WMS No. 15171 1 Addendum No. 2 CITY OF CADIZ, KENTUCKY WATER TREATMENT PLANT (WMS #15171) ADDENDUM NO. TWO TO THE CONTRACT DOCUMENTS VOLUME I – CONTRACT SPECIFICATIONS The following additions and modifications shall be made to the CONTRACT SPECIFICATIONS: 1. SPECIAL CONDITIONS (a.) Insert the attached Storm Water Pollution Prevention Plan at the end of the Special Conditions. (b.) Insert the attached vicinity map for the location of the existing raw water intake structure. 2. SECTION 16B (a.) Revise Paragraph 3.10.2 to read as follows: “Raceways in Control Room and Office may utilize electrical metal tubing (EMT). All other raceways shall be rigid galvanized steel as noted herein.” 3. SECTION 18C (a.) Revise Paragraph 1.1 to read as follows: “There shall be furnished and installed equipment for two (2) circular spiral scraper shaft drive clarifiers.” 4. SECTION 18E (a.) Revise Paragraph 1.3.A.2 to read as follows: “MF Unit Assemblies as shown on the drawings. Units shall be designed with spare capacity for the expansion of the unit to a filtration rate of no less than 1.0 MGD through the addition of membrane modules.” (b.) Revise Paragraph 4.1 to add the following: “Equipment manufactures shall supply the control system and equipment as specified herein or equal. Equipment manufacturer is responsible for the design and configuration to provide a fully functional control system for the operation of the membrane filtration equipment. The flow rate for the membrane equipment shall be controlled through the variation of the membrane feed pump speed. The membrane filtration equipment Master PLC shall modulate the speed of the pumps to maintain a preset level in the feed pump wet well. Provisions to control the pumps shall be provided within the Master PLC.” (c.) Revise Paragraph 4.2.E to read as follows: “The current computer hardware arrangement is for a laptop computer to be located in a control room to provide operator interface with the Master PLC in addition to the HMI installed in the Master PLC cabinet.” VOLUME II – CONTRACT DRAWINGS The following additions and modifications shall be made to the CONTRACT DRAWINGS: 1. Sheet G-8
Transcript

WMS No. 15171 1 Addendum No. 2

CITY OF CADIZ, KENTUCKY

WATER TREATMENT PLANT (WMS #15171)

ADDENDUM NO. TWO TO THE CONTRACT DOCUMENTS

VOLUME I – CONTRACT SPECIFICATIONS

The following additions and modifications shall be made to the CONTRACT SPECIFICATIONS:

1. SPECIAL CONDITIONS

(a.) Insert the attached Storm Water Pollution Prevention Plan at the end of the SpecialConditions.

(b.) Insert the attached vicinity map for the location of the existing raw water intake structure.

2. SECTION 16B

(a.) Revise Paragraph 3.10.2 to read as follows:

“Raceways in Control Room and Office may utilize electrical metal tubing (EMT). All other raceways shall be rigid galvanized steel as noted herein.”

3. SECTION 18C

(a.) Revise Paragraph 1.1 to read as follows:

“There shall be furnished and installed equipment for two (2) circular spiral scraper shaft drive clarifiers.”

4. SECTION 18E

(a.) Revise Paragraph 1.3.A.2 to read as follows:

“MF Unit Assemblies as shown on the drawings. Units shall be designed with spare capacity for the expansion of the unit to a filtration rate of no less than 1.0 MGD through the addition of membrane modules.”

(b.) Revise Paragraph 4.1 to add the following:

“Equipment manufactures shall supply the control system and equipment as specified herein or equal. Equipment manufacturer is responsible for the design and configuration to provide a fully functional control system for the operation of the membrane filtration equipment.

The flow rate for the membrane equipment shall be controlled through the variation of the membrane feed pump speed. The membrane filtration equipment Master PLC shall modulate the speed of the pumps to maintain a preset level in the feed pump wet well. Provisions to control the pumps shall be provided within the Master PLC.”

(c.) Revise Paragraph 4.2.E to read as follows:

“The current computer hardware arrangement is for a laptop computer to be located in a control room to provide operator interface with the Master PLC in addition to the HMI installed in the Master PLC cabinet.”

VOLUME II – CONTRACT DRAWINGS

The following additions and modifications shall be made to the CONTRACT DRAWINGS:

1. Sheet G-8

WMS No. 15171 2 Addendum No. 2

(a.) Replace the Typical Paving and Drive Detail on Sheet G-8 with the attached detail.

(b.) Revise the Typical Fence and Gate Details notes as follows:

“5. Install a 1” underground conduit from the motorized gate into the control room and mount a momentary switch in a gang box for control of the access gate.

6. Provide LiftMaster access control keypad, MINIKEY MK500GS, installed on agooseneck pedestal to allow for control of the motorized gate.

7. Provide Viking call box, w3000, and C1000B controller or equal for integration with thephone system.”

2. Sheet A-5

(a.) Add the following notes:

“1. Furnish letters and hardware necessary to install Flat Cut Metal letter signage as follows:

Cadiz Water Treatment Plant

2. Letters shall be 9” in height for the top row and 6” for the second row.

3. Letters shall be laser or water jetcut cut from 5052 Aluminium with a minimum 1/2”thickness.

4. Provide a brushed face finish with bead blasted returns and a baked clear low-glosspowder coated finish.

5. Letters shall be installed using blind studs with top and bottom rails and tiebacks asrequired by the manufacturer. ”

3. Sheet M-1

(a.) Replace Sheet M-1 with the attached sheet that provides legible text.

4. Sheet M-2

(a.) Replace Sheet M-2 with the attached sheet that provides legible text.

WATER MANAGEMENT SERVICES, LLC Consulting Engineers

By: ____________________________ Steven M. Jones License No. 26233

Dated: April 11, 2018

Company Name

Signature Date

Please acknowledge receipt of this Addendum by signing below and emailing or faxing this page back to Water Management Services, LLC at 615/366-6203. Thank you.

sjones
Callout
Existing Raw Water Intake
sjones
Typewritten Text
Gentry Gray Rd.

Cadiz W

TP (#15171) A

ddendum N

o. 2

GENERAL MECHANICAL SPECIFICATIONS

WTR HTR.

100103 104114113

112 111

110

109

108107

105

106101

102

MECHANICAL PLAN - OFFICE / CONTROL BUILDING

5'-0" 10'-0" 20'-0"

1/8" = 1'-0"

CODED NOTES

4-TON SPLIT SYSTEM WITH GAS FURNACE

4-TON SPLIT SYSTEM WITH GAS FURNACE

1-TON MINI SPLIT

AIR INTAKE LOUVER - INSTALL AT 12" A.F.F.

VENTILATION FAN - INSTALL AT 12" BELOW CEILING

UNIT HEATER - INSTALL AT 11' A.F.F.

FACE AREA (SQ. FT.)

CO

OLI

NG

CO

IL

COIL FACE AREA (SQ. FT.)

VOLTAGE / PHASE / Hz (OUTDOOR)

NO. ROWS / FINS

RESISTANCE (IN. WG.)

E.A.T. °F WB

E.A.T. °F DB

MODEL NUMBER:

COMBINED RATING W/ COIL (ARI)

COMPRESSOR RLA

COND. UNIT MCA / MOCP

EVAPORATOR FAN H.P.

VOLTAGE / PHASE / Hz (INDOOR)

CO

ND

. UN

ITE

LEC

TRIC

AL

REMARKS

LOCATION

S.E.E.R.

MANUFACTURER

AVAILABLE E.S.P.

DRIVE TYPE

MODEL NO.

BTUH HEAT OUTPUT

BTUH GAS INPUT

MIN. OUTSIDE AIR CFM

SUPPLY AIR CFM

SPLIT FURNACE SCHEDULE

MODEL NUMBER

FUR

NA

CE

SYMBOL

7-DAY PROGRAMMABLE AUTO-CHANGEOVER THERMOSTATSMOKE DETECTOR MOUNTED IN RETURN AIR DUCT PRIORTO MIXING WITH OUTSIDE AIR FOR AUTOMATIC

ACCESSORIES:1.2.

SHUTDOWN OF FAN UPON DETECTION OF SMOKEINCLUDE CONDENSATE PUMP3.

2. BACKDRAFT DAMPER

4. INTERLOCK WITH LIGHTS3. FAN MOUNTED SPEED CONTROLLER

Sound Rating (SONES)

OPERATING WEIGHT

LOCATION

REMARKS:

ACCESSORIES

1. ROOF CAP / WALL CAP (SEE DWG)

B.H.P.

Voltage / Phase

H.P. / WATTS

EXHAUST FAN SCHEDULE

TYPE

C.F.M.

S.P. IN W.G.

R.P.M.

TIP SPEED (RPM)

SYMBOL

MANUFACTURER

MODEL No.

RR-EF-1 JAN-EF

L. COOK

GC-124

13

CEILING

1.2

59.2W

115 / 1Ø

CABINET

1,797

N/A

0.25''

900

75

1, 2, 4

L. COOK

GC-144

15

CEILING

1.4

74.0W

115 / 1Ø

CABINET

1,859

N/A

0.25''

931

100

1, 2, 4

VENT-EF-3

L. COOK

48XMPH

550

PUMP ROOM

40

3.6 HP

208 / 3Ø

PROPELLOR

7,652

5.0 HP

0.125''

609

25,000

2, 5, 6

GAS FIRED UNIT HEATER SCHEDULE

MINI SPLIT SYSTEM

MITSUBISHI PKA COOLING ONLY SYSTEM - 12,000BTUH COOLING CAPACITY, 208-230/1Ø

INDOOR UNIT:MITSUBISHI MODEL # PKA-A12HA - WALL MOUNTEDAIR HANDLER, NOMINAL - 1.0 MCA, 0.33 FLA,WEIGHS 29 LBS, ROUTE CONDENSATE ANDREFRIGERANT LINES INSIDE WALL, MAKE POWERCONNECTIONS ABOVE CEILING, INCLUDECONDENSATE PUMP

OUTDOOR UNIT:MITSUBISHI MODEL # PUY-A12NHA4 CONDENSINGUNIT - 13 MCA, 15 MOCP, 0.35 FLA, 12COMPRESSOR RLA, 14 COMPRESSOR LRA,WEIGHS 85 LBS

NOTE: CONNECT PIPING TO BACK OF INDOORUNITS TO CONCEAL REFRIGERANT ANDCONDENSATE PIPING.

RR-EF-1

L. COOK

GC-124

13

CEILING

1.2

59.2W

115 / 1Ø

CABINET

1,797

N/A

0.25''

900

75

1, 2, 4

5. WALL MOUNTED ON / OFF SWITCH6. INTERLOCK WITH INTAKE LOUVERS

MECHANICAL PLAN - FLUORIDE BUILDING

5'-0" 10'-0" 20'-0"

1/8" = 1'-0"

VENT-EF-2VENT-EF-1

L. COOK

10XW24D103

20

FLUORIDE ROOM

16.6

51.3 W

115 / 1Ø

PROPELLOR

2,528

N/A

0.125''

966

250

2, 5, 6

L. COOK

10XW24D103

20

FLUORIDE ROOM

16.6

51.3 W

115 / 1Ø

PROPELLOR

2,528

N/A

0.125''

966

250

2, 5, 6

WTR HTR.

100103 104114113

112 111

110

109

108107

105

106101

102

PLUMBING PLAN - OFFICE / CONTROL BUILDING

5'-0" 10'-0" 20'-0"

1/8" = 1'-0"

KS-2

EWC

LS-1

LS-2

SH

LAV

WC-1JS

LAV WC-1

SH

WH-1

FD

FD

FD

FD

IM

DW

RPBP

EW

WH-2

FDEW

WH-2

EW

WH-2

2" VTR 2" VTR

REFER SCHEDULEPROTECTION SADDLE

WITH SOCKETS AND SADDLETRAPEZE ROLLER HANGER

PIPE HANGER DETAILNO SCALE

5/8"

PIPING - SEE SCHEDULEFOR MATERIALS

INSULATION (IF REQUIRED)

HANGER SPACING SCHEDULE

(IN.)

(FT.)

PIPE COVERING

(SEE SCHEDULE)ALL-THREAD ROD

HANGERS

HANGER RODSIZE

MAXIMUMDISTANCEBETWEEN

NOMINALPIPE SIZE

3/8"3/8"3/8" 3/8" 1/2"1/2" 5/8"

2"

10'

1 1/4"

8'7'

1"

9'

1 1/2"

11'

2 1/2"

12' 14'

3" 4"

3/4"

16' 17'

5" 6"

GENERAL PLUMBING SPECIFICATIONS

FURNISH, INSTALL, PROVIDE AND MAKE OPERATIVE ALL EQUIPMENT,MATERIALS, SUPERVISION, LABOR AND ANY AND ALL ITEMS NECESSARY FORTHE PROPER INSTALLATION OF A CORRECTLY FUNCTIONING PLUMBINGSYSTEM AS SHOWN ON THE DRAWINGS AND SPECIFIED HEREIN.

EQUIPMENT SHALL BE INSTALLED IN ACCORDANCE WITH THEMANUFACTURER'S RECOMMENDATIONS. EQUALS SHALL BE ACCEPTED FOREQUIPMENT UNLESS OTHERWISE NOTED.

ORDINANCES, PERMITS AND CODES: THE WORKMANSHIP AND MATERIALSCOVERED BY THESE SPECIFICATIONS SHALL CONFORM TO ALL REGULATIONSOF ALL THE AUTHORITIES HAVING JURISDICTION.

THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, CONNECTIONAND INSPECTION FEES AS REQUIRED FOR THE COMPLETE INSTALLATION OFTHE PLUMBING SYSTEM.

THE LOCATION OF PIPING AND EQUIPMENT, AS SHOWN ON THE DRAWINGS, ISDIAGRAMMATIC AND SCHEMATIC AND IT IS THE RESPONSIBILITY OF THECONTRACTOR TO MAKE HIS OWN WORKING LAYOUT TO ELIMINATE ALLSTRUCTURAL AND ARCHITECTURAL CONFLICTS IN THE BUILDING.

VERIFY ALL MEASUREMENTS AT THE SITE AND COORDINATE ALL WORK SOTHAT IT DOES NOT INTERFERE WITH THE WORK OF THE OTHER TRADES.INSULATION: ALL INSULATION, INCLUDING JACKET, OR FACING AND ADHESIVEUSED TO ADHERE FACING OR JACKET TO THE INSULATION SHALL HAVE ACOMPOSITE FIRE AND SMOKE HAZARD RATING TESTED BY THE PROCEDURERECOMMENDED BY ASTM E-84, NFPA 225 OR U.L. 723, NOT EXCEEDING:FLAME SPREAD 25, SMOKE DEVELOPED 50. ALL INSULATION ACCESSORIESSHALL ALSO HAVE THE RATING LISTED ABOVE.

DOMESTIC WATER PIPES SHALL BE INSULATED WITH ONE (1) INCH THICKPREFORMED HIGH DENSITY FIBERGLASS WITH FACTORY APPLIED VAPORBARRIER AND SELF SEALING LAP, SUCH AS OWENS CORNING 25 ASJ.

DOMESTIC WATER PIPES SHALL BE TYPE "L" COPPER ABOVE GROUND / SLABAND TYPE ''K'' COPPER BELOW GRADE / SLAB. INSTALL DIELECTRIC UNIONSAT CONNECTION TO DISSIMILAR METALS.PEX PIPING IS ACCEPTABLE FOR DOMESTIC WATER PIPING UNDER 2".

SANITARY WASTE AND VENT PIPE SHALL BE CAST IRON WITH NO-HUBFITTINGS. SCHEDULE 40 PVC PERMISSIBLE IF NOT ROUTED WITHIN A RETURNAIR PLENUM.

SUPPLIED WITH WALL HANGER

POLYURETHANE FOAM INSULATION

NOTE: INSULATE ALL EXPOSED LAVATORY WASTE LINES ANDEXPOSED HOT WATER LINES WITH BROCAR (OR EQUAL)

MOEN FAUCET MODEL L64601, AERATOR IS LIMITED TO 0.5 GPM MAX.McGUIRE # 155-A GRID DRAIN, 1 1/4" # 8812 P-TRAP, # 2165CC SUPPLIES(MTD. WITH TOP OF FRONT RIM AT 34'' A.F.F.)

AMERICAN STANDARD MODEL # 0321 . 026, HOLES ON 4" CENTERSLAV LAVATORY (WALL HUNG, VITREOUS CHINA, A.D.A. COMPLIANT)

WATER CLOSET (TANK TYPE, A.D.A.)

ELONGATED BOWL, 1 . 6 GALLON PER FLUSHZURN # Z-8804-CR SUPPLY WITH WHEEL STOPOLSONITE # 100 CLOSED FRONT SEAT WITH COVER

AMERICAN STANDARD MODEL # 2998 . 014

TOP OF SEAT AT MIN. 17'' / MAX. 19'' A.F.F.

WC-1

PLUMBING FIXTURE SPECIFICATIONS

STEEL, 3/4 HP, 120V, 1725 RPMIN-SINK-ERATOR FOOD WASTE DISPOSER # PRO333 STAINLESS

WRIST BLADE HANDLES, JUST # JB-99 1 1/2" DRAIN WITH BASKETJUST #J-1174-KS CONCEALED MIXING FAUCET WITH SPRAY HOSE, WITH

KS-2JUST MODEL # DL-1933-A-GR STAINLESS STEEL SINK 18 GA.

STRAINER, TAILPIECE AND CONTINUOUS WASTEMcGUIRE # 2165CC FLEXIBLE SUPPLIES WITH WHEEL STOPS

BREAK SINK (DOUBLE COMPARTMENT, 19"x33"x7 1/2")

EWC

HEIGHT TO 4" ABOVE SPOUT. PROVIDE APRON FOR UPPER UNIT.115V / 1~. UNIT MOUNTED WITH SPOUT AT 34" A.F.F. - ADJUST STREAM

OASIS MODEL # M8CR, FLEXIBLE BUBBLER GUARD, 8 . 0 GPM OF 50°F WATER, 1/5 H.P. COMPRESSOR, 4.6 FLA - 340 WATTS,

ELECTRIC WATER COOLERS (SPLIT-LEVEL, BARRIER FREE)

WITH VAPOR BARRIER3/8" WATER LINES TO BE INSULATED WITH MIN. 1" THICK INSULATION

FLOOR DRAIN (ROUND TOP, 3" DIAMETER OUTLET)FDJ.R. SMITH MODEL #2005 CAST IRON BODY WITH REVERSIBLE FLASHINGCOLLAR PERMITS ADJUSTMENT OF STRAINER TO MEET FINISHED FLOOR LEVEL. TRAP PRIMER CONNECTION.

HD2'' DIAMETER OPEN SITE DRAIN STUBBED UP MINIMUM 2" ABOVEFINISHED FLOOR - PROVIDE P-TRAP WITH PRIMER CONNECTION.

HUB DRAIN

JANITOR SINK (23" x 23 1/2") JS

CONSTRUCTION USING NATURAL CRUSHED STONE WITH POLYESTERRESIN. TUB TO INCLUDE INTEGRALLY MOLDED DRAIN ASSEMBLY,STOPPER, FLOOR MOUNTING HARDWARE.CHICAGO MODEL 1100-E35CP FAUCET (1.5 GPM) WITH WRIST BLADE

TAILPIECE. HOLES ON 8" CENTERS.

HBWOODFORD MODEL B67 FREEZELESS WALL HYDRANT, 3/4" MALEHOSE THREAD, BACKFLOW PREVENTER, AUTOMATIC DRAINING, HYDRANT DRAINS WHEN SHUT OFF, ENCLOSED IN A FLUSH MOUNTEDWALL BOX, WALL CLAMP AND LOOSE TEE KEY.

HOSE BIBB (NON-FREEZE)

IMOATEY MODEL 39152 ICE MAKER BOX WITH VALVE. CONTRACTORSHALL MAKE FINAL CONNECTION. PROVIDE 1/2" COLD WATER SUPPLYWITH SEPARATE ISOLATION VALVE IN BRANCH LINE. PROVIDE UNIONAT CONNECTION POINT TO REFRIGERATOR AND ENOUGH COPPERPIPE TO ALLOW REFRIGERATOR TO BE PULLED OUT FOR CLEANINGAND MAINTENANCE. INSTALL SHOCK ABSORBER ON WATER LINE.

ICE MAKER ROUGH-IN (REFRIGERATOR)

SHOCK ABSORBER

RECOMMANDED BY MANUFACTURER.JOSAM FIG. # 75001 THROUGH 75006, SIZE AS

COLD WATER LINE - PROVIDE ONE VALVE PER TRAPOR VALVES WITH DISTRIBUTION UNITS AS REQUIREDTO SERVE ALL P-TRAPS

TRAP PRIMER VALVE - INSTALL WITH COUPLING IN NEARBYPRECISION PLUMBING PRODUCTS INC. # PR-500

TP TRAP PRIMER

ECOJ.R. SMITH # 4429Y-04 WITH HEAVY DUTYCAST IRON COVER(SEE PLANS FOR SIZES)

(SEE PLANS FOR SIZES)

J.R. SMITH # 4031L-04 DUCO CAST IRON CLEANOUT WITH ROUNDADJUSTABLE SCORIATED SECURED NICKEL BRONZE TOP.

ICO

EXTERIOR CLEAN-OUT

INTERIOR CLEAN-OUT

SA

SINK WITH SEPARATE ISOLATION VALVE BELOW SINK. PROVIDE

ENTERING SIDE OF ADJACENT SINK P-TRAP.CONNECTION SIZE FLEXIBLE DRAIN LINE CONNECTED TOUNION AT CONNECTION POINT TO DISHWASHER. PROVIDE

1/2" HOT WATER SUPPLY FEED FROM BELOW ADJACENTCONTRACTOR SHALL MAKE FINAL CONNECTION. PROVIDE

DW DISHWASHER (ROUGH-IN, RESIDENTAL)

LS-1JUST # SLX-2019-A-GR 18 GA. TYPE 304, 18-8 STAINLESS STEELLAB SINK (COUNTERTOP, SINGLE COMPARTMENT, 20"x19"x 10.5")

CHICAGO # 201-AGN8AE35-317CP FAUCET, SWING GOOSENECK SPOUT,AERATOR IS LIMITED TO 1.5 GPM MAX., WRIST BLADE HANDLES.JUST # JB-99 DRAIN, # JT-200 2" O.D. P-TRAPMcGUIRE # 2165-CC FLEXIBLE SUPPLIES WITH WHEEL STOPS

LS-2 LAB SINK (COUNTERTOP, 22"x37"x12" DOUBLE COMPARTMENT)JUST # DLXD-2237-A-GR 18 GA. TYPE 304, 18-8 STAINLESS STEELCHICAGO # 201-AGN8AE35-317CP FAUCET, SWING GOOSENECK SPOUT,AERATOR IS LIMITED TO 1.5 GPM MAX., WRIST BLADE HANDLES.JUST # JB-99 DRAIN, # JT-200 2" O.D. P-TRAPMcGUIRE # 2165-CC FLEXIBLE SUPPLIES WITH WHEEL STOPS

PLUMBING EQUIPMENT SPECIFICATIONS

THERMOSTATIC MIXING VALVE

WATER HEATERWH-1 (26" DIA. x 70-5/8" TALL)STATE MODEL # SDV75 70 NE GAS WATER HEATER - 75 GALLON CAP.-81 GPH RECOVERY AT 80° F RISE - 70,000 BTU/HR NAT. GAS INPUT - PROVIDEEMERGENCY DRAIN PAN, TANK DRAIN WITH HOSE CONNECTION, 3'' DIA. GASFLUE, ASME T & P RELIEF VALVE, DIELECTRIC UNIONS AT CONNECTIONS TODISSIMILAR METALS, SHUT-OFF VALVES ON HOT & COLD WATER HEATERTO HAVE POWER DIRECT-VENT & WIRE GRILL VENT CAP. SETTEMPERATURE TO 140°

WATER DETECTOR SHUTOFFTACO "WAGS" WATER DETECTOR AND WATER & GAS SHUT-OFFVALVE. VALVE CONTROL UNIT AUTOMATICALLY SHUTS OFF WATER &GAS IF LEAK IS DETECTED

WILKINS MODEL #ZW3870T THERMOSTATIC MIXING VALVE INSTALLEDON HOT WATER OUTLETS NOT SPECIFIED TO HAVE 140° WATER.

RPBPWILKINS MODEL # 975XL BRONZE BODY - 1-1/4'' SIZE - 12 PSIG PRESSUREDROP AT 25 GPM FLOW - PROVIDE SHUT-OFF VALVES AND RELIEFPIPING WITH AIR-GAP TO SPILL TO NEAREST DRAIN

MOLDED FOLD UP SEAT, SHELVES, SOAP TRAY AND CENTER DRAINAQUARIUS MODEL # S 4136 BF ACRYLIC MOLDED CONSTRUCTION WITH

SH SHOWER ENCLOSURE (41" x 36", A.D.A. COMPLIANT)

BRADLEY MODEL S19-210X EYE/FACE WASH FIXTURE, 10" DIAMETER STAINLESS STEEL EYE WASH BOWL. CHROME-PLATED BRASS 1/2" IPSSTAY-OPEN BALL VALVE. HAND OPERATED BY A LARGE, HIGHLYVISIBLE PUSH HANDLE OR FOOT PEDAL. GALVANIZED STEEL ANDWASTE TEE WITH FLOOR FLANGE PROTECTED WITH "BRADTECT"SAFETY YELLOW COATING. 1/2" HW & 1/2" CW SUPPLY WITH MIXING VALVE.

EMERG. EYE WASH (PEDESTAL-MOUNTED, HAND OR FOOT OPERATION)EW

SYMMONS MODEL # 96-1, TEMPTROL PRESSURE-BALANCING MIXINGVALVE WITH ADJUSTABLE STOP SCREW, TUB SPOUT, LOW FLOW HEAD

1/2" WATER CONNECTION, 2" DRAIN CONNECTION1.5 GPM MAXIMUM, CLEAR-FLOW SHOWERHEAD WITH ARM AND FLANGE.

HB

CODED NOTES:

CONNECT NEW 1-1/4" COLD WATER LINE TO 3" WATERLINE BEFORE BACKFLOW PREVENTOR, BACKFLOWPREVENTION FOR OFFICES IN JANITOR'S CLOSET

SPILL CONDENSATE FROM AIR HANDLING UNITS TOFLOOR DRAIN

NEW GAS METERBY GAS UTILITYCOMPANY

SEE SITE PLAN FORCONTINUATION OF 4"SANITARY SEWER LINE

FD

EW

WH-2

EW

WH-2

ICO

FD FD FD

HB

HB

ICOICO

WH-2 - WALL MOUNTEDEEMAX ELECTRIC INSTANTANEOUS WATER HEATER - MODEL # SP42084 . 1 KW AT 208V / 1Ø - 19.7 AMPS - 0.5 GPM MAX. FLOW - INSTALL ON WALL.REFER PLANS FOR EXACT LOCATION

PLUMBING PLAN - FLUORIDE BUILDING

5'-0" 10'-0" 20'-0"

1/8" = 1'-0"

FD FD

ICO

SEE SITE PLAN FORCONTINUATION OF 4"SANITARY SEWER LINE

TP

TP

TP

TP

CONNECT TRAPPRIMER TO 2" WATERLINE SERVINGBUILDING