Solar PV Systems I , Spring 2011
Final ProjectBob McGonigle
Grid Tied Solar PV System
• Limited amount of space• High efficiency panels• Inverter limited to min startup voltage
Annual Electricity Usage 11.6 kWh
0
200
400
600
800
1000
1200
1400
1600
kWh
Month/Year
kWh Used
Solar Pathfinder Results
Big Maple TreeBig problem !!!
Facing East
Facing West
PV Watts Analysis
Buy American (ARRA) Compliant Solar Panels
Zep System IIMounting System
Calculations
MODULE INFORMATION STCVOC = 36.90 VISC = 8.91 APtolerance = +5/-3%Max fuse rating = 15 APMAX = 245 WVPMAX = 29.8 VIPMAX = 8.23 AARRAY INFORMATIONNumber of modules in series = 5Total Watts = 1225 W
OPERATING VOLTAGEVPMAX = 29.8 VNumber of modules in series = 529.8 V VPMAX x 5 = 149 Volts
OPERATING CURRENTIPMAX = 8.23 AMAXIMUM SYSTEM VOLTAGEModule Voc = 36.9 VNumber of Modules in series = 5 Lowest temp. on record = -21.7°C
(Coefficient of 1.25 from NEC 690.7)Maximum System Voltage36.9 V x 5 x 1.25 = 230.63 Volts < 600 Volts
MAX PV SOURCE CIRCUIT CURRENTISC = 8.91 A8.91 A x 1.25 = 11.4 A8.91 A x 1.56 = 13.9 A
Calculations
WIRING OVERCURRENT PROTECTION
CONDUCTOR AMPACITYFrom PV Array8.91 AISC x 1.25 = 11.14 A11.14 A x 1.25 = 13.92 A
Record High Temp. 39.4°CAmbient Temp. Adjustment for conduit exposed to sunlight on rooftops 22°CAmpacity Correction Factor = .58 CFtemp
# of wires in conduit correction factor = .80 CFconduit
13.92 A ÷ (.58 x .80) = 30 A = 12 AWG USE-2
VOLTAGE DROPVdrop = Iop x Rc x LVdrop% = Vdrop ÷ Vop
Vdrop = 8.23 A x 1.93 x .019 = 301.79 mVVdrop% = 301.79 mV ÷ 149 V = .002025 < 1%
Calculations
INVERTER KACO Blue Planet 360Ixi grid tied invertermax. continuous power at 40°CDC input voltageAC output voltage range
MINIMUM INVERTER OUTPUT CIRCUIT CONDUCTOR AMPACITYInverter continuous output rating = 3600 WMinimum Inverter Voltage = 125 VMax Operating Current = 3600 W ÷ 125 V = 28.8 AMin. Inverter Output Circuit ampacity = 28.8 A x 1.25 = 36 A
Calculations
POINT OF CONNECTIONsum of the supply breakers feeding the busbar of a panel can be up to 120% of busbar rating100 A busbar100 A main breaker100 A x 120% = 120 APV breaker = 20 A
GROUNDINGWEEB Grounding Washers (between module and rack)WEEB Grounding Lug (to rack)
ARRAYMOUNTING INFORMATIONZep System II