G-22-X3 x 440PBM/G-27-X3 x 440PBM/G-32-X3 x 440PBM/G-37-X3 x 440PBM/G-43-X
23.5
28.5
34.0
39.0
45.5
31.0
37.5
42.5
48.5
56.0
Table W
Contact rod 440PB-CR
+ M16 studCable reducer
611CA-W
Table X
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
185
240
300
400
500
630
185(K)M-12-2
240(K)M-12-2
300(K)M-12-2
400(K)M-12-2
500(K)M-12-2
–
185KM-12-1
240KM-12-1
300KM-12-1
400KM-12-1
500KM-12-1
630KM-12-1
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
400(K)M-11-2
500(K)M-11-2
630(K)M-11-2
400.
630-
14-5
20
01/2
011
ApplicationSeparable connectors (boltedtype) for dual cable arrangements.
Technical characteristics���������� �����������
jacket provides a total safe to touch screen.
���������������������������tested for AC withstand and partial discharge prior to leaving the factory.
Specifications and standardsThe 434TBM-P2 connectors meet the requirements of CENELEC HD 629.1.
Up to 36 kV630 A (1250 A)
Design 1. Type C interface as described by CENELEC EN 50180 and 50181. 2. Bus for 440PB. 3. Conductive EPDM insert. 4. Insulating EPDM layer moulded between the insert and the jacket. 5. Conductive EPDM jacket. 6. Conductive EPDM cap. 7. Basic insulating plug (with VD point). 8. Conductor connector. 9. Cable reducer. 10. Earthing lead. 11. Threaded M16 stud for the equipment bushing.
The screen break designenables cable outer sheathtesting without removing ordismantling the connector.
434TBM-P2DUAL CABLE ARRANGEMENT FOR
434TB CONNECTOR
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Separable connector
type
VoltageUm(kV)
CurrentIr
(A)
Current Ir (A)Conductor sizes (mm2)
When installed on an appropriate equipment bushing and when using a copper (-11-2) or a
bolted (-12-5 or -14-5) conductor contact min max
434TBM-P2K434TBM-P2M434TBM-P2
122436
630630630
125012501250
185185185
630630630
155 mm
345 mm
18
3
4
5
9
7
6
2
440PBcoupling
connector434TBconnector
11
10
21
Kit contentsThe complete (K)(M)434TBM-P2 connector kit comprises 3 x the following components:
In mm.
When installed on an appropriate equipment
bushing: 1250 A continuously
For use withother cable types.
Please contact our representative.
For use withcopper tape
screened cables. Order: Kit MT.
For use with Alupe orC 33-226 cables.
Please contact our representative.
For applicationsoutdoors and in humid climate.
Order: +MWS.
For use witheasy strip semi-conductive screened cables. Order: Field control mastic
(type MFC).
Ordering instructionsTo order the coupling connector, select the ordering part number which gives you the best centring of your core insula-tion diameter and substitute X using table X, according to your conductor size and type.Add a 'K' for use up to 24 kV, add an 'M' for use up to 36 kV.
Example:The copper wire screened cable is 36 kV, 240 mm2 stranded aluminium with a diameter over core insulation of 37.0 mm.Order 3 x M434TBM-P2-32-240(K)M-12-2 coupling connector kit.
Orderingpart number
Dia. over core insulation (mm)
min max
3 x 434TBM-P2-22-X3 x 434TBM-P2-27-X3 x 434TBM-P2-32-X3 x 434TBM-P2-37-X3 x 434TBM-P2-43-X
23.5
28.5
34.0
39.0
45.5
31.0
37.5
42.5
48.5
56.0
Table W
Table X
110 155
440PBcouplingconnector
434TBteeconnector
300BIPAbasicinsulatingplug
345
Conduc-tor sizes (mm2)
Aluminium conductor Copper conductor
DINhexagonal
Deepindent
BoltedDIN
hexagonalBolted
185
240
300
400
500
630
185(K)M-12-2
240(K)M-12-2
300(K)M-12-2
400(K)M-12-2
500(K)M-12-2
–
185KM-12-1
240KM-12-1
300KM-12-1
400KM-12-1
500KM-12-1
630KM-12-1
185(K)M-11-2
240(K)M-11-2
300(K)M-11-2
400(K)M-11-2
500(K)M-11-2
630(K)M-11-2
400.
630-
14-5
22
01/2
011
Up to 36 kV - 630 A
400AR-3INTERFACE C
EQUIPMENT BUSHING
ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...
Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.
Specifications and standardsThe bolted type equipment bushings 400AR-3 are moulded epoxy insulated parts and meet the requirements of CENELEC EN 50180 and IEC 60137.
Ordering instructionsTo order the equipment bushing, specify the type.The bushings can be supplied with an earth jumper (/J).E.g. M400AR-3/J.For use in potentially explosive atmospheres (for 12 kV max), order: 400AR-3/ATEX. Minimum oil level:
-12 kV: 40 mm-24 kV: 50 mm-36 kV: 70 mm
40
Dia. 128
133
144
330
Dia. 88
Dia.25
Dia. 70M16
10
30
In mm.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
400AR-3K400AR-3M400AR-3
122436
630630630
23
In mm.
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-3/J Bushing
Fixing dimensions standards DIN 42 538German standards.
M10
55
Dia. 140Dia. 90
25
6 fixingstuds
equipmentconnection
fixing studs
bushing interface
equipment
sealing gasket
fixing flangeB DIN 42 538
E DIN 42 538stud clamp
earth jumper
Bushing clamping kitTo order the bushing clamping kit, according to DIN 42 538 standards, simply specify KBCD-400B.Contents: - 1 x fixing flange B - 6 x stud clamp E - 1 x sealing gasket.
24
01/2
011
Up to 36 kV - 1250 A
400AR-4INTERFACE C
EQUIPMENT BUSHING
ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.
Specifications and standardsThe bolted type equipment bushings 400AR-4 are moulded epoxy insulated parts and meet the requirements of CENELEC EN 50180 and IEC 60137.
Ordering instructionsTo order the equipment bushing, specify the type.The bushings can be supplied with an earth jumper (/J) or an earth plate (/GS). This earth connection must be specified when ordering.E.g. M400AR-4/GS.
In mm.
40
10
138
329
Minimum oil level:-12 kV: 40 mm-24 kV: 50 mm-36 kV: 70 mm
36
139
Dia. 150Dia. 100Dia. 70
M16
Dia. 32
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
400AR-4K400AR-4M400AR-4
122436
125012501250
25
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-4/GS Bushing
Bushing clamping kitTo order the bushing clamping kit, according to NFC 52-053standards, simply specify KBCNF-400.Contents: - 4 x claw clamp NF - 1 x sealing gasket.
In mm.
Fixing dimensions standards NF C 52-053French standards.
400AR-4/J Bushing
NF C 52-053claw clamp
earth plate
bushing interface
fixing studs
equipment
equipmentconnection
sealing gasket
earth jumper
F DIN 42 538stud clamp
fixing flange
Bushing clamping kitTo order the bushing clamping kit with DIN style fixing flange, simply specify KBCDS-400.Contents: - 1 x fixing flange DIN style - 6 x stud clamp F DIN 42 538 - 1 x sealing gasket.
Fixing dimensions
Dia. 105Dia. 171
6030
6 fixingstuds
M10M10 or
M12
Dia. 105Dia. 171
50 to70 25
4 fixingstuds
26
01/2
011
Up to 36 kV - 1250 A
400AR-5INTERFACE C
EQUIPMENT BUSHING
ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.
Ordering instructionsTo order the equipment bushing, specify the type.The bushings can be supplied with an earth jumper (/J) or an earth plate (/GS). This earth connection must be specified when ordering.E.g. M400AR-5/GS.
In mm.
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
400AR-5K400AR-5M400AR-5
122436
125012501250
32
72
245
Minimum oil level:-12 kV: 40 mm-24 kV: 50 mm-36 kV: 70 mm
36
139
Dia. 150Dia. 76
M16
Dia. 32
Specifications and standardsThe bolted type equipment bushings 400AR-5 are moulded epoxy insulated parts and meet the requirements of CENELEC EN 50180 and IEC 60137.
27
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-5/GS Bushing
In mm.
NF C 52-053claw clamp
earth plate
bushing interface
fixing studs
equipment
equipmentconnection
sealing gasket
earth jumper
F DIN 42 538stud clamp
fixing flange
Bushing clamping kitTo order the bushing clamping kit, according to NFC 52-053standards, simply specify KBCNF-400.Contents: - 4 x claw clamp NF - 1 x sealing gasket.
Fixing dimensions standards NF C 52-053French standards.
Bushing clamping kitTo order the bushing clamping kit with DIN style fixing flange, simply specify KBCDS-400.Contents: - 1 x fixing flange DIN style - 6 x stud clamp F DIN 42 538 - 1 x sealing gasket.
Fixing dimensions
Dia. 105Dia. 171
6030
6 fixingstuds
M10M10 or
M12
Dia. 105Dia. 171
50 to70 25
4 fixingstuds
400AR-5/J Bushing
28
01/2
011
Up to 36 kV - 630 A
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
400AR-6
K400AR-6
M400AR-6
12
24
36
630
630
630
400AR-6INTERFACE C
EQUIPMENT BUSHING
ApplicationFor use in equipment insulated with oil fluid, typically for transformers, switchgear, capacitors...
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV
Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.
Ordering instructionsTo order the equipment bushing, specify the type.The bushings can be supplied with an earth jumper (/J). This earth connection must be specified when ordering.E.g. M400AR-6/J.
In mm.
Specifications and standardsThe bolted type equipment bushings 400AR-6 are moulded epoxy insulated parts and meet the requirements of CENELEC EN 50180 and IEC 60137.
40
Dia. 128Dia. 74Dia. 70
10
213
398
Minimum oil level:-12 kV: 40 mm-24 kV: 50 mm-36 kV: 70 mm
30
133
Dia.25
M16
29
FIXINGS FOR EQUIPMENT BUSHINGS
400AR-6/J Bushing Bushing clamping kitTo order the bushing clamp-ing kit, according to DIN 42 538 standards, simply specify KBCD-400B.Contents: - 1 x fixing flange B - 6 x stud clamp E - 1 x sealing gasket.
In mm.
Fixing dimensions standards DIN 42 538German standards.
equipmentconnection
fixing studs
bushing interface
equipment
sealing gasket
fixing flangeB DIN 42 538
E DIN 42 538stud clamp
earth jumper
M10
55
Dia. 140Dia. 80
25
6 fixingstuds
30
01/2
011
Up to 36 kV630 A & 1250 A
400SFR-BINTERFACE C
EQUIPMENT BUSHING
ApplicationFor use in equipment insulated with SF6 gas.
DesignThe equipment bushing is a moulded epoxy insulated part with a connector interface in accordance with CENELEC EN 50180. The 400SFR-B bushing has a shank outside this standard, adapted to use in SF6 gas.
Technical characteristics Each bushing is tested forAC withstand and partialdischarge prior to leaving thefactory.
Ordering instructionsTo order the equipment bushing, simply specify the type.
Specifications and standardsThe bolted type equipment bushing 400SFR-B meets the requirements of CENELEC EN 50180 and IEC 60137.
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
Dia. D(mm)
400SFR-B
K400SFR-B
M400SFR-B
400SFR-B 1250 A
K400SFR-B 1250 A
M400SFR-B 1250 A
12
24
36
12
24
36
630
630
630
1250
1250
1250
25
25
25
32
32
32
Dia. 70
95
33
219.5
Dia. 70
Dia. 109
Dia. D
M12
In mm.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
31
FIXINGS FOR EQUIPMENT BUSHINGS
400SFR-B Bushing for gas insulated switchgear
In mm.
MOUNTED
equipment
sealingO-ringgasket
equipmentconnection
bushinginterface 6 fixing
screwsM6
60°
60°60°
UNMOUNTED
Dia. 91.5Dia. 103.1
83
earthconnection
M4
M6
M4
32
01/2
011
400A-24BINTERFACE C
IN-AIR BUSHING
Up to 24 kV - 630 A
Ordering instructionsTo order the equipment bushing, specify the type.The bushings are supplied with an earth jumper.To include the ring clamp, add:������������������������� �� �����������������!������� �� ����"���������"��������� �� �#E.g. 400A-24B/D.For use in potentially explosive atmospheres (for 12 kV max), order: -/ATEX.
Technical characteristics Each bushing is tested forAC withstand and partial discharge prior to leavingthe factory.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
Equipmentbushing
type
VoltageUr
(kV)
CurrentIr
(A)
Creepage distanceA-B
(mm)
400A-24B
400A-24B
12
24
630
630
520
520
In mm.Dia. 80
30
20
Dia. 80
Dia. 110
40
250
434
M16 B
A
Dia.25
ApplicationFor use in equipment insulated with air, typically for dry type transformers, motors, switchgear, capacitors...
Specifications and standardsThe bolted type equipment bushings 400A-24B are moulded epoxy insulated parts and meet the requirements of CENELEC EN 50180, IEC 60071 and IEC 60137.
33
400A-24B In-air bushing
In mm
FIXINGS FOR EQUIPMENT BUSHINGS
10
Dia.12
Type BCA-B : BS 2562 British standardsType BCA-D : DIN 42 538 German standards
4Dia. 94.5
Dia. 111
BS 2562 stand.: 120DIN 42 538 stand.: 123
Dia. 150
F
120°
120°
Type BCA-F : NFC 52-053 French standards
Dia. 150
10
Dia.124
Dia. 94.5
Dia. 111
126
fixing studs andnuts M10
bushing interface
earth jumper
equipment
gasket
equipmentconnection
fixing flangeBCA-B orBCA-D
fixing flangeBCA-F
Fixing dimensions standards NF C 52-053French standards.
Fixing dimensions standards DIN 42 538German standards.
M10
Dia. 123Dia. 82
5520
4 fixingstuds
3 fixingstuds
Dia. 82
5220
M10
Dia. 126
34
01/2
011
ApplicationSurge arrester designed to protect 12, 24 and 36 kV class components, including transformers, equipment, cable and accessories from high voltage surges resulting from lightning or switching.It has been designed to be used with the 430TB or 434TB separable tee connector.
Up to 36 kV
300SASURGE ARRESTER
FOR 430TB AND 434TB CONNECTOR
Technical characteristics ����������$����������������!�����
oxide varistor surge arrester in an elbow configuration.
����������������������� ������%�withstand, partial discharge and critical voltage prior to leaving the factory.
Surgearrester
type
Nominal discharge
currentIn (kA)
Rated voltageUr (kV)
Max. continuousoperatingvoltageUc (kV)
Dimensions(mm)
L1 L2
300SA-10-15N300SA-10-18N300SA-10-22N300SA-10-24N300SA-10-30N300SA-10-36N300SA-10-45N
10101010101010
15182224303645
12.014.417.619.224.028.836.0
230230230320320320430
270270270360360360470
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Dia.65 mm
170 mm
105 mm
Dia.75 mm
L2
L1
5
2
1
3
4
6
7
8
9
DesignSurge arrester comprising:1. Interface designed to fit the 430TB/G or 434TB/G tee connector. 2. Conductive EPDM insert.3. Conductive EPDM jacket.4. Insulating EPDM layer moulded between the insert and the jacket.5. Receptacle for contact rod.6. Metal oxide valve elements.7. Steel cap.8. Earth connection.9. Earth lead.
Specifications and standardsThe 300SA surge arresters meet the test requirements of IEC 60099-4.
35
Typical application anddimensions
Ordering instructionsTo order the surge arrester, specify the surge arrester type, as described on previous page.
Example:For a maximum continuous operating voltage (r.m.s.) of 24 kV and a nominal discharge current of 10 kA.Order a 300SA-10-30N surge arrester.
Technical data
Surgearrester
type
Steep currentresidual
voltage @ 10 kA[1/20 μs] (kV)
Lightning currentresidual voltage[8/20 μs] (kV)
Switching impulseresidual voltage[36/90 μs] (kV)
High currentimpulse
withstand(kA)@ 5 kA @ 10 kA @ 20 kA @ 125 A @ 500 A
300SA-10-15N300SA-10-18N300SA-10-22N300SA-10-24N300SA-10-30N300SA-10-36N300SA-10-45N
48.158.170.177.097.0
115.9144.1
39.748.057.963.680.195.7
119.0
43.252.263.069.287.2
104.2129.5
48.458.570.677.697.7
116.8145.1
30.536.844.448.861.573.591.3
32.539.247.352.065.578.397.3
100100100100100100100
290 mm
180 mm 107 mm
Type430TB or
434TBtee connector
Type 300SAsurge arrester
36
01/2
011
ApplicationSurge arrester designed to protect medium voltage components, including transformers, equipment, cable and accessories from high voltage surges resulting from lightning or switching.
Up to 36 kV
400PB-XSAINTERFACE C
SURGE ARRESTER
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
Surgearrester
type
Nominal discharge
currentIn (kA)
Rated voltageUr (kV)
Max. continuousoperatingvoltageUc (kV)
Dimensions(mm)
L1 L2
400PB-5SA-15L400PB-5SA-18L400PB-5SA-22L400PB-5SA-24L400PB-5SA-30L
400PB-10SA-15N400PB-10SA-18N400PB-10SA-22N400PB-10SA-24N400PB-10SA-30N400PB-10SA-36N400PB-10SA-45N
55555
10101010101010
151822243015182224303645
12.014.417.619.224.012.014.017.619.224.028.836.0
250250350350350250250350350350350450
290290390390390290290390390390390490
Technical characteristics ����������$����������������!�����
oxide varistor surge arrester in an elbow configuration.
����������������������� ������%�withstand, partial discharge and critical voltage prior to leaving the factory.
4
1
2
3
8
7
6
5
9
252 mm
150 mm
Dia.80 mm
L2L1
Dia.70 mm
DesignSurge arrester comprising:1. Conductive EPDM insert.2. Conductive EPDM jacket.3. Insulating EPDM layer moulded between the insert and the jacket.4. Contact rod.5. Earthing lead.6. Earth connection.7. Steel cap.8. Metal oxide valve elements.9. Type C - 630 A interface as described by CENELEC EN 50180 and 50181.
Specifications and standardsThe 400PB-XSA surge arresters meet the test requirements of IEC 60099-4.
37
Typical applications anddimensions
Ordering instructionsTo order the surge arrester, specify the surge arrester type, as described on previous page.
Example:For a maximum continuous operating voltage (r.m.s.) of 24 kV and a nominal discharge current of 10 kA.Order a 400PB-10SA-30N surge arrester.
Technical data
Surgearrester
type
Steep currentresidual
voltage @ 10 kA[1/20 μs] (kV)
Lightning currentresidual voltage[8/20 μs] (kV)
Switching impulseresidual voltage[36/90 μs] (kV)
High currentimpulse
withstand(kA)@ 5 kA @ 10 kA @ 20 kA @ 125 A @ 500 A
400PB-5SA-15L400PB-5SA-18L400PB-5SA-22L400PB-5SA-24L400PB-5SA-30L
400PB-10SA-15N400PB-10SA-18N400PB-10SA-22N400PB-10SA-24N400PB-10SA-30N400PB-10SA-36N400PB-10SA-45N
47.156.569.275.294.048.158.170.177.097.0
115.9144.1
38.946.757.162.177.639.748.057.963.680.195.7
119.0
42.350.862.267.684.543.252.263.069.287.2
104.2129.5
47.456.969.775.894.748.458.570.677.697.7
116.8145.1
29.835.843.847.759.630.536.844.448.861.573.591.3
31.838.246.750.863.532.539.247.352.065.578.397.3
6565656565100100100100100100100
185 mm
410 mm
220 mm
Type400TB
or 440TBtee connector
Type 400PB-5SAor 400PB-10SAsurge arrester
38
01/2
011
400TR and 400TR-LBINTERFACE C
TEST RODS
Application������������� ���������� ����* - cable fault location - cable testing - phasing checks, etc.��%����������!�;����!� ��
with a cable lug, a 4 mm plug or spring clips.
InstallationThe test rod is mounted onto the clamping screw in the type C interface tee and coupling connectors. The test cable is connected to the threaded stem and the insulating shroud moved to its final position over the end of the test rod.
Design1. Insulating shroud.2. Threaded rod for test connection.3. Two nuts M12.4. Insulation.5. Copper test rod stem.6. Wing nut.
An insulating shroud isprovided to allow theapplication of test voltageswhen bushings are closelyspaced.
Test rod type
Maximum A.C.test voltage
(50 Hz - 1 min)
Maximum D.C.test voltage
(8 x U0 - 30 min)
Impulse voltage (1.2 x 50 μs)
min
400TR
400TR-LB
36 kV
36 kV
96 kV
96 kV
95 kV
95 kV
Technical characteristics ������<==�>�������� ����
be used with 400TE, 430TB, 400TB and 440TB connectors.
������<==�>?@�������������Q����the 400LB connector.
In mm.
400TR 400TR-LB
Ordering instructionsSimply specify:400TR or 400TR-LB test rod.
465
310
M10
Dia.25
60
1
2
6
4
5
1
2
4 288
480
403
5
M12
39
01/2
011
400TK & 400SWINSTALLATION TOOL
Application��������Y����������� ���Y�
spanner key are designed to facilitate assembly of 400TE, 400TB and 440TB connectors.
������<==�Z���Y������������used to install the 400TEF clamping pin contact or 400TCS clamping screw.
Ordering instructionsSimply specify:- 400TK box spanner- 400SW box spanner key
������<==[\���Y���������key fits on the hex nut of the 400BIPA basic insulating plug.
400TK
400SW
40
01/2
011
ACCESSORIESINTERFACE C
Up to 36 kVApplicationFor use with connectors and bushings with an interface C as described by CENELEC EN 50180 and 50181.
Technical characteristics All these products, except theearthing plugs, are tested forAC withstand and partial discharge prior to leavingthe factory.
400SOP-BStand-off plugIs designed to support and 'dead-end' connectors with a type C interface when removed from equipment.
Ordering instructionsOrder 400SOP-B for 12 kV,K400SOP-B for 24 kV,M400SOP-B for 36 kV orP400SOP-B for 41.5 kVapplications.
400GP-BEarthing plugIs designed to support and earth connectors with a type C interface when removed from equipment.
Ordering instructionsOrder 400GP-B for 12, 24, 36 or41.5 kV applications.
300GP-BEarthing plugIs designed to earth the 430TB and 434TB connectors when it is fixed-mounted to the equipment (maintenance earthing).
Ordering instructionsOrder 300GP-B for 12, 24, 36 or41.5 kV applications.
400DR-BDead-end receptacleFits over a bushing with a type C interface to provide 'dead-end' facility.
Ordering instructionsOrder 400DR-B for 12 kV,K400DR-B for 24 kV orM400DR-B for 36 kVapplications.The dead-end receptacle canbe supplied with an earth lead.Order with suffix -/G.E.g. K400DR-B/G.
6/10 (12) kV6.35/11 (12) kV8.7/15 (17.5) kV
12/20 (24) kV12.7/22 (24) kV
18/30 (36) kV19/33 (36) kV
41
Kit MTEarthing kit for copper tape screened cablesContains a tinned copper braid (25 mm² - L = 500 mm), a tinned copper wire for cleating and some water sealing mastic.
Ordering instructionsOrder Kit MT for 12 kV, 24 kV 36 kV or 41.5 kV applications.
400RTPAReducing tap plugProvides a type A interface to connectors with a type C interface.A 'C' spanner, 600SW, is used to tighten the reducing tap plug on to its mating part.
Ordering instructionsOrder 400RTPA for 12 kV or K400RTPA for 24 kVapplications.
Order 600SW for the 'C'spanner.
400CP-SCConnecting plugFor connecting two or more connectors with a type C interface together, thus creating a separable cable joint or a multiple cable connection to equipment.
Ordering instructionsOrder 400CP-SC for 12 kV, K400CP-SC for 24 kV orM400CP-SC for 36 kVapplications.
400BIPABasic insulating plugActs as a tightening nut for the 400TB and 440TB tee connector kits.The plug contains a voltage detection point.The conductive rubber protection cap is included.
Ordering instructionsOrder 400BIPA for 12 kV, K400BIPA for 24 kV M400BIPA for 36 kV orP400BIPA for 41.5 kVapplications.
440CPConnecting plugFor connecting two or more 440TB connectors, thus creating a separable cable joint or a multiple cable connection to equipment.For use up to 1250 A.Only for use with 440TB.
Ordering instructionsOrder 440CP for 12 kV, K440CP for 24 kV orM440CP for 36 kVapplications.
Order (K)(M)440CP + 676SA for connection to an already installed 440TB connector.
430CPConnecting plugFor connecting two or more 430TB connectors, thus creating a separable cable joint or a multiple cable connection to equipment.
Ordering instructionsOrder 430CP for 12 kV orK430CP for 24 kV applications.
42
01/2
011
POSSIBLE ARRANGEMENTSINTERFACE C
430TBSingle cable arrangement.Order 430TB for 12 kV,K430TB for 24 kV or M430TB for 36 kV applications.
430TBM-P2Dual cable arrangement.Order 430TBM-P2 for 12 kV,K430TBM-P2 for 24 kV or M430TBM-P2 for 36 kV applications.
In mm.
430TBM-P3Triple cable arrangement.Order 430TBM-P3 for 12 kV,K430TBM-P3 for 24 kV or M430TBM-P3 for 36 kV applications.
430TBM-L33-way connection.Order 430TBM-L3 for 12 kV,K430TBM-L3 for 24 kV or M430TBM-L3 for 36 kV applications.
185
300BIPAbasicinsulatingplug
430TB teeconnector
425
300PBMcouplingconnectors
430TB tee connector
400BIPA basic
insulating plug
300BIPAbasicinsulatingplug
110 105
430TB teeconnector
300PBMcouplingconnector
290
300BIPAbasicinsulatingplug
300BIPAbasicinsulatingplug
300PBMcouplingconnectors
430TB teeconnector
43
434TBSingle cable arrangement.Order 434TB for 12 kV,K434TB for 24 kV or M434TB for 36 kV applications.
110 155
440PBcouplingconnector
434TBteeconnector
300BIPAbasicinsulatingplug
345
434TBM-P2Dual cable arrangement.Order 434TBM-P2 for 12 kV,K434TBM-P2 for 24 kV or M434TBM-P2 for 36 kV applications.
434TBM-P2 + 300SADual cable arrangement with surge arrester.Order 434TBM-P2+300SA for 12 kV, K434TBM-P2+300SA for 24 kV or M434TBM-P2+300SA for 36 kV applications.
440TB + 400PB-XSACable arrangement with surge arrester.Order 440TB+400PB-XSA for 12 kV, K440TB+400PB-XSA for 24 kV or M440TB+400PB-XSA for 36 kV applications.
110
185
300BIPAbasicinsulatingplug
434TB teeconnector
110
400BIPA basicinsulatingplug
400PB-XSAsurge arrester
440TBtee connector
410
110 155
450
300BIPA basicinsulatingplug
440PBcouplingconnector
300SAsurge arrester
434TBtee connector
44
In mm.
400TB/GSingle cable arrangement.Order 400TB/G for 12 kV, K400TB/G for 24 kV,M400TB/G for 36 kV or P400TB/G for 41.5 kV applications.
400TB/G-P2Dual cable arrangement.Order 400TB/G-P2 for 12 kV, K400TB/G-P2 for 24 kV or M400TB/G-P2 for 36 kV applications.
400TB/G-L22-way connection.Order 400TB/G-L2 for 12 kV, K400TB/G-L2 for 24 kV or M400TB/G-L2 for 36 kV applications.
250
teeconnector
basicinsulatingplug
110
400TB/G-L33-way connection.Order 400TB/G-L3 for 12 kV, K400TB/G-L3 for 24 kV or M400TB/G-L3 for 36 kV applications.
500
110 245
basicinsulating
plug
connectingplug
45
Connector on stand-off plugOrder 400SOP-B for 12 kV, K400SOP-B for 24 kV or M400SOP-B for 36 kV applications.
In mm.
400TB/G-L4Disconnectable tap-off.Order 400TB/G-L4 for 12 kV, K400TB/G-L4 for 24 kV or M400TB/G-L4 for 36 kV applications.
400TB/G-L52-way connection with tap-off.Order 400TB/G-L5 for 12 kV or K400TB/G-L5 for 24 kV applications.
505
400TB/G teeconnectorstand-off
plug
400BIPAbasicinsulatingplug
430TB teeconnector
stand-offplug
300BIPAbasicinsulatingplug
46
Earthing plug on connectorOrder 300GP-B for 12 kV, 24 kV and 36 kV applications.
In mm.
Cable and equipment testing
Connector on earthing plugOrder 400GP-B for 12 kV, 24 kV and 36 kV applications.
Additional catalogue information on power cable accessoriesis available by contacting us at the address below: