G3901.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: ALUPLAST US CORP SERIES/MODEL: IDEAL 4000 TYPE: In-Swing Tilt-Turn Casement Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC G3901.01A 1-1/4" IG (1/8" annealed, 1" air space, 1/8" annealed) 32 25 G3901.01B 1-3/8" IG (1/8" annealed exterior, 1" air space, 1/4" laminated interior), Glass temperature 75°F 36 27 Reference should be made to Intertek-ATI Report No. G3901.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request. 130 Derry Court York, PA 17406 p. 717.764.7700 f. 717.764.4129 www.archtest.com www.intertek.com/building
Transcript
Page 1: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0 ACOUSTICAL PERFORMANCE TEST REPORT

ASTM E90

Rendered to:

ALUPLAST US CORP

SERIES/MODEL: IDEAL 4000

TYPE: In-Swing Tilt-Turn Casement Window

Summary of Test Results

Data File No. Glazing (Nominal Dimensions) STC OITC

G3901.01A 1-1/4" IG (1/8" annealed, 1" air space, 1/8" annealed) 32 25

G3901.01B 1-3/8" IG (1/8" annealed exterior, 1" air space, 1/4" laminated interior), Glass temperature 75°F

36 27

Reference should be made to Intertek-ATI Report No. G3901.01-113-11 for complete test specimen description. This page alone is not a complete report. Flanking limit tests and reference specimen tests are available upon request.

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 2: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

Acoustical Performance Test Report

ALUPLAST US CORP 180 South 1140 West

Building 16 A Bay 6 North Ogden, Utah 84404

Report No G3901.01-113-11 Test Date 10/18/16 Report Date 12/22/16 Project Scope Architectural Testing, Inc., an Intertek company ("Intertek-ATI"), was contracted to conduct a sound transmission loss test. The complete test data is included as Appendix B of this report. The client provided the test specimen. Test Methods Testing for this project was conducted in accordance with the following standards. The equipment listed in the attachments meets the requirements of the following standards. ASTM E90-09, Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements ASTM E413-10, Classification for Rating Sound Insulation ASTM E1332-10a, Standard Classification for Rating Outdoor-Indoor Sound Attenuation ASTM E2235-04 (2012), Standard Test Method for Determination of Decay Rates for Use in Sound Insulation Test Methods

Test Procedure All measurements were conducted in the HT test chambers at Intertek-ATI located in York, Pennsylvania. The sensitivity of the microphones was checked before measurements were conducted. The transmission loss values were obtained for a single direction of measurement. Two background noise sound pressure level and five sound absorption measurements were conducted at each of five microphone positions. Two sound pressure levels were made simultaneously in the receive and source rooms at each of five microphone positions.

The air temperature and relative humidity conditions were monitored and recorded during all measurements.

130 Derry CourtYork, PA 17406

p. 717.764.7700f. 717.764.4129

www.archtest.com www.intertek.com/building

Page 3: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0 Page 2 of 6

Specimen Installation A sound transmission loss test was initially performed on a filler wall. The specimen plug was removed from the filler wall assembly. A filler wall-reducing element, consisting of two separate 2x6 wood frames filled with concrete, was used to adjust the test opening size to accommodate the test specimen. A dense neoprene gasket was placed between the two wood and concrete frames. The specimen was placed on an isolation pad in the custom test opening. Duct seal was used to seal the perimeter of the specimen to the test opening on both sides. The interior side of the specimen, when installed, was approximately 1/4" from being flush with the receive room side of the filler wall. A stethoscope was used to check for any abnormal air leaks around the test specimen prior to testing. Operable portions of the test specimen, if any, were cycled at least five times prior to testing. Test Calculations Transmission loss (TL) at each 1/3 octave frequency is the average source room sound pressure level minus the average receive room sound pressure level, plus, 10 times the log of the specimen area divided by the sound absorption of the receive room with the sample in place. STC Rating To obtain the Sound Transmission Class (STC), read the TL of the contour curve at 500 Hz. The sum of the deficiencies below the contour curve must not exceed 32. The maximum deficiency at any one frequency must not exceed 8. OITC Rating The Outdoor-Indoor Transmission Class (OITC) is calculated by subtracting the logarithmic summation of the TL values from the logarithmic summation of the A-weighted transportation noise spectrum stated in ASTM E1332.

Page 4: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0 Page 3 of 6

Specimen Descriptions

Frame Vent

Size 47-1/4" by 59" 44" by 55-7/8"

Thickness 3-5/8" 2-3/4"

Corners Mitered Mitered

Fasteners Welds Welds

Seal Method N/A N/A

Material Vinyl Vinyl

Reinforcement Steel located in all members Steel located in all members

Thermal Break Material N/A N/A

Daylight Opening Size N/A 37-5/8" by 49-1/2"

Glazing Option A

Measured Overall Insulation Glass Unit Thickness 1.279"

Spacer Type Super spacer

Exterior Sheet Gap Interior Sheet

Measured Thickness 0.111" 1.051" 0.117"

Muntin Pattern N/A N/A N/A

Material Annealed Air* Annealed

Laminate Material N/A N/A N/A

Glazing Method Interior

Glazing Material EPDM

Glazing Bead Material Vinyl

* - Stated per Client/Manufacturer, N/A-Not Applicable

Page 5: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0 Page 4 of 6

Specimen Descriptions (Continued)

Glazing Option B

Measured Overall Insulation Glass Unit Thickness 1.299"

Spacer Type Super spacer

Exterior Sheet Gap Interior Sheet

Measured Thickness 0.117" 0.925" 0.114", 0.029", 0.114"

Muntin Pattern N/A N/A N/A

Material Annealed Air* Laminated

Laminate Material N/A N/A PVB

Glazing Method Interior

Glazing Material EPDM

Glazing Bead Material Vinyl

Components

Type Quantity Location

Weatherstrip

Hollow bulb gasket 1 Row Perimeter of frame

Hollow gasket with 1/4" leaf gasket 1 Row Perimeter of vent

Hardware

Tilt-turn hinge 2 Hinge jamb

Multi-point lock system 1 Perimeter of vent

Keeper 8 Perimeter of frame

Drainage

1" by 3/16" Weep slot 2 Sill face

1" by 1/8" Weep slot 2 Bottom rail of vent

* - Stated per Client/Manufacturer, N/A-Not Applicable

Page 6: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0 Page 5 of 6

Specimen Descriptions (Continued)

Test Option Total Weight (lbs) Average Weight (lbs/ft2)

A 102 5.27

B 125 6.46

Comments A drawing of the test specimen is included in Appendix D. Intertek-ATI will store samples of test specimens for four years. Intertek-ATI will service this report for the entire test record retention period. Test records, such as detailed drawings, datasheets, representative samples of test specimens, or other pertinent project documentation, will be retained by Intertek-ATI for the entire test record retention period. The test record retention period ends four years after the test date. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen tested. This report is intended to help in the client’s quality assurance program, but it does not represent a continuous or exhaustive evaluation of the specimen tested or of other products or materials that were not evaluated. The statements and data provided herein do not constitute approval, disapproval, certification, or acceptance of performance or materials. This report may not be reproduced, except in full, without the written approval of Intertek-ATI. For INTERTEK-ATI: Zachary P. Golden Kurt A. Golden Technician - Acoustical Testing Project Lead – Acoustical Testing ZPG:jmcs

Attachments (pages): This report is complete only when all attachments listed are included.

Appendix A: Equipment description (1) Appendix B: Complete test results (4) Appendix C: Photographs (1) Appendix D: Drawing (1)

Page 7: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0 Page 6 of 6

Revision Log

Rev. # Date Page(s) Revision(s)

R0 12/22/16 N/A Original Report Issue

This report produced from controlled document template ATI 00271, revised 08/31/15.

Page 8: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

TL Test Opening4.27 m (14 ft) wide by

Vibration break between source and receive rooms3.05 m (10 ft) high

Receive Room 234 m3 (8291.3 ft3)

1251 Pistonphone Calibrator

Source Room

Rotating vane and stationary diffusers Temperature and humidity controlledIsolation pads under the floor

65105 05/16Microphone Calibrator Norsonic

N/A-Not Applicable

206.6 m3 (7296.3 ft3)Stationary diffusers only

Temperature and humidity controlled

Maximum Size Description

Microphone and Preamplifier

*- Note: The calibration frequency for this equipment is every two years per the manufacturer's recommendation.

Test Chamber:

Volume Description

03/16

Source Room

Environmental IndicatorComet T7510 Source Room 64914 03/16

Comet T7510

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64910

Receive Room

MicrophonePCB Piezotronics

Receive Room

Environmental Indicator64915

12/15

Receive Room

378B20 Microphone and Preamplifier 64908 12/15

378B20 Microphone and Preamplifier 64911 12/15

Microphone and Preamplifier 12/15

Receive Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64909 12/15

Receive Room

MicrophonePCB Piezotronics

12/15

Receive Room

MicrophonePBC Piezotronics 378B20 Microphone and Preamplifier 64907 12/15

Microphone and Preamplifier 65103

Source Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64906

64905Source Room

MicrophonePCB Piezotronics

Source Room

MicrophonePCB Piezotronics 378B20 Microphone and Preamplifier 64902 07/16

64903 12/15

378B20

12/15

Source Room

MicrophonePCB Piezotronics 378B20

Source Room

MicrophonePCB Electronics 378B20

Data Acquisition Unit National Instruments PXI-1033

Description ATI NumberDate of

Calibration

Data Acquisition card 65126 05/16 *

G3901.01 -113-11

Appendix A

Instrumentation:

Instrument Manufacturer Model

Page 9: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0

Appendix B

Complete Test Results

Page 10: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

OITC Rating (Outdoor-Indoor Transmission Class)

00.19

0.21 0

5000

6.9 12.5

Notes: 1) Receive Room levels less than 5 dB above the Background levels are red.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

41.1 0.21 -

4000

Page 1 of 2ATI 00760 Revised 05/23/16

25

93

36.6

32

7.8 15.8

40.6

42

94

45 42.4

27

3150 6.2 10.0

8.4

49

95

2500 6.0 93 46

1250 10.9 6.6 44.4

7.32000 6.6 95 44 44.7

0

0.35 0

1600 8.3 7.0

0.23 097 47

0.19 0

103 52 45.0 0.19

1000 13.7 6.0 97 50

0800 16.9 5.8 100 55 39.4 0.42

0.24 0

630 18.9 5.6 100 60 35.3

41.6

00.46

500 21.0 5.7 96 60 30.8 0.25 1

400 24.9 5.9 96 65 25.8 0.38 5

0.80 8

315 28.2 5.5 99 73 20.8 0.36 7

1.03 0

250 34.6 5.6 106 84 16.7

0.87 2

200 40.1 4.8 106 84 17.6 0.65 4

4.7 104 83 16.9

80 39.2 4.6 105 84 17.9

76 23.9

100 37.4 5.0 106 76 26.8 1.50 -

SPL SPL

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

Test Date 10/18/16

Data File No. G3901.01A

Client Aluplast US Corp

Description

(Hz) (dB) (m²) (dB) (dB)

1.84 -

160 41.4

Limit Deficiencies

125 37.5 4.8 104

Number

(dB)

Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-1/4" IG (1/8" annealed,

1" air space, 1/8" annealed)

22.8 °C

Confidence of

50%

Specimen Area 1.80 m² Receive Temp. 22.9 °C Source Temp.

Source Receive

Receive Humidity 49% Source HumidityTechnician

FreqBackground

AbsorptionSpecimen

TL

95%

Zachary Golden

SPL

Page 11: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

Receive Temp. 22.8 °C

Data File No.

ATI 00760 Revised 05/23/16

Description Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-1/4" IG (1/8" annealed,

1" air space, 1/8" annealed)

Specimen Area

Client

Receive Humidity 49% 50%Technician Zachary Golden

G3901.01A

Source Humidity

10/18/16Test Date

22.9 °C Source Temp.

Aluplast US Corp

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

1.80 m²

Page 2 of 2

0

10

20

30

40

50

60

70

80

90

100

31.5 63 125 250 500 1000 2000 4000 8000

Sou

nd

Tra

nsm

issi

on

Lo

ss (

dB

)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL Contour Curve

Page 12: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

STC Rating (Sound Transmission Class)

Deficiencies (Sum of Deficiencies)

OITC Rating (Outdoor-Indoor Transmission Class)

4000

00.23

0.26 0

ATI 00760 Revised 05/23/16

5000

6.8 13.3

Notes:

Page 1 of 2

1) Receive Room levels less than 5 dB above the Background levels are red.

2) Specimen TL levels listed in red indicate the lower limit of the transmission loss.

3) Specimen TL levels listed in green indicate that there has been a filler wall correction applied

47.2 0.29 -

28

27

93

44.0

36

7.7 17.5

95 45 43.7

46 40.4

36

94

443150 6.3 10.6

8.7

41

95

2500 6.2

42.8

93

1250 10.6 6.6 45.4

7.52000 6.8

0

0.34 0

1600 8.7 7.0

0.26 097 46

0.19 0

102 52 44.8 0.12

1000 13.4 6.0 97 48

0800 17.5 5.8 100 52 42.5 0.39

0.25 0

630 20.3 5.5 100 56 39.4

44.1

00.46

500 22.6 5.6 96 55 36.6 0.29 0

400 26.5 5.7 96 60 31.4 0.35 4

0.69 6

315 30.5 5.5 99 67 26.7 0.42 5

1.11 0

250 36.7 5.3 106 78 23.1

1.01 8

200 40.8 4.8 106 81 20.7 0.64 5

4.6 104 84 15.2

80 39.0 4.5 106 82 20.4

76 23.9

100 36.4 5.0 105 74 28.0 1.54 -

SPL SPL

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

Test Date 10/18/16

Data File No. G3901.01B

Client Aluplast US Corp

Description

(Hz) (dB) (m²) (dB) (dB)

1.72 -

160 41.4

Limit Deficiencies

125 39.4 5.1 104

Number

(dB)

Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-3/8" IG (1/8" annealed

exterior, 1" air space, 1/4" laminated interior), Glass temperature 75°F

20.8 °C

Confidence of

45%

Specimen Area 1.80 m² Receive Temp. 21.5 °C Source Temp.

Source Receive

Receive Humidity 44% Source HumidityTechnician

FreqBackground

AbsorptionSpecimen

TL

95%

Zachary Golden

SPL

Page 13: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

1.80 m² Receive Temp. 20.8 °C

Data File No.

ATI 00760 Revised 05/23/16

Description Series/Model: Ideal 4000, in-swing tilt-turn casement window with 1-3/8" IG (1/8" annealed

exterior, 1" air space, 1/4" laminated interior), Glass temperature 75°F

Specimen Area

Client

Receive Humidity 44% 45%Technician Zachary Golden

G3901.01B

Source Humidity

10/18/16Test Date

21.5 °C Source Temp.

Aluplast US Corp

AIRBORNE SOUND TRANSMISSION LOSSASTM E 90

Page 2 of 2

0

10

20

30

40

50

60

70

80

90

100

31.5 63 125 250 500 1000 2000 4000 8000

Sou

nd

Tra

nsm

issi

on

Lo

ss (

dB

)

Frequency (Hz)

Airborne Sound Transmission Loss

Specimen TL Contour Curve

Page 14: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0

Appendix C

Photographs

Receive Room View of Installed Test Specimen

Source Room View of Installed Test Specimen

Page 15: Acoustical Field Test Report - eurotekwindows.comeurotekwindows.com/wp-content/uploads/2017/11/g3901.01-113-11-r0.pdf · Acoustical Performance Test Report . ALUPLAST US CORP . ...

G3901.01-113-11-R0

Appendix D

Drawing