NECITR-YTC ART-SEP/03 V02 PNMT 1 PNMT - GENERAL PASOLINK NETWORK MANAGEMENT TERMINAL (PNMT) IS A MOBILE TERMINAL CONSISTING OF A PORTABLE COMPUTER WITH A SIMPLIFIED VERSION OF THE PASOLINK NETWORK MANAGEMENT SOFTWARE DEVELOPED FOR MANAGEMENT OF NEC PASOLINK SERIES SHORT HAUL RADIO TRANSMISSION NETWORK. PNMT IS DESIGNED AS AN ONSITE MAINTENANCE TOOL TO BE USED BY THE FIELD ENGINEERS AND TECHNICIANS. IT CONNECTS DIRECTLY TO THE LA PORT OF THE PASOLINK IDU. PNMT CAN BE USED TO MONITOR LOCAL / REMOTE EQUIPMENT STATUS AND PROVIDES CONTROL CAPABILITIES SIMILAR TO THOSE AVAILABLE IN PNMS. PNMT IS ALSO USED TO DOWN LOAD THE SYSTEM AND CONFIGURATION FILES TO THE PM CARD AND UPGRADE THE SOFTWARE IN THE IDU WHEN CONNECTED TO AN IDU PNMT CAN MONITOR NOT ONLY THE LOCAL EQUIPMENT BUT ANY REMOTE NETWORK ELEMENT UNDER THE CONTROL OF THE CENTRAL PM CARD. TO USE THE PNMT, PM CARD SHOULD BE MOUNTED IN THE IDUs.
Transcript
Page 1: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 1

PNMT - GENERALPASOLINK NETWORK MANAGEMENT TERMINAL (PNMT) IS A MOBILE TERMINAL CONSISTING OF A PORTABLE COMPUTER WITH A SIMPLIFIED VERSION OF THE PASOLINK NETWORK MANAGEMENT SOFTWARE DEVELOPED FOR MANAGEMENT OF NEC PASOLINK SERIES SHORT HAUL RADIO TRANSMISSION NETWORK.

PNMT IS DESIGNED AS AN ONSITE MAINTENANCE TOOL TO BE USED BY THE FIELD ENGINEERS AND TECHNICIANS. IT CONNECTS DIRECTLY TO THE LA PORT OF THE PASOLINK IDU. PNMT CAN BE USED TO MONITOR LOCAL / REMOTE EQUIPMENT STATUS AND PROVIDES CONTROL CAPABILITIES SIMILAR TO THOSE AVAILABLE IN PNMS.

PNMT IS ALSO USED TO DOWN LOAD THE SYSTEM AND CONFIGURATION FILES TO THE PM CARD AND UPGRADE THE SOFTWARE IN THE IDU

WHEN CONNECTED TO AN IDU PNMT CAN MONITOR NOT ONLY THE LOCAL EQUIPMENT BUT ANY REMOTE NETWORK ELEMENT UNDER THE CONTROL OF THE CENTRAL PM CARD.

TO USE THE PNMT, PM CARD SHOULD BE MOUNTED IN THE IDUs.

Page 2: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 2

FUNCTIONS

MICROSOFT WINDOWS 98/NT/200/XP WORKSTATION GRAPHICAL USER INTERFACE

ONE HOP LINK DISPLAY ON THE PNMT SCREEN

COLLECTS ALARM AND STATUS INFORMATION FROM THE LOCAL AND REMOTE PM CARDS

COMMUNICATE WITH REMOTE PM CARDS ON THE SAME NETWORK

TRANSMISSION EQUIPMENT CONTROL VIA LOCAL AND REMOTE PM CARDS

SEVERAL LEVELS OF LOGIN / LOGOUT

EVENT LOGGING WINDOW

PERFORMANCE MONITORING FUNCTION WINDOW

LOCAL / REMOTE EQUIPMENT CONTROL FUNCTION

LOCAL/REMOTE PM CARD CONFIGURATION MANAGEMENT

LOCAL/REMOTE UP GRADING OF APPLICATION SOFTWARE

Page 3: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 3

PNMT COMMUNICATION INTERFACECOMMUNICATION BETWEEN THE PNMT AND THE RADIO NETWORK EQUIPMENT CAN BE :

VIA THE LA PORT OF THE LOCAL PASOLINK EQUIPMENT

VIA THE DIGITAL SERVICE CHANNEL DSC TO A REMOTE PASOLINK EQUIPMENT

LA PORT IS LOCATED ON THE FRONT OF THE EQUIPMENT AND CONSISTS OF A DB15 CONNECTOR. LA PORT CONNECT THE PM CARD IN THE IDU VIA A SERIAL CABLE TO THE RELEVANT COMMUNICATION PORT OF THE PNMT COMPUTER.

PROPERTIES OF THE LA PORT ARE AS FOLLOWS:

PORT CONFIGURATION RS-232

CONNECTOR TYPE D-SUB 15 (FEMALE)

BITS PER SECOND RATE UP TO 19200

LA PORT

Page 4: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 4

HARDWARE/SOFTWARE CONFIGURATION

RECOMMENDED PNMT MOBILE PC CONFIGURATION

LAPTOP PC WITH TFT DISPLAY (IBM COMPATIBLE)

CPU: PENTIUM-400 OR HIGHERRAM: 128 MB OR MOREHDD: 2 GB OR MOREFDD: 3.5INCHCD-ROM: 8 x OR HIGHERINTEGRATED SOUND CARD AND SPEAKER

OPERATING SYSTEM

WINDOWS XP (ENGLISH VERSION) WITH SP1 OR HIGHER

WINDOWS 98 (ENGLISH VERSION)WINDOWS NT WORKSTATION Ver 4.0 (ENGLISH VERSION) WITH SP 6.0 OR HIGHERWINDOWS 2000 (ENGLISH VERSION) WITH SP3 OR HIGHER

ALL STRUCTURED AND MODULAR PROGRAMS USED IN PNMT ARE RESIDENT IN THE HARD-DISK AND RAM OF THE PERSONAL COMPUTER. THE WINDOWS OPERATING SYSTEM IS EMPLOYED WHICH IS CAPABLE OF MULTITASK PROCESSING. THE PNMT SOFTWARE BASICALLY CONSISTS OF TWO PARTS, THE OPERATING SYSTEM AND THE APPLICATION PROGRAM

SOFTWARE CONFIGURATION

APPLICATION PROGRAMNEC PNMT SOFTWAREIE 5.0 OR HIGHERACROBAT READER

Page 5: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 5

START UP

AFTER CONNECTING TO THE PASOLINK EQUIPMENT TRIES TO ACQUIRE DATA FROM THE LOCAL EQUIPMENT AND THE REMOTE EQUIPMENT TO DISPLAY ON THE LINK SUMMARY WINDOW

DOUBLE CLICK ON THE PNMT SHORTCUT ICON ON THE DESKTOP OR CLICK ON START>>PROGRAM>>PNMT>>PNMT

PNMT PROGRAM STARTUP AND TRIES TO GET CONNECTED TO PASOLINK EQUIPMENT USING THE DIAL-UP CONNECTION “PNMT”

CONNECT THE PNMT PC COM1 PORT AND THE PASOLINK IDU LA PORT USING A RS232C CABLE

From the Control Panel select Phone and Modem Options. Add a Standard 19200 bps Modem and assign it to the COM1 port ( or the COM port to be used)

Create a Dial-up connection using the above standard modem and name it as “pnmt”

PREPARATION

Install the NEC PNMT software

See PNMT Install Manual for details

Page 6: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 6

SHUT DOWN

IN THE DIALOG BOX THAT OPENS CLICK YES

TO EXIT THE PNMT PROGRAM CLICK ON EXIT IN THE SYSTEM DROPDOWN MENU AND CLICK YES.

THE SCREEN INDICATES NOW PNMT SHUTDOWN. IT WILL TAKE FEW MINUTES TO SHUTDOWN

IF YOU HAVE NOT LOGIN FIRST THE EXIT MENU CANNOT BE SELECTED.

Page 7: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 7

PNMT MAIN SCREEN

PNMT WINDOW

MENU BAR

LINK SUMMARY WINDOW

COMMON TOOL BAR

NE-SPECIFIC MENU ITEMS

NE-SPECIFIC DATA

TAB SELECTION FOR OTHER EQUIPMENT VIEWS

BLOCK DIAGRAM

PNMT MAIN SCREEN IS SPLIT EVENLY TO DISPLAY THE DATA FROM THE TWO NEs IN THE HOP.

CLICK ON THE ARROW ICONS IN THE MIDDLE OF THE SCREEN TO EXPAND THE LEFT OR RIGHT DATA FIELD. CLICKING ON THE BLOCK WILL RETURN THE ORIGINAL SPLIT SCREEN.

Page 8: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 8

PNMT MAIN SCREEN

COMMON MENU BAR

COMMON TOOL BAR

NE SPECIFIC DATA :

TRANSMIT ATTENUATION

NE SPECIFIC MENU ITEMS:

EQUIPMENT CONFIGURATION

LINK PERFORMANCE MONITOREVENT LOG

MAINTENANCE

NE BLOCK DIAGRAM:

STATUS OF EACH MAIN UNIT IN THE PASOLINK EQUIPMENT (ODU, IDU, AUX I/P AND PMC) ARE SHOWN IN THE BLOCK DIAGRAM AS SYMBOLS. WHEN ANY SYMBOL IS CLICKED THE RELATED EQUIPMENT WINDOW OPEN AND SHOWS THE DETAILS OF ALARM AND STATUS DETAILS AND OTHER PARAMETERS,

LINK SUMMARY WINDOW SHOWS THE SELECTED NETWORK ELEMENT (NE) AND ITS OPPOSITE NE AS A LINK (HOP). THE SELECTED NE IS SHOWN ON THE LEFT HAND SIDE WINDOW AND THE OPPOSITE NE ON THE RIGHT HAND SIDE WINDOW OF THE LINK SUMMARY WINDOW. IT SHOWS GRAPHICALLY THE STATUS OF THE PASOLINK EQUIPMENT IN BLOCK DIAGRAM FORM. NE-SPECIFIC PARAMETERS AND NE-SPECIFIC MENU ITEMS ARE ALSO SHOWN IN THIS WINDOW

LINK SUMMARY WINDOW

COMMON TOOL BAR OF THE PNMT WINDOW HOLDS THE ICONS OF THE FREQUENTLY USED MENU ITEMS

COMMON MENU BAR OF THE PNMT WINDOW PRESENTS THE SYSTEM AND HELP MENU ITEMS. EACH MENU ITEM HAVE A DROP DOWN MENU SHOWING THE OPTIONS AVAILABLE.

NE SPECIFIC DATA ARE SHOWN IN SEVERAL DATA WINDOWS SELECTED BY THE TABS AT THE BOTTOM OF THE WINDOW OR BY CLICKING THE EQUIPMENT SYMBOLS IN THE BLOCK DIAGRAM. DATA DISPLAYED DEPENDS ON THE EQUIPMENT TYPE (PASOLINK +, V3, V4, ETC.)

EQUIPMENT SETUP

TAB SELECTION

DETAILED MONITORING STATUS AND ALARMS OF EACH MAIN UNIT IN THE PASOLINK EQUIPMENT (ODU, IDU, AUX I/P AND PMC) CAN BE VIEWED BY CLICKING ON THE RELEVANT TAB.

Page 9: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 9

PNMT WINDOW MENU ITEMS

SYSTEM HELP

LOGIN / LOGOUT

CHANGE PASSWORD

ALARM BUZZER

CONNECT

EXIT

DISPLAY A LIST OF PNMT MANUALS IN PDF FILE FORMAT

THIS FUNCTION OPEN THE LOGIN/LOGOUT WINDOW TO ENTER THE USER NAME AND PASSWORD.

THIS FUNCTION OPEN THE PASSWORD CHANGE WINDOW

THIS FUNCTION IS USED TO ENABLE/DISABLE THE BUZZER FUNCTION AND DEFINE THE BUZZER SOUND

THIS FUNCTION IS USED TO DISPLAY THE SUMMARY LIST OF THE NETWORK ELEMENTS IN THE NETWORK

THIS FUNCTION IS USED TO CLOSE THE PNMT PROGRAM

HELP

ABOUT DISPLAY THE PNMT VERSION NUMBER

REFRESH

THIS FUNCTION ENABLES PNMT TO ACQUIRE ALL STATUS MANUALLY AND TO UPDATE EQUIPMENT INFORMATION

Page 10: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 10

NE SPECIFIC MENU ITEMSCONFIGURATION EVENT LOG

EQUIPMENT SETUP

MAINTENANCE

MAINT MODE ON/OFF

TX MUTE ON/OFF

CW ON/OFF

THIS FUNCTION UPLOAD THE EVENT LOG INFORMATION FROM THE SELECTED NE AND DISPLAY THE INFORMATION IN EVENT LOG WINDOW

THIS FUNCTION OPEN THE G826 LINK PERFORMANCE INFORMATION WINDOW.

LINK PERFORMANCE MONITOR

BER AIS ON/OFF

SWITCHOVER (1+1)

FREQUENCY SETTING

TX POWER CONT

LAN SETTING

FRAME ID

BER THRESHOLD

AIS SEND ON/OFF

AIS RCVD ON/OFF

SC4 & SC5 SETTING

NE NAME

NOTE

BIT RATE

SYSTEM CONFIG

Page 11: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 11

PNMT LOGIN / LOGOUT & EXIT

CLICK ON SYSTEM IN THE MENU BAR AND THEN CLICK ON LOGIN/LOGOUT IN THE DROP DOWN MENU TO OPEN THE LOGIN/LOGOUT WINDOW

ENTER THE USER NAME ACCORDING TO THE PRIVILEGES AND THE PASSWORD.

CLICK OK TO LOGIN

TO PROTECT THE NETWORK AND NETWORK MANAGEMENT SYSTEM FROM UNAUTHORIZED ACCESS OR MODIFICATIONS, FIVE LEVELS OF USERS ARE DEFINED WITH DIFFERENT PRIVILEGES. THE FUNCTIONS AVAILABLE DEPENDS ON THE USER ACCESS LEVEL, (SEE THE TABLE NEXT PAGE)

TO LOGOUT SELECT LOGOUT IN THE LOGIN/LOGOUT WINDOW AND CLICK OK.

TO LOGIN SELECT LOGIN IN THE LOGIN/LOGOUT WINDOW.

Page 12: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 12

USER NAMES & PRIVILEGESCategory Item Monitor(0) User(1) Local(2) Remote(3) Admin(4)

MENU-SYSTEM DATE TIME

ALARM BUZZER

DOWNLOAD PMC PROGRAM FILE

CONNECT (REMOTE LOGIN)

MENU-CONFIGURATION FILE DOWNLOAD FILE/ UPLOAD FILE

UPDATE

IDU WS ALARM INHIBIT (OPTION)

CH (LB1) / CH(LB2)

CH (ALARM INHIBIT)

MAINTENANCE MAINTENANCE MODE

TX MUTE

CW

BER AIS

SWITCH OVER (1+1)

EQUIPMENT CONFIGURATION FREQUENCY PLAN (CH)

TX ATTENUATION

BIT RATE

FRAME ID

BER THRESHOLD

AIS RCVD ALARM ON/OFF

AIS SEND ALARM ON/OFF

SC4 AND SC5

PASOLINK NAME

NOTE

AUX I/O OPTO ITEM TYPE

OPTO NAME

RELAY NAME

RELAY CONTROL

PMON PMON THRESHOLD

PMON DATA RESET

SAVE TO DISK

LOGGING SAVE TO DISK

PMC RESET

Page 13: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 13

OVERALL WINDOW

CLICK THE OVERALL TAB TO DISPLAY THE OVERALL WINDOW

OVERALL WINDOW FOR (1+1) CONFIGURATION

OVERALL WINDOW FOR (1+0) CONFIGURATION

TX ATTENUATION USED

TX AND RX FREQUENCIES USED

BIT RATE USED

MAINTENANCE MODE ON OR OFF STATUS. IF ON, BACK GROUND COLOR CHANGE TO YELLOW.

SELECTED TX AND RX CHANNEL IN (1+1) HOT STANDBY CONFIGURATION

FRAME ID USED

OVERALL WINDOW DISPLAY THE FOLLOWING INFORMATION:

ODU TYPE USED V3 OR V4

TX POWER CONTROL USED

Page 14: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 14

ODU WINDOWCLICK THE ODU SYMBOL IN THE BLOCK DIAGRAM TO OPEN THE ODU WINDOW TO VIEW THE ODU DETAILS

ODU WINDOW FOR (1+1) CONFIGURATION ODU WINDOW FOR (1+0) CONFIGURATION

CLICK THE ODU TAB TO OPEN THE ODU WINDOW TO VIEW THE ODU DETAILS

Page 15: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 15

ODU DETAIL

STATUS COLORSGREEN NORMALRED ALARM

(1+1) CONFIGURATION SELECTED/NOT SELECTED STATUSGREEN SELECTEDWHITE NOT SELECTED

IF INPUT – IF INPUT LEVEL IN THE ODU FALLS BELOW (APPROXIMATELY) -63 dB

TX APC – ODU TX SIDE SYNTHESIZER IS UNLOCKED

TX POWER – TRANSMIT POWER DECREASED BY 3 TO 5 dB

TX ATTENUATION – INDICATES THE ATTENUATION VALUE USED IN MTPC MODE

TX POWER – INDICATES THE ODU TRANSMIT POWER AS DETECTOR VOLTAGE AND IN dBm

ALARMS

STATUS AND MONITORING

RX LEVEL – ODU RECEIVE LEVEL FALLS BELOW SQUELCH LEVEL

RX APC – ODU RX SIDE SYNTHESIZER IS UNLOCKED

ALARMS

RX LEVEL – INDICATES THE ODU RX LEVEL AS THE AGC VOLTAGE AND IN dBmSTATUS AND MONITORING

ODU-IDU LINK – INDICATES THE STATUS OF THE COMMUNICATION BETWEEN IDU AND ODUALARMS

ODU TYPE – INDICATES THE TYPE OF ODU CONNECTED TO THE V4 PASOLINK

STATUS AND MONITORING

TX SIDE ALARMS AND STATUS /MONITORING

RX SIDE ALARMS AND STATUS /MONITORING

COMMON ALARMS AND STATUS /MONITORING

Page 16: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 16

IDU WINDOWCLICK THE IDU SYMBOL IN THE BLOCK DIAGRAM TO OPEN THE IDU WINDOW TO VIEW THE IDU DETAILS

IDU WINDOW FOR (1+1) CONFIGURATIONIDU WINDOW FOR (1+0) CONFIGURATION

CLICK THE IDU TAB TO OPEN THE IDU WINDOW TO VIEW THE IDU DETAILS

Page 17: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 17

IDU DETAIL

(1+1) CONFIGURATION ON LINE SELECTED/NOT SELECTED STATUSGREEN SELECTEDWHITE NOT SELECTED

MOD – MODULATOR 850 MHz PLL OSCILLATOR UNLOCK ALARM

TX DPU – LOSS OF TX SIDE CLOCK

TX SIDE IDU ALARMS

STATUS COLORSGREEN NORMALRED ALARM

DEM – RX CARRIER NOT SYNCHRONIZED OR LOST

LOW BER – WHEN THE RECEIVE BER IS > 10-6

HIGH BER – WHEN THE RECEIVE BER IS >10-3

RX SIDE IDU ALARMS

BER ALARM – ALARM TRIGGER POINT SELECTABLE (10-3,10-4,10-5 AND 10-6)FRAME ASYNC – LOSS OF RX FRAME SYNCHRONIZATION AT THE RX DPU

ODU-IDU LINK – STATUS OF THE ODU-IDU IF LINK

IDU COMMON ALARMS

CPU – STATUS OF THE IDU CPU

INPUT – LOSS OF WS INPUT SIGNAL IN THE WS INTFC CARDWAY SIDE( OPTION) ALARMS

BP OUTPUT – RX WS SIGNAL LOSS FROM DEMODULATOR (WS INTFC CARD)

AIS SEND – STATUS AIS SENT OUT FORM THE WS INTFC CARDAIS RECEIVED – AIS DETECTED IN WS INPUT SIGNALALARM INHIBIT – WHEN WS SIGNAL IS NOT USED ALARM INHIBIT STATUS

PINK MINOR ALARM

RX CLK LOSS – LOSS OF RX SIDE CLOCK

LAN INTFC – LAN INTERFACE OPTION CARD IS NORMAL OR FAULTY

LAN INTFC (OPTION) ALARMS

LAN LINK – LAN PORT 1 & 2 LINK STATUS NORMAL OR ALARMNormalNormal

NormalNormal

Normal

Port 1 Port 2

LAN COLLISION – COLLISION STATUS OF THE LAN PORT 1 & 2

Page 18: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 18

IDU DETAIL

INPUT – LOSS OF 2MB INPUT SIGNAL2MB CH STATUS AND ALARMS

BP OUTPUT – RX 2MB SIGNAL LOSS DETECTED FROM DEMODULATOR

AIS SEND – AIS SENT OUT STATUS FORM THE 2MB INTFC CARD

AIS RECEIVED – AIS DETECTED STATUS IN 2MB INPUT SIGNAL

LB-1– UNDER MAINTENANCE MODE NEAR END LOOPBACK STATUS

NORMAL/SENDNORMAL/RECEIVEDON/OFF

NORMAL/ALARMNORMAL/ALARM/INHIBIT

ON/OFF

ON/OFF

LB-2 – UNDER MAINTENANCE MODE, TO FAR END LOOPBACK STATUS

ALARM INHIBIT – ALARM INHIBIT STATUS OF NOT USED 2MB STREAMS

CLICK THE CH BUTTON TO OPEN THE CHANNEL CONTROL WINDOW

STATUS COLORSGREEN NORMALRED ALARM

YELLOW MAINTENANCE

LOOPBACK 2 CONTROLLOOPBACK 1 CONTROL

CH ALARM INHIBIT CONTROL

BP OUTPUT – RX 2MB SIGNAL LOSS DETECTED FROM DEMODULATOR

ALARM INHIBITOFFWS

WS CH STATUS AND ALARMSINPUT – LOSS OF 2MB WS INPUT SIGNALBP OUTPUT – RX 2MB WS SIGNAL LOSS DETECTED FROM DEMODULATORAIS SEND – AIS SENT OUT STATUS FORM THE WS INTFC CARDAIS RECEIVED – AIS DETECTED STATUS IN WS INPUT SIGNALALARM INHIBIT – ALARM INHIBIT STATUS OF NOT USED 2MB STREAMS

Page 19: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 19

CHANNEL CONTROL

LB1 TAB PROVIDES NEAR END LOOPBACK. SELECT ON OR OFF AND CLICK ON EXECUTE TO ENABLE NEAR END LOOPBACK ON THE SELECTED CHANNEL. BEFORE ENABLING LOOPBACK SELECT MAINTENANCE MODE ON. OTHERWISE AN ERROR MESSAGE. IS DISPLAYED

IN THE IDU WINDOW CLICK ON THE CH # TO BE CONTROLLED. SELECTED CHANNEL CONTROL WINDOW OPENS

LB2 TAB PROVIDES FAR END LOOPBACK. SELECT ON OR OFF AND CLICK ON EXECUTE TO ENABLE FAR END LOOPBACK ON THE SELECTED CHANNEL..

ALARM TAB PROVIDES INHIBIT OF ALARM ON THE SELECTED CHANNEL. USED TO INHIBIT ALARMS FROM THE UNUSED 2 MB CHANNELS.

ON – INHIBIT ALARMS

OFF - ENABLE ALARMS

CLICK EXECUTE TO SELECT THE CHANGE

INDICATE LOOPBACK ON, YELLOW BACKGROUND INDICATE MAINTENANCE MODE

INDICATE CHANNEL ALARMS INHIBIT ON

INDICATE CHANNEL ALARMS INHIBIT ON

Page 20: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 20

CHANGE PASSWORD

ENTER THE NEW PASSWORD

CLICK OK TO CHANGE THE PASSWORD.

CLICK ON CHANGE PASSWORD IN THE SYSTEM DROPDOWN MENU TO OPEN THE CHANGE PASS WORD WINDOW.

ENTER THE OLD PASSWORD

RE-ENTER THE NEW PASSWORD TO CONFIRM

CLICK CANCEL TO EXIT WITHOUT CHANGING PASSWORD

Page 21: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 21

ALARM BUZZERCLICK ON ALARM BUZZER ON THE SYSTEM DROP DOWN MENU TO OPEN THE ALARM BUZZER SETTING WINDOW.

SELECT WAVE FILE TO ENABLE THE BUZZER. THE BUZZER SOUND CAN BE CHANGED BY SELECTING A DIFFERENT WAV FILE. USE BROWSE TO LOCATE THE PATH TO THE WAV FILE.

SELECT NO SOUND TO DISABLE THE BUZZER

CLICK HERE TO TEST THE BUZZER SOUND

BEEP FREQUENCY CAN BE DEFINED BY CLICKING ON EDIT AND SELECTING THE FREQUENCIES AND DURATION FOR EACH FREQUENCY. CLICK THE ARROW KEY TO ADD TO THE LIST. SEVERAL FREQUENCIES CAN BE ADDED TO THE BEEP SIGNAL. SELECTED FREQUENCIES CAN BE DELETED BY SELECTING THE FREQUENCY FROM THE LIST AND CLICKING ON THE DELETE SYMBOL.

SELECT BEEP TO ENABLE THE BUZZER WITH BEEP FREQUENCIES INSTEAD OF WAVE FILE SOUND

CLICK OK TO IMPLEMENT THE OPTION SELECTED OR CLICK CANCEL TO EXIT WITHOUT CHANGING THE SETTINGS.

Page 22: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 22

SEARCH / CONNECT TO NETWORK ELEMENT

CLICK THE SEARCH FOR NETWORK ELEMENT TO SEARCH AND LIST THE OTHER NEs IN THE NETWORK

CLICK CONNECT ON THE SYSTEM DROP DOWN MENU TO LIST THE LOCAL NEs THE PNMT IS CONNECTED TO.

TO VIEW A REMOTE NE FROM THE NETWORK ELEMENT LIST, SELECT AND HIGHLIGHT THE NE IN THE LIST. THEN CLICK THE CONNECT TO NETWORK ELEMENT FROM THE LIST DROP DOWN MENU. SELECT YES FROM THE DIALOG BOX. THE SELECTED NE AND ITS OPPOSITE NE WILL BE DISPLAYED IN THE LINK SUMMARY WINDOW.

SEARCH FOR NETWORK ELEMENT

CONNECT TO NETWORK ELEMENT

TOOL BAR ITEMS

LIST MENU

Page 23: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 23

HELP FUNCTION

OPEN THE LOGIN/LOGOUT WINDOW

CONNECT - OPEN THE NE LIST WINDOW

BUZZER STOP – ICON IS ACTIVE ONLY WHEN THE, THE ALARMED EQUIPMENT DISPLAY WINDOW IS SELECTED FROM THE TABs OR FROM THE BLOCK DIAGRAM SYMBOLS.

DISPLAY THE PNMT SOFTWARE VERSION INFORMATION

PNMT HELP FUNCTION IS AVAILABLE AS PNMT MANUAL IN PDF FILE FORMAT. IF THE ACROBAT READER IS INSTALLED IN THE PNMT PC, CLICKING HELP AND SELECTING THE RELEVANT PNMT FILE WILL OPEN THE PDF FILE TO PROVIDE HELP FUNCTION TO THE USER.

REFRESH – REFRESH METERING ITEMS

Page 24: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 24

EQUIPMENT CONFIGURATION WINDOW

SHOW THE TYPE AND NUMBER OF OPTIONAL INTERFACE CARDS MOUNTED

INDICATES THE ODU FREQUENCY BAND INFORMATION AND TX/RX FREQUENCIES

SHOW THE LAN SIGNAL STATUS FOR PORT1 AND PORT2, WHEN MAIN LAN INTFC OPTION IS USED

SHOW THE CURRENT IDU CONFIGURATION

INDICATES THE TX POWER CONTROL MODE AND TX ATT

SHOW THE SERVICE CHANNEL INFORMATION

SHOW IP ADDRESS AND NAME OF THE SELECTED NE

SHOW THE WS CHANNEL INFORMATION

Page 25: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 25

FREQUENCY AND POWER SETTING

CLICK ON THE FREQUENCY PLAN BUTTON TO SELECT THE ODU TX AND RX FREQUENCIES.

CLICK THE EXECUTE BUTTON TO CHANGE THE FREQUENCIES. THIS OPERATION WILL INTERRUPT THE TRAFFIC

REFER TO THE RADIO FREQUENCY ASSIGNMENT TABLES TO SELECT THE CHANNEL NUMBER CORRESPONDING TO THE REQUIRED TRANSMIT AND RECEIVE FREQUENCIES.

SELECT THE CHANNEL NUMBER AND THE CORRESPONDING TX AND RX FREQUENCIES FOR THE SELECTED CHANNEL. ARE DISPLAYED

CLICK THE CLOSE BUTTON TO EXIT THE FREQUENCY PLAN WINDOW.

CLICK ON THE TX ATTENUATION BUTTON TO SET THE TX ATTENUATION FOR MTPC.

SELECT THE AMOUNT OF ATTENUATION REQUIRED AND CLICK THE EXECUTE BUTTON.

THE TX ATTENUATION RANGE OF ODU IS 0 TO 30 dB

CLICK CLOSE TO EXIT THE TX ATTENUATION SETTING WINDOW.

INFORMATION ABOUT THE ODU FREQUENCY BAND ARE DISPLAYED

ODU SECTION OF THE EQUIPMENT SETUP WINDOW FOR THE SELECTED PASOLINK HAS THREE CONTROLS, FREQUENCY PLAN , TX ATTENUATION AND TX POWER CONTROL SETTING.

IN THE CASE OF (1+1) HOT STANDBY CONFIGURATION, FREQUENCY IS SET FOR BOTH ODUs.

This information may include :

TX frequency used is High band or Low band Frequency Sub band used A, B, C, or D. Default Channel and TX frequency set in the ODU. CH Separation shift frequency

Page 26: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 26

ATPC SETTING

IN ALL SETTING WINDOWS, CLICK CLOSE TO EXIT THE WINDOW

AFTER SELECTING OR SETTING THE PARAMETER CLICK EXECUTE BUTTON TO IMPLEMENT THE SETTING.

AUTOMATIC TX POWER MAX AND MIN RANGE

ATPC RANGE DEFINES THE MAXIMUM AND MINIMUM TRANSMISSION POWER DURING ATPC OPERATION. IN MTPC MODE THIS MENU ITEM DOES NOT APPEAR.

IF THE MAXIMUM OUTPUT POWER OF THE ODU IS +20 DBM, THEN FOR AN ATPC MAX PWR SETTING OF 0DB AND ATPC MIN PWR SETTING OF -10DB, THE ODU OUTPUT POWER DURING ATPC OPERATION CAN VARY BETWEEN +20 DBM AND +10 DBM

RX THRESHOLD LEVELWHEN THE MONITORED RX SIGNAL LEVEL FALLS BELOW THIS LEVEL, CONTROL SIGNAL SENT TO THE OPPOSITE STATION INITIATE THE ATPC FUNCTION.

CLICK THE APPROPRIATE BUTTON TO OPEN THE SELECTED SETTING WINDOW..

VALUE SET IS THE ATTENUATION IN dB FROM MAX ODU POWER.

THIS IS EFFECTIVE ONLY WHEN THE OPPOSITE STATION IS SET TO ATPC MODE

TX POWER CONTROLSELECTS THE TX POWER CONTROL MODE ATPC OR MTPC. WHEN ATPC IS SELECTED, “ATPC RX THRESHOLD” , ”ATPC MAX POWER” AND “ATPC MIN POWER” BUTTONS ARE ACTIVE. WHEN TX CONTROL MODE IS CHANGED

FROM ATPC TO MTPC, THE TX ATTENUATION SETTING IS AUTOMATICALLY SET TO THE ATPC MAX POWER SETTING VALUE.

WHEN TC CONTROL MODE IS ATPC, TX ATTENUATION SETTING VALUE IS IGNORED

Page 27: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 27

IDU SETTINGIDU SECTION OF THE EQUIPMENT SETUP WINDOW FOR THE SELECTED PASOLINK HAS CONTROL SETTINGS FOR THE MAIN SIGNAL.

CLICK BIT RATE BUTTON TO OPEN THE BIT RATE SETTING WINDOW. THIS FUNCTION APPLIES TO THE VARIABLE BIT RATE IDUs. SELECT THE BIT RATE AND CLICK THE EXECUTE BUTTON TO CHANGE THE BIT RATE SETTING..

CLICK REDUNDANCY BUTTON TO OPEN THE REDUNDANCY CONFIGURATION SETTING WINDOW. SELECT THE REQUIRED CONFIGURATION. CLICK ON THE EXECUTE BUTTON TO SET THE REDUNDANCY CONFIGURATION.

MAKE SURE THAT BOTH NEs IN THE HOP HAVE THE SAME FRAME ID VALUE.

CLICK BER THRESHOLD BUTTON TO OPEN THE BER THRESHOLD SETTING WINDOW. SELECT THE DESIRED VALUE FOR THE BER THRESHOLD. CLICK ON THE EXECUTE BUTTON TO SET THE BER THRESHOLD VALUE.

BIT RATE SETTING

REDUNDANCYBER THRESHOLD SETTING

AT THIS BER THRESHOLD VALUE AIS SIGNAL IS INSERTED TO THE 2MB STREAMS

FRAME ID

CLICK FRAME ID BUTTON TO OPEN THE FRAME ID SETTING WINDOW.

SELECT THE FRAME ID AND CLICK ON THE EXECUTE BUTTON TO SET IT.

Page 28: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 28

AIS SEND / RCVD SETTINGIN THE PASOLINK SYSTEM WHEN AIS IS DETECTED FROM THE INPUT 2MB STREAM AIS RCVD CONDITION IS DECLARED. THIS CONDITION CAN BE DEFINED AS AN ALARM CONDITION OR STATUS CHANGE EVENT. SIMILARLY AIS IS SENT TO THE 2MB STREAM IN THE RECEIVE DIRECTION UNDER CERTAIN CONDITIONS. AIS SEND CAN ALSO BE DEFINED AS AN ALARM CONDITION OR STATUS CHANGE EVENT.

SELECT AIS RECEIVED CONDITION AS AN ALARM CONDITION OR STATUS CONDITION.

CLICK EXECUTE TO CARRY OUT THE SETTING.

CLICK CLOSE TO EXIT

SELECT AIS SEND CONDITION AS AN ALARM CONDITION OR STATUS CONDITION.

CLICK EXECUTE TO CARRY OUT THE SETTING.

CLICK CLOSE TO EXIT

CLICK AIS RCVD BUTTON TO OPEN THE AIS RCVD SETTING WINDOW.CLICK AIS SEND BUTTON TO OPEN THE

AIS SEND SETTING WINDOW.

Page 29: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 29

SERVICE CHANNEL SETTING

OVERHEAD SERVICE CHANNELS

SC1 EOW Analog

SC2 DSC3 Analog ASC INTFC orDSC INTFC

OptionSC3 DSC4 Digital Option

SC4 DSC1 Digital 9.6Kbps RS 232C or64Kbps with G703/V11 card Option

SC5 DSC2 Digital 9.6Kbps RS232C / RS422 / RS485

SC6 NMS

64K V.11 64K G703 9.6K RS-232

SC4

SC4

SC4 AS A DEFAULT USE A 9.6K RS232 INTERFACE. IF THE OPTIONAL 64K INTERFACE CARDS ARE MOUNTED. THEN THE SC4 BUTTON IS ACTIVE TO SELECT EITHER 9.6 OR 64K. INTERFACE

SERVICE CHANNELS USED IN THE PASOLINK IS SHOWN ON THE TABLE. SC2 AND 3 NEEDS OPTIONAL ANALOG OR DIGITAL SERVICE CHANNEL INTERFACE CARD.

WHEN OPTIONAL 64K INTERFACE IS MOUNTED THIS BUTTON IS ACTIVE.. CLICK ON SC4 BUTTON TO OPEN THE SC4 SETTING WINDOW.

SELECT THE REQUIRED OPTION AND CLICK EXECUTE.

CLICK ON SC5 BUTTON TO OPEN THE SC5 SETTING WINDOW.

CLICK CLOSE TO EXIT THE WINDOW

OPTION PANEL STATUS SHOWS THE OPTION CARDS MOUNTED IN THE IDU.

Page 30: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 30

PMC CARD SETTINGTHE NAME ENTERED TO IDENTIFY THE NETWORK ELEMENT CAN BE CHANGED FORM THIS WINDOW. A MAXIMUM OF 32 CHARACTERS CAN BE USED.

A NOTE DESCRIBING THE NETWORK ELEMENT CAN BE ENTERED FROM THIS WINDOW. UP TO 80 CHARACTERS CAN BE USED IN THIS FIELD

FROM THE EQUIPMENT SETUP WINDOW CLICK THE NE NAME BUTTON TO OPEN THE NE NAME SETTING WINDOW.

CLICK THE NOTE BUTTON TO OPEN THE NOTE WINDOW.

ENTER THE NOTE AND CLICK EXECUTE TO SHOW THE NOTE IN THE EQUIPMENT SETUP WINDOW.

ENTER THE NAME AND CLICK EXECUTE TO SHOW THE NAME IN THE EQUIPMENT SETUP WINDOW.

Page 31: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 31

MAINTENANCECLICK MAINTENANCE, ON THE, CONFIGURATION DROP DOWN MENU TO OPEN THE MAINTENANCE WINDOW

TO CARRY OUT ANY MAINTENANCE CONTROL ,SET THE SELECTED NE TO MAINTENANCE MODE. CLICK THE MAINT BUTTON ON THE MAINTENANCE WINDOW TO OPEN MAINTENANCE MODE SELECTION WINDOW. SELECT MAINT MODE ON OR OFF AND CLICK EXECUTE TO IMPLEMENT THE MODE SELECTION

THIS CONTROL MUTE THE OUTPUT POWER OF THE SELECTED PASOLINK CHANNEL .

CLICK THE TX MUTE BUTTON ON THE MAINTENANCE WINDOW TO OPEN THE TX MUTE CONTROL WINDOW. CLICK ON/OFF AND EXECUTE TO IMPLEMENT THE CONTROL.

THIS CONTROL TRANSMIT AN UN- MODULATED CARRIER FOR MEASUREMENT PURPOSE.

CLICK THE CW BUTTON ON THE MAINTENANCE WINDOW TO OPEN THE CW CONTROL WINDOW. CLICK ON/OFF AND EXECUTE TO IMPLEMENT THE CONTROL.

THIS CONTROL INHIBIT INSERTION OF AIS DURING BER ALARM CONDITION FOR MEASUREMENT PURPOSE.

CLICK THE BER AIS BUTTON ON THE MAINTENANCE WINDOW TO OPEN THE BER AIS CONTROL WINDOW. CLICK ON/OFF AND EXECUTE TO IMPLEMENT THE CONTROL.

THESE CONTROL ARE AVAILABLE FOR (1+1) CONFIGURATION. PROVIDES MANUAL SWITCH OVER OF PASOLINK CHANNEL

FOR NORMAL OPERATION SELECT AUTO FOR AUTO REDUNDANCY SWITCHING..

TO CLOSE ANY MAINTENANCE CONTROL WINDOW CLICK CLOSE BUTTON. TO NORMALIZE MAINTENANCE MODE NORMALIZE MAINTENANCE CONTROLS FIRST.

Page 32: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 32

AUX I/O WINDOW - MONITORINGAUXILIARY INPUT / OUTPUT FACILITY CAN BE USED TO MONITOR SIX EXTERNAL MONITOR ITEMS AND FOUR EXTERNAL CONTROL ITEMS USING THE PASOLINK MANAGEMENT SYSTEM. MONITORING ITEMS ARE CONNECTED THROUGH OPTICAL COUPLERS AND CONTROLS VIA RELAYS. THESE ITEMS ARE ALSO KNOWN AS HOUSEKEEPING ALARMS AND CONTROLS.

CLICK THE INPUT 1-6 BUTTONS TO CONFIGURE THE EXTERNAL ALARM

ENTER THE SELECTED EXTERNAL ALARM NAME, (UP TO 32 CHARACTERS)

CLICK EXECUTE TO CARRY OUT THE CHANGE

EXTERNAL MONITORING ITEMS CAN BE DEFINED AS ALARMS OR AS STATUS CHANGE.

CLICK THE CLOSE BUTTON TO CLOSE THE WINDOW

CLICK THE AUX SYMBOL IN THE BLOCK DIAGRAM OR AUX I/O TAB TO VIEW THE AUX ALARM/STATUS/CONTROL DISPLAY

SELECT THE CONDITION FOR ALARM, EVENT ON OR EVENT OFF

ENTER THE LABEL FOR ALARM/ STATUS EVENT ON AND EVENT OFF.

CLICK THE OUTPUT 1-4 BUTTONS TO CONFIGURE THE EXTERNAL CONTROLS

ENTER THE LABEL FOR EACH CONDITION EVENT ON AND EVENT OFF

ENTER THE NAME TO APPEAR FOR SELECTED CONTROL ITEM ( UP TO 32 CHARACTERS)

CONFIGURE ALARM INPUTS

CONFIGURE CONTROL RELAY OUTPUTS

CLICK EXECUTE TO CARRY OUT THE CHANGE

Page 33: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 33

PMC & VERSION WINDOWSCLICK THE PMC SYMBOL ON THE BLOCK DIAGRAM OR THE PMC TAB TO DISPLAY THE PMC WINDOW FOR THE SELECTED NE.

VERSION WINDOW DISPLAY THE DATE OF MANUFACTURE , SOFTWARE VERSIONS, SERIAL NUMBER, CODE NUMBER ETC.. OF THE PASOLINK EQUIPMENT IN THE SELECTED NETWORK ELEMENT.

CONFIGURATION AND SETTING OF THE PASOLINK MANAGEMENT CARD IS PROVIDED IN THIS WINDOW.

CLICK THE VERSION TAB TO DISPLAY THE VERSION INFORMATION WINDOW FOR THE SELECTED NE.

Page 34: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 34

DATE TIME SETTINGDATE AND TIME STORED IN THE SELECTED NETWORK ELEMENT’S PM CARD CAN BE DISPLAYED AND ADJUSTED FORM THIS CONTROL ITEM

CLICK DATE/TIME BUTTON IN THE PMC WINDOW TO OPEN THE DATE/TIME SETTING CONTROL WINDOW

TO DISPLAY THE CURRENT DATE/TIME STORED IN THE PM CARD, SELECT GET DATE/TIME AND CLICK EXECUTE.

THE CURRENT DATE/TIME STORED IN THE PM CARD, IS DISPLAYED.

TO DISPLAY AND SET THE DATE/TIME SET IN THE PNMT PC TO THE PM CARD, SELECT DISPLAY PC TIME BOX AND CLICK THE EXECUTE BUTTON.

CHANGE THE DATE /TIME SETTING AS REQUIRED, CLICK THE EXECUTE BUTTON.

TO CHANGE THE PM CARD DATE TIME SETTING, SELECT SET DATE/TIME.

TO CHANGE THE PM CARD DATE TIME SETTING, SELECT SET DATE/TIME.

[PMC WINDOW]

Page 35: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 35

DOWN LOAD CONFIGURATION FILESTHIS FUNCTION IS USED TO DOWN LOAD CONFIGURATION FILES CREATED BY THE NETWORK CONFIG TOOL TO THE PM CARD IN THE SELECTED NETWORK ELEMENT. THERE ARE TWO FILES CREATED FOR EACH NE, SYSTEM.CFG CONTAINS THE IP ADDRESS OF THE PM CARD AS WELL AS THE IP ADDRESS OF THE OPPOSITE STATION. THE NETWORK.CFG FILE CONTAINS THE INFORMATION ABOUT THE PASOLINK NETWORK WHERE THE PM CARD IS LOCATED.

CLICK THE CONFIGURATION FILE BUTTON UNDER THE DOWNLOAD (PC>>PMC) IN THE PMC WINDOW, TO OPEN THE DOWNLOAD CONFIGURATION FILE WINDOW.

SELECT EACH CONFIG FILE ONE BY ONE FROM THE TYPE WINDOW

BROWSE AND SELECT THE PATH/LOCATION TO THE FILE SELECTED IN THE TYPE WINDOW.

CLICK EXECUTE BUTTON TO DOWN LOAD THE SELECTED CONFIG FILE..

MAKE SURE THAT THE CORRECT CONFIGURATION FILE IS DOWN LOADED TO THE PM CARD IN THE CORRECT NE. INCORRECT CONFIGURATION FILE WILL LEAD TO PM CARD OR NETWORK FAILURE

WARNING

REPEAT THE DOWNLOAD PROCEDURE FOR THE OTHER CONFIG FILE..

A MESSAGE WINDOW INDICATE THE STATUS OF THE DOWNLOAD OPERATION AND IT WILL CLOSE AUTOMATICALLY ONCE THE OPERATION IS OVER

AFTER THE SUCCESSFUL DOWN LOAD OF THE CONFIGURATION FILES. CLICK UPDATE BUTTON. UPDATE CONFIGURATION FILE WINDOW OPENS.

SELECT THE APPROPRIATE BOX FOR THE TYPE OF CONFIGURATION FILE(S) THAT WILL BE UPDATED.

System Config

Network Config

ME Config

With ROM (PMC Program ) Switching

PPP Config

Execute

CLICK OK BUTTON TO START THE UPDATE OPERATION..

WHEN UPDATING SYSTEM.CFG FILE , PMC TO PMC COMMUNICATION WILL BE LOST WHEN PM CARD INITIALIZES TO THE NEW SYSTEM CONFIGURATION. DURING THIS TIME PNMT CONNECTION TO THE PASOLINK WILL BE LOST BUT WILL AUTOMATICALLY BE RECONNECTED AFTER THE PMC RESETS

MAKE SURE THAT YOU HAVE SUCCESSFULLY DOWN LOADED THE CONFIGURATION FILE BEFORE DOING UPDATE. OTHERWISE THE PM CARD WILL SWITCH TO AN EMPTY ROM THAT MAY CAUSE PM CARD FAILURE.

CLICK CLOSE BUTTON WHEN DONE

UPDATE

DOWN LOAD

[PMC WINDOW]

Page 36: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 36

DOWN LOAD PROGRAM FILE

A:\pm.pof

THIS FUNCTION IS USED TO UPDATE THE APPLICATION PROGRAM ON THE PM CARD. THIS OPERATION AFFECTS THE ONLY THE PMC TO PMC COMMUNICATION. AND WILL NOT DISRUPT THE RADIO LINK.

CLICK ON THE PROGRAM FILE BUTTON UNDER THE DOWNLOAD (PC>>PMC) IN THE PMC WINDOW.

ENTER THE PATH TO THE PROGRAM FILE TO BE DOWNLOADED OR CLICK BROWSE TO LOCATE THE PROGRAM FILE.

CLICK THE EXECUTE BUTTON TO START DOWNLOAD OPERATION

A MESSAGE WINDOW APPEARS TO SHOW THE STATUS OF THE DOWNLOAD OPERATION, AND WILL CLOSE AUTOMATICALLY ONCE THE DOWNLOAD IS COMPLETED.

MAKE SURE THAT THE CORRECT PROGRAM FILE IS DOWNLOADED TO THE PM CARD. INCORRECT PROGRAM FILE WILL LEAD TO PM CARD FAILURE.

WARNINGCLICK ON THE PMC RESET BUTTON TO SWITCH TO THE NEW PROGRAM FILE

SELECT WITH ROM (PMC PROGRAM) SWITCHING OPTION IF YOU WANT TO SWITCH TO A NEWLY DOWNLOADED PMC PROGRAM FILE RESETTING THE PMC WILL NOT AFFECT THE

TRAFFIC. THE CONNECTION TO THE SELECTED PASOLINK WILL BE LOST FOR FEW MINUTES AND WILL BE RECONNECTED AUTOMATICALLY.

PM CARD CAN BE RESET USING THIS FUNCTION

CLICK THE PMC RESET BUTTON ON THE PMC WINDOW.

CLICK EXECUTE BUTTON TO RESET THE PM CARD.

[PMC WINDOW]

Page 37: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 37

UPLOAD CONFIGURATION FILE

SELECT THE TYPE OF CONFIG FILE TO BE UPLOADED FROM THE TYPE WINDOW., SYSTEM CONFIG OR NETWORK CONFIG.

THIS FUNCTION IS USED TO UPLOAD THE CONFIGURATION FILES FROM THE PM CARD OF THE SELECTED NE TO THE PNMT PC.

ENTER THE LOCATION THE FILE TO BE UPLOADED AND THE FILE NAME IN THE FILE WINDOW. USE BROWSE TO LOCATE THE DIRECTORY IF NECESSARY.

CLICK EXECUTE BUTTON TO START THE UPLOAD OPERATION. A MESSAGE WINDOW APPEARS TO SHOW THE STATUS OF THE UPLOAD OPERATION, AND WILL CLOSE AUTOMATICALLY ONCE THE OPERATION IS COMPLETED..

AFTER THE UP LOAD IS FINISHED CLICK THE CLOSE BUTTON TO CLOSE THE WINDOW.

CLICK THE CONFIGURATION FILE UNDER THE UPLOAD (PM>>PC) TO OPEN THE UPLOAD CONFIGURATION FILE WINDOW.

[PMC WINDOW]

Page 38: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 38

EVENT LOG

CLICK ON THE EVEN LOG IN THE NE SPECIFIC MENU BAR TO UPLOAD THE EVEN LOG ITEMS FROM THE SELECTED NE.

A MESSAGE WINDOW SHOWS THE PROGRESS OF THE UPLOAD

EVENT LOG VIEW WINDOW SHOWS ALARM EVENTS, COMMAND EVENTS AND STATUS CHANGES.

DIFFERENT COLORS SHOWS THE TYPE OF EVENT.

EVENT LOG IS PRESENTED IN A TABLE FORM SHOWING THE DATE OF THE EVENT , THE ITEM THAT TRIGGERED THE EVENT AND THE STATUS CHANGE.

CLICK FILE-UPLOAD TO REFRESH THE EVENT LOG DISPLAY

CLICK FILE-SAVE AS TO SAVE THE EVENT LOG TO

CLICK FILE-PRINT TO PRINT THE EVENT LOG INFORMATION

NE SPECIFIC MENU BAR

Page 39: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 39

LINK PERFORMANCE MONITOR

THE FOLLOWING PERFORMANCE ITEMS CAN BE MONITORED ACCORDING TO THE G.826 RECOMMENDATIONS.

NE SPECIFIC MENU BAR

SES SEVERELY ERROR SECONDSUAS UNAVAILABLE SECONDSBBE BACKGROUND BLOCK ERRORS

THE RED COLOR IN THE PERFORMANCE MONITOR WINDOW INDICATES THE OCCURRENCE OF PERFORMANCE ITEMS EXCEEDING THE THRESHOLD VALUE. THE THRESHOLD VALUES CAN BE SET IN THRESHOLD WINDOW. ALL DATA CAN BE RESET BY USING ALL DATA RESET BUTTON. ( MAKE SURE THAT THE CURRENT DATA HAS BEEN SAVED AS THIS OPERATION WILL DELETE ALL THE PERFORMANCE DATA IN THE CURRENT WEEK.)

CLICK ON THE LINK PERFORMANCE MONITOR IN THE NE SPECIFIC MENU BAR OF THE LINK SUMMARY WINDOW OF THE PASOLINK TO BE MONITORED.

ES ERROR SECONDS

SELECT THE PERFORMANCE ITEM THAT IS TO BE CONFIGURED ON THE TABLE SHOWN. SET THE VALUE WHEN THE ALARM OCCUR AND WHEN THE ALARM RECOVER IN THE APPROPRIATE FIELD.

AFTER SETTING ALL THE THRESHOLD VALUES CLICK EXECUTE TO ACTIVATE THE NEW SETTING.

CLOCK CLOSE TO CLOSE THE THRESHOLD SETTING WINDOW..

THRESHOLD VALUE SETTING

CLICK THE THRESHOLD(%) BUTTON TO OPEN THE THRESHOLD SETTING WINDOW.

CURRENT BER VALUE IS SHOWN IN THIS FIELD

Page 40: 48379379-PNMT-V4

NECITR-YTCART-SEP/03 V02

PNMT 40

LINK PERFORMANCE MONITOR

THE LINK PERFORMANCE MONITOR DAILY DATA WINDOW DISPLAY THE DETAILED 15MIN PERFORMANCE DATA

CLICK ON THE DETAIL BUTTON IN THE LINK PERFORMANCE MONITOR WINDOW TO DISPLAY THE WEEKLY DETAIL WINDOW.

THIS WINDOW CONTAINS THE LINK PERFORMANCE DATA OF THE LAST .8 DAYS.

THE DATE BUTTONS ON THE RIGHT HAND SIDE OF THE TABLE ARE SELECTABLE. AND CAN OPEN THE SUMMARY DATA FOR THAT SPECIFIC DATE..

CLICK ON A DATE BUTTON TO DISPLAY THE DAILY DATA WINDOW FOR THE SELECTED DATE

CLICK FILE – SAVE AS TO SAVE THE DATA IN TEXT FORMAT

CLICK FILE - UPLOAD TO REFRESH THE DATA

Page 41: 48379379-PNMT-V4