AMCA 210-07 Wind Tunnel AMCA 210 Series Wind Tunnel Introduction Long Win Science & Technology Co., Ltd. +886-3-4643221 E-mail: [email protected] Web Site: www.longwin.com
Transcript
Page 1: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

AMCA 210 SeriesWind Tunnel Introduction

Long Win Science & Technology Co., Ltd.+886-3-4643221

E-mail: [email protected] Site: www.longwin.com

Page 2: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

1. AMCA 210 / ISO 5801

4. Calibration

3. Operation

2. Principle

5. Features

Content

6. Application / Q&A

Page 3: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Long Win – Taiwan

Page 4: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Long Win IntroductionExpert in:1. Electronics thermal management.

2. Mechanics and manufacture engineering.

3. Control field technologies.

4. More than 600 system design experiences.

5. More than 2000 m2 fluid and thermal lab.

Page 5: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

AMCA 210 Standard

Air Movement and Control Association

Lab. Methods of Testing Fans forAerodynamic Performance Rating

American National Standard Institute

ANSI/AMCA 210-07ANSI/ASHRAE 51-2007

Published by

American Society of Heating, Refrigerating and Air Conditioning Engineers

Page 6: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Long Win Wind Tunnel Compliance

GB/TGB/T 12361236-- 2000

AMCA 210AMCA 210-- 07

ISO 5801ISO 5801-- 2007Industrial fans -- Performance testing using standardized airways

Laboratory Methods of Testing Fans for Aerodynamic Performance Rating

JIS B 8330JIS B 8330

ASHRAE 51ASHRAE 51-- 07

Household Range Hoods - Methods for Measuring PerformanceIEC 61591-2005

Page 7: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Long WinAMCA 210-07 Series Wind Tunnel

Introduction | Principle | Operation | Calibration | Features | Model

Application

Page 8: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

AMCA 210-99 Wind Tunnel Introduction

Wind Tunnel withFlow / Pressure Measuring Mode

A.FlowA.Flow Measuring ModeMeasuring Mode::Low Cost.Large Uncertainty.

B.PressureB.Pressure Measuring Mode:Measuring Mode:Higher Cost to Compare with A Mode.Higher Accuracy and Repeatability.

Introduction | Principle | Operation | Calibration | Features | ModelFolw Mode | Pressure Mode | Installation Type Back to Top

Page 9: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Circular Cross-section, 24 Points Measuring.AMCA 210-99 Fig.7、13、16 Structure.

A. Flow Measuring Ducts

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Q = Uduct x Aduct

Uduct : Average Velocity.Aduct : Cross-section .Q : Volume Flow rate.

Page 10: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Page 11: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Duct & Chamber to Measuring the Pressure DifferenceAcross the Nozzle(ΔP56) to Calculate the Air Flow Rate.Fig.8~12,14,15 Structure.

QN = Cd x Un x An single nozzleQT = Σ QN multi-nozzle

Cd : Discharge Coefficient.Un : Velocity at Nozzle Throttle.An : Nozzle Throttle Cross-section.

QN : Single Nozzle Air Flow RateQT : Multi Nozzle Air Flow Rate.

B. Pressure Measuring Mode:B. Pressure Measuring Mode:Flow Mode | Pressure Mode | Installation Type

ΔP Across the Nozzle

Introduction | Principle | Operation | Calibration | Features | Model

Page 12: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Page 13: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Page 14: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation Type

Type AFree Inlet,Free Outlet

Type BFree Inlet,Ducted Outlet

Type CDucted Inlet,Free Outlet

Type DDucted Inlet,Ducted Outlet

Introduction | Principle | Operation | Calibration | Features | Model

Page 15: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Back to Top

Fig.12 12025 DC12V with Different Type

Page 16: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Back to Top

Fig.12/15 8038 DC12V with Different Type

Page 17: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Back to Top

Fig.12/15 8038 DC12V with Type A

Page 18: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Flow Mode | Pressure Mode | Installation TypeIntroduction | Principle | Operation | Calibration | Features | Model

Back to Top

Fig.12/15 8038 DC12V with Type B

Page 19: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Chamber Size | Chamber Shape

Introduction | Principle | Operation | Calibration | Features | ModelChamber | Settling Means | Nozzle Back to Top

Outlet ChambersAn outlet chamber (Figure 11 or 12) shall have across-sectional area at least nine times the areaof the fan outlet or outlet duct for fans with axis ofrotation perpendicular to the discharge flow and across-sectional area at least sixteen times thearea of the fan outlet or outlet duct for fans withaxis of rotation parallel to the discharge flow.

Inlet ChambersInlet chambers (Figure 13, 14, or 15) shall have across- sectional area at least five times the faninlet area.

From AMCA 210-99 page10

Page 20: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Chamber Size | Chamber Shape

A chamber may have a circular orrectangular cross-sectional shape.

The dimension M in the test setupdiagram is the inside diameter of acircular chamber or the equivalentdiameter of dimensions a and bwhere

From AMCA 210-99 Page10

Chamber | Settling Means | Nozzle Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 21: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Introduction | Upstream | DownstreamChamber | Settling Means | Nozzle Back to Top

Any combinations of screens orperforated plates that will meetthese requirements may be used,but in general a reasonablechamber length for the settlingmeans is necessary to meet bothrequirements.

Screens of square mesh roundwire with open areas of 50% to60% are suggested and severalwill usually be needed to meet theabove performance specifications.

A performance check will benecessary to verify the flow settlingmeans are providing proper flowpatterns.

From AMCA 210-99

Introduction | Principle | Operation | Calibration | Features | Model

Page 22: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Introduction | Upstream | Downstream

Upstream Settling MeansWhere a measuring plane is locatedupstream of the settling means, thepurpose of the settling screen is toabsorb the kinetic energy of theupstream jet. and allow its normalexpansion as if in an unconfined space.

This requires some backflow to supplythe air to mix at the jet boundaries, butthe maximum reverse velocity shall notexceed 10% of the calculated Plane 2 orPlane 6 mean jet velocity.

From AMCA 210-99

Chamber | Settling Means | Nozzle Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 23: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Introduction | Upstream | Downstream

Downstream Settling MeansFlow settling means shall be installed inchambers where indicated on the testsetup figures to provide proper airflowpatterns.

Where a measuring plane is locateddownstream of the settling means, thesettling means is provided to ensure asubstantially uniform airflow ahead of themeasuring plane.

In this case, the maximum local velocityat a distance 0.1 M downstream of thescreen shall not exceed the averagevelocity by more than 25% unless themaximum local velocity is less than2 m/s (400 fpm).

From AMCA 210-99

Chamber | Settling Means | Nozzle Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 24: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Nozzle Shape | Nozzle Location | Nozzle Flow RateChamber | Settling Means | Nozzle Back to Top

Notes1. Nozzle throat dimension L shall be either

0.6D±0.005D (recommended) or 0.5D±0.005D.2. Nozzle shall have elliptical section as shown.

Two and three radii approximations to theelliptical form that do not differ at any point in thenormal direction more than 1.5% D from theelliptical form may be used. The outlet edge ofthe nozzle shall be square, sharp, and free fromburrs, nicks or roundings.

3. The nozzle throat shall be measured (to anaccuracy of 0.001 D) at the minor axis of theellipse and the nozzle exit. At each place, fourdiameters—approximately 45°apart must bewithin ±0.002 D of the mean. At the entrance tothe throat the mean may be 0.002 D greater, butno less than the mean at the nozzle exit.

>> Next Page

Introduction | Principle | Operation | Calibration | Features | Model

Page 25: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Nozzle Shape | Nozzle Location | Nozzle Flow RateChamber | Settling Means | Nozzle Back to Top

Notes4. The nozzle surface shall fair smoothly so that a

straight-edge may be rocked over the surfacewithout clicking and the surface waves shall notbe greater than 0.001 D peak to peak.

5. When nozzles are used in a chamber, either ofthe types shown above may be used. Where anozzle discharges directly to a duct, nozzles withthroat taps shall be used, and the nozzle outletshould be flanged.

6. Throat tap nozzles shall have four static pressuretaps 90°apart connected to a piezometer ring.

From AMCA210-99

<< Previous Page

Introduction | Principle | Operation | Calibration | Features | Model

Page 26: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Nozzle Shape | Nozzle Location | Nozzle Flow RateChamber | Settling Means | Nozzle Back to Top

6.3.4 Multiple Nozzles.

Multiple nozzles shall be located as symmetrically aspossible.The centerline of each nozzle shall be at least1.5 nozzle throat diameters from the chamber wall.

The minimum distance between centers of any twonozzles in simultaneous use shall be three times thethroat diameter of the larger nozzle.

The uncertainty of the airflow rate measurement can bereduced by changing to a smaller nozzle or combinationof nozzles for the lower airflow rate range of the fan.

From AMCA210-99

Introduction | Principle | Operation | Calibration | Features | Model

Page 27: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Nozzle Shape | Nozzle Location | Nozzle Flow RateChamber | Settling Means | Nozzle Back to Top

Pressure Measuring Mode

Single Nozzle:QN = Cd x Un x An

Multi-Nozzle:QT =Σ QN

WhereCd = Discharge CoefficientUn = Throat VelocityAn = Throat Cross Section

How to get Cd How to get Un

Introduction | Principle | Operation | Calibration | Features | Model

AnUn

Cd

Page 28: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Nozzle Shape | Nozzle Location | Nozzle Flow RateChamber | Settling Means | Nozzle Back to Top

Back to Nozzle Flow Rate

Introduction | Principle | Operation | Calibration | Features | Model

Page 29: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Nozzle Shape | Nozzle Location | Nozzle Flow RateChamber | Settling Means | Nozzle Back to Top

WhereUn = Throat velocity ΔPn

= Pressure difference betweenPL5 and PL6

ρ = Air flow density

Back to Nozzle Flow Rate

Introduction | Principle | Operation | Calibration | Features | Model

Page 30: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 31: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 32: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 33: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 34: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 35: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 36: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

Page 37: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt - step mode Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 38: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt - Indicated mode Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 39: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 40: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 41: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 42: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 43: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 44: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 45: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(1) Constant Volt Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 46: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(2) PWM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 47: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(2) PWM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 48: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(2) PWM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 49: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(2) PWM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 50: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(2) PWM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 51: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(2) PWM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 52: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(2) PWM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 53: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(3) Constant RPM Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 54: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(3) Constant RPMWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 55: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(3) Constant RPMWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 56: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(3) Constant RPMWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 57: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(3) Constant RPMWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 58: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(3) Constant RPMWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 59: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(4) CPK test Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 60: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

(4) CPK test Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 61: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

(5) OP (DC Fan)

Page 62: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

(5) OP (AC Fan)

Page 63: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

(5) OP (Impeller)

Page 64: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

(5) OP

Page 65: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

(5) OP

Page 66: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

(5) OP

Page 67: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

(5) OP

Page 68: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(6) AC Constant VoltWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 69: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(6) AC Constant VoltWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 70: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(6) AC Constant VoltWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 71: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

(6) AC Constant Volt

Introduction | Principle | Operation | Calibration | Features | Model

Page 72: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

(6) AC Constant Volt

Introduction | Principle | Operation | Calibration | Features | Model

Page 73: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

(6) AC Constant Volt

Introduction | Principle | Operation | Calibration | Features | Model

Page 74: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

(6) AC Constant Volt

Introduction | Principle | Operation | Calibration | Features | Model

Page 75: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

(6) AC Constant Volt

Introduction | Principle | Operation | Calibration | Features | Model

Page 76: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

(6) AC Constant Volt

Introduction | Principle | Operation | Calibration | Features | Model

Page 77: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation(7) External Constant RPMWarm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 78: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

(7) External Constant RPM

Page 79: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

(7) External Constant RPM

Page 80: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

(7) External Constant RPM

Page 81: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

(7) External Constant RPM

Page 82: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

(7) External Constant RPM

Page 83: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (A/D) fan & fan tray performance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

(7) External Constant RPM

Page 84: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (B/E) system or module impedance test Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

Page 85: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (B/E) system or module impedance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 86: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (B/E) system or module impedance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 87: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (B/E) system or module impedance test Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 88: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Warm Up | Operation>> (C/F) offer air flow rate for system testing Back to TopBack to Operation

Introduction | Principle | Operation | Calibration | Features | Model

Page 89: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (C/F) offer air flow rate for system testing Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 90: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (C/F) offer air flow rate for system testing Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 91: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (C/F) offer air flow rate for system testing Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 92: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Operation

Warm Up | Operation>> (C/F) offer air flow rate for system testing Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 93: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

The quality of our thermometer, pressure, electrical meter (voltage,current, fan speed) will be approved by a third party (SGS) undersupervision of Chinese National Laboratory Accreditation (CNLA).

Introduction | Principle | Operation | Calibration | Features | Model

Page 94: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 95: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 96: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 97: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 98: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 99: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 100: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 101: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 102: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Meters | Wind tunnel flow calibration & validation | Create wind tunnel flow impedance databaseOutgoing Inspection | Traceability Back to Top

Long Win provides the orificeplate to create original flowimpedance curve.

Introduction | Principle | Operation | Calibration | Features | Model

Page 103: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Outgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 104: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Outgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 105: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Outgoing Inspection | Traceability Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

Page 106: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Introduction | Principle | Operation | Calibration | Features | Model

☆ 2 in 1 Combine AMCA 210-99 Fig.12 & Fig.15

☆ System Control Automatically

☆ 5 Mode Fan Performance Curve Test

☆ Multi Fan Performance Curve Test

☆ System Impedance Curve (SRC) Test

☆ Thermal Module Performance R-Q Test Automatically

☆ QC – Cpk Test

☆ QC – Operation Point Check

☆ Equipment Accuracy Certificate

Features

☆ STP Conversion

☆ High Ps Fan Performance Curve Test

Page 107: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

Page 108: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ System Control Automatically

* Auto Change Nozzles

* Auto Switching Ps

* Dynamic Scanning and

Optimize Testing Parameters

* Good Gauge R&R(Repeatability and Reproducibility)

Page 109: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Auto Switching Nozzle Open & Closed

Page 110: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

All meter will be approved by a third party (SGS).

☆ Equipment Accuracy Certificate

Page 111: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Equipment Accuracy Certificate

NML: National Measurement Lab

Page 112: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Equipment Accuracy Certificate

Page 113: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ 5 Mode Fan Performance Curve Test

Page 114: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ 5 Mode Fan Performance Curve Test

Page 115: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ 5 Mode Fan Performance Curve Test

Page 116: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ 5 Mode Fan Performance Curve Test

Page 117: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ 5 Mode Fan Performance Curve Test

Different Kind of Fan Test.

Page 118: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Fan with Heat Exchanger Performance Test

Page 119: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ 5 Mode Fan Performance Curve Test

Page 120: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ 5 Mode Fan Performance Curve Test

Page 121: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

Fan AerodynamicsPerformance Test

2000 RPM

PSTP QSTP Torque N

mmAq CFM N-m RPM

72.25 0.00 10.220 1995

57.72 1369.73 9.300 1999

44.26 2728.86 8.520 2003

30.84 4420.32 7.860 2006

24.66 5700.39 7.970 2006

0.06 8662.61 7.260 2009

Page 122: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Axial FAN 8038 AMCA 210 Fig.12 Setup,Installation Type B, Constant Voltage DC 12V

Parameter 1 : Test Condition

( Standard Temperature and Pressure)

Page 123: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Ps dP56 Q P STP Q STPm m A q inA q m m A q CM M CFM m m A q CFM

2.94 0.116 2.9 0.000 0.00 3.14 0.00

1.40 0.055 64.9 0.298 10.52 1.50 10.52

0.00 0.000 38.0 0.674 23.79 0.00 23.79

From Test Condition convert to Nominal Values (STP).

STP: Standard Air Property is Air at(Td) 20 ℃ Temperature,(RH) 50 % Relative Humidity,(Pb) 760 mmHg Barometric Pressure.

Page 124: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

Parameter 1 : Test Condition

☆ STP Conversion

Same Fan, Same Wind Tunnel,

Constant Voltage Input.

Not Sure Get Same Result

Page 125: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

Report Info.

☆ STP Conversion

Parameter 2 : Installation Type

Page 126: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

Type AFree Inlet,Free Outlet

Type BFree Inlet,Ducted Outlet

Type CDucted Inlet,Free Outlet

Type DDucted Inlet,Ducted Outlet

☆ STP Conversion

Page 127: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Page 128: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

Fig.12/15 8038 DC12V with Type A

☆ STP Conversion

Page 129: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

3. Convert PQ Curve to Assigned RPM by Fan Law.

2. Convert PQ Curve from

Test Condition to STP Condition.

1. Check Same Installation Type.

Comparison Methodology

☆ STP Conversion

Page 130: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Test Condition to STP Condition.

Assume Fan constant RPM, Nc = N at Different Condition

pc

pcc K

KNNQQ

cc

vpc

pcct

vctcsc

NNP

kk

NNP

PPP22

Qc / Psc : Nominal Values

From AMCA 210-99 Eq. 8.59~8.62

Page 131: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Page 132: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

STP Condition

Orifice Plate SRC Test

Test Condition

☆ STP Conversion

Page 133: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Test ReportTest Condition

( 1 – 4 )

Page 134: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Test ReportRow Data

( 2 – 4 )

Page 135: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Test ReportRow Data

( 3 – 4 )

Page 136: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ STP Conversion

Test ReportChart

( 4 – 4 )

Page 137: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Multi Fan Performance Curve Test

Up to 7 Fan.

( Amp. / Volt. / RPM )

Page 138: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Multi Fan Performance Curve Test

Parallel Series

Page 139: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

05

1015202530354045

0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00

Q (CFM)

Stat

ic P

ress

ure

(mm

Aq) Test1

Test 2Test 3

Fan1 Fan2

test1 12V 12V

test2 10V 12V

test3 12V 10V

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Multi Fan Performance Curve Test

Page 140: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Multi Fan Performance Curve Test

Page 141: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ High Ps Fan Performance Curve Test

Ps up to 200 mmAq

Page 142: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ High Ps Fan Performance Curve Test

Page 143: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ System Impedance Curve (SRC) Test

Page 144: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ System Resistance Curve (SRC) Test

Page 145: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ SRC : Duct Pressure Drop Test

1. Straight2. Bend3. Converge4. Diverge

Page 146: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ Offer Air Flow Rate Automatically

☆ Thermal Module R-Q Test Automatically (Option)

Page 147: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ QC – Cpk Test

Page 148: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to Top

Back to Features

Introduction | Principle | Operation | Calibration | Features | Model

☆ QC – Operation Point Check

Page 149: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9125RSAN Back to Top

1. Basic Specifications:

Model Air Flow Rate(CFM)

Overall DimensionW x L x H (M)

9014 0.2 ~ 18 0.6 x 3 x 1.6

9081 1.6 ~ 60 0.6 x 3 x 1.6

9015 2.4 ~ 250 0.85 x 3.6 x 1.8

9185 5 ~ 1500 1.2 x 4.6 x 1.9

9120 100 ~ 5000 2.6 x 7 x 2.3

9293 230 ~ 30000 3.0 x 10 x 2.6

Introduction | Principle | Operation | Calibration | Features | Model

850 CMM

Page 150: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9125RSAN Back to Top

Specifications:1.Air Flow Rate Range: 0.2 ~ 10 CFM.2.Nozzle Definition:

NO.Dimension Air flow rate Accuracy

mm min. max. % INFS1 3 0.20 0.64 3.52 4 0.32 1.15 33 5 0.87 1.80 2.54 6 1.26 2.60 25 8 2.25 4.66 1.5

INFS is the full scale of designated nozzle

3. Power source: AC 220 V,single phase,3A.4. Overall dimension: 0.6 (W) x 3 (L) x 1.6 (H) M.

Introduction | Principle | Operation | Calibration | Features | Model

Page 151: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9125RSAN Back to Top

Specifications:1.Air Flow Rate Range: 1.6 ~ 60 CFM.2.Nozzle Definition:

NO.

Dimension Air flow rate Accuracy

mm min. max. % INFS1 5 1.5 1.8 3.52 6 1.7 2.6 33 8 2.5 4.6 2.54 14 4.5 14.4 25 24 14.5 42.6 1.5

INFS is the full scale of designated nozzle

3. Power source: AC 220 V,single phase,3A.4. Overall dimension:

0.6 (W) x 3 (L) x 1.6 (H) M.

Introduction | Principle | Operation | Calibration | Features | Model

Page 152: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9125RSAN Back to Top

Specifications:1.Air Flow Rate Range: 2.4 ~ 250 CFM.2.Nozzle Definition:

NO.

Dimension Air flow rate Accuracymm min. max. % INFS

1 8 2.4 4.6 3.52 14 4.5 14.1 33 24 13 41 2.54 34 26 83 25 42 40 127 1.5

INFS is the full scale of designated nozzle

3. Power source: AC 220 V,single phase,5A.4. Overall dimension:

0.85 (W) x 3.6 (L) x 1.8 (H) M.

Introduction | Principle | Operation | Calibration | Features | Model

Page 153: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9125RSAN Back to Top

Specifications:1.Air Flow Rate Range: 2.9 ~ 800 CFM.2.Nozzle Definition:

NO.Dimension Air flow rate Accuracy

mm min. max. % INFS1 10 2.9 7.2 3.52 17 6.6 20.9 33 32 23 73 2.54 53 63 202 25 84 160 509 1.5

INFS is the full scale of designated nozzle

3. Power source: AC 220 V,3 phase,20A.4. Overall dimension:

1.2 (W) x 4.6 (L) x 1.9 (H) M.

Introduction | Principle | Operation | Calibration | Features | Model

Page 154: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9125RSAN Back to Top

Specifications:1.Air Flow Rate Range: 40 ~ 5000 CFM.2.Nozzle Definition:

NO.Dimension Air flow rate Accuracy

mm min. max. % INFS1 24 20 42 3.52 42 41 131 33 53 66 209 2.54 62 90 287 25 72 121 388 1.5

INFS is the full scale of designated nozzle

3. Power source: AC 220 V,3 phase,20A.4. Overall dimension:

2.6 (W) x 5.2 (L) x 2.3 (H) M.

Introduction | Principle | Operation | Calibration | Features | Model

Page 155: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9125RSAN Back to Top

Specifications:1.Air Flow Rate Range: 50 ~ 8000 CFM.2.Nozzle Definition:

NO.Dimension Air flow rate Accuracy

mm min. max. % INFS1 40 50 119 3.52 70 115 367 33 90 188 600 2.54 110 282 898 2.55 130 395 1256 2.5

INFS is the full scale of designated nozzle

3. Power source: AC 220 V,3 phase,30A.4. Overall dimension:

2.6 (W) x 7 (L) x 2.6 (H) M.

Introduction | Principle | Operation | Calibration | Features | Model

Page 156: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Basic Specification | 9014N-RSAN | 9081RSAN | 9015RSAN | 9185RSAN | 9120RSAN | 9293RSAN Back to Top

Specifications:1.Air Flow Rate Range: 230 ~ 30000 CFM.2.Nozzle Definition: ψ145 mm X 20 pcs

3. Power source: AC 380 V,3 phase,100A.4. Overall dimension:

3.0 (W) x 10 (L) x 2.6 (H) M.

Introduction | Principle | Operation | Calibration | Features | Model

Page 157: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Application

☆ NB Thermal Design

Back to Top

☆ Car Radiator Thermal Design

☆ Server Thermal Design

☆ Power Supply Thermal Design

☆ Application Summary

☆ Range Hood Airflow Design

Page 158: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Application Back to TopBack Application

☆ NB Thermal Design

Offer Air Flow Qair

NBPower ON

TemperatureData Log

Worst caseDefine mini air flow rate

Step1 :

Page 159: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Application Back to TopBack Application

☆ NB Thermal Design

NBFlow Impedance

Step2 :

Page 160: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Application Back to TopBack Application

☆ NB Thermal Design

NBBlower

Step 3Step3 :

Page 161: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Offer Air Flow Qair

Server

Worst caseDefine mini air flow rate

☆ Server Thermal Design

Step1 :

Back to TopBack Application

Page 162: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Server

ServerServerFlow Impedance

Step2 :

☆ Server Thermal DesignBack to Top

Back Application

Page 163: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Step3 :

CheckOperation Point

☆ Server Thermal DesignBack to Top

Back Application

Page 164: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

ServerBack to Top

Back Application

2U server1 fan in system airflow is 58 CFM6 fan (Parallel) in system flow is 98 CFM

Server fan tray case study

Page 165: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Check Operation Point

☆ PSU Thermal DesignBack to Top

Back Application

Page 166: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Thermal Evaluation

☆ PSU Thermal DesignBack to Top

Back Application

1. Layout scenario analysis2. Worse case study3. Cooling method choice4. HS choice5. Required cooling airflow rate6. Airflow impedance (SRC)7. Fan selection

Page 167: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Thermal Simulation

☆ PSU Thermal DesignBack to Top

Back Application

1. CFD2. Input / Output3. Tools

Page 168: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Thermal Verification

☆ PSU Thermal DesignBack to Top

Back Application

1. IR scanning2. Temperature testing3. Airflow testing

Page 169: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Thermal Verification

☆ PSU Thermal DesignBack to Top

Back Application

1. IR Camera2. Thermocouples / Data Log3. Worst ambient chamber4. AMCA 210 wind tunnel

Testing Facilities

Page 170: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Offer Air Flow Qair

Car Radiator

TemperatureData Log

Worst caseDefine mini air flow rate

☆ Car Radiator Thermal Design

Step1 :

Back to TopBack Application

Page 171: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Car Radiator

Car RadiatorCar RadiatorFlow Impedance

Step2 :

☆ Car Radiator Thermal DesignBack to Top

Back Application

Page 172: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Step3 :

CheckOperation Point

☆ Car Radiator Thermal DesignBack to Top

Back Application

Page 173: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application☆ Range Hood Airflow Design

Fig.12 - Outlet Chamber

Page 174: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application☆ Range Hood Airflow Design

O.P.15 CMM at 250 Pa

Fig.15 - Inlet Chamber

Page 175: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application☆ Range Hood Airflow Design

Flow Visualization

Page 176: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Application

AMCA 210 Fig.12Blow In Test

AMCA 210 Fig.15Exhaust Test

Fan Performance Test

Back to TopBack Application

Page 177: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application

)(QQ2

112 RPMRPM

)()(PP1

22

1

212

RPMRPM

(A) Constant Fan RPM

P

Q

1

2

)(PP1

212

1 Sea Level, 2: High Land

☆ Fan Performance at High Land

Page 178: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application

(B) Constant Fan Voltage

P

Q

Constant Voltage

P

QConstant RPM

1

2

Increase RPM

☆ Fan Performance at High Land

Page 179: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application

☆ Fan Performance at High Land

Page 180: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

SystemResistance Test

BTX System

Back to TopBack Application

Page 181: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application

Server Thermal TestImpedance TestAirflow Test

Page 182: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

PSUSystem Resistance Test

Back to TopBack Application

Page 183: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Thermal Wind TunnelThermal Test Platform withAMCA 210 Wind Tunnel

Back to TopBack Application

Page 184: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

AMCA 210 Link with TTP

Link withThermal Test Platform

AMCA Wind Tunnel

Back to TopBack Application

Page 185: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

R i V s Q a

R vs Q

dP vs Q a

0.00

0.20

0.40

0.60

0.80

1.00

0 2 4 6 8 10

Q a ( cfm )

Ri (o C

/W )

0

1

2

3

4

5

dP ( m

mAq )

Thermal Module - Thermal ResistanceRQ Curve Test

Back to TopBack Application

Page 186: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Heat Exchanger Performance Test

Page 187: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Temperature ControlledAirflow

Heating Capacity:30kW-Hr

Heat Exchanger Performance Test

Chiller for Liquid Cooling

Cooling Capacity:35KW

Page 188: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Cooling Capacity:40KWLiquid Flow : 120 LPM

Heat Exchanger Performance Test

ΔP、ΔT、Cooling Capacity

Page 189: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

☆ Thermal Module – Performance at High Land

Back to TopBack Application

Page 190: AMCA 210 Series Wind Tunnel Introduction - Long...AMCA 210 ...

AMCA 210-07 Wind Tunnel

Back to TopBack Application

Thank you !