CEP7-EELECTRONIC MOTOR PROTECTION RELAYS
Sales 1300 NHP NHP | nhp.com.au
MOTOR PROTECTION WITH LEADING EDGE TECHNOLOGY, EXPANDABLE PROTECTION AND COMMUNICATION.
MOTOR CONTROL
CEP 7-EDN DeviceNetTM communication module - available for fully adjustable jam / stall protection and thermal warning to indicate imminent overload trip
CEP 7-EPRB Profibus® communication module includes warning for jam trip, overload and underload. Includes device trip and warn status
CEP 7-ETN Ethernet / IP communication module with built-in webserver support for configuration and monitoring
CEP 7-DNCT - hand held programming terminal includes one metre cable to be used with CEP 7-EDN (DeviceNetTM module)
Side mount modules also deliver entry level communication with DeviceNetTM, Profibus® and Ethernet / IP:
FOR FURTHER INFORMATION vIsIT: nhp.com.au/s+s
CEP 7-ERRREMOTE REsET MODULE
CEP 7-EGJGROUND FAULT / JAM PROTECTION AND REMOTE REsET MODULE
CEP 7-EPTPTC THERMIsTOR RELAY AND REMOTE REsET MODULE
CEP 7-EGFGROUND FAULT PROTECTION AND REMOTE REsET MODULE
CEP 7-EJMJAM PROTECTION AND REMOTE REsET MODULE
The new CEP 7 overloads now boast a formidable range of smart add-on modules:
Introduction to CEP 7 electronic overload relays ..........................................................................[3, 4]
CEP 7-ED1 standard electronic overload relays .....................................................................................[5]
Overview of CEP 7-EE features ...........................................................................................................................[6]
CEP 7-EE enhanced electronic overload relays .....................................................................................[7]
CEP 7-E_P pass through electronic overload relays ............................................................................[8]
CEP 7 side mount modules ...................................................................................................................................[9]
CEP 7-CBCT core balance transformers and communication modules ...........................[10]
Accessories ..........................................................................................................................................................[11, 12]
CEP 7 quick reference guide ....................................................................................................................[13, 14]
Dimensions ..........................................................................................................................................................[15, 16]
CEP 7 module technical information ............................................................................................... [17 - 19]
CEP 7-ETN Ethernet Network Communication Module ................................................................[20]
CEP 7-CBCT core balance transformers (technical information) ....................................[21-24]
Trip curves ......................................................................................................................................................................[25]
Technical information ...................................................................................................................................[25, 26]
Contents
• New contactor and overload selection tool
• Calculates full load current of 3-phase motors based on. •kW •Voltage(415,690and1000VAC)
• selection made easy by providing part numbers and product photo.
AVAILABLE FROM THE ITUNES APP STORE NOW!
CONTACTOR SELECT IPHONE APP
2
Electronic overload relays
CEP 7 comprehensive motor protectionSprecher + Schuh have introduced their new CEP 7, second generation electronic overload protection relays. The new CEP 7 overloads incorporate a greater use of sophisticated electronic control and monitoring. With recent advances in micro electronic technology and the introduction of the ASIC chip set, it has become possible to improve on and add new features to the popular CEP 7 range. The CEP 7 second generation overload now incorporates greater accuracy and versatility whilst providing increased overall protection.
The new CEP 7 incorporates the following improved features:
• Awidersettablecurrentrange(5:1)
• Adjustableclasstripsettings(10,15,20and30)(EEversion)
• Fieldinstallablesidemountmodules(EEversion)
• Anextremelylowpowerconsumptionof150mW
• Robustmountingtocontactor.
Range overview
CEP 7-ED1 basic model
The CEP 7-ED1 is the standard or base model version. The ED1 model is available in the currentrangeof0.1-45A,incorporatesafixedtripclassof10,andissuitedto3phaseoperation. A manual reset function, visible trip indicator and test / reset button are also included.
CEP 7-EE enhanced model
TheenhancedCEP7-EEvariantcoversanoperatingrangeof0.1-800Awithadjustabletripclasssettingsof10,15,20and30(viadipswitchselection).TheEEmodelcanbefurther enhanced by the addition of side mounted plug-in modules.
CEP 7-E_P pass through model
Forcurrentranges1-27Aaversionisavailablethatmountsseparatefromthecontactor.The motor wires pass through CT openings.
Superior phase failure protectionOnboard electronics constantly monitors all motor phases. If the ASIC chip set senses that one or more of the phases is missing during a steady state operation of a fully loaded motor, it will trip in 3 seconds. If a single phase condition is present during starting,theCEP7willtripwithin8seconds(foramotorloadingof>80%).Thesetriptimesaresignificantlyfasterthenconventionalbimetaloverloads.Inaddition,theCEP7relaydetectsa50%phaseimbalanceinthesamewayasaphaseloss.
Rated up to 1000 VACComplies to IEC-60997 for nominal operation voltage of 1000 volts.
27A
45A
90 A
27A
800 A
Dip switch settings (EE version)
ROBUsT MO
U
NT I N G TO CO
NTA
CTOR •
Electronic overload relays for 3 phase motor applications to IEC 60947
CEP 7 ED/EE/E_P x x
PRoDuCT TyPE MoDEL
CuRRENT RANGE oF SINGLE PHASE MoToRS
CuRRENT RANGE oF THREE PHASE MoToRS
CoDE To SuIT CA 7 / CA 6 CoNTACToRS
CEP 7 = 3 phase ED1 = Basic model 3) P =1.0...5.0amps RatedVoltage:690VAC B=CA7-9...23
CEP 7S = 1 phase EE = Enhanced model R=3.2...16amps A=0.1...0.5amps D = CA 7 - 30...43
EE_P = Enhanced pass through 2)
S=5.4...27amps B=0.2...1.0amps E = CA 6 - 60...97
T=9.0...45amps C=1.0...5.0amps F=CA6-115...180
U = 18...90 amps D=3.2...16amps G=CA6-210...420
E=5.4...27amps H = CA 6 - 630...860 4)
F=9.0...45amps
G = 18...90 amps
V = 60...120 amps
RatedVoltage:1000VAC
H=30...150amps
J=40...200amps
K = 60...300 amps
L=100...500amps
M=120...600amps
N = 160...800 amps
Modular in design, clever in application The new CEP 7-EE overloads now offer a formidable range of smart add on modules. Thesesmallsidemountedplug-inmodulesextendtheCEP7capabilitytosomethingmore potent in terms of motor protection. Communication modules are also available.
CEP 7-EPRB Profibus® communication module
CEP 7-EDN DeviceNetTM communication module
CEP 7-ETN EtherNet / IP communication module
CEP 7-ERR Remoteresetmodule
CEP 7-EJM Jam protection and remote reset module
CEP 7-EPT PTC thermistor relay and remote reset module
CEP 7-EGF Ground fault protection and remote reset module
CEP 7-EGJ Groundfault/jamprotectionandremoteresetmodule
CEP 7-ERID Remoteindicationmodule(workswithanysidemodule1)
CEP 7-EE + EDN DeviceNetTM
CEP 7-EE + EPRB Profibus®
NoTE: 1) Not compatible with communication modules
2) Only available in 3 Phase. Current range options available are C, D and E only. Ratedto1000VACwith1000Vratedinsulationcables
3) Only available in 3Phase.CurrentrangeoptionsavailableareA,B,C,D,EandFonly. 4) Ratedupto690VAC3 4
CEP 7-ED1 standard electronic overload relays
Electronic overload relays for 3 phase motors to IEC 60947
Manual reset, trip class 10 - standard 0.1…45 amps• 5:1currentadjustmentrange
• Lowpowerconsumption(150mW)
• Selfpowered
• Visibletripindicator
• 1N/Ctripcontactand1N/Oalarmcontact
• DirectmountingtoCA7contactorsuptoCA7-97.
APPRox kw RANGE
CuRRENT SETTING RANGE (A) To SuIT CoNTACToR CAT No.
0.02…0.12 0.1…0.5 CA7-9/12/16/23 CEP 7-ED1AB
0.06…0.25 0.2…1.0 CA7-9/12/16/23 CEP 7-ED1BB
0.25…2.2 1.0…5.0 CA7-9/12/16/23 CEP 7-ED1CB
1.5…7.5 3.2…16 CA7-9/12/16/23 CEP 7-ED1DB
2.2…15 5.4…27 CA7-9/12/16/23 CEP 7-ED1EB
4…22 9.0…45 CA 7 - 30/37/43 CEP 7-ED1FD
Electronic overloads for single phase applications to IEC 60947
same features as above, plus: • Optionaljam/stallandgroundfaultprotectionmodule
• Selectableauto/manualreset.
APPRox kw RANGE
CuRRENT SETTING RANGE (A) To SuIT CoNTACToR CAT No.
- 1.0…5.0 CA7-9/12/16/23 CEP 7S-EEPB
- 3.2…16 CA7-9/12/16/23 CEP 7S-EERB
- 5.4…27 CA7-9/12/16/23 CEP 7S-EESB
- 9.0…45 CA 7 - 30/37/43 CEP 7S-EETD
- 18…90 CA7-60/72/85/97 CEP 7S-EEuE
wiring diagrams
MANuAL RESET CLASS 10
SINGLE PHASE
3 phase CEP 7-ED1/EE/E_P Single phase CEP 7S-EE/E_P
5 6
CEP 7-EPRB
CEP 7-EDN
CEP 7-ETN
overview of CEP 7-EE features
Communication options with add-on modulesAllCEP7-EEversionsfrom0.1-800Acanbefittedwithsideaccessories(1peroverload).Inthecaseoffieldbuscommunicationsidemodules,theyprovidethepossibilitytocontrolthecontactororcollectinputsoverthefieldbusnetwork.Further,itthenbecomes possible to monitor trips, warnings and motor operating parameters.
Profibus® - CEP 7-EPRB
• SupportsDP-V0andDP-V1
• Auto-bandupto12MB/s
DeviceNetTM - CEP 7-EDN
• CanalsobestandaloneprogrammedusingCEP7-DNCTprogrammer
EtherNet/IP - CEP 7-ETN
• Built-inwebserversupportforconfigurationandmonitoring
Allcommunicationmodulesaddthefollowingfeatures:
• Overloadwarning
• Jamtripandwarning
• Overloadwarning
• 2inputs
• 1output
• Diagnostics:
-%thermalutilised
-Averagecurrent%FLA
- Device status
- Trip and warn status
MouLDED PowER CoNNECToRS
TEST BuTToN
MECHANICAL TRIP TEST
TRIP STATuS INDICAToR
CoNTRoL TERMINALS
CoNTACToR CoNNECTING MECHANISM
RESET BuTToN
DIP SwITCHES
FLA SETTING DIAL
LoAD TERMINATIoNS
7 8
CEP 7-EE enhanced electronic overload relays 1)
Electronic overload relays for 3 phase motors to IEC 60947
Auto / manual reset, trip class 10, 15, 20 or 30 - enhanced 0.1 to 800 amps • 5:1currentadjustmentrange
• DirectmountingtoCA7andCA6contactors
• Selfpowered
• Lowpowerconsumption(150mW)
• 1N/Ctripcontactand1N/Oalarmcontact
• Visibletripindicator
• Selectablemanualreset
• Adjustabletripclass10,15,20and30
• OptionalDeviceNet™communicationmodule
• OptionalProfibus® communication module
• OptionalEtherNet/IPcommunicationmodule
• Optionaljam/stallandremoteresetmodule
• OptionalPTCthermistorrelayandremotereset
• Optionalgroundfaultprotectionandremotereset.
APPRox kw RANGE
CuRRENT SETTING RANGE (A) To SuIT CoNTACToR CAT No.
RatedOperationVoltage:690VoltsAC
0.02…0.12 0.1…0.5 CA7-9/12/16/23 CEP 7-EEAB
0.06…0.25 0.2…1.0 CA7-9/12/16/23 CEP 7-EEBB
0.25…2.2 1.0…5.0 CA7-9/12/16/23 CEP 7-EECB
1.5…7.5 3.2…16 CA7-9/12/16/23 CEP 7-EEDB
2.2…15 5.4…27 CA7-9/12/16/23 CEP 7-EEEB
2.2…15 5.4…27 CA 7 - 30/37/43 CEP 7-EEED
4…22 9.0…45 CA 7 - 30/37/43 CEP 7-EEFD
11…45 18…90 CA7-60/72/85/97 CEP 7-EEGE
25…55 60…120 CA7-60/72/85/97 CEP 7-EEVE
RatedOperationVoltage:1000VoltsAC
18.5…90 30…150 CA6-115/140/180 CEP 7-EEHF
22…1102) 40…200 CA6-115/140/180 CEP 7-EEJF
22…110 40…200 CA6-210/250/300/420 CEP 7-EEJG
37…180 60…300 CA6-210/250/300/420 CEP 7-EEKG
55…300 100…500 CA6-210/250/300/420 CEP 7-EELG
75…385 120…600 CA 6 - 630/860 CEP 7-EEMH
100…510 160…800 CA 6 - 630/860 CEP 7-EENH
CEP 7-EEAB
AuTo / MANuAL RESET CLASS 10, 15, 20 oR 30
CEP 7-EEGE
CEP 7-EEJF
CEP 7-EEJG
CEP 7-EEMH
NoTE: 1) EEversionscanbefittedwithsidemountaccessories-referpages9-10 NoTE: 1) With 1000V rated insulated cables.
CEP 7-E_P pass through electronic overload relays TheCEP7-E_Pversionsprovideadditionalapplicationflexibilityandaredesignedtobemounted separately from the contactor. The motor wires are simply passed through the CT openings in the device and straight to the contactor which reduces the number of connectionpoints.ThismakesthemidealinretrofitapplicationsandwhenusedwithcontactorsotherthanCA7orwherespaceisrestricted.ThePversioncanbefitteddirectlyonto DIN rail to speed up assembly. The EE_P version can also accept any of the side mount accessories including the communication modules; DevicenetTM,Profibus® or Ethernet / IP.
CEP 7-EE_P Enhanced model
CAT No.CuRRENT SETTING RANGE (A)
CoNTRoL TERMINAL wIRE VARIABLE
CoNTRoL TERMINAL ToRquE VARIABLE TRIP CLASS
RatedOperationVoltage:1000VoltsAC1)
CEP 7-EECP 1.0…5.0 0.5...4mm2 0.55Nm 10-30
CEP 7-EEDP 3.2…16 0.5...4mm2 0.55Nm 10-30
CEP 7-EEEP 5.4…27 0.5...4mm2 0.55Nm 10-30
The pass through version of the CEP 7 permits separate mount of the overload relay.
Motor load side cables simply pass through a window in the overload relay body. The internal current transformers monitor the current flow.
9 10
CEP 7 side mount modules 1)
ACCESSoRy DESCRIPTIoN To SuIT CAT No.
CEP7-ERR
Remote reset module• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID
CEP7(S)-EE CEP 7-EE_P
CEP7-ERR
CEP 7-EJM
Jam protection and remote reset module• Dipswitchadjustablejamprotection
-Jamsetpoints-150%,200%,300%,or400%FLA
-Tripdelay-0.5,1,2,or4sec.
• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID
CEP7(S)-EE CEP 7-EE_P
CEP7- EJM
CEP 7-EPT
PTC thermistor relay and remote reset module• PTCprotectionandLEDstatusindication
Typeofcontrolunit MarkA Number of sensors 6 Maximumcoldresistanceofsensorchain 1500Ω Tripresistance 3400Ω±150Ω Resetresistance 1600Ω±50Ω Shortcircuittripresistance 25Ω±10Ω Opencircuittripresistance >20,000Ω Maximumvoltageat1T1/1T2(Rptc=4kΩ) <7.5VDC Maximumvoltageat1T1/1T2(Rptc=open) <30VDC PTCresponsetime 500…800ms
• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID
CEP7(S)-EE CEP 7-EE_P
CEP 7-EPT
CEP7-EGF
Ground fault protection and remote reset module 2) 3)
• Dipswitchadjustablegroundfaultprotection
>GFcurrentrangesetpoints -20…100mA -100…500mA -0.2…1.0A -1.0…5.0A
>GFtriplevel20%-100%
• LEDstatusindication
• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID
• MustusewithCEP7-CBCTcurrentsensor
CEP7(S)-EE_ CEP 7-EE_P
CEP 7-EGF
CEP 7-EGJ
Ground fault/jam protection and remote reset module 2) 3)
• Dipswitchadjustablegroundfaultprotectionsameas CEP7-EGFshownabove
• Jamtripwhenthemotorcurrentexceeds400%FLA setting when enabled
• LEDstatusindication
• ProvisionforresetaftertripfromremotepilotdeviceorCEP7-ERID
• MustusewithCEP7-CBCTcurrentsensor
CEP7(S)-EE CEP 7-EE_P
CEP 7-EGJ
NoTE: 1) Sidemountmodulesmusthave24-240V,47-63HzorDCappliedtoterminalsA1andA2forcontrolpower
2) Attention: The CEP 7 overload relay is not a ground fault circuit interruptor for personnel protection
3) Must be used with core balance transformer - refer page 11
CEP 7-CBCT core balance transformers for CEP 7-EGF / EGJGround fault current is sensed by passing all lines carrying current to and from a motor through the window of a special core balance current transformer often called a toroid / ground fault sensor. If all the current to the motor returns throughthelinesinthetoroid,nosignificantcurrentwillbeinducedinthetoroidsecondary.If,however,groundfaultcurrentreturnsviaapathexternaltothetoroid,suchasviatheconduitwalls,acurrentwillbeinducedinthetoroidsecondary.Thiscurrentwillbesensedandamplifiedbysolidstatecircuits.Ifthegroundfaultcurrentislargerthantheselected ground fault trip level of the overload relay, the overload relay will trip.
SENSoR TyPE APPRox. CuRRENT RATING
INSIDE DIAMETER
MAx REC. CABLE SIzE @ 600 V
TyPICAL uSE wITH CoNTACToR SIzE CAT No.
45A 19 mm 10 mm21) CA 7 - 9... CA 7 - 43 CEP 7-CBCT1
90 A 40 mm 35mm21) CA7-9...CA7-85 CEP 7-CBCT2
180 A 64 mm 120mm21) CA 6 - 180 CEP 7-CBCT3
420A 82mm 185mm21) CA6-420 CEP 7-CBCT4
860 A 160 mm 300 mm21) CA 6 - 860 CEP 7-CBCT5
Communication modulesDESCRIPTIoN To SuIT CAT No.
Ethernet / IP communication module Includeswarningforjamtrip,overloadandunderload Inputs/outputs - 2inputs(24VDCrated) - 1outputrelay(B300rated) - status indication LED Monitoring - %thermalutilised - averagecurrent%FLA - device, trip and warn status
CEP7(S)-EE CEP 7-EE_P
CEP 7-ETN
Profibus® communication module Includeswarningforjamtrip,overloadandunderload Inputs/outputs - 2inputs(24VDCrated) - 1outputrelay(B300rated) - status indication LED Monitoring - %thermalutilised - averagecurrent%FLA - device, trip and warn status
CEP7(S)-EE CEP 7-EE_P
CEP 7-EPRB
DeviceNet communication module CEP7(S)-EE CEP 7-EE_P
CEP 7-EDN
DeviceNet™ Hand Held Programmer HMI 2)
Programming terminal includes 1 m communication cable TobeusedwithCEP7-C1/C2/C3andCEP7-EDNmodule
CEP7(S)-EE CEP 7-EE_P
CEP 7-DNCT
NoTE: 1) With a 3 phase system with one cable per phase
2) Can be used on any DeviceNetTMproductornetwork.CompatiblewithCEP7C
11 12
Accessories
ACCESSoRy DESCRIPTIoN FoR uSE wITH CAT No.
DIN-rail / panel adaptorForseparatemountingofoverloadrelaytobackpanortophatDIN-rail
CEP 7-ED1_B CEP7(S)-EE_B
CEP 7-EPB
CEP7-EE…D CEP 7-EPD
CEP7-EE…E CEP 7-EPE
Current adjustment shieldPreventsinadvertentadjustmentofthecurrentsetting
All CEP 7 CEP 7-BC8
External reset button adaptorProvides a larger “target area” for resetting the overload relay whenusinganexternalresetbutton
All CEP 7 CEP 7-ERA
External reset buttonManual reset pushbutton used for resetting overloads mountedinenclosures.TobeusedwithCEP7-ERA
All CEP 7 D7P-R611
Reset rodTosuitD7externalresetpushbutton(D7P-R611)and CEP7-ERAadaptor
All CEP 7 D7-ATR08
Adjustment cover for external modules All CEP 7 CEP 7-EMC
Remote reset solenoids 24VAC
110VAC
240VAC
24VDC
48VDC
110VDC
All CEP 7
All CEP 7
All CEP 7
All CEP 7
All CEP 7
All CEP 7
CEP 7-EMRJCEP 7-EMRDCEP 7-EMRACEP 7-EMRz24CEP 7-EMRz48CEP 7-EMRz01
1 metre communications cable with micro-connector CEP 7-DNCT CEP 7-CM1
1 metre communications cable with bare leads (includedwiththeCEP7-DNCT)
CEP 7-DNCT CEP 7-BC1
Door / panel mount bezel kit CEP 7-DNCT CEP 7-DNCT - Bz1
ACCESSoRy DESCRIPTIoN FoR uSE wITH CAT No.
Remote indication and reset module 1)
PanelmountedIP66uses22.5mmfixinghole.Itmustbeusedinconjunctionwithasidemountmoduleandconnectsvia twowirestotheremoteresetterminalsR1andR2.
Indication LEDS Power
Overload
• Trip(solid)
• Warning(flash)
Phase loss
ModulespecificLED-groundfault,PTC,jam
CEP7-ERR
CEP 7-EJM
CEP 7-EPT
CEP7-EGF
CEP 7-EGJ
CEP 7-ERID
NoTE: 1) Must be used with side mount modules. Not compatible with communication modules
works with CEP7-EE overloads from 0.1 to 800 Amps
overload Conditions LED • Trip(RED,solid) • Warning(YELLOW,flash)
Display Status • Modulepower(GREEN,flash) • Modulepower&motorcurrent (GREEN, solid) • Hardwarefault(RED,solid)
Module Fault LED • Groundfaulttrip(RED,oneflash) • Jamtrip(RED,twoflashes) • PTCtrip(RED,threeflashes) • Faultdetected(RED,rapidflash)
Phase Loss LED • Trip(RED,solid)
Remote Reset
IP 66 rated
Installation Dimensions (mm)
355
300
420
250
210
180
140115
16
23
912
16
23630
860
43
30
37
8597
7260
9
12
500kW
Amps
455540
32
22
18.5
15
250
185
150
132
110
9075
4 5.57.5
11
4
5.5
7.5
11
CuRRENT SETTING RANGE (A)
CEP7-EEJG40...200CEP7-EEKG60...300CEP7-EELG100...500
CuRRENT SETTING RANGE (A)
CEP7-EEHF30...150CEP7-EEJF40...200
CuRRENT SETTING RANGE (A)
CEP7-EEMH120...600
CEP7-EENH160...800
CuRRENT SETTING RANGE (A)
CEP7-EEGE18...90 CEP7-EEVE30...150
CEP 7 quICK REFERENCE GuIDE
Motor protection CEP 7 overload relaysNHP have introduced the new sprecher + schuh CEP 7, second generation electronic overload protection relays. The new CEP 7 overloads incorporate a greater use of sophisticated electronic control and monitoring. The CEP 7 second generation overload now incorporates greater accuracy and versatility whilst providing increased overall protection.
CEP 7-EE
CEP 7-EE CEP 7-EE
CEP 7-EE CEP 7-EE
CEP 7-EDCEP 7-EE
CEP 7
quick Reference GuideCEP 7 sIDE MOUNT MODULEs
• RemoteresetmoduleCEP7-ERR
• Jamprotectionandremoteresetmodule CEP 7-EJM
• PTCthermistorrelayandremotereset module CEP 7-EPT
• GroundfaultprotectionandremoteresetmoduleCEP7-EGF
• Groundfault/jamprotectionandremote reset module CEP 7-EGJ
• Profibus® communication moduleCEP7-EPRB
• DeviceNetTM communication module CEP 7-EDN
• Ethernet/IPcommunicationmodule CEP 7-ETN
• Electronicoverloadsalsoavailablefor single phase applications to IEC 60947. Current settings from 1...90 amps. See page 6.
• ElectronicoverloadsCEP7-E_Ppass through version also available. See page 9.
• ElectronicoverloadsCEP7-C1andCEP7-C2completewithcommunication(DeviceNetTM). Current settings from 0.4...860 amps. See NHP Part-A Catalogue for more details.
Enhanced electronic overload relays for 3 phase motors
standard electronic overload relays for 3 phase motors
CuRRENT SETTING RANGE (A)
CEP7-EEAB0.1...0.5
CEP7-EEBB0.2...1.0
CEP7-EECB1.0...5.0
CEP7-EEDB3.2...16
CEP7-EEEB5.4...27
CEP7-ED1AB0.1...0.5
CEP7-ED1BB0.2...1.0
CEP7-ED1CB1.0...5.0
CEP7-ED1DB3.2...16
CEP7-ED1EB5.4...27
CuRRENT SETTING RANGE (A)
FEATuRES:• Manual reset• Tripclass10• 5:1currentadjustmentrange• self powered• Lowpowerconsumption(150mW)• Direct mounting to CA 7
contactors• 1 N/C trip contact and 1 N/O
alarm contact• visible trip indicator
FEATuRES:• Auto/manualreset• Adjustabletripclass10,15,20and30• 5:1currentadjustmentrange• Selfpowered• Lowpowerconsumption(150mW)• DirectmountingtoCA7contactors• 1N/Ctripcontactand1N/Oalarmcontact• Visibletripindicator• Optionalsidemountmodules
kW
CuRRENT SETTING RANGE (A)
CEP7-EEED5.4...27CEP7-EEFD9.0...45
Amps
CA 6
(10
00 V
AC) CA
7 (690 VAC)
Dimensions (mm)
CEP 7 MouNTED To CA 7 CoNTACToR (wITH SIDE MouNTED MoDuLE)
A
F
G
B
D
E
K
L
H
C
J
Wire size and torque specifications
1X
2X
0.2...3.3 mm2
0.2...1.3 mm2
0.55 Nm
1X
2X
0.2...2.5 mm2
0.25...1 mm2
0.55 Nm
1X
2X
0.2...2.5 mm2
0.2...1 mm2
0.55 Nm
oVERLoAD Cat. No.
CoNTACToR Cat. No.
mm
A B C D E F G H J K L
CEP 7*-EE_B CA7-9/12/16/23 63 148 85.2 24.5 13.9 35 60 86.5 2 4.5 18
CEP 7*-EE_DCA 7 - 30/37 63 148 101.2 24.5 13.9 35 60 104 2 4.5 18
CA 7 - 43 67.5 148 101.2 24.5 18.4 45 60 107 2 4.5 18
CEP 7*-EE_E CA7-60/72/85/97 90 191.6 120.4 29 23.8 55 100 126 2 5.4 18
CEP7 module technical information
A
F
G
B
D
E
K
L
H
C
J
Wire size and torque specifications
1X
2X
0.2...3.3 mm2
0.2...1.3 mm2
0.55 Nm
1X
2X
0.2...2.5 mm2
0.25...1 mm2
0.55 Nm
1X
2X
0.2...2.5 mm2
0.2...1 mm2
0.55 Nm
• ConnectremoteresetpilotdevicetoterminalsR1andR2.
• DonotapplyexternalvoltagetoR1andR2.Equipmentdamagewilloccur.
• Recommenduseoftwistedpairforremotereset,0.2mm2 minimum.
• Apply24-240V,47-63HzorDCtoterminalsA1andA2forcontrolpower.
• Ratedinsulationvoltage(Ui) 300V
• Ratedoperatingvoltage(Ue) 24-240VAC,50/60Hz 24-240VDC
• Poweratratedoperatingvoltage 24VAC 0.3W (Typical) 120VAC 0.3W 240VAC 0.5W
• Ratedimpulsewithstandvoltage(Uimp) 2.5kV
• Dynamicinhibitonstart.AuniquecircuitwithintheCEP7protectionmodulesmonitors for motor starting inrush current. The circuit inhibits the protection feature during the motor start period and arms the protection function after the inrush current falls to motor rated current. This allows the motor to start and run, avoiding nuisance tripping during the inrush period.
Dimensions (mm)
NoTE: * No letter indicates 3 phase; ‘S’ indicates single phase
oVERLoAD Cat. No.
CoNTACToR Cat. No.
Awidth
BHeight B1 C
Depth D E1 E2 F G H J K M
Without terminal covers
With terminal covers
Reset
CEP 7-EE_F
CA6-115(EI) 120 336.3 418 311.8 152.7 156 36 226.3 12.5 100 145 135 22.3 8-5.6
CA6-140(EI)120 339.8 418 317.8 152.7 156 36 226.3 16 100 145 135 22.3 8-5.6
CA6-180(EI)
CEP 7-EE_GCA6-210EI
155 385.8 487.4 360.8 176.5 180 36 265.5 21 130 180 140 23.5 8-6.5CA6-420EI
CEP 7-EE_HCA 6 - 630 EI
255 552 915 508 269.3 270.7 36 384.1 52.5 226 230 108 109 8 - 13CA 6 - 860 EI
CEP 7 PASS THRouGH oVERLoAD
CEP 7-EEVF MouNTED To CA 6 CoNTACToR
261
Ø 5.6
145
46.4
100
120
12.5
CA6-110]
153.7
151.2
196.2
158.3 RESET BUTTONTRAVEL: 2.5
CEP 7-EE_F...EE_H MouNTED To CA 6 CoNTACToR
15 16
wiring diagrams
CEP 7-ERR AND CEP 7-EJM wIRING DIAGRAMS
CEP 7-ERR / EJM oPERATIoNAL LED
CEP 7-EJM DIP SwITCH
2R
1R
2A
1A A1
A2
R1
R2Adjustment Settings
Remote Reset
Enable: ISW1 Disable: 0
Jam Protection
Jam Trip Level
Enable: 0
SW 3 SW 4
150% 0 0
200% 0 I
300% I 0
400% I I
SW2 Disable: I
Jam Trip Delay
SW 5 SW 6
0.5 sec I I
1 sec I 0
2 sec 0 I
4 sec 0 0
CEP7-EPT Wiring Diagrams
2R
1R
2TI
1TI
2A
1A A1
A2
R1
R2
IT2IT1 Adjustment Settings 1)
SW1 Manual: I
SW2 Enable: I
Overload Relay and PTC Reset Mode
PTC ProtectionDisable: 0
Automatic: 0
SW3 3 Phase: IOverload Relay Type
1 Phase: 0
• Apply24-240V,47-63HzorDCtoterminals A1andA2forcontrolpower.
• ConnectremoteresetpilotdeviceorCEP7-ERIDto terminals R1andR2.
STATuS LED
steady green - Module is powered up.
2R
1R
2A
1A A1
A2
R1
R2Adjustment Settings
Remote Reset
Enable: ISW1 Disable: 0
Jam Protection
Jam Trip Level
Enable: 0
SW 3 SW 4
150% 0 0
200% 0 I
300% I 0
400% I I
SW2 Disable: I
Jam Trip Delay
SW 5 SW 6
0.5 sec I I
1 sec I 0
2 sec 0 I
4 sec 0 0
CEP7-EPT Wiring Diagrams
2R
1R
2TI
1TI
2A
1A A1
A2
R1
R2
IT2IT1 Adjustment Settings 1)
SW1 Manual: I
SW2 Enable: I
Overload Relay and PTC Reset Mode
PTC ProtectionDisable: 0
Automatic: 0
SW3 3 Phase: IOverload Relay Type
1 Phase: 0
CEP 7-EPT wIRING DIAGRAM
CEP 7-EPT oPERATIoNAL LED
CEP 7-EPT DIP SwITCH
2R
1R
2A
1A A1
A2
R1
R2Adjustment Settings
Remote Reset
Enable: ISW1 Disable: 0
Jam Protection
Jam Trip Level
Enable: 0
SW 3 SW 4
150% 0 0
200% 0 I
300% I 0
400% I I
SW2 Disable: I
Jam Trip Delay
SW 5 SW 6
0.5 sec I I
1 sec I 0
2 sec 0 I
4 sec 0 0
CEP7-EPT Wiring Diagrams
2R
1R
2TI
1TI
2A
1A A1
A2
R1
R2
IT2IT1 Adjustment Settings 1)
SW1 Manual: I
SW2 Enable: I
Overload Relay and PTC Reset Mode
PTC ProtectionDisable: 0
Automatic: 0
SW3 3 Phase: IOverload Relay Type
1 Phase: 0
• Apply24-240V,47-63HzorDCtoterminalsA1andA2forcontrolpower.
• Connectremoteresetpilotdeviceor CEP7-ERIDtoterminalsR1andR2.
• ConnectterminalIT1andIT2to PTC chain.
STATuS LED
steady green - Module is powered up.
Flashing LED - The number of flashes followed by a pause identifiesthespecifictripcodeasfollows:
(1) Flash - overload trip
(2) Flash - phase loss trip
(3) Flash - PTC trip
(4)Flash- PTC open circuit
(5)Flash- PTC short circuit
Fastflash- Impending trip. PTC thermistor fault detected and CEP 7 not yet capable of tripping.
steady red - Hardware fault. Internal hardware fault detected and CEP 7 trip attempted.
2R
1R
2A
1A A1
A2
R1
R2Adjustment Settings
Remote Reset
Enable: ISW1 Disable: 0
Jam Protection
Jam Trip Level
Enable: 0
SW 3 SW 4
150% 0 0
200% 0 I
300% I 0
400% I I
SW2 Disable: I
Jam Trip Delay
SW 5 SW 6
0.5 sec I I
1 sec I 0
2 sec 0 I
4 sec 0 0
CEP7-EPT Wiring Diagrams
2R
1R
2TI
1TI
2A
1A A1
A2
R1
R2
IT2IT1 Adjustment Settings 1)
SW1 Manual: I
SW2 Enable: I
Overload Relay and PTC Reset Mode
PTC ProtectionDisable: 0
Automatic: 0
SW3 3 Phase: IOverload Relay Type
1 Phase: 0
wiring diagrams
CEP 7-EGF AND CEP 7-EGJ wIRING DIAGRAMS
CEP 7-EGF oPERATIoNAL LED
CEP 7-EGF DIP SwITCH
2A
1A A1
A2
R1R2
S1
S2
2R
1R
2S
1S
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
SW8 Not Used
Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current
Ground Fault Sensor (CEP 7-CBCT) Control Wiring
Motor
L2 L3L1
GroundFault
Sensor
CEP 7Overload Relay
with Side Mount Module
S1 S2
SW8 Enable: I Jam Protection
Disable: 0
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current
• Apply24-240V,47-63HzorDCtoterminalsA1andA2forcontrolpower.
• ConnectremoteresetpilotdeviceorCEP7-ERIDtoterminalsR1andR2.
• Connectcurrentsensortoterminal S1andS2.
STATuS LED:
steady green - Module is powered up.
Flashing LED - The number of flashes followed by a pauseidentifiesthespecifictripcodeasfollows:
(1) Flash - overload trip
(2) Flash - phase loss trip
(3) Flash - ground fault trip
Fastflash- Impending trip ground fault detected and CEP 7 not yet capable of tripping.
steady red - Hardware fault. Internal hardware fault detected and CEP 7 trip attempted.
2A
1A A1
A2
R1R2
S1
S2
2R
1R
2S
1S
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
SW8 Not Used
Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current
Ground Fault Sensor (CEP 7-CBCT) Control Wiring
Motor
L2 L3L1
GroundFault
Sensor
CEP 7Overload Relay
with Side Mount Module
S1 S2
SW8 Enable: I Jam Protection
Disable: 0
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current
CEP 7-EGF AND CEP 7-EGJ INSTALLATIoN
CEP 7-EGJ oPERATIoNAL LED
CEP 7-EGJ DIP SwITCH
2A
1A A1
A2
R1R2
S1
S2
2R
1R
2S
1S
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
SW8 Not Used
Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current
Ground Fault Sensor (CEP 7-CBCT) Control Wiring
Motor
L2 L3L1
GroundFault
Sensor
CEP 7Overload Relay
with Side Mount Module
S1 S2
SW8 Enable: I Jam Protection
Disable: 0
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current
STATuS LED:
steady green - Module is powered up.
Flashing LED - The number of flashes followed by a pauseidentifiesthespecifictripcodeasfollows:
(1) Flash - overload trip
(2) Flash - phase loss trip
(3) Flash - ground fault trip
(4)Flash-jamtrip
Fastflash- Impending trip ground fault detected and CEP 7 not yet capable of tripping.
steady red - Hardware fault. Internal hardware fault detected and CEP 7 trip attempted.
2A
1A A1
A2
R1R2
S1
S2
2R
1R
2S
1S
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 m A100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
SW8 Not Used
Disable/Off20 % Max GF Current35 % Max GF Current50 % Max GF Current65 % Max GF Current80 % Max GF Current90 % Max GF Current100 % Max GF Current
Ground Fault Sensor (CEP 7-CBCT) Control Wiring
Motor
L2 L3L1
GroundFault
Sensor
CEP 7Overload Relay
with Side Mount Module
S1 S2
SW8 Enable: I Jam Protection
Disable: 0
Adjustment Settings
SW1 Manual: I
SW 2 SW30 00 II 0I I
SW 4 SW 6SW 50 0
00
0 I00IIII
0
0
II I
I
III00
0
20...100 mA100...500 mA0.2...1.0 A1.0...5.0 A
Overload Relay Reset Mode
Ground Fault Current Range
Ground Fault Trip Level
Automatic: 0
SW7 3 Phase: I Overload Relay Type
1Phase: 0
Disable/Off20 % Max GF Curren t35 % Max GF Curren t50 % Max GF Curren t65 % Max GF Curren t80 % Max GF Curren t90 % Max GF Current100 % Max GF Current
NoTE: 1) The delay between the occurrence of a PTC out-of-range fault and a trip of the CEP 7 varies, but is generally described byoneofthefollowing:
• 500ms±250ms,typical; - <6seconds,foraPTCout-of-rangefaultpresentatpower-upofthesidemountmodule. - UndernoconditionsshouldaPTCtriptakelongerthan6seconds.17 18
wiring diagrams
CEP 7-EDN DEVICENETTM MoDuLE CEP 7-EPRB PRoFIBuS® MoDuLE
CEP 7-ETN ETHERNET / IP MoDuLE
CEP7-ETN Ethernet Network Communication Module ConnectstothenetworkviaRJ45(Cat5)connector.
SupportsI/Oandexplicitmessagingfordataaccessbyprogrammableautomatic controller.
ContainspredefinedControlLogixstyletagsfordirectsoftwareaccess.
Includes an integrated web server to allow users to read information and configureparametersviaacomputerwebbrowserfromremotelocations.
UsesaSimpleMailTransferProtocol(SMTP)servertosende-mailortextmessages in the event of a warning or trip condition.
EtherNet /IP Communications
TCP Connection 150
CIP Connection 48
CIP Unconnected Messages 128
I/OPacketRates 500/s
ExplicitPacketRates 500/s
SpeedDuplex(Half/Full) 10/100
Duplicate IP Detection Yes
ElectricalPowER SuPPLy RATINGS
RatedSupplyVoltage 24VDC
RatedOperationRange 20.4...26.4VDC
RatedSupplyCurrent 0.1A
MaximumSurgeCurrentatPower-up 2.5A
MaximumPowerConsumption 2.5...2.7WouTPuT RELAy RATINGS
Terminal OUT A 13/14
Type of Contacts FormASPST-NO
RatedThermalCurrent 5A
RatedInsulationVoltage 300V AC
RatedOperatingVoltage 240VAC
RatedOperatingCurrent
3A(@120VAC)
1.5A(@240VAC)
0.25A(@110VDC)
0.1A(@220VDC)
Minimum Operating Current 10mA(@5VDC)
RatingDesignation B300
UtilizationCategoryAC -15
ResistiveLoadRating(p.f.1.0)5A,250VDC
5A,30VDC
InductiveLoadRating
(p.f.=0.4),(L/R=7ms)
2A,250VAC
2A,30VDC
ShortCircuitCurrentRating 1000 A
RecommendedControlCircuitFuse KTK-R-6(6A,600V)
offers Integrated web and E-mail ServerView the status and events of your overload relay on the web at
anytime, anywhere!
The CEP7-ETN contains a web server to allow users to read informationandconfigureparametersviatheweb.
Usesasimplemailtransferprotocol(SMTP)servertosendemailortextmessagesintheeventofawarningortripcondition.
19 20
CEP 7-CBCT Core balance transformers
Control wiring installation
CEP 7-CBCT GRouND FAuLT TRIP DATA
• The control wiring must be a twisted pair
• Linesinexcessofonemetrelongmustbeashieldedpairwiththeshieldconnectedtogroundatonlyonepoint
Important: the shield, if present, of the twisted pair must be connected to earth ground at the sensor, with no connection made at the overload relay
• Maximumlengthis30metresfortheshieldedcable
• Sensorfastenertorque2.94-3.39Nm
• CEP7-CBCT lead wires should be twisted before termination by applying one twist per inch
CEP 7 oVERLoAD RELAy wITH CEP 7-EGF oR CEP 7-EGJ (CEP 7-EE)
Motor
L2 L3L1
S1 S2
Attention:thegroundfaultprotectionsystemisintendedforequipmentuseonly.Thissystemisnotagroundfaultcircuit interrupter for personnel protection.
Ground fault trip delayThe delay between the occurrence of a ground fault and a trip of the CEP 7 varies, but is generally described by one of thefollowing:
<6seconds,foragroundfaultpresentatpowerupofthesidemountmodule
<30seconds,iftheprotectioninhibithasnotbeencleared.Undernoconditionsshouldagroundfaulttriptakelongerthan 31 seconds
Power cable installation
1 Allpowercables,includingtheneutralwhenused,mustpassthroughthesensorwindow.Theequipmentgroundconductor(theconductorusedtocarrythenon-currentcarryingmetalpartsofequipment)mustnotpassthroughthe sensor window.
2 The power cables, going through the sensor window, must be straight, tightly bundled, centred in the window, and perpendiculartothesensorforalengthequaltoorgreaterthansixtimesthecablebundlediameter(includinginsulation)fromthesensor(seeFigure1).
3 Allotherconductorswithavailablefaultcurrentsinexcessof1,000Ashouldbeplacedadistanceequaltoorgreaterthansixtimesthecablebundlediameter(includinginsulation)fromthesensor(seeFigure2).
4 The power cables of the branch circuit, to be protected by the overload relay, must not be grounded on the load side of the ground fault sensor.
5 Ifthepowercablesareenclosedinaconductingjacket,thejacketmustbegroundedonthelinesideofthesensor.Thejacketmustnotpassthroughthesensorwindow,butmustbecutatthewindowandjoinedwithaconductorthat passes outside the sensor window.
6 The power system must be solidly grounded or grounded through an impedance at the source, as long as the impedance allows for a magnitude of current to flow that is within the operational range of the overload relay.
CEP 7 oVERLoAD RELAy wITH CEP 7-EGF oR CEP 7-EGJ (CEP 7-EE)
Attention:Topreventelectricalshock,disconnectfrompowersourcebeforeinstallingorservicing.Installinasuitableenclosure,keepfreefromcontaminants.
Do not apply power to a system with power cables going through the sensor unless the sensor is connected to the overload relay. Operation without a low impedence connection to the secondary windings may result in damage to the sensor.
Figure 1 Figure 2
21 22
Locating phase conductors in the sensor window
• Firmlysecuretheconductorsinthecentreofthesensorwindowsothattheycannotbemovedaccidentallyorunder fault conditions
• Maintain as large a distance as possible between the bundled conductors and the wall of the sensor window
• Forapplicationshavingonecableperphase,arrangetheconductorsperFigureA
• Forapplicationshavingtwocablesperphase,arrangetheconductorsperFigureB.Aspacer,havingthesamediameter as the conductors being used, should be used to separate the phase conductors
Single cable per phase Two cables per phase
B erugiFA erugiF
spacerA
B C
C
B B
A
A
C
Attention:Thegroundfaultprotectionsystemisintendedforequipmentuseonly.Thissystemisnotagroundfaultcircuit interrupter for personnel protection.
An ideal core-balanced ground fault toroid responds only to the sum of the currents flowing through the sensor window, however, an actual core balanced transformer may saturate if the phase currents are too large. This results ingroundfaultsensoroutputevenifthesumofthephasecurrentsiszero.Saturationcanbeminimisedbychoosingagroundfaultsensorwithadequatecoresizeandsymmetricallylocatingthephaseconductorsinthecentreofthesensor window as shown above.
Dimensions (mm)
CEP 7-CBCT 1
45.3
23.1
Ø 19.1
Ø 44.5
63.550.8
3.2 4
12.7
CEP 7-CBCT 2 AND 3
11.8
3.2
Ø D
5.3
E
F B
A
C44.5
CAT No.mm
A B C Ø D E F
CEP 7-CBCT 2 96 89 48.3 39.6 54.6 69.9
CEP 7-CBCT 3 122.4 115.9 59.7 63.5 54.1 96
CEP 7-CBCT 4
56.2
74.4
123.2 96.7
11.8 146.8
143.5
5.5
74.93.2
82.6
23 24
NoTE: 1)Performancecriteria1requirestheDUTtoexperiencenodegradationorlossofperformance
2)Environment2
NoTE: 1) Typical reset time for CEP 7 Second Generation devices set to “automatic reset” mode is 120seconds
Technical information
CoNTRoL CIRCuIT
Rated insulation voltage - uI [V] 690 AC
Rated insulation strength - uimp [kV] 6 AC
Rated operation voltage - ue [V] 690AC(IEC)/690AC(UL/CSA)
Rated operation current - ue
12...120V [A] 220...240V [A] AC-15 380...480V [A] 500...600V [A]
3/21)1.5/1.50.75/0.75
0.6 / 0.6 24V [A] DC-13 110 V [A] atL/R15ms 220V [A] 440 V [A]
1.1 / 1.10.4 / 0.40.2/0.2
0.08 / 0.08
Thermal current - Ithe [A]Contact reliability [kV]Screw terminal cross sectionTerminal screw One conductor [mm2] Flexiblewithwire Torque [Nm] end ferrule Two conductors [mm2] Torque [Nm]
517V,5mA
M31x(0.5...2.5)
0.552x(0.25...1.5)
0.55
One conductor [mm2] Coursestranded Torque [Nm] / solid Two conductors [mm2] Torque [Nm]
1x(0.5...4)0.55
2x(0.22...2.5)0.55
One conductor [mm2] Stranded Torque [Nm] / solid Two conductors [mm2] Torque [Nm]
1x(0.2...5.3)0.55
2x(0.2...3.3)0.55
Pozidrivescrewdriversize 1
Slottedscrewdriversize [mm] 0.6x3.5
ENVIRoNMENTAL RATINGS
Ambient temperature Storage [°C] Operating [°C]
-40...+85-20...+60
Humidity Operating [%] Damp Heat
5...95,non-condensingperIEC68-2-3andIEC68-2-30
Vibration(perIEC68-2-6) [G] 3
Shock (perIEC68-2-27) [G] 30
Maximum altitude [m] 2000
Pollution environment Pollution degree 3
Degree of protection IP20
Type of relay Ambient compensated, time delay, phase loss standard
Nature of relay Solid stateTrip ratingTrip class Type ED Type EE
120%FLA10
10,15,20,30Reset mode Type ED Type EE
ManualManual or automatic
Trip curves 1)
1000
1000
100
100
10
10
Tim
e (s
econ
ds)
Tim
e (s
econ
ds)
FLA multiple
FLA multiple
TRIP ClASS 15
TRIP ClASS 30
1
1
0.1
0.1
1
1
10
10
1000
1000
100
100
10
10
Tim
e (s
econ
ds)
Tim
e (s
econ
ds)
FLA multiple
FLA multiple
TRIP ClASS 10
TRIP ClASS 20
1
1
0.1
0.1
1
1
10
10
TRIP CuRVE LEGEND
Cold tripHot trip
Technical information
ELECTRoMAGNETIC CoMPATIBILITy
Electrostatic discharge immunity Testlevel [kV]
Performance level
8kVairdischarge6kVcontactdischarge
1 1)2)RF immunity Test level [V/m] Performance level
10 V/m1 1)2)
Electrical fast transient burst immunity Test level [V/m] Performance level
4kV1 1)2)
Surge immunity Test level [V/m]
Performance level
2kV(L-E)1kV(L-L)
1 1)2)
GENERAL
Standards UL,508,CSAC22.2No.14,NEMA(CD2-1993
Part4,EN60947-4-1,EN60947-5-1)Approvals CE,C-Tick,CSA,UL,Atex(pending)
25 26
NHP Electrical Engineering Products Pty LtdA.B.N.84004304812
NSPRECHEP7C©CopyrightNHP2011
AUSTRAlIAnhp.com.au
SALES 1300 NHP NHP
VICToRIAMelbourne 43-67RiverStreet Richmond VIC3121 Tel+61394292999
laverton 104-106 William Angliss Drive Laverton North VIC3026 Tel+61393682901
Albury / Wodonga 847RamsdenDrive Albury NSW2640 Tel+61260490600
Dandenong 40-42CyberLoop Dandenong South VIC3175 Tel +61 3 8773 6400
TASMANIAHobart 2/65AlbertStreet Moonah TAS 7009 Tel+61362289575
launceston 3/13-17 Merino Street Kings Meadows TAS7249 Tel+61363452600
NEW SoUTH WAlESSydney 30-34 Day Street North Silverwater NSW2128 Tel+61297483444
Newcastle 575MaitlandRoad MayfieldWest NSW2304 Tel+61249602220
Wollongong 34IndustrialRoad Unanderra NSW2526 Tel+61242725763
ACTCanberra 1/187 Gladstone Street Fyshwick ACT2609 Tel+61262809888
WESTERN AUSTRAlIAPerth 38 Belmont Ave Rivervale WA 6103 Tel+61892771777
NoRTHERN TERRIToRyDarwin 3 Steele Street Winnellie NT0820 Tel+61889472666
QUEENSlANDBrisbane 16RiverviewPlace Murarrie QLD4172 Tel +61 7 3909 4999
Townsville 5LeylandStreet Garbutt QLD 4814 Tel +61 7 4779 0700
Rockhampton 14RobisonStreet QLD 4701 Tel+61749272277
Toowoomba Cnr Carroll Street and Struan Court QLD4350 Tel +61 7 4634 4799
Cairns 2/1BrampClose Portsmith QLD 4870 Tel+61740356888
SoUTH AUSTRAlIAAdelaide 36-38CroydonRoad Keswick SA5035 Tel+61882979055
NEW ZEAlANDnhp-nz.com
SALES 0800 NHP NHP
POBox62-009 Mount Wellington Auckland1641 New Zealand
Auckland 118aCarbineRoad Mt Wellington 1060 Tel+6492761967