+ All Categories
Home > Documents > 04 Vibro V1000 Vs068en Englisch

04 Vibro V1000 Vs068en Englisch

Date post: 02-Mar-2016
Category:
Upload: flerasgard
View: 74 times
Download: 0 times
Share this document with a friend

of 36

Transcript
  • CV-110 / 116Measuring and Monitoringof Absolute Bearing Vibrationsusing Velocity Transducer

    VIBROCONTROL 1000Single Channel Machine Monitoring Units

  • All rights reservedNo part of this technical documentation may be reproducedwithout prior written permission of SCHENCK PROCESS GmbH.

    Subject to change without prior notice.Copyright 1996 by SCHENCK PROCESS GmbH, D-64273 Darmstadt

    Telephone (06151) 32-2952 Fax (06151) 32-1468

  • CV - 110 / 116 CONTENTS

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 1

    Contents

    1 Description ................................................................................................................................... 31.1 Block diagram...................................................................................................................... 4

    2 Technical Data ............................................................................................................................. 52.1 Ordering code for instrument type CV-110.......................................................................... 92.2 Ordering code for instrument type CV-116........................................................................ 10

    3 Commissioning.......................................................................................................................... 113.1 Installation ......................................................................................................................... 113.2 Connections for instrument type CV-110 .......................................................................... 123.3 Connections for instrument type CV-116 .......................................................................... 133.4 Alarm relay ........................................................................................................................ 16

    3.4.1 What you should know about alarm relays ........................................................ 163.4.2 Reset (acknowledging of relay messages) ........................................................ 173.4.3 Setting limit values ............................................................................................. 17

    3.5 OK relay (self-monitoring).................................................................................................. 183.6 Readiness for operation .................................................................................................... 18

    4 Explosion protection................................................................................................................. 19

    5 Service ........................................................................................................................................ 205.1 Changing settings.............................................................................................................. 205.2 Trouble shooting................................................................................................................ 22

  • CONTENTS CV - 110 / 116

    CV110/116E2 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

  • CV - 110 / 116 Description

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 3

    1 DescriptionThe vibration monitoring system VIBROCONTROL 1000 series C,comprising the electronic system and the vibration velocity transducer VS - ...

    is used for measuring and monitoring absolute bearing vibrations.The vibration transducer converts the vibrations occuring at the be-aring housing into electric signals. These electric signals are supp-lied to the measuring and monitoring electronics.The electronic system can either generate the effective value of vibration velocity (veff) or the peak value of vibration displacement (sp)comparing either of these values with 2 preset limit values. If theselimit values are exceeded the respective alarm relays are tripped.Via the potential-free relay contacts warnings (pre-alarm) or thedisconnection of the machine (master alarm) can be triggered.

    The instruments types CV-110 and CV-116 only differ in thepower supply voltage.CV-110 requires a power supply voltage of 230 V AC,CV-116 requires a power supply voltage of 24 V DC.

  • Description CV - 110 / 116

    CV110/116E4 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    1.1 Block diagram

    Figure 1 Block diagram

  • CV - 110 / 116 Technical Data

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 5

    2 Technical DataNo. of measuring channels 1

    Measuring Input designed for a vibration velocity transducer with atransmission factor of:100 mV/mm/s, fo = 8 Hz, Ri = 4 kor75 mV/mm/s, fo = 15 Hz, Ri = 2,8 k

    Input resistor Rin = 27 k without linearization100 k with linearizationThe measuring input is adapted in the factory, according to the ordering code.

    Working frequency range transducer fo = 8 Hz:10 ... 1000 Hz or 1 ... 1000 Hz (with linearization)transducer fo = 15 Hz15 ... 1000 Hz or 2 ... 1000 Hz (with linearization)determined by jumpers

    Measured variable Effective value of vibration velocity veff (mm/s) orPeak value of the vibration displacement (m)determined by jumpers

    Measuring ranges 0 ... 2 mm/s 0 ... 20 m0 ... 5 mm/s 0 ... 50 m0 ... 10 mm/s 0 ... 100 m0 ... 20 mm/s 0 ... 200 m0 ... 50 mm/s 0 ... 500 m0 ... 100 mm/s 0 ... 1000 mMeasuring ranges are changed by means ofjumpers

  • Technical Data CV - 110 / 116

    CV110/116E6 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    Analog outputs

    Number 2 - for simultanious useVoltage output 0 ... 10 V, RL 100 kCurrent output 0/4 ... 20 mA, RB 500

    Current output is changed by means of jumpersError 5 % of the measured value

    3 % of full scale10 % for the whole measuring chain, includingvibration transducer

    System connection for instrument type CV-110

    System voltage 230 V AC (196...253 V AC) 50 ... 60 Hz or115 V AC ( 96...128 V AC) 50 ... 60 Hz

    Power consumption 10 VAFuse Power supply transformer has an in built

    thermal fuse

    System connection for instrument type CV-116

    System voltage 24 V DC (18 ... 32 V DC)Power consumption 10 VAFuse F403 500 mA, 250 V, slow

    Housing

    Design Aluminium castingType of protection IP 65 as per DIN 40 050Painting RAL 7032 (grey)Dimension 220 x 120 x 90 mm (L x W x H)Weight approx. 2 kg

    Admissible ambient conditions

    Storing temperature -40 C ... + 100 CWorking temperature 0 C ... + 65 CAir humidity max 95 %, non condensing

  • CV - 110 / 116 Technical Data

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 7

    EMC

    EC directive 89/336/EWG, EMC directive92/031/EWG73/023/EWG, low voltage directive93/68/EWG

    Harmonized standards applied EN 61010, EN 61000-4-11/1994EN 50082-2, EN 61000-4-2/1995EN 55011, ENV 50141/1993EN 50081-1, EN 61000-4-4/1995

    National technical specificationsapplied VDE0160/7.6.2, VDE 877 T2

    VDE 0875/T11, VDE 877 T1VDE 0878/T22VDE 847/T4-11

    Limit values

    Number 2Setting range 10 % ... 100 % of full scaleSetting error 5 % of full scaleResponse delay limit value LIM1 (pre-alarm)

    30 ms, 1 s, 3 s, 10 s, 5 %limit value LIM2 (main alarm)30 ms, 1 s, 3 s, 10 s, 5 %response delay is changed by means of jumpers

    Switching hysteresis 3 % of full scale

    Alarm relay

    Number 2Design monostable relay, optionally

    normally de-energized or normally energized latching or non latchingdetermined by jumpers

  • Technical Data CV - 110 / 116

    CV110/116E8 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    Contact loading (ohmic load)Switching voltage AC max. 250 V, at max. 1 A

    DC max. 300 V: at max. 1 ASwitching capacity

    AC max. 250VA bei max. 1 ADC voltage dependent:

    ....................... at 300 V: P < 55 W

    ....................... at 250 V: P < 80 W

    ....................... at 24 V: P < 24 WA spark suppressor must be provided in the case of inductive load !

    Self-monitoring

    Transducer system, signal line and mains supplyare monitored as to interruption; fault messageis signalled by the OK-relay (without responsedelay).

    OK relay

    Number 1Design monostable relay, generally in normally energized

    non-latching

  • CV - 110 / 116 Technical Data

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 9

    2.1 Ordering code for instrument type CV-110

    Figure 2 Ordering code

  • Technical Data CV - 110 / 116

    CV110/116E10 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    2.2 Ordering code for instrument type CV-116

    Figure 3 Ordering code

  • CV - 110 / 116 Commissioning

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 11

    3 Commissioning

    Adhere to attached safety instructions !

    3.1 InstallationRemove housing cover and fix the base part by using 4 Phillipshead screws M6.Any installation position is accepted!Replace unused conduit threads replaced by sealed metallic pegsto ensure type protection IP 65 and EMC.

    Figure 4 Dimensions

  • Commissioning CV - 110 / 116

    CV110/116E12 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    3.2 Connections for instrument type CV-110Removal of the housing enables access to the connectionterminals.

    Figure 5 Connection terminal diagram(The relay contacts are shown in de-energized condition)

  • CV - 110 / 116 Commissioning

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 13

    3.3 Connections for instrument type CV-116Removal of the housing enables access to the connectionterminals.

    Figure 6 Connection terminal diagram(The relay contacts are shown in de-energized condition)

  • Commissioning CV - 110 / 116

    CV110/116E14 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    Note:This chapter describes the connectiion terminals of CV-110 andCV-116. Possibly necessary changes of the device setting aredescribed in the Service chapter.

    Protective conductorThe protective conductor PE of the mains supply cable must beconnected to earthing point 1 inside the housing (cf. fig. 7). Use theforked terminal which is already fixed at earthing point 1.

    EMCThe external grounding screw (cf. fig. 7) must be grounded with theshortest possible length of cable having a minimum crosssctionalarea of at least 2,5 mm2.

    Figure 7 Position of the grounding points (arrows)

  • CV - 110 / 116 Commissioning

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 15

    ScreeningAll cables connected to the electronic system must be screened!

    There are two different cases: The screen of the transducer cable must be passed through

    the PG-screwed connection and is to connect with earthingpoint 1.Use the forked terminal which is already fixed atearthing point.

    The screens of all the other cables must be connected with thecorresponding PG-screwed connection (cf. fig 8).

    Figure 8 Connecting the cable screen to the conduit thread

  • Commissioning CV - 110 / 116

    CV110/116E16 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    3.4 Alarm relayIf the limit values are exceeded the corresponding alarm relaysrespond time-delayed, via the potential-free change-over contactsby means of which a warning signal or the disconnection of themachine can be triggered.

    3.4.1 What you should know about alarm relaysTwo switching variants are possible: Normally de-energized

    If the limit values are not exceeded (OK) the coil of the relay isde-energized, however, if the limit values are exceeded (alarm)the coil is current-carrying, the relay is energized.

    Normally energizedIf the limit values are not exceeded (OK) the coil of the relay iscurrent-carrying, if the limit values are exceeded (alarm) thecoil is de-energized, the relay is released.

    The desired variant is determined by jumpers (cf. 5.1).

    Figure 9 Limit value relayThe contacts are shown in dead condition

    2 modes of operation are possible: latching non-latching

    The adjusted mode of operation is stated on the information sheetinside of the housing.

  • CV - 110 / 116 Commissioning

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 17

    3.4.2 Reset (acknowledging of relay messages)Latching alarm relays must be reset after an alarm message has been given orswitching on the monitoring electronics

    The jumper installed between terminal 14 and 15 causes a"permanent reset".If required, the jumper can be removed and be replaced by anexternal reset pushbutton which bridges the terminals 14 and 15only upon actuation of same (cf. fig.5 and 6).Connect the reset button with screened line only!

    3.4.3 Setting limit valuesThe limit values of both alarm relays are determined by means ofthe two potentiometers LIM 1 and LIM 2. The setting is performedin % related to the adjusted full scale value.

    Example:Requirement Pre-alarm at 10 mm/s

    Main alarm at 14 mm/sSetting Measuring range: 20 mm/s (= 100 %)

    Pre-alarm: Potentiometer LIM110 mm/s = 50 %Main alarm: Potentiometer LIM214 mm/s = 70 %

    Figure 10 Alarm potentiometer

  • Commissioning CV - 110 / 116

    CV110/116E18 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    3.5 OK relay (self-monitoring)By means of an integrated self-monitoring system interruptions inthe transducer system or the signal line as well as the failure ofmains voltage are signalled.The message is effected without response delay via the OK-relay.

    The OK-relay is always Normally energized and Non-latching

    Upon connection of the measuring and monitoring electronics andafter the elimination of all malfunctions the OK-relay switchesautomatically from "ALARM" to "OK" (reset is not necessary).Limit value messages are not influenced by the self-monitoringunit.

    3.6 Readiness for operationIf all connections and adjustments have been carried out properly,the mains voltage can be applied; the OK-relay is energized and isswitched to "OK".For latching alarm relays the external reset pushbutton must beactuated - no alarm signal must be available!

    During the accelleration phase the machine might reach vibrationvalues that exceed the limit values (e.g. passing the resonance).To avoid that the machine is disconnected during this phase theshut down system coupled with the monitoring electronics can beblocked until the operational speed is reached.

    Upon reaching of the working order: actuate the reset pushbutton reactivate shut-down system

  • CV - 110 / 116 Explosion protection

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 19

    4 Explosion protectionBy means of vibration monitoring system VIBROCONTROL 1000,series C, one can also monitor machines in hazardous areas.

    The electronics must be installed outside thehazardous area !!!

    When installing an explosion-proofed transducer a back-up fuse inthe measuring electronics is mandatory. If - according to the ordercode - the electronic system is designed for the connection of avibration transducer with explosion protection the required fuse willalready be integrated in the factory.Solder fuses F101, F102Explosion protection 2 x 15 mA, qiuck-blow

    Figure 11 Position of the fuses F101 and F102

    It is within the responsibility of the user to make sure that theinstallation is effected in accordance with the local regulation andthe local acceptance authorities.

    For further information please refer to the connecting diagram (fig.5 and 6) and the description of the transducer.

  • Service CV - 110 / 116

    CV110/116E20 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    5 Service

    Adhere to attached safety instructions!

    5.1 Changing settingsDe-energize the electronic system before opening thehousing!

    Basic adjustments must not be changed but by authorized servicepersonnel only !!! Unauthorized adjustments are forbidden!The adjustments of the electronic system can be changed bydifferent jumpers, which are accessable after the housing coverhas beeen removed (cf. fig. 12).The following adjustments are possible: Measured variable

    Vibration velocity Vibration displacement

    Frequency range (with/without linearization) Measuring range Mode of the alarm relays

    Normally energized or normally de- energized Latching or non-latching Delay

    Analog output current 0 ... 20 mA 4 ... 20 mA

    The measuring and monitoring electronics have been set and test-ed according to the details given in your order.The setting data are defined on insert sheet "Ordering code/devicesetting". The insert sheet is contained in the housing.If the device setting is other than standard, you will find the settingdata under the heading of "Factory setting". For your own safetyyou should write down each change of the setting data togetherwith the serial no. in the insert sheet.

  • CV - 110 / 116 Service

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 21

    Figure 12 Table of adjustment (above) and position of the jumpers (below)

  • Service CV - 110 / 116

    CV110/116E22 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    5.2 Trouble shootingIf the OK-relay signals a malfunction, proper functioning of themonitoring system cannot be guaranteed any longer.We recommend to perform the following tests:

    1. Checking voltage supplyfor instrument type CV-110

    Deenergize the instrument! required voltage at the mains terminals? Power supply transformer thermal fuse has opened?

    Wait until the power supply transformer has cooled off.If upon retrying to switch the instrument on the fuse againopens, then the instrument should be sent to an authorisedservice centre and checked.

    2. Checking voltage supplyfor instrument type CV-110

    Deenergize the instrument! required voltage at the mains terminals Power supply fuse F403 ok?

    3. Checking the transducer connection are the terminal connections of the signal line ok?

    is the terminal protective housing - if existent - installedcorrectly?

    cable fracture in the signal line or winding fracture in thetransducer?

    The self-monitoring unit only reacts if the signal circuit isinterrupted; by bridging the signal input (terminals 2 and 3) properworking order can be simulatedIf this jumper is positioned e.g. at the terminal protective housing,the source of malfunction can be determined much faster.

    The self-monitoring unit does not detect a short-circuit occured inthe transducer/transducer connection.

    However, despite the existing vibration level, the following valuescan be measured at the analog outputs:Analog output 0 ... 10 V: 0 V

    0 ... 20 mA: 0 mA4 ... 20 mA: 4 mA

    If these measures are not suited to eliminate this malfunction, theelectronic system together with the transducer have to be returnedfor repair.Further trouble shooting "on site" can be performed by authorizedservice personnel only.

  • CV - 110 / 116 Service

    CV110/116E Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98 23

    Advantages and disadvantages of 24 VDC operation with theCV-110 resp. CV-116

    24 V DC connection to CV-116

    AdvantagesThe instrument has a DC/DC converter. Therefore the potentialfreedom of the power voltage is guaranteed. This makes theanalog outputs also potential free.A further advantage is in the large tolerance range for the 24 Vpower supply (18 36 VDC)In addition, with this connection maintenance of the EMV guidelinesof the manufacturer are also guaranteed

    24 V DC connection to CV-110

    DisadvantagesUnder certain prerequisites the CV-110 can be operated with 24 VDC. When connecting the 24 V DC the following conditions mustbe met:1. For such a connection the operator must guarantee mainte-

    nance of the EMV guidelines2 The inputs and outputs are not potential-free; i.e. the 0 volt

    terminal of the analog output is always at the same potentialas the 0 V of the operating power!

    3. The tolerance range of the power supply is limited to +24 VDC -20 % +10 %

    4. Any disturbance on the 24 V power supply will directly affectthe measurement electronics

    Note:The 24 V DC input is protected by a 0,5 A fuse.

  • Service CV - 110 / 116

    CV110/116E24 Schenck VIBRO GmbH, D-64273 Darmstadt, 27.02.98

    This page has been left for your own notes.

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00 1

    Vibration Velocity Sensors

    VS - 068 / 069 / 077 / 079

    1 ApplicationSCHENCK vibration velocity sensors operate in accordance withthe electrodynamic principle and are used for measuring the bea-ring absolute vibration of machines.

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E2 SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00

    1.1 Connection Diagram

    1.2 PolarityWith the illustrated direction of movement of the bearing shell, apositive polarity signal is produced at the white wire of the cable.

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00 3

    2 Technical Data

    2.1 General DataSensor cable Teflon cable; PTFE (C)

    2 x 0,38 mm2; shieldedLength 5 m; wire ends: open

    Extension of the sensor connecting cableto a max. of 200 m is possible(wiht a terminal box)

    Housing stainless steel; hermetically sealedFixing Central mounting by means of stud

    M10 x 25; DIN 914; A2Fmax. tightening torque 87 Nm

    Protective classas per DIN 40 050 IP 66Weight of sensor without cable approx. 500 gEMC EN 50082-2: 1995 Pkt. 1.1, 1.2, 1.4, 2.1, 2.2

    EN 50081-2: 1994 Pkt. 1.1, 1.2

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E4 SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00

    2.2 Technical data for VS-068 and VS-069Measuring parameter Vibration velocityMeasuring principle electrodynamic

    Sensitivity E at f = 80 Hz E mVmm s

    xR

    k RL

    L=

    +

    1004/

    Typical frequency response and sensitivity

    Internal impedance 4 k 5 %Transverse sensitivity 7 %Natural frequency fo 8 Hz 10 %Operating temperature range -40 ... + 80 C (short-term max. + 100 C)Max. admissible vibration displacement 0,45 mmCable protection Flexible steel protective hose encased

    with PU material

    Magnetic field sensitivity < 0 0301, /

    ,

    mm s

    mT

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00 5

    2.3 Technical data for VS-077Measuring parameter Vibration velocityMeasuring principle electrodynamic

    Sensitivity E at f = 80 Hz E mVmm s

    xRL

    k RL=

    +

    753/

    Typical frequency response and sensitivity

    Internal impedance 3 k 5 %Transverse sensitivity 5 %Natural frequency fo 15 Hz 2 %Operating temperature range -40 ... + 80 CMax. admissible vibration displacement 1 mmCable protection Flexible steel protective hose encased

    with PU material

    Magnetic field sensitivity < 0 02401

    , /,

    mm s

    mT

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E6 SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00

    2.4 Technical data for VS-079Measuring parameter Vibration velocityMeasuring principle electrodynamic

    Sensitivity E at f = 80 Hz E mVmm s

    xRL

    k RL=

    +

    703/

    Typical frequency response and sensitivity

    Internal impedance 3 k 5 %Transverse sensitivity 6 %Natural frequency fo 15 Hz 5 %Operating temperature range -40 ... + 200 CMax. admissible vibration displacement 1 mmCable protection Rust-free stainless-steel, not encased

    Magnetic field sensitivity < 0 02401

    , /,

    mm s

    mT

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00 7

    3 Mounting

    3.1 Attaching the sensor

    The following applies on principle: Mounting surface flat and clean, i.e. without paint, rust etc Threaded stud perpendicular to mounting surface; the trans-

    ducer must be tightened to the mounting surface Secure stud with LOCTITE

    (e.g. LOCTITE 243 medium-duty, LOCTITE 270 heavy-duty) Avoid auxiliary fixtures for mounting;if unavoidable, the fixture

    should be as rigid as possible For protection against mechanical damage and for increase

    EMC safety the connection cable should be laid in flexible steelprotective conduit. Bending radius rmin = 50 mm

    Tighten transducer directly to mounting surfaceMax. tightening torque 87 Nm

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E8 SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00

    3.2 Preparing the steel protective conduitAdapt the steel protective conduit to the site conditions by takingthe following steps: If the protective conduit has a braided shield, to ensure a clean

    cut through the braided wrap a strip of metallised adhesivetape around the area where the cut is to be made beforestarting the cut.

    Cut the protective conduit with a suitable cutting tool, e.g.metal saw, cutting disc.

    De-burr the cut end.

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00 9

    3.3 Mounting steel protective hose at VS-068 / 069 / 077

    To achleve the optimum shielding performance of AC-331according VDE 0245 and DIN 47250 part 4, the protectiveconduit with connector should be assembled as follows:

    Cut protective conduit to appropriate length (see 3.2). Disassemble connector and slide pressure screw (long

    version) over the conduit. Slide sealing ring over the conduit with tapered edge facing the

    pressure screw. Uncover the outer jacket of the conduit with care leaving a

    section as long as 1.5 x the width of the brass-thrust collar. Cut copper shield with scissors flush with the conduit. Slide brass-thrust collar (with taper side as shown) over the

    conduit as illustrated above. Screw brass ferrule into the conduit until it stops. Assemble the rest of the individual components and tighten so

    that the O-ring is not movable. For liquid-tight installations install the additional O-ring at the

    connector thread side.

  • VS - 06x / 07x DATA SHEET

    VS068-69-77-79E10 SCHENCK VIBRO GmbH, D-64273 Darmstadt, 19.10.00

    3.4 Fixing steel protective conduit at VS-079

    Cut protective conduit to appropriate length (see 3.2) Slide the union nut and sealing ring on steel protective hose

    behind the cutting point Screw the inner tube onto the steel protective conduit Slide steel protective hose slide over transducer cable and fix

    protective hose joint to the transducer and the steel protectivehose

    Adjust sensor cable length to suit and ansulate Solder screen onto transducer cable; protect soldering joint by

    means of shrink tubing and rubber bushing Fix end sleeves to cable ends

    CV-110 / 116Contents1 Description1.1 Block diagram

    2 Technical DataAnalog outputsSystem connection for instrumentAdmissible ambient conditionsLimit valuesAlarm relayContact loading (ohmic load)Self-monitoring2.1 Ordering code for instrument type CV-1102.2 Ordering code for instrument type CV-116

    3 Commissioning3.1 Installation3.2 Connections for instrument type CV-1103.3 Connections for instrument type CV-116Protective conductorScreening

    3.4 Alarm relay3.4.1 What you should know about alarm relays3.4.2 Reset (acknowledging of relay messages)3.4.3 Setting limit values

    3.5 OK relay (self-monitoring)3.6 Readiness for operation

    4 Explosion protection5 Service5.1 Changing settings5.2 Trouble shooting24 V DC connection to CV-11624 V DC connection to CV-110

    v06x07xe.pdfVS - 06x Vibration Velocity Sensors1 Application1.1 Connection Diagram1.2 Polarity

    2 Technical Data2.1 General Data2.2 Technical data for VS-068 and VS-0692.3 Technical data for VS-0772.4 Technical data for VS-079

    3 Mounting3.1 Attaching the sensor3.2 Preparing the steel protective conduit3.3 Mounting steel protective hose at VS-068 / 069 / 0773.4 Fixing steel protective conduit at VS-079


Recommended