Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet Network Catalog Numbers Logix5000 Controllers, 1734 POINT I/O Modules Quick Start
Transcript
Page 1: conectar Point Io a Red Devicenet

Logix5000 Control Systems: Connect POINT I/O Modules over a DeviceNet NetworkCatalog Numbers Logix5000 Controllers, 1734 POINT I/O Modules

Quick Start

Page 2: conectar Point Io a Red Devicenet

Important User Information

Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

Allen-Bradley, FLEX, Integrated Architecture, Logix5000, POINT I/O, Rockwell Software, Rockwell Automation, RSLogix, RSNetWorx, and TechConnect are trademarks of Rockwell Automation, Inc.

Trademarks not belonging to Rockwell Automation are property of their respective companies.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

Page 3: conectar Point Io a Red Devicenet

Table of Contents

Preface About This Publication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Before Using This Publication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Other Logix5000 Control System Quick Starts . . . . . . . . . . . . . . . . . . . . . . 8Where to Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9How Hardware is Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Required Software. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Chapter 1Prepare the Distributed POINT I/O Hardware

Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13What You Need. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Mount and Connect the 1734-ADN DeviceNet Adapter . . . . . . . . . . . . 15Mount the 1734-OB4E Digital Output Module . . . . . . . . . . . . . . . . . . . . 17Mount and Wire the 1794-PS3 Power Supply . . . . . . . . . . . . . . . . . . . . . . 18Wire the 1734-ADN DeviceNet Adapter to the Power Supply . . . . . . . 19Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Chapter 2Create DeviceNet Network Software Files

Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22What You Need. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23Register an EDS File - Optional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24Set the 1769-SDN Scanner Module’s Node Address. . . . . . . . . . . . . . . . . 27Create a DeviceNet Configuration File. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30Edit the DeviceNet Adapter Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34Configure the DeviceNet Subnet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36Create a DeviceNet Scanlist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Chapter 3Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47What You Need. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49Create DeviceNet Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50Add Ladder Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53Download the Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56Test the 1734-OB4E Digital Output Module’s Tags . . . . . . . . . . . . . . . . 57

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 3

Page 4: conectar Point Io a Red Devicenet

Table of Contents

Notes:

4 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 5: conectar Point Io a Red Devicenet

Preface

About This Publication

This quick start provides examples and procedures for including POINT I/O modules in a Logix5000 controllers control system over a DeviceNet network. The programming examples are not complex, and offer easy solutions to verify that devices are functioning and communicating properly.

Before Using This Publication

You can only complete the tasks described in this publication after first completing some prerequisite tasks with a Logix5000 controller. For example, before you can add a POINT I/O module to an RSLogix 5000 project, as described in Chapter 3, you must first create the project.

For more information on how to complete these tasks with specific Logix5000 controllers, see the Integrated Architecture: Logix5000 Control Systems Quick Starts Quick Reference, publication IASIMP-QR024.

IMPORTANT This publication describes example tasks you complete when using POINT I/O modules on a DeviceNet network. The tasks described are not the only tasks you can complete with the POINT I/O modules on a DeviceNet network. You will likely need to complete additional tasks when using POINT I/O modules in a specific Logix5000 control system.

IMPORTANT Multiple Logix5000 controllers support the use of a DeviceNet network. The specific hardware used and software configuration parameter settings vary by Logix5000 controller. This quick starts describes using POINT I/O modules over a DeviceNet network in a CompactLogix 5370 L3 control system.

The example graphics shown in Table 1 - Required Tasks To Complete Before Using this Quick Start on page 6 are for CompactLogix 5370 L3 controllers. Depending on the Logix5000 controller you are using, the specific steps to complete the tasks described in the table might vary.

The tasks described in this publication are written with the assumption that you have already installed the CompactLogix 5370 L3 control system and it is powered.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 5

Page 6: conectar Point Io a Red Devicenet

Preface

This table describes the tasks you must complete before using this publication.

Table 1 - Required Tasks To Complete Before Using this Quick Start

Task Description

Prepare the Logix5000 control system hardware

Assembling the control system and connecting to the DeviceNet network. At minimum, your system must include a controller, DeviceNet scanner module to access the DeviceNet network and the components required to install a DeviceNet network. For example, you need an external power source to power a DeviceNet network.

For example purposes, this quick start uses a CompactLogix 5370 L3 controller with a 1769-SDN scanner module as shown above, and the tasks described in Chapter 2 and Chapter 3 are done so with that controller and scanner module. We recommend that you use those components with this quick start.If you use a different Logix5000 controller and DeviceNet scanner module, you can complete the tasks in these chapters but you must account for any hardware differences.

For more information on installing a DeviceNet network, see the DeviceNet Media Design and Installation Guide, publication DNET-UM072.

This task does not include installation of remote hardware components, for example, POINT I/O modules, used over the network included in your application.

Prepare the computer Installing required software, for example RSLogix 5000 software, on your complete

1 (Front)2 (Rear)

00:00:BC:2E:69:F6

6 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 7: conectar Point Io a Red Devicenet

Preface

Configure the network Complete tasks associated with configuring the DeviceNet network with RSNetWorx for DeviceNet software, such setting the node address for the DeviceNet scanner module your controller uses to access the DeviceNet network.

This quick start uses a CompactLogix 5370 L3 controller with a 1769-SDN scanner module, and the tasks described in Chapter 2 and Chapter 3 are done so with that controller and scanner module. We recommend that you use those components and corresponding software files with this quick start.

If you use a different Logix5000 controller and DeviceNet scanner module and corresponding DeviceNet network software files, you can complete the tasks in Chapter 2 and Chapter 3 but you must account for any software differences.

Create an RSLogix 5000 project

Project used with your Logix5000 controller that includes all required control system components. Your project must include the DeviceNet scanner module used by your controller to access the DeviceNet network.

This quick start uses a CompactLogix 5370 L3 controller with a 1769-SDN scanner module, and the tasks described in Chapter 2 and Chapter 3 are done so for that controller and scanner module. We recommend that you use those components with this quick start.

If you use a different Logix5000 controller and DeviceNet scanner module and corresponding RSLogix 5000 software files, you can complete the tasks in Chapter 2 and Chapter 3 but you must account for any software differences.

Table 1 - Required Tasks To Complete Before Using this Quick Start

Task Description

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 7

Page 8: conectar Point Io a Red Devicenet

Preface

Other Logix5000 Control System Quick Starts

This quick start describes how to use a single component-type over a single network in a Logix5000 control system. Typically, though, a Logix5000 control system includes more than the controller, communication module and a single component over a single network.

For example, if a Logix5000 control system operates on a DeviceNet network, the system might use remote I/O modules, HMI devices and drives in addition to the controller and communication modules.

For a complete list of Logix5000 control system quick starts that describe how to other devices in Logix5000 control systems, see the Integrated Architecture:Logix 5000 Control Systems Quick Starts Quick Reference, publication IASIMP-QR024.

The beginning of each chapter contains the following information. You should read these sections before beginning work in each chapter:

• Before You Begin - This section lists the tasks you must complete before starting the chapter.

• What You Need - This section lists the tools that are required to complete the tasks in the current chapter. This includes, but is not limited to, hardware and software.

• Follow These Steps - This section illustrates the steps in the current chapter.

8 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 9: conectar Point Io a Red Devicenet

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 9

Preface

Where to Start

Prepare the Distributed POINT I/O Hardware

Required TasksDescribed in the appropriate Logix5000 controller quick start1. Prepare the Controller Hardware2. Prepare the Computer3. Configure the Network4. Create RSNetWorx for DeviceNet and RSLogix 5000 Software Projects

page 13

Create DeviceNet Network Software Files

page 21

Logix5000 Controller

Use the POINT I/O Adapter and Output Module in

an RSLogix 5000 Project

page 47

Page 10: conectar Point Io a Red Devicenet

10 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Preface

How Hardware is Connected

This quick start demonstrates the following Logix5000 control system using POINT I/O modules on a DeviceNet network.

Required Software

To complete examples in this quick start, you need this software.

Software Required Software Version, Min. Required for this Task

RSLogix 5000 20.00.00 or later(1)

(1) RSLogix 5000 software, version 20.00.00 or later is required for use of this quick start because the example Logix5000 controller, and associated tasks, described herein are completed in a CompactLogix 5370 L3 control system. CompactLogix 5370 control systems require RSLogix 5000 software, version 20.00.00 or later. If you connect a 1734 POINT I/O module over a DeviceNet network in a Logix5000 control system that uses a different controller, the minimum software version may differ.

Change RSLogix 5000 projects to use POINT I/O modules.

RSNetWorx for DeviceNet 11.00.00 Modify DeviceNet configuration file to include the POINT I/O modules described in this publication.

DeviceNet Tag Generator 20.00.00 or later Generate new programs and tags in your RSLogix 5000 project.

24VDCSourceOutput

Module Status

Network Status

1734OB4E

NODE:

0

1

2

3

AdapterStatus

SystemPower

DeviceNetStatus

PointBus Status

FieldPower

1734-ADN

Logix5000 Controller with DeviceNet Scanner Module

Computer Connected to Logix5000 Controller

POINT I/O Modules

DeviceNet Power Supply 1606-XLDNET8

Page 11: conectar Point Io a Red Devicenet

Preface

Parts List

You need these parts to use this publication.

Quantity Cat. No. Description

1 1734-ADN POINT I/O DeviceNet adapter

1 1734-OB4E POINT I/O protected output module

1 1734-TB POINT I/O mounting base assembly with base and removable terminal block

1 1734-RTB POINT I/O removable terminal block

1 POINT I/O end cap

1 1794-PS3 FLEX FLEX I/O 85…264V AC to 24V DC 3 A power supply (1794-PS3)

1 1485K-P1F5-R5 KwikLink right-angle micro male to micro female connector cable

1 1485P-P1E4-R5 KwikLink sealed micro connector

1 1799-DNC5MMS 5-pin linear to micro male adapter

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 11

Page 12: conectar Point Io a Red Devicenet

Preface

Additional Resources

Use the additional resources listed in this table for more information when using POINT I/O modules over a DeviceNet network in a Logix5000 controller project.

You can view or download publications at http://www.rockwellautomation.com/literature/. To order paper copies of technical documentation, contact your local Allen-Bradley distributor or Rockwell Automation or sales representative.

Resource Description

POINT I/O DeviceNet Adapter Installation Instructions, publication 1734-IN026

Describes the installation of the adapter and technical specifications.

POINT I/O DeviceNet Adapter User Manual, publication 1734-UM002

Describes the installation, configuration, and troubleshooting of your 1734-ADN module.

POINT I/O Protected Output Module, publication 1734-IN056

Provide details regarding installation of the 1734-OB4E module.

POINT I/O Sink Input Module Installation Instructions, publication 1734-IN051

Provide details regarding installation of the 1734-IB4 module.

POINT I/O Wiring Base Assembly Installation Instructions, publication 1734-IN013

Describes the installation of the 1734-TBS and 1734-TBS POINT I/O wiring base assemblies.

FLEX I/O DC Power Supply Installation Instructions, publication 1794-IN069

Provide details regarding installation of the 1794-PS and1794-PS13 FLEX I/O power supplies.

DeviceNet Media Design and Installation Guide, publication DNET-UM072.

Describes how to install a DeviceNet network.

DeviceNet Modules in Logix5000 Control Systems, publication DNET-UM004

Describes the installation, configuration, and troubleshooting of DeviceNet modules.

Logix5000 Controllers Common Procedures Programming Manual, publication 1756-PM001

Provides details about adding and configuring modules, establishing communication, and writing ladder logic.

Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1

Provides general guidelines for installing a Rockwell Automation industrial system.

Product Certifications website, http://www.ab.com Provides declarations of conformity, certificates, and other certification details.

12 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 13: conectar Point Io a Red Devicenet

Chapter 1

Prepare the Distributed POINT I/O Hardware

In this chapter, you learn how to complete the following tasks:• Install the 1734-ADN DeviceNet adapter• Install the 1734-OB4E digital output module• Install the 1794-PS3 FLEX I/O power supply• Connect power to the 1734-ADN DeviceNet adapter

Before You Begin

Before you begin, complete these tasks described in Before Using This Publication on page 5:

• Prepare the Logix5000 control system hardware - Verify the control system and DeviceNet network are powered before using this chapter.

• Prepare the computer

• Configure the network

• Create an RSLogix 5000 projectThe example RSLogix 5000 project used in this quick start uses a CompactLogix 5370 L3 controller.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 13

Page 14: conectar Point Io a Red Devicenet

14 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Chapter 1 Prepare the Distributed POINT I/O Hardware

What You Need

This table lists what products you need to complete the tasks described in this chapter.

Follow These Steps

Quantity Cat. No. Description

1 1734-ADN POINT I/O DeviceNet adapter

1 1734-OB4E POINT I/O protected output module

1 1734-TB POINT I/O mounting base assembly with base and removable terminal block

1 1734-RTB POINT I/O removable terminal block

1 POINT I/O end cap

1 1794-PS3 FLEX FLEX I/O 85…264V AC to 24V DC 3 A power supply (1794-PS3)

1 1485K-P1F5-R5 KwikLink right-angle micro male to micro female connector cable

1 1485P-P1E4-R5 KwikLink sealed micro connector

1 1799-DNC5MMS 5-pin linear to micro male adapter

Mount and Connect the 1734-ADN

DeviceNet Adapter

Mount the 1734-OB4E

Digital Output Module

Mount and Wire the 1794-PS3 Power

Supply

Wire the 1734-ADN DeviceNet Adapter to the Power Supply

page 15

page 19

page 18

page 17

AdapterStatus

SystemPower

DeviceNetStatus

PointBus Status

FieldPower

1734-ADN

24VDCSourceOutput

Module Status

Network Status

1734OB4E

NODE:

0

1

2

3

AdapterStatus

SystemPower

DeviceNetStatus

PointBus Status

FieldPower

1734-ADN

Page 15: conectar Point Io a Red Devicenet

Prepare the Distributed POINT I/O Hardware Chapter 1

Mount and Connect the 1734-ADN DeviceNet Adapter

Complete the following tasks to mount and connect the 1734-ADN DeviceNet adapter.

1. Press the adapter onto the DIN rail.

2. Set the network node address with the thumbwheel switch.

This quick start uses node 02.

3. If the DeviceNet connector is installed on the 1734-ADN adapter module, remove it.

ModuleStatus

PointBusStatus

ControlNet AStatus

1734-ACNRControlNet BStatus

0 2Switches

DeviceNet Connector

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 15

Page 16: conectar Point Io a Red Devicenet

Chapter 1 Prepare the Distributed POINT I/O Hardware

4. Connect the 1799-DNC5MMS 5-pin linear to micro male adapter to the female end of the 1485K-P1F5-R5 KwikLink right-angle micro male to micro female connector cable.

5. Connect the female end of the DeviceNet cable to the adapter.

6. Connect the other end of the cordset to the DeviceNet network.

7. Remove the safety end cap.

This exposes the backplane and power interconnections.

ATTENTION: Do not discard the end cap. Use this end cap to cover the exposed interconnections on the last mounting base on the DIN rail. Failure to do so could result in equipment damage or injury from electric shock.

AdapterStatus

SystemPower

DeviceNetStatus

PointBus Status

FieldPower

1734-ADN

Safety End Cap

16 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 17: conectar Point Io a Red Devicenet

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 17

Prepare the Distributed POINT I/O Hardware Chapter 1

Mount the 1734-OB4E Digital Output Module

1. Install the removable terminal base (RTB) on the mounting base; making sure the handle is in the down position.

2. Using a small screwdriver, rotate the keyswitch on the mounting base to match the position on the keyswitch on the 1734-OB4E module.

This example shows the keyswitch in position 1.

3. Press the 1734-OB4E module into the wiring base.

4. Snap the handle up to lock the RTB on the module.

5. Connect the wiring base assembly, including mounting base, module, and RTB, to the POINT I/O Ethernet adapter via the slots on the right side of the adapter.

6. Slide the wiring base assembly along the right side of the network adapter and press it onto the DIN rail.

7. Slide the safety end cap onto the right side of the 1734-OB4E module.

HandleKeyswitch

Mounting Base

Removable Terminal Block

Tongue-and-groove Slots

Module

Page 18: conectar Point Io a Red Devicenet

Chapter 1 Prepare the Distributed POINT I/O Hardware

Mount and Wire the 1794-PS3 Power Supply

Use a 1794 FLEX I/O power supply to power the distributed POINT I/O modules. This publication uses the 1794-PS3 power supply.

1794-PS3 Power Supply

1. Hook the upper-lip of the DIN rail latch onto the DIN rail.

2. Press the module onto the DIN rail.

3. Connect the 120/230V AC power, 120/230V AC common, and AC Ground wires.

WARNING: Verify that all incoming power is turned off before wiring power.

Upper-lip of DIN rail latch.

rewoPCD V42YLPPUS REWOP3SP-4971

V42

MOC

GRL2/N

L1

18 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 19: conectar Point Io a Red Devicenet

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 19

Prepare the Distributed POINT I/O Hardware Chapter 1

Wire the 1734-ADN DeviceNet Adapter to the Power Supply

1. Connect the 12/24V DC common and 12/24V DC power wires from the power supply to the adapter.

2. Turn on incoming power.

Additional Resources

For a list of additional resources that might assist you when preparing the distributed POINT I/O module hardware, see page 12.

24VDCSourceOutput

Module Status

Network Status

1734OB4E

NODE:

0

1

2

3

AdapterStatus

SystemPower

DeviceNetStatus

PointBus Status

FieldPower

1734-ADN

Common

Power

Page 20: conectar Point Io a Red Devicenet

Chapter 1 Prepare the Distributed POINT I/O Hardware

Notes:

20 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 21: conectar Point Io a Red Devicenet

Chapter 2

Create DeviceNet Network Software Files

In this chapter, you complete the following tasks:

• Register an EDS file in RSNetWorx for DeviceNet software

• Set the DeviceNet scanner module’s node address

• Create a DeviceNet configuration file

• Change the POINT I/O DeviceNet network adapter’s configuration

• Change the DeviceNet network configuration

IMPORTANT Multiple Logix5000 control systems can use POINT I/O modules over a DeviceNet network. For example purposes, this quick start describes the use of POINT I/O modules over a DeviceNet network in a CompactLogix 5370 L3 control system.If you have already completed the steps in this chapter before using this quick start, skip to Chapter 3, Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project on page 47.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 21

Page 22: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

Before You Begin

Before you begin, you must complete these tasks:• These tasks described in Before Using This Publication on page 5:– Prepare the Logix5000 control system hardware– Prepare the computer– Configure the network– Create an RSLogix 5000 project

• These tasks described in Chapter 1, Prepare the Distributed POINT I/O Hardware on page 13:

– Mount and Connect the 1734-ADN DeviceNet Adapter– Mount the 1734-OB4E Digital Output Module– Mount and Wire the 1794-PS3 Power Supply– Wire the 1734-ADN DeviceNet Adapter to the Power Supply

What You Need

You need RSNetWorx for DeviceNet software to complete the tasks in this chapter.

22 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 23: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

Follow These Steps

Create a DeviceNet

Configuration Filepage 30

Create a DeviceNet

Scanlist

Configure the DeviceNet Subnet

Edit the DeviceNet Adapter Paramete

rspage 34

page 36

page 41

Set the 1769-SDN Scanner Module’s

Node Addresspage 27

Register an EDS File - Optional page 24

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 23

Page 24: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

Register an EDS File - Optional

You might need to register a device for use in RSNetWorx for DeviceNet software so the software recognizes the device and uses it appropriately. You register an electronic data sheet (EDS) file in the software.

If you do not need to register an EDS file in RSNetWorx for DeviceNet software, skip to Set the 1769-SDN Scanner Module’s Node Address on page 27.

1. Access the Rockwell Automation website that provides access to EDS files at: http://www.rockwellautomation.com/resources/eds/.

2. Use the pull-down menus to narrow the search parameters.

3. Click the link for the file you need to register.

4. Save the file to a location on your computer that you will remember.

5. In RSNetWorx for DeviceNet software, choose EDS Wizard . . . from the Tools pull-down menu.

24 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 25: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

6. When the EDS dialog box appears, click Next.

7. Verify that Register an EDS file(s). is checked and click Next.

8. Browse to the EDS file and click Next.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 25

Page 26: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

9. When the EDS File Installation Test Results screen appears, click Next.

10. Select the graph image for the device you want to register and click Next.

11. Select the device you want to register and click Next.

12. Click Finish when the registration is successful.

26 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 27: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

Set the 1769-SDN Scanner Module’s Node Address

To complete the steps described in this chapter, the scanner module uses the DeviceNet network node address 1.

• If your scanner module’s node address is already set to 1, you can skip this section and move to Create a DeviceNet Configuration File on page 30.

• If your scanner module’s node address is not set to 0, use this section to learn how to change it from its current value. For example purposes, the scanner module’s node number is 3 before it is changed.

1. Verify the controller’s mode switch is in the PROG position.

2. Start RSNetWorx for DeviceNet software.

3. From the Tools pull-down menu, choose Node Commissioning.

IMPORTANT The tasks described in this section require the use of the Node Commissioning tool in RSNetWorx for DeviceNet software. If you are using RSLogix 5000 software, version 20 or later, as required with this quick start, the Node Commissioning tool was an optional choice during the software installation.If you did not install the Node Commissioning tool previously, do so now.

RUN

REM

PROG

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 27

Page 28: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

4. Click Browse.

When the Device Selection dialog box appears, you can browse to the 1769-SDN scanner module over an EtherNet/IP network or USB connection. This example uses an EtherNet/IP network connection.

5. Under the AB_ETHIP-1 driver, expand the path to the 1769-SDN scanner module as shown in the example graphic.

6. Click OK.

7. If you receive a linking device warning, click Yes.

The Node Commissioning dialog box is populated with the 1769-SDN module’s current settings.

28 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 29: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

8. Enter a node address of 1 for the 1769-SDN scanner module and click Apply.

The Address is applied and is confirmed in the Messages box.

9. Record the node address.

10. Click Close.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 29

Page 30: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

Create a DeviceNet Configuration File

1. From the File pull-down menu, choose New.

2. Click Who Active to go online.

3. Expand the networks to the appropriate DeviceNet network.

In this example, the network is Port 2, DeviceNet.

30 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 31: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

4. Record the following information about the 1769-SDN scanner module:

• Slot number in the CompactBus = 1

• DeviceNet network node number = 1

5. Click OK.

6. Click OK when the alert about uploading or downloading device information.

RSNetWorx for DeviceNet software browses the network and shows the scanner module at DeviceNet network node number 1 and the 1734-ADN adapter at node number 2.

TIP Once the software browses the DeviceNet network to recognize the two nodes installed while completing the tasks described in this quick start, you can click Cancel and the browse function ends.

Slot number = 1

DeviceNet network node number = 1

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 31

Page 32: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

7. Right-click the 1769-SDN scanner module and choose Properties.

8. Click the Module tab.

9. Click Download.

All configuration is cleared from the 1769-SDN scanner module, and the software is synchronized with the module.

32 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 33: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

10. From the Platform pull-down menu, choose CompactLogix.

11. Enter the slot number of the 1769-SDN scanner module.

12. Click OK.

13. Save the file and record the file name and path.

This quick start uses the example file name DeviceNet.dnt.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 33

Page 34: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

Edit the DeviceNet Adapter Parameters

Complete the following steps to edit the 1734-ADN adapter’s configuration parameters.

1. Right-click the adapter and choose Properties.

2. Click the Parameters tab.

3. When prompted to upload or download configuration, click Upload.

34 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 35: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

4. Change the following parameters:

• AutoAddress Backplane Modules= 1

• Auto Start Mode = Map Data to DWord Boundaries.

5. Click Apply.

6. When prompted to update the adapter’s configuration, click Yes.

7. Click OK.

8. Save the DeviceNet configuration file.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 35

Page 36: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

Configure the DeviceNet Subnet

1. From the File pull-down menu, choose New.

2. Click Who Active to go online.

3. Expand the appropriate network and select the DeviceNet Subnet, DeviceNet network.

4. Click OK.

5. Click OK to upload device information.

36 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 37: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

The modules on the subnet appear.

6. From the Network pull-down menu, choose Upload from Network.

7. When prompted to upload entire network, click Yes.

8. Right-click the 1734-ADN adapter and choose Properties.

The remaining steps will associate a main and subnet .dnt project for the 1734-ADN module so you can easily switch between the two projects in RSNetWorx for DeviceNet software.

You also need the main and subnet .dnt projects to use the DeviceNet Tag Generator utility.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 37

Page 38: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

9. On the Device Bridging tab, click Associate File.

10. Select the main DeviceNet configuration file and click Open.

11. When the updated 1734-ADN Point I/O Scanner dialog box appears, click OK.

38 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 39: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

12. Save the DeviceNet subnet configuration file.

Name the file so it can be easily identified as the subnet. This quick start uses the name SubnetDeviceNet.dnt.

13. Record the file name.

14. From the File menu, choose Open.

15. Select the main DeviceNet file and click Open.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 39

Page 40: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

16. Right-click the 1734-ADN adapter and choose Properties.

17. On the Device Bridging tab, click Associate File.

18. Select the subnet configuration file and click Open.

40 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 41: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

19. When the updated 1734-ADN Point I/O DeviceNet Adapter dialog box appears, click OK.

20. Click OK.

21. Save your main DeviceNet configuration file.

Create a DeviceNet Scanlist

1. Verify that the network is online.

2. If the network is not online, choose Online from the Network pull-down menu.

3. When alerted to uploading or downloading device information, click OK.

4. From the Network pull-down menu, choose Upload from Network.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 41

Page 42: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

5. When prompted to upload entire network, click Yes.

6. Right-click the 1734-ADN adapter and choose Properties.

7. Click the Parameters tab and record the parameters shown.

8. Click OK.

42 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 43: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

9. Right-click the 1769-SDN scanner module and choose Properties.

10. On the Scanlist tab, click Upload from Scanner.

The configuration is uploaded from the device.

11. On the Upload Scanlist from Scanner dialog box, check All Records and click Upload

12. Click Upload.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 43

Page 44: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

13. Select the 1734-ADN adapter and move it to the Scanlist.

14. Click Edit I/O Parameters.

15. Verify that the I/O parameters match step 7 on page 42; if not, update them.

16. Click OK.

17. Verify that Automap on Add is checked and click Apply.

44 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 45: conectar Point Io a Red Devicenet

Create DeviceNet Network Software Files Chapter 3

18. When prompted to download changes, click Yes.

19. Click OK to close the 1769-SDN Scanner Module dialog box.

20. Save the configuration file.

21. Close RSNetworx for DeviceNet software.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 45

Page 46: conectar Point Io a Red Devicenet

Chapter 3 Create DeviceNet Network Software Files

Notes:

46 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 47: conectar Point Io a Red Devicenet

Chapter 3

Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

In this chapter, you complete the following tasks:• Create DeviceNet tags with the DeviceNet Tag Generator tool• Add ladder logic to the RSLogix 5000 project• Download the updated project to your controller• Test the ladder logic on your 1734-OB4E output module

Before You Begin

Before you begin, you must complete these tasks:

• These tasks described in Before Using This Publication on page 5:– Prepare the Logix5000 control system hardware– Prepare the computer– Configure the network– Create an RSLogix 5000 project

IMPORTANT Multiple Logix5000 control systems can use POINT I/O modules over a DeviceNet network. For example purposes, this quick start describes the use of POINT I/O modules over a DeviceNet network in a CompactLogix 5370 L3 control system that includes a 1769-SDN scanner module in a local expansion module slot.

This section uses an RSLogix 5000 project that matches the control system described previously and is named POINT_IO_on_DeviceNet_quick_start.acd. The 1769-SDN scanner module has been configured so the RSNetWorx tab links the RSLogix 5000 project to the DeviceNet file created in Create a DeviceNet Configuration File on page 30.

If you use a different Logix5000 controller and DeviceNet scanner module, you can complete the tasks in this chapter but must account for any software differences.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 47

Page 48: conectar Point Io a Red Devicenet

Chapter 3 Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

• These tasks described in Chapter 1, Prepare the Distributed POINT I/O Hardware on page 13:

– Mount and Connect the 1734-ADN DeviceNet Adapter– Mount the 1734-OB4E Digital Output Module– Mount and Wire the 1794-PS3 Power Supply– Wire the 1734-ADN DeviceNet Adapter to the Power Supply

• These tasks described in Chapter 2, Create DeviceNet Network Software Files on page 21:

– Set the 1769-SDN Scanner Module’s Node Address– Create a DeviceNet Configuration File– Edit the DeviceNet Adapter Parameters– Configure the DeviceNet Subnet– Create a DeviceNet Scanlist

What You Need

You need the following software to complete the tasks in this chapter:• RSLogix 5000 software• DeviceNet Tag Generator tool in RSLogix 5000 software

48 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 49: conectar Point Io a Red Devicenet

Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project Chapter 3

Follow These Steps

Download the Project

page 57

Create DeviceNet Tags

page 50

page 56

Test the 1734-OB4E Digital Output Module’s Tags

Add Ladder Logic page 53

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 49

Page 50: conectar Point Io a Red Devicenet

Chapter 3 Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

Create DeviceNet Tags

1. Launch the DeviceNet Tag Generator.

2. Select your RSLogix 5000 project and click Select Scanner.

3. Select the 1769-SDN scanner module that scans the network where the device is located and click Select RSNetWorx Project.

IMPORTANT Before running the DeviceNet Tag Generator, verify the following:• RSLogix 5000 software is running and the project is open.• RSNetWorx for DeviceNet software is closed.

50 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 51: conectar Point Io a Red Devicenet

Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project Chapter 3

4. Select the main DeviceNet configuration file and click Select Scanner Node.

5. Select the node of the DeviceNet scanner module and click Generate Tags.

6. Click Generate Tags.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 51

Page 52: conectar Point Io a Red Devicenet

Chapter 3 Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

7. When prompted to continue, click Yes.

When tag generation is complete, the text log appears.

8. Close the DeviceNet Tag Generator.

The DeviceNet Tag Generator created new programs and tags that were added to the controller organizer in your RSLogix 5000 project.

52 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 53: conectar Point Io a Red Devicenet

Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project Chapter 3

Add Ladder Logic

1. In RSLogix 5000 software’s controller organizer, expand Tasks >MainTask>MainProgram.

2. Double-click MainRoutine.

A blank routine opens.

3. Add a new rung to the routine.

4. From the Element Toolbar, drag and drop an Examine On element and an Output Energize element onto the rung.

5. Double-click the ? in the Examine On element.

6. Type PB for push button.

7. Press Enter.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 53

Page 54: conectar Point Io a Red Devicenet

Chapter 3 Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

8. Right-click PB and choose New “PB”.

9. When the New Tag dialog box appears, click Create and Close to use the default values.

10. Double-click the ? in the Output Energize element.

11. Name the Output Energize element OB4E_Light.

12. Right-click the OB4E_Light tag and choose New ‘OB4E_Light’.

IMPORTANT Do not use spaces in the tag name. Use underscores (__) instead.

54 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 55: conectar Point Io a Red Devicenet

Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project Chapter 3

13. From the Type pull-down menu, choose Alias.

14. From the Alias For pull-down menu, browse to the 1734-OB4E digital output module and choose the bit for the light you want to turn on.

This example uses Local_DeviceNet_scanner_N02_S01_COS_O.Data_0.

15. Click Create and Close.

This graphic shows the rung with each element configured.

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 55

Page 56: conectar Point Io a Red Devicenet

Chapter 3 Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

Download the Project

1. Save your changes.

2. Move the controller’s mode switch to the PROG position.

3. Click the Controller Status icon and choose Download.

4. In the Who Active dialog box, choose your controller and click Download.

5. Click Download one more time.

RUN

REM

PROG

56 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 57: conectar Point Io a Red Devicenet

Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project Chapter 3

Test the 1734-OB4E Digital Output Module’s Tags

1. Move the controller’s mode switch to the RUN position.

2. In the configuration tree, double-click Controller Tags.

3. Change the O.CommandRegister.Run tag to 1.

The 1769-SDN scanner module transitions to Run mode.

RUN

REM

PROG

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 57

Page 58: conectar Point Io a Red Devicenet

Chapter 3 Use the POINT I/O Adapter and Output Module in an RSLogix 5000 Project

4. If not open, open the project’s Main Routine to find the ladder logic written earlier in this chapter.

5. Select the PB and press Ctrl+T.

This toggles the state from 0 to 1 (off to on).

6. Verify that the light on the distributed digital output module turns on.

7. Press Ctrl+T to toggle the state back to 0 (off ).

8. Go Offline.

58 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 59: conectar Point Io a Red Devicenet

Index

Numerics1485K-P1F5-R5 KwikLink right-angle micro

male to micro female connector cable 11, 14

1485P-P1E4-R5 KwikLink sealed micro connector 11, 14

1734-ADN adapter 11, 141734-OB4E output module 11, 141734-RTB removable terminal block 11, 141734-TB mounting base 11, 141769-SDN scanner module 27-291785K-P1F5-R5 KwikLink right-angle micro

male to micro female connector cable 11, 14

1785P-P1E4-R5 KwikLink sealed micro connector 11, 14

1794-PS3 power supply 11, 14mount 18

1799-DNC5MMS 5-pin linear to micro male adapter 11, 14

Bbaud rate

set on 1734-ADN DeviceNet adapter 15

Cconfigure

1734-ADN adapter 34-351769-SDN scanner module node address 27-

29DeviceNet configuration file 30-33DeviceNet network 7, 21-45DeviceNet scanlist 41-45DeviceNet subnet 36-41ladder logic in RSLogix 5000 software 53-58

connectionsconnect 1734-ADN DeviceNet adapter to

DeviceNet network 15-16hardware 10wire power to 1734-ADN adapter 19

conventions 12

DDeviceNet network

1485K-P1F5-R5 KwikLink right-angle micro male to micro female connector cable 11, 14

1485P-P1E4-R5 KwikLink sealed micro connector 11, 14

1734-ADN adapter 11, 141769-SDN scanner module 27-291799-DNC5MMS 5-pin linear to micro male

adapter 11, 14configuration file 30-33configure network 7, 21-45configure scanlist 41-45configure subnet 36-41create tags 50-52set node address on 1734-ADN DeviceNet

adapter 15set node address on 1769-SDN scanner

module 27-29DeviceNet Tag Generator tool 10, 50-52

EEDS file

register in RSNetWorx for DeviceNet software 24-26

FFLEX I/O

power supply 11, 14

Hhardware

1485P-P1E4-R5 KwikLink sealed micro connector 11, 14

1734-ADN adapter 11, 14, 15-161734-OB4E output module 11, 14, 171734-RTB removable terminal block 11, 141734-TB mounting base 11, 141769-SDN scanner module 27-291785K-P1F5-R5 KwikLink right-angle micro

male to micro female connector cable 11, 14

1794-PS3 power supply 181799-DNC5MMS 5-pin linear to micro male

adapter 11, 14connections 10set node address on 1734-ADN DeviceNet

adapter 15set node address on 1769-SDN scanner

module 27-29

II/O module

1734-OB4E output module 11, 141734-RTB removable terminal block 11, 141734-TB mounting base 11, 14

Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012 59

Page 60: conectar Point Io a Red Devicenet

Index

Lladder logic

use to test 1734-OB4E output module 53-58Logix5000 controllers

prerequisite tasks 6-7quick starts 8

Mmount

1734-ADN adapter 15-161734-OB4E output module 171794-PS3 power supply 18

Nnode address

set on 1734-ADN DeviceNet adapter 15set on 1769-SDN scanner module 27-29

PPOINT I/O

DeviceNet adapter 11, 14mounting base 11, 14output module 11, 14removable terminal block 11, 14

power supplyFLEX I/O 11, 14

prerequisite tasks 6-7

Qquick starts

for devices in other Logix5000 control systems 8

Rrequirements

prerequisite tasks 6-7software 10

RSLogix 5000 software 7add DeviceNet adapter and output module

47-58add ladder logic 53-58requirements 10use DeviceNet Tag Generator 50-52

RSNetWorx for DeviceNet software 7, 21-45configuration file 30-33configure network subnet 36-41configure scanlist 41-45edit 1734-ADN adapter parameters 34-35register an EDS file 24-26requirements 10set node address on 1769-SDN scanner

module 27-29

Ssoftware

DeviceNet configuration file 30-33DeviceNet Tag Generator 10, 50-52register an EDS file in RSNetWorx for

DeviceNet 24-26requirements 10RSLogix 5000 7, 10

add DeviceNet adapter and output module 47-58

add ladder logic 53-58RSNetWorx for DeviceNet 7, 10, 21-45

configure scanlist 41-45configure subnet 36-41edit 1734-ADN adapter’s parameters

34-35

Ttasks

prerequisite tasks 6-7

60 Rockwell Automation Publication IASIMP-QS026A-EN-P - July 2012

Page 61: conectar Point Io a Red Devicenet
Page 62: conectar Point Io a Red Devicenet

Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400

Publication IASIMP-QS026A-EN-P - July 2012Copyright © 2012 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

Rockwell Automation Support

Rockwell Automation provides technical information on the Web to assist you in using its products. At http://www.rockwellautomation.com/support/, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.

For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit http://www.rockwellautomation.com/support/.

Installation Assistance

If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.

New Product Satisfaction Return

Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.

Documentation Feedback

Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.

United States or Canada 1.440.646.3434

Outside United States or Canada Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.

United States Contact your distributor. You must provide a Customer Support case number (call the phone number above to obtain one) to your distributor to complete the return process.

Outside United States Please contact your local Rockwell Automation representative for the return procedure.

Power, Control and Information Solutions HeadquartersAmericas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444

Europe/Middle East/Africa: Rockwell Automation NV, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640

Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846

www.rockwel lautomation.com


Recommended