Prefabricated busbar trunking from 1000 to 5000 A
Canalis
CatalogueCanalis KTC
K9CE01010
PD
2023
81
PD
2023
82
PD
2023
43
1Schneider Electric
Intr
oduc
tion
In decentralised distribution,Canalis hits the high note!
Canalis on its second world tourTo better meet your needs, Canalis extends its system solutions.New low and medium power busbar trunking products.Pre-equipped luminaires.Strip lighting.Specially designed cable trays.
A total coordination with theSchneider Electric systemCanalis is now part of a comprehensive offering of Schneider Electric products designed to operate together. This concept covers all low and medium voltage electrical distribution components. The result is an optimised electrical installation with even higher performance through full electrical, mechanical and communication compatibility.With the new Canalis range, you get a complete, tested distribution solution that complies with standards. It is perfectly suited to traditional applications (factories, warehouses, etc.) and to the distribution of electrical power from the incoming transformer on through to all types of loads in offi ces, commercial premises, laboratories, etc.
Canalis KT is changing to provide you with
more fl exibility. The adjustable section adapts to the worksite thus making sure you meet deadlines.
bbbbb
b
ease of connection with the plug and play transformer and switchboard connections.
more assistance. Our teams will assist you throughout your project.
b
b
Canalis moves forward without changing the way you workThe new Canalis range is fully compatible with the existing range.An existing installation can be upgraded without any problem.
More than 50,000 km of Canalis busbar trunking has been sold around the world.
K9CE01020
PD
2020
43P
D20
2044
PD
2021
55
2 Schneider Electric
Intr
oduc
tion
With Canalis, you play all the right notes!
Distribution systems Schneider Electric offers different distribution systems to fi t your operating needs.
Centralised distributionFor all continuous processes:cement plantsoil and gaspetrochemicalssteelpaper, etc.Centralised distribution offers:continuity of servicecombined distribution of power, control and monitoring circuitssupervision, etc.
Our solutions:Prisma Plus and Okken switchboards.
bvvvvvbvvv
b
Decentralised distributionFor manufacturing industries:mechanicaltextileslumberinjection mouldingelectronicspharmaceuticalslivestock, etc.Decentralised distribution lets you:design installations without layout detailsupgrade without shutting down productionget systems up and running sooner thanks to faster installationgenerate savings depending on the number of loads.
Our solutions:Prisma Plus switchboardsCanalis busbar trunking.
bvvvvvvvbvvvv
bb
Combined distributionWhere the advantages of both centralised and decentralised distribution are required.
Commercial and service buildings:offi cesstoreshospitalsexhibition halls, etc.Infrastructures:airportstelecommunicationsinternet data centrestunnels, etc.Industrial facilities:pharmaceuticalsfood processing, etc.
Our solutions:Prisma Plus and Okken switchboardsCanalis busbar trunking.
bvvvvbvvvvbvv
bb
K9CE01020
PD
2023
83P
D20
2427
3Schneider Electric
Intr
oduc
tion
With Canalis, you play all the right notes!
The Canalis decentralised distribution concept
Electrical power available at all points,throughout the installation.
Exclusive features of the Schneider Electric systemTotal coordination of the Schneider Electric system provides maximum safety of life and property, continuity of service, upgradeability and ease of installation.Total coordination is made easy by the tables in the Selection Guide. They help you chose the right combination of circuit breakers and busbar trunking.Product characteristics are checked by calculations and tests carried out in our laboratories.
A competitive installation.Simplicity, upgradeability, safety and continuity of service and operation.
Savings start with installationWith tap-off points every 3 metres, Canalis busbar trunking reduces installation costs.Given the low cost of adding new circuits, savings increase as the number of loads increases, a natural consequence of the growth of your business.
Upgradeable during operationIn decentralised distribution, evolving operating requirements and costs are integrated right from the start.
The addition, relocation or replacement of load equipment can be carried out quickly, without de-energising the supply trunking or shutting down operation.
The cost of making such changes is greatly reduced:loads are located close to supply pointstap-off points are always availabletap-units can be reused or new ones added quickly for load relocation or
replacement needs.
b
bvvv
Reusable in the event of major changesWhen making major modifi cations to your installation, the existing trunking can be easily dismantled and reused.
DD
2056
58
K9CE01030
DD
2056
75D
D20
5674
2 Schneider Electric
Intr
oduc
tion
Canalis, in total harmony with the environment!
Safety of life and property With Canalis, no risk in case of fi reThe busbar trunking has a low combustible load. Its construction uses very little consumable material and is halogen free.In the event of a fi re, the busbar trunking does not emit any gas or toxic smoke.
An inherent fi re barrier, the busbar trunking helps prevent the propagation of a fi re through partition walls and fl oors for a duration of 2 hours.
Halogen-sensitive applicationsPublic buildings (infrastructures, hospitals, schools, etc.).Buildings with evacuation diffi culties (high-rises, ships, etc.) and service-activity
buildings.Sensitive processes (production of electronic components, etc.).
Canalis contains no PVCsWhen PVCs burn, they produce large amounts of smoke that can be a serious safety hazard.
Reduced visibility:risk of paniccomplicates rescue workSmoke toxicity:hydrogen chloride gas (highly toxic)carbon monoxide (danger of asphyxiation).
bb
b
bvvbvv
Canalis reduces the risk of exposure to electromagnetic fi eldsAccording to the WHO (World Health Organisation), exposure to electromagnetic fi elds can be a health hazard starting at levels as low as 0.2 micro-Teslas and could represent a long-term risk of cancer. Some countries have created standards that stipulate limits (e.g. 0.2 T at 1 metre in Sweden).
All electrical conductors generate magnetic fi elds proportional to the distance between them. The design of Canalis busbar trunking with tightly spaced conductors in a metal enclosure helps to considerably reduce radiated electromagnetic fi elds.
The electromagnetic fi eld characteristics of Canalis busbar trunking are well-defi ned and measurements show that they are far below potentially dangerous levels.You will fi nd the magnetic induction values of our products on the Characteristics pages.
Example:Consequences of a fi re in a 100 m2 offi ce with electrical distribution by cables.200 kg of cables (i.e. 20 kg of PVC) produces:
4400 m3 of smoke7.5 m3 of hydrochloric acid3.7 kg of corroded steel.
bbb
Health
K9CE01030
DD
2056
73
3Schneider Electric
Intr
oduc
tion
Canalis, in total harmony with theenvironment!
Environment Canalis is fully recyclableCanalis busbar trunking can be reused.
Canalis busbar trunking is designed for a long service life and can easily be dismantled, cleaned and reused.
All packaging materials can be recycled (cardboard or recyclable polyethylene fi lm).
All Canalis products are designed for safe end-of-life recycling. PVC, on the other hand, requires neutralisation of the hydrochloric acid produced using lime and generates dioxins that are extremely toxic.
Canalis helps conserve natural resourcesThe depletion of raw materials (copper, plastics, etc.) is one of our ongoing concerns.For this reason, we have optimised the used of all materials used to make our busbar trunking.
Reduction of dangerous or polluting materials. We design our products to meet future European directives.
Reduction in the weight of insulating materials.Reduction in the use of plastics for improved fi re performance: less energy
released during combustion, thereby limiting propagation and facilitating extinction (lower calorifi c value).
b
b
b
b
bb
Example:1 kg of PVC generates 1 kg of waste.
Energy savings Canalis reduces your line losses by 40 %Canalis divides your consumption of copper and insulation by a factor of threeThe cost of an electrical installation includes the initial investment for the equipment and its installation, the cost of maintenance and the cost of energy losses during operation.The cross-sections of our products are dimensioned to minimise the total cost of your installation over a 3-year period for medium intensity use (30 % load level,5 days a week and 10 hours a day).
Example:30 m of Canalis KS 250 A trunking equipped with ten 4-pole 25 A feeders.
DD
2056
56
K9CE01040
PD
2023
84
2 Schneider Electric
Intr
oduc
tion
Canalis, fortissimo throughoutthe range!
K9CE01040 3Schneider Electric
Intr
oduc
tion
Canalis, fortissimo throughoutthe range!
K9CE02010
PD
2023
85D
D20
2860
2 Schneider Electric
Intr
oduc
tion
Canalis KT, a display of advantages!
The compact size of Canalis KT means it takes up very little space in the building:
used as a rising main, it takes up only a minimum of space,used for horizontal distribution, it fi ts easily into the buildings structure (false
fl oors, false ceilings, service shafts, etc).
Changes in direction have been designed to optimise the space taken up, contrary to an equivalent installation using cables which requires large bending radii.
Tap-off units, complete with protective devices, are fi tted along the entire length of the busbar trunking thus reducing the fl oor area taken up by the electrical distribution switchboards.
b
vv
b
b
A compact solution
A simple and economical system
The design study is easy to perform as it does not require a detailed layout of each load. Equipment choice is pre-determined and optimised.
Installing the busbar trunking requires 2 or 3 people only, for a time equivalent to that for installing cableways. The time normally needed for laying cables is therefore saved.
Connection to the MV/LV substation is made using a quick fi tting joint block. The tap-off units can be prepared in the workshop thus reducing on-site time. Their connection to the busbar trunking is done in a single plugging-on operation.
Installing busbar trunking lengths can be done as and when building work progresses, thus optimising on-site work and allowing possible unexpected events to be anticipated in advance.
It is also important to note that busbar trunking is a factory tested solution, meaning the time needed for inspecting connections is reduced (visual inspection of tightening torque).
b
b
b
b
b
K9CE02010
PD
2022
29-6
8P
D20
2386
3Schneider Electric
Intr
oduc
tionComplete safety Busbar trunking temperature rise and short-circuit withstand are known and independent of the installation. Coordination of the Schneider Electric system
results in complete control of the electrical network.
Installation standards UTE C 15-105 chapter B.6.2 and IEC 60 364 chapter 5.523.6 stipulate that above 4 parallel cables, it is preferable to use busbar trunking. Paralleling many cables leads to uneven distribution of currents and the risk of abnormal temperature rise.
The busbar trunking and tap-off units are designed to guarantee the safety of personnel and equipment:
plug-on connections to silver-plated copper bars,bolted connections with tightening torque guaranteed by torque nuts,foolproof system to avoid the risk of assembly errors,IP55 certifi ed splash and dust protection,sprinkler resistance test in compliance with Volkswagen specifi cations,access to live parts have IPxxD protection (1 mm wire diameter).
Its metal enclosure and high protection degree protect the busbar trunking from all external aggressions (corrosion, rodents, etc).
b
b
b
vvvvvv
Operating continuity When working on the electrical installation, the busbar trunking provides immediate readability of the electrical circuit thus allowing the appropriate zone to be quickly identifi ed.Tap-off units can be plugged-on and off without the need for a shutdown; service continuity is thus irreproachable.
The quality of the electrical contacts guarantees maintenance free operating continuity.
A large range of tap-off units Canalis KS tap-off units are fully compatible with Canalis KT:they cover all your requirements:Canalis KS tap-off units: 63 to 400 A,Canalis KT tap-off units: 400 to 1000 A,they offer circuit-breaker or fuse protection.
This offer includes tap-off units that can be fi tted with the Transparent Ready system:
they monitor your installation to avoid overloads, thus ensuring service continuity,they provide metering to allow accurate management of your electrical
distribution network (allocation of costs to each consumer).
bvvb
vv
Canalis KT, a display of advantages!
K9CE02020
PD
2023
91
PD
2023
88
PD
2023
87
PD
2023
89
PD
2023
90
2 Schneider Electric
Intr
oduc
tion
Canalis KT, everyone to their music!
Key points
Fire barrier.
Halogen free.
Small size.
Operating continuity.
b
b
b
b
Offi ce and hospital buildings
Key points
Halogen free.
Distribution and metering.
Able to be evolved.
Sprinklers.
b
b
b
b
Shopping centres, airports and exhibition centres
K9CE02020
PD
3950
77-6
8
PD
2023
92
PD
2023
93
1094
05
PD
2023
94
PD
2023
95
3Schneider Electric
Intr
oduc
tion
Canalis KT, everyone to their music!
Key points
Operating continuity.
Able to be evolved.
Low voltage drops.
Network readability.
b
b
b
b
Car industry andindustrial buildings
Key points
Operating continuity.
High tap-off density.
Able to be evolved.
Network compactness and readability.
b
b
b
b
Internet Data Centers
K9CE020302 Schneider Electric
Intr
oduc
tion
Play all the worlds musicwith Canalis!
TertiaryName Lighting and low current Medium current High
currentCountry
KDP KBA KBB KN KS KT
Offi ces
PD
2022
44 Air France (headquarters) b b FranceAllianz b b GermanyAxa b b FranceChamber of Commerce b b LuxembourgCommerz Bank b b GermanyLexel b b b SwedenTelefnica b b SpainTrade Center b b SpainTour du RDC b b TunisiaTurning Torso b SwedenVodafone b b New Zealand
Internet Data Center
PD
2022
45 Banco Commercial Portugus b b PortugalColt b b FranceDigiplex b b SwedenIBM b b b b Spain, ItalyMCI-Worldcom b b b b Italy, United Kingdom
Hotels and restaurantsHyatt b TunisiaMc Donalds b FranceSoldeo Andorra Hotel b b Spain
Hospitals
PD
2022
47 Children Clinic b b SwedenBrussels University Hospital b BelgiumDerby Hospital b United KingdomOran Hospital b b AlgeriaSt Joseph Hospital b FranceStockholm Hospital b SwedenVal de Grce Hospital b FranceMichalon Hospital b b FranceManussia Hospital b Egypt
Supermarkets and hypermarkets
PD
2022
48 Alcampo b b b SpainAuchan b b b b b b WorldB&Q b b b United KingdomCarrefour b b b b b b WorldCoop b b b ItalyFnac b b Spain, FranceIkea b b b b b China, Spain, France,
SwedenMark & Spencer b Belgium, Spain,
United KingdomToysR Us b Spain
Play all the worlds music
K9CE02030 3Schneider Electric
Intr
oduc
tion
with Canalis!
IndustryName Lighting and low current Medium current High
currentCountry
KDP KBA KBB KN KS KT
Car industry
PD
2022
49 BMW b b b b ItalyCitron b b b b b b China, Spain, FranceDaewo b South KoreaDacia b b b b b RomaniaIveco b b b b Spain, ItalyPeugeot b b b b China, Spain, FranceNissan b b b b b SpainRenault b b b b b Spain, France, Czech
RepublicSeat SpainValo b b b China, France, Italy,
PolandVolkswagen b b b Spain, Germany
Other industriesAerospace industry
Airbus b b b Italy
Food-processing industryCoca-Cola b b Spain, Italy, BelgiumDanone b b b WorldPasquier b b France
Livestock production farms and greenhousesFavier henhouse b b FranceGreenhouse b Netherlands
Ceramic industryEsmalglas ceramic b b b b b Spain
ElectricityLegrand b France, Turkey
Watch-makingRolex b b b Switzerland
MicroelectronicsIntel b b b b IrelandeST Micro-lectronique b b b b France
Lead industry and water treatmentGrundfos b China
Industrial technologyBosch b b China
TelephonyPhillips b NetherlandsNokia b b Sweden
Textile industryLouis Vuitton b b b SpainDelta b b Israel
K9CE020304 Schneider Electric
Intr
oduc
tion Infrastructure
Name Lighting and low current Medium current High current
Country
KDP KBA KBB KN KS KT
Airports
PD
2022
50 Paris Airport b b b b b France
Cairo Airport b Egypt
Heathrow Airport b b b United Kingdom
Hong-Kong Airport b China
Landvetter Airport b Sweden
Arlanda b b b Sweden
Satelite Barajas b Spain
Marine
PD
2022
51 Chantier de lAtlantique b b France
Meyerwerft b b Germany
Undergrounds
PD
2022
52 Guanghzou Underground b China
London Underground b United Kingdom
Madrid Underground b b Spain
Singapore Underground b Singapore
Other infrastructuresAlexandria Library b b Egypt
Centre international dexposition de Suzhou
b b China
CERN b b Switzerland
Stade de France b b France
Play all the worlds musicwith Canalis!
K9CE02030 5Schneider Electric
Intr
oduc
tion
Play all the worlds musicwith Canalis!
K9CE020402 Schneider Electric
Intr
oduc
tion
With the Canalis tools and services, let us compose your project!
Technical fi les The technical fi les have been compiled from completed contracts and provide answers to questions concerning the installation of Canalis busbar trunking in specifi c business sectors.
In data centersReference:ART 3722DESBS001FR
In exhibition centresReference:ART 65946KD0C00CTAFEEN / 65946
In shopping centresReference:Available in your sales offi ce.
In electronics factoriesReference:ART 65944KD0C00CTAFEEN / 65944
In tiles factoriesReference:DEBU005EN
In car plantsReference:Available in your sales offi ce.
In livestock buildingsReference:DESWED105010EN
In greenhousesReference:ART 808260DESWED105013EN
In logistic centresReference:ART 807993DESWED105011EN
In cruise shipsReference:DESWED105014EN
In garagesReference:DESWED103004EN
Find a large range of Cahier Technique publications on the Schneider Electric web site: www.schneider-electric.com.
K9CE02040
PD
2023
96D
D21
0861
3Schneider Electric
Intr
oduc
tion
With the Canalis tools and services, let us compose your project!
Work-out yoursolution together
Our teams are available to provide customers with technical assistance throughout the installation of their projects.
Design of electrical distribution architectures:design of decentralised transport and distribution systems,technical and fi nancial optimisation of busbar trunking design projects,transformer / switchboard link,installation coordination and discrimination.
Full installation drawings:3D Autocad drawings with corresponding parts lists,2D drawing with dimensions,detailed connection drawings.
Site supervision and commissioning assistance.
Training for designers and contractors.
bvvvv
bvvv
b
b
Project launch
Technical support
CanBrass drawing
Autocad drawing
Production
Project management
On-site instruction and installation
After-sales service
K9CE020404 Schneider Electric
Intr
oduc
tion
Enter Canalis run characteristics.
With the Canalis tools and services, let us compose your project!
Switchboard access estimation of material and labour costs.
Schneider Electric offers a comprehensive design and costing software.The CanBrass software, edited by Schneider Electric, was developed to help you design and cost Canalis busbar trunking runs.
CanBrass, a comprehensive toolThe CanBrass software allows you to quickly design the best layout for your project.It allows:
the material needed to be easily chosen,a list of catalogue numbers and their exact quantities to be defi ned,a comprehensive quote that includes material and labour.
There are 2 options:linear metre costing,graphical costing.
bbb
bbb
CanBrass gives you all the help you need
Design guide
Linear metre costingThe user enters the following parameters:
for the power run: rating, polarity, protection degree,for each feeder: number of machines, rating and protection,overall run length, number of change-of-direction sections and the connection
type.
bbb
PD
2023
74
PD
2023
75P
D20
2376
K9CE02040 5Schneider Electric
Intr
oduc
tion
With the Canalis tools and services, let us compose your project!
Defi nition of catalogue numbersThe software gives an optimum breakdown of the project and provides a bill of materials: catalogue number, quantity, price.The software can also generate 2D or 3D drawings with dimensions.
Breakdown of the run by product function.
QuoteThe CanBrass software can generate a comprehensive customised quote (quantity, catalogue number, unit price, total net price and installation time).
Graphical costingSimply create a 3D drawing of the busbar trunking using appropriate dialogue boxes.Enter the following:
rating,polarity,connection types.
bbb
PD
2023
77P
D20
2378
PD
2023
79
K9CE110002 Schneider Electric
Pres
enta
tion
Presentation
Range Canalis KDP Canalis KBA
PD
2022
16
PD
2022
17
Run componentsDegree of protection IP55 IP55Number of circuits 1 1Rating 20 A 25 and 40 ATap-off intervals 1200 - 1350 - 1500 - 2400 - 2700 and 3000 mm 500 - 1000 and 1500 mmStandard lengths 24 and 192 meters 2 and 3 metersFinish - Galvanised steelMaximum distance between xing points 0,33 meter 3 meters
KDP-KBA-KBB tap-off units
PD
2022
25
PD
2022
25
Rating 10 and 16 A 10 and 16 A
Option- White RAL 9010- Bus conductor- -
Panorama of Canalis rangeLighting distribution
Canalis KTC
K9CE11000 3Schneider Electric
Pres
enta
tion
Canalis KBB Canalis KBX
PD
2022
19
PD
2022
20
IP55 IP201 or 2 125 and 40 A 25 A500 and 1000 mm -2 and 3 meters 1,53 and 3,06 metersGalvanised steel White5 meters 3 meters
PD
2022
25
10 and 16 A
White RAL 9010 -Bus conductor -Clean earth -
Presentation
Canalis KTC
Panorama of Canalis rangeLighting distribution
K9CE110004 Schneider Electric
Pres
enta
tion
Range Canalis KN Canalis KS
PD
2022
21
PD
2022
22
Run componentsDegree of protection IP55 IP55Polarity 3L + N + PE 3L + N + PERating 40, 63, 100 and 160 A 100, 160, 250, 400, 500, 630, Tap-off intervals 500 - 1000 or 3000 mm 1000 mm on each faceStandard lengths 3 meters 3 and 5 metersFinish White RAL 9001 White RAL 9001Maximum distance between xing points 3 meters 3 meters
Tap-off units
PD
2022
27
PD
2022
28
Rating Plug-in 16 to 63 A 25 to 400 ABolt-on
OptionRemote control conductor -
Presentation
Canalis KTC
Panorama of Canalis rangePower distribution
K9CE11000 5Schneider Electric
Pres
enta
tion
Canalis KS colonne montante Canalis KT
PD
2022
23
PD
2022
24
IP55 IP553L + N + PE 3L + PE ; 3L + N +PE ; 3L + N + oversized PE
800 and 1000 A 100, 160, 250, 400, 500, 630, 800 and 1000 A 1000, 1350, 1600, 2000, 2500, 3200, 4000 and 5000 A500 mm 500 - 1000 mmDe ned by the oor pitch 2 and 4 metersWhite RAL 9001 White RAL 9001Li au pas dtage 3 meters
PD
2022
28
PD
2022
29
25 to 400 A 25 to 400 A400 to 1000 A
- -
Presentation
Canalis KTC
Panorama of Canalis rangePower distribution
24 Schneider Electric
Pres
enta
tion
Canalis KTC from 1000 to 5000 AFor horizontal transport and distribution
Presentation
Run sections Tap-off units Change-of-direction sections
Rating: 1000 to 5000 A.Transport sections:fi xed lengths: 2 and 4 metres,non-standard lengths: 0.5 and 3 metres,Distribution sections:fi xed lengths: 2 and 4 metres,Adjustable lengths 1.10 to 1.50 metres.
bbvvbvb
Canalis KS plug-on tap-off units are compatible with the Canalis KT busbar trunking:
protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS
circuit breakers.Canalis KT fi xed tap-off units:protection by 400 to 1000 A Compact NS
circuit breakers
b
vv
bv
Change-of-direction sections adapt to all busbar trunking requirements.
There are both fi xed and made-to-measure lengths.
b
b
Canalis KTC
PD
2023
45P
D20
2328
PD
2023
46
PD
2023
47
PD
2023
14
25Schneider Electric
Pres
enta
tion
Presentation Canalis KTC from 1000 to 5000 AFor horizontal transport and distribution
Interface connections Universal supply connections Horizontal fi xing supports
Pre-fabricated interfaces connections can be incorporated into:
Prisma Plus and Okken switchboards,France Transfo dry-type transformers.
b
vv
Supply connections allow the busbar trunking to be connected to the switchboards busbar or to the transformer.
b There are two types of support for installing the busbar trunking horizontally.
One type of fi xing: to fi x the busbar trunking to its support.
b
b
Canalis KTC
PD
2023
44
PD
2024
31
PD
2023
48
PD
2023
18
PD
2023
58
26 Schneider Electric
Pres
enta
tion
Run sectionsRating: 800 to 4000 A.Distribution sections, fi xed 2 metre lengths.Transport sections for going through fl oor slabs,
fi xed 0.5 to 3 metre lengths.
bbb
Vertical fi xing supportFor installing the busbar trunking vertically, they
ensure:height and depth adjustment,load sharing,absorption of expansions, vibrations, etc.They can be fi xed either to the fl oor, the wall or to
a bracket.
b
vvvb
Tap-off unitsCanalis KS tap-off units are compatible with the
Canalis KT busbar trunking:protection by 25 to 400 A fuses,protection by 100 to 400 A Compact NS circuit
breakers.Canalis KT fi xed tap-off units:protection by 400 to 1000 A Compact NS circuit
breakers.
b
vv
bv
Presentation Canalis KTA from 800 to 4000 AFor distribution to different levelsRising mains
Canalis KTA
PD
2023
49
PD
2023
319
PD
2023
21P
D20
2322
27Schneider Electric
Pres
enta
tion
Rating (A) Type of protectionModular switchgear Compact NS Fuses Compact NS with
measurement and meteringPlug-on tap-off units25 to 125
PD20
2149
PD20
2150
PD20
2138
25 / 50 A for NF / DIN fuses32 A for BS fuses63 A, 8 x 18 mm modules
PD20
2148
PD20
2147
For Compact NS100 circuit breaker
100 A, 12 x 18 mm modules63 A for DIN fuses100 A for NF / DIN fuses80 A for BS fuses
160
PD20
2150
PD20
2150
PD20
2323
For NG125 / 160 circuit breaker For Compact NS160 circuit breaker 160 A for NF / DIN / BS fuses250 to 400
PD20
2324
PD20
2184 Fitted with DIN rail for Powerlogic
PM810
PD20
2324
For Compact NS250 circuit breaker
PD20
2325
For Compact NS250 circuit breaker
PD20
2325
250 / 400 A for NF / DIN fuses
For Compact NS400 circuit breaker
For Compact NS400 circuit breakerFixed tap-off units400 and 630
PD20
2326
For Compact NS400 and NS630 circuit breaker
800 and 1000
PD20
2327
Tap-off units from 25 to 1000 APresentation
Canalis KTC
K9CE12000
DD
2023
87D
D20
2388
DD
2023
89
DD
2024
34-m
DD
2024
35-m
DD
2024
36-m
DD
2024
45
2 Schneider Electric
Des
crip
tion
8 ratings are available, from 1000 to 5000 A.4 copper live conductors with identical cross-sections (3L + N + PE version).Conductors insulated using polyester fi lm, class B 130 C, halogen free.Standard busbar trunking is IP55.Insulation voltage: 1000 Volts.Available polarities: 3L + PE, 3L + N +PE, 3L + N + PER (reinforced PE)
The KT busbar trunking is of compact design and can be installed edgewise, fl at or vertically.This design, without the addition of a fi re barrier joint, allows the busbar trunking to be installed through a fl oor slab or fi re barrier wall.As standard, the Canalis KT busbar trunking acts as a 2-hour fi re barrier in accordance with ISO 834.The RAL 9001 pre-lacquered galvanized steel casing provides protection and mechanical fi xing of the conductors. Further, it is used as the PE protective conductor (in accordance with NFC 15100 and IEC 60367).In its reinforced version 3L + N + PER, the busbar trunking is fi tted with an additional internal conductor with a cross-section equal to half that of the phase conductor.This version also has lateral reinforcements to allow high short-circuit currents (Isc) to be supported.
The Canalis KT busbar trunking is suitable for applications containing harmonics by taking into account the appropriate derating factor. See Harmonic currents in the Design guide.
bbbbbb
The conductors are sandwiched together inside the metal casing.
The junction between sections is made using a joint block.The joint block provides the following:
electrical junction between live conductors and between PE protective conductors, mechanical link between the two sections.
Contact zone coating:silver-plated copper
It provides simultaneous continuity between all conductors.It is tightened using torque bolt(s) (1 to 4 depending on the rating) with snap-off heads.The nut head snaps-off, freeing a red washer, when the correct tightening torque is reached.
This operation is checked visually:if the red washer is absent: it has been tightened,if the red washer is visible: it has not been tightened.
This device guarantees the necessary contact pressure between live conductors and is operator independent.
For dismantling or maintenance operations, the nut has a second head.The tightening torque is 6 daN.m.
All sections (apart from ER and EL feed units) are supplied with their joint block, delivered in a separate parcel.If the run has a feed unit (ER or EL) at each end, an additional joint block must be ordered.
bb
b
bb
The KS plug-on tap-off units are connected to the busbar trunking whilst live (off-load) via spring jaw connections.Contact zone coating:
silver-plated copper at jaw contact points.b
3L + N + PER
Description
The Canalis KT busbar trunking is intended for high power distribution and transport in industrial, commercial and tertiary buildings. Assembly of prefabricated sections that adapt to all run confi gurations.
General
3L + PE
3L + N + PE
Run sections
Tap-off contact
Joint block
Canalis KTC
K9CE12000
DD
2023
90D
D20
2438
DD
2024
37D
D20
2483
3Schneider Electric
Des
crip
tion
Run sections
Transport sections - Type ETTransport the current without tap-off points.Available in 2 and 4 metre fi xed lengths or made to measure from 0.50 to 3 metres.
Adjustable section -Type AJCompensates for dimensional differences in the installation.Adjustable length from 1.10 to 1.50 metres.
Sections with tap-off points for plug-on tap-off unitsType EDED run sections are for current distribution. They use 25 to 400 A KS tap-off units.These tap-off units can be plugged-on whilst live, but off-load.Available in fi xed 2 or 4 metre lengths with 3 tap-off points on one side.
Sections with tap-off points for fi xed tap-off units - Type EBEB run sections are for current distribution. They use specifi c KT 400 to 1000 A tap-off units.These tap-off units can only be fi tted / removed when the run is not energised.Available in a 2 metre fi xed length with one tap-off point or a 4 metre fi xed length with 2 tap-off points.
Description
Canalis KTC
Straight sections
K9CE12000
DD
2023
91D
D20
2392
DD
2024
39D
D20
2441
DD
2024
40D
D20
2446
DD
2108
11A
DD
2108
13
4 Schneider Electric
Des
crip
tion
The TP type transposes the phases.b
Expansion section - Type DBIt controls and absorbs the expansion of Canalis runs and must be used on runs over 30 metres and each time the busbar trunking passes through a building expansion joint.Refer to the installation guide.
Available in a 1 metre length, it can be fi tted vertically or horizontally.At its centre it has fl exible conductor joints and a sliding case able to absorb the relative movements of each part of the section.
Transposition sections - Types TN, TPUsed when the phase order of the switchboard is different to that of the transformer.Available in a 1 metre length and is the same physical size as a transport section.
The TN version transposes the neutral.b
Additional joint block - Type YAIf the run has a feed unit (supplied without a joint block) at each end, an additional joint block must be ordered.Each joint block is supplied with the necessary covers, nuts and boltsRun end cover - Type FAThe end cover protects and insulates the conductor ends and is fi tted to the last section.
Other run sectionsDisconnectors and run protective devices
Fitted between 2 fl at or edgewise sections, they isolate or protect a busbar trunking part run.Each assembly is supplied fi tted with a 3 or 4-pole device complete with rotary handle.Supplied with:
an auxiliary connection terminal,lifting rings,upstream and downstream terminal shields.
Colour: white RAL 9001, 100 % polyester paint on galvanized sheet steel.Refer to manufacturers data for switchgear characteristics.Fitted with a rotary handle, the tap-off unit can only be opened once the device has been switched off.
Run disconnector tap-off units - Type SLType SL for:
Compact NS 1000 to 1600 A type NA fi xed isolators:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Interpact INV isolator, 2000 to 2500 A:unhingeable door,3-point closing (possibility of locking with key lock, not supplied),Masterpact NW 3200 A type HF fi xed isolator supplied with:transparent protection cover,adaptation kit for Ronis lock + 1 Ronis lock,complete Harting plug, not cabled.
Run protection tap-off units - Type PLType PL for:
Compact NS 1000 to 1600 A type N fi xed circuit-breakers:unhingeable door,3-point closing (possibility of locking with key lock, not supplied).
For circuit-breakers greater than 1600 A, consult the sales offi ce.
bbb
bvvbvvbvvv
bvv
Description
Canalis KTC
Other run sections
Disconnectors and run protective devices
K9CE12000
DD
2023
93D
D20
2394
DD
2023
95D
D20
2396
DD
2023
97D
D20
2398
DD
2024
33D
D20
2432
5Schneider Electric
Des
crip
tion
Elbows - Types LP and LCTo go up or down, to turn right or left:
type LP, fl at elbow available in fi xed or made-to-measure lengths,b
Zeds - Types ZP, ZC, CP3-branch made-to-measure:fl at or edgewise, to move the run axis upwards, downwards, to the right or to the
left without having to bend the busbar trunking:type ZP, fl at Zed,
b
v
Edgewise T junctions - Type TCTo feed runs perpendicular to the main run.
Change of direction sectionsDescription
type LPpC, fl at made-to-measure angled elbow,b
type LC, edgewise elbow available in fi xed or made-to-measure lengths,b
type LCpC, edgewise made-to-measure angled elbow.b
type ZC, edgewise Zed,v
edgewise / fl at, to provide the busbar trunking with a bend.Type CP, edgewise and/or fl at Zed.
bv
Canalis KTC
Simple changes of direction
Changes of direction
K9CE12000
DD
2023
06D
D20
2310
DD
2023
14
6 Schneider Electric
Des
crip
tion
To connect the KTC busbar trunking to different terminals or to transformer, switchboard, generator set, etc. busbars. Canalis offers high performance connection sections which meet all requirements.
These sections provide installation fl exibility combined with quick and simple assembly.
Further, the connections are made using torque bolts which provide both ease of installation (use of a standard spanner for tightening to 6 daN.m) and a visual check before energising.
Direct connection to Trihal transformers and Prisma Plus & Okken switchboards.Supplied factory or panelbuilder assembled and tested to IEC 60439-1 and 2.Quick and simple connection of the busbar trunking to the interface.Reduced size.Joint block integrated into the interface.A sealing kit (rating dependent) must be ordered.
Connection sectionsDescription
Sealing kit
Prisma Plus and Okken switchboardsFor fi xed or draw-out incoming device, front or rear connection:
Masterpact NW08 to NW40 or NT06 to NT16 circuit-breaker,Compact NS630b to NS1600 circuit-breaker.
Possibility of switching the phases around.
bb
Prisma Plus switchboard
Okken switchboard
Canalis KTC
Connections via interface to Prisma Plus, Okken and Trihal
K9CE12000
DD
2025
03
7Schneider Electric
Des
crip
tion
Connection sectionsDescription
France Transfo Trihal dry type transformersFor naturally ventilated or force ventilated transformers.Protection degree:
IP00,IP31.
Secondary voltage: 410 V
15 mm adjustment in the 3 axes.
bb
Canalis KTC
K9CE12000
DD
2023
99
DD
2107
77D
D20
2502
8 Schneider Electric
Des
crip
tion
Feed units - Type ERThey allow the busbar trunking to be connected to a switchboards busbar, or to the terminals of an oil immersed transformer, generator set, etc.
They come complete with a mounting plate fi tted:either directly to the roof of the switchboard,or via the intermediary of a protective cover.
Vertical or horizontal incoming busbar trunking.
bb
Connection:either directly to the busbar,or by fl exible bars and connection plates,or by braids,or by cables.
ER feed units are supplied without a joint block.If the run has a feed unit at each end, an additional joint block must be ordered.
bbbb
bb
Types ER N1/N2
Connection sectionsDescription
Canalis KTC
Universal connections to switchboards and oil immersed transformers
Types ER N3/N4 Types ER N5/N6 Type ER N7
K9CE12000
DD
2023
21D
D20
2325
1027
6 -0
3-d1
1027
6-3
03-d
4D
D20
5623
DD
2056
24
9Schneider Electric
Des
crip
tion
Protective covers - Types CS, CR, BCProtects the external part of the connection.
Type CSHeight adaptable fl exible protective cover adaptable for ER N1 to N6 feed units with a between centres distance of 115 mm.
b
Connection sectionsDescription
For a vertical incomer - Types CR1 to CR3Made-to-measure rigid protective cover for ER N1 to N7 feed units.They are height adjustable by 50 mm.
Type CR 1 for a horizontal incomer.b
Types CR7 and CR8Protective covers for oil immersed transformers.Only for ER N1 to N6 feed units with a between centres distance of 150 or 170 mm depending on the rating.
Fit directly onto the BT series transformer tanks.
Type CR7 for a vertical incomer.
b
v
Type BCProtective cover for direct cable connection to ER N1 to N6 feed units with a between centres distance of 115 mm.
v
Type CR8 for a horizontal incomer.v
Canalis KTC
Types CR2 and CR3 for a vertical incomer.b
K9CE12000
DD
2024
44
DD
2024
43D
D20
2442
DD
2024
48D
D20
2447
10 Schneider Electric
Des
crip
tion
Feed units - Type ELFor dry type transformers with the neutral between the phases.They allow optimum connection to the busbar trunking.
The junction with the busbar trunking is achieved:either from the side,b
Connection sectionsDescription
They are of similar design to straight transport sections and can be installed edgewise or fl at.If installed fl at, a set of angle brackets can be ordered.
The following must be specifi ed at the time of order:phase order,distance between phases (a 20 mm lateral adjustment can be made use of on site).
The link between the transformer terminals and the connection section is either by fl exible bar connection plates or by braids.
Type EL N1/N2
or from the centre.b
Type EL N3/N4 Type EL N5
Canalis KTC
Universal connections to dry type transformers
K9CE12000
DD
2023
43D
D20
2346
DD
2023
42
11Schneider Electric
Des
crip
tion
Protective covers - Type CR4 to CR6These protect the connections with an IP31 casing when connecting to a transformer.They are height adjustable by 50 mm.
Type CR4Protective cover for EL N1 to N4 feed units.Edgewise assembly.
b
Connection sectionsDescription
Type CR5Protective cover for EL N1 to N4 feed units.Flat assembly.
b
Type CR6Protective cover for EL N5 feed unit.Edgewise assembly.
b
Canalis KTC
K9CE12000
DD
2024
00
DD
2024
11
DD
2024
10
DD
2024
03D
D20
2402
DD202401
DD
2023
63D
D20
2478
DD
2107
84
12 Schneider Electric
Des
crip
tion
The conductors of ER N1 to N6 feed units are connected directly to the switchboard busbars.YB2 copper spacers are available to compensate differences in thickness between the switchboard bars (10 mm) and the connection part (6 mm).
Make-up of kit:8 x 2 mm thick copper spacers,16 off M12 x 60 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.
Order a set per feed unit whatever the rating.
bbbbb
The conductors of ER N1 to N6 feed units are connected via connection plates to the switchboard busbars.
The YC types are fl exible bars made up of 5 copper sheets of 1 x 100 mm (500 mm cross-section).The number of connection plates needed is proportional to the busbar trunking rating.There are 3 types:
YC1, uninsulated 600 mm long bar with 4 oblong holes at one end.The length of the holes at the switchboard side are to be adapted on-site.b
Connection accessoriesDescription
YC2, uninsulated bar, made-to-measure length of 250 to 600 mm with 4 oblong holes at each end, ready to use.b
YC5, insulated 1000 mm long fl exible bar, stripped at one end and with 4 oblong holes.The length of the holes at the switchboard side are to be adapted on-site.
b
Nuts and boltsThe connection plates are fi xed to the feed unit using the YB3 nut and bolt kit, made up of:
16 off M12 x 60 mm bolts, class 8.8,16 contact washers16 torque nuts,8 steel spacer plates.
ClampsYS1 clamps enable high short-circuit current levels to be withstood; only for bars with a 115 mm spacing.
bbbb
Canalis KTC
Switchboard connection accessories using connection plates
Accessories for direct connection to the switchboard
InsulationA YF sheath is available to insulate the phases from one another.It can be fi tted to the YC1 and YC2 connection plates once they have been connected.
K9CE12000
DD
2024
12D
D20
2414
DD
2024
13D
D20
2415
DD
2024
50
13Schneider Electric
Des
crip
tion
The feed unit conductors are connected to the transformer bars via connection plates or braids:
connection plates, YC types, are fl exible bars made up of 5 copper sheets of 1 x 100 mm (500 mm cross-section).
braids, YT type, are copper braids with a 600 mm cross-section.
The number of connection plates needed is proportional to the busbar trunking rating.
Connection platesThe YC3 is an uninsulated bar with an expansion kink; it is 400 mm long and has 4 holes at one end.They can be fi tted to the transformer side:
either using bar clamps (no drilling),or drilled and bolted (to be carried out on site).
b
b
bb
Connection accessoriesDescription
YS2 and YS3 bar clamps enable connection without the need to drill the connection plates.They allow height adjustment.
Type YS2, bar clamps for 100 mm transformer connection terminals.Type YS3, bar clamps for 120 mm transformer connection terminals.
Make-up of kit: 1 set of 8 parts.
bb
The YC4 is an uninsulated bar with an expansion kink; it is 400 mm long and has 4 oblong holes at each end (ready to use).b
BraidsType YT, 400 mm long insulated braid with 4 holes at each end.
The connection plates and braids are fi xed to the feed unit using the YB4 nut and bolt kit, made up of:
16 off M12 x 80 mm bolts, class 8.8,16 contact washers,16 torque nuts,8 steel spacer plates.
bbbb
Canalis KTC
Transformer connections - Types YC, YT
K9CE12000
DD202372
DD
2024
84D
D20
2486
DD
2024
85
DD
2023
69D
D20
2368
DD
2024
96
DD
2023
74
14 Schneider Electric
Des
crip
tion
Supports and fixings
The ZA types allow the busbar trunking to be fi xed and adjusted along its length, as well as absorbing its movements.
Supports for horizontal sectionsType ZA1, to support edgewise busbar trunking only, consists of a steel angle
bracket and 2 x 1.2 metre threaded M10 rods. The maximum distance between supports is:
3 metres for edgewise busbar trunking,2 metres for fl at busbar trunking.
See installation precautions.
b
vv
Fixing bracketThe ZA3 keeps the busbar trunking in place on its support, without blocking it, in order to allow expansion movements.
The ZA5 is for supporting vertical sections.They fi x sections of a vertical run to the buildings structure.This type of fi xing support has the following advantages:
assembly:to a wall,to a wall bracket,to the fl oor,height and depth adjustment,spring adjustment to ensure distribution of the load at each fl oor,avoids the transmission of building forces to the busbar trunking (expansion and
vibration).
bvvvbbb
Description
Type ZA4, to support the busbar trunking from the top.These supports are needed to fi x edgewise EL N1 to N4 feed units for dry type
transformers.
bb
For KTC1000 to KTC2000. For KTC2500 to KTC5000.
To a wall. To a wall bracket. To the fl oor.
Canalis KTC
Horizontal supports
Vertical supports
K9CE12000 15Schneider Electric
Des
crip
tion
Description
Canalis KTC
K9CE13000
DD
2104
66D
D20
2012
DD
2102
75D
D21
0276
2 Schneider Electric
Tap-off units
The tap-off units are used to instantly connect loads or secondary runs, and comply with installation standards and regulations, whatever the earthing system (TT, TNS, TNC or IT).When off-load, they can be plugged-on and off and be operated whilst live.Plugging-on and plugging-off automatically opens and closes the tap-off point.
Description
No live part is accessible with the door open. The protection degree is IPXXB (fi nger protection).They are IP55 by construction (no accessory is required).
Safety and operationFuse and modular switchgear tap-off units (AC22 to AC20) are isolated as soon as the tap-off unit door is opened.This isolating operation must only be carried out off-load.For circuit breaker tap-off units, there are safety mechanisms to prevent:
the tap-off unit being plugged-on and plugged-off with the tap-off unit door closed,
the door being closed if the tap-off unit has not been locked onto the busbar trunking,
access to the electrical equipment and connection terminals when live,the door being opened in the ON position for tap-off units fi tted with a Compact
NS or NG circuit breaker.
These tap-off units can be fi tted with accessories such as:door early break contacts,adapter for lead sealing,etc.
The sheet steel tap-off units are fi tted with a carrying handle.
Characteristics of tap-off units up to 125 AColour: white (RAL 9001) body and carrying handles,transparent green door (similar design to the Kaedra enclosures).Material: self-extinguishing, halogen-free insulating plastic (fi re resistant and very
high temperature withstand).Other characteristics: cable gland drilling zone, stainless steel screws and the door can be lead sealed.
Characteristics of tap-off units from 160 to 400 AColour:white (RAL 9001) body,black carrying handles (RAL 9005),100 % polyester paint.Material: galvanized sheet steel.
Other characteristics:unhingeable door (120 opening hinges),vertically bevelled polyurethane seals with a double fold for increased rigidity
(similar design to the Sarel Spatial 3D enclosures),25 mm grill type gland plates for a maximum access area.
b
b
bb
bbb
bvvb
bvvvb
bb
b
Canalis KTA
K9CE13000
DD
2104
65D
D21
0461
DD
2021
54D
D21
0454
3Schneider Electric
Plug-on tap-off units for circuit breakers
Isolator tap-off units for modular switchgearMost 18 mm Multi 9 modular devices can be fi tted into these tap-off units.They have a window on the front face for switchgear control and visualisation.
A transparent shutter ensures the window can be sealed.Two tap-off ratings are available:
63 A nominal current for 8 modules,125 A nominal current for 12 modules (accepts C120 and NG125 circuit
breakers).bb
Tap-off units for NG type modular switchgearThese tap-off units are fi tted with a DIN rail and upstream connections for 18 mm wide modular devices.The switchgear is operated via a rotary handle which prevents door opening when the circuit breaker is in the ON position.Nominal current: 160 A for a 13-module capacity (accepts NG125 or NG160 fi tted
with a Vigi unit).Isolator tap-off units for Compact NS circuit breakersThese tap-off units are fi tted with mounting plates and upstream connections for fi xed, front-connected 160 to 400 A Compact NS circuit breakers (N, H or L version) with a rotary handle.The 400 A tap-off units can only be fi tted onto straight lengths with a rating greater than 400 A.
For plug-on circuit breakers, Vigi units, etc, please consult your Schneider Electric
contact.Measurement and metering isolator tap-off unitsThese tap-off units allow sub-metering to re-allocate power consumption costs by consumer and to monitor installations by, for example, following run load levels.The values measured using the Compact NS TI unit are sent to the measurement unit which then sends the information to a central unit via a bus. (See Measurement and metering).They are fi tted with:
a mounting plate for a Compact NS 250 or 400 A circuit breaker with an extended rotary handle and a Compact NS current transformer module (TI unit),
a DIN rail for installing a Powerlogic PM810 measurement unit, a set of terminals, etc.
In severe operating conditions (> 40C ambient temperature), we recommend the use of a PM810 without display.
b
b
Description
Canalis KTA
K9CE13000
DD
2104
72D
D20
2012
DD
2104
66
4 Schneider Electric
These tap-off units provide the tap-offs with fuse protection (fuses not supplied).They can only be fi tted to a horizontally mounted busbar trunking.
Plastic tap-off unitsFitted with carriers for:
50 to 100 A cylindrical NF fuses,25 to 63 A DIN screwed fuses,100 A DIN blade fuses,32 to 80 A BS screwed fuses.
bbbb
Plug-on tap-off units for fusesDescription
Steel tap-off unitsFitted with carriers for:
160 to 400 A NF / DIN blade fuses,160 A BS screwed fuses.
bb
Canalis KTA
K9CE13000
DD
2024
51D
D20
2497
5Schneider Electric
Fixed tap-off units for circuit breakers
Steel tap-off unitsThese tap-off units are used to supply loads or secondary runs (e.g. medium power distribution using Canalis KS). They are fi tted to specifi c EB type straight lengths.They comply with installation standards and regulations, whatever the earthing system (TT, IT, TNS or TNC):
tap-off units fi tted with a mounting plate for Compact NS400/1000 A, 3 or 4 P:fi xed device,front connections,extended rotary handle.
2 models:Compact NS400/630 A, connection capacity: 3 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm),150 mm for the PE,Compact NS800/1000 A, connection capacity:4 x 300 mm2 cables for the phases and neutral (hole diameter = 15 mm),200 mm2 for the PE (cable clamp).
The standard tap-off unit is IP54.
bvvv
bvvbvv
Characteristics of tap-off units from 400 to 1000 AColour:white (RAL 9001) body,Material: galvanized sheet steel.Other characteristics: the cables exit laterally through 2 aluminium plates (to be drilled by the
installation contractor),cabling space can be increased by using the cable box supplied with the tap-off
unit,the door is fi xed using 6 captive M6 screws and can be completely removed to
facilitate cabling.
bvbbv
v
v
Description
Safety and operationThe electrical connection is made by plugging-on the tap-off unit into dedicated tap-off point whilst the busbar trunking is de-energised (plugging-off the unit must also be done with the busbar trunking de-energised).The connection is mechanically tightened using a one-use torque bolt (10 daN.m).A mechanical foolproof system avoids the risk of incorrect assembly.The door can only be opened once the load has been isolated (rotary handle).The bolt can only be tightened or untightened with the door open.No live part is accessible with the door open, protection degree IP2X.
Canalis KTA
K9CE20000 Schneider Electric 3
Cat
alog
ue n
umbe
rsD
imen
sion
s
Catalogue-number coding
K T p p p p p p p p ppFour digits indicationg
the rating of the trunking.b
Two letters identifying the type of component.Type CodeAdjustable straight length AJCable box BCBolt-on tap-off unit CBEdgewise and fl at zed CPRigid protective cover CRFlexible protective cover CSExpansion unit DBDistribution length for bolt-on tap-off units EBDistribution length for plug-in tap-off unts EDFeed unit for dry-type transformers ELFeed unit ERFeeder length ETEnd cover FAEdgewise elbow LCFlat elbow LPTap-off unit with protective device PLTap-off unit with isolator SLEdgewise tee TCNeutral crossover TNPhase crossover TPSealing kit TTConnection device YAConnection torque nut kit YBFlexible bar YCBracket YEInsulating sheath YFBar supports YSBraids YTSupports and fi xing devices ZAEdgewise zed ZCFlat zed ZP
b
One digit indicating the trunking polarityPolarity Code3L + PE 33L + N + PE 43L + N + PER(1) 7(1) PER = oversized PE.
b
Variable number of alphanumeric characters indicating characteristics specifi c to the component.See the section dealing with the given component.
b
Trunking cross sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Number of bar jointing bolts 1 1 1 2 2 2 4 4Bar cross-section (mm) 70 x 6 100 x 6 120 x 6 160 x 6 200 x 6 2 x (120 x 6) 2 x (160 x 6) 2 x (200 x 6)Trunking height H (mm)
DD
2021
80
DD
2021
81
Holes for connections (mm)
DD
2021
82
Y 230 230 230 350 350 350 510 510
Catalogue-number composition
One letter designating the material.Type CodeCopper CNon conducting B
b
Catalogue numbers anddimensions
Canalis KTC
K9CE21010
DD
2107
94
DD
2107
95
DD
2107
96
DD
2107
97
2 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
sCatalogue numbers and dimensions
Straight feeder lengths
Run componentsIP55
Type Length L(mm)
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed 4000 KTCppppET340 KTCppppET440 KTCppppET7402000 KTCppppET320 KTCppppET420 KTCppppET720
Made to measure
500 to 1500 KTCppppET31A KTCppppET41A KTCppppET71A1501 to 1999 KTCppppET32B KTCppppET42B KTCppppET72B2001 to 2500 KTCppppET32C KTCppppET42C KTCppppET72C2501 to 3000 KTCppppET33D KTCppppET43D KTCppppET73D
KTCppppETppp
Ordering
Complete the catalogue number by replacing pppp by the rating.Important:
add the dimensions of the selected component as a technical comment
Example: the catalogue number of an 1000 A feeder length, 3L + N + PE,2450 mm long, is:KTC1000ET42C, L = 2450
b
Rating
(1) See the Trunking cross-section table opposite.
Canalis KTC
Adjustable straight lenghts
Type Length L(mm)
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Adjustable 1300 (basic)Adjustable: 200
KTCppppAJ310 KTCppppAJ410 KTCppppAJ710
KTCppppAJp10
(1) See the Trunking cross-section table opposite.
Table of dimensionsRating (A) Dimension A (mm) Weight (kg)1000 186 52.001350 219 68.001600 241 78.002000 307 102.002500 351 121.003200 395 141.004000 527 179.005000 615 218.00
KTCppppETppp
KTCppppAJp10
K9CE21010
DD
2107
98
DD
2107
99D
D21
0800
3Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Catalogue numbers and dimensions
Run componentsIP55
Straight lengths with plug-in tap-off units
Type Length L (mm)
Number of tap-offs
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed 4000 3 KTCppppED340 KTCppppED440 KTCppppED7402000 3 KTCppppED320 KTCppppED420 KTCppppED720
KTCppppEDp40
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67
(1) See the Trunking cross-section table below.
Canalis KTC
KTCppppEDp20
KTCppppEDp20
KTCppppEDp40
K9CE21010
DD
2108
01
DD
2108
02D
D21
0803
DD
2107
66
4 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Straight lengths with bolt-on tap-off units
Type Length L (mm)
Number of tap-offs
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed 4000 2 KTCppppEB340 KTCppppEB440 KTCppppEB7402000 1 KTCppppEB320 KTCppppEB420 KTCppppEB720
KTCppppEBp40
(1) See the Trunking cross-section table below.
KTCppppEBp20
KTCppppEBp20
KTCppppEBp40
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67Catalogue numbers and dimensions
Canalis KTC
Run componentsIP55
K9CE21010 5Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
DD
2108
05
DD
2108
06
DD
2108
07
DD
2108
08
DD
2108
09
DD
2108
10
2 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
sCatalogue numbers and dimensions
Straight expansion unit
Additional run componentsIP55
Type Length L(mm)
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed 1000 KTCppppDB310 KTCppppDB410 KTCppppDB710
KTCppppDBp10
Ordering
Complete the catalogue number by replacing pppp by the rating.Important:
add the dimensions of the selected component as a technical comment
Example: the catalogue number of a 1350 A straght expansion unit, 3L + PE, 1000 mm long, is:KTC1350DB310
b
Rating
(1) See the Trunking cross-section table opposite.
Canalis KTC
Neutral crossover length
Type Length L(mm)
Cat. no.3L + N + PE
Fixed 1000 KTCppppTN410
KTCppppTNp10
(1) See the Trunking cross-section table opposite.
Phase crossover length
Type Length L(mm)
Cat. no.3L + N + PE
Fixed 1000 KTCppppTP410
KTCppppTPp10
(1) See the Trunking cross-section table opposite.
KTCppppDBp10
KTCppppTNp10
KTCppppTPp10
DD
2108
11
DD
2108
12
DD
2108
13
DD
2108
14n
DD
2108
68
3Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Catalogue numbers and dimensions
Additional run componentsIP55
Additional jointing unitsType Cat. no.
3L + PE 3L + N + PE 3L + N + PERJointing unit KTCppppYA3 KTCppppYA4 KTCppppYA4
KTCppppYAp
(1) See the Trunking cross-section table below.
Canalis KTC
End coversType Rating of the
trunking (A)Height H of the trunking (mm)
Cat. no.
End cover 1000 74 KTB0074FA1350 104 KTB0104FA1600 124 KTB0124FA2000 164 KTB0164FA2500 204 KTB0204FA3200 244 KTB0244FA4000 324 KTB0324FA5000 404 KTB0404FA
KTB0pppFA
KTCppppYAp
KTB0pppFA
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67
(1) See the Trunking cross-section table below.
K9CE22010
DD
2108
22D
D21
0824
DD
2108
15D
D21
0816
DD
2108
21D
D21
0823
2 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
sCatalogue numbers and dimensions
Elbow components for changing directionIP55
Flat elbows
Type Position of neutral
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed N1 KTCppppLP3A1 KTCppppLP4A1 KTCppppLP7A1N2 KTCppppLP3A2 KTCppppLP4A2 KTCppppLP7A2
Made to measure
N1 KTCppppLP3B1 KTCppppLP4B1 KTCppppLP7B1N2 KTCppppLP3B2 KTCppppLP4B2 KTCppppLP7B2
KTCppppLPppp
Ordering
Complete the catalogue number by replacing pppp by the rating.Important:
add the dimensions of the selected component as a technical comment
Example: the catalogue number of a 2000 A fl at elbow, N1, 3L + N + PE with dimensions A = 300 mm and B = 650 mm is:KTC2000LP4B1, A = 300, B = 650.
b
Rating
(1) See the Trunking cross-section table opposite.
DimensionsType Rating (A) Dimensions (mm)
A BFixed All 300 300Made to measure(2)
All 300 301 to 799301 to 799 300
(2) Only one llmb may be made to measure.
Canalis KTC
Flat elbows with made to measure angles
Type Position of neutral
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Made to measure angle
N1 KTCppppLP3C1 KTCppppLP4C1 KTCppppLP7C1N2 KTCppppLP3C2 KTCppppLP4C2 KTCppppLP7C2
KTCppppLPpCp
(1) See the Trunking cross-section table opposite.
DimensionsType Rating (A) Dimensions (mm)
A B WMade to measure All 300 300 91 to 179
KTCppppLPpp1
KTCppppLPpp2
KTCppppLPpC1
KTCppppLPpC2
K9CE22010
DD
2108
25
DD
2108
26
3Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Catalogue numbers and dimensions
Elbow components for changing directionIP55
Edgewise elbows
Type Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed KTCppppLC3A KTCppppLC4A KTCppppLC7AMade to measure KTCppppLC3B KTCppppLC4B KTCppppLC7B
KTCppppLCpp
(1) See the Trunking cross-section table below.
DimensionsType Rating (A) Dimensions (mm)
A BFixed 1000 275 275
1350 290 2901600 300 3002000 320 3202500 340 3403200 360 3604000 400 4005000 440 440
Made to measure(2)
1000 276 to 774 275275 276 to 774
1350 291 to 789 290290 291 to 789
1600 301 to 799 300300 301 to 799
2000 321 to 819 320320 321 to 819
2500 341 to 839 340340 341 to 839
3200 361 to 859 360360 361 to 859
4000 401 to 899 400400 401 to 899
5000 441 to 939 440440 441 to 939
(2) Only one llmb may be made to measure.
Canalis KTC
KTCppppLCpp
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67
K9CE22010
DD
2108
19
DD
2108
20
4 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
sCatalogue numbers and dimensions
Canalis KTC
Elbow components for changing directionIP55
Edgewise tee
Type Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed KTCppppTC3 KTCppppTC4 KTCppppTC7
KTCppppTCp
KTCppppTCp
(1) See the Trunking cross-section table below.
DimensionsType Rating (A) Dimensions (mm)
A B CFixed 1000 275 275 275
1350 290 290 2901600 300 300 3002000 320 320 3202500 340 340 3403200 360 360 3604000 400 400 4005000 440 440 440
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67
K9CE22010 5Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
K9CE22020
DD
2021
83
DD
2021
84D
D20
2186
DD
2021
85D
D21
0827
2 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
sCatalogue numbers and dimensions
Zed components for changing directionIP55
Edgewise zed units
Type Position of neutral
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Made to measure
N1 KTCppppZC31 KTCppppZC41 KTCppppZC71N2 KTCppppZC32 KTCppppZC42 KTCppppZC72
KTCppppZCpp
Flat zed unitsType Cat. no.
3L + PE 3L + N + PE 3L + N + PERMade to measure KTCppppZP3 KTCppppZP4 KTCppppZP7
KTCppppZPp
Ordering
Complete the catalogue number by replacing pppp by the rating.Important:
add the dimensions of the selected component as a technical comment
Example: the catalogue number of a 1600 A edgewise zed unit, N2, 3L + N + PE with dimensions A = 300 mm, B = 450 mm, C = 300 mm is:KTC1600ZC42, A = 300, B = 450, C = 300.
b
Rating
(1) See the Trunking cross-section table opposite.
DimensionsRating (A) Dimensions (mm)
A B CAll 300 130 to 599 300
(1) See the Trunking cross-section table opposite.
DimensionsRating (A) Dimensions (mm)
A B C1000 275 90 to 549 2751350 290 90 to 579 2901600 300 90 to 599 3002000 320 90 to 639 3202500 340 90 to 679 3403200 360 90 to 719 3604000 400 90 to 799 4005000 440 90 to 879 440
KTCppppZPp
KTCppppZCp1
KTCppppZCp2
Canalis KTC
K9CE22020
DD
2021
87
DD
2021
88
DD
2108
28D
D21
0829
DD
2108
30
DD
2023
67
3Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Catalogue numbers and dimensions
Zed components for changing directionIP55
Edgewise and fl at zed units
Type Position of neutral
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Made to measure
N1 KTCppppCP31 KTCppppCP41 KTCppppCP71N2 KTCppppCP32 KTCppppCP42 KTCppppCP72N3 KTCppppCP33 KTCppppCP43 KTCppppCP73N4 KTCppppCP34 KTCppppCP44 KTCppppCP74
(1) See the Trunking cross-section table below.
Canalis KTC
KTCppppCPp1
KTCppppCPp2
KTCppppCPp3
KTCppppCPp4
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67
KTCppppCPp3and KTCppppCPp4
KTCppppCPp1and KTCppppCPp2
DimensionsRating (A) Dimensions (mm)
A B C1000 300 195 to 574 2751350 300 210 to 589 2901600 300 220 to 599 3002000 300 240 to 619 3202500 300 260 to 639 3403200 300 280 to 659 3604000 300 320 to 699 4005000 300 360 to 739 440
K9CE23000
DD
2023
04D
D20
2306
DD
2023
05D
D20
2307
2 Schneider Electric
Cat
alog
ue n
umbe
rsCatalogue numbers Canalis interfaces for Prisma Plus
LV switchboard
Interfaces for Masterpact NW circuit breakers
Circuit breaker
Type of circuit breaker
Number of poles
Connection Cat. no.Top direct Rear
NW08 / 16 Fixed or drawout 3 b b 047154 b b 04716
NW20 / 25 Fixed or drawout 3 b b 047254 b b 04726
NW32 Fixed or drawout 3 b b 047354 b b 04736
NW40 Fixed or drawout 3 b 047374 b 04738
For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.
Number of modules required in the switchboardCircuit breaker Connection Type of circuit
breakerNumber of vertical modules(1)
NW08 / 16 Top direct Fixed or drawout 27Rear Fixed 16
Drawout 17NW20 / 25 Top direct Fixed or drawout 28
Rear Fixed 16Drawout 17
NW32 Top direct or rear Fixed or drawout 28NW40 Rear Fixed or drawout 36(1) 1 module = 50 mm.
Canalis KTC
Interfaces for Masterpact NT and Compact NS circuit breakers
Masterpact NTCircuit breaker
Type of circuit breaker
Number of poles
Connection Cat. no.Top direct Rear
NT06 / 12 Fixed or drawout 3 b b 047034 b b 04704
NT16 Fixed or drawout 3 b 047034 b 04704
For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.
Compact NSCircuit breaker
Type of circuit breaker
Number of poles
Connection Cat. no.Top direct Rear
NS630b / 1250 Fixed or drawout 3 b b 047034 b b 04704
NS1600 Fixed or drawout 3 b 047034 b 04704
For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.
Number of modules required in the switchboardCircuit breaker Connection Type of circuit
breakerNumber of vertical modules(1)
NT06 / 12NS630b / 1250
Top direct Fixed 17Drawout 18
Rear Fixed or drawout 16NT16NS1600
Rear Fixed or drawout 16
(1) 1 module = 50 mm.
Top direct connection
Rear connection
Top direct connection
Rear connection
K9CE23000
DD
2023
08D
D20
2309
3Schneider Electric
Cat
alog
ue n
umbe
rs
Catalogue numbers
Canalis KTC
Canalis interfaces for Prisma Plus LV switchboard
Interface supports and protection covers
Masterpact NWCircuit breaker
Type of circuit breaker
Connection Supports Terminal extension bar supports
Cover
NW08 / 32 Fixed or drawout
Top direct 03561 3 x 04694 04871 + 04861Rear 03561 2 x 04694 04871 + 04863
NW40 Fixed or drawout
Top direct 03561 - 04871 + 04861Rear 03561 - 04871 + 04863
Masterpact NTCircuit breaker
Type of circuit breaker
Number of poles
Connection Supports Canalis /circuit breaker connection
Cover
NT06 / 12 Fixed or drawout
3P Top direct 03561 04712 04871 + 04852Rear 03561 04713 04871 + 04853
4P Top direct 03561 04712 04871 + 04852Rear 03561 04714 04871 + 04853
NT16 Fixed or drawout
3P Rear 03561 04713 04871 + 048544P Rear 03561 04714 04871 + 04854
Compact NSCircuit breaker
Type of circuit breaker
Number of poles
Connection Supports Canalis /circuit breaker connection
Cover
NS630b /1250
Fixed 3P Top direct 03561 04712 04871 + 04851Rear 03561 04713 04871 + 04853
4P Top direct 03561 04712 04871 + 04851Rear 03561 04714 04871 + 04853
Drawout 3P Top direct 03561 04711 04871 + 04852Rear 03561 04713 04871 + 04854
4P Top direct 03561 04712 04871 + 04852Rear 03561 04714 04871 + 04854
NS1600 Fixed 3P Rear 03561 04713 04871 + 048534P Rear 03561 04714 04871 + 04853
Drawout 3P Rear 03561 04713 04871 + 048544P Rear 03561 04714 04871 + 04854
03561
04711047120471304714
Arc-chute covers
Circuit breaker Type of circuit breaker Number of poles Cat. no.Masterpact NT Fixed 3P 47335
4P 47336Compact NS Fixed 3P 33596
4P 33597
K9CE23000
DD
2023
10D
D20
2312
DD
2023
11D
D20
2313
4 Schneider Electric
Cat
alog
ue n
umbe
rsCatalogue numbers Canalis interfaces for Okken
LV switchboard
Interfaces for Masterpact NW circuit breakersFitting the interface does not change switchboard modularity as fi xed by the devices.
Circuit breaker
Type of circuit breaker
Number of poles
Connection Cat. no.Top direct Rear
NW08 / 16 Drawout 3 b 87811b 87821
4 b 87812b 87822
NW20 / 25 Drawout 3 b 87813b 87823
4 b 87814b 87824
NW32 Drawout 3 b 87815b 87825
4 b 87816b 87826
NW40 Drawout 3 b 87817b 87827
4 b 87818b 87828
For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.
Canalis KTC
Interfaces forMasterpact NT circuit breakersFitting the interface does not change switchboard modularity as fi xed by the devices.
Circuit breaker
Type of circuit breaker
Number of poles
Connection Cat. no.Top direct Rear
NT08 / 16 Drawout 3 b 87811b 87821
4 b 87812b 87822
For the position in the switchboard, see the Installation guide.For connection to the PER, consult your sales agency.
Interface supports
Circuit breaker Type of circuit breaker Connection Cat. no.NW08 / 40NT08 / 16
Drawout Top direct 87800
NW08 / 32(1)NT08 / 16
Drawout Rear 87801
(1) For rear connection of the interface to a Masterpact NW40 circuit breaker, the supports are supplied with the interface.
Top direct connection (RDH)
Rear connection (RAR)
Top direct connection (RDH)
Rear connection (RAR)
K9CE23000
DD
2023
14
5Schneider Electric
Cat
alog
ue n
umbe
rs
Catalogue numbers
Canalis KTC
Sealing kitsIP55
Sealing kits for switchboard and Trihal transformer roofs with interfaceType Rating of the
trunking (A)Height H of the trunking (mm)
Cat. no.
Sealing kit 1000 74 KTB0074TT011350 104 KTB0104TT011600 124 KTB0124TT012000 164 KTB0164TT012500 204 KTB0204TT013200 244 KTB0244TT014000 324 KTB0324TT015000 404 KTB0404TT01
KTB0pppTT01
K9CE24010
DD
2108
31
DD
2108
32
2 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
sCatalogue numbers and dimensions
Feed units for switchboards and oil immersed transformersIP55
Straight feed units
Type Position of neutral
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Fixed N1 KTCppppER31 KTCppppER41 KTCppER71Made to measure N2 KTCppppER32 KTCppppER42 KTCppER72
KTCppppERp1, KTCppppERp2
To order
Complete the catalogue number by replacing pppp by the rating.Important:
add the dimensions of the selected unit as a technical comment.
Example: the catalogue number of a 1350 A made to measure end feed unit, N2, 3L + N + PE, 235 mm long and with between centres J, K and M = 170 mm, is: KTC1350ER42, A = 235, J = 170, K = 170 and M = 170.
b
Rating
(1) See the Trunking cross-section table opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
Table of dimensionsRating (A) Neutral Dimensions (mm)
A J, K, M Y1000 to 1600 N1 235 115 230
N2 235 to 534 80 to 250 2302000 to 3200 N1 235 115 350
N2 235 to 534 80 to 250 3504000 and 5000 N1 235 115 510
N2 235 to 534 80 to 250 510
KTCppppERp1KTCppppERp2
Canalis KTC
Dimensions of connection padsRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Drilling for connection (mm)
DD
2021
82
K9CE24010
DD
2108
33
DD
2108
35
DD
2108
34
DD
2108
36
3Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Flat elbow feed units
Type Position of neutral
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Made to measure N3 KTCppppER33 KTCppppER43 KTCppER73N4 KTCppppER34 KTCppppER44 KTCppER74
KTCppppERp3
(1) See the Trunking cross-section table below.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
Tableau of dimensionsRating (A) Neutral Dimensions (mm)
A B J, K, M Y1000 to 1600 N3, N4 200 to 534 300 80 to 250 2302000 to 3200 N3, N4 200 to 534 300 80 to 250 3504000 and 5000 N3, N4 200 to 534 300 80 to 250 510
KTCppppERp3
KTCppppERp4
Catalogue numbers and dimensions
Canalis KTC
Feed units for switchboards and oil immersed transformersIP55
Cut-out drawing for feed units placed directly on the device roof
Table of dimensionsRating (A) Dimensions (mm)
Y U V1000 to 1600 230 K / 2 + J + 80 K / 2 + M + 802000 to 3200 350 K / 2 + J + 80 K / 2 + M + 804000 and 5000 510 K / 2 + J + 80 K / 2 + M + 80
KTCppppERp4
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67
K9CE24010
DD
2108
39
DD
2108
37D
D21
0838
DD
2108
36
4 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Edgewise elbow feed units
Type Position of neutral
Cat. no.3L + PE 3L + N + PE 3L + N + PER
Made to measure N5 KTCppppER35 KTCppppER45 KTCppER75N6 KTCppppER36 KTCppppER46 KTCppER76
KTCppppERp5
KTCppppERp5
KTCppppERp6
(1) See the Trunking cross-section table opposite.(2) PE drilled diameter = 14 mm pour cables with crimped lugs.
Table of dimensionsRating (A) Neutral Dimensions (mm)
A B J, K, M Y1000 N5, N6 175 to 509 275 80 to 250 2301350 N5, N6 190 to 524 290 80 to 250 2301600 N5, N6 200 to 534 300 80 to 250 2302000 N5, N6 220 to 554 320 80 to 250 3502500 N5, N6 240 to 574 340 80 to 250 3503200 N5, N6 260 to 594 360 80 to 250 3504000 N5, N6 300 to 634 400 80 to 250 5105000 N5, N6 340 to 674 440 80 to 250 510
Cut-out drawing for feed units placed directly on the device
Table of dimensionsRating (A) Dimensions (mm)
Y U V1000 to 1600 230 K / 2 + J + 80 K / 2 + M + 802000 to 3200 350 K / 2 + J + 80 K / 2 + M + 804000 and 5000 510 K / 2 + J + 80 K / 2 + M + 80
Catalogue numbers and dimensions
Canalis KTC
Feed units for switchboards and oil immersed transformersIP55
KTCppppERp6
Dimensions of connection padsRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Drilling for connection (mm)
DD
2021
82
K9CE24010
DD
2023
16
DD
2023
15
DD
2023
17
5Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Catalogue numbers and dimensions
Canalis KTC
Feed units for switchboards and oil immersed transformersIP55
Bar feed units, fl at outlets
Type Cat. no.3L + PE 3L + N + PE 3L + N + PER
Made to measure KTCppppER37 KTCppppER47 KTCppppER77Connection pad dimensions are identical to those of the feed units.
KTCppppERp7
KTCppppERp7
(1) See the Trunking cross-section table below.
Table of dimensionsRating (A) Dimensions (mm)
A P - Q S - R ou R - S Q, R, S minimum Y1000 to 1600 235 to 734 160 to 600 160 to 600 80 2302000 to 3200 235 to 734 160 to 600 160 to 600 80 3504000 and 5000 235 to 734 160 to 600 160 to 600 80 510
Cut-out drawing for straight feed units connected directly to the device
Table of dimensionsRating (A) Dimensions (mm)
Y U V1000 to 1600 230
U = P + 80 if S > R, V = S + 80if R > S, V = R + 802000 to 3200 3504000 and 5000 510
Trunking cross-sectionRating (A) 1000 1350 1600 2000 2500 3200 4000 5000Weight (kg / m) 3L + PE 19 25 29 36 44 51 66 82
3L + N + PE 23 31 35 45 55 64 84 1043L + N + PER 25 33 39 49 60 71 92 114
Height H (mm)Width W (mm)
DD
2021
80
DD
2108
67
K9CE24010
DD
2023
26
DD
2023
25
6 Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Rigid horizontal protective covers for feed units ER N1 to N7Important : when ordering a horizontal cover, make sure you indicate dimensions D, G and Z with the catalogue number.
Rating (A) Dimensions Y (mm) Cat. no. Weight (kg)1000 to 1600 230 KTB0230CR1 12.002000 to 3200 350 KTB0350CR1 12.004000 and 5000 510 KTB0510CR1 12.00
KTBppppCR1
KTBppppCR1
Protective cover for ER N1 to N6 straight end feed connectorsDimensions D and G are determined by the between centres dimensions (J, K and M) of the end feed connector bars to be protected.The position of the neutral on the feed connector also determines the rule to be used for calculating parameters D and G.
If the feed connector comes into the cover with the neutral on the right:D = K / 2 + M + 100G = K / 2 + J + 100
If the feed connector comes into the cover with the neutral on the left:D = K / 2 + J + 100G = K / 2 + M + 100
Table of dimensionsRating (A) Dimensions (mm)
Y D G Z1000 to 1600 230 220 to 475 220 to 475 310 to 8002000 to 3200 350 220 to 475 220 to 475 430 to 8004000 and 5000 510 220 to 475 220 to 475 590 to 800
Protective cover for ER N7 straight end feed connectorsDimensions D and G are determined by the between centres dimensions (P, Q, R and S) of the end feed connector bars to be protected.Position of the neutral on the feed connector also determines the rule to be used for calculating parameters D and G.
If the feed connector comes into the cover with the neutral on the right:D = max(R ; S) + 100G = max(P ; Q) + 100
If the feed connector comes into the cover with the neutral on the left:D = max(P ; Q) + 100G = max(R ; S)+ 100
Table of dimensionsRating (A) Dimensions (mm)
Y D G Z1000 to 1600 230 340 to 1000 340 to 1000 310 to 8002000 to 3200 350 340 to 1000 340 to 1000 430 to 8004000 and 5000 510 340 to 1000 340 to 1000 590 to 800
Catalogue numbers and dimensions
Canalis KTC
Rigid protective coversIP55
To order
To order a protective cover onto which a feed connector is fi tted, the parameters D, G and Z, which depend on the feed connector, must be given.
Example: the catalogue number of a rigid vertical protective cover with dimension Y = 350 intended for a feed unit with different between centre dimensions D, G and Z (in mm) is:KTB0350CR2, D = 330, G = 450 and Z = 500.
K9CE24010
DD
2023
22
DD
2023
21
DD
2023
24
DD
2023
23
7Schneider Electric
Cat
alog
ue n
umbe
rsD
imen
sion
s
Rigid vertical protective covers for feed units ER N1 to N7Important: when ordering a vertical cover, make sure you indicate dimensions D, G and Z with the catalogue number.
400 to 800 mm high coversRating (A) Dimensions Y (mm) Cat