PRESENTATION TITLE PRESENTER DATE Seminar 25 Wire-to-Air Fan Power Performance and Energy Consumption 2017 Winter Conference Tim Mathson, Principal Eng. Greenheck Fan Corp [email protected] Measurement of Fan Component Efficiencies Las Vegas, Nevada Currently with AMCA Int’l [email protected]
Transcript
Page 1: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Seminar 25Wire-to-Air Fan Power Performance

and Energy Consumption

2017 Winter Conference

Tim Mathson, Principal Eng.Greenheck Fan Corp

[email protected]

Measurement of Fan Component Efficiencies

Las Vegas, Nevada

Currently with AMCA Int’[email protected]

Page 2: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Learning Objectives• Estimate fan system energy consumption at part load

conditions• Describe difference between direct-on-line and variable

frequency driven motor performance • Identify variables that impact the efficiency of drive system

components• Illustrate the interdependence of individual drive system

components on overall fan efficiency

ASHRAE is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported to ASHRAE Records for

AIA members. Certificates of Completion for non-AIA members are available on request.

This program is registered with the AIA/ASHRAE for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement

by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product. Questions related to specific materials,

methods, and services will be addressed at the conclusion of this presentation.

Page 3: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Acknowledgements

• Baldor Engineering staff• ABB Engineering staff• Chris Eiden, Greenheck

Page 4: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

VFD Electrical Loss

Agenda - Overall Energy Efficiency

Useful Output Power

Aerodynamic Loss

Bearing Friction

Loss

V-BeltFrictionLoss

Motor Electrical

Loss

Input Power

Additional Motor Loss

ηoverall =Output PowerInput Power

= ηfan × ηtrans× ηmtr × ηvfd

Page 5: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

VFD Electrical Loss

Motor/VFD Efficiency

Electrical Power Input

Additional Loss from VFD

Motor Electrical

Loss

Mechanical Power Output

𝜂𝜂𝑚𝑚,𝑣𝑣 ≠ 𝜂𝜂𝑚𝑚𝑚𝑚𝑚𝑚 × 𝜂𝜂𝑣𝑣𝑣𝑣𝑣𝑣

Page 6: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Scope of Testing

Motors - Premium Efficient Induction1, 5, 10 hp (.75, 4, 7.5 kW), 4 Pole, TEFC, 460V 60Hz

VFD’s - General Purpose IGBT for HVAC1, 5, 10 hp (.75, 4, 7.5 kW), Constant V/Hz, 4 kHz Carrier Frequency

V-Belt drivesSpeeds 1200, 1800, 2700 RPMService Factors 1.0, 1.5, 2.0, 3.0, 4.0Number of belts

Fan - 27” (685mm) Mixed FlowBelt or dynamometer driven

Page 7: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Motor Test SetupLoad Motor

Torque/SpeedTransducer

Test Motor

Power Meter

Page 8: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – Full Load Motor Efficiency, X-Line

Motor

NEMA Premium Nominal

Measuredwith 60 Hz Line Power

Differencefrom

Nominal

1 hp 85.5 84.3 -1.2

5 hp 89.5 88.0 -1.5

10 hp 91.7 91.5 -0.2

Page 9: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – Part Load Motor Efficiency, X-Line

50% Load1 hp -4.7%5 hp -1.8%10 hp -0.3%

Page 10: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Motor & VFD Test Setup – AHRI 1210Load Motor

Torque/SpeedTransducer

Test Motor

Power Meter VFD

Page 11: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – Motor & VFD at Full Load

Motor

Motor AloneWith 60 Hz Line Power

CombinedMotor & VFD

@ 60 Hz

1 hp 84.3 82.4

5 hp 88.0 87.0

10 hp 91.5 89.7

Page 12: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Motor & VFD - Part Load Operation

Motor Selection Options

1–4

1 3

24

Page 13: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – 10 hp Motor & VFD at Part Load

1

234

Com

bine

d VF

D &

Mot

or E

ffici

ency

(%)

Page 14: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – 10 hp Motor & VFD at Part Load

1

2

3 4

Com

bine

d VF

D &

Mot

or E

ffic

ienc

y (%

)

Page 15: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – 10 hp Motor & VFD at Part Load

12

3

4

Efficiency vs. PowerRegardless of how the motor was originally selected (cases 1-4), these curves lined up very well. Any prediction of motor/VFD efficiency at partial loads should be related to percent nameplate power.

Com

bine

d VF

D &

Mot

or E

ffici

ency

(%)

Page 16: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – 10 hp Motor & VFD at Part LoadCo

mbi

ned

VFD

& M

otor

Effi

cien

cy (%

)

Page 17: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – 5 hp Motor & VFD at Part LoadCo

mbi

ned

VFD

& M

otor

Effi

cien

cy (%

)

Page 18: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – 1 hp Motor & VFD at Part LoadCo

mbi

ned

VFD

& M

otor

Effi

cien

cy (%

)

Page 19: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – Motor & VFD at Part Load

1 hp

10 hp

50% Load1 hp -5%5 hp -2%10 hp -1%

50% Speed1 hp -26%5 hp -14%10 hp -11%

5 hp

VFD

& M

otor

Effi

cien

cy (%

)Co

mbi

ned

VFD

& M

otor

Effi

cien

cy (%

)

Page 20: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results vs. AMCA 207 Prediction

1 hp

10 hp

5 hp

“AMCA 207 is Conservative”

Page 21: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Load MotorTorque/RPM Transducer

Test Motor

Belt Drive Test SetupLoad Motor

Torque/RPM Transducer Jackshaft

Tested Motor

Force Transducer

V-be

lt Dr

ive

Power Meter VFD

Page 22: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Belt Drive Efficiency – AMCA 203

AMCA 203Appendix L

Page 23: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Belt Drive Efficiency – AMCA 203

Remove Test Points

AMCA 203 Losses converted to Efficiencies

Range of Drive Efficiencies for Standard Belts

Page 24: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Belt Drive EfficiencyMotor HP DriveN RPM # Belts SF

1 HP

27001 1.5

2 3

18001 1.5

2 3

12001 1.5

2 3

5 HP

27001 1.5

2 3

18001 2

2 4

12001 1

2 2

10 HP

2700 2 1.5

1800 2 1.5

1200 2 1.5

Full Load Eff.

94

90

96

90

96

92

96

93

98

96

97

95

97

98

99

Experimental Variables:

1. BHP2. RPM3. Service Factor

Page 25: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – Belt Drive at Full Load

Page 26: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – Belt Drive at Part Load

Page 27: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Results – Belt Drive at Part Load

Page 28: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Fan Efficiency - 27” (685mm) Mixed Flow

AMCA 210/ASHRAE 51 Test, Figure 12, Installation Type BExtended fan shaft allows Dynamometer or Motor driven

Page 29: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Fan Curve at Constant Speed

Dynamometer Driven,Corrected to 1840 RPM

Ps

BHP

SE

Airflow (CFM)

Page 30: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Fixed System Resistance

Dynamometer Driven,Fixed System Resistance

Ps

BHP

SE

Airflow (CFM)

Page 31: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Variable Speed TestDynamometer Driven,Fixed System Resistance,Tested at Reduced Speeds

6% Drop at 30% Speed

Ps

BHP

SE

Airflow (CFM)

Page 32: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Fan Curve at Constant Speed

VFD / Motor / Belt DrivenCorrected to 1840 RPM

Ps

kW

OSE

Airflow (CFM)

Page 33: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Fixed System Resistance

VFD / Motor / Belt DrivenFixed System Resistance

PskW

OSE

Airflow (CFM)

Page 34: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Variable Speed TestVFD / Motor / Belt Driven,Fixed System Resistance,Tested at Reduced Speeds

35% Drop at 18 Hz

14% Drop at 30 Hz

PskW

OSE

Airflow (CFM)

Page 35: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Overall Fan Static Efficiency

ηoverall =Output PowerInput Power

= ηfan × ηtrans× ηmtr × ηvfd

Page 36: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

AMCA 207 Estimates

ηoverall =Output PowerInput Power

= ηfan × ηtrans× ηmtr × ηvfd

Page 37: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

ConclusionsComponent Efficiencies:• Motor efficiency is a function of load and is typically available

from motor manufacturers• Motor/VFD efficiency is a function of load (power), regardless of

torque or speed• AMCA 203 V-belt drive loss estimates are reasonable, even at

decreased fan speeds • AMCA 207 is conservative, for belt drive and Motor/VFD

efficiencies • Fan efficiency drops slightly with speed• Largest losses at part load are from Motor/VFD

Overall Efficiency:• ηoverall = ηfan × ηtrans× ηmtr × ηvfd

Page 38: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

Bibliography

• AMCA 203 “Field Performance Measurement of Fan Systems”

• Draft AMCA 207 “Fan System Efficiency and Fan System Input Power Calculation”

Page 39: 2017 Winter Conference of Fan... · 2019. 11. 11. · • AMCA 203 V-belt drive loss estimates are reasonable, even at decreased fan speeds • AMCA 207 is conservative, for belt

PRESENTATION TITLEPRESENTER

DATE

QUESTIONS?