+ All Categories
Home > Documents > Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans -...

Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans -...

Date post: 31-Aug-2019
Category:
Upload: others
View: 131 times
Download: 3 times
Share this document with a friend
48
Axial Flow Fans
Transcript
Page 1: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Axial Flow Fans

Page 2: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Section 4

Axial Fan

s - Section

4

Fläkt Woods offers a wide range of axial flow fans for

general air movement and special applications such

as emergency high temperature smoke extract and

pressurisation. ATEX fans for explosive atmospheres and

multistage options for increased pressure development.

All fans are tested to the latest internationally recognised

standard IS05801 Part 1 (1997), installation category D

(AMCA approved) for aerodynamic performance and

BS848 Part 2 (1985) for acoustic performance. Coupled

with the above fan diameters, the adjustable pitch

Aerofoil impeller gives the exact performance required,

with a non overloading fan characteristic.

Page 3: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

Page 4: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sizes

31JM - (315mm) to 100JM - (1000mm).Larger sizes up to 2800mm diameter are also available. Please enquire.

Fan Performance

All fans are tested to the latest internationally recognised standard IS05801 Part 1 (1997), installation category D (AMCA approved) for aerodynamic performance and BS848 Part 2 (1985) for acoustic performance.Coupled with a wide range of fan diameters, the adjustable pitch Aerofoil impeller gives the exact performancerequired, with a non overloading fan characteristic.

Impellers

A unique high efficiency aerofoil section blade with a purposely smoothed hub and clamp plate for adjustablepitch angle availability.The Fläkt Woods impellers are all high pressure die cast to offer thin aerofoil sections for low generation of noise.Every cast aluminium component is X-ray examined using Real Time Radiography inspection prior to assembly.The maximum pitch angles shown allow for speed control by frequency inverter (3ph only).

Motors

All motors are totally enclosed air stream rated class F insulation. Constructed from aluminium or cast iron as standard with special ‘T’ slot or pad mounted fixings. Single speed motors are suitable for speed control by voltage regulation where indicated. Three phase motors are suitable for use with frequency inverters.Two speed motors where available are pole change type.Suitable for horizontal through to vertical shaft operation. Supplied IP55, with removable drain plugs. Sealed for life bearings lubricated with wide temperature range grease. The BT, CT, F22 and PM112 motors are all fitted with overheat protection thermostat as standard. D motors are fitted with Thermistor OHP.These motors are suitable for inverter speed control down to 20% of full speed.

Electrical Supply

220 - 240 V / 50 Hz / 1 φ380 - 420 V / 50 Hz / 3 φ

Temperature Range

-40°C to 50°C as standard. (All motors are not suitable for starting at temperatures lower than -20°C.) Fans thatinclude BT or CT motors can be continuously operated at temperatures up to 70°C. When these fans are operatingin excess of 50°C they should be run at full speed only. Other fans can be operated up to 70°C with appropriatederation of motors.Most standard 3φ fans can be offered for a one off emergency operation at 200˚C for 2 hours.

Casings

JM Aerofoil fans are available in either a long cased form, complete with an externally mounted pre-wiredelectrical terminal box, or short cased for duct or plate installation. Casings are spun from sheet steel with integralpre-drilled and radiused inlet flanges. The galvanised finish gives a high resistance to corrosion and is ideal forexternal as well as internal use.

Accessories

Silencers, Mounting feet, Vibration isolators, Matching flanges, Flexible connectors, Air operated non return dampers, Guards, Bell mouth inlets. Electronic and transformer type speed controllers and frequency inverters.

• Eleven sizes are offered from 315mm to 1000mm diameter.

• Volume flows of up to 19m3/s• Static pressures up to 800 Pa• High energy efficiency

• Low installed noise levels• Motor protection IP55• All casings are hot dipped galvanised• Overheat protection is fitted as standard • Inverter controllable

74

Aerofoil - JM Aerofoil Section 4

Section

4 - A

erofoil - JM A

erofoil

Standards available contact your local ExpressDistributor for more details. See section 4.3.

Page 5: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Summary JM Aerofoil Data Section 4

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

75

Dia. Product Product Speed Sound Electronic m3/s at Pa (Static)

mm Code Number rev/min Level Speed

dBA Controller 0 50 100 150 200 250 300 400 500

315 31JM/16/4/5/38 DX321460 1420 44 ME1.1 0.65 0.54

315 31JM/16/2/5/32 DX321202 2840 61 N/A 1.15 1.11 1.06 0.99 0.94 0.86 0.78 0.59

355 35JM/16/4/5/40 DX361460 1420 49 ME1.1 1.00 0.86 0.63

355 35JM/16/2/5/34 JL361205 2840 64 N/A 1.73 1.70 1.63 1.56 1.45 1.40 1.31 1.12

400 40JM/16/4/5/40 DX411452 1420 52 ME1.3 1.50 1.31 1.06

400 40JM/16/2/5/28 JL411203 2840 66 N/A 2.33 2.26 2.19 2.11 2.05 1.97 1.72 1.67 1.42

450 45JM/16/4/5/30 JL461452 1420 57 ME1.3 1.80 1.61 1.40 1.11

450 45JM/16/4/5/40 DX461466 1420 56 ME1.3 2.20 1.95 1.72

450 45JM/16/2/5/18 JL461201 2840 66 N/A 2.50 2.45 2.40 2.30 2.20 2.10 2.05 1.85 1.6

500 50JM/16/4/5/34 DX511464 1420 57 ME1.6 2.75 2.50 2.21 1.85

500 50JM/16/4/5/40 JL511460 1420 59 ME1.6 3.00 2.75 2.43

500 50JM/20/4/6/20 DX511455 1420 53 ME1.3 1.85 1.70 1.50 1.25

500 50JM/20/4/6/32 DX511466 1420 56 ME1.6 2.60 2.41 2.20 1.95 1.60

560 56JM/16/4/5/22 JL571453 1420 57 ME1.6 2.90 2.70 2.35 2.10 1.65

560 56JM/16/4/5/28 DX571456 1420 58 ME1.6 3.40 3.15 2.85 2.55 2.10

630 63JM/20/4/6/16 DX641453 1420 61 ME1.6 3.45 3.30 3.10 2.90 2.65 2.25

220 - 240 V / 50 Hz / 1φ

Quick selection guide to the JM Cased Aerofoil fans available

Express Range - These products are available from our UK Express Distributor on same day deliveryfrom the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

Full selection details and dimensions see section 4.1 or 9.1 (which covers all accessories)

Page 6: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Summary JM Aerofoil Data Section 4

Section

4 - A

erofoil - JM A

erofoil

76

Dia. Product Product Speed Sound Electronic m3/s at Pa (Static)

mm Code Number rev/min Level Speed Inverter

dBA Controller 0 50 100 150 200 250 300 400 500 600 800

315 31JM/16/4/5/40 DX341460 1420 44 ME3.5S FWD1 0.67 0.55

315 31JM/16/2/5/36 DX341202 2840 61 N/A FWD1 1.25 1.18 1.15 1.06 1.01 0.93 0.85

355 35JM/16/4/5/40 DX381460 1420 49 ME3.5S FWD1 1.00 0.86 0.63

355 35JM/16/2/5/34 DX381210 2840 64 N/A FWD1 1.73 1.70 1.63 1.56 1.45 1.40 1.31 1.12

355 35JM/16/2/5/40 JL381204 2840 66 N/A N/A 2.00 1.93 1.90 1.82 1.73 1.65 1.55 1.27

400 40JM/16/4/5/40 DX431452 1420 52 ME3.2D FWD1 1.50 1.31 1.06

400 40JM/16/2/5/32 DX431203 2840 66 N/A FWD2 2.60 2.51 2.42 2.35 2.27 2.18 2.08 1.86 1.61

450 45JM/16/4/5/30 JL481452 1420 52 ME3.2D N/A 1.80 1.61 1.40 1.11

450 45JM/16/4/5/40 DX481460 1420 56 ME3.2D FWD1 2.20 1.95 1.72

450 45JM/16/2/5/20 JL481202 2840 66 N/A N/A 2.65 2.60 2.54 2.48 2.40 2.31 2.20 2.02 1.80

450 45JM/20/2/6/34 EX481205 2910 72 N/A FWD4 3.85 3.80 3.70 3.60 3.52 3.40 3.31 3.12 2.90 2.70

500 50JM/16/4/5/34 DX531460 1420 57 ME3.2D FWD1 2.75 2.50 2.21 1.85

500 50JM/16/4/5/40 JL531454 1420 59 ME3.2D N/A 3.00 2.75 2.43

500 50JM/20/4/6/20 JL531456 1420 53 ME3.2D N/A 1.85 1.70 1.50 1.25

500 50JM/20/4/6/32 DX531462 1420 56 ME3.2D FWD1 2.60 2.41 2.20 1.95 1.60

500 50JM/20/4/6/40 JL531458 1420 58 ME3.2D N/A 2.97 2.77 2.51 2.20

500 50JM/20/2/6/24 EX531203 2840 70 N/A FWD4 4.30 4.22 4.18 4.05 4.00 3.90 3.80 3.62 3.42 3.22 2.60

500 50JM/20/2/6/34 DX531204 2840 74 N/A FWD6 5.52 5.48 5.35 5.27 5.20 5.09 4.92 4.75 4.45 4.22 3.60

560 56JM/16/4/5/24 JL591452 1420 57 ME3.2D N/A 3.05 2.82 2.55 2.22 1.82

560 56JM/16/4/5/32 DX591453 1420 58 ME3.2D FWD1 3.73 3.42 3.23 2.80 2.38

560 56JM/20/4/6/36 DX591458 1420 61 ME3.2D FWD2 4.05 3.82 3.60 3.21 2.90

560 56JM/20/2/6/24 EX591201 2910 73 N/A FWD6 6.30 6.20 6.10 6.05 5.90 5.85 5.70 5.46 5.20 5.08 4.35

630 63JM/20/6/6/22 JL661651 900 49 ME3.2D N/A 2.51 2.20 1.75

630 63JM/20/6/6/34 JL661652 900 50 ME3.2D N/A 3.55 3.10 2.50

630 63JM/20/4/6/22 DX661453 1420 61 ME3.2D FWD2 4.05 3.8 3.6 3.4 3.1 2.85

630 63JM/20/4/6/32 DX661454 1420 61 AT7.0 FWD2 5.30 5.10 4.81 4.55 4.15 3.82

710 71JM/20/6/6/22 JL741652 900 53 ME3.2D FWD1 3.75 3.55 3.00

710 71JM/20/6/6/36 EX741653 900 55 N/A FWD2 5.55 4.90 4.20

710 71JM/20/4/6/20 DX741404 1440 64 N/A FWD5 6.1 5.8 5.6 5.4 5.2 4.8 4.5

710 71JM/20/4/6/24 EX741401 1440 65 N/A FWD3 6.45 6.20 6.00 5.75 5.50 5.22 4.87

800 80JM/20/6/6/28 EX831651 935 58 N/A FWD2 6.60 5.70 5.20 4.50

800 80JM/20/6/6/36 JL831603 935 60 N/A FWD3 7.90 7.25 6.50 5.60

800 80JM/20/4/6/24 JL831412 1440 69 N/A FWD5 9.41 9.00 8.51 8.18 7.82 7.40 6.90

800 80JM/25/4/9/22 EX831405 1440 71 N/A FWD5 8.50 8.10 7.90 7.60 7.40 7.00 6.60 6.00

800 80JM/25/4/9/26 EX831408 1440 71 N/A FWD6 9.50 9.25 9.00 8.70 8.40 8.05 7.60 6.90

900 90JM/25/8/9/34 JL931802 695 58 N/A FWD2 8.20 7.32 6.25

900 90JM/25/6/6/32 EX933652 935 65 N/A FWD2 9.60 9.00 8.15 7.10

900 90JM/25/6/9/24 JL931602 935 63 N/A FWD3 8.50 8.05 7.55 7.05 6.55 5.70

900 90JM/25/4/9/22 EX931403 1440 74 N/A FWD7 12.50 12.10 12.00 11.50 11.10 10.70 10.40 10.00 8.90

900 90JM/25/4/9/30 EX931406 1440 75 N/A FWD8 16.20 15.20 14.80 14.40 14.00 13.70 13.30 12.40 11.80

1000 100JM/25/8/9/24 JL131802 695 61 N/A FWD2 8.80 7.90 6.70

1000 100JM/25/6/6/22 EX133652 950 68 N/A FWD3 10.80 9.90 8.10 6.90

1000 100JM/25/6/9/34 JL131609 960 71 N/A FWD6 15.40 14.60 14.00 13.00 12.00 10.80

1000 100JM/25/4/6/22 EX133402 1470 79 N/A FWD7 16.20 15.90 15.20 14.70 14.10 13.80 13.10 11.70 10.00

1000 100JM/25/4/9/20 JL131419 1470 79 N/A FWD8 16.50 16.00 15.50 15.10 14.90 14.30 13.90 12.80 11.60

1000 100JM/25/4/9/24 EX131405 1470 79 N/A FWD9 18.80 18.28 17.75 17.48 17.20 16.30 15.40 14.50 13.60

380 - 420 V / 50 Hz / 3φ

Full selection details and dimensions see section 4.1.

Page 7: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 31JM - 35JM Section 4.1

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

77

4 Pole

31JM/16/4/5/... 35JM/16/4/5/...

2 Pole

31JM/16/2/5/... 35JM/16/2/5/...

Electrical Data

† BT4 - 3φ

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Fans that include BT or CT motors can be continuously operated at temperatures up to 70°C.When these fans are operating in excess of 50°C they should be run at full speed only.

For Short cased fans please omit the prefix from the product number and state S-type on enquiries/orders.Product numbers shown are for Long cased fans.

Wiring diagram references can be found in section 9.2.

380-420V/50Hz/3φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 400V) (at 400V) Ref Elec- Trans- Inverter Level

(˚) (kW) (A) (A) tronic former dBA

31JM/16/4/5/40 1420 BT5/4 DX341460 34-40 0.13 0.47 1.8 CD1344 ME3.5S MT3.0.5 FWD1 44

31JM/16/2/5/34 2840 BT9 DX341202 8-34 0.58 1.4 6 CD1344 N/A N/A FWD1 61

35JM/16/4/5/40 1420 BT4 DX381460 22-40 0.13 0.47 1.8 CD1344 ME3.5S MT3.0.5 FWD1 49

35JM/16/2/5/34 2840 CT5 DX381210 8-34 0.95 2 9.5 CD1344 N/A N/A FWD1 64

35JM/16/2/5/40 2840 CT9 JL381204 36-40 1.7 3.7 19 CD1344 N/A N/A N/A 66

220-240V/50Hz/1φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 230V) (at 230V) Ref Elec- Trans- Level

(˚) (kW) (A) (A) tronic former dBA

31JM/16/4/5/40 1420 BT5/4† DX321460 24-38 0.12 0.9 1.8 CD1705 ME1.1 MT1.1 44

31JM/16/2/5/34 2840 BT9 DX321202 26-30 0.5 3.3 9 CD1705 N/A N/A 61

35JM/16/4/5/40 1420 BT4 DX361460 28-40 0.13 1 2 CD1705 ME1.1 MT1.1 49

35JM/16/2/5/34 2840 CT5 JL361205 32-34 1.0 5.9 11.5 CD1705 N/A N/A 64

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400

31JM/16/4/5/40 1420 0.67 0.55

31JM/16/2/5/34 2840 1.25 1.18 1.15 1.06 1.01 0.93 0.85

35JM/16/4/5/40 1420 1.00 0.86 0.63

35JM/16/2/5/34 2840 1.73 1.70 1.63 1.56 1.56 1.40 1.31 1.12

35JM/16/2/5/40 2840 2.00 1.93 1.9 1.82 1.73 1.65 1.55 1.27

Page 8: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 31JM - 35JM Section 4.1

Section

4 - A

erofoil - JM A

erofoil

78

Dimensions

All dimensions shown in mm.

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which covers all accessories)

Long Cased

Short Cased

Product Motor A B C D E F G H J K L M N P S T U X Max. Fan

Code Range Weight (kg)

Long Cased

31JM BT4/5 315 395 330 235 2.0 25 175 355 66 245 265 315 10 200 8 10 - 0.8 23

31JM BT9 315 395 375 235 2.5 25 175 355 66 289 265 315 10 200 8 10 - 0.8 27

35JM BT4/CT5 355 435 330 256 2.0 25 200 395 66 245 305 355 10 225 8 10 - 1.1 24

35JM CT9 355 435 375 256 2.5 25 200 395 66 289 305 355 10 225 8 10 - 1.1 28

Short Cased

31JM BT4/5 315 395 301 225 2.5 - - 355 - - - - - - 8 10 - - 13.5

31JM BT9 315 395 333 225 2.5 - - 355 - - - - - - 8 10 - - 15

35JM BT4/5 355 435 301 225 2.5 - - 395 - - - - - - 8 10 - - 14

35JM CT5 355 435 308 225 2.5 - - 395 - - - - - - 8 10 - - 16.5

35JM CT9 355 435 348 225 2.5 - - 395 - - - - - - 8 10 - - 20.5

Page 9: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

79

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

Aerofoil fan 40JM - 45JM Section 4.1

4 Pole

40JM/16/4/5/... 45JM/16/4/5/...

2 Pole

40JM/16/2/5/... 45JM/16/2/5/... 45JM/20/2/6/...

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400 500 600

40JM/16/4/5/40 1420 1.50 1.31 1.06

40JM/16/2/5/32 2840 2.60 2.51 2.42 2.35 2.27 2.18 2.08 1.86 1.61

45JM/16/4/5/30 1420 1.80 1.61 1.40 1.1

45JM/16/4/5/40 1420 2.20 1.95 1.72

45JM/16/2/5/20 2840 2.65 2.60 2.54 2.48 2.40 2.31 2.20 2.02 1.80

45JM/20/2/6/34 2910 3.85 3.80 3.70 3.60 3.52 3.40 3.31 3.12 2.90 2.70

Electrical Data

380-420V/50Hz/3φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 400V) (at 400V) Ref Elec- Trans- Inverter Level

(˚) (kW) (A) (A) tronic former dBA

40JM/16/4/5/… 1420 BT9 DX431452 36-40 0.3 0.89 4.6 CD1559 ME3.2D MT3.1 FWD1 52

40JM/16/2/5/… 2840 CT9 DX431203 8-32 1.7 3.7 20 CD1344 N/A N/A FWD2 66

45JM/16/4/5/… 1420 BT9 JL481452 26 0.3 0.89 4.6 CD1559 ME3.2D MT3.1 N/A 52

45JM/16/4/5/… 1420 CT5 DX481460 40 0.58 1.7 6.5 CD1559 ME3.2D MT3.2 FWD1 56

45JM/16/2/5/… 2840 CT9 JL481202 8-20 1.7 3.7 20 CD1344 N/A N/A N/A 66

45JM/20/2/6/… 2910 F22 EX481205 8-34 3.8 7.2 64 CD1343 N/A N/A FWD4 72

220-240V/50Hz/1φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 230V) (at 230V) Ref Elec- Trans- Level

(˚) (kW) (A) (A) tronic former dBA

40JM/16/4/5/… 1420 BT9 DX411452 34-40 0.3 2.1 5.3 CD1705 ME1.3 MT1.5 52

40JM/16/2/5/… 2840 CT9 JL411203 24-28 1.4 8.3 27 CD1705 N/A N/A 66

45JM/16/4/5/… 1420 BT9 JL461452 24-30 0.3 2.1 5.3 CD1705 ME1.3 MT1.5 52

45JM/16/4/5/… 1420 CT5 DX461466 36-40 0.45 2.8 6 CD1705 ME1.3 MT1.5 5645JM/16/2/5/… 2840 CT9 JL461201 16-18 1.4 8.3 27 CD1705 N/A N/A 66

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Fans that include BT or CT motors can be continuously operated at temperatures up to 70°C.When these fans are operating in excess of 50°C they should be run at full speed only.

For Short cased fans please omit the prefix from the product number and state S-type on enquiries/orders.Product numbers shown are for Long cased fans.

Wiring diagram references can be found in section 9.2.

Page 10: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

80

Section

4 - A

erofoil - JM A

erofoil

Aerofoil fan 40JM - 45JM Section 4.1

Product Motor A B C D E F G H J K L M N P S T U X Max. Fan

Code Range Weight (kg)

Long Cased

40JM BT9:CT9 400 480 375 279 2.5 25 225 450 66 289 350 400 10 250 8 12 - 1.2 30

45JM CT5 450 530 330 306 2.0 25 225 500 66 245 400 450 10 280 8 12 - 1.5 32

45JM BT9:CT9 450 530 375 306 2.5 25 225 500 66 289 400 450 10 280 8 12 - 1.5 32

45JM F22 450 530 520 306 3 25 255 500 66 434 400 450 10 280 8 12 - 1.5 50

Short Cased

40JM BT 400 480 333 225 2.5 - - 450 - - - - - - 8 12 - - 16.5

40JM CT 400 480 333 348 2.5 - - 450 - - - - - - 8 12 - - 21

45JM BT 450 530 333 225 2.5 - - 500 - - - - - - 8 12 - - 18.5

45JM CT 450 530 348 225 2.5 - - 500 - - - - - - 8 12 - - 23

45JM F22 450 530 444 225 3 - - 500 - - - - - - 8 12 - - 40

All dimensions shown in mm.

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Dimensions

Long Cased

Short Cased

Page 11: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

81

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

Aerofoil fan 50JM Section 4.1

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

† For 56JM tabular data – see page 83

4 Pole

50JM/16/4/5/... 50JM/20/4/6/...

2 Pole

50JM/ 20/2/6/... †56JM/20/2/6/...

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400 500 600

50JM/16/4/5/34 1420 2.75 2.50 2.21 1.85

50JM/16/4/5/40 1420 3.00 2.75 2.43

50JM/20/4/6/20 1420 1.85 1.70 1.50 1.25

50JM/20/4/6/32 1420 2.60 2.41 2.20 1.95 1.60

50JM/20/4/6/40 1420 2.97 2.77 2.51 2.20

50JM/20/2/6/24 2840 4.30 4.22 4.18 4.05 4.00 3.90 3.80 3.62 3.42 2.60

50JM/20/2/6/34 2840 5.52 5.48 5.35 5.27 5.20 5.09 4.92 4.75 4.45 3.60

Electrical Data

380-420V/50Hz/3φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 400V) (at 400V) Ref Elec- Trans- Inverter Level

(˚) (kW) (A) (A) tronic former dBA

50JM/16/4/5/… 1420 CT5 DX531460 28-34 0.58 1.7 6.5 CD1559 ME3.2D MT3.2 FWD1 57

50JM/16/4/5/… 1420 CT9 JL531454 34-40 0.91 2.49 13 CD1559 ME3.2D MT3.2 N/A 59

50JM/20/4/6/… 1420 BT9 JL531456 16-20 0.3 0.89 4.6 CD1559 ME3.2D MT3.1 N/A 53

50JM/20/4/6/… 1420 CT5 DX531462 26-32 0.58 1.7 6.5 CD1559 ME3.2D MT3.2 FWD1 56

50JM/20/4/6/… 1420 CT9 JL531458 34-40 0.91 2.49 13 CD1559 ME3.2D MT3.2 N/A 58

50JM/20/2/6/… 2840 F22 EX531203 8-24 3.8 7.1 44 CD1343 N/A N/A FWD4 70

50JM/20/2/6/… 2840 PM112 DX531204 26-34 6.2 11.6 100 CD1343 N/A N/A FWD6 74

220-240V/50Hz/1φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 230V) (at 230V) Ref Elec- Trans- Level

(˚) (kW) (A) (A) tronic former dBA

50JM/16/4/5/… 1420 CT5 DX511464 32-34 0.55 3.7 5.5 CD1705 ME1.6 MT1.5 57

50JM/16/4/5/… 1420 CT9 JL511460 38-40 0.68 4.2 11 CD1705 ME1.6 MT1.5 59

50JM/20/4/6/… 1420 BT9 DX511455 16-20 0.3 2.1 5.3 CD1705 ME1.3 MT1.5 53

50JM/20/4/6/… 1420 CT5 DX511466 30-32 0.55 3.7 5.5 CD1705 ME1.6 MT1.5 56

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Fans that include BT or CT motors can be continuously operated at temperatures up to 70°C.When these fans are operating in excess of 50°C they should be run at full speed only.

For Short cased fans please omit the prefix from the product number and state S-type on enquiries/orders.Product numbers shown are for Long cased fans.

Wiring diagram references can be found in section 9.2.

Page 12: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 50JM Section 4.1

Section

4 - A

erofoil - JM A

erofoil

82

Product Motor A B C D E F G H J K L M N P S T U X Max. Fan

Code Range Weight (kg)

Long Cased

50JM CT5 500 594 330 338 2.0 25 290 560 66 235 450 500 10 315 12 12 - 2.0 34

50JM BT9:CT9 500 594 375 338 2.5 25 290 560 66 280 450 500 10 315 12 12 - 2.0 34

50JM F22/PM112 500 594 520 338 3 25 290 560 66 424 450 500 10 315 12 12 - 2.0 67

Short Cased

50JM BT9 500 594 333 225 2.5 - - 560 - - - - - - 12 12 - - 20

50JM CT5 500 594 308 225 2.5 - - 560 - - - - - - 12 12 - - 20.5

50JM CT9 500 594 348 225 2.5 - - 560 - - - - - - 12 12 - - 25

50JM F22 500 594 444 225 3 - - 560 - - - - - - 12 12 - - 43

50JM PM112 500 594 392 225 3 - - 560 - - - - - - 12 12 - - 50

Dimensions

All dimensions shown in mm.

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Long Cased

Short Cased

Page 13: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 56JM - 63JM Section 4.1

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

83

Electrical DataFor graphical data of 56JM 2 Pole see page 69

4 Pole

56JM/20/4/6/... 63JM/20/4/6/...

6 Pole

63JM/20/6/6/...

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400 500 600

56JM/16/4/5/24 1420 3.05 2.82 2.55 2.22 1.82

56JM/16/4/5/32 1420 3.73 3.42 3.23 2.80 2.38

56JM/20/4/6/36 1420 4.05 3.82 3.60 3.21 2.90

56JM/20/2/6/24 2910 6.30 6.20 6.10 6.05 5.90 5.85 5.70 5.46 5.20 4.35

63JM/20/6/6/22 900 2.51 2.2 1.75

63JM/20/6/6/34 900 3.55 3.10 2.50

63JM/20/4/6/18 1420 3.45 3.30 3.10 2.90 2.65 2.25

63JM/20/4/6/32 1420 5.30 5.10 4.81 4.55 4.15 3.82

380-420V/50Hz/3φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 400V) (at 400V) Ref Elec- Trans- Inverter Level

(˚) (kW) (A) (A) tronic former dBA

56JM/16/4/5/… 1420 CT5 JL591452 18-24 0.45 1.6 6 CD1343 ME3.2D MT3.2 N/A 57

56JM/16/4/5/… 1420 CT9 DX591453 26-32 0.91 2.49 13 CD1343 ME3.2D MT3.2 FWD1 5

56JM/20/4/6/… 1420 CT9 DX591458 32-36 1.15 3 14 CD1343 ME3.2D AT7.0 FWD2 61

56JM/20/2/6/… 2910 PM112 EX591201 8-24 6.2 11.6 100 CD1343 N/A N/A FWD6 73

63JM/20/6/6/… 900 CT5 JL661651 20-22 0.3 1.1 3.3 CD1559 ME3.2D MT3.2 N/A 49

63JM/20/6/6/… 900 CT9 JL661652 30-34 0.52 1.7 7.5 CD1559 ME3.2D MT3.2 N/A 50

63JM/20/4/6/… 1420 CT9 DX661453 20-22 1.15 3 14 CD1559 ME3.2D AT7.0 FWD2 61

63JM/20/4/6/… 1420 F22 DX661454 24-32 2.1 5 27 CD1343 N/A AT7.0 FWD2 61

220-240V/50Hz/1φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 230V) (at 230V) Ref Elec- Trans- Level

(˚) (kW) (A) (A) tronic former dBA

56JM/16/4/5/… 1420 CT5 JL571453 22 0.55 3.7 5.5 CD1705 ME1.6 MT1.5 57

56JM/16/4/5/… 1420 CT9 DX571456 28 0.97 6.2 19 CD1705 ME1.6 MT1.8 58

56JM/16/4/5/… 1420 CT9 DX571455 32 0.97 6.2 19 CD1705 ME1.6 MT1.8 58

56JM/20/4/6/... 1420 CT9 DX571459 28 0.97 6.2 19 CD1705 ME1.6 MT1.8 58

63JM/20/4/6/… 1420 CT9 DX641453 16 0.97 6.2 19 CD1705 ME1.6 MT1.8 61

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Fans that include BT or CT motors can be continuously operated at temperatures up to 70°C.When these fans are operating in excess of 50°C they should be run at full speed only.

For Short cased fans please omit the prefix from the product number and state S-type on enquiries/orders.Product numbers shown are for Long cased fans.

Page 14: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 56JM - 63JM Section 4.1

Section

4 - A

erofoil - JM A

erofoil

84

Dimensions

All dimensions shown in mm.

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Wiring diagram references can be found in section 9.2.

Product Motor A B C D E F G H J K L M N P S T U X Max. Fan

Code Range Weight (kg)

Long Cased

56JM CT 560 654 375 368 2.5 25 330 620 66 280 510 560 10 355 12 12 - 2.3 38

56JM F22 560 654 520 368 3 25 330 620 66 424 510 560 10 355 12 12 - 2.3 62

63JM CT 630 724 375 403 3 25 375 690 66 289 580 630 10 400 12 12 - 2.4 52

63JM F22/PM112 630 724 520 403 3 25 375 690 66 434 580 630 10 400 12 12 - 2.4 83

Short Cased

56JM CT5 560 654 308 225 2.5 - - 620 - - - - - - 12 12 - - 22

56JM CT9 560 654 348 225 2.5 - - 620 - - - - - - 12 12 - - 26

56JM PM112 560 654 392 225 3 - - 620 - - - - - - 12 12 - - 52

63JM CT5 630 724 308 225 3 - - 690 - - - - - - 12 12 - - 36

63JM CT9 630 724 348 225 3 - - 690 - - - - - - 12 12 - - 40

63JM F22 630 724 444 225 3 - - 690 - - - - - - 12 12 - - 56

Long Cased

Short Cased

Page 15: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 71JM - 80JM Section 4.1

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

85

80JM/20/6/6/...

6 Pole

71JM/20/6/6/... 80JM/25/4/9/...

4 Pole

71JM/20/4/6/... 80JM/20/4/6/...

Electrical Data

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400

71JM/20/6/6/22 900 3.75 3.55 3.00

71JM/20/6/6/36 900 5.55 4.90 4.20

71JM/20/4/6/24 1440 6.45 6.20 6.00 5.75 5.50 5.22 4.87

71JM/20/4/6/20 1440 8.8 8.4 8.0 7.6 7.2 6.8 6.3

80JM/20/6/6/28 935 6.60 5.70 5.20 4.50

80JM/20/6/6/36 935 7.90 7.25 6.50 5.60

80JM/20/4/6/24 1440 9.41 9.00 8.51 8.18 7.82 7.40 6.90

80JM/25/4/9/22 1440 8.50 8.10 7.90 7.60 7.40 7.00 6.60 6.00

80JM/25/4/9/26 1440 9.50 9.25 9.00 8.70 8.40 8.05 7.60 6.90

380-420V/50Hz/3φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Rating Current Current Diagram Sound

rev/min (at 400V) (at 400V) Ref Elec- Trans- Inverter Level

(˚) (kW) (A) (A) tronic former dBA

71JM/20/6/6/… 900 CT9 JL741652 20-22 0.52 1.7 7.5 CD1559 ME3.2D MT3.2 FWD1 53

71JM/20/6/6/… 900 F22 EX741653 24-36 1.35 3.6 15 CD1559 N/A AT7.0 FWD2 55

71JM/20/4/6/… 1440 F22 EX741401 8-24 2.7 5.8 30 CD1343 N/A N/A FWD3 65

71JM/20/4/6/… 1440 PM112 DX741404 18-36 4.4 9.3 55 CD1343 N/A N/A FWD5 68

80JM/20/6/6/… 935 F22 EX831651 24-26 1.35 3.6 15 CD1559 N/A AT7.0 FWD2 58

80JM/20/6/6/… 935 F22 JL831603 30-36 2.5 6.4 26 CD1343 N/A N/A FWD3 60

80JM/20/4/6/… 1440 PM112 JL831412 8-24 4.4 9.3 55 CD1343 N/A N/A FWD5 69

80JM/25/4/9/… 1440 PM112 EX831405 8-22 4.4 9.3 55 CD1343 N/A N/A FWD5 71

80JM/25/4/9/… 1440 *D132 EX831408 24-26 6.3 12.7 86 CD1343 N/A N/A FWD6 71

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Fans that include BT or CT motors can be continuously operated at temperatures up to 70°C.When these fans are operating in excess of 50°C they should be run at full speed only.

For Short cased fans please omit the prefix from the product number and state S-type on enquiries/orders.Product numbers shown are for Long cased fans.

* OHP = Thermistor. Maximum pitch angle at 200° = 24°.Wiring diagram references can be found in section 9.2.

Page 16: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Section

4 - A

erofoil - JM A

erofoil

86

Aerofoil fan 71JM - 80JM Section 4.1

Dimensions

All dimensions shown in mm

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Product Motor A B C D E F G H J K L M N P S T U X Max. Fan

Code Range Weight (kg)

Long Cased

71JM CT9 710 804 375 443 3 25 415 770 66 259 660 710 10 440 16 12 - 4.5 54

71JM F22/PM112 710 804 520 443 3 25 415 770 66 404 660 710 10 440 16 12 - 4.5 87

80JM F22/PM112 800 894 520 488 3 25 485 860 66 404 750 800 10 510 16 12 - 5.8 96

80JM D132 800 894 520 525 5 25 485 860 66 400 750 800 12 510 16 12 - 7.0 192

Short Cased

71JM CT9 710 804 348 225 3 - - 770 - - - - - - 16 12 - - 42

71JM F22 710 804 348 225 3 - - 770 - - - - - - 16 12 - - 52

71JM PM112 710 804 348 225 3 - - 770 - - - - - - 16 12 - - 63

80JM F22 800 894 444 225 3 - - 860 - - - - - - 16 12 - - 65

80JM PM112 800 894 392 225 3 - - 860 - - - - - - 16 12 - - 72

80JM D132 800 894 478 260 4 - - 860 - - - - - - 16 12 - - 174

Long Cased

Short Cased

Page 17: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 90JM - 100JM Section 4.1

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

87

Electrical Data

8 Pole

90JM/25/8/9/... 100JM/25/8/9/...

4 Pole

90JM/25/4/9/... 100JM/25/4/9/...

100JM/25/6/9/...

6 Pole

90JM/25/6/6/... 100JM/25/6/6/...

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400 500

90JM/25/8/9/34 695 8.20 7.32 6.25

90JM/25/6/6/32 935 9.60 9.00 8.15 7.10

90JM/25/6/9/24 935 8.50 8.05 7.55 7.05 6.55 5.70

90JM/25/4/9/22 1440 12.5 12.1 12.0 11.5 11.1 10.7 10.4 10.0 8.9

90JM/25/4/9/30 1440 16.2 15.2 14.8 14.4 14.0 13.7 13.3 12.4 11.8

100JM/25/8/9/24 695 8.8 7.9 6.7

100JM/25/6/6/22 950 10.8 9.9 9.0 8.1 6.9

100JM/25/6/9/34 960 15.4 14.6 14.0 13.0 12.0 10.8

100JM/25/4/6/22 1470 16.2 15.9 15.2 14.7 14.1 13.8 13.1 11.7 10.0

100JM/25/4/9/20 1470 16.5 16.0 15.5 15.1 14.9 14.3 13.9 12.8 11.6

100JM/25/4/9/24 1470 18.8 18.28 17.75 17.48 17.2 16.3 15.4 14.5 13.6

380-420V/50Hz/3φ

Product Speed Motor Product Pitch Pitch Motor Full Load Starting Wiring Speed Controller

Code Number Angle Angle Rating Current Current Diagram Sound

rev/min 200˚C (at 400V) (at 400V) Ref Elec- Trans- Inverter Level

(˚) (˚) (kW) (A) (A) tronic former dBA

90JM/25/8/9/… 695 F22 JL931802 8-32 32 1.4 4.9 18 CD1343 N/A N/A FWD2 58

90JM/25/6/6/… 935 F22 JL933602 24-32 28 2.5 6.4 26 CD1343 N/A N/A FWD3 65

90JM/25/6/9/… 935 F22 JL931602 8-24 24 2.5 6.4 26 CD1343 N/A N/A FWD3 63

90JM/25/4/9/… 1450 *D132 EX931403 8-16 20 9 16.6 125 CD1343 N/A N/A FWD7 74

90JM/25/4/9/… 1440 *D160 EX931406 24-28 28 13 24.3 172 CD1343 N/A N/A FWD8 75

100JM/25/6/6/… 950 F22 JL133602 8-22 30 2.5 6.42 26 CD1343 N/A AT7.0 FWD3 68

100JM/25/6/9/… 960 *D132 JL131609 28-34 18 6.3 13.7 104 CD1343 N/A N/A FWD6 71

100JM/25/4/6/… 1470 *D132 EX133402 8-20 18 9 16.6 125 CD1343 N/A N/A FWD7 79

100JM/25/4/9/… 1470 *D160 JL131419 8-18 18 13 23.4 164.6 CD1343 N/A N/A FWD8 79

100JM/25/4/9/… 1470 *D160 EX131405 24 20 17 32.1 226.2 CD1343 N/A N/A FWD9 79

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented forcomparative purposes only.

For Short cased fans please omit the prefix from the product number and state S-type on enquiries/orders.Product numbers shown are for Long cased fans.

* OHP = Thermistor

Page 18: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil fan 90JM - 100JM Section 4.1

Section

4 - A

erofoil - JM A

erofoil

88

Dimensions

All dimensions shown in mm.

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Wiring diagram references can be found in section 9.2.

Product Motor A B C D E F G H J K L M N P S T U X Max. Fan

Code Range Weight (kg)

Short Cased

90JM F22 900 1006 520 538 3 25 491 970 66 444 850 900 10 518 16 15 - 5.3 94

90JM D132 900 1006 520 575 5 25 491 970 66 440 850 900 12 518 16 15 - 5.3 206

90JM D160 900 1006 711 575 5 25 491 970 66 629 850 900 10 518 16 15 - 5.3 270

100JM F22 1000 1106 520 588 3 25 547 1070 66 444 950 1000 10 574 16 15 - 6.2 102

100JM D132 1000 1106 625 588 5 25 547 1070 66 440 950 1000 10 574 16 15 - 6.2 227

100JM D160 1000 1106 711 625 6 25 547 1070 66 539 950 1000 12 574 16 15 - 6.2 286

Long Cased

90JM F22 900 1006 444 225 3 - - 970 - - - - - - 16 15 - - 67

90JM D132 900 1006 438 300 5 - - 970 - - - - - - 16 15 - - 143

90JM D160 900 1006 515 300 5 - - 976 - - - - - - 16 15 - - 207

100JM F22 1000 1106 444 225 3 - - 1070 - - - - - - 16 15 - - 72

100JM D132 1000 1106 478 300 5 - - 1070 - - - - - - 16 15 - - 190

100JM D160 1000 1106 643 300 5 - - 1070 - - - - - - 16 15 - - 291

Long Cased

Short Cased

Page 19: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sec

tion

4 - A

erof

oil - JM

Hig

h T

empe

ratu

re

Page 20: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

90

Aerofoil - JM High Temperature Section 4.2

Section

4 - A

erofoil - JM H

igh Tem

perature

Sizes

31JM - (315mm) to 100JM - (1000mm).Other sizes are available on request.

Fan Performance

All fans are tested to the latest internationally recognised standard IS05801 Part 1, installation category D for aerodynamic performance and BS848 Part 2 (1985) for acoustic performance. Coupled with a wide range of diameters, the adjustable pitch Aerofoil impeller gives the exact performancerequired, with a non overloading fan characteristic.

Impellers

A unique high efficiency aerofoil section blade with a purposely smoothed hub and clamp plate for adjustablepitch angle availability. The Fläkt Woods impellers are all high pressure die cast to offer thin aerofoil sections for low generation of noise.Every cast aluminium component is X-ray examined using Real Time Radiography inspection prior to assembly.The maximum pitch angles shown allow for speed control by frequency inverter.

Motors

Fläkt Woods H.T. Series fans utilise a totally enclosed squirrel cage motor.The grades of motor insulation have been selected to meet the specific requirements for each of the H.T. Categories.These motors are suitable for inverter speed control down to 20% of full speed.

Electrical Supply

400 V / 50 Hz / 3 φ

Temperature Range

Fans are tested in compliance with high temperature test standard directive 89/106/EEC to EN 12101-3, and are fully CE marked accordingly.Fläkt Woods H.T. Series fan motors are sized to run the fans continuously at normal ambient temperatures (-40°C to 50°C), as well as operating at their emergency high temperature category. (All motors are not suitable for starting at temperatures lower than -20°C.).

Most Standard 3 φ fans can be offered for a one off emergency operation at 200°C for 2 hours.Note: During emergency use inverter should be overridden for full speed.

Casings

JM HT Aerofoil fans are available in either a long cased form, complete with an externally mounted pre-wired electrical terminal box.

Casings are spun from sheet steel with integral pre-drilled and radiused inlet flanges. The galvanised finish gives a high resistance to corrosion and is ideal for external as well as internal use.

AccessoriesSilencers, Mounting feet, Spring type vibration isolators, Matching flanges, Flexible connectors, Air operated non return dampers, Guards, Bell mouth inlets.

• Designed for emergency ventilation of hot firesmoke applications

• 300°C or 400°C for two hours operation, CE marked to EN12101-3 2002

• Sizes from 315mm to 1000mm

• All casings are hot dipped galvanised• Volume flows up to 21m3/s • Static pressures up to 600 Pa• Motor protection IP55• Inverter controllable for ambient temperatures

Page 21: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM HT 300/2 Section 4.2

Sec

tion

4 - A

erof

oil - JM

Hig

h T

empe

ratu

re

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

91

Electrical Data

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400 500 600

31JM/16/2/5/... 2770 1.3 1.25 1.2 1.1 1.05 1.0 0.88

40JM/16/2/5/... 2725 2.6 2.5 2.4 2.3 2.25 2.2 2.1 1.8 1.6

63JM/20/4/6/... 1385 5.4 5.1 4.9 4.7 4.4 4.2

71JM/20/4/6/... 1385 7.8 7.7 7 6.8 6.5 6.1 5.8

80JM/25/4/9/... 1460 12.2 11.9 11.5 11 10.4 10.1 9.8 8.8

90JM/25/4/9/... 1450 16 15.7 15.5 15.2 14.8 14.5 14 13 12 11

100JM/25/4/9/... 1440 20.4 19.6 19 18.7 18.4 18 17.5 16.4 15.5 14.4

380-420V/50Hz/3φProduct Speed Motor Product Pitch Motor Full Load Starting Wiring Speed

Code Number Angle Rating Current Current Diagram Controller Sound

rev/min (at 400V) (at 400V) Ref Inverter Level

(˚) (kW) (A) (A) dBA

31JM/16/2/5/.. 2770 80 EF349232 38 0.9 1.9 9.2 CD1344 FWD1 59

40JM/16/2/5/.. 2725 80 EF439230 32 1.73 3.65 19.3 CD1344 FWD2 48

63JM/20/4/6/.. 1385 100L EF669432 36 3.65 7.04 38.7 CD1344 FWD4 63

71JM/20/4/6/.. 1385 100L EF749431 30 3.6 7.04 38.7 CD1344 FWD4 65

80JM/25/4/9/.. 1460 132M EF839433 36 9 17 113.9 CD1343 FWD7 71

90JM/25/4/9/.. 1450 132M/L EF939431 30 12.1 23.2 181 CD1343 FWD8 76

100JM/25/4/9/.. 1440 160L EF139435 28 18 34.7 170.7 CD1343 FWD9 81

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Performance shown at emergency operating temperatures.

For short cased fans please enquire.

Wiring diagram references can be found in section 9.2.

4 Pole

63JM/20/4/6/... 31JM/16/2/5/...

2 Pole

80JM/20/4/6/... 100JM/25/4/9/... 40JM/16/2/5/...

Page 22: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM HT 300/2 Section 4.2

Section

4 - A

erofoil - JM H

igh Tem

perature

92

All dimensions shown in mm.

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories).

Product Motor A B C D E G H K L M N P S T X Max. Fan

Code Range (kg) Weight (kg)

Long Cased

31JM/16/2/5/... 2770 315 395 375 235 2.5 175 355 289 265 315 10 200 8 10 0.8 31

40JM/16/2/5/... 2725 400 480 375 279 2.5 225 450 289 350 400 10 250 8 12 1.2 32

63JM/20/4/6/... 1385 630 724 520 403 3 375 690 434 580 630 10 400 12 12 2.5 75

71JM/20/4/6/... 1385 710 804 520 443 3 415 770 404 660 710 10 440 16 12 4.5 77

80JM/25/4/9/... 1460 800 894 520 525 5 485 860 400 750 800 12 510 16 12 5.8 163

90JM/25/4/9/... 1450 900 1006 520 575 5 491 970 444 850 900 12 518 16 15 5.3 177

100JM/25/4/9/... 1140 1000 1006 625 625 5 547 1070 545 950 1000 12 574 16 15 6.2 284

Dimensions

Long Cased

Page 23: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM HT 400/2 Section 4.2

Sec

tion

4 - A

erof

oil - JM

Hig

h T

empe

ratu

re

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

93

Electrical Data

4 Pole

63JM/20/4/6/...71JM/25/4/9/... 80JM/25/4/9/...100JM/31/4/9/...

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400 500 600

31JM/16/2/5/... 2850 1.25 1.18 1.15 1.05 1.01 0.93 0.85

35JM/16/2/5/... 2750 2.0 1.93 1.9 1.82 1.73 1.65 1.55 1.27

40JM/16/2/5/... 2720 2.6 2.51 2.42 2.35 2.27 2.18 2.08 1.86 1.61

63JM/40/4/6/... 1440 4.9 4.8 4.3 4.1 3.9 3.4

71JM/28/4/9/... 1440 6.9 6.6 6.4 6.2 6.0 5.7 5.4 4.5

80JM/25/4/9/... 1440 10.6 10.3 10 9.8 9.5 9.0 8.6 7.8

90JM/31/4/6/... 1455 14.8 14.5 14.0 13.8 13.2 13.0 12.3 11.9 10.8

100/JM31/4/6/... 1450 17 16.5 16 15.3 14.5 13.7 13.0 11.4 11.0 10.0

100/JM31/4/9/... 1450 20.4 19.6 19.0 18.7 18.4 18 17.5 16.4 15.5 14.4

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Performance shown at emergency operating temperatures.For short cased fans please enquire.Wiring diagram references can be found in section 9.2.

380-420V/50Hz/3φProduct Speed Motor Product Pitch Motor Full Load Starting Wiring Speed

Code Number Angle Rating Current Current Diagram Controller Sound

rev/min (at 400V) (at 400V) Ref Inverter Level

(˚) (kW) (A) (A) dBA

31JM/16/2/5/... 2850 D80 EF349242 40 0.9 1.9 4.47 CD1344 FWD1 61

35JM/16/2/5/... 2750 80 EF389240 40 1.73 3.69 19.2 CD1344 FWD2 66

40JM/16/2/5/... 2720 80 EF439241 32 1.73 3.69 19.2 CD1344 FWD2 66

63JM/40/4/6/... 1440 90L EF669442 28 1.8 3.87 24 CD1344 FWD2 61

71JM/28/4/9/... 1440 100L EF749443 28 3.6 7.82 46.9 CD1344 FWD4 68

80JM/25/4/9/... 1440 132S EF839444 30 6.6 12.9 86.4 CD1343 FWD6 71

90JM/31/4/6/... 1455 132M EF939440 26 11 21.1 139 CD1343 FWD7 75

100/JM31/4/6/... 1450 132M EF139448 24 11 21.1 139 CD1343 FWD7 81

100/JM31/4/9/... 1450 160L EF139447 28 18 34.7 163 CD1343 FWD9 86

40JM/16/2/5/...

4 Pole

31JM/16/2/5 35JM/16/2/5/...

Page 24: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM HT 400/2 Section 4.2

Section

4 - A

erofoil - JM H

igh Tem

perature

94

Product Motor A B C D E G H K L M N P S T X Max. Fan

Code Range (kg) Weight (kg)

Long Cased

31JM/16/2/5/... D80 315 395 375 235 2.5 175 355 289 265 315 10 200 8 10 0.8 31

35JM/16/2/5/... 80 355 435 375 358 2.5 200 395 285 305 355 10 225 8 5 0.75 36

40JM/16/2/5/... 80 400 480 375 279 2.5 225 450 289 350 400 10 250 8 12 1.2 32

63JM/20/4/6/... 90L 630 724 520 403 3 375 690 434 580 630 10 400 12 12 2.5 73

71JM/25/4/9/... 100L 710 804 520 443 3 415 770 404 650 710 10 440 16 12 4.5 77

80JM/25/4/9/... 132S 800 894 520 525 5 485 860 400 750 800 12 510 16 12 5.8 166

90JM/25/4/9/... 132M 900 1006 520 575 5 491 970 444 850 900 12 518 16 15 5.3 177

100JM/31/4/6/... 132M 1000 1106 520 625 5 547 1070 444 950 1000 12 574 16 15 6.2 226

100JM/31/4/9/... D160 1000 1106 625 625 5 547 1070 545 950 1000 12 574 16 15 6.2 284

Dimensions

All dimensions shown in mm.

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Long Cased

Page 25: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Aerofoil ATEX Section 4.3

Sec

tion

4 - A

erof

oil - JM

ATE

X

95

Atex standards now available with the Fläkt Woods JM Aerofoil range. Contact your local Express Distributor for further details on availability.

The high specification Industrial Markets in Europe require high specification products for the hazardous application sector. To support our customers Fläkt Woods can offer ATEX compliance on its JM Aerofoil axial fans and its new Centripal EU range of centrifugal fans. This combined range is considered the widest range available from a single manufacturer.

What is ATEX?

As from July 1, 2003 the new EU ATEX Directive requires most products to be used in potentially explosive environments to be ATEX compliant. The new directive covers a surprisingly large range of equipment including products used in petro-chemicalplants, chemicals, pharmaceuticals, battery rooms, flourmills, grain silos and other areas where a potentially explosive atmospheremay be present.

Potential explosive hazards are very common and include gases, vapours, mists and dust. The specific mixture being handledcategorises the features each product must include.

Who does ATEX apply to?

End users have the ultimate responsibility to ensure ATEX compliance and Fläkt Woods can assist in this area. Our website www.atex-fans.com provides much of the information and forms required.

• Manufacturers • OEM’s • Specifiers • Distributors

Products installed after 1/7/03 may have to be replaced should they not comply with the ATEX directive. Users must act now to specify the correct product.

Fläkt Woods ATEX Compliant Fans

Fläkt Woods offers both Aerofoil axial fans and Centripal EU range of centrifugal fans that are all ATEX compliant. We have ensured that all the necessary systems are in place during production to continue ATEX compliance. Fläkt Woods have invested heavily in Engineering design and specification to comply with ATEX.

Fläkt Woods fans have been modified in a number of ways including changes to motors, materials, locking systems and conduit systems as well as adapting and revising product guides and operation manuals.

Acceptance throughout Europe

Having the ability to supply ATEX compliance and by CE marking our fans, Fläkt Woods are able to sell fan products anywhere in Europe without further requirements being applied. This also enables refurbishment of existing installations OEM customers can be confident in using Fläkt Woods products to gain the relevant certification of their products.

Fläkt Woods Certificate number ST M07 TEC 2885

For more information visit www.atex-fans.com

Page 26: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Aerofoil ATEX Section 4.3

Section

4 - A

erofoil - JM A

TEX

96

Performance Range covered by The JM ATEX range.

Regulation t-box fixings and cable connectionsas per standard requirements.

Page 27: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sec

tion

4 - A

erof

oil - JM

Bifur

cate

d

Page 28: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Bifurcated Aerofoil Section 4.4

Sizes

40JM.Bif - 400mm, 50JM.Bif - 500mm, 63JM.Bif - 630mm, 80JM.Bif - 800mm.800 and 1000mm JM.Bif available please contact Fläkt Woods for details.Also larger sizes are available, please enquire.

Fan Performance

Coupled with the above fan diameters the fully adjustable pitch Aerofoil impeller gives the exact performance required with a non overloading fan characteristic. Higher pressures are obtained by multi-staging the Bifurcated Aerofoil fan.

Impellers

A unique high efficiency aerofoil section blade with a purposely smoothed hub and clamp plate for adjustable pitch angle availability.

The Fläkt Woods impellers are all high pressure die cast to offer thin aerofoil sections for low generation of noise.Every component is X-rayed using Real Time Radiography inspection prior to assembly. The maximum pitchangles shown allow for speed control by frequency inverter.

Motors

All motors are totally enclosed fan cooled class F insulation with protection to IP55. All motors are supplied with sealed for life bearings or extended lubricators.

These motors are suitable for inverter speed control down to 20% of full speed.

Electrical Supply

380 - 420 V / 50 Hz / 3 φ

Temperature Range

Up to 200˚C continuous operation.

Casings

Bifurcated fans are available long case only. Long casing covers impeller and motor and has duct mounted terminal box. The hot dipped galvanised casing gives a high resistance to corrosion.

Accessories

Silencers, Mounting feet, Vibration isolators, Matching flanges, Flexible connectors, Guards, Bell mouth inlets.

• 400mm - 800mm diameter• Volume flow up to 7 m3/s • Static pressures up to 650 Pa• Suitable for temperatures up to 200°C• Motor protection IP55• Overheat protection fitted as standard

• All aluminium cast components are x-ray examined

• All casings are hot dipped galvanised• Multi-stage is available for higher pressures• All casings are hot dipped galvanised• Inverter speed controllable

98

Section

4 - A

erofoil - JM B

ifurcated

Page 29: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Bifurcated Aerofoil Section 4.4

Sec

tion

4 - A

erof

oil - JM

Bifur

cate

d

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

99

Electrical Data

80°C

Performance Data

380-420V/50Hz/3φProduct Speed Motor Product Pitch Motor Full Load Starting Wiring Speed

Code Number Angle Rating Current Current Diagram Controller Sound

rev/min (at 400V) (at 400V) Ref Inverter Level

(˚) (kW) (A) (A) dBA

40JM.Bif/16/4/5/… 1440 D71C DB245001 8-38 0.25 0.79 3.5 1344 N/A 57

40JM.Bif/20/2/6/… 2910 F2225 DB245003 8-32 2 4.5 30 1343 FWD2 74

50JM.Bif/16/4/5/… 1440 D80C DB275001 8-38 0.75 2.0 9.9 1344 FWD1 63

50JM.Bif/20/2/6/… 2910 F2229 DB275005 8-30 5.5 11.1 90 1343 FWD5 80

63JM.Bif/20/4/6/… 1440 F2245 DB305001 8-32 2.2 5.0 30 1344 FWD2 71

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Wiring diagram references can be found in section 9.2.

200°C380-420V/50Hz/3φ

Product Speed Motor Product Pitch Motor Full Load Starting Wiring Speed

Code Number Angle Rating Current Current Diagram Controller Sound

rev/min (at 400V) (at 400V) Ref Inverter Level

(˚) (kW) (A) (A) dBA

40JM.Bif/20/4/6/40 1440 F22c JN245005 8-40 0.5 1.49 9.5 1343 FWD1 58

40JM.Bif/20/2/6/32 2950 F22c JN245004 8-32 2.0 4.25 32 1343 FWD2 74

50JM.Bif/20/4/6/32 1440 F22c JN275007 8-32 0.75 3.0 16.4 1343 FWD1 63

50JM.Bif/20/2/6/24 2950 F22c JN275004 8-24 4.0 8.04 68 1343 FWD4 79

63JM.Bif/20/4/6/30 1440 F22c JN305002 8-30 2.0 4.4 2.7 1344 FWD2 70

Page 30: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Bifurcated Aerofoil Section 4.4

Section

4 - A

erofoil - JM B

ifurcated

100

Dimensions

40JM.Bif-50JM.Bif

All dimensions shown in mm

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Product Motor A B C D E F G H J K L M N P Q S T Weight

Code Range (kg)

40JM.Bif/20/4/6/40 F2225 400 524 727 367 3 375 332 450 27 641 350 400 10 250 3 8 12 72

50JM.Bif/20/4/6/32 F2225 500 610 787 408 3 375 371 560 27 691 450 500 10 315 3 12 12 83

50JM.Bif/20/4/6/32 F2229 500 610 787 408 3 430 371 560 27 691 450 500 10 315 3 12 12 93

63JM.Bif/20/4/6/30 F2245 630 724 616 436 3 400 400 690 27 530 580 630 14 400 3 12 12 112

80JM.BIF/20/4/6/20 F2249 800 894 660 520 3 468 484 860 27 544 750 800 10 510 5 16 12 155

63JM.Bif - 80JM.Bif

Page 31: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sec

tion

4 - A

erof

oil - B

ifur

cate

d Ser

ies

33

Page 32: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

102

JM Bifurcated Series 33 Fan Section 4.5

Section

4 - A

erofoil - Bifurcated S

eries 33

Sizes

15JM.Bif -152mm, 25JM.Bif - 254mm, 30JM.Bif - 305mm.

Fan Performance

Ideally suited for exhausting or recirculating fumes, gases and hot air up to temperatures of 200°C.Motor must have access to ambient air. All fans have non overloading characteristics.

Impellers

Cast in aluminium silicon alloy and has a fixed pitch aerofoil section blade. This ensures strength, reliability and performance at high temperature.

Motors

All motors are totally enclosed fan cooled, class F insulation with motor protection to IP55. All motors are supplied with sealed for life bearings.

Electrical Supply

220 - 240 V / 50 Hz / 1 φ380 - 420 V / 50 Hz / 3 φ

Temperature Range

Up to 200°CFor higher temperatures please enquire.

Casings

All casings are hot dip galvanised for long life and a high resistance to corrosion. A seal is provided on the motor shaft.

Accessories

Silencers, Mounting feet/plates, Vibration isolators, Matching flanges, High temperature flexible connectors.

• 152mm - 305mm diameter• Volume flow up to 0.89 m3/s • Static pressures up to 380 Pa

• Suitable for temperatures up to 200°C• Motor protection IP55• Series 33 is cost effective solution to

Bifurcated applications

Page 33: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

103

JM Bifurcated Series 33 Fan Section 4.5

Sec

tion

4 - A

erof

oil - B

ifur

cate

d Ser

ies

33

Electrical Details

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, based on form B running under free field conditions, and are presented for comparative purposes only. Cylindrical silencers are available as standard. Bifurcated fans are not suitable for speed regulation.

Wiring diagram references can be found in section 9.2.

Performance Data

Product Speed m3/s at Pa (Static)

Code rev/min 0 25 50 75 100 150 200 250 375

25JM.33 1400 0.29 0.25 0.19

25JM.33 2900 0.57 0.54 0.52 0.51 0.49 0.46 0.38

30JM.33 1400 0.49 0.44 0.38 0.31

30JM.33 2900 0.98 0.96 0.93 0.91 0.88 0.83 0.77 0.70 0.44

380-420V/50Hz/3φProduct Speed Motor Product Motor Full Load Starting Wiring Speed

Code Number Rating Current Current Diagram Controller Sound

rev/min (at 400V) (at 400V) Ref Inverter Level

(kW) (A) (A) dBA

25JM.Bif.33 1400 D63C DB215608 0.18 0.57 2.28 CD1344 FWD1 40

25JM.Bif.33 2900 D71C DB215609 0.37 0.9 4.95 CD1344 FWD1 55

30JM.Bif.33 1400 D63C DB025608 0.18 0.57 2.28 CD1344 FWD1 46

30JM.Bif.33 2900 D71C DB025609 0.37 0.9 4.95 CD1344 FWD1 63

Page 34: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Bifurcated Series 33 Fan Section 4.5

Section

4 - A

erofoil - Bifurcated S

eries 33

104

.All dimensions shown in mm

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Product Motor A B C D E H J L M S T Weight

Code Range (kg)

15JM.33 D63 152 208 610 257 1.6 184 CM20 - - 4 8 15

25JM.33 D63 254 324 489 400 2 299 CM20 222 254 8 10 21

25JM.33 D71 254 324 489 400 2 299 CM20 222 254 8 10 24

30JM.33 D63 305 375 584 470 2 349 CM20 273 305 8 10 26

30JM.33 D71 305 375 584 470 2 349 CM20 273 305 8 10 28

Dimensions

Page 35: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Aerofoil - 2 Speed Section 4.6

Sec

tion

4 - A

erof

oil - JM

Aer

ofoi

l 2 S

peed

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

105

2 speed fans offer energy saving characteristics. Fläkt Woods offer a range of 2 speed JM Aerofoil fans on Standard delivery to suit most requirements

Performance Data

Performance is shown at highest speed.

Electrical Data - Pole Change Type

Product Speed m3/s at Pa (Static)

Code rev/min 0 50 100 150 200 250 300 400

31JM/16/2-4/5/38 1420/700 1.3 1.25 1.2 1.15 1.0 0.98 0.86

40JM/16/4-8/5/38 1420/700 1.46 1.28 1.02

40JM/16/2-4/5/26 2910/1440 2.24 2.18 2.12 2.07 1.98 1.92 1.82 1.66

50JM/16/4-8/5/40 1420/700 3.02 2.69 2.44 2.05

50JM/20/2-4/6/30 2900/1400 5.1 5.0 4.95 4.85 4.75 4.6 4.45 4.3

56JM/20/4-8/6/40 1420/720 4.3 4.1 3.8 3.5 3.07

56JM/20/2-4/6/20 2910/1400 5.6 5.4 5.3 5.2 5.1 5.0 4.9 4.7

63JM/20/4-8/6/28 1420/720 4.6 4.4 4.2 3.85 3.6 3.25

63JM/20/4-8/6/36 1440/700 5.9 5.64 5.26 4.96 4.60 4.20

63JM/25/2-4/9/22 2910/1470 7.2 7.1 7.0 6.9 6.8 6.7 6.6 6.4

71JM/20/4-8/6/26 1440/700 6.85 6.5 6.3 6.1 5.85 5.7 5.4

80JM/25/4-8/9/28 1440/730 10.1 9.80 9.50 9.25 9.0 8.6 8.2 7.2

90JM/25/4-8/9/32 1470/730 16.3 15.9 15.5 15.1 14.8 14.4 13.9 13.0

100JM/25/6-12/9/26 960/480 13.0 12.2 11.5 10.6 9.9 9.0

100JM/25/4-8/9/22 1470/730 17.5 17.2 16.9 16.2 16.0 15.5 15.0 13.6

380-420V/50Hz/3φProduct Speed Motor Product Pitch Motor Full Load Starting Wiring

Code Number Angle Rating Current Current Diagram Sound EDC22

rev/min (at 400V) (at 400V) Ref Level 2 Speed/

(˚) (kW) (A) (A) dBA DOL Starter

40JM/16/4-8/5/38 1420/700 CT5 EL431480 8-38 0.5/0.06 1.28/0.5 3.7/1.0 CD1466 50 418141

40JM/16/2-4/5/26 2910/1440 CT9 EL431280 8-26 1.4/0.17 3.1/1.1 16.5/5.0 CD1466 63 418142

50JM/16/4-8/5/40 1420/700 CT9 EL531480 8-40 0.9/0.12 2.5/1.0 9.0/2.5 CD1466 59 418142

50JM/20/2-4/6/30 2900/1400 PM112 EL531281 8-30 5.0/0.65 10.1/3.2 78/20 CD1466 73 418143

56JM/20/4-8/6/40 1420/720 F22 EL591480 8-40 1.8/0.24 4.3/1.5 20.0/5.0 CD1466 62 418144

56JM/20/2-4/6/20 2910/1400 PM112 EL591281 8-20 5.0/0.65 10.1/3.2 78/20 CD1466 73 418143

63JM/20/4-8/6/28 1420/720 F22 EL661481 8-28 1.8/0.24 4.3/1.5 20.0/5.0 CD1466 60 418144

63JM/20/4-8/6/36 1440/700 F22 EL661480 28-36 3.1/0.4 6.8/2.2 37/7.5 CD1466 62 418147

63JM/25/2-4/9/22 2910/1470 D160 EL661281 8-22 12/1.5 22.6/3.1 130/32 CD1466 74 418148

71JM/20/4-8/6/26 1440/700 F22 EL741480 8-26 3.1/0.4 6.8/2.2 37/7.5 CD1466 65 418147

80JM/25/4-8/9/28 1440/730 D132 EL831481 8-28 6.3/0.82 12.3/2.8 72/14 CD1466 72 418149

90JM/25/4-8/9/32 1470/730 D160 EL931481 8-32 13.4/1.68 24.7/5.34 154/27 CD1466 76 418150

100JM/25/6-12/9/26 960/480 D132 EL131681 8-26 4.7/0.56 10.4/2.3 52/8.5 CD1466 70 418154

100JM/25/4-8/9/22 1470/730 D160 EL131481 8-22 13.4/1.68 24.7/5.34 154/27 CD1466 80 418150

Sound pressure levels quoted are average dB(A) at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

Wiring diagram references can be found in section 9.2.

380-420V/50Hz/3φProduct Speed Motor Product Pitch Motor Full Load Starting Wiring

Code Number Angle Rating Current Current Diagram Sound EDC19

rev/min (at 400V) (at 400V) Ref Level 2 Speed/

(˚) (kW) (A) (A) dBA DOL Starter

31JM/16/2-4/5 2820/1460 71 EL341282 38 0.66/0.08 1.62/0.61 7.29/2.26 CD1371 62 Enquire

40JM/16/2-4/5 2885/1465 90L EL431283 26 1.3/0.17 2.91/0.8 18.6/4.05 CD1371 63 Enquire

50JM/20/2-4/6 2875/1445 112M EL531282 24 3.8/0.48 7.71/1.28 47.8/6.4 CD1371 72 Enquire

50JM/20/4-8/6 1460/710 90L EL531481 38 0.9/0.25 2.92/1.27 6.13/2.29 CD1371 59 Enquire

56JM/20/2-4/3 2875/1445 112M EL592201 22 3.8/0.48 7.71/1.28 47.8/6.4 CD1371 73 Enquire

63JM/20/4-8/6 1460/710 90L EL661401 16 0.9/0.25 2.92/1.27 6.13/2.29 CD1371 59 Enquire

Electrical Data - Dual Wound Type

Page 36: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM Aerofoil - 2 Speed Section 4.6

Section

4 - A

erofoil - JM A

erofoil 2 S

peed

106

Product Motor A B C D E F G H J K L M N P S T X Max. Fan

Code Range Weight (kg)

31JM D71 315 395 975 235 2.5 25 175 355 66 265 315 315 10 200 8 10 0.8 31

40JM CT 400 480 375 279 2.5 25 225 450 66 290 350 400 10 250 8 12 1.2 30

50JM CT 500 594 375 338 2.5 25 290 560 66 280 450 500 10 315 12 12 2.0 34

50JM F22 500 594 520 338 3 25 290 560 66 424 450 500 10 315 12 12 2.0 65

56JM F22 560 654 520 368 3 25 330 620 66 424 510 560 10 355 12 12 2.3 67

63JM F22 630 724 711 403 3 25 375 690 66 434 580 630 10 400 12 12 2.4 70

63JM D160 630 724 520 440 6 25 375 690 66 619 580 630 12 400 12 12 4.8 270

71JM F22 710 804 520 443 3 25 415 770 66 404 660 710 10 440 16 12 4.5 85

80JM D132 800 894 520 525 5 25 485 860 66 400 750 800 12 510 16 12 7.0 192

90JM D160 900 1006 711 575 5 25 491 970 66 629 850 900 12 518 16 15 5.3 270

100JM D132 1000 1106 520 625 5 25 547 1070 66 444 950 1000 12 574 16 15 6.2 227

100JM D160 1000 1106 711 625 6 25 547 1070 66 539 950 1000 12 574 16 15 6.2 286

Dimensions

All dimensions shown in mm

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Long Cased

Page 37: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sec

tion

4 - A

erof

oil - JM

Mul

ti-S

tage

Page 38: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

108

Aerofoil - JM Multi-Stage Section 4.7

Section

4 - A

erofoil - JM M

ulti-Stage

Sizes

31JM - 315mm, 35JM - 355mm, 40JM - 400mm, 45JM - 450mm, 50JM - 500mm, 56JM - 560mm, 63JM - 630mm, 80JM - 800mm.

Fan Performance

All fans are tested to the latest internationally recognised standard IS05801 1997, installation category D for aerodynamic performance and BS848 Part 2 (1985) for acoustic performance.

Coupled with the above fan diameters, the adjustable pitch Aerofoil impeller gives the exact performancerequired, with a non overloading fan characteristic.

Impellers

A unique high efficiency aerofoil section blade with a purposely smoothed hub and clamp plate for adjustablepitch angle availability.

The Fläkt Woods impellers are all high pressure die cast to offer thin aerofoil sections for low generation of noise.Every cast aluminium component is X-ray examined using Real Time Radiography prior to assembly.

The maximum pitch angles shown allow for speed control by frequency inverter.

Motors

All motors are totally enclosed air stream rated class F insulation. Constructed from aluminium as standard withspecial ‘T’ slot or pad mounted fixings. Single speed motors are suitable for speed control by frequency inverters.

Suitable for horizontal through to vertical shaft operation. Supplied IP55, with removable drain plugs.

Sealed for life bearings lubricated with wide temperature range grease.

Motors are fitted with thermostat overheat protection as standard.These motors are suitable for inverter speed control down to 20% of full speed.

Electrical Supply

380 - 420 V / 50 Hz / 3 φ

Temperature Range

-40°C to 50°C as standard. (All motors are not suitable for starting at temperatures lower than -20°C.) Fans that include BT or CT motors can be continuously operated at temperatures up to 70°C. When these fans are operating in excess of 50°C they should be run at full speed only. Other fans can be operated up to 70°C with appropriate deration of motors.

Most standard 3φ fans can be offered for a one off emergency operation at 200˚C for 2 hours.

Casings

JM Aerofoil fans are available long cased, complete with an externally mounted pre-wired electrical terminal box.

Casings are spun from sheet steel with integral pre-drilled and radiused inlet flanges. The galvanised finish gives a high resistance to corrosion and is ideal for external as well as internal use.

Accessories

Silencers, Mounting feet, Vibration isolators, Matching flanges, Flexible connectors, Air operated non return dampers, Guards, Bell mouth inlets.

• 315mm - 800mm diameter• Volume flow up to 9 m3/s • Static pressures up to 1500 Pa• High energy efficiency• All casings are hot dipped galvanised

• Low installed noise levels• Motor protection IP55• Overheat protection fitted as standard• Inverter controllable

Page 39: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil - JM Multi-Stage Section 4.7

Sec

tion

4 - A

erof

oil - JM

Mul

ti-S

tage

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

109

Performance DataProduct Speed m3/s at Pa (Static)

Code rev/min 0 100 200 300 400 500 800 1000 1200 1500

31JM2/16/4/5/40/32 1420 0.75 0.68 0.58

35JM2/16/4/5/40/32 1420 1.19 1.08 0.93 0.78

35JM2/16/2/5/24/20 2840 1.5 1.45 1.4 1.38 1.35 1.3 1.15 1.0 0.85

40JM2/16/2/5/27/22 2840 2.45 2.4 2.3 2.25 2.2 2.15 1.9 1.75 1.6

45JM2/16/4/5/40/32 1420 2.6 2.45 2.18 1.95 1.55

45JM2/20/2/6/29/24 2910 3.7 3.64 3.61 3.59 3.58 3.50 3.25 3.11 2.95 2.80

50JM2/20/4/6/41/32 1420 3.6 3.45 3.30 3.10 2.8 2.50

50JM2/20/2/6/20/16 2910 4 3.9 3.8 3.7 3.65 3.6 3.45 3.3 3.15 3

50JM2/20/2/6/30/24 2910 5.6 5.5 5.4 5.3 5.2 5.2 4.9 4.8 4.55 4.3

56JM2/20/4/6/30/24 1420 3.8 3.7 3.4 3.2 2.95 2.7

56JM2/20/4/6/36/28 1420 4.4 4.2 4.0 3.75 3.55 3.2

63JM2/20/4/6/35/28 1420 6.5 6.3 6.1 5.8 5.5 5.2

63JM2/25/4/9/40/32 1440 7.2 7.0 6.8 6.6 6.43 6.3 5.5 4.85

80JM2/25/4/9/20/16 1440 8.4 8.2 8.0 7.7 7.5 7.2 6.6 5.8 4.6

Sound pressure levels quoted are average dBA at 3 m distance over a sphere, under free field conditions and are presented for comparative purposes only.

† Speed controllers sized one per two stage fan.

Fans that include BT or CT motors can be continuously operated at temperatures up to 70°C.

When these fans are operating in excess of 50°C they should be run at full speed only. Product numbers shown are for Long cased fans.

For Short cased fans please omit the prefix from the product number and state S-type on enquiries/orders.

Wiring diagram references can be found in section 9.2.

Electrical Data380-420V/50Hz/3φ

Product Speed Motor Product Motor Full Load Starting Wiring †Speed

Code Number Rating Current Current Diagram Controller Sound

rev/min (at 400V) (at 400V) Ref Inverter Level

(kW) (A) (A) dBA

31JM2/16/4/5/40/32 1420 BT4 EQ341451 0.13 0.5 1.8 CD1344 FWD1 57

35JM2/16/4/5/40/32 1420 BT5 EQ381402 0.13 0.5 1.8 ENQ FWD1 60

35JM2/16/2/5/24/20 2840 CT5 EQ381203 0.95 2 9.5 CD1344 FWD2 76

40JM2/16/2/5/27/22 2840 CT9 EQ431203 1.7 3.5 20 CD1344 FWD4 80

45JM2/16/4/5/40/32 1420 CT5 EQ481453 0.58 1.7 6.5 CD1343 FWD2 67

45JM2/20/2/6/29/24 2840 F22 EQ481205 3.8 7.2 64 CD1343 FWD6 84

50JM2/20/4/6/41/32 1420 CT9 EQ531408 1.4 3.5 14 CD1343 FWD3 73

50JM2/20/2/6/20/16 2840 F22 EQ531203 3.8 7.2 64 CD1343 FWD6 84

50JM2/20/2/6/30/24 2840 PM112 EQ531204 6.2 11.6 100 CD1343 FWD8 88

56JM2/20/4/6/30/24 1420 CT9 EQ591458 1.15 3 14 CD1343 FWD3 73

56JM2/20/4/6/36/28 1420 CT9 EQ591408 1.4 3.5 14 CD1343 FWD3 75

63JM2/20/4/6/20/16 1440 F22 EQ661407 2.7 5.8 30 CD1343 FWD5 78

63JM2/25/4/9/40/32 1440 PM112 EQ661405 4.4 9.3 55 CD1343 FWD7 80

80JM2/25/4/9/20/16 1440 PM112 EQ831404 4.4 9.3 55 CD1343 FWD7 82

Page 40: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Aerofoil - JM Multi-Stage Section 4.7

Section

4 - A

erofoil - JM M

ulti-Stage

110

All dimensions shown in mm

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Dimensions

Long Cased

Product Motor A B C D E F G H J K L M N P S T W X Weight

Code (kg) (kg)

31JM2/16/4/5/40/32 BT4 315 395 750 235 2.5 25 175 355 66 290 265 315 10 200 8 10 375 0.8 44

35JM2/16/4/5/40/32 BT5 355 435 750 256 2.5 25 200 395 66 290 305 355 10 225 8 10 375 1.1 48

35JM2/16/2/5/24/20 CT5 355 435 750 266 2.5 25 200 395 66 290 305 355 10 225 8 10 375 1.1 56

40JM2/16/2/5/27/22 CT9 400 480 750 279 2.5 25 225 450 66 290 350 400 10 250 8 12 375 1.2 60

45JM2/16/4/5/40/32 CT5 450 530 750 306 2.5 25 255 500 66 290 400 450 10 280 8 12 375 1.5 64

45JM2/20/2/6/29/24 F22 450 530 1040 306 3 25 255 500 66 434 400 450 10 280 8 12 520 1.5 88

50JM2/20/4/6/41/32 CT9 500 564 750 338 2.5 25 290 560 66 280 450 500 10 315 12 12 375 2.0 68

50JM2/20/2/6/20/16 F22 500 594 1040 338 3 25 290 560 66 424 450 500 10 315 12 12 520 2.0 108

50JM2/20/2/6/30/24 PM112 500 594 1040 338 3 25 290 560 66 424 450 500 10 315 12 12 520 2.0 130

56JM2/20/4/6/30/24 CT9 560 654 750 368 2.5 25 330 620 66 280 510 560 10 355 12 12 375 2.3 76

56JM2/20/4/6/36/28 CT9 560 654 750 368 2.5 25 330 620 66 280 510 560 10 355 12 12 375 2.3 76

63JM2/20/4/6/20/16 F22 630 724 1040 403 3 25 375 690 66 434 580 630 10 400 12 12 520 2.4 140

63JM2/25/4/9/40/32 PM112 630 724 1040 403 3 25 375 690 66 434 580 630 10 400 12 12 520 2.4 162

80JM2/25/4/9/20/16 PM112 800 894 1040 488 3 25 485 860 66 434 750 800 10 510 16 12 520 5.8 188

Page 41: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM - Accessories Section 4.8

Sec

tion

4 - J

M- A

cces

sori

es

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

111

JM Damper

JM Mounting Feet

JM – Matching Flanges and Flexible Connector

Note: Flexible Connection weight includes two Matching Flanges.Suitable for up to 600˚C emergency operation for 2 hours and 200˚C continuous.

Product Product Frame G L M N P T V WCode Number Size

315 DA408199 BT/CT.F22 175 265 315 10 200 10 20 60

355 DA408200 BT/CT.F22 200 305 355 10 225 10 20 60

400 DA408201 BT/CT.F22 225 350 400 10 250 12 20 60

450 DA408202 BT/CT,F22 255 400 450 10 280 12 20 60

500 DA408203 BT/CT,F22 290 450 500 10 315 12 25 65

560 DA408204 BT/CT,F22 330 510 560 10 355 12 25 65

630 DA243495 BT/CT,F22 375 580 630 10 400 14 25 65

710 DA245874 BT/CT,F22 415 660 710 10 440 14 25 80

800 245024 BT/CT,F22 485 750 800 12 510 14 25 80

800 249468 D132 485 750 800 1 510 14 25 80

900 249467 F22 491 850 900 12 518 14 25 60

900 249258 D132 491 850 900 12 518 14 25 60

1000 249464 F22 547 950 1000 10 574 15 25 60

1000 249255 D132 547 50 1000 12 574 15 25 60

Suitable Product Numbers Weight (kg)

for fan Matching Flexible C Matching Flexible

OA Flange Connector Flange Connection

315 DA408238 DA414865 110 1.1 3.3

355 DA501351 DA414866 110 1.3 3.9

400 DA074913 DA414867 110 1.5 4.5

450 DA501353 DA414868 110 1.7 5.0

500 DA074914 DA414869 110 2.0 5.5

560 DA501355 DA414901 110 2.3 6.8

630 DA074915 DA414844 160 3.0 7.5

710 DA074916 DA414845 160 3.2 8.1

800 74917 414846 160 3.6 9.1

900 404841 414847 160 4.1 10.4

1000 74918 414848 160 4.6 11.6

Note: Suitable for up to 400˚C emergency operation and 200˚C continuous.

Suitable for Product Weightfan OA Number C D kg

315 414942 225 – 8

355 414943 225 – 9

400 414944 225 17 10

450 414945 225 39 12

500 414473 225 75 16

560 414474 225 125 18

630 414475 225 176 20

710 414476 225 210 23

800 414477 225 270 27

900 414478 225 305 31

1000 414479 225 345 36

Page 42: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

112

JM - Accessories Section 4.8

Section

4 - JM

- Accessories

Acoustic Performance B Type (without Pod)

Acoustic Performance C Type (with Pod)

Silencer

The above silencers give the following approximate dBA reductions:B Type 1 diameter length – 7 to 10 dBA C Type 1 diameter length – 12 to 15 dBAFor full acoustic details and resistance to airflow for type C see publication SPO1

Acoustic Performance (dB) – Octave Band Mid Frequency – HzBore Dia. Length

63 125 250 500 1K 2K 4K 8Kmm (D)

315 1D 1 2 4 9 11 10 9 7

355 1D 1 2 4 10 12 10 9 7

400 1D 2 3 5 10 13 11 9 8

450 1D 2 3 6 12 13 11 10 6

500 1D 2 3 6 13 14 10 10 5

560 1D 2 4 7 14 14 19 10 7

630 1D 2 5 7 15 13 8 9 8

710 1D 3 5 7 15 13 9 9 8

800 1D 3 5 8 16 12 9 9 8

900 1D 3 5 10 17 13 11 10 8

1000 1D 4 5 11 16 11 10 8 9

Acoustic Performance (dB) – Octave Band Mid Frequency – HzBore Dia. Length

63 125 250 500 1K 2K 4K 8Kmm (D)

315 1D 2 5 5 9 18 20 18 15

355 1D 2 5 6 9 18 22 19 16

400 1D 2 6 6 10 19 24 20 17

450 1D 2 4 7 13 20 23 22 17

500 1D 2 3 8 16 21 22 21 17

560 1D 3 5 8 16 20 18 19 15

630 1D 3 5 8 15 19 16 14 12

710 1D 3 5 8 15 19 15 14 12

800 1D 4 5 8 16 19 15 14 13

900 1D 4 5 9 17 19 15 14 13

1000 1D 5 5 11 18 19 15 14 13

Suitable Product Numbers Weight (kg)

for fan B Type C Type

OA (Pod Kit) B C J B Type C Type

315 DS211401 DA415792 415 315 M8 ID 13

355 DS221401 DA415793 455 355 M8 12 15

400 DS241401 DA415794 500 400 M10 15 18

450 DS251401 DA415795 600 450 M10 20 24

500 DS271401 DA415796 650 500 M10 25 29

560 DS281401 DA415797 710 560 M10 30 35

630 DS301401 DA415798 780 630 M10 35 42

710 DS311401 DA415799 860 710 M10 44 53

800 331401 416212 1000 800 M10 55 66

900 341401 416213 1100 900 M12 70 84

1000 351401 416214 1200 1000 M12 82 100

JM – Cylindrical Silencers

Page 43: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

JM - Accessories Section 4.8

Sec

tion

4 - J

M- A

cces

sori

es

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

113

JM Bell Mouth Inlet – Fan with flanged inlet only

All dimensions shown in mm

Suitable Product Numbers C D Weight (kg)for fan φA

315 408593 65 379 1.0

355 248950 85 423 1.2

400 74880 80 480 1.5

450 248952 95 536 2.0

500 74881 87 600 3.2

560 248953 100 668 4.0

630 74882 108 757 4.8

710 74883 126 857 5.4

800 74884 134 957 6.8

900 404842 150 1077 8.0

1000 74885 167 1199 17.8

Guard – JM Aerofoil

Type I & TypeII

Impeller Side L & S Type

Motor Side S Type

(BT, CT & F22)

Type II guards have a Ø220 hole cut out of centre.

Type III

Motor Side S Type

(D132 & D160)

Type IV

Bellmouth & L Type

Motor Side

Suitable Type C Weightfor fan φA

315 I 137 1.2

315 IV 30 0.5

355 I 137 1.4

355 IV 30 0.5

400 I 137 1.6

400 IV 30 0.6

450 I 137 1.8

450 II 137 1.6

450 IV 30 0.6

500 I 137 2.0

500 II 137 1.8

500 IV 30 0.7

560 I 137 2.2

560 II 137 2.0

560 IV 50 1.0

630 I 137 2.8

630 II 137 2.6

630 III 350 3.0

630 IV 50 1.2

710 I 137 3.2

710 II 137 3.0

710 III 350 3.4

710 IV 50 1.4

800 I 137 3.5

800 II 137 3.3

800 III 350 3.9

800 IV 50 1.5

900 I 137 4.2

900 II 137 4.2

900 III 310 4.8

900 IV 50 1.7

1000 I 137 5.0

1000 II 137 4.8

1000 III 310 5.6

1000 IV 50 2.0

Page 44: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Section

4 - JM

- Accessories

Page 45: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sec

tion

4 - J

M- Por

tabl

e C

oole

r

Page 46: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

116

Aerofoil - JM Portable Cooler Section 4.9

Section

4 - JM

- Portable C

ooler

Sizes

40JM.PC – 400mm, 50JM.PC – 500mm

Fan Performance

The fan uses the JM aerofoil impeller set at maximum pitch for the motor to give maximum cooling velocity.

Impellers

A true aerofoil section high pressure die cast aluminium assembly. All cast aluminium components are X-rayinspected to ensure strength, reliability, performance and safety.

Motors

All motors are totally enclosed with class F insulation. Protection IP55. All motors are supplied with sealed for life bearings.

Electrical Supply

100 - 110 V / 50 Hz / 1 φ220 - 240 V / 50 Hz / 1 φ380 - 420 V / 50 Hz / 3 φ

Temperature Range

-40°C to 50°CFor higher temperatures please enquire.

(All motors are not suitable for starting at temperatures lower than -20°C.)

Casings

Casings are hot dip galvanised with built in conical inlet to ensure performance. The fan is mounted in a heavy duty purpose built tubular frame, a heavy duty isolator is also fitted. Fans are supplied complete with motor side and impeller side safety guards.

• 400mm – 500mm diameter• Air throw, up to 25 m @ 1.25 m/s velocity • Purpose built cradle• Adjustable discharge angle• Aluminium JM aerofoil impeller

• 100% X-ray of impeller• Heavy duty isolator• Motor protection IP55• Motor side and impeller side guards• Casing hot dip galvanised

Page 47: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Sec

tion

4 - J

M- Por

tabl

e C

oole

r

Express Range - These products are available from our UK Express Distributor on same daydelivery from the date of order.

Standard Service - Please consult your local distributor for availability maximum 15 days.

117

Aerofoil - JM Portable Cooler Section 4.9

Performance Data

The performance shown describes the velocity of the air at the distance from the fan.

Sound pressure levels quoted are average dBA at 10m distance over a sphere, under free field conditions and are presented for comparative purposes only.

For details on speed control please enquire.

Electrical Data

100-110V/50Hz/1φ

Product Speed Motor Product Motor Full Load Starting Wiring

Code (rev/min) Number Rating Current Current Diagram

(kW) (at 105V) (at 105V) Ref

(A) (A)

PC40JM 1350 BT9 DPO40028 0.22 4 6 CD1731

380-420V/50Hz/3φ

Product Speed Motor Product Motor Full Load Starting Wiring Sound

Code (rev/min) Number Rating Current Current Diagram Level

(kW) (at 400V) (at 400V) d.o.l. Ref dBA

A) (A)

PC50JM 2910 F22 JP050001 3.8 7.21 64 CD1739 73

Page 48: Axial Flow Fans - Air Movement and Control Association Cat ID JM.pdf · Section 4 Axial Fans - Section 4 Fläkt Woods offers a wide range of axial flow fans for general air movement

Section

4 - JM

- Portable C

ooler

118

Aerofoil - JM Portable Cooler Section 4.9

Dimensions

All dimensions shown in mm

For a full range of accessories including silencers, speed controllers and mountings, please refer to section 4.8 or 9.1 (which shows all accessories)

Wiring diagram references can be found in section 9.2.

Code Motor A B C Weight (kg)

40JM.PC BT9 557 591 649 32

50JM.PC F2225 690 706 890 64


Recommended