WMS No. 15171 1 Addendum No. 2
CITY OF CADIZ, KENTUCKY
WATER TREATMENT PLANT (WMS #15171)
ADDENDUM NO. TWO TO THE CONTRACT DOCUMENTS
VOLUME I – CONTRACT SPECIFICATIONS
The following additions and modifications shall be made to the CONTRACT SPECIFICATIONS:
1. SPECIAL CONDITIONS
(a.) Insert the attached Storm Water Pollution Prevention Plan at the end of the SpecialConditions.
(b.) Insert the attached vicinity map for the location of the existing raw water intake structure.
2. SECTION 16B
(a.) Revise Paragraph 3.10.2 to read as follows:
“Raceways in Control Room and Office may utilize electrical metal tubing (EMT). All other raceways shall be rigid galvanized steel as noted herein.”
3. SECTION 18C
(a.) Revise Paragraph 1.1 to read as follows:
“There shall be furnished and installed equipment for two (2) circular spiral scraper shaft drive clarifiers.”
4. SECTION 18E
(a.) Revise Paragraph 1.3.A.2 to read as follows:
“MF Unit Assemblies as shown on the drawings. Units shall be designed with spare capacity for the expansion of the unit to a filtration rate of no less than 1.0 MGD through the addition of membrane modules.”
(b.) Revise Paragraph 4.1 to add the following:
“Equipment manufactures shall supply the control system and equipment as specified herein or equal. Equipment manufacturer is responsible for the design and configuration to provide a fully functional control system for the operation of the membrane filtration equipment.
The flow rate for the membrane equipment shall be controlled through the variation of the membrane feed pump speed. The membrane filtration equipment Master PLC shall modulate the speed of the pumps to maintain a preset level in the feed pump wet well. Provisions to control the pumps shall be provided within the Master PLC.”
(c.) Revise Paragraph 4.2.E to read as follows:
“The current computer hardware arrangement is for a laptop computer to be located in a control room to provide operator interface with the Master PLC in addition to the HMI installed in the Master PLC cabinet.”
VOLUME II – CONTRACT DRAWINGS
The following additions and modifications shall be made to the CONTRACT DRAWINGS:
1. Sheet G-8
WMS No. 15171 2 Addendum No. 2
(a.) Replace the Typical Paving and Drive Detail on Sheet G-8 with the attached detail.
(b.) Revise the Typical Fence and Gate Details notes as follows:
“5. Install a 1” underground conduit from the motorized gate into the control room and mount a momentary switch in a gang box for control of the access gate.
6. Provide LiftMaster access control keypad, MINIKEY MK500GS, installed on agooseneck pedestal to allow for control of the motorized gate.
7. Provide Viking call box, w3000, and C1000B controller or equal for integration with thephone system.”
2. Sheet A-5
(a.) Add the following notes:
“1. Furnish letters and hardware necessary to install Flat Cut Metal letter signage as follows:
Cadiz Water Treatment Plant
2. Letters shall be 9” in height for the top row and 6” for the second row.
3. Letters shall be laser or water jetcut cut from 5052 Aluminium with a minimum 1/2”thickness.
4. Provide a brushed face finish with bead blasted returns and a baked clear low-glosspowder coated finish.
5. Letters shall be installed using blind studs with top and bottom rails and tiebacks asrequired by the manufacturer. ”
3. Sheet M-1
(a.) Replace Sheet M-1 with the attached sheet that provides legible text.
4. Sheet M-2
(a.) Replace Sheet M-2 with the attached sheet that provides legible text.
WATER MANAGEMENT SERVICES, LLC Consulting Engineers
By: ____________________________ Steven M. Jones License No. 26233
Dated: April 11, 2018
Company Name
Signature Date
Please acknowledge receipt of this Addendum by signing below and emailing or faxing this page back to Water Management Services, LLC at 615/366-6203. Thank you.
GENERAL MECHANICAL SPECIFICATIONS
WTR HTR.
100103 104114113
112 111
110
109
108107
105
106101
102
MECHANICAL PLAN - OFFICE / CONTROL BUILDING
5'-0" 10'-0" 20'-0"
1/8" = 1'-0"
CODED NOTES
4-TON SPLIT SYSTEM WITH GAS FURNACE
4-TON SPLIT SYSTEM WITH GAS FURNACE
1-TON MINI SPLIT
AIR INTAKE LOUVER - INSTALL AT 12" A.F.F.
VENTILATION FAN - INSTALL AT 12" BELOW CEILING
UNIT HEATER - INSTALL AT 11' A.F.F.
FACE AREA (SQ. FT.)
CO
OLI
NG
CO
IL
COIL FACE AREA (SQ. FT.)
VOLTAGE / PHASE / Hz (OUTDOOR)
NO. ROWS / FINS
RESISTANCE (IN. WG.)
E.A.T. °F WB
E.A.T. °F DB
MODEL NUMBER:
COMBINED RATING W/ COIL (ARI)
COMPRESSOR RLA
COND. UNIT MCA / MOCP
EVAPORATOR FAN H.P.
VOLTAGE / PHASE / Hz (INDOOR)
CO
ND
. UN
ITE
LEC
TRIC
AL
REMARKS
LOCATION
S.E.E.R.
MANUFACTURER
AVAILABLE E.S.P.
DRIVE TYPE
MODEL NO.
BTUH HEAT OUTPUT
BTUH GAS INPUT
MIN. OUTSIDE AIR CFM
SUPPLY AIR CFM
SPLIT FURNACE SCHEDULE
MODEL NUMBER
FUR
NA
CE
SYMBOL
7-DAY PROGRAMMABLE AUTO-CHANGEOVER THERMOSTATSMOKE DETECTOR MOUNTED IN RETURN AIR DUCT PRIORTO MIXING WITH OUTSIDE AIR FOR AUTOMATIC
ACCESSORIES:1.2.
SHUTDOWN OF FAN UPON DETECTION OF SMOKEINCLUDE CONDENSATE PUMP3.
2. BACKDRAFT DAMPER
4. INTERLOCK WITH LIGHTS3. FAN MOUNTED SPEED CONTROLLER
Sound Rating (SONES)
OPERATING WEIGHT
LOCATION
REMARKS:
ACCESSORIES
1. ROOF CAP / WALL CAP (SEE DWG)
B.H.P.
Voltage / Phase
H.P. / WATTS
EXHAUST FAN SCHEDULE
TYPE
C.F.M.
S.P. IN W.G.
R.P.M.
TIP SPEED (RPM)
SYMBOL
MANUFACTURER
MODEL No.
RR-EF-1 JAN-EF
L. COOK
GC-124
13
CEILING
1.2
59.2W
115 / 1Ø
CABINET
1,797
N/A
0.25''
900
75
1, 2, 4
L. COOK
GC-144
15
CEILING
1.4
74.0W
115 / 1Ø
CABINET
1,859
N/A
0.25''
931
100
1, 2, 4
VENT-EF-3
L. COOK
48XMPH
550
PUMP ROOM
40
3.6 HP
208 / 3Ø
PROPELLOR
7,652
5.0 HP
0.125''
609
25,000
2, 5, 6
GAS FIRED UNIT HEATER SCHEDULE
MINI SPLIT SYSTEM
MITSUBISHI PKA COOLING ONLY SYSTEM - 12,000BTUH COOLING CAPACITY, 208-230/1Ø
INDOOR UNIT:MITSUBISHI MODEL # PKA-A12HA - WALL MOUNTEDAIR HANDLER, NOMINAL - 1.0 MCA, 0.33 FLA,WEIGHS 29 LBS, ROUTE CONDENSATE ANDREFRIGERANT LINES INSIDE WALL, MAKE POWERCONNECTIONS ABOVE CEILING, INCLUDECONDENSATE PUMP
OUTDOOR UNIT:MITSUBISHI MODEL # PUY-A12NHA4 CONDENSINGUNIT - 13 MCA, 15 MOCP, 0.35 FLA, 12COMPRESSOR RLA, 14 COMPRESSOR LRA,WEIGHS 85 LBS
NOTE: CONNECT PIPING TO BACK OF INDOORUNITS TO CONCEAL REFRIGERANT ANDCONDENSATE PIPING.
RR-EF-1
L. COOK
GC-124
13
CEILING
1.2
59.2W
115 / 1Ø
CABINET
1,797
N/A
0.25''
900
75
1, 2, 4
5. WALL MOUNTED ON / OFF SWITCH6. INTERLOCK WITH INTAKE LOUVERS
MECHANICAL PLAN - FLUORIDE BUILDING
5'-0" 10'-0" 20'-0"
1/8" = 1'-0"
VENT-EF-2VENT-EF-1
L. COOK
10XW24D103
20
FLUORIDE ROOM
16.6
51.3 W
115 / 1Ø
PROPELLOR
2,528
N/A
0.125''
966
250
2, 5, 6
L. COOK
10XW24D103
20
FLUORIDE ROOM
16.6
51.3 W
115 / 1Ø
PROPELLOR
2,528
N/A
0.125''
966
250
2, 5, 6
WTR HTR.
100103 104114113
112 111
110
109
108107
105
106101
102
PLUMBING PLAN - OFFICE / CONTROL BUILDING
5'-0" 10'-0" 20'-0"
1/8" = 1'-0"
KS-2
EWC
LS-1
LS-2
SH
LAV
WC-1JS
LAV WC-1
SH
WH-1
FD
FD
FD
FD
IM
DW
RPBP
EW
WH-2
FDEW
WH-2
EW
WH-2
2" VTR 2" VTR
REFER SCHEDULEPROTECTION SADDLE
WITH SOCKETS AND SADDLETRAPEZE ROLLER HANGER
PIPE HANGER DETAILNO SCALE
5/8"
PIPING - SEE SCHEDULEFOR MATERIALS
INSULATION (IF REQUIRED)
HANGER SPACING SCHEDULE
(IN.)
(FT.)
PIPE COVERING
(SEE SCHEDULE)ALL-THREAD ROD
HANGERS
HANGER RODSIZE
MAXIMUMDISTANCEBETWEEN
NOMINALPIPE SIZE
3/8"3/8"3/8" 3/8" 1/2"1/2" 5/8"
2"
10'
1 1/4"
8'7'
1"
9'
1 1/2"
11'
2 1/2"
12' 14'
3" 4"
3/4"
16' 17'
5" 6"
GENERAL PLUMBING SPECIFICATIONS
FURNISH, INSTALL, PROVIDE AND MAKE OPERATIVE ALL EQUIPMENT,MATERIALS, SUPERVISION, LABOR AND ANY AND ALL ITEMS NECESSARY FORTHE PROPER INSTALLATION OF A CORRECTLY FUNCTIONING PLUMBINGSYSTEM AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN.
EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THEMANUFACTURER'S RECOMMENDATIONS. EQUALS SHALL BE ACCEPTED FOREQUIPMENT UNLESS OTHERWISE NOTED.
ORDINANCES, PERMITS AND CODES: THE WORKMANSHIP AND MATERIALSCOVERED BY THESE SPECIFICATIONS SHALL CONFORM TO ALL REGULATIONSOF ALL THE AUTHORITIES HAVING JURISDICTION.
THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, CONNECTIONAND INSPECTION FEES AS REQUIRED FOR THE COMPLETE INSTALLATION OFTHE PLUMBING SYSTEM.
THE LOCATION OF PIPING AND EQUIPMENT, AS SHOWN ON THE DRAWINGS, ISDIAGRAMMATIC AND SCHEMATIC AND IT IS THE RESPONSIBILITY OF THECONTRACTOR TO MAKE HIS OWN WORKING LAYOUT TO ELIMINATE ALLSTRUCTURAL AND ARCHITECTURAL CONFLICTS IN THE BUILDING.
VERIFY ALL MEASUREMENTS AT THE SITE AND COORDINATE ALL WORK SOTHAT IT DOES NOT INTERFERE WITH THE WORK OF THE OTHER TRADES.INSULATION: ALL INSULATION, INCLUDING JACKET, OR FACING AND ADHESIVEUSED TO ADHERE FACING OR JACKET TO THE INSULATION SHALL HAVE ACOMPOSITE FIRE AND SMOKE HAZARD RATING TESTED BY THE PROCEDURERECOMMENDED BY ASTM E-84, NFPA 225 OR U.L. 723, NOT EXCEEDING:FLAME SPREAD 25, SMOKE DEVELOPED 50. ALL INSULATION ACCESSORIESSHALL ALSO HAVE THE RATING LISTED ABOVE.
DOMESTIC WATER PIPES SHALL BE INSULATED WITH ONE (1) INCH THICKPREFORMED HIGH DENSITY FIBERGLASS WITH FACTORY APPLIED VAPORBARRIER AND SELF SEALING LAP, SUCH AS OWENS CORNING 25 ASJ.
DOMESTIC WATER PIPES SHALL BE TYPE "L" COPPER ABOVE GROUND / SLABAND TYPE ''K'' COPPER BELOW GRADE / SLAB. INSTALL DIELECTRIC UNIONSAT CONNECTION TO DISSIMILAR METALS.PEX PIPING IS ACCEPTABLE FOR DOMESTIC WATER PIPING UNDER 2".
SANITARY WASTE AND VENT PIPE SHALL BE CAST IRON WITH NO-HUBFITTINGS. SCHEDULE 40 PVC PERMISSIBLE IF NOT ROUTED WITHIN A RETURNAIR PLENUM.
SUPPLIED WITH WALL HANGER
POLYURETHANE FOAM INSULATION
NOTE: INSULATE ALL EXPOSED LAVATORY WASTE LINES ANDEXPOSED HOT WATER LINES WITH BROCAR (OR EQUAL)
MOEN FAUCET MODEL L64601, AERATOR IS LIMITED TO 0.5 GPM MAX.McGUIRE # 155-A GRID DRAIN, 1 1/4" # 8812 P-TRAP, # 2165CC SUPPLIES(MTD. WITH TOP OF FRONT RIM AT 34'' A.F.F.)
AMERICAN STANDARD MODEL # 0321 . 026, HOLES ON 4" CENTERSLAV LAVATORY (WALL HUNG, VITREOUS CHINA, A.D.A. COMPLIANT)
WATER CLOSET (TANK TYPE, A.D.A.)
ELONGATED BOWL, 1 . 6 GALLON PER FLUSHZURN # Z-8804-CR SUPPLY WITH WHEEL STOPOLSONITE # 100 CLOSED FRONT SEAT WITH COVER
AMERICAN STANDARD MODEL # 2998 . 014
TOP OF SEAT AT MIN. 17'' / MAX. 19'' A.F.F.
WC-1
PLUMBING FIXTURE SPECIFICATIONS
STEEL, 3/4 HP, 120V, 1725 RPMIN-SINK-ERATOR FOOD WASTE DISPOSER # PRO333 STAINLESS
WRIST BLADE HANDLES, JUST # JB-99 1 1/2" DRAIN WITH BASKETJUST #J-1174-KS CONCEALED MIXING FAUCET WITH SPRAY HOSE, WITH
KS-2JUST MODEL # DL-1933-A-GR STAINLESS STEEL SINK 18 GA.
STRAINER, TAILPIECE AND CONTINUOUS WASTEMcGUIRE # 2165CC FLEXIBLE SUPPLIES WITH WHEEL STOPS
BREAK SINK (DOUBLE COMPARTMENT, 19"x33"x7 1/2")
EWC
HEIGHT TO 4" ABOVE SPOUT. PROVIDE APRON FOR UPPER UNIT.115V / 1~. UNIT MOUNTED WITH SPOUT AT 34" A.F.F. - ADJUST STREAM
OASIS MODEL # M8CR, FLEXIBLE BUBBLER GUARD, 8 . 0 GPM OF 50°F WATER, 1/5 H.P. COMPRESSOR, 4.6 FLA - 340 WATTS,
ELECTRIC WATER COOLERS (SPLIT-LEVEL, BARRIER FREE)
WITH VAPOR BARRIER3/8" WATER LINES TO BE INSULATED WITH MIN. 1" THICK INSULATION
FLOOR DRAIN (ROUND TOP, 3" DIAMETER OUTLET)FDJ.R. SMITH MODEL #2005 CAST IRON BODY WITH REVERSIBLE FLASHINGCOLLAR PERMITS ADJUSTMENT OF STRAINER TO MEET FINISHED FLOOR LEVEL. TRAP PRIMER CONNECTION.
HD2'' DIAMETER OPEN SITE DRAIN STUBBED UP MINIMUM 2" ABOVEFINISHED FLOOR - PROVIDE P-TRAP WITH PRIMER CONNECTION.
HUB DRAIN
JANITOR SINK (23" x 23 1/2") JS
CONSTRUCTION USING NATURAL CRUSHED STONE WITH POLYESTERRESIN. TUB TO INCLUDE INTEGRALLY MOLDED DRAIN ASSEMBLY,STOPPER, FLOOR MOUNTING HARDWARE.CHICAGO MODEL 1100-E35CP FAUCET (1.5 GPM) WITH WRIST BLADE
TAILPIECE. HOLES ON 8" CENTERS.
HBWOODFORD MODEL B67 FREEZELESS WALL HYDRANT, 3/4" MALEHOSE THREAD, BACKFLOW PREVENTER, AUTOMATIC DRAINING, HYDRANT DRAINS WHEN SHUT OFF, ENCLOSED IN A FLUSH MOUNTEDWALL BOX, WALL CLAMP AND LOOSE TEE KEY.
HOSE BIBB (NON-FREEZE)
IMOATEY MODEL 39152 ICE MAKER BOX WITH VALVE. CONTRACTORSHALL MAKE FINAL CONNECTION. PROVIDE 1/2" COLD WATER SUPPLYWITH SEPARATE ISOLATION VALVE IN BRANCH LINE. PROVIDE UNIONAT CONNECTION POINT TO REFRIGERATOR AND ENOUGH COPPERPIPE TO ALLOW REFRIGERATOR TO BE PULLED OUT FOR CLEANINGAND MAINTENANCE. INSTALL SHOCK ABSORBER ON WATER LINE.
ICE MAKER ROUGH-IN (REFRIGERATOR)
SHOCK ABSORBER
RECOMMANDED BY MANUFACTURER.JOSAM FIG. # 75001 THROUGH 75006, SIZE AS
COLD WATER LINE - PROVIDE ONE VALVE PER TRAPOR VALVES WITH DISTRIBUTION UNITS AS REQUIREDTO SERVE ALL P-TRAPS
TRAP PRIMER VALVE - INSTALL WITH COUPLING IN NEARBYPRECISION PLUMBING PRODUCTS INC. # PR-500
TP TRAP PRIMER
ECOJ.R. SMITH # 4429Y-04 WITH HEAVY DUTYCAST IRON COVER(SEE PLANS FOR SIZES)
(SEE PLANS FOR SIZES)
J.R. SMITH # 4031L-04 DUCO CAST IRON CLEANOUT WITH ROUNDADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP.
ICO
EXTERIOR CLEAN-OUT
INTERIOR CLEAN-OUT
SA
SINK WITH SEPARATE ISOLATION VALVE BELOW SINK. PROVIDE
ENTERING SIDE OF ADJACENT SINK P-TRAP.CONNECTION SIZE FLEXIBLE DRAIN LINE CONNECTED TOUNION AT CONNECTION POINT TO DISHWASHER. PROVIDE
1/2" HOT WATER SUPPLY FEED FROM BELOW ADJACENTCONTRACTOR SHALL MAKE FINAL CONNECTION. PROVIDE
DW DISHWASHER (ROUGH-IN, RESIDENTAL)
LS-1JUST # SLX-2019-A-GR 18 GA. TYPE 304, 18-8 STAINLESS STEELLAB SINK (COUNTERTOP, SINGLE COMPARTMENT, 20"x19"x 10.5")
CHICAGO # 201-AGN8AE35-317CP FAUCET, SWING GOOSENECK SPOUT,AERATOR IS LIMITED TO 1.5 GPM MAX., WRIST BLADE HANDLES.JUST # JB-99 DRAIN, # JT-200 2" O.D. P-TRAPMcGUIRE # 2165-CC FLEXIBLE SUPPLIES WITH WHEEL STOPS
LS-2 LAB SINK (COUNTERTOP, 22"x37"x12" DOUBLE COMPARTMENT)JUST # DLXD-2237-A-GR 18 GA. TYPE 304, 18-8 STAINLESS STEELCHICAGO # 201-AGN8AE35-317CP FAUCET, SWING GOOSENECK SPOUT,AERATOR IS LIMITED TO 1.5 GPM MAX., WRIST BLADE HANDLES.JUST # JB-99 DRAIN, # JT-200 2" O.D. P-TRAPMcGUIRE # 2165-CC FLEXIBLE SUPPLIES WITH WHEEL STOPS
PLUMBING EQUIPMENT SPECIFICATIONS
THERMOSTATIC MIXING VALVE
WATER HEATERWH-1 (26" DIA. x 70-5/8" TALL)STATE MODEL # SDV75 70 NE GAS WATER HEATER - 75 GALLON CAP.-81 GPH RECOVERY AT 80° F RISE - 70,000 BTU/HR NAT. GAS INPUT - PROVIDEEMERGENCY DRAIN PAN, TANK DRAIN WITH HOSE CONNECTION, 3'' DIA. GASFLUE, ASME T & P RELIEF VALVE, DIELECTRIC UNIONS AT CONNECTIONS TODISSIMILAR METALS, SHUT-OFF VALVES ON HOT & COLD WATER HEATERTO HAVE POWER DIRECT-VENT & WIRE GRILL VENT CAP. SETTEMPERATURE TO 140°
WATER DETECTOR SHUTOFFTACO "WAGS" WATER DETECTOR AND WATER & GAS SHUT-OFFVALVE. VALVE CONTROL UNIT AUTOMATICALLY SHUTS OFF WATER &GAS IF LEAK IS DETECTED
WILKINS MODEL #ZW3870T THERMOSTATIC MIXING VALVE INSTALLEDON HOT WATER OUTLETS NOT SPECIFIED TO HAVE 140° WATER.
RPBPWILKINS MODEL # 975XL BRONZE BODY - 1-1/4'' SIZE - 12 PSIG PRESSUREDROP AT 25 GPM FLOW - PROVIDE SHUT-OFF VALVES AND RELIEFPIPING WITH AIR-GAP TO SPILL TO NEAREST DRAIN
MOLDED FOLD UP SEAT, SHELVES, SOAP TRAY AND CENTER DRAINAQUARIUS MODEL # S 4136 BF ACRYLIC MOLDED CONSTRUCTION WITH
SH SHOWER ENCLOSURE (41" x 36", A.D.A. COMPLIANT)
BRADLEY MODEL S19-210X EYE/FACE WASH FIXTURE, 10" DIAMETER STAINLESS STEEL EYE WASH BOWL. CHROME-PLATED BRASS 1/2" IPSSTAY-OPEN BALL VALVE. HAND OPERATED BY A LARGE, HIGHLYVISIBLE PUSH HANDLE OR FOOT PEDAL. GALVANIZED STEEL ANDWASTE TEE WITH FLOOR FLANGE PROTECTED WITH "BRADTECT"SAFETY YELLOW COATING. 1/2" HW & 1/2" CW SUPPLY WITH MIXING VALVE.
EMERG. EYE WASH (PEDESTAL-MOUNTED, HAND OR FOOT OPERATION)EW
SYMMONS MODEL # 96-1, TEMPTROL PRESSURE-BALANCING MIXINGVALVE WITH ADJUSTABLE STOP SCREW, TUB SPOUT, LOW FLOW HEAD
1/2" WATER CONNECTION, 2" DRAIN CONNECTION1.5 GPM MAXIMUM, CLEAR-FLOW SHOWERHEAD WITH ARM AND FLANGE.
HB
CODED NOTES:
CONNECT NEW 1-1/4" COLD WATER LINE TO 3" WATERLINE BEFORE BACKFLOW PREVENTOR, BACKFLOWPREVENTION FOR OFFICES IN JANITOR'S CLOSET
SPILL CONDENSATE FROM AIR HANDLING UNITS TOFLOOR DRAIN
NEW GAS METERBY GAS UTILITYCOMPANY
SEE SITE PLAN FORCONTINUATION OF 4"SANITARY SEWER LINE
FD
EW
WH-2
EW
WH-2
ICO
FD FD FD
HB
HB
ICOICO
WH-2 - WALL MOUNTEDEEMAX ELECTRIC INSTANTANEOUS WATER HEATER - MODEL # SP42084 . 1 KW AT 208V / 1Ø - 19.7 AMPS - 0.5 GPM MAX. FLOW - INSTALL ON WALL.REFER PLANS FOR EXACT LOCATION
PLUMBING PLAN - FLUORIDE BUILDING
5'-0" 10'-0" 20'-0"
1/8" = 1'-0"
FD FD
ICO
SEE SITE PLAN FORCONTINUATION OF 4"SANITARY SEWER LINE
TP
TP
TP
TP
CONNECT TRAPPRIMER TO 2" WATERLINE SERVINGBUILDING