Advanced synchro parallel genset controller with internal load sharing, synchronizer and PLC functions DST4602Evolution DST4602Evolution Datasheet_EN_REV_1.8
Transcript
Page 1: DST4602Evolution - TTTT Global

Advanced synchro parallel genset controller with internal load sharing, synchronizer and PLC functions

DST4602Evolution

DST4602Evolution Datasheet_EN_REV_1.8

Page 2: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

DESCRIPTION

DST4602Evolution is the top-level device among SICES controllers.

It is an highly configurable genset controller for advanced and complex parallel applications, where a huge number of settings are required (functions and parameters) for the genset management, and its auxiliary circuits.DST4602Evolution allows to connect up to 24 gensets on the same bus, working in island mode and in parallel with the mains.

Thanks to the controller’s high configurable level and built-in PLC functions (with PID blocks), DST4602Evolution can be used for CHP power plants equipped with Gas, Diesel, Biofuel and Dual fuel Engine.The controller also features fully integrated Air-Fuel Ratio (AFR) control, furthering its ability for such applications.

DST4602Evolution is fully equipped with internal Load Sharing, Synchronizer and W and VAR regulation. This controller includes a CAN J1939 interface, supporting a wide range of engines (Volvo Penta, Scania, Perkins, MTU, Deutz, Cummins, John Deere, Caterpillar and others). It can be also used with traditional engines, where measurements and control are performed by the embedded analogue interfaces.

DST4602Evolution can be used together with all Sices genset controllers (GC600, GC400). In case of multiple gensets in parallel with the mains where the reverse synchronization is required, DST4602Evolution can be interfaced with the Sices mains controllers (MC200, MC400), to avoid in this way any further blackouts on the loads.

The controller’s configurable parameters make standard and customized tasks easy to manage.All the parameters can be set directly by the controller’s keyboard or, alternatively using the free software tool (BoardPRG3), available from SICES’ website.It is also available a free PLC software editor, (SicesPlcEditor) to set the PLC logics.

The enhanced and large 7” graphic colour display with TFT technology, is a user-friendly interface, conceived for a quick and easy visualization of measures and alarms coming from the genset.

This controller stores events and periodical data in the internal memory, this information can be read from the front panel display.

DST4602Evolution provides several communications interfaces for local or remote control.

In case of complex applications, like Oil&Gas stations, the inbuilt protections can be expanded by using the external protection relay D-PRO.

Page 3: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

USB port16 Calendars

RS485 PLC Logic control Ethernet connection

20 Digital inputs 16 Digital output

AND/OR Logic control

5 Analogue inputs 2 Analogue outputs

Event history log

RS232

TIER4 final STAGE V

Air fuel ratio

INPUTS - OUTPUTS AND AUXILIARY FUNCTIONS

• N. 20 opto-insulated digital Inputs.• N. 5 analogue inputs including oil pressure, oil temperature, coolant temperature,

fuel level (2 voltage inputs, 3 resistive inputs, all can be used as digital).• N. 2 insulated analogue outputs for the regulation of frequency and voltage.• N. 16 digital outputs.

Communication:N.2 MODBUS RTU Serial Ports: RS232 and insulated RS485.

N.1 Ethernet Port 10/100Mbps.

N.1 USB FUNCTION for the configuration.

• Internal clock with history log.• Front protection degree: IP65 with gasket always included for free.

Page 4: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

OPERATION MODE

OFF/RESETEngine start not allowed; load is forced to be supplied from the Mains.

When the engine is running and the operating mode is turned to ‘OFF/RESET’, the engine shutdown sequence is activated.

Reset of all alarms.

Parameters change allowed (programming).

PROGRAMAccess to all programmable parameters.

Programming access can be controlled by means of three level passwords.

Some parameters can be changed even if the engine is running.

MANUALEngine manual START and STOP controls are enabled.

The genset protections are activated.

The starting command is automatically disabled when the engine is running.

MCB and GCB pushbuttons are enabled when generator is in operating range.

Their function depends on the selected application.

Manual synchronization can be easily accomplished by built-in function.

AUTOMATIC

The operating sequence depends on the selected application:

Single Prime Mover, Stand-by, Stand-by and Short Time Parallel, Single Parallel to Mains, Multiple Prime Mover, Multiple

Parallel to Mains.

TESTAutomatic start for testing operations with safety protections enabled.

Test can be made unloaded, loaded or in parallel to mains.

Upon mains failure, the load is immediately supplied by the genset.

PARALLEL APPLICATIONS

Parallel to mains application is allowed by the internal power regulator. Soft loading and unloading is automatically

performed. The most common Loss Of Mains protection are embedded.

Multiple prime mover application is allowed by means of CAN interface that allows load sharing.

Synchronization is done through an internal digital synchronizer, avoiding expensive external synchronizers.

Page 5: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

MAIN FEATURES > Digital UP/DOWN commands for speed governor and AVR.

> Mains and Genset circuit breaker management.

> True RMS readings on generator and mains voltages and on generator currents,

with an additional current measurement for neutral or differential protection.

> Active, reactive and apparent power measurements.

> Frequency and power measurements on mains input.

> 20 fully programmable digital inputs with possibility of additional several inputs.

> 16 fully programmable digital outputs with possibility of additional several

outputs.

> Several communication tools (RS232, Insulated RS485, RJ45 Ethernet, USB port).

> Large TFT graphic coloured display 7’’ 800x480 pixel.

> Real Time Clock, events and data recording.

> Remote control systems.

> KEMA Certification - Guideline BDEW (DE).

DYNAMIC SUPPORT OF THE GRID

The dynamic support to the grid is available: automatic adjustment of the active power output based on the mains

frequency value. This feature allows the genset to support the grid in case of over/under production.

> Operating mode selection (available in two versions):

• with selector key,

• with two dedicated push buttons.

> Engine START and STOP pushbutton.

> GCB and MCB command using push buttons.

> ACK/MODE (acoustic alarm silencing and other aux. functions).

> Four ARROW keys for LCD display selection mode, window selection, parameter change and

other.

> EXIT, ENTER and SHIFT keys.

> LCD CONTRAST DECREASE/INCREASE.

CONTROLS

Page 6: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1.True RMS measurement.Lx-N max. voltage < 300Vac cat. IV.Max. measurable voltage = 50.000V (by external VT).

L1, L2, L3, N (*).True RMS measurement.Nominal max. current: 5Aac, 1Aac.Overload measurable current: 4 x 5Aac (sinusoidal).Internal current transformers.Max. nominal current = 6000A (by external CT).(*) Neutral generator current measure or, in alternative used for the measure of the power on the mains.

L1-N, L2-N, L3-N, L1-L2, L2-L3, L3-L1.True RMS measurement.Lx-N max. voltage < 300Vac cat. IV.Max. measurable voltage = 50.000V (by external VT).

Resolution = 0.1 Hz. Accuracy = ±50ppm, ±35ppm/°C (typical).

Resolution = 0.1V.

Configurable curve based on sensors available.

Configurable curve based on sensors available.

Configurable curve based on sensors available.

By pick-up.Programmable teeth number.Same input can be used by W signal.

Active power: total and phase by phase.Reactive power: total and phase by phase.Apparent power: total and phase by phase.Power factor: total and phase by phase.Active and reactive energy counter.Hours counter for maintenance/rental.Start Counter.

Generator voltages:

Generator currents:

Mains voltages:

Generator and mains frequency meter:

Battery voltmeter:

Oil pressure gauge:

Coolant or Oil Thermometer:

Fuel level:

Engine revolution counter:

Derived values:

MEASURES

Power and currents peak values are stored with date and time.Additional engine analogue measures are available in case of engines with CANBUS J1939 interface.

Page 7: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

• Undervoltage (27).• Overvoltage (59).• Underfrequency (81U).• Overfrequency (81O) .• Voltage unbalance (47).• Phase sequence (47).

• Rate of Change of Frequency (81R ROCOF).• Vector shift.• Undervoltage (27).• Overvoltage (59).• Underfrequency (81U).• Overfrequency (81O).

• Max power. Underfrequency (81U).• Overfrequency (81O).• Undervoltage (27).• Overvoltage (59).• Power direction (32).• Loss of excitation (Reverse reactive 40).• Time dependent overcurrent (51) IDMT.• Instantaneous overcurrent (50).• Phase overcurrent with voltage restraint/control (50V/51V).• Synchro-check (25).• Phase sequence (47).• Current and Voltage unbalance (46/47).• Ground Fault Protection (64) as alternative to neutral protection (50N).• Negative sequence (I2).

Possibility to extend the protections of the controller using SICES Protection Relay D-PRO.

• Overspeed (12).• Incomplete sequence (48).• Belt-break.• Coolant and lube oil temperature warning and alarm.• Lube oil pressure warning and alarm.• Max. power.• Fuel level.• Emergency stop.

AMF Mains protections

Loss Of Mains (LOM) protections

Generator protections

Engine protections

PROTECTIONS

Page 8: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

GENERAL FUNCTIONS

> Hour, minute, second, day, month, year (leap year), day of week. > Rechargeable Lithium battery available as standard. > Genset operation can be enabled based on days of the week and time. > Test operation can be enabled based on days of the week. > Date and time can be remotely adjusted by software.

> Up to 860 record based on the configuration.

> Up to 860 record based on the configuration.

> The controller manages a fuel pump by means an external power relays and by 5 input level signals, or by the analogue measurement.

> Auto or manual operating modes.

> The controller can issue a warning when the running hours for maintenance are elapsed. Three timers are available for this task.

> The controller can issue a warning when controller temperature is approaching a specified temperature.

> Internal alarm horn make easier panel assembling.

Real time clock calendar

Periodical data recording

On event data recording

Fuel pump

Maintenance warning

Controller temperature warning

Internal alarm horn

COMMUNICATIONS

• N..1 Serial port RS232 with MODBUS RTU protocol.• N..1 Serial port RS232 or insulated RS485 with MODBUS RTU protocol.• N..1 USB port for firmware upgrade. • N..1 USB port with MODBUS RTU protocol.• N..1 Ethernet port with Modbus TCP protocol

• Direct GSM and PSTN modem management.• Automatic call or SMS in case of event.

• Modem GSM.• REWIND - Module interface for SIMONE using GPRS/GSM and GPS technology.• DANCE - Module interface for SIMONE using Ethernet technology.• Supervision software SicesSupervisor3 and SIMONE.

DST4602Evolution

As option

Page 9: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

TECHNICAL DATA > Supply voltage: 8…33 Vdc. > Power consumption: less than 7W (+5W for display lamp) typically. > Rated Genset frequency: 50 or 60 Hz. > Digital Input: opto-insulated. > Static outputs: 500mA @ 25°C, 360mA @ 50 °C, 20 Apk. > Relay outputs: 10A nominal. > Auxiliary relays outputs: 1/2,5/4A 30V. > Weight: 1,6kg. > Overall dimension: 260 (W) x 202 (H) x 86 (D) mm. > Panel cut-out: 240 (W) x 172 (H) mm. > Panel mounting: by means of stud-bolt. > Protection Grade: IP54 (front panel, by means of additional keylock protective

cap and gasket). > EMC: compliant with EN61326-1. > Safety: built in compliance with EN61010-1.

Display Features > DST4602Evolution 800x480 Pixel TFT, 7’’ Colour display. > Overall dimension: 155(L) x 93(H) mm. > Operating temperature: -20 °C to 60 °C. > Stock temperature: -30 °C to 80 °C.

LOAD MANAGEMENT In case of plants with several gensets connected in parallel on the same bus, it is possible to set different automatic logics for start/stop gensets, based on the load request.

> Manual setting of the master genset by means of selector switch on the control panel.

> Automatic rotation of the Master genset after a fixed time per day. > Automatic rotation of the Master genset after an elapsed time. > Automatic selection of working gensets having a matching power with the

request on load (*). > Running hours equalizations.

(*) Functions available for a max of 5 gensets.

Power regulation is allowed through internal power regulator.For electronic engines, a CAN line is available for speed regulation.For traditional engines is available a proper analogue interface.

DST4602Evolution controls AVR directly in order to manage the reactive power.

DST4602Evolution is a multilanguage device. The display languages available are: English, Italian, French, German, Spanish, Russian, Albanian, Greek, Polish and Brazilian Portuguese.

In detail

Active power modulation

Reactive power regulation

DST4602EvolutionIs equipped with a dual processor for improved response.One processor is aimed for the measures and operation sequences.The other one is aimed for the human interface(display).

Page 10: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

FAST PARALLELING SYSTEM (Dead bus paralleling)

DST4602Evolution has a built-in innovative and automatic start sequence, that allows to achieve a fast paralleling of several gensets in a maximum time of 9 - 15 sec. (it depends on the alternators and engines features).

The advanced system so called “Fast Paralleling” or “Dead Bus Paralleling”, is an effective solution for those sensitive stations where any mains failure, even for a few seconds, could cause huge problems to people and data security, by creating damages during the production processes (banks, hospitals, data centres, etc…).

Using the Fast Paralleling feature, gensets are switched on, synchronized and ready to supply the loads in a few seconds from the mains failure signal.

HOW IT WORKS

In case of a mains failure, Sices genset control panel gets a signal from the existing ATS (it may be ATS115, MC200 or MC400) to start the gensets.

The implemented logic in DST4602Evolution controls the gensets status, checking which of them are ready and available to start taking the load.

The gensets start working together with the relevant circuit breakers (GCB) already closed.By means of a safety and proper control of speed ramp and excitation range, gensets are simultaneously brought to the rated conditions.

All gensets are, therefore, ready and in parallel in 9-15 seconds max. (it depends on the engines and alternator types).The load is supplied by all gensets running in parallel.

If some gensets won’t start at first attempt, the control logic opens the relevant circuit breaker.The other gensets carry on with the fast-starting operations.The genset that has reached the rated conditions with delay, can be inserted afterwards, making the usual synchronization operations.

Page 11: DST4602Evolution - TTTT Global
Page 12: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

ADDITIONAL REMOTE DISPLAY

For each local DST4602Evolution it is possible to add one or more remote displays, called DST4602Remote.

This solution is usually recommended in case of remote-control room where the genset monitoring is required.It is possible to connect up to 4 remote displays to a single DST4602Evolution controller.

• Via RS485 Modbus RTU (max 800mt).• Via ethernet TCP/IP (max. distance 100mt without any hub).

If via ethernet, it is possible to connect several DST4602Remote to one local controller.

DST4602Remote is equipped with a powerful 7’’ colour graphic display TFT - 800x480 pixel.

• Command disabled: no operation is allowed.• Command enabled: all operations are allowed.• Remote reset: reset of alarms/warnings.

REMOTE START: starting is enabled if the operating mode of the local controller is in AUTO.REMOTE STOP: used to remotely stop the genset.• If the genset has been started by the DST4602Remote, the “REMOTE STOP”

stops the genset with the cooling operations.• If the genset has been started by the local DST4602, the “REMOTE STOP” stops

the genset immediately without any cooling operations.GCB: for manual opening/closure of the Genset Circuit Breaker.

System safety can be increased with a dedicated password, on both local and remote controller.

Connection between DST4602Remote and

DST4602Evolution

Graphic display

Key selector controls

Push buttons

Security

Page 13: DST4602Evolution - TTTT Global

DST4602evo Datasheet_EN

REDUNDANT CONTROLLER FUNCTION

DST4602 Compact

Power generator

DST4602 Compact(BACK-UP)

MONITORINGSYSTEM

In sensitive contests, it is necessary to ensure a safe control of the genset.Basically, a reliable control is achieved using a “Master unit” which is able to control the genset, combined to a “Back-up unit”. The “Master unit” is equipped with a self-diagnostic system (watch dog), able to detect any failure of the controller.After an elapsed and settable time, the “Back-up unit” automatically switches on, taking responsibility of controlling the genset.

When the “Master unit” is ON, the “Back-up unit” is OFF and vice-versa.In this way, there is no command failures risks between the controllers.The redundancy available is defined “warm type”, taking consideration that 6-7 seconds are required before the “Back-up unit” is activated.It is possible to configure the redundancy of the controllers as follows.For each genset:A) 2 x DST4602 compact,B) 2 x DST4602 SCM + N.1 DST4602 HMI (display).

With the case b) there is one common display (DST4602 HMI) and the backup is done on DST4602 SCM (the internal box).

Power generator

DST4602 SCMT (MASTER)

DST4602 SCMT (BACK-UP)

DST4602 Compact(BACK-UP)

MONITORINGSYSTEM

DST4602Evolution - HMI

Page 14: DST4602Evolution - TTTT Global

1 2

OFFONON

OFF

10mA

+ 20mA

OFF ONON

OFF

SET CURRENTLOOP

N.A.

0..1k 0..1k

20mA

J9

AVR

VO

LTA

GE

SP

EE

D G

OV

ER

NO

R

1 2

OFFONON

OFF

10mA

+ 20mA

OFF ONON

OFF

SET CURRENTLOOP

OFF

SE

T

N.A.

20mA

J11J14 J15

AN

. OU

TPU

T 1

AN

. OU

TPU

T 2

SW1 SW1ON

SW2 SW2ON

J12 J13

J10 SW

4

ON

J17

SW

3ON

P1

J26 1

2

OFF

ON

OFF

OFF

RS

232(

J16)

FW U

PG

RA

DE

NO

RM

AL

ON

ON

ON

OFF

OP

ER

ATIO

N

RE

SE

RV

ED

US

B (

J9)

FW

UP

GR

.

SW

3

12

STA

ND

AR

D

AN

ALO

GIN

PU

TS

SP

EC

IAL

AN.INPUT 3

AN.INPUT 4

OFF

OFF

ON

ON

SW

4

±±

±± + -+ -

1 2 1 2 1 2 1 2

1 2 3

S1ON OFF

120R

1 2 3 1 2 3

12

12

FW U

PGR

ADE

2 3 41+C.L

.

n.c.

n.c.

-C.L

.

+ -

2 3 41+C.L

.

-C.L

.VTR1

TR1

TR2

TR2

TR4

TR4

TR3

TR3

I I

+ -

+-

2 3 41+C.L

.

-C.L

.

+ -

2 3 41+C

.L.

-C.L

.V+ -

+-

RS 232 INTERFACE

+BAT

T.

GN

D1 2 1 2 3 4 5 6

L1 L2 L3 N

J20SUPPLY

J16

CURRENT INPUTSC.T.1 ÷ C.T.3 J21 J23

1 2 3 4 5 8 96 7 2 3 4 5 61 1 2 3 4 5

4A/30V

54 621 3

J1 J2 J3 J5 J6J4 1A/30VMAX OUTPUT

USB 2.0Slave

CAN_0(ANALOGINPUTS 1..2)

ECU

INTE

RFA

CE

DIGITALINPUTS 1..9

DIGITALINPUTS 10..15

DIGITALINPUTS 16..20

DIGITAL OUTPUTS 15..16MAX OUTPUT 4A/250VAC

DIGITAL OUTPUTS 1..6

1 2 3 4 5 6 7 1 2 3 4 5

1 2 3 4 5

S5ON OFF

120RS4RS232 RS485

ANALOGINPUTS 6

1 2

CURRENT INPUTC.T.4

L1 L2 L3 N

J24

L11

L22

L33

N4

100V INPUT

L11

L22

L33

N4

100V INPUTJ18 J19

1 2

TOROID INPUT

CAN_1PMCBUS

S2ON OFF

120R

CAN_2EXBUS

S3ON OFF

120R

COM2

RS232/485ISOLATEDINTERFACE

1 2 3 4

J22

HMI SERIAL INTERFACE

J27

123456789

1

2

3

4

5

6

7

8

DIG

ITA

L O

UTP

UTS

7..1

4

SCM VERSION ONLY

(RS 422)

8

C.T

.4

CO

MC

.T.4

AN

ALO

G IN

PUTS

4A/30V

GENERATOR VOLTAGE

DST4602 Evolution

BUS/MAINS VOLTAGE

MA

X O

UTP

UT

350m

A/4

0V@

50°C

J7

n.c.

n.c.

J8

1 2 3 4 1 2 3 4

SW

5 ON

12

12 OFF

ON

OFF

OFF

NO

RM

AL

ON

OFF

OP

ER

ATIO

N

RE

SE

RV

ED

US

B (

J28)

FW

U

PG

R.

SW

5- D

ISP

LAY

OFF

SE

T

J9

J10

J11

J12

J13

J14

J15

J17J22

J25AJ25B

+C.L.

-C.L.

+-

+C.L.

V

-C.L.

+-

+-

+C.L.

-C.L.

II

+-

+C.L.

V

-C.L.

+-

+-

NO OUT. 16COM OUT. 16

NC OUT. 16

NC OUT. 15

COM OUT. 15NO OUT. 15 1

2345

J4

89

67

IN 1IN 2IN 3IN 4IN 5IN 6

OUTPUT 3OUTPUT 4

OUTPUT 5OUTPUT 6

COMMONPLUS

IN 7

J1

J2

J3J5

IN 8IN 9

IN 10IN 11IN 12IN 13IN 14IN 15

OUTPUT 1OUTPUT 2D

IGIT

AL

INPU

TS 1

..9

DIG

ITA

L O

UTP

UTS

15.

.16

(MC

B)

DIG

ITA

LIN

PUTS

10.

.15

EXC. D+ 12VEXC D+ 24V

RESERVED(D+ IN)

D+ BATT.CHARG.ALTERN.

AN. INPUT 6

J6

DIG

ITA

L O

UTP

UTS

1..6

(SPEED GOVERNOR)

J7

1

2

34

1

2

34

ANALOGOUTPUT 2

(AVR VOLTAGE) J8

1

2

34

1

2

34

ANALOGOUTPUT 1

USB

2.0

Func

tion

(OPTIONAL) (RS

422

)

HM

I SER

IAL

INTE

RFA

CE

123

CAN_H

N.C.CAN_L

CAN_0

(ECU INTERF.)

123

CAN_HN.C.CAN_L

CAN_1

(PMCBUS)

123

CAN_HN.C.CAN_L

CAN_2

(EX_BUS)

1234

A/RXB/TXGNDDTR

COM2(RS232/485ISOLATEDINTERFACE)

1234

AN. INPUT 1(0..10V)REF. IN 1(GND)AN. INPUT 2(0..5V)REF. IN 2(GND)

5 REF. OUT 5VAN. INPUTS 1..2

AN. INPUT 3

ANALOG. REF.

PICK-UP IN/WPICK-UP IN RTN

RESERVED

GUARD EARTH

J27

J28AJ28B

AN

ALO

G IN

PUTS

USB 2.0 Host

TOROID INPUT

12

123456789

(OIL PRESSURE)AN. INPUT 4(COOLANT TEMP.)AN. INPUT 5(FUEL LEVEL)

ININ RTN

CURRENTC.T.4

12

J26

DIG

ITA

L ST

ATIC

OU

TPU

TS 7

..14

C.T.4

10/100Mb/s

COM C.T.4

123456

12345678

OUT. 7OUT. 8

123456

OUT. 9

OUT. 10OUT. 11OUT. 12

OUT. 13

OUT. 14

GND

IN 16IN 17IN 18IN 19IN 20

12345 D

IGIT

AL

INPU

T 16

..20

123

45

67

12345

COMPUTERINTERFACE

RS 232J16

123

L1L2L3

4 N GEN

ERAT

OR

VOLT

AG

E(4

00V)

J23

123

L1L2L3

4 N BU

S/M

AIN

SVO

LTA

GE

(400

V)

J24

GENERATORVOLTAGE(100V)

J18

BU

S/M

AIN

SVO

LTA

GE

(100

V)J1

9

123

L1L2L3

4 N

123

L1L2L3

4 N

1 GND2+BATTERY

J20SUPPLY

123456

C.T.1

C.T.1

C.T.2

C.T.2

C.T.3

C.T.3

J21

CU

RR

ENT

INPU

TSC

T1..C

T3

ETH

ERN

ET

(OPTIONAL)

(OP

TIO

NA

L)8

COMMON

MA

X O

UTP

UT

350m

A/4

0V@

50°C

J25A

/B

J28A

/BET

HER

NET

U S B 2. 0

RJ4

5U

SB A

Fem

ale

ON OFF

120RON OFF

120RON OFF

120R

10/1

00M

b/s

78,6mm [3.09”]

184m

m [7

.24”

]

76,6mm [3.09”]

90mm [3.54”]

260mm [10.24”]

160mm [6.29”]

202m

m [7

.95”

]

100% PROUDLY ITALIAN

S.I.C.E.S. SRLSocietà Italiana Costruzione

Elettriche Sumirago

Via Molinello 8B, 21040 Jerago con Orago (VA) Italy

Tel. +39 0331 212941Fax +39 0331 216102

[email protected]

sices.eu