+ All Categories
Home > Documents > 050131-Power Factor Correction

050131-Power Factor Correction

Date post: 07-Apr-2018
Category:
Upload: fedilino-p-fornolles
View: 233 times
Download: 13 times
Share this document with a friend

of 26

Transcript
  • 8/3/2019 050131-Power Factor Correction

    1/26

    Power Factor CorrectionPower Factor Correction

    Save Money and Energy

    Presented by:Alan L. OQuinn, P.E.

    Team Power Solutions, LLC

    [email protected]

    (404) 213-8368

  • 8/3/2019 050131-Power Factor Correction

    2/26

    What is Power Factor

    Correction?

    Usually adding capacitance to PowerSystem.

    Ideal power factor is 1.0

    Typical industrial complex is 0.65 0.8 pf.

  • 8/3/2019 050131-Power Factor Correction

    3/26

    How Do You Get Low PF?

    Motor loads are inductive and need VARs.

    R

    M => L

  • 8/3/2019 050131-Power Factor Correction

    4/26

    Whats Wrong With Low PF?

    Wastes Power Overloads Equipment

    Costs Money Uses Up Natural Resources

  • 8/3/2019 050131-Power Factor Correction

    5/26

    Complex Power

    Apparent Power = S = P + j Q VA

    Real Power = P = | V | | I | cos () W

    Reactive Power = Q = | V | | I | sin () VAR

    Power Factor = PF = cos ()

  • 8/3/2019 050131-Power Factor Correction

    6/26

    Single Phase Power

    I = kVA / kV = kW / (kV PF)

    kVA = kV I

    kW = kVA PF

  • 8/3/2019 050131-Power Factor Correction

    7/26

    Three Phase Power

    I = kVA / ( kV 1.732 ) = kW / (kV 1.732 PF)

    kVA = kV 1.732 I

    kW = kVA PF

    Note: kV is the phase-to-phase voltage

  • 8/3/2019 050131-Power Factor Correction

    8/26

    Power Triangle

    KVA

    KVAR

    KW

  • 8/3/2019 050131-Power Factor Correction

    9/26

    Classic PF Example

    Facility has peak demand of 1000 kW Load Power Factor is 0.707 lagging

    Calculate kVAR. Calculate amount of capacitance in kVAR

    needed to correct to a 0.9 PF

    How much is capacitance in microfarads?

  • 8/3/2019 050131-Power Factor Correction

    10/26

    Draw Power Triangle

    KVA = 1000/0.707 = 1414

    = acos(0.707) = 45o

    KVAR =

    sqrt (1414^2 1000^2)

    = 1000

    KW = 1000

  • 8/3/2019 050131-Power Factor Correction

    11/26

    Graphical Representation of PowerPF = 0.707

    -400

    -200

    0

    200

    400

    600

    800

    1000

    0 0.005 0.01 0.015 0.02

    Time

    Po

    wer

    Real Reactive Apparent

  • 8/3/2019 050131-Power Factor Correction

    12/26

    PF Example Continued Slide 1 of 4

    KVAR =sqrt (1111^2 1000^2)

    = 484

    KVA = 1000/0.9 = 1111

    = acos(0.9) = 25.8o

    KW = 1000

    Added kVAR = 1000 - 484 = 516

  • 8/3/2019 050131-Power Factor Correction

    13/26

    Comparison

    KVAR = 1000

    KVAR = 484

    KW = 1000

    Added kVAR = 1000 - 484 = 516

  • 8/3/2019 050131-Power Factor Correction

    14/26

    Graphical Representation of PowerPF = 0.9

    -300

    -200-100

    0

    100

    200

    300

    400

    500

    600

    700

    800

    0 0.005 0.01 0.015 0.02

    Time

    Po

    wer

    Real Reactive Apparent

  • 8/3/2019 050131-Power Factor Correction

    15/26

    PF Example Continued Slide 2 of 4

    C = ( kVAR 103

    ) / (2 f ) (kV)2

    = ( 500 103 ) / (2 60 ) (0.480)2

    = 5,759 microfarads

    Note: 480 volts was the assumed voltage.

  • 8/3/2019 050131-Power Factor Correction

    16/26

    PF Example Continued Slide 3 of 4

    Load

    1000 kW

    0.707 pf

    A

    B

    M

    UtilitySource

    C

    Meter reads 0.9 pf

  • 8/3/2019 050131-Power Factor Correction

    17/26

    PF Example Continued Slide 4 of 4

    What is the reduction in amps supplied by the utility?

    kVA before was 1414

    kVA after pf correction is 1111

    Reduced kVA is 303 kVA

    Reduced amps is 303 / ( 0.480 1.732 ) = 364 amps

  • 8/3/2019 050131-Power Factor Correction

    18/26

    Benefits

    Reduced I2

    R losses Less voltage drop. VLN = I Zeq

    Reduced conductor size. Possible reduce substation transformer size.

    ProvidesVoltage support

  • 8/3/2019 050131-Power Factor Correction

    19/26

    Harmonics

    Multiple of the fundamental frequencydistortions. 5th = 300 Hz, 7th = 420 Hz

    Created by non-linear devices such as UPS

    systems, rectifiers, VFDs, welders,

    fluorescent ballasts, personal computers

    IEEE 519-1992

  • 8/3/2019 050131-Power Factor Correction

    20/26

    5th Harmonic Distortion

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    0 2 4 6 8 10 12

    Fundamental 5th Harmonic Total

  • 8/3/2019 050131-Power Factor Correction

    21/26

    5th, 7th, 11th 13th Harmonics

    -1.5

    -1

    -0.5

    0

    0.5

    1

    1.5

    0 1 2 3 4 5 6

    Total Fundamental

  • 8/3/2019 050131-Power Factor Correction

    22/26

    Harmonic Resonance

    Occurs when capacitance reactance andsystem reactance are equal.

    Large currents circulate between

    transformer and capacitor. Higher voltages may occur across

    equipment.

    Usually 5th, 7th, 11th, and 13th are thefrequencies of most concern

  • 8/3/2019 050131-Power Factor Correction

    23/26

    Systems Harmonic ResonancePrevious Example: 1500 kVA Transformer, %Z = 5.75

    500 kVAR of Capacitance

    Harmonic Order = h = sqrt( kVASC/ kVAR )

    kVASC = kVA / (%Z/100) = 1500 = 1500/0.0575 = 26,087

    h = sqrt (26,087 / 500 ) = 7.22

  • 8/3/2019 050131-Power Factor Correction

    24/26

    Load has 5th, 7th, 11th and 13th Harmonics each with 10%Current Distortion

    Easy Power Model

  • 8/3/2019 050131-Power Factor Correction

    25/26

    1 . 0 2 . 2 3 . 4 4 . 6 5 . 8 7 . 0 8 . 2 9 . 4 1 0 . 6 1 1 . 8 1 3 . 0

    0 . 0 0

    1 5 . 0 0

    3 0 . 0 0

    4 5 . 0 0

    6 0 . 0 0

    7 5 . 0 0

    9 0 . 0 0

    1 0 5 . 0 0

    1 2 0 . 0 0

    1 3 5 . 0 0

    1 5 0 . 0 0

    F re q ue n c y S c a n - In j e c t io n o n B U S - 2

    H a r m o n i c

    ZpuM

    agnitude

    B U S - 2

  • 8/3/2019 050131-Power Factor Correction

    26/26

    Documented Sources GE Corporation, GE Low Voltage Power Factor Correction Capacitors GEP-974-G,

    2003 Su, Kendall L. Fundamentals of Circuit Analysis, Waveland Press, 1993

    Matthes, John H. Introduction to the Design and Analysis of Building Electrical

    Systems. Van Nostrand Reinhold, 1993


Recommended