AIRTRONIC / AIRTRONIC MTroubleshooting and Repair Instructions
25.2115.95.1901 01.2019
Airtronic
AirtronicD2,12VAirtronicD2,24VAirtronicD2Camper,12V
Completepackage
AirtronicD2,12VAirtronicD2,24V
Orderno.
252069050000 252070050000 252326050000
252675050000 252676050000
Air heater for diesel and petroloperating independently of the engine.
2
4
3
1
2
1Contents
ThislistofcontentsgivesyoupreciseinformationaboutthecontentsoftheTroubleshootingandRepairInstructions.
Introduction
Usetheindex,listofabbreviations,etc,tolookforaterm,technicalwordoranexplanationforanabbreviation.
Chapter Title Contents Page
Introduction • Foreword.................................................................................................................. 4 • Accidentprevention.................................................................................................. 4 • Specialtextstructure,presentationandpicturesymbols........................................... 4 • Importantinformationbeforestartingwork................................................................ 4
Function and use Cutawayview............................................................................................................ 5 • Descriptionoffunctions – Switchingon.......................................................................................................... 6 – StartingtheAirtronic.............................................................................................. 6 – StartingtheAirtronicM.......................................................................................... 6 – Temperatureselectionwiththecontrolelement...................................................... 6 – Controlinheatingmode......................................................................................... 6 – Ventilatingmode.................................................................................................... 6 – Switchingoff.......................................................................................................... 6 • Controlandsafetydevices........................................................................................ 7 – Forcedshut-downforADRoperation..................................................................... 7 – Emergencyshutdown–EMERGENCYOFF........................................................... 7
Technical data • Airtronic(fordiesel)................................................................................................... 8 • AirtronicM(forpetrol)................................................................................................ 9 • AirtronicM(fordiesel)........................................................................................ 10,11 • Checkvalues – Testspeedfortheblower..................................................................................... 12 – Resistan\cevalues............................................................................................... 12 – Switchingvalue.................................................................................................... 12 – Exhaustemissionspecification............................................................................. 12 – Check“externaltemperaturesensor”................................................................... 12 – Tableofvalues:“Externaltemperaturesensor”..................................................... 12
Troubleshooting • Whattocheckfirstincaseoffaults – Check.................................................................................................................. 13 – Electricalcomponents.......................................................................................... 13 – Measurebatteryvoltage....................................................................................... 13 – Measuresvoltagesupply..................................................................................... 13 – Checkswitch-onsignal........................................................................................ 13 – Checkcontrolunit................................................................................................ 13 • Overviewoftheindividualtestequipmentandcontrolunits..................................... 14 • Lockingthecontrolbox........................................................................................... 14 • Cancelthecontrolboxlock..................................................................................... 14 • Importantnotes(diagnosisofheaterswithmini-controller)....................................... 14 • Testingdeviceforthecontroldevice........................................................................ 15 • Faultdiagnosisusingthediagnosticunit........................................................... 15,16 • FaultdiagnosisusingtheEDiTHdiagnosticstoolwithISOadapter.......................... 17 • AirpressuresensordiagnosisusingEDiTHdiagnosticstoolandISOadapter.......... 18 • FaultdiagnosisusingtheEDiTHdiagnosticstoolwithbasicadapter....................... 19 • Faultdiagnosisusingthemoduletimer.................................................................... 20 • FaultdiagnosisusingtheradioremotecontrolTP5................................................. 21 • FaultdiagnosisusingtheEasyStartR+radioremotecontrolor theEasyStartTtimer............................................................................................... 22 • Faultcodetable...............................................................................................23–27
3
Introduction
7
6
5
1
Chapter Title Contents Page
Repair instructions • Repairinstructions.................................................................................................. 28 • Alwaysobservethefollowingsafetyinstructionsbeforeworkingontheheater........ 28 • Specialtool,AMPreleasetool................................................................................. 28 • AssemblydrawingAirtronic/AirtronicM................................................................. 29 • Repairstep1,removetheheatercover................................................................... 30 • Repairstep2,dismantlecontrolbox,checkcontrolbox......................................... 30 • Repairstep3,dismantleglowplug.......................................................................... 31 • Repairstep4,renewlining...................................................................................... 31 • Repairstep5,dismantlecombinationsensor(overheating/flamesensor............... 32 • Repairstep6,installcombinationsensor(overheating/flamesensor)..................... 33 • Repairstep7,dismantleheatexchanger/ dismantlecombustionairfan................................................................................... 34 • Repairstep8,dismantlecombustionchamber........................................................ 35 • Checkfuelsupply.................................................................................................... 36 • Measuringthefuelquantity...................................................................................... 36
Circuit diagrams Overviewofthepartslistsandcircuitdiagrams........................................................... 37 • PartslistcircuitdiagramsAirtronic/AirtronicM....................................................... 38 • CircuitdiagramAirtronic/AirtronicM..................................................................... 39 Thiscircuitdiagramisvalidforheaterswithonediagnosiscable andacontrolboxcableloomwichisfirmlyencapsulated. • CircuitdiagramAirtronic/AirtronicM..................................................................... 40 Thiscircuitdiagramisforheaterswith2diagnosticscableandwhose controlboxcableloomiswoundwithcabletape. • Partslistcircuitdiagrams,controlunits.................................................................... 41 • Circuitdiagramcontrolunits–part1....................................................................... 42 • Circuitdiagramcontrolunits–part2....................................................................... 43 • Circuitdiagramcontrolunits–part3....................................................................... 44 • Circuitdiagramcontrolunits–part4....................................................................... 45 • Circuitdiagramcontrolunits–part5....................................................................... 46 • Circuitdiagramcontrolunits–part6....................................................................... 47 • Circuitdiagramcontrolunits–part7....................................................................... 48 • PartslistcircuitdiagramcontrolunitEasyStartR+/R/T........................................ 49 • CircuitdiagramcontrolunitEasyStartR+(controlboxwith1diagnosticscable)...... 50 • CircuitdiagramcontrolunitEasyStartR+(controlboxwith1diagnosticscable)...... 51 • CircuitdiagramcontrolunitEasyStartR+(controlboxwith2diagnosticscable)...... 52 • CircuitdiagramcontrolunitEasyStartR(controlboxwith1/2diagnosticscables). 53 • CircuitdiagramcontrolunitEasyStartR(controlboxwith2diagnosticscables)...... 54 • CircuitdiagramcontrolunitEasyStartR(controlboxwith1diagnosticscables)...... 55 • CircuitdiagramcontrolunitEasyStartT(controlboxwith1diagnosticscable)........ 56 • CircuitdiagramcontrolunitEasyStartT(controlboxwith2diagnosticscable)........ 57 • PartslistcircuitdiagramsAirtronic/AirtronicM–ADR............................................ 58 • CircuitdiagramAirtronic/AirtronicM–ADR.......................................................... 59 1encapsulateddiagnosticscableandcontrolboxcableloomfirmlyencapsulated • CircuitdiagramAirtronic/AirtronicM–ADR.......................................................... 60 2diagnosticscablesandcontrolboxcableloomwithcabletape • Partslistcircuitdiagrams,controlunits–ADR......................................................... 61 • Partslistcircuitdiagrams,controlunits–EasyStartT–ADR................................... 61 • Circuitdiagramcontrolunits–ADR......................................................................... 62 • CircuitdiagramcontrolunitEasyStartT–ADR(controlboxwith1diag.cable)....... 63 • CircuitdiagramcontrolunitEasyStartT–ADR(controlboxwith2diag.cable)....... 64
Service • Certification............................................................................................................. 65 • Disposal.................................................................................................................. 65 • ECDeclarationofConformity.................................................................................. 65 • Listofkeywords..................................................................................................... 66 • Listofabbreviations................................................................................................ 67
4
Special text structure, presentation and picture symbols
Specialtextformatsandpicturesymbolsareusedintheseinstructionstoemphasisedifferentsituationsandsubjects.Pleaserefertothefollowingexamplesfortheirmeaningsandappropriateaction.
Special text formats and presentations• Adot(•)indicatesalist,whichisstartedbyaheading.
– Ifanindenteddash(–)followsa“dot”,thislistisasub-sectionoftheblackdot.
Picture symbols
Danger!Thisinformationpointsoutadangeroussituationforapersonand/ortheproduct.Failuretocomplywiththeseinstructionscanresultininjuriestopeopleand/ordamagetomachinery.
Caution!Thisinformationpointsoutadangeroussituationforapersonand/ortheproduct.Failuretocomplywiththeseinstructionscanresultininjuriestopeopleand/ordamagetomachinery.
Important information before starting work
Initial commissioning of the heater or functional test after a repair
• Afterinstallingtheheater,thewholefuelsupplysystemmustbecarefullyvented:pleaserefertoandfollowthevehiclemanufacturer’sinstructions.
• Duringtheheatertrialrun,allfuelconnectionsmustbecheckedforleaksandsecure,tightfit.
• Iffaultsoccurwhiletheheaterisrunning,useadiagnosticunittodetermineandcorrectthecauseofthefault.
1 IntroductionForeword
TheseTroubleshootingandRepairInstructionsareapplicabletotheheaterslistedonthetitlePage,totheexclusionofallliabilityclaims.Dependingontheversionorrevisedstatusoftheheater,theremaybedifferencesbetweenitandthesetroubleshootingandrepairinstructions.Theusermustcheckthisbeforecarryingouttherepairworkand,ifnecessary,takethedifferencesintoaccount.
Caution!Safety instructions for installation and repair!
ImproperinstallationorrepairofEberspächerheaterscancauseafireorresultpoisonousexhaustenteringtheinsideofthevehicle.Thiscancauseseriousandevenfatalrisks.
Theheatermayonlybeinstalledaccordingtothespecifica-tionsinthetechnicaldocumentsorrepairedusingoriginalsparepartsbyauthorisedandtrainedpersons.Installationandrepairsbyunauthorisedanduntrainedper-sons,repairsusingnon-originalsparepartsandwithoutthetechnicaldocumentsrequiredforinstallationandrepairaredangerousandthereforearenotpermitted.
Arepairmayonlybecarriedoutinconnectionwiththere-spectiveunit-relatedtechnicaldescription,installationinstruc-tions,operatinginstructionsandmaintenanceinstructions.Thisdocumentmustbecarefullyreadthroughbefore/duringinstallationandrepairandfollowedthroughout.Particularattentionistobepaidtotheofficialregulations,thesafetyinstructionsandthegeneralinformation.
Please note!
Therelevantrulesofsoundengineeringpracticeandanyinformationprovidedbythevehiclemanufactureraretobeobservedduringtheinstallationandrepair.Eberspächerdoesnotacceptanyliabilityfordefectsanddamage,whichareduetoinstallationorrepairbyunauthor-isedanduntrainedpersons.Compliancewiththeofficialregulationsandthesafetyinstruc-tionsisprerequisiteforliabilityclaims.Failuretocomplywiththeofficialregulationsandsafetyinstructionsleadstoexclu-sionofanyliabilityoftheheatermanufacturer.
Accident prevention
Generalaccidentpreventionregulationsandthecorrespond-ingworkshopandoperatingsafetyinstructionsaretobeobserved.
5
Cutaway view
1 Heaterimpeller 2 Controlbox 3 Combustionairfanimpeller 4 Glowplug 5 Cover 6 Heatexchanger 7 Combinationsensor(overheating/flamesensor) 8 Radioremotecontrol(mobileunit) 9 Radioremotecontrol(stationaryunit)10 Button11 Temperaturesensor(roomtemperature)12 Fusebracketwithmainfuseand“actuation”fuse13 Electricalmotor14 Fuelconnection15 Flangeseal
16 Combustionchamber17 Outlethood18 Combustionairhose19 Meteringpump20 Pot-typestrainer,installedinthedosingpump21 Outflow22 FlexibleexhaustpipeF= FreshairW= HotairA= ExhaustB= FuelV= Combustionair
Functionanduse2
6
Description of functions
Switching on
Whentheheaterisswitchedon,thecontrollampinthecon-trolunitlightsup.Theglowplugisswitchedonandthefanstartsatlowspeed.
fthereisstilltoomuchresidualheatintheheatexchangerfromwhentheheaterwaslastused,firstlyonlythefanstartsup(coldblowing).Oncetheresidualheathasbeencleared,theheaterstarts.
Starting Airtronic
Afterapprox.65secondsthefuelsupplystartsandthefuel/airmixtureinthecombustionchamberignites.Oncethecombinedsensor(flamesensor)hasdetectedtheflame,theglowplugisswitchedoffafter60seconds.Theheaterisnowinstandardoperation.
Starting Airtronic M
Afterapprox.60secondsthefuelsupplystartsandthefuel/airmixtureinthecombustionchamberignites.Aftertheflamesensorhasdetectedtheflame,theglowplugisswitchedoffafterapprox.90sec.Theheaterisnowinstandardoperation.Afteranother120seconds,theheaterhasreachedthe“POWER”stage(maximumfuelquantity,maximumfanspeed).
Temperature selection with the control element
Thecontrolcanbeusedtopreselectaninteriortemperature.Theresultingtemperaturecanbewithintherangeof+10°Cto+30°Canddependsontheselectedheater,onthesizeofthespacetobeheatedandontheprevailingoutdoortem-perature.Thesettingtobeselectedatthecontrolisanempiricalvalue.
Control in the heating mode
Duringtheheatingmode,theroomtemperatureorthetem-peratureofthesuckedinheatingairisconstantlymeasured.Ifthetemperatureishigherthanthetemperatureselectedonthecontrolelement,theheaterstartstoregulateitsoutput.Thereare4controlstagessothattheoutflowofheatpro-ducedbytheheatercanbeadjustedfinelytotheheatingrequirements.Fanspeedandfuelquantitycorrespondtotheparticularcontrolstage.Ifthesettemperatureisstillexceededinthesmallestcontrolstage,theheatergoestothe“OFF”stagewiththefanrunningonforapprox.4minutestocooloff.Thefanthencontinuesrunningatminimumspeed(circulationmode)untiltherestartorisswitchedoff(freshairmodewithexternaltemperaturesensor).
Ventilating mode
TheEasyStartR+andEasyStartTcontrolunitsandthemini-controllercanbeusedtoactivatethe„Ventilate“function.The„Heat/Ventilate“switchisalsorequiredforthemodulartimerandcontroldevicewhereby,forfanmode,the„Heat/Ventilate“switchmustbepressedfirstandthentheheaterswitchedon.Theblowerrunsatmaximumspeedinfanmode.
Switching off
Whentheheaterisswitchedoff,thecontrollampgoesoffandthefuelsupplyisswitchedoff.Thefanrunsonforapprox.4minutestocooldown.Whilethefanisrunningon,theglowplugisswitchedonforapprox.40secondstoclean.Specialcase:Ifnofuelhasbeensuppliedoriftheheaterisinthe“OFF”stageuntilitisswitchedoff,theheaterisstoppedwithoutanyafterrunning.
Functionanduse2
Please note!
7
Forced shut-down for ADR operation
Invehiclesforthetransportofdangerousgoods(e.g.tankertrucks),theheatermustbeswitchedoffbeforethetruckdrivesintoadangerarea(refinery,petrolstation,etc.).Failuretocomplyresultsintheheaterautomaticallyswitchingoffif:• thevehicleengineisswitchedoff,• anadditionalunitisstartedup(auxiliarydriveforunloading
pump,etc.),• avehicledoorisopened(ADR99regulation,onlyinFrance).Thefanthenrunsonformax.40seconds.
Functionanduse2
Emergency shutdown – EMERGENCY OFFIfanemergencyshutdown–EMERGENCYOFF–isre-quiredduringoperation,executethefollowing:• Switchtheheateroffatthecontrolelementor• removethefuseor• disconnecttheheaterfromthebattery.
Control and safety devices
• Iftheheaterdoesnotignitewithin90secondsafterstartingthefuelpump,thestartisrepeated.Iftheheaterstilldoesnotigniteafteranother90secondsofpumpingfuel,theheaterisswitchedoff,i.e.thefuelsupplyisoffandthefanrunsonforapprox.4minutes.
• Iftheflamegoesoffbyitselfduringoperation,theheaterisrestarted.Iftheheaterdoesnotignitewithin90secondsafterthefuelpumphasstarted,orignitesandgoesoffagainwithin15minutes,theheaterisswitchedoff,i.e.thefuelsupplyisoffandthefanrunsonforapprox.4minutes.Thisstatuscanberemediedbybrieflyswitchingoffandonagain.Donotrepeattheswitchingoff/onroutinemorethantwice.
• Inthecaseofoverheating,thecombinedsensor(flamesensor/overheatingsensor)triggers,thefuelsupplyisinterruptedandtheheaterswitchedoff.Oncethecauseoftheoverheatinghasbeeneliminated,theheatercanbere-startedbyswitchingoffandonagain.
• Iftheloweroruppervoltagelimitisreached,theheaterisswitchedoffafter20seconds.
• Theheaterdoesnotstartupiftheglowplugorblowermo-torisdefectiveoriftheelectricleadtothemeteringpumpisinterrupted.
• Ifthecombinedsensor(flamesensor/overheatingsensor)isdefectortheelectricleadinterrupted,theheaterstartsupandisthenswitchedoffagainduringthestartphase.
• Thespeedofthefanmotorismonitoredcontinuously.Ifthefanmotordoesnotstartuporifthespeeddeviatesbymorethan10%,theheaterisswitchedoffafter30sec.
• Whentheheaterisswitchedoff,theglowplugis switchedonfor40seconds(after-glowing)whilethe fanrunsontocleanoffanycombustionresidues.
Please note!
Donotrepeattheswitchingoff/onroutinemorethantwice.
8
Technichaldata3
Providednolimitvaluesaregiven,thetechnicaldatalistedissubjecttothetolerancesusuallyapplicabletoheatersof±10%fornominalvoltage,ambienttemperature20°CandreferencealtitudeEsslingen.
Caution!Safety instructions for technical data!Failuretocomplywiththetechnicaldatacanresultinmalfunc-tions.
Technichal data
Heatertype
Heater
Version
Heatingmedium
Controloftheheatflow
Heatflow(watt)
Heaterairflowratewithoutcounterpressure(kg/h) withhoodØ60mm
Fuelconsumption(l/h)
Elektr.powerconsumption(watt)
inoperation(12and24volt)
atstart(12and24volt)
Ratedvoltage
Operatingrange Lowervoltagelimit:Anundervoltageprotectioninthe
controllerswitchesofftheheaterwhenthevoltagelimitisreached.
Uppervoltagelimit: Anuppervoltageprotectioninthecontrollerswitchesoffthe
heaterwhenthevoltagelimitisreached.
Fuel
Tolarableambienttemperature
Heater
Dosingpump
Maximumairintaketemperature
Interferencesuppression
Weight
Ventilationmode
Airtronic
AirtronicD2/AirtronicD2Camper
D2/D2Camper
Air
Stage
Power Large Medium Small Off
2200 1800 1200 850 –
105 90 60 40 13
0.28 0.23 0.15 0.10 –
34 22 12 8 5
#100
12or24volt
approx.10.5voltresp.21voltUndervoltageprotectiontriggertime:20seconds
approx.16voltresp.32voltOvervoltageprotectiontriggertime:20seconds
DieselDINEN590(commerciallyavailable)
inoperation nooperation
–40°Cto+70°C –40°Cto+85°C
–40°Cto+50°C –40°Cto+125°C
max.+40°C
Interferencesuppressionclass5toDINEN55025
approx.2.7kg
possible
Please note!
9
Technichaldata3Technichal data
Heatertype
Heater
Version
Heatingmedium
Controloftheheatflow
Heatflow(watt)
Heaterairflowratewithoutcounterpressure(kg/h) withhoodØ90mm
Fuelconsumption(l/h)
Elektr.powerconsumption(watt)
inoperation(12and24volt)
atstart(12and24volt)
Ratedvoltage
Operatingrange Lowervoltagelimit:Anundervoltageprotectioninthe
controllerswitchesofftheheaterwhenthevoltagelimitisreached.
Uppervoltagelimit: Anuppervoltageprotectioninthecontrollerswitchesoffthe
heaterwhenthevoltagelimitisreached.
Fuel
Tolarableambienttemperature
Heater
Dosingpump
Maximumairintaketemperature
Interferencesuppression
Weight
Ventilationmode
Airtronic M
AirtronicB4
B4
Air
Stage
Power Large Medium Small Off
3800 3200 2100 1300 –
185 160 120 85 24
0.54 0.46 0.29 0.18 –
40 29 15 9 5
#100
12volt
approx.10.5voltUndervoltageprotectiontriggertime:20seconds
16voltOvervoltageprotectiontriggertime:20seconds
PetrolDINEN228(commerciallyavailable)
inoperation nooperation
–40°Cto+50°C –40°Cto+85°C
–40°Cto+20°C –40°Cto+125°C
max.+40°C
Interferencesuppressionclass5toDINEN55025
ca.4.5kg
possible
Providednolimitvaluesaregiven,thetechnicaldatalistedissubjecttothetolerancesusuallyapplicabletoheatersof±10%fornominalvoltage,ambienttemperature20°CandreferencealtitudeEsslingen.
Caution!Safety instructions for technical data!Failuretocomplywiththetechnicaldatacanresultinmalfunc-tions.
Please note!
10
Technichaldata3Technichal data
Heatertype
Heater
Version
Heatingmedium
Controloftheheatflow
Heatflow(watt) D3
D4
D4Plus
Heaterairflowratewithoutcounterpressure(kg/h) D3withhoodØ90mm
D4withhoodØ90mm
D4PluswithhoodØ75mm
Fuelconsumption(l/h) D3
D4
D4Plus
Elektr.powerconsumption(watt) D3
inoperation(12and24volt) D4
D4Plus
atstart(12and24volt)
Ratedvoltage
Operatingrange Lowervoltagelimit:Anundervoltageprotectioninthe
controllerswitchesofftheheaterwhenthevoltagelimitisreached.
Uppervoltagelimit: Anuppervoltageprotectioninthecontrollerswitchesoffthe
heaterwhenthevoltagelimitisreached.
Fuel
Tolarableambienttemperature
Heater
Dosingpump
Maximumairintaketemperature
Interferencesuppression
Weight
Ventilationmode
Airtronic M
AirtronicD3/AirtronicD4/AirtronicD4Plus
D3/D4/D4Plus
Air
Stage
Power Large Medium Small Off
3000 2200 1600 900 –
4000 3000 2000 900 –
4000 3000 2000 900 –
150 120 90 60 24
185 150 110 60 24
175 140 100 55 22
0.38 0.28 0.2 0.11 –
0.51 0.38 0.25 0.11 –
0.51 0.38 0.25 0.11 –
24 16 10 7 5
40 24 13 7 5
55 30 16 7 5
#100
12or24volt
approx.10.5voltresp.21voltUndervoltageprotectiontriggertime:20seconds
approx.16voltresp.32voltOvervoltageprotectiontriggertime:20seconds
DieselDINEN590(commerciallyavailable)
inoperation nooperation
–40°Cto+70°C –40°Cto+85°C
–40°Cto+50°C –40°Cto+125°C
max.+40°C
Interferencesuppressionclass5toDINEN55025
approx.4.5kg
possible
Providednolimitvaluesaregiven,thetechnicaldatalistedissubjecttothetolerancesusuallyapplicabletoheatersof±10%fornominalvoltage,ambienttemperature20°CandreferencealtitudeEsslingen.
Caution!Safety instructions for technical data!Failuretocomplywiththetechnicaldatacanresultinmalfunc-tions.
Please note!
11
Technichaldata3Technichal data
Heatertype
Heater
Version
Heatingmedium
Controloftheheatflow
Heatflow(watt) D4S
D4Camper/D4CamperPlus
Heaterairflowratewithoutcounterpressure(kg/h) D4S
D4Camper/D4CamperPlus
Fuelconsumption(l/h)) D4S
D4Camper/D4CamperPlus
Elektr.powerconsumption(watt) D4S
inoperation(12and24v) D4Camper/D4CamperPlus
atstart(12and24v)
Ratedvoltage
Operatingrange Lowervoltagelimit:Anundervoltageprotectioninthe
controllerswitchesofftheheaterwhenthevoltagelimitisreached.
Uppervoltagelimit: Anuppervoltageprotectioninthecontrollerswitchesoffthe
heaterwhenthevoltagelimitisreached.
Fuel
Tolarableambienttemperature
Heater
Dosingpump
Maximumairintaketemperature
Interferencesuppression
Weight
Ventilationmode
Airtronic M
AirtronicD4S/Airtronic D4Camper/AirtronicD4CamperPlus
D4S/D4Camper/D4CamperPlus
Air
Stage
Power Large Medium Small Off
3500 3000 2000 1000 –
4000/3500 3000 2000 900 –
160 140 100 60 22
185/160 150/140 110/100 60/55 24/22
0.44 0.38 0.25 0.13 –
0.51/0.44 0.38 0.25 0.11 –
40 30 16 8 5
40 24/30 13/16 7/8 5
#100
12or24volt
approx.10.5voltresp.21voltUndervoltageprotectiontriggertime:20seconds
approx.16voltresp.32voltOvervoltageprotectiontriggertime:20seconds
DieselDINEN590(commerciallyavailable)
inoperation nooperation
–40°Cto+70°C –40°Cto+85°C
–40°Cto+50°C –40°Cto+125°C
max.+40°C
Interferencesuppressionclass5toDINEN55025
approx.4.5kg
possible
Providednolimitvaluesaregiven,thetechnicaldatalistedissubjecttothetolerancesusuallyapplicabletoheatersof±10%fornominalvoltage,ambienttemperature20°CandreferencealtitudeEsslingen.
Caution!Safety instructions for technical data!Failuretocomplywiththetechnicaldatacanresultinmalfunc-tions.
Please note!
12
Check values
Test speed for the blower
Airtronic D2 / D2 Camper(12volt/24volt)• 12volt 5000rpm±25% atU=10,0volt• 24volt 5000rpm±25% atU=18,0volt
AirtronicB4 (12volt)AirtronicD3 / D3 Camper(12volt)AirtronicD4(12volt/24volt)AirtronicD4 Camper(12volt)• 12volt 4400rpm±25% atU=10,0volt• 24volt 4400rpm±25% atU=18,5volt
AirtronicD4S/Airtronic D4 Plus (12volt/24volt)AirtronicD4 Camper Plus (12volt)• 12volt 4400rpm±25% atU=10,5volt• 24volt 4400rpm±25% atU=19,0volt
Resistance values at 20 °C
12 volt 24 volt
Glowplug 0.42 –0.70 1.2 –2.0Dosingpump 9.5±0.50 36.0±1.8
Control unit resistance values
Switch position, left limit stop
Switch position, right limit stop
Controldevice12volt/24volt
min.1720max.1760
min.2096max.2216
Modulartimerandmini-controller12volt/24volt
min.1730max.1780
min.2120max.2240
Switching value Overheatingsensor 140°C–170°C measuredinthe“High”controlstage andatadistanceof300mmdownstream fromthehotairoutletExhaust emission specificationCO2 in exhaustincontrolstage“high” 7,5–12,5Vol.%SmokespotnumberaccordingtoBacharach <4
Temperature (°C)
Res
ista
nce
(ohm
)
2200
2000
1800
1600
1400
1200
1000±40 ±20 0 20 40±10±30 10 30
2400
50
Technicaldata3
Check “external” temperature sensor(OrderNo.:251774890300)The“external”temperaturesensortestmustbecarriedoutusingadigitalmultimeter.Iftheresistancevalueisnotthesameasthecurveinthediagramorthetableofvalues,re-placethetemperaturesensor.
Table of values – “external” temperature sensor
Temperature°C Resistance
min. max.0 1600 16605 1670 1730
10 1745 180015 1820 187020 1895 195025 1970 203030 2050 211035 2130 219040 2210 228045 2295 2370
13
Troubleshooting4What to check first in case of faults
• Check– Fuelinthetank?– Fuelpipesleaking?(visualcheck)– Summerdieselinthefuelpipe?– Combustionairsystemorexhaustsystemdamagedor
blocked?– Hotairsystemblocked?– Airpressuresensorinstalled?Ifyes,referto„Whattodo
if…?“chapterofthe„AltitudeKit“installationinstructions.– Newgenerationcontrolboxinstalled? Features: >Cableloomofcontrolboxwoundwithcabletie >Temperaturesensormountedonthesideofthecontrol
box(visiblewhencoverremoved)
• Electrical components– Cables,connectionsdamaged?– Contactscorroded?– Fusesdefective?– Incorrectwiring?(shortcircuits,interrupted/broken)
• Measure battery voltage– Batteryvoltage<10.5volt,theundervoltageprotectionof
the12voltheaterhastriggered.– Batteryvoltage<21volt,theun
• Measure voltage supply (Cl 30) Disconnectthe16-pinconnectorS1/B1andmeasurethe
voltageappliedatconnectorB1betweenchamber1(cable2.52rt)andchamber10(cable2.52br).
Ifitdiffersfromthebatteryvoltage,checkthefuses,thesupplycables,thenegativeconnectionandthepositivesupportpointonthebatteryforvoltagedrop(corrosion/interruption).
• Check switch-on signal Disconnectthe16-pinconnectorS1/B1andthenswitch
ontheheateratthecontrolunit. CheckwhethervoltageisappliedintheconnectorB1
betweenchamber4(cable0.52ge)andchamber10(cable2.52br).
Ifnovoltageismeasured,thencheckthesupplycable(ca-ble0.52ge),the5Afuse(item2.7.1inthecircuitdiagram)andthecontrolunit.
• Check control unit
Control device, mini-timer, mini-controller and modular timer
Disconnecttheconnectoratthecontrolunit;installajumperbetweenthered0.5²rtcableandtheyellow0.5²gecable.
IfavoltageismeasuredinconnectorB1betweencham-ber4(cable0.5²ge)andchamber10(cable2.5²br),thenreplacethecontrolunit.
EasyStart R+ / EasyStart R / EasyStart T Disconnecttheconnectoratthecontrolunit;installajumper
betweentheyellow0.5²gecableandthered0.5²rtcable. IfavoltageismeasuredinconnectorB1betweencham-
ber8(cable0.5²ge)andchamber10(cable2.5²br),thenreplacethecontrolunit.
14
Troubleshooting4Overview of the test equipment and control units suitable for diagnosis
Theelectroniccontrolboxcanstoreupto5faults,whichcanbereadoutanddisplayed.Thefollowingtestequipmentand/orcontrolunitscanbeusedtoquerythefaultmemoryinthecontrolboxandifnecessarytodeletethelockingofthecontrolbox:
Test equipment Order No.:
• Testingdevice forthecontroldevice 221509890000
• Diagnosticunit 221529890000 additionallyrequired: Adaptercable 221000318600
• EDiTHdiagnostictool – Basicadapterwithsoftware 221542890000 additionallyrequired: Airtronicextension 221537890000
– ISO-adapter 221541890000 additionallyrequired: Adaptercable 221000318600
– „Airpressuresensor“adaptercable221000333100 Onlyforheaterswithconnectedairpressuresensorfor
readingoutthe„airpressuresensor“faultmemory.
Ifadiagnosticscableisconnected,thefollowingcontrolunitscanalsobeused:
Control units Order No.:
• Moduletimer 221000303400
• TP5radioremotecontrol 221000320100
• EasyStartT 221000328800
• EasyStartR+ 221000328000
Please note!
Ifthefaultmemorycannotbereadout,checkthediagnosticscableforcorrectlayingandpossibledamage.
Important notes on diagnosis of heaters with mini-controller control unit
Caution!WhencheckingtheheaterwiththediagnosticsunitortheEDiTHdiagnosticstooltheordergiveninthefollowingnotesmustalwaysbefollowedasotherwisetheheaterdetectsError62(controlunit–interruption)andswitchestoemergencyoperation.
Mini-controller in stand-alone operation
• Connectadaptercable221000318600asdescribedintheoperatinginstruction.
• Selectoperatingmode(Heat/Ventilate)atthemini-control-ler
• PerformdiagnosisusingthediagnosticsunitortheEDiTHdiagnosticstool.
• Switchoffthemini-controllerafterfinishingthediagnosis• Removetheadaptercable
Mini-controller in combination with mini-timer
• Connectadaptercable221000318600asdescribedintheoperatinginstruction.
• Pressthembuttonofthemini-timer• Selectoperatingmode(seemini-timeroperatinginstruc-
tions)• PerformdiagnosisusingthediagnosticsunitortheEDiTH
diagnosticstool.• Switchoffthemini-timerafterfinishingthediagnosis• Removetheadaptercable
Mini-controller in combination with TP5
• Connectadaptercable221000318600asdescribedintheoperatinginstruction.
• Pressthe buttonoftheTP5radioremotecontrol• Selectoperatingmode(seeTP5radioremotecontroloper-
atinginstruction)• Performdiagnosis.• SwitchoffTP5radioremotecontrolafterfinishingthediag-
nosis• Removetheadaptercable
Please note!
IftheoperatingmodeistobechangedduringthetesttheheatermustbeswitchedofffirstusingthediagnosticsunitortheEDiTHdiagnosticstool,otherwisetheheaterdetectsError62(controlunit–interruption)andswitchestoemergencyoperation.
Test mini controller
Themini-controllermustbeconnectedtotheheaterfortest-ing.ThesetpointvaluecanbedisplayedusingtheEDiTHdiagnosticstool.Iftherotaryknobisattheleftlimitstopthesetpointvalueis8°C,attherightlimitstopitis34°C.
Please note!
Theresistanceofthesetpointvaluepotentiometercannotbemeasureddirectly.Themeasuredvaluesarenotmeaningful.
15
Troubleshooting4Testing device for the control device(OrderNo.:221509890000)
Prepare for testConnectthecorrectoperatingvoltage(12or24volt)tothete-stingdevice,withplusattheredconnectorsocketandminusattheblueconnectorsocket.
• Disconnectsocketfromthecontrolunit.• Connectcableloomfromtestingdevicewiththecontrol
unit.• Settherotaryknobofthecontrolunitto“Heat”,thecorre-
spondingredLEDinthetestingdevicemustlightup.• Setcontrolunitto“0”,thenpressthe“LED–red”button,
theredcontrollampinthecontrolunitmustlightup.• Setcontrolunitto“Heat”,thenpressthe“LED–green”
button,correspondingredcontrollampinthetestingdeviceandthegreencontrollampinthecontrolunitmustlightup.
Caution!Safety instructions for checking the control unit!Ensureyouusethecorrectoperatingvoltage,otherwisetheconnectedcomponentscanbeseverelydamaged.
Check the setpoint potentiometer of the control unitSetthe“Temperaturesensor/Potentiometer”switchinthetestingdevicetothe“Potentiometer”settingandslowlyturntherotaryknobofthecontrolunit.ThegreenLED–temperaturesensor/potentiometermustlightupcontinuously.Incaseofafault,replacethecontrolunit.
1 Testingdevice2 Controldevice
Diagnostic unit(OrderNo.:221529890000)
Anadditionaladaptercableisrequiredtoconnectthediag-nosticunit(OrderNo.:221000318600).
Thecurrentfaultisdisplayedas“AF”anda2-digitnumberandisalwayswritteninthememorypositionF1.PrecedingfaultsaremovedtothememorylocationsF2–F5,ifnecessarythecontentsofmemorypositionF5isoverwrit-ten.
• Notonlythedefectivecomponent,butalsoadefectivecur-rentcircuitresultsinafaultbeingdisplayed.
• Inheaterswithconnectedairpressuresensorthediagnos-ticsunitcanbeusedtoreadoutthefaultmemoryoftheheateronly.
Thefaultmemoryofthe„airpressuresensor“canbereadoutusingtheEDiTHdiagnosticstoolonly.
• Faultcode,faultdescription,cause/remedialactionaredescribedonPages23–27.
l–Deletefaultmemoryl–Deletefaultmemoryd–Switchheateron/off,requestdiagnosise–Reverse,F5–F1f–Forward,F1–F5,currentfault(AF)
Connectdiagnosticsunit,seepage16.
Please note!
16
Connect diagnostic unit• Disconnectthe8-pinconnectoroftheheater’scablehar-
nessandconnecttheadaptercable.• Connectthediagnosticunittotheadaptercable. Displayisasfollows:
Query fault memory• UsetheDkeytoswitchontheheater. Displayisasfollows:
• After8secthefollowingisdisplayed: Displayisasfollows:
Heaterhasnomalfunction or
e.g.currenterror/faultcode64
or
Faultdiagnosisnotpossible
Possiblecauses: – Adaptercableisnotproperlyconnected. – Controlboxisdefectiveorisnotcapableofdiagnosing
(notauniversalcontrolbox).
Display of the fault memory F1 – F5 or F5 – F1• Presstheeorfbutton,orpressseveraltimes,todisplay
thefaultmemory. Displayisasfollows:
e.g.faultmemory2/faultcode10
Onlythefaultmemorypositionswithanerrorassignedtothemaredisplayed.
Delete fault memory• PressbothLbuttonssimultaneouslyuntilthefollowingap-
pearsinthedisplay: Displayisasfollows:
• Ifthefaultmemoryhasbeendeletedthemostrecentcur-rentfaultisdisplayed.Thecurrentfaultisnotresetto00untiltheheaterisrestarted–providedthereisnonew,morerecentfault.
Displayisasfollows:
Heaterhasnomalfunction
Cancel the control box lock• Deletethefaultmemoryasdescribedandswitchoffthe
heaterusingthedkey.• Thecontrolboxlockiscancelledandthediagnosisclosed. Displayisasfollows:
Troubleshooting4
1 Heater2 Adaptercable3 Diagnosticunit
1
2
3
Please note!
17
Troubleshooting4EDiTH diagnostic tool with ISO adapter(OrderNo.:221541890000)
AnadditionaladaptercableisrequiredtoconnecttheISOadapter(OrderNo.:221000318600).
• Itisveryimportanttoalwaysinstallinthegivenorder.• Notonlythedefectivecomponent,butalsoadefectivecur-
rentcircuitresultsinafaultbeingdisplayed.• Faultcode,faultdescription,cause/remedialactionare
describedonPages23–27.• TheEDiTHdiagnosticstoolscopeofsupplydoesnot
includethesoftware;thismustbedownloadedfromtheServicePortal.
Connect ISO adapter
• Disconnecttheheater’scableharness.• Connecttheadaptercabletothecableharness–asshown
inthesketch.• ConnecttheadaptercabletotheISOadapter.• ConnecttheSUB-DconnectioncablewiththePCandthe ISOadapter.
Installing the software on your PC• Doubleclickthe“setup.exe”filetostarttheinstallationand
followingtheSETUPprograminstructions.
Query / delete fault memory F1 – F5 or cancel the control box lock• StartthesoftwareonyourPC: – onthedesktop—>doubleclickthe“EDiTH”icon – Selectheatertype – Pressthe“GO”button.
• Deletefaultmemoryorcancelthecontrolboxlock: – pressthe“Deletefaultmemory”button —>thestoredfaultsF1–F5aredeletedandthecontrol
boxisunlocked.
Quit diagnosis• Pressthe“STOP”button—>faultmemoryqueryisended.
1 Heater2 Adaptercable3 ISOadapter
4 SUB-Dconnectioncable5 USBtoSerialRS-232adapter
� �
�
�
�
Please note!
18
Troubleshooting4Air pressure sensor diagnosis using EDiTH diagnostics tool and ISO adapter(OrderNo.221524890000)
AnadditionaladaptercableisrequiredtoconnecttheISOadapter(OrderNo.:221000333100).
Theairpressuresensorconnectedtotheheatercanbediag-nosed.Iffaultsoccurduringthealtitudeadjustmenttheyarestoredintheairpressuresensor.Ifnecessary,faultscanbereadoutusingtheISOadapterinconjunctionwiththeEDiTHdiagnosticstool–fromVersionS3V7-F–andtheadditionallynecessaryadaptercable.
Please note!
• Itisveryimportanttoalwaysinstallinthegivenorder.• Notonlythedefectivecomponent,butalsoadefectivecur-
rentcircuitresultsinafaultbeingdisplayed.• Faultcode,faultdescription,cause/remedialactionare
describedonpages27.• TheEDiTHdiagnosticstoolscopeofsupplydoesnot
includethesoftware;thismustbedownloadedfromtheServicePortal.
Perform diagnosis of the air pressure sensor
Disconnecttheconnectorbetweentheairpressuresensor/heater,controlunit,connecttheISOadapterwiththeadaptercable(seesketch).Startthediagnosisoftheairpressuresensor.
• Double-clickthe>>EDiTH
19
Caution! Magnetic field!Duringthetestoperationamagneticfielddevelopsattheadapter.Therefore,donotplaceanyobjectssuchasdatamedia,creditcards,etc.ontheadapterorinitsimmediatevicinity.
Troubleshooting4
(A) Basicadapter(B) SUB-Dconnectioncable(C) Mainsconnection(D) Mainsswitch(E) USBtoSerialRS-232adapter(F) Adapter(G) Controlbox
Cable colourssw = blackgn = greenbl = blue
EDiTH diagnostic tool with basic adapterEDiTHbasicadapter(OrderNo.:221542890000)
Anadditionalextensionisrequiredtocheckthecontrolbox(OrderNo.:221537890000).
• Itisimportanttoalwaysfollowthepreciseconnectionorderasgivenbelow!
• TheHallsensorintegratedinthecontrolboxcanonlybeproperlytestedinthecontrolboxiscorrectlyplacedontheextension.
• Onlypushorpullontheconnectors,notonthecables!• OnlyusethenetworkcableandRS232cablewithsnap
ferritesincludedinthescopeofsupply.Useoriginalacces-sorieswithsnapferritesonlytoconnectthetestequipment.
• Notonlythedefectivecomponent,butalsoadefectivecurrentcircuitresultsinafaultbeingdisplayed.
• Faultcode,faultdescription,cause/remedialactionaredescribedonPages23–27.
Connect basic adapter• Startcomputerandwaituntilthesystemhassuccessfully
booted.• StartPCsoftware.• Inserttheunitconnectorofthemainscableinthebasic
adapter(A)andconnectthemainsconnection(C)tothemains.
• ConnecttheSUB-Dconnectioncable(B)withthePCandbasicadapter(A).
Connect extension and test control box• Connecttheextensiontothebasicadapter(A).• Connectthecontrolbox(E)totheextensionandtheadap-
ter(F).• Switchonthebasicadapter(A)atthemainsswitch(D).• Selectthecontrolboxversionandoperatingvoltage
(12V/24V)inthePCsoftware.• StartthecontrolboxtestwiththePCsoftware.Amorede-
taileddescriptionofhowtooperatethebasicadapters(A)isgivenintheEDiTHonlinehelp.
Please note!
20
Troubleshooting4Module timer(OrderNo.:221000303400)
Thecurrentfaultisdisplayedas“AF”andisalwayswritteninmemorypositionF1.PrecedingfaultsaremovedtothememorylocationsF2–F5,ifnecessarythecontentsofmemorypositionF5isoverwrit-ten.
• Notonlythedefectivecomponent,butalsoadefectivecur-rentcircuitresultsinafaultbeingdisplayed.
• Inheaterswithconnectedairpressuresensorthemodulartimercannotbeusedtoperformdiagnoses.Thediagnos-ticsunitortheEDiTHdiagnosticstoolmustbeusedtoperformthediagnosis.
Thefaultmemoryofthe„airpressuresensor“canbereadoutusingtheEDiTHdiagnosticstoolonly.
• Faultcode,faultdescription,cause/remedialactionaredescribedonPages23–27.
Query fault memory F1 – F5 Condition:Theheaterisswitchedoff.
• Pressckey–>theheaterisswitchedon.
• Pressakeyandkeeppressed, thenpresspkeywithin2seconds. Displayisasfollows: AF=currentfault 3digitnumber=faultcode cflashes.
• Pressfkeyonceorseveraltimes,faultmemorypositionsF1–F5aredisplayed.
Cancel the control box lock and simultaneously delete the fault memoryCondition:Anelectricalconnectionexistsfromterminal15(ignition)tothemoduletimer,12-pinconnector,chamber10.
• Pressckey Displayisasfollows: thecurrentfaultF15orF50.
• Pressbuttona,keepitdepressedandthenpressbuttonpwithin2seconds.
Themoduletimerisnowinthe“Queryfaultmemory”pro-gram.
• Switchoffignition(terminal15).
• Simultaneouslypressbuttonaandbuttonp,inaddition,switchontheignition(terminal15)andwaituntilthefollow-ingappearsinthedisplay.
Afterignition“ON”thefollowingappearsinthedisplay:
Displayflashes, Heatersymboldoesnotflash
• Switchtheheateroffandon–>thecontrolboxisunlocked,theheaterrestarts.
Afterswitchingtheheateroffandonandrenewedqueryofthefaultmemory,thefollowingappearsinthedisplay:
Displayflashes, Heatersymboldoesnotflash
a–Timep–Presetc–Heate–Reversef–Forward
Please note!
21
Troubleshooting4TP5 radio remote control(OrderNo:221000320100)
Iffaultsoccurwhiletheheaterisrunning,theyaredisplayedwith“Err”afterthemobileunitisactivated.
Afterthediagnosticscable(bl/ws)hasbeenconnectedandthefirstlogshavearrivedatthestationaryunit,thediagnosecanbecarriedoutusingthemobileunitoftheTP5radioremotecontrol.Thecurrentfault“F0”isdisplayed.Thestoredfaults“F1”to“F5”canbequeried.
• Inordertocarryoutthediagnosis,thediagnosticscable(bl/ws)mustbeconnectedtothestationaryunitandtheheatercableharness.Tothisend,pleaserefertoandfollowthecircuitdiagramfortheTP5radioremotecontrolandtheheater.
• Ifthediagnosticscable(bl/ws)isnotconnected,the“Diag-nosis”menuisblocked.
• Notonlythedefectivecomponent,butalsoadefectivecur-rentcircuitresultsinafaultbeingdisplayed.
• InheaterswithconnectedairpressuresensortheTP5radioremotecontrolcannotbeusedtoperformdiagnoses.ThediagnosticsunitortheEDiTHdiagnosticstoolmustbeusedtoperformthediagnosis.
Thefaultmemoryofthe„airpressuresensor“canbereadoutusingtheEDiTHdiagnosticstoolonly.
• Faultcode,faultdescription,cause/remedialactionaredescribedonPages23–27.
Buttontoactivate/deactivatethemobileunit
Buttonforforwardtimesetting
Buttonforbackwardtimesetting
Buttonforactivatingthepossiblesettings
Buttonforswitchingheat/ventilateON/OFF; Activate/deactivatepreselectedtime
Enquire / delete fault memoryUsethe keytoactivatethemobileunit.Switchontheheaterwiththe key.Pressthe keytwicetoopentheTimesettingmenu–thetimeflashesinthedisplay.
Pressthe keyforapprox2sec–untilthefollowingap-pearsinthedisplay:
Press key.Press key.Press keytwice.Press key.
Malfunctioninheater: Heaterhasnomalfunction:
Usethe and buttonstocallupthefaultmemoryposi-tions1to5.
Delete fault memory / Cancel the control box lockUsethe keytodeletethefaultmemory.
Toconfirm,pressthe keyforapprox2secuntil lightsupinthedisplay–faultmemoryisdeleted.
Please note!
22
The following actions are possible• Callupfaultmemory. CallupthefaultmemorypositionsF1–F5with or .
• Callupfaultmemoryagain. Brieflypress and simultaneously.
• Deletefaultmemory (displaydEL) Press .
Press again.
The diagnosis is completed.
Switch off heater.
Enquire / delete fault memoryActivatemobilepart/timer(seeEasyStartR+/EasyStartToperatinginstructions)
Confirmsymbol with .
Heater is switched on.
Confirmoperatingtimewith .
Brieflypress and simultaneously.
Troubleshooting4EasyStart R+ radio remote control(Order-No.:221000328000)
EasyStart T timer(Order-No.:221000328800)
Iffaultsoccurwhiletheheaterisrunning,theyaredisplayedwith“Err”afterthemobileunitortimerisactivated.
Thecurrentfaultisdisplayed.Thestoredfaults“F1”to“F5”canbequeried.
• Inordertocarryoutthediagnosis,thediagnosticscable(bl/geatheaterconnector,bl/wsatcableharnessconnector)mustbeconnectedtothestationaryunitandtheheatercableharness.Tothisend,pleaserefertoandfollowthecircuitdiagramfortheradioremotecontrolandtheheater.
• Ifthediagnosticscableisnotconnected,the“Diagnosis”menuisblocked.
• Notonlythedefectivecomponent,butalsoadefectivecur-rentcircuitresultsinafaultbeingdisplayed.
• Theheaterdiagnosiscanalsobeperformediftheairpres-suresensorisconnected.
Thefaultmemoryofthe„airpressuresensor“canbereadoutusingtheEDiTHdiagnosticstoolonly.
• Faultcode,faultdescription,cause/remedialactionaredescribedonPages23–27.
Backcontrolkey
Nextcontrolkey
ON/OFFactivationkeymobileunit/timer
OKkey(symbolselection/confirminput)
Please note!
23
Troubleshooting4Fault codeDisplay
Fault description Comments• Remedial action
000 Nofaults ——
004 Warning:Shortcircuitincontrolbox,freshairoutput
• DisconnectconnectorS1/B1attheheaterandattheconnectorB1,PIN16checkthecableuptothefreshairfanrelayforshortcircuittonegative,ifok—>replacecontrolbox.
005 Warning:Shortcircuitincontrolbox,caralarmoutput
• DisconnectconnectorS1/B1attheheaterandattheconnectorB1,PIN15checkthecableuptotherelayisolatingswitchorburglaralarmsysteminputforshortcircuittonegative,ifok—>replacecontrolbox.
006 Warning:Inexplicableatmosphericaltitudeinformation(Displayonlyifheaterslabelled“H-Kit”onthenameplate.)
Controlboxhasnotreceivedanyexplicablealtitudeinformation.• ReadoutfaultmemoryintheairpressuresensorusingtheEDiTHdiagnos-
ticstoolandcorrectfault.
009 Cut-offADR ADRshutdownduetosignalchangefrom(+)to(–)atconnectorS1,PIN13(D+)orplussignalatconnectorS1,PIN14(HA+).
010 Overvoltage–cut-off Overvoltageappliedtocontrolboxforatleast20secondswithoutinterruption–heaternotworking.• DisconnectconnectorS1/B1attheheater,startthevehicle’sengine,
measurethevoltageatconnectorB1betweenPIN1(cable2.52rt)andPIN10(cable2.52br).
Airtronic12volt–voltage>16volt—>checkgeneratorregulator Airtronic24volt–voltage>32volt—>checkgeneratorregulator
011 Undervoltage–cut-off Undervoltageappliedtocontrolboxforatleast20secondswithoutinterrup-tion–heaternotworking.• DisconnectconnectorS1/B1attheheater,thevehicle’sengineisswitched
off,measurethevoltageatconnectorB1betweenPIN1(cable2.52rt)andPIN10(cable2.52br).
Themeasuredvalueandthevoltageatthebatteryshouldbethesame. Incaseofavoltagedrop,checkthefuses,thesupplycables,thenegative
connectionsandthepositivesupportpointonthebatteryforcorrosionandcorrectcontact.
012 Overheatingattheoverheatingsensor Temperatureoftheoverheatingsensortoohigh.• Checkhotairpipesforblockage—>removeblockage.• Sumofthecomponentratingsofair-conductingpartsistoolarge—>
Checkairsystem,ifnecessaryre-lay–forcomponentratings,pleaserefertoadditionalpartscatalogue.
• Checkoverheatingsensor,fordiagramandtableofvaluespleaserefertoPage32,ifok—>measurefuelquantity,seePage36.
013 Overheatingattheflamesensor Flamesensorsignalstemperatureatheatexchangeristoohigh.• Checkhotairpipesforblockage—>removeblockage.• Sumofthecomponentratingsofair-conductingpartsistoolarge—>
Checkairsystem,ifnecessaryre-lay–forcomponentratings,pleaserefertoadditionalpartscatalogue.
• Checkflamesensor,ifok—>checkoverheatingsensor,ifoverheatingsensordefective—>replacecombinationsensor,ifoverheatingsensorok—>measurefuelquantity,seePage36,fordiagramandtableofvaluesforflamesensorandoverheatingsensorpleaserefertoPage32.
014 Temperaturedifferencebetweenflamesensorandoverheatingsensortoolarge
Temperaturedifferencebetweenflamesensorandoverheatingsensortoolarge• Checkhotairpipesforblockage—>removeblockage.• Sumofthecomponentratingsofair-conductingpartsistoolarge—>
Checkairsystem,ifnecessaryre-lay–forcomponentratings,pleaserefertoadditionalpartscatalogue.
• Checkflamesensor,ifok—>checkoverheatingsensor,ifoverheatingsen-sordefective—>replacecombinationsensor,ifoverheatingsensorok—>measurefuelquantity,seePage36,iffuelquantityok—>replacecontrolbox.Fordiagramandtableofvaluesforflamesensorandoverheatingsen-sor,seePage32.
24
Troubleshooting4Fault codeDisplay
Fault description Comments• Remedial action
015 Operatinglock-out Thefaultcode015isdisplayed,iftheheaterwasswitchedbackonafterthefaultcodedisplay017.
Thehardwarethresholdvaluefortheoverheatingsensorhasbeenexceeded—>thecontrolboxislocked.
• Replacecontrolbox.
017 Overheating Thehardwarethresholdvaluefortheoverheatingsensorhasbeenexceeded,becausethecontrolboxfailedtorecognisethefaultcode012or013–>thecontrolboxislocked.Iftheheaterisswitchedonagain,thefaultcode015isdisplayed.• Replacecontrolbox.
018 Startingenergyoftheglowplugistoolow(Displayonlyifheaterslabelled“H-Kit”onthenameplate.)
• Checkglowplug(seefaultcode020and021),ifok• Checkglowplugcableharnessforcorrectlayinganddamage,ifok—>
checkcableharnessforcontinuity,ifok—>replacecontrolbox.
019 Ignitionenergytoolow • Checkglowplug(seefaultcode020and021),ifok• Checkglowplugcableharnessforcorrectlayinganddamage,ifok—>
checkcableharnessforcontinuity,ifok—>replacecontrolbox.
020
021
Glowplug–interruption
Glowplug–shortcircuit,overloadorshortcircuitafternegative
• Checkglowplugforfunctionandcontinuityatambienttemperature20°C. 12voltheater–0.42upto±0.7 24voltheater–1.2upto±2.0
• Ifthevaluesareok—>checkglowplugleadharnessfordamageandcon-tinuity,ifok—>replacecontrolbox.
022 * Glowplug,output(+)–shortcircuitafterUB(batteryvoltage)
• Checkglowplugleadharnessforcorrectlayinganddamage,ifok—>checkleadharnessforcontinuity,ifok—>replacecontrolbox.
025 * Diagnosticscablebl/ws–shortcircuit–afterUB(batteryvoltage)
Faultcodedisplayisnotpossible.Thisfaultcodecannotbereadoutfromthefaultmemoryuntilthefaulthasbeencorrected.• Checkdiagnosticscableforcorrectlayingandpossibledamage.
031 Blower–interruption • Checkthattheleadharnessoftheblowermotorhasbeencorrectlylaidandcheckfordamage,ifok—>removeleadharnessatcontrolboxandcheckforcontinuity,ifok—>replacecontrolbox.
032 Blowermotor–shortcircuitafternegative
Please note!
Ensurecompliancewiththetestvolt-age(seepage12).Thecomponentisdestroyedifthevoltagevalueisexceeded.Ensure the power pack has ad-equate short-circuit resistance – min 20 A.
• Carryoutfunctionaltestontheblowermotor,todothisremovethecon-nectorfromthecontrolbox.Applyatestvoltage(seepage12)totheblow-ermotorandmeasurethecurrentintensityafter40sec.
Currentintensity<6.5A–blowermotorok–>replacecontrolbox. Currentintensity>6.5A—>replaceblower.• Checkwiringforshortcircuit.
033 Blowermotorwon’trotateorshortcircuitafternegative
Please note!
Ensurecompliancewiththetestvolt-age(seepage12).Thecomponentisdestroyedifthevoltagevalueisexceeded.Ensure the power pack has ad-equate short-circuit resistance – min 20 A.
Speeddeviation>10%fromsetpointvalueforlongerthan30seconds.Useanon-contactr.p.m.countertomeasurethespeedofthecombustionair
fan(seepage12fortestspeedandtestvoltage).• Speedtoolow: Blowerblocks–checkblowerforfreerunning,ifnecessaryremoveforeign
body,ifok—>checkblower(seefaultcode032).• Speedtoohigh: – Magnetmissingfromblowerimpeller—>replaceblower. – Speedsensorincontrolboxisdefective—>replacecontrolbox.• Checkwiringforshortcircuit.
* Thisfaultcodeorohmicvalueisvalidforanewgenerationcontrolboxonly.Thisdiffersfromthecontrolboxtodatebyitscableloomwrappedincabletapeandbyatemperaturesensormountedontheside,whichbecomesvisiblewhenthecoverisremoved.
25
Troubleshooting4Fault codeDisplay
Fault description Comments• Remedial action
034 * Blowermotor,outlet(+)shortcircuitafterUB(batteryvoltage)
• Checkthattheleadharnessoftheblowermotorhasbeencorrectlylaidandcheckfordamage,ifok—>removeleadharnessatcontrolboxandcheckforcontinuity,ifok—>replacecontrolbox.
047 Meteringpump–shortcircuitoroverload
• Removeconnectorfromthemeteringpump,ifthefaultcode048(inter-ruption)isdisplayedthemeteringpumpisdefective—>replacemeteringpump.
• Ifthefaultcode047continuestobedisplayed,disconnectconnectorS1/B1attheheater,andattheconnectorB1,PIN5checkthecable12gn/rtuptothemeteringpumpforshortcircuittonegative(PIN10),ifok–>replacecontrolbox.
048 Meteringpump–interruption • Disconnectconnectorfrommeteringpumpandmeasuretheresistancevalueofthemeteringpump(seePage12forvalues),ifresistancevalueok,re-connectthecableloomtothemeteringpump.
• DisconnectconnectorS1/B1attheheaterandmeasuretheresistancevalue(seePage12)betweenPIN5andPIN10,ifok—>replacecontrolbox.
049 * Meteringpumpoutlet(+)Shortcircuit–afterUB(batteryvoltage)
• Checkthattheleadharnessofthemeteringpumphasbeencorrectlylaidandcheckfordamage,ifok—>removeleadharnessandcheckforconti-nuity,ifok—>replacecontrolbox.
050 Toomanyfailedstartattempts(opera-tinglock-out)
Thecontrolboxlocksaftertoomanyfailedstartattempts(max.255startat-tempts).• Unlockthecontrolboxbydeletingthefaultmemorywiththetimer,thedi-
agnosticunit,EDiTHdiagnostictool,theTP5radioremotecontrol/EasyS-tartR+andtheEasyStartTtimer.
051 Flamedetectedwhenswitchingon If,afterbeingswitchedon,theresistancevalueoftheflamesensoris1274(>70°C)theheater’sfanrunsforapprox15mintocooldown,iftheresist-ancedoesnotfallbelowtheaforementionedvaluewithin15mintheheaterisswitchedoff.
• Checkflamesensor,seePage32fordiagramandtableofvalues,ifok—>replacecontrolbox.
052 Safetytimeexceeded Noflamedetectedwithinthestartphase.• Checkexhaustandcombustionairsystem.• Checkfuelsupply/measurefuelquantity,seePage36.• Checksparkplug(seefaultcode020and021)• Checkflamesensor,diagramandtableofvalues,seePage32,
ifok—>replacecontrolbox.
053
054
055
056
Flamecutoutinthe
“POWER”controlstage
“HIGH”controlstage
“MEDIUM”controlstage
“LOW”controlstage
Theheaterhasignited(flamedetected)andsignalsflamecutoutduringapowerstage.
• Checkexhaustandcombustionairsystem.• Checkfuelsupply/measurefuelquantity,seePage36.• Checkflamesensor,diagramandtableofvalues,seePage32,
ifok—>replacecontrolbox.
057 Flamecutoutfromstartphase(Displayonlyifheaterslabelled“H-Kit”onthenameplate.)
Aflamecutoutwasdetectedduringthestartphase..• Checkexhaustandcombustionairsystem.• Checkfuelsupply/measurefuelquantity,seePage36.• Checkglowplug(seefaultcode020and021).• Checkflamesensor,diagramandvaluestable,seepage32,
ifok—>replacecontrolbox.
060 Externaltemperaturesensor–interruption
• DisconnecttheconnectorS4/B4oftheexternaltemperaturesensorandmeasuretheresistancevalueatconnectorB2,fordiagramandtableofva-luesseePage12,iftemperaturesensorok,reassembleconnectorS4/B4.
• DisconnectconnectorS1/B1attheheaterandmeasuretheresistancevalueinconnectorhousingB1betweenPIN6andPIN12.Ifinterruptedtheohmicvalueis>7175/3k*.Ifresistancevalueok—>replacecontrolbox.
* Thisfaultcodeorohmicvalueisvalidforanewgenerationcontrolboxonly.Thisdiffersfromthecontrolboxtodatebyitscableloomwrappedincabletapeandbyatemperaturesensormountedontheside,whichbecomesvisiblewhenthecoverisremoved.
26
Troubleshooting4Fault codeDisplay
Fault description Comments• Remedial action
061 Externaltemperaturesensor–shortcircuit
• DisconnectconnectorS4/B4oftheexternaltemperaturesensor,iffaultcode060isdisplayed—>checkexternaltemperaturesensor,diagramandtableofvalues,seePage32.Iftemperaturesensorok—>checkconnec-tioncables0.5grand0.5br/wsforshortcircuit,ifok,reassemblethecon-nectorS2/B2.
• DisconnectconnectorS1/B1attheheaterandmeasuretheresistancevalueinconnectorhousingB1betweenPIN6andPIN12.Incaseofshortcircuittheohmicvalueis<486/<800*.
Iferror061continuestobedisplayed—>replacecontrolbox.
062 Controlunit–interruption
Please note!
Refertonotesondiagnosiswithmini-controlleronpage14.
Heaterrunsin„High“controlstageonly• Removeconnectoratthecontrolunitandmeasuretheresistancevalueof
thesetpointpotentiometer,forconnectorpinsseePage42onwards.Iftheresistancevalueisok,reconnectconnectoratthecontrolunit.
• DisconnectconnectorS1/B1attheheater,measuretheresistancevaluebetweenPIN6andPIN7inconnectorhousingB1,ifresistancevalueok—>replacecontrolbox.Resistancevalueincaseofinterruption>7175 />3k *.Normalvalues:seepage12.
063 Controlunit–shortcircuit
Faultrecognitiononlyworksinhea-tingmode.If,ontheotherhand,theshortcircuithasalreadyoccurredandthentheheaterisswitchedon,„Venti-lation“isactive(notafaultcode).
• Ifthe“Ventilate”switchisinstalled,disconnectitandcheckitworks.Ifnotok—>replaceswitch.
• Disconnectconnectoratcontrolunit,iferrorcode062isdisplayed,replacethecontrolunit.Ifcontrolunitok,checkconnectioncables0.5gr/rtand0.5br/wsforshortcircuit,ifok—>reconnectconnectoratcontrolunit.
• DisconnectconnectorS1/B1attheheater,iftheerror063continuestobedisplayed—>replacecontrolbox.Resistancevalueincaseofshort-circuit<486 / <800 *.Normalvalues:seepage12.
064 Flamesensor–interruption • Dismantlecontrolboxanddisconnectgreenconnectorfromcontrolbox.Checkflamesensor,diagramandtableofvalues,seePage32,ifflamesen-sorok—>replacecontrolbox.Resistancevalueincaseofinterruption>7175 />3k *.
065 Flamesensor–shortcircuit Dismantlecontrolbox,removegreenconnectorfromcontrolbox,iferror064isdisplayed—>replacecombinationsensor.
Iferror065continuestobedisplayed—>replacecontrolbox. Resistancevalueincaseofshortcircuit<486 /<500*,seealsodia-
gramonPage32.
071 Overheatingsensor–interruption • Dismantlecontrolbox,disconnectblueandgreenconnectorsfromcontrolbox.MeasureresistancevalueatblueconnectorPIN1(cable0.52bl)andatgreenconnectorPIN2(cable0.52br/ws),ifok,—>replacecontrolbox.
Resistancevalueincaseofinterruption>223k />1600k *,seealsodiagramonPage32.
072 Overheatingsensor–shortcircuit • Dismantlecontrolbox,removeblueconnectorfromcontrolbox,iferror071isdisplayed—>replacecombinationsensor.
Iferror072continuestobedisplayed—>replacecontrolbox. Resistancevalueincaseofshortcircuit<183 /<95*,seealsodia-
gramonPage32.
074 * Controlboxdefective • Overheatingthresholdvalueisnotdetectedbycontrolbox—>replacecon-trolbox.
090 Controlboxdefective(internalfault) • Replacecontrolbox.
091 Externalinterferencevoltage • Controlboxfaultduetointerferencevoltagesfromthevehicle’selectricalsystem.Possiblecauses:
Poorbattery,charger—>removeinterferencevoltage.
092 Controlboxisdefective(ROMerror) • Replacecontrolbox.
093 * Controlboxdefective • Replacecontrolbox.
* Thisfaultcodeorohmicvalueisvalidforanewgenerationcontrolboxonly.Thisdiffersfromthecontrolboxtodatebyitscableloomwrappedincabletapeandbyatemperaturesensormountedontheside,whichbecomesvisiblewhenthecoverisremoved.
27
Troubleshooting4Fault codeDisplay
Fault description Comments• Remedial action
094 Controlboxdefective(EEPROM-Fehler)
• Replacecontrolbox.
095 * Controlboxdefective • Replacecontrolbox.
096 Internaltemperaturesensordefective • Replacecontrolboxoruseanexternalroomtemperaturesensor..
097 Controlboxdefective • SReplacecontrolbox.
098 * Controlboxdefective • Replacecontrolbox.
099 * Toomanyresetsinsequence
Transistorerrorincontrolbox
• Voltageshort-term<5–6volt(for12volt)or<7–8volt(for24volt). Incaseofavoltagedrop,checkthefuses,thesupplycables,thenegative
connectionsandthepositivesupportpointonthebatteryforcorrosionandcorrectcontact.
Testcontrolboxwithtestingdevice,ifok—>checkleadharnessoftheex-ternalcomponentshasbeencorrectlylaidandcheckfordamage,ifok—>checkleadharnessforcontinuity,ifok—>replacecontrolbox.
Air pressure sensor fault code displayFault code display
Fault description Comments• Remedial action
0 Nofaults —
11 Communicationloss Interruptionofthediagnosticscablebetweenthecontrolbox(heater)andtheairpressuresensor• Checkwiringandplug-inconnections
12 Noaltitudeadjustment Controlbox(heater)doesnotsupportaltitudeoperationwiththeairpressuresensor• Useacontrolbox(heater)whichsupportsaltitudeadjustment
13 Airpressuresensorfault Theairpressuresensorisdefective• Replacetheairpressuresensor
* Thisfaultcodeorohmicvalueisvalidforanewgenerationcontrolboxonly.Thisdiffersfromthecontrolboxtodatebyitscableloomwrappedincabletapeandbyatemperaturesensormountedontheside,whichbecomesvisiblewhenthecoverisremoved.
28
Repair instructions
Thepermittedrepairworktotheheaterisdescribedinthe“RepairInstructions”chapter.Ifextensiverepairsarenecessary,itmakessensetodismantletheheater.
Theheaterisassembledinthereverseorder,ifapplicablenotadditionalinstructions.
Aftercompletingalltheworkontheheater,youmustcarryoutafunctionalcheck(seePage4).
Always observe the following safety instructions before working on the heater:
Danger!Risk of injury, burns and poisoning!• Alwaysswitchofftheheaterbeforehandandleaveittocool.• Disconnectthebattery.• Theheatermustnotbeoperatedinclosedroomssuchas
garagesorworkshops. Exception: Exhaustsuctionavailabledirectlyattheentrytotheexhaust
pipe.
Caution!• Thesealsofdismantledcomponentsmustberenewed.• Duringrepairwork,checkallcomponentsfordamageandif
necessaryreplace.• Checkconnectorcontacts,plug-inconnectionsandcables
forcorrosionanddamageandifnecessaryrepair.• OnlyeveruseEberspächersparepartsifreplacementsare
necessary.• Operationortheafterrunningoftheheatermayonlybe
stoppedinanemergency(see“EMERGENCYOFF”Page8)byinterruptingthebatterycurrent(riskofheateroverheat-ing).
Repairinstructions5Special tool
AMP release tool
TheAMPreleasetoolisusedtoreleaseplug-incontactsinaconnectorhousing.
ThisreleasetoolcanbeordereddirectlyfromAMP.
• ForMicroTimer: AMPOrderNo.0-0539960-1
• ForJunior-Power-Timer: AMP-Bestell-Nr.1-1579007-6
Please note!
29
Assembly drawing Airtronic / Airtronic M
Partslist
1 Combustionairfan 2 Seal–combustionairfan/heatexchanger 3 Combustionchamber 4 Seal–combustionchamber/heatexchanger 5 Heatexchanger 6 Controlbox 7 Combinationsensor(overheating/flamesensor)with
assemblytool
8 Bracket 9 Glowplug,withspecialtool(SW12)10 Lining–glowplugsocket,withassemblytool11 Cover12 Outershell(bottomsection)13 Flangeseal14 Sleeve(forpetrolonly)
Repairinstructions5
30
Repair step 1Remove the heater’s cover (seeFigure1)
Unlockbothfasteningclips,liftthecoverandremovefromthefront.
Theheater’scovermustberemovedforallrepairsteps.Ifnecessary,waituntiltheunithascooleddown.
Cableharnessoutletfromthehousingoptionallyonleftorright-handside.
1. 2.
Figure1
Cover Fasteningclips
Repair step 2Dismantle control box (seeFigure2)
• Repairstep1.• Unscrewfixingscrew,• Presstogethertheretainingclamps.• Removethecontrolboxfromabove.• Unclipcablesfromholderoncontrolbox (Notethepositionofthecables).• Pullgrommetoutoftheoutershell(bottomsection).• Pullconnectoroutofcontrolbox,thecontrolboxcannow
beremoved.
Whenassemblingthecontrolbox,ensurethecablesareclip-pedintotheholderonthecontrolboxandtheconnectorsarepluggedintothecontrolbox(unmistakeable).TighteningtorqueofthefixingscrewItem:2+0.2Nm
Figure2
Fixingscrew Retainingclamp Controlbox Grommet
Check control box
TheEDiTHdiagnostictoolisrequiredtocheckthecontrolboxwhenitisdismantled.Forconnection,useandOrderNo.,seePage19.
5 Repairinstructions
Please note!
Please note!
31
Repair step 3Dismantle glow plug (seeFigure3)
Important!Safety instruction for installation of the rubber grommetTopreventleaks,inserttherubbergrommetpreciselyintheglowplugholeintheheatexchanger.Failuretocomplywiththisinstructioncanresultinpersonalinjuriesaswellasmalfunctioningordamagetotheheater.
• Repairstep2.• Disconnectconnectorfrom“glowplug”cableloomoncon-
trolbox.• Removerubbergrommetandunscrewtheglowplugusing
thespecialtool(SW12).(Thespecialtoolisincludedwiththeglowplug).
Tighteningtorqueforglowplug:6+0.5Nm
Specialglowplugtool
Figure3
Glowplug Connectorfromglowplugcableloom Rubbergrommet
Please note!
Withtheglowplugdismantled,visuallycheckthesocketliningoftheinstalledglowplugfordirt.Iftheliningishighlysoiledanditssurfaceclosed,renewthelining.
Removing the lining (see Figure 4)
Uselongnoseplierstopulltheliningoutofthesocketfromabove.Blowoutthesocketwithcompressedairandifnecessarycleanthesideventhole.
Usethespecialtooltoinstallthenewlining.Thespecialtoolisincludedwiththelining.Pushtheliningonthetool.Pushinthetooltogetherwiththelininguptothelimitstop.Welding points of lining must lie opposite the fuel intake.
Figure4
Specialtool Lining
5
Repairinstructions
32
Repair step 5 Dismantle combination sensor (overheating / flame sen-sor) (seeFigure5)
• Repairstep2.• Removebothconnectorsfromthe“combinationsensor”
cableloomatthecontrolbox.• Unlockbracketfromcombinationsensor.• Removethecombinationsensor.
Figure5
“Combinationsensor”cableloom Bracket,unlocked
Check combination sensor
Theexternaltemperaturesensormustbecheckedwithadigi-talmultimeter.Replacetheoverheatingorflamesensoriftheresistancevalueisnotthesameasthecurveinthediagramorthetableofvalues.
Table of overheating sensor values
Temperature °C Resistance k min. max. – 40 1597.00 1913.00 – 20 458.80 533.40 0 154.70 175.50 20 59.30 65.84 40 25.02 28.04 60 11.56 13.16 80 5.782 6.678 100 3.095 3.623 120 1.757 2.081 140 1.050 1.256 160 0.6554 0.792 180 0.4253 0.5187 200 0.2857 0.3513
Table of flame sensor values
Temperature °C Resistance min. max.– 40 842.7 825.9 859.6– 20 921.6 803.2 940.0 0 1000.0 980.0 1020.0 20 1077.9 1056.4 1099.5 40 1155.4 1132.3 1178.5 60 1232.4 1207.8 1257.1 80 1308.9 1282.8 1335.1 100 1385.1 1357.4 1412.8 120 1460.7 1431.5 1489.9 140 1535.8 1505.1 1566.6 160 1610.5 1578.3 1642.8
Res
ista
nce
(kO
hm)
Temperature(°C)
5
Notethemax.temperatureof320°Cforthetest.
Temperature(°C)
Res
ista
nce
(Ohm
)
Overheating sensor Flame sensor
Repairinstructions
Please note!
33
Sketch2
Specialtool–onlyrequiredforAirtronic Combinationsensor
Figure6
Specialtool–onlyrequiredforAirtronic Combinationsensor
Repair step 6 Install combination sensor (overheating / flame sensor)(seeFigure6,7andSketch2–4)
•Repairstep2.• ForAirtronic(assemblywithspecialtool,seeSketch2) Pushthespecialtoolaontothecombinationsensorb.Use
thespecialtooltopositionthecombinationsensorontheheatexchanger,thespecialtoolslidesontheheatexchang-eruntilthecombinationsensorhitsthecollar(installationpositionofthecombinationsensor).
Lockthecombinationsensor’sbracketandremovethespecialtool.Thenalwayscheckthatthecombinationsen-sorsitsflatontheheatexchanger.Ifnecessary,useaidssuchasamirrorandlamp.
Laythe“combinationsensor”cableloomalongthebracket,throughthebracketeyeletuptothecontrolboxandcon-nect.
• ForAirtronicM(assemblywithoutspecialtool) Placethecombinationsensorontheheatexchanger;itis
importanttoensurethecombinationsensorsitsflatontheheatexchanger.
Lockthecombinationsensor’sbracketandcheckagainthatthecombinationsensorissittingflatontheheatex-changer.
Laythe“combinationsensor”cableloomalongthebracket,throughthebracketeyeletuptothecontrolboxandcon-nect.
Sketch4
Bracket Combinationsensor
Figure7
Bracket,locked “Combinationsensor”cableloom Specialtool–onlyrequiredforAirtronic
Circuit diagram for combination sensor (overheating sensor / flame sensor)
Sketch3
NTC50KΩ=overheatingsensorPT1000=flamesensor
Connectorblue
Connectorgreen
5 Repairinstructions
34
Repair step 7 Dismantle heat exchanger (seeFigure8andSketch5)Dismantle combustion air fan (seeFigure8andSketch5)
• Repairstep2.• Removeflangeseal.Removeheaterfromtheoutershell
(bottomsection). Unscrewthe4fixingscrewsfromthecombustionairfan. Removethecombustionairfanandthesealfromtheheat
exchanger.
Caution!Wheninstallingthecombustionairfanthesealmustalwaysberenewed.
Tightenthe4fixingscrewsofthecombustionairfan–intheordershowninSketche–withatighteningtorqueof4+0.5Nm. Figure8
Combustionairfan Heatexchanger Fixingscrew
Sketch5
1–4 Tightenthefixingscrewsinthisorderwithatightening
torqueof4+0.5Nm
5
5 Alwaysrenewthesealbetweenthecombustionairfanandtheheatexchanger.
5
2
4
3
1
Repairinstructions
35
Repair step 8Dismantle combustion chamber (seeFigure9andSketch6)
• Repairstep3.• Repairstep7.• Unscrewthefixingscrews. IntheAirtronic=3fixingscrews, intheAirtronicM=4fixingscrews.• Pulloutthecombustionchamberfromthefrontandremove
theheatexchanger’sseal.
Caution!Whenassemblingthecombustionchamber,alwaysrenewtheseal,whichisincludedwiththesparepart.
Tightenthefixingscrewsofthecombustionchamberwithatighteningtorqueof5+0.5Nm
Iftheheatexchangerisreplacedthecombinationsensor(overheatingsensor/flamesensor)mustbedismantledandfittedonthenewheatexchanger(seeRepairstep6,Page33).
Sketch6
1Combustionchamber2Alwaysrenewthesealbetweenthecombustionchamber
andtheheatexchanger.3Heatexchanger
4Fixingscrew Airtronic=3fixingscrews AirtronicM=4fixingscrews
Figure9
Combustionchamber Heatexchanger Fixingscrew Airtronic=3fixingscrews AirtronicM=4fixingscrews
5
4
1
2
3
Repairinstructions
Please note!
36
Measuring the fuel quantity
1. Preparation
Removethefuelpipeattheheaterandinsertameasuringcylinder(size10ml).Switchontheheater,ifthefuelisuniformlypumped(beginsapprox.60secafterbeingswitchedon),thefuelpipeisfullandvented.Switchoffheaterandemptymeasuringcylinder.
Forprecisefuelmeasurementatleast11volt/22voltormaximum13volt/26voltshouldbeappliedtothecontrolboxduringthemeasurement.
2. Measurement
Thefuelbeginstobepumpedapprox.60secafterswitchingontheheater.Holdthemeasuringcylinderatglowpluglevelduringthemeasurement.
Airtronic Afterapprox.90secofthefuelbeingpumpeditisautomati-callyswitchedoff.
Caution!Switch off heater,asotherwiseitwillstartupagain.
Readoffthequantityoffuelinthemeasuringcylinder.
Airtronic MAfterapprox.105secofthefuelbeingpumpeditisautomati-callyswitchedoff.
Caution!Switch off heater,asotherwiseitwillstartupagain.
Readoffthequantityoffuelinthemeasuringcylinder..
Ifthemeasuredfuelquantityliesoutsidethevaluesgivenbelow,themeteringpumpmustbereplaced.
1 Heater2 Meteringpump
Check fuel supply
Beforemeasuringthefuelquantity,checkthefollowingpointsinthefuelsupply.
• Checkthescreeninthemeteringpump.• Checkthelayingofthefuelpipes.• Checkfuelpipesforleaks.• Checkandtightenthehoseconnections.• Isthefuelremovalinstalledaccordingtothedetailsinthe
technicaldescription?
5
3 Measuringcylinder(size10ml)4 Disconnectfuelpipeatheaterandinsertinameasuringcylinder.
1
2
3
4
Table of values – fuel quantity
Heater Fuel Fuel quantity
Minimal Maximal
Airtronic diesel 3,5ml/90sec 4,3ml/90sec
AirtronicM petrol 6,8ml/105sec 7,6ml/105sec
AirtronicM diesel 5,0ml/105sec 6,0ml/105sec
Bitte beachten!
Repairinstructions
37
Circuitdiagram6Overview of the parts lists and circuit diagrams
PartslistcircuitdiagramAirtronic/AirtronicM................................................................................................................................ 38CircuitdiagramAirtronic/AirtronicM.............................................................................................................................................. 39 Thiscircuitdiagramisforheaterswithonediagnosticscableandacontrolboxcableloomwhichisfirmlyencapsulated.CircuitdiagramAirtronic/AirtronicM.............................................................................................................................................. 40 Thiscircuitdiagramisforheaterswith2diagnosticscableandwhosecontrolboxcableloomiswoundwithcabletape.
Partslistcontrolunits..................................................................................................................................................................... 41Circuitdiagramscontrolunits...................................................................................................................................................42–48
PartslistEasyStartR+/R/Tcontrolunits..................................................................................................................................... 49EasyStartR+circuitdiagram...................................................................................................................................................50–52EasyStartRcircuitdiagram......................................................................................................................................................53–55EasyStartTcircuitdiagram....................................................................................................................................................... 56,57
PartslistcircuitdiagramAirtronic/AirtronicM–ADR..................................................................................................................... 58CircuitdiagramAirtronic/AirtronicM–ADR................................................................................................................................... 59 Thiscircuitdiagramisforheaterswithonediagnosiscableandacontrolboxcableloomwhichisfirmlyencapsulated.CircuitdiagramAirtronic/AirtronicM–ADR................................................................................................................................... 60 Thiscircuitdiagramisforheaterswith2diagnosticscableandwhosecontrolboxcableloomiswoundwithcabletape.
Partslistcontrolunits–ADR.......................................................................................................................................................... 61Circuitdiagramcontrolunits–ADR............................................................................................................................................... 62EasyStartT–ADRcircuitdiagram............................................................................................................................................ 63,64
38
Parts list circuit diagrams Airtronic / Airtronic M
1.1 Burnerengine1.2 Glowplug1.5 Overheatingandflamesensor2.1 Controlbox2.2 Meteringpump2.7 Mainfuse 12volt=20A 24volt=10A2.7.1Fuse,actuation5A5.1 Battery
a) Connectionofcontrolunitandexternalsensoraccord-ingto“controlunits”circuitdiagram
•rt Powersupply,plus–terminal30 •ge Switch-onsignal–S+ •gr Temperature–actualvalue •wsrt Switchofftheanti-theftalarmsystem (ADR–feedbacksignalfortimer) •br Powersupply,minus–terminal31 •blws Diagnosis •grrt Temperature–setpoint •brws Groundconnectionforexternaltempera-
turesensorandtemperaturesetpoint b) Option •Vehiclefancontrol and/or •separatefreshairfan
Thecircuitdiagramsareassignedviatheinstalledcontrolbox:• Controlboxwithonediagnosticscable: Atthe16pinconnectorthediagnosticscablebl/wsiscon-
nectedtochamber8.• Controlboxwith2diagnosticscablesandJEdiagnosis: Atthe16pinconnectorthediagnosticscablebl/wsis
connectedtochamber3,thediagnosticscablebl/geisconnectedtochamber8.
• Insulateunusedcableends.• Connectorsandbushhousingsareshownfromthecable
inletside.
Circuitdiagram6
Cable colours circuit diagramssw = blackws = whitert = redge = yellowgn = greenvi = violetbr = browngr = greybl = blueli = purple
Please note!
39
Circuit diagram – Airtronic / Airtronic M
252069009801APartslistPage38
Circuitdiagram6
Thiscircuitdiagramisforheaterswithadiagnosticscableandwhosecontrolboxcableloomwhichisfirmlyencapsulated.
Please note!
40
Circuit diagram – Airtronic / Airtronic M
Circuitdiagram6
Thiscircuitdiagramisforheaterswith2diagnosticscableandwhosecontrolunitcableloomiswoundwithcabletape.
252069009801BPartslistPage38
Bitte beachten!
41
Circuitdiagram6Parts list circuit diagrams, control units
2.15.1 Temperaturesensor,external(roomtemperature)2.15.9 Temperaturesensor(externaltemperature)3.1.9 Changeoverswitch“heat/ventilate”3.1.11 Controlunit,round3.1.16 Radioremotecontrolbutton3.1.17 MinicontrollerAirtronic3.1.18 ButtonCalltronic3.2.8 Moduletimer(ADR–potentiometer)3.2.12 Timer,mini–12/24volt3.2.14 Lighting,timer,mini–12voltonly3.3.6 RadioremotecontrolstationarypartTP41i3.3.7 RadioremotecontrolstationarypartTP53.3.8 RemotecontrolCalltronic3.8.3 Antenna3.9.1 Diagnosis,JEdiagnosis
a)ConnectioncontrolelementstotheAirtronic •rt Powersupply,plus–terminal30 •ge Switch-onsignal–S+ •gr Temperature–actualvalue •wsrt Switchoffburglaralarm (ADR–feedbackfortimer) •br Powersupply,minus–terminal31 •blws Diagnosis •grrt Temperature–setpoint •brws Groundconnectionforexternaltempera-
turesensorandtemperaturesetpoint b) Terminal15–necessaryforconnectionTP4i c) Lighting,terminal58d) Connection,diagnosticunit e) Connection,externaltemperaturesensor g) Connection,externalheatingbutton h) Connection,radioremotecontrolTP4i j) Connection,temperaturesensor(outsidetemperature) k) Ifconnectingtimerorradioreceiver– Disconnectcablehere l) Connection,change-overswitch“heat/ventilate” option) Initialoperation:Activatechangeoverswitch “heat/ventilate”,thenswitchontheheater. z) Lighting,terminal58
• Insulateunusedcableends.• Connectorsandbushhousingsareshownfromthecable
inletside.
Cable colours circuit diagramssw = blackws = whitert = redge = yellowgn = greenvi = violetbr = browngr = greybl = blueli = purple
Please note!
42
Circuit diagram, control units – part 1
252069009701CPartslistPage41
Circuitdiagram6
43
Circuitdiagram6
252069009701CPartslistPage41
Circuit diagram, control units – part 2
44
Circuit diagram, control units – part 3
252069009702APartslistPage41
Circuitdiagram6
45
Circuit diagram, control units – part 4
252069009702APartslistPage41
Circuitdiagram6
46
Circuit diagram, control units – part 5
252069009704APartslistPage41
Circuitdiagram6
47
Circuit diagram, control units – part 6
252069009704APartslistPage41
Circuitdiagram6
48
Circuit diagram, control units – part 7
PartslistPage41
Circuitdiagram6
252069009703B
49
Circuitdiagram6Parts list circuit diagram control units – EasyStart R+ / R / T
2.15.1 Temperaturesensor(roomtemperature) (includedinscopeofsupplyforEasyStartR+, optionalforEasyStartR/T)2.15.9 Outsidetemperaturesensor(optional)
3.1.7 “OFF”button3.1.9 “Heat/ventilate”switch3.1.11 “Round”controlunit3.1.16 Radioremotecontrolbutton3.1.17 “Minicontroller”controlunit
3.2.15 EasyStartTtimer
3.3.9 RadioremotecontrolEasyStartR(stationaryunit)3.3.10 RadioremotecontrolEasyStartR+(stationaryunit)
3.6.1 Leadharness
3.8.3 Antenna
a) Connectionofcontrolunitsattheheaterc) Terminal58(lighting)d) Parkingventilationwithvehiclefan(optional)e) ConnectionofEasyStartTtimertimerg) Connection“ON/OFF”key (optionale.g.OrderNo.:221000328400)h) Connectionof“Ventilate”viaEasyStartR+x) ADRjumpery) Connectandinsulatecables
•Note heater type!•Thejumperlabelledwithy)inthecircuitdiagrammustalways
beconnected.•Insulateunusedcableends.•Connectorsandbushhousingsareshownfromthecable
inletside.
Assignment of the circuit diagrams for Airtronic heatersThecircuitdiagramsareassignedviatheinstalledcontrolbox:• Controlboxwithonediagnosticscable: Atthe16pinconnectorthediagnosticscablebl/wsiscon-
nectedtochamber8.• Controlboxwith2diagnosticscablesandJEdiagnosis: Atthe16pinconnectorthediagnosticscablebl/wsis
connectedtochamber3,thediagnosticscablebl/geisconnectedtochamber8.
Cable colours circuit diagramssw = blackws = whitert = redge = yellowgn = greenvi = violetbr = browngr = greybl = blueli = purple
Please note!
EasyStart TPinassignmentEasyStartT-connectorS1
1 Terminal 30 (positive) rt 2 S+(switchingonsignal) ge 3 Terminal 31 (negative) br 4 DATcable vi 5 Diagnosis cable (K line) bl/ws 6 Terminal58 gr/sw 7 Temperaturesensor(positive)) gr 8 Temperaturesensor(negative) br/ws 9 –– ––
EasyStart R Pinassignmentatthestationaryunitconnector
1 Terminal31(negative) 2 –– 3 –– 4 DATcable 5 Pushbutton/LED(negative) 6 –– 7 Terminal30(positive) 8 S+(switching on signal) 9 LED(positive)10 Diagnosiscable(Kline))11 Pushbutton(negative)12 ––
EasyStart R+ Pinassignmentatthestationaryunitconnector
1 Terminal31(negative) 2 –– 3 Ventilate(switchingsignal–) 4 DATcable 5 Pushbutton/LED(negative) 6 Temperaturesensor(negative) 7 Terminal30(positive) 8 S+(switchingonsignal) 9 LED(positive)10 Diagnosiscable(Kline)11 Pushbutton(negative)12 Temperaturesensor(positive)
Pin assignments
50
Circuitdiagram6EasyStart R+ control unit circuit diagram(Controlboxwithonediagnosticscable)
PartslistPage49 252069009706B
51
Circuitdiagram6
PartslistPage49 252069009706B
EasyStart R+ control unit circuit diagram(Controlboxwithonediagnosticscable)
52
Circuitdiagram6EasyStart R+ control unit circuit diagram(Controlboxwithtwodiagnosticscables)
PartslistPage49 252361009701B
53
Circuitdiagram6EasyStart R control unit circuit diagram(Controlboxwithoneortwodiagnosticscables)
PartslistPage49 252361009705B
54
Circuitdiagram6EasyStart R control unit circuit diagram(Controlboxwithtwodiagnosticscables)
PartslistPage49 252361009702B
55
Circuitdiagram6EasyStart R control unit circuit diagram(Controlboxwithonediagnosticscable)
PartslistPage49 252069009707B
56
Circuitdiagram6EasyStart T control unit circu