1.45 Gas & Oil Systems
2.30 Electric Heating
3.00 Heat Pumps
3.15 Solar Thermal & PV
3.25 Green Deal
3.30 Roundup and questions
3.45 Close
Boiler (the heat source)
Cylinder (to store the hot water)
Boiler programmer or timer (to turn the hot water
and heating system on automatically)
Room thermostat (to control the temperature of
the house)
Radiators (to heat the room)
Sealed heating system
No open water tanks in the loft
“Condensing” Boiler ◦ All boilers are now “condensing”
◦ Recovers some heat from the flue
Piped natural gas, oil, LPG
Produces hot water on demand
Good points:
◦ Water heated only when needed
◦ Don’t need a cylinder
Bad points ◦ May not deliver hot water quickly enough
◦ Cannot feed both heating and hot water at the same
time
◦ More sensitive to mains water pressure
Hot water stored in a tank
Some people like an airing cupboard
Good points: ◦ Can use a lot of water at once
Bad points ◦ Cylinder takes up space
◦ Heat loss from cylinder
It’s a fire!
Gas jets enter a sealed chamber where they are
ignited
Fire heats a pipe containing cold water
Heats water up to about 60 degrees
Pipe is part of a pipe system that goes round the
whole house through the radiators
Boiler may be on but not producing heat
A radiator is: ◦ Copper pipe bent back and forth 10 to 20 times
◦ Surrounded by steel to protect and make bigger
surface area
Either on or off
Cannot be set to different temperatures
Valves will either let water through or not
When warm will give off heat into room as room
is cooler
We have a boiler
We have a pipe system
We have radiators
So we have a hot house!
We need control over the system: ◦ Thermostatic Radiator Valves
◦ Boiler programmer
◦ Room Thermostat
Radiator still on or off
But now you have more control
Set the TRV to a temp level you want
When the room is cooler the valve opens ◦ Hot water goes through the radiator
When room reaches temperature the valve closes
◦ Radiator will cool down as no more hot water going
through
Doesn’t stop the boiler running
Could be separate or built into the boiler
For a combi boiler sets:
◦ when boiler is on for heating
For other types of boiler sets: ◦ When boiler is on for heating
◦ When boiler is on for hot water
Set the times that the boiler is on
Programme this to suit your lifestyle
Overall control of the boiler for heating
Takes the temperature in one room
Won’t have a TRV in that room
When the boiler is turned on RT decides if the
boiler needs to produce heat
Calls for heat
Can be digital, programmable
Setting a higher temperature does not increase
the speed that the house will heat up!
The boiler produces the heat
The boiler programmer turns the boiler on and
off
The room thermostat calls for heat
The radiators distribute the heat
The TRV will allow the room temperature to be
set comfortably
Replaces boiler programmer & room stat
Does the job of both
May be able to programme a range of
temperatures, eg: ◦ 7am = 20o
◦ 9am = 15o
◦ 4pm = 20o
◦ 9pm = 13o
There is a lot of debate and opinion on this
Our recommendation is…
Don’t leave it on permanently
Set programmer to go off 30mins before you go
out
If you want the house warm to come home to,
set it to come on 20mins before you expect to
arrive home (but this will cost you)
Only have heating on when you need it
Use the boiler programmer
Change the programmer the night before for the
next day
Lower the temperature of the room thermostat –
reduce calls for heat
Use the TRVs to set each room’s temperature
Reduce the temperature of the water in the
heating system on the boiler
Do you have windows open with heating on?
Do you leave the door open when you go to the
car, garden etc?
Close curtains when it gets dark to keep heat in
With a combi boiler just open the hot tap a little
until the water gets hot, then open it as much as
you need. Saves gas and water
Don’t leave an electric immersion heater on all the
time, especially if you have a gas boiler
Lifestyle will affects costs
Can change your lifestyle to lower your costs – if
you want to
Heating System FAQs
My radiator isn’t warm ◦ Is the gas on?
◦ Is the electricity on? Systems needs electricity
◦ Is there money on the meter (if pre-payment)
◦ Is the boiler programmer turning the heating on?
◦ Is the room thermostat set high enough to call for
heat?
◦ Is the TRV set too low?
◦ Is the room warm enough? May be that the radiator
doesn’t need to be on.
Some rooms are too hot, some too cold ◦ Adjust the TRVs so that each room is the right
temperature
◦ Don’t leave windows open
No hot water ◦ Is the gas on?
◦ Is the electricity on?
◦ Is there money on the meter (if pre-payment)
◦ With a hot water tank - is the boiler programmer
turning the hot water on?
Electricity distribution is really, really technical
UK electricity at roughly 240 volts
Volts x Amps = Watts
So a 2400w hairdryer will be working at 10 amps
If you have a 3 amp fuse in a plug the most
power that will go through is 720w
1000w is a kilowatt (kw)
If you use 1kw for one hour you have used one
kilowatt hour (1kWh)
Electricity supplier measures your usage by kWh
10kW electric shower running for 15 minutes
uses 2.5kWh
Three main types:
Normal
◦ same rate throughout the day & night eg EDF £0.1271
Economy 7 ◦ At night cheaper than “normal”: EDF £0.0522
◦ Daytime more expensive than “normal”: EDF £0.1512
Economy 10 ◦ As Economy 7
◦ Extra few hours during the day at cheap rate
Hundreds of tariffs – don’t be on a standard one!
Two main types
Storage
◦ Night storage heaters
On Demand ◦ Panel heaters
◦ Convector heaters, hot air fans
◦ Electric fires
Only one company makes these
Different types:
◦ Manual control
◦ Automatic controls
◦ Built in fan
Common sizes ◦ 0.8kW
◦ 1.6kW
◦ 2.6kW
◦ 3.4kW
Insulated box
Filled with special bricks
Bricks heated up by electricity during the night
Release heat during the night and day
The heat will come out during the day
Most of the heat comes from the metal box
Some control over how quickly it comes out
Often not enough heat left in the evening
Power rating refers to how much electricity will
go in per hour
So a 3.4kW NSH can cost:
◦ 3.4kW x 7 hours = 23.8kWh
◦ On EDF E7 tariff = 23.8 x £0.0522 = £1.24 per day
Input control ◦ Controls how much electricity goes into the heater
how much it will cost to run
how much heat there will be to come out the next day
◦ A thermostat inside the heater turns off the incoming
electricity when they reach a set temperature
Output control ◦ Opens & closes flap on top of heater
◦ More open equals warmer
◦ More open will lose heat faster
Input control ◦ Increase the input as the weather gets colder
◦ Decrease the input as the weather gets warmer
◦ Check the forecast every night and increase or reduce
the input
◦ Don’t want to be opening windows to reduce room
temperature the next day
◦ Well insulated properties less susceptible to variation
Output control
◦ Turn it right down when you go out and at night
◦ Open it as little as is comfortable
Setting them up
Set the input control to mid position
If the next day is not warm enough increase the
input control
Leave as is if the forecast says the next day will
be warmer
Input Control ◦ Input is controlled by a room thermostat
◦ Try different settings to decide which is most
comfortable during the day
◦ Set to the click point then adjust up or down
◦ Don’t need to change the setting when the weather
changes
◦ If you use a top-up heater late into the night may affect
the thermostat
Output Control ◦ Thermostatically controlled
◦ Opens or closes flap to maintain temperature
◦ Doesn’t account for how much heat is in the heater
◦ Reduce temperature when you go out & at night
Heat generation
◦ Heat pumps
◦ Solar thermal water heating
◦ Micro CHP
◦ Biomass boiler
Electricity generation
◦ Photovoltaic
◦ Hydro electric
◦ Wind
Heat pumps ◦ Air source
◦ Ground source
◦ Exhaust air
Ground source more efficient
Air source more cost effective to install
Exhaust air not as efficient, not widely used
Ground source ◦ Gets heat from the ground
◦ A borehole up to 100m deep
◦ A long pipe with a liquid that picks up heat
Air source (air to water) ◦ Gets heat from the air
◦ Outside fan unit
◦ Sucks air across a radiator
Exhaust air ◦ Reclaims heat produced in the property
◦ Mainly from kitchen & bathroom
◦ Residents need to generate heat
3 types connect to a normal radiator system
Radiators will probably need to be bigger
Produces heat more efficiently than hot water
Will be cheaper than electric heating & immersion
heater
About 2000 installed by Advantage SW Members
Will be contacting them about satisfaction
NOT free heating & hot water
Basically a big fridge in reverse
For every 1kw electricity that goes in, about
2.5kw heat & hot water comes out
So ◦ More efficient than electrical heating
◦ Cheaper to run than electrical heating
◦ Probably not cheaper to run than gas
Keep the heat pump on all the time
Call for heat controlled by room thermostat
The higher the heat required, the lower the
efficiency
Radiators shouldn’t be hot – just warm
Keep the room temperature as low as is
comfortable
Keep the hot water temperature as low as is
comfortable
If hot water used throughout the day leave keep
the hot water on during the day
If used at specific times eg breakfast & evening
programme on for those times
The controls are not user-friendly
New product has friendlier controls
Explanatory video at www.advantagesw.co.uk
Uses roof collectors to heat stored water
Does not need to be immediately used
Generally needs a hot water tank
Generally only heats hot water, not heating
Liquid within the collectors absorbs the heat from the sun and is fed into a water cylinder
Heat is transferred by a heat exchanger to the domestic hot water supply
The cooler liquid is returned to the collector for reheating
If there is not enough solar radiation then the boiler will top up the heat
Tenant’s savings depend on ◦ How much hot water they use
◦ Whether they have an electric shower
◦ Roof orientation
◦ Less susceptible than PV to shading problems
Income to Landlord ◦ Renewable Heat Incentive – uncertain
Value for money? Not great: ◦ Doesn’t provide all hot water
◦ Doesn’t help heating
Need to use electricity immediately or
Sell unused electricity to the national grid
Has been expensive but prices coming down
Income to landlord from Feed in Tariffs
Feed in Tariffs cut from 43p per kWh to 14p
No desire from landlords to pursue PV at the
moment
Enough sunlight hits the Earth every day to
satisfy our power requirements for 27 years
Sun hits the Modules, convert energy to power
Modules on the roof give a DC output
Inverter converts DC to AC at 240v
Connects to fusebox
Peak time is between 11am & 2pm
If the tenant is home can use the electricity
produced
Tenant benefits from lower electricity bills
Savings dependent on how much of the
generated electricity the tenant can use
May be Feed in Tariff income to the landlord
Output will be affected by ◦ Location – south west best in England
◦ Amount of light
◦ Orientation – facing south is best
◦ Roof angle
◦ Shading – will affect all panels, not just those shaded
Each kWp will generate about 900kWh pa
For 2 kWp peak system
◦ Will cost about £3,500
◦ 12 square metres
◦ Output 1800kWh p.a.
◦ Feed in tariff of £250 pa
◦ Energy saving of up to £180 pa
For private sector and social housing
Landlord / Leaseholder will need to give consent
Upgrade property fabric & heating equipment
Make savings on energy bill
The upgrades will cost less than the savings
Loan is against the electricity meter
Future residents will continue to pay off the loan
Landlords currently working on their consent
policies