+ All Categories
Home > Documents > EHC 500 MW

EHC 500 MW

Date post: 05-Apr-2018
Category:
Upload: sam
View: 271 times
Download: 6 times
Share this document with a friend

of 55

Transcript
  • 7/31/2019 EHC 500 MW

    1/55

    ELECTRO HYDRAULICCONTROLLER

    HEMANT KUMAR

  • 7/31/2019 EHC 500 MW

    2/55

    EHC Speed measurement

    Speed controller Load controller

    Pressure controller Controller Selection

    Position controller

  • 7/31/2019 EHC 500 MW

    3/55

    SPEED MEASUREMENT Four Nos of hall probes mounted around a

    disk containing 120 magnets (alternative60 N-pole & 60 S-pole)

    One rotation will produce 60 pulses.

    Three probes are used for measurement

    0.8 mm gap is maintained b/w hall probeand disc.

    Hall probe output is a sine wave with peakvoltage 700 to 800 mV.

  • 7/31/2019 EHC 500 MW

    4/55

    SPEED MEASUREMENT Pulse converters will convert the sine waves tosquare wave of peak 10 V.

    Each pulse converter card will generate three

    isolated output out of which two are used. Speed measurement is done in two different

    channels.

    Both channels will receive signal from each pulseconverters. One channel is used for indication andLVM & the other one for controller. nACT is shownin digital indicator provided in UCB

    range: (0- 3300 rpm)

  • 7/31/2019 EHC 500 MW

    5/55

    SPEED CONTROLLER SC is used for increasing speed from

    Barring speed to rated speed & to assist

    auto synchronizer in synchronizing the m/c. SC can be used to load the m/c fully but it

    is used only for loading upto 10% as

    frequency variation will affect the v/vopening.

    v/v opening is directly proportional to thediff. b/w grid freq and speed set point.

  • 7/31/2019 EHC 500 MW

    6/55

    SPEED CONTROLLER Speed set point

    Set point Tracking

    Speed set point controller

    Droop

    dn/dt monitoring No load pressure correction

    Speed controller loop.

  • 7/31/2019 EHC 500 MW

    7/55

    SPEED CONTROLLER

    Speedcontroller

    49

  • 7/31/2019 EHC 500 MW

    8/55

    Speed set point Speed reference nRCan be changed from

    desk, auto synchronizer, ATRS, C&I cabinet& AVR console.

    The set point changes at a gradient of2160 rpm/min up to a setting of 2820 rpm.

    After 2820 rpm it changes at a rate of

    360 rpm/min to have accurate control. Speed set point indicator is available in two

    ranges 1) 0-3300 rpm

    2) 2700-3300 rpm

  • 7/31/2019 EHC 500 MW

    9/55

    Set point Tracking If the frequency is between 49 Hz & 51 Hzand LC or PC in action speed set point willtrack grid speed by +15 rpm.

    This ensures that SC will not interfere innormal operation when frequency changes.

    After turbine trips speed set point will followthe actual m/c speed by -120 rpm.

    This ensures that speed set point is less thanactual speed (barring speed). So nxt timedurin rollin n has to be increased.

  • 7/31/2019 EHC 500 MW

    10/55

    Speed set point controller nRwhich is a step signal will beconverted to time delayed ramp signaln

    RTD

    or nRLIM

    by an integrator for whichgradient is decided by TSE upper margin.nRlim indicator is available in ucb(0-3300rpm)

    This has three parts

    1. Gradient

    2. Stop reference

    3. Fast balance

  • 7/31/2019 EHC 500 MW

    11/55

    Speed set point controller1.Gradient

    This is the rate at which the out put of SSPC

    changes. Max rate is set at 600 rpm/min.

    The rate also depends on TSE upper margin.

    If it is 30ok then rate is maximum. Ratereduces as margin comes below 300k linearly.Min rate is 108 rpm/min.

    This is to ensure minimum thermal stress

    during rolling.

  • 7/31/2019 EHC 500 MW

    12/55

    Speed set point controller2.Stop reference

    The output of the SSPC will be blocked

    under certain condition given below. Though nRcan be changed no change will

    be there in nRTD.

    The controller can be enabled again afterthe TSE influence is switched off and faultreset by C&I. Then made on and SPD set

    point release push button is pressed in UCB.

  • 7/31/2019 EHC 500 MW

    13/55

    Speed set point controllerStop reference logic

  • 7/31/2019 EHC 500 MW

    14/55

    3. Fast balance

    When the set point is in tracking mode

    (follow up mode) there will beinstantaneous change in nRTD valuefor a change in nR.

    The controller doesnt see the gradient inthis mode.

    Speed set point controller

  • 7/31/2019 EHC 500 MW

    15/55

    DroopAfter synchronization ifnR is increased

    then actual speed will not increase.Instead the control will open more.

    The droop is set at 5%. As the rated speedis 3000 rpm,5% is 150 rpm.

    The deviation of 150 rpm will correspond

    to full opening or full closing of control v/v(with the assumption that full opening ofCV will give full load at rated parameters).

  • 7/31/2019 EHC 500 MW

    16/55

    Droop

    Droop= %51003000

    30003150

    X

  • 7/31/2019 EHC 500 MW

    17/55

    dn/dt monitoring KWU turbine got critical speeds between

    700 rpm and 2850 rpm.

    It is not advisable to run turbine forprolonged time in this speed zone.

    For preventing low acceleration rate dn/dt

    monitoring is provided. When following conditions satisfy dn/dt

    monitoring actuates and will bring the speed

    to 600rpm.

  • 7/31/2019 EHC 500 MW

    18/55

    dn/dt monitoring nR is more than 600 rpm

    ESVs open

    G. bkr NOT ON

    nact less than 2850 rpm

    dn/dt less than 108 rpm/min SC in action

  • 7/31/2019 EHC 500 MW

    19/55

    No load pressure correctionAs the speed controller loop is PD(P)

    controller an error in input must be thereto keep the control V/Vs open.

    As the v/v opening required for runningm/c at rated speed is directly proportionalto steam pressure, a pressure dependent

    correction signal is give to the speedcontroller loop.

    Correction is approximately 20 rpm for

    100 bar.

  • 7/31/2019 EHC 500 MW

    20/55

  • 7/31/2019 EHC 500 MW

    21/55

    LOAD CONTROLLER Load controller is used to maintain load set

    by the operator or load dispatch center

    (optional) LC comes into action only after

    synchronization.

    LC is also responsible for taking care offrequency changes and correcting load iffrequency influence is ON.

    It is divided into following subsections.

  • 7/31/2019 EHC 500 MW

    22/55

    LOAD CONTROLLER Load set point

    Load set point controller

    Frequency influence

    Load limiter

    Actual load measurement Load controller loop

    Isolated grid

  • 7/31/2019 EHC 500 MW

    23/55

    LOAD CONTROLLER

    Loadcontroller

    TSE & loadgradient

    UCBATRS

    C&I panelCMC

    Stop fastbalance

    Load setPoint

    Controller

    Gradient

    PR

    PACT

    CMC ON

    PR

    LC output0 to +10V

    FI ON/OFF

    Frequencyinfluence

    MIN

    PRTD

    Loadlimiter

    +

    _

    droop

    nACT set freq(51Hz)

    PRf

    PRCMC

    Pressurecorrection

  • 7/31/2019 EHC 500 MW

    24/55

    Load set point

    Load set point can be changed from desk,C&I cabinet, ATRS & CMC

    Set point changes at a gradient of 250MW/min

    The gradient remains the same throughout

    the range Load set point PR,indicator is available UCB

    . range(0-600 MW).

  • 7/31/2019 EHC 500 MW

    25/55

    Load set point controller PRwhich is a step signal will be converted to

    time delayed ramp signal PRTD or PRLIM by

    an integrator for which gradient is decided byload gradient and TSE influence .

    PRLIM indicator is available in ucb (0-600MW)

    LSPC has three parts

    1. Load gradient and TSE influence

    2. Stop reference

  • 7/31/2019 EHC 500 MW

    26/55

    Load set point controller

    1) Load gradient and TSE influence

    Load gradient acts in parallel with TSE

    margin with a minimum selector. Load gradient range is 0-60 MW/min and

    can be set from UCB

    TSE margin 0-30

    0

    k corresponds to0 to 60 MW/min

    Both are having individual ON/OFF switch.The one which is ON will control the

    output.

  • 7/31/2019 EHC 500 MW

    27/55

    If both are OFF then PRTDchanges at a fixed rate of60 MW/min.

    If both are ON min of two will be selected for

    controlling the output. Load gradient setting is common for increasing as

    well as decreasing.

    But in case of TSE , upper margin controls theincreasing rate and lower margin controls thedecreasing rate.

    If TSE fault occurs, the gradient will be 30 MW/min(50%)

    Load set point controller

  • 7/31/2019 EHC 500 MW

    28/55

    Load set point controller

    2) Stop reference

    The PRTD will freeze on any of following conditions.

    i) TSE is ON and it develops fault. It can be resetby switching OFF TSE influence and fault resetby C&I. Then made ON and Load set point

    release push button is pressed in UCB.ii) Limit pressure reached AND PC in action AND

    Load set point raised.

    iii) Load set point controller disabled

  • 7/31/2019 EHC 500 MW

    29/55

    Load set point controller

    3) Fast balance

    In this mode output of LSPC, PRTD, will follo

    the actual load if any of the followingcondition exists

    i) generator breaker is OFF

    ii) Load controller OFFiii) Load shedding to less than station aux

    load AND MW error> 5%

  • 7/31/2019 EHC 500 MW

    30/55

    Load set point controller

    This ensures PRTD brought down to zeroafter GB opening.

    After synchronization PRTD tracks the actualload so that more time is not wasted inbringing PRTD from zero to working value

  • 7/31/2019 EHC 500 MW

    31/55

    Frequency influence Frequency influence is used to correct PRTD.

    The MW correction corresponding to frequency

    deviation is added to PRTD. FI has a droop of 5% (it can be changed 2.5%

    to 8.0% in steps of 0.5%). ie, a deviation of0.5 Hz will cause a load change of 100 MW.

    FI can be switched ON/OFF from UCB.

    UCB indicator for the correction signal is knownas PRf.(range:-200 to +200 MW).

    Pressure correction is similar as that of SC

  • 7/31/2019 EHC 500 MW

    32/55

    Load limiter Load limiter is used to limit the load to a

    certain value set by the operator. Load limitervalue is shown in UCB indicator.(range: 0-600 MW)

    Final set point (sum of PRTD & PRf )is fed to aminimum selector with the load limiter.

    As load limiter acts after PRTD it can be usedfor fast reduction of load in case ofemergency.

    Final set point after load limiter is know as PR

  • 7/31/2019 EHC 500 MW

    33/55

    Actual load measurement

    Three load transducers are used formeasurement.

    Actual load 0-600 MW corresponds to 4-20 mA.

    Median value of the three will be selected forprocessing.

    If any value drifts from the other value by morethan 5%, the selective card discards thedefective channel.

  • 7/31/2019 EHC 500 MW

    34/55

    Load controller loop

    Final control loop is a PI controller.

    error signal= PRPACT.

    Error is fed to a PI controller which producesan output of 0 to +10V which corresponds to0-600MW.

    LC has provision for two follow modesi) follow above

    ii) follow low

  • 7/31/2019 EHC 500 MW

    35/55

  • 7/31/2019 EHC 500 MW

    36/55

    Load controller loop

    Follow lowmode is present when the GB is ONand speed controller is still in action

    During this mode LC tracks the SC out put withan error of -150mV.

    The LC output can go more than SC output and

    hence LC can be taken into service. Due to this follow mode, the LC can be taken

    into service anytime without any delay after

    synchronization.

  • 7/31/2019 EHC 500 MW

    37/55

    Isolated grid

    Isolated grid operation will act If,

    i) PR Pact >10% (50MW) AND

    ii) frequency > 51 Hz AND

    iii) LC in action

    In this condition the controller will be changed to

    proportional (P) type for fast corrective action. This condition can be eliminated by adjusting

    load set point near to actual load and pressing

    the Isolated grid reset button in UCB desk.

  • 7/31/2019 EHC 500 MW

    38/55

    PRESSURE CONTROLLER Pressure controller maintains the throttle

    pressure within working range at all loads.

    Deviation= actual (PrAct) - set pressure (PrR) The operating range of deviation is 0 to+150mV

    As long as deviation is more than +150mV ,the PC output remains at max saturation(+12V).

    ie, for a deviation of 0 to+150mV, PC willproduce an output of 0 to+12V.

    PC has two modes of operation.

    PC is a PI controller

  • 7/31/2019 EHC 500 MW

    39/55

    PRESSURE CONTROLLER

    PrAct

    Pressurecontroller

    &

    PrR Limitpressureselected

    15ksc

    15ksc

    +

    +

    _

    Pr

    Limitpressure

    reached

    PC output0V to +12V

    +

    _

    Limitpressureselected

  • 7/31/2019 EHC 500 MW

    40/55

    PRESSURE CONTROLLER1)Initial pressure mode

    In initial pressure mode PC will try to

    maintain the throttle pressure. Any deviation in pressure will be adjusted

    by opening or closing the control v/v.

    2)Limit pressure mode

    In limit pressure mode boiler storagecapacity is utilized.

    There wont be any change in PC out put

    till Pr deviation becomes -15 ksc.

  • 7/31/2019 EHC 500 MW

    41/55

    PRESSURE CONTROLLER

    Once the throttle pressure falls below the setvalue (15 kgc) then further fall in pressure isprevented by varying the control v/v positionand hence load.

    p indicator is provided in UCB

    Range:(-30 to +30 kgc)

    Minimum EHC output is set at 30% to avoidcomplete closing of the control v/v whendeviation isve.

  • 7/31/2019 EHC 500 MW

    42/55

    PRESSURE CONTROLLER

    Initial pressure mode will be selected on following

    conditions.1. Boiler control on manual

    2. Turbine follow mode

    3. IP mode selected from console

    Limit pressure mode will be selected on followingconditions.

    1. Boiler follow mode

    2. CMC selected3. LP mode selected from console

  • 7/31/2019 EHC 500 MW

    43/55

    CONTROLLER SELECTION

    M

    A

    X

    A

    D

    D

    M

    I

    N

    M

    I

    N

    +10V

    SC out put

    -10V to +10V

    LC out put0V to +10V

    PC out put0V to +12V

  • 7/31/2019 EHC 500 MW

    44/55

    CONTROLLER SELECTION

    SC output is -10V to +10V for 0 to 150 rpm.

    LC out put is 0 to +10V for 0 to 600MW.

    PC output is 0V to +12V for 0 to +150mV. SC output and LC output passes through a MAX

    gate.

    The value selected is passed to MIN-I gate. Theother input to the MIN-I gate is the adder outputgot by adding 10V(100%) to SC output.

    The MIN-I output is fed to MIN-II gate for which

    the other input is PC output.

  • 7/31/2019 EHC 500 MW

    45/55

    CONTROLLER SELECTION

    The MIN-II gate out put is fed to the positioncontroller.

    Adder is provided to prevent over speeding ofthe turbo set.

    In normal condition SC output will be +1V as

    nR is tracking grid speed by 15 rpm. During over speeding, nRwill stop tracking at

    3060 rpm(51 Hz). At this point nRwill be

    3075 rpm.

  • 7/31/2019 EHC 500 MW

    46/55

    CONTROLLER SELECTION If frequency further increases at 51.25 Hz

    (3075 rpm) SC output will become 0V. From thispoint onwards SC output will beve for increase

    in frequency which will reduce adder output.

    Suppose if m/c is at 500MW (LC active), LC outputwill be 8.33 V. If adder output comes less than this

    value SC will become active and m/c will startunloading.

    At 53.75 Hz (3225 rpm) SC output will be -10Vand adder output will be 0V. ie, m/c will be fullyunloaded.

  • 7/31/2019 EHC 500 MW

    47/55

    POSITION CONTROLLER Position controller is a PID controller

    Error signal is generated by comparing the

    selection circuit output with the positionfeedback obtained from Collins transformer.

    There are two Collins transformers which givesoutput voltage corresponding to piston position.

    The output of the two Collins transformer passesthrough a MIN gate (logical max selector as itsout put isve) and the selected value is fed to

    the controller.

  • 7/31/2019 EHC 500 MW

    48/55

    POSITION CONTROLLER

  • 7/31/2019 EHC 500 MW

    49/55

    POSITION CONTROLLER

    Plunger coil is an integrator type.

    The balance position of the pilot v/v piston is

    achieved if -1.0V is fed to the plunger coil. For moving the piston in open direction the voltage

    has to be increased. Say -0.9V is fed to the coil,then piston will keep on moving towards openingdirection till the voltage again made -1.0V.

    Similarly if the voltage is made -1.1V, then thepiston will keep on moving towards closing

    direction till voltage is again brought back to -1V.

  • 7/31/2019 EHC 500 MW

    50/55

    POSITION CONTROLLERPlunger coil

  • 7/31/2019 EHC 500 MW

    51/55

    POSITION CONTROLLER

    Collins transformer is a differential transformerand produces output from -8.0V to +8.0V which

    is converted into 0.0 to -10.0V. 0.0V output corresponds to the position at which

    first control v/v just starts opening.

    -10.0V corresponds to the position at which lastcontrol v/v is just full open.

    A constant bias of +200mV is given for secondCollins txr so as to avoid frequent changeover

    from one Collins to the other.

  • 7/31/2019 EHC 500 MW

    52/55

    POSITION CONTROLLER

    If at any time the difference b/w the twoCollins exceeds 700mV a fault alarm isgenerated.

    There is provision to switch ON/OFF thevoltage supply to plunger coil. This can bedone only if the output of position controller

    is more than +5.0V. This ensures that at the time of switching

    OFF, the piston is full open and there will

    not any jump after switching OFF.

  • 7/31/2019 EHC 500 MW

    53/55

    POSITION CONTROLLER

    If at any time during operation plungercoil wire breaks, the piston will go to

    full open position and plunger coil faultalarm will be generated.

    As the piston goes to full open position,

    the control v/vs also will open fully.

  • 7/31/2019 EHC 500 MW

    54/55

    POSITION CONTROLLER

    EHC fault will occur on following condition1. Starting device faulty

    2.

    Collins-1 faulty3. Collins-2 faulty

    4. Plunger coil faulty

    5. nAct-1 ~ nAct-2 >5%

    6. Turbine tripped7. Power supply faulty

    8. EHC faulty

    9. Speed acquisition faulty

  • 7/31/2019 EHC 500 MW

    55/55


Recommended