Bus Protection Fundamentals - Relay...

Post on 07-Feb-2018

228 views 5 download

transcript

Bus Protection Fundamentals

Terrence Smith – GE Grid Solutions

2017 Texas A&M Protective Relay Conference

High bus fault currents due to large number of circuits connected:• CT saturation often becomes a problem as the CT may not be

sufficiently rated• Large dynamic forces associated with bus faults call for fast

clearing times in order to reduce damage due to a bus fault• High incident energy/arc flash

False trip by bus protection may create serious problems:• Service interruption to a large number of customers

(distribution and sub-transmission voltage levels)• System-wide stability problems (transmission voltage levels)• With both dependability and security important, preference

is always given to security

Bus Protection Requirements

Interlocking schemes

Overcurrent (unrestrained, unbiased) differential

Overcurrent percent (restrained, biased) differential

High-Impedance schemes

Low-Impedance microprocessor-based schemes

Bus Protection Techniques

The Over-Current Problem

Downstream Fuse FS1

Phase TOC_ Upstream Relay 52-1

Phase TOC_ Downstream Relay 52-2

Phase IOC_ Upstream Relay 52-1

Phase IOC_ Downstream Relay 52-2

0 1000 2000 3000 40000

0.5

1

1.5

2

2.5

3

Fault current at 11 kV

Tim

e to

ope

rate

(s)

Gen

60 MVA11 kV

Bus1 Bus2

52-1 52-2

F60-1 F60-2

CT1 CT2F-1 F-2

F-3

Bus 3Load = 5 MVA

75 A

500 kVA11kV/.44 kV

LoadLoad Load

Load

FS1

F-4

F-2

The Over-Current Problem

The CT Problem

The CT Problem

Fault with full DC offset:

The Re-Configurable Bus Problem

NORTH BUS

SOUTH BUS

CT-8

B-5

B-6

CT-5

CT-6

S-5

S-6

B-4CT-4

S-3

S-4

B-3CT-3

S-1

S-2

B-2CT-2

CT-1

B-1

C-1 C-2 C-4

C-3 C-5

CT-7

B-7

Interlocking Schemes

• Blocking scheme typically used

• Short coordination time required

• Practically, not affected by CT saturation

• The blocking signal could be sent over communications ports

• This technique is limited to simple one-incomer distribution buses

50

50 50 50 50 50

BLO

CK

Overcurrent (unrestrained) Differential

• Differential signal formed by summation of the bus currents

• CT ratio matching may be required

• On external faults saturated CTs yield spurious differential current

• Time delay used to cope with CT saturation

• Instantaneous (unrestrained) differential OC function useful on integrated microprocessor based relays

51

Percent (restrained) Differential

• Percent characteristic used to cope with CT saturation

• Restraining signal can be formed in a number of ways

• No dedicated CTs needed

• Protection of re-configurable buses possible

87

nDIF IIII ...21

nRES IIII ...21

nRES IIII ...,,,max 21

Sloped Diff & CT Saturation Problem

diffe

rent

ial

restrainingt0

t2

Sloped Diff & CT Saturation Problem

diffe

rent

ial

restrainingt0

t2

• No need for dedicated CTs

• High Internal CT ratio compensation

• Advanced algorithms supplement the percent differential protection function making the relay very secure

• Protection of re-configurable busbars becomes easy as the dynamic bus replica (bus image) can be accomplished without switching physically secondary current circuits

• Integrated Breaker Fail (BF) function can provide optimal tripping strategy depending on the actual configuration of a busbar

• Distributed architectures replace CT wires with fiber

Low Impedance Bus Protection

High Impedance Bus Differential

High Impedance Bus Differential

Relay

CB nCB 3CB 2CB 1

I1 I2 I3 In

i1

i2

i3in

• I1 + I2 + I3 + …… + In = Id = 0 The vectorial sum of all primary currents in and out of the bus equals zero

• i1 + i2 + i3 + ……. + in = id = 0 The vectorial sum of all CT secondary currents (assuming same CT ratioand no CT saturation) in and out of the bus equals zero

• v1 +v2 + v3 + ……+ vn = vd = 0 The vectorial sum of all voltages induced on all CT secondary windingsduring normal load or external fault (no CT saturation) equals zero

vd = 0

id = 0

+ -- +

• Fast, secure and proven

• Require dedicated CTs, preferably with the same CT ratio. Cannot handle nicely inputs from CTs set on different taps.

• Input from not fully distributed CT winding creates danger for the equipment, because of inducing very high voltages – autotransformer effect

• Can be applied to small buses

• Depending on bus internal and external fault currents, they may not provide adequate settings for sensitivity and security

• Cannot be easily applied to re-configurable buses

• Require a voltage limiting varistor capable of absorbing significant energy

• Does not provide benefits of a microprocessor based relay (e.g. metering, monitoring, oscillography, breaker fail)

High Impedance Bus Protection

Thank You

Questions?