1 DER Growth: Load Forecast & Customer Data Appendix E
Transcript
Page 1: DER Growth: Customer Data Appendix E

1

DER Growth: Load Forecast & Customer DataAppendix E

Page 2: DER Growth: Customer Data Appendix E

CORCORAN RFOAlpaugh New Feeder

Page 3: DER Growth: Customer Data Appendix E

3

Corcoran Bank and Feeders Location Overview

• Equipment: Corcoran Bank 3 – Feeders 1112, 1116, and 1118

• Electrical Service:

• 3-phase, 30 MVA bank with three 12.47 kV feeders

Location

Corcoran substation Bank 3, Kings County

All data depicted in thisapplication is for PG&Einternal use only.Dissemination to any entityoutside of PG&E requires theapproval of Corporate Security.

Corcoran

Page 4: DER Growth: Customer Data Appendix E

4

Technical and Operational Requirements

• A combined need of at least 4.4 MW across Corcoran feeders 1112, 1116, and 1118 is required• At least 2.3 MW of the 4.4 MW must be sourced at Corcoran feeder 1112

Page 5: DER Growth: Customer Data Appendix E

5

Corcoran Bank 3 (Feeders 1112, 1116, 1118)

Technical and Operational Requirements

Facility Rating = 29.7 MW

4.4 MW

Page 6: DER Growth: Customer Data Appendix E

6

Corcoran 1112

Technical and Operational Requirements

Facility Rating = 11.8 MW

2.3 MW

Page 7: DER Growth: Customer Data Appendix E

7

Corcoran 1116

Technical and Operational Requirements

0.5MW

Page 8: DER Growth: Customer Data Appendix E

8

Corcoran 1118

Technical and Operational Requirements

0

2

4

6

8

10

12

14

0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Load

(M

W)

Hour

Hourly Load Forecast - Peak Year (2028)

May June July August September October Facility Rating

1.1 MW

Page 9: DER Growth: Customer Data Appendix E

9

Customer Composition Served by

Corcoran Feeder 1112

Customer Class Total Customer Count Peak Day Demand (MW)

Residential 2,458 5.14

Commercial/ Industrial 146 1.09

Agricultural 46 2.84

Other 0 0.00

Total 2650 9.07

Page 10: DER Growth: Customer Data Appendix E

10

Load by Customer Class – Corcoran 1112

(Peak Load Day – July 19th 2018)

Page 11: DER Growth: Customer Data Appendix E

11

Customer Composition Served by

Corcoran Feeder 1116

Customer Class Total Customer Count Peak Day Demand (MW)

Residential 241 0.44

Commercial/ Industrial 49 0.85

Agricultural 128 5.6

Other 0 0.00

Total 418 6.89

Page 12: DER Growth: Customer Data Appendix E

12

Load by Customer Class – Corcoran 1116

(Peak Load Day – July 19th 2018)

Page 13: DER Growth: Customer Data Appendix E

13

Customer Composition Served by

Corcoran Feeder 1118

Customer Class Total Customer Count Peak Day Demand (MW)

Residential 163 0.4

Commercial/ Industrial 42 1.25

Agricultural 212 6.63

Other 0 0.00

Total 417 8.28

Page 14: DER Growth: Customer Data Appendix E

14

Load by Customer Class – Corcoran 1118

(Peak Load Day – July 19th 2018)

Page 15: DER Growth: Customer Data Appendix E

15

Corcoran 1112 DER Overview

Page 16: DER Growth: Customer Data Appendix E

16

Corcoran 1116 DER Overview

Page 17: DER Growth: Customer Data Appendix E

17

Corcoran 1118 DER Overview