iEM3100 series / iEM3200 series DOCA0005EN 04/2012 iEM3100 series / iEM3200 series Energy Meters User Manual 04/2012 DOCA0005EN-01 www.schneider-electric.com
Transcript
Page 1: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3100 series iEM3200 series

DOCA0005EN 042012

iEM3100 series iEM3200 seriesEnergy Meters User Manual

042012

DO

CA

0005

EN

-01

wwwschneider-electriccom

The information provided in this documentation contains general descriptions andor technical charactershyistics of the performance of the products contained herein This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications It is the duty of any such user or integrator to perform the appropriate and complete risk analysis evaluation and testing of the products with respect to the relevant specific application or use thereof Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein If you have any suggestions for improvements or amendments or have found errors in this publication please notify us

No part of this document may be reproduced in any form or by any means electronic or mechanical including photocopying without express written permission of Schneider Electric

All pertinent state regional and local safety regulations must be observed when installing and using this product For reasons of safety and to help ensure compliance with documented system data only the manufacturer should perform repairs to components

When devices are used for applications with technical safety requirements the relevant instructions must be followed

Failure to use Schneider Electric software or approved software with our hardware products may result in injury harm or improper operating results

Failure to observe this information can result in injury or equipment damage

copy 2012 Schneider Electric All rights reserved

DOCA0005EN 042012 2

Table of Contents

Safety Information 5About the Book 7

Chapter 1 Presentation 9Presentation 10Physical Description 11

Chapter 2 Installation 15Safety Measures 16Dimensions 17DIN Rail Mounting and Dismantling 18Connection 20Typical Applications 29

Chapter 3 Use 31Presentation 32Settings for all Energy Meters 34Modifying Parameters 35Clock Setting 36Configuration 37HMI Display 50

Chapter 4 Communication via Modbus RS-485 5341 Modbus Configuration 54

Configuration of RS-485 Communication Port 5442 Modbus Functions 55

Function List 56Table Format 57

43 Command Interface 58Presentation 59Command List 60

44 Modbus Register Table 65Register List 65

45 Read Device Identification 70Register List 70

Chapter 5 Technical Characteristics 71Specifications 71

Chapter 6 Maintenance and Troubleshooting 73Safety Precautions 74Troubleshooting 75

DOCA0005EN 042012 3

DOCA0005EN 042012 4

sect

Safety Information

Important Information

NOTICE

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTE

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation and has received safety training to recognize and avoid the hazards involved

DOCA0005EN 042012 5

DOCA0005EN 042012 6

About the Book

At a Glance

Document Scope

This manual is intended for use by designers system builders and maintenance technicians who are concerned with electrical distribution systems featuring monitoring devices

Validity Note

The energy meters are used to measure the amount of active energy consumed by an installation or a part of an installation

This function meets the requirements forz consumption monitoringz evaluation of energy items (cost accounting etc)

This function also satisfies the power-saving incentives implemented by many countries

Related Documents

Title of Documentation Reference Number

Instruction sheet iEM3100 iEM3110 iEM3115 S1B46581 S1B62907

Instruction sheet iEM3150 iEM3155 S1B46583 S1B62908

Instruction sheet iEM3200 iEM3210 iEM3215 S1B46598 S1B62910

Instruction sheet iEM3250 iEM3255 S1B46602 S1B62911

You can download these technical publications and other technical information from our website at wwwschneider-electriccom

User Comments

We welcome your comments about this document You can reach us by e-mail at techcommschneidershyelectriccom

DOCA0005EN 042012 7

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 2: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

The information provided in this documentation contains general descriptions andor technical charactershyistics of the performance of the products contained herein This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications It is the duty of any such user or integrator to perform the appropriate and complete risk analysis evaluation and testing of the products with respect to the relevant specific application or use thereof Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein If you have any suggestions for improvements or amendments or have found errors in this publication please notify us

No part of this document may be reproduced in any form or by any means electronic or mechanical including photocopying without express written permission of Schneider Electric

All pertinent state regional and local safety regulations must be observed when installing and using this product For reasons of safety and to help ensure compliance with documented system data only the manufacturer should perform repairs to components

When devices are used for applications with technical safety requirements the relevant instructions must be followed

Failure to use Schneider Electric software or approved software with our hardware products may result in injury harm or improper operating results

Failure to observe this information can result in injury or equipment damage

copy 2012 Schneider Electric All rights reserved

DOCA0005EN 042012 2

Table of Contents

Safety Information 5About the Book 7

Chapter 1 Presentation 9Presentation 10Physical Description 11

Chapter 2 Installation 15Safety Measures 16Dimensions 17DIN Rail Mounting and Dismantling 18Connection 20Typical Applications 29

Chapter 3 Use 31Presentation 32Settings for all Energy Meters 34Modifying Parameters 35Clock Setting 36Configuration 37HMI Display 50

Chapter 4 Communication via Modbus RS-485 5341 Modbus Configuration 54

Configuration of RS-485 Communication Port 5442 Modbus Functions 55

Function List 56Table Format 57

43 Command Interface 58Presentation 59Command List 60

44 Modbus Register Table 65Register List 65

45 Read Device Identification 70Register List 70

Chapter 5 Technical Characteristics 71Specifications 71

Chapter 6 Maintenance and Troubleshooting 73Safety Precautions 74Troubleshooting 75

DOCA0005EN 042012 3

DOCA0005EN 042012 4

sect

Safety Information

Important Information

NOTICE

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTE

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation and has received safety training to recognize and avoid the hazards involved

DOCA0005EN 042012 5

DOCA0005EN 042012 6

About the Book

At a Glance

Document Scope

This manual is intended for use by designers system builders and maintenance technicians who are concerned with electrical distribution systems featuring monitoring devices

Validity Note

The energy meters are used to measure the amount of active energy consumed by an installation or a part of an installation

This function meets the requirements forz consumption monitoringz evaluation of energy items (cost accounting etc)

This function also satisfies the power-saving incentives implemented by many countries

Related Documents

Title of Documentation Reference Number

Instruction sheet iEM3100 iEM3110 iEM3115 S1B46581 S1B62907

Instruction sheet iEM3150 iEM3155 S1B46583 S1B62908

Instruction sheet iEM3200 iEM3210 iEM3215 S1B46598 S1B62910

Instruction sheet iEM3250 iEM3255 S1B46602 S1B62911

You can download these technical publications and other technical information from our website at wwwschneider-electriccom

User Comments

We welcome your comments about this document You can reach us by e-mail at techcommschneidershyelectriccom

DOCA0005EN 042012 7

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 3: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Table of Contents

Safety Information 5About the Book 7

Chapter 1 Presentation 9Presentation 10Physical Description 11

Chapter 2 Installation 15Safety Measures 16Dimensions 17DIN Rail Mounting and Dismantling 18Connection 20Typical Applications 29

Chapter 3 Use 31Presentation 32Settings for all Energy Meters 34Modifying Parameters 35Clock Setting 36Configuration 37HMI Display 50

Chapter 4 Communication via Modbus RS-485 5341 Modbus Configuration 54

Configuration of RS-485 Communication Port 5442 Modbus Functions 55

Function List 56Table Format 57

43 Command Interface 58Presentation 59Command List 60

44 Modbus Register Table 65Register List 65

45 Read Device Identification 70Register List 70

Chapter 5 Technical Characteristics 71Specifications 71

Chapter 6 Maintenance and Troubleshooting 73Safety Precautions 74Troubleshooting 75

DOCA0005EN 042012 3

DOCA0005EN 042012 4

sect

Safety Information

Important Information

NOTICE

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTE

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation and has received safety training to recognize and avoid the hazards involved

DOCA0005EN 042012 5

DOCA0005EN 042012 6

About the Book

At a Glance

Document Scope

This manual is intended for use by designers system builders and maintenance technicians who are concerned with electrical distribution systems featuring monitoring devices

Validity Note

The energy meters are used to measure the amount of active energy consumed by an installation or a part of an installation

This function meets the requirements forz consumption monitoringz evaluation of energy items (cost accounting etc)

This function also satisfies the power-saving incentives implemented by many countries

Related Documents

Title of Documentation Reference Number

Instruction sheet iEM3100 iEM3110 iEM3115 S1B46581 S1B62907

Instruction sheet iEM3150 iEM3155 S1B46583 S1B62908

Instruction sheet iEM3200 iEM3210 iEM3215 S1B46598 S1B62910

Instruction sheet iEM3250 iEM3255 S1B46602 S1B62911

You can download these technical publications and other technical information from our website at wwwschneider-electriccom

User Comments

We welcome your comments about this document You can reach us by e-mail at techcommschneidershyelectriccom

DOCA0005EN 042012 7

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 4: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012 4

sect

Safety Information

Important Information

NOTICE

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTE

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation and has received safety training to recognize and avoid the hazards involved

DOCA0005EN 042012 5

DOCA0005EN 042012 6

About the Book

At a Glance

Document Scope

This manual is intended for use by designers system builders and maintenance technicians who are concerned with electrical distribution systems featuring monitoring devices

Validity Note

The energy meters are used to measure the amount of active energy consumed by an installation or a part of an installation

This function meets the requirements forz consumption monitoringz evaluation of energy items (cost accounting etc)

This function also satisfies the power-saving incentives implemented by many countries

Related Documents

Title of Documentation Reference Number

Instruction sheet iEM3100 iEM3110 iEM3115 S1B46581 S1B62907

Instruction sheet iEM3150 iEM3155 S1B46583 S1B62908

Instruction sheet iEM3200 iEM3210 iEM3215 S1B46598 S1B62910

Instruction sheet iEM3250 iEM3255 S1B46602 S1B62911

You can download these technical publications and other technical information from our website at wwwschneider-electriccom

User Comments

We welcome your comments about this document You can reach us by e-mail at techcommschneidershyelectriccom

DOCA0005EN 042012 7

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 5: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

sect

Safety Information

Important Information

NOTICE

Read these instructions carefully and look at the equipment to become familiar with the device before trying to install operate or maintain it The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure

PLEASE NOTE

Electrical equipment should be installed operated serviced and maintained only by qualified personnel No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material

A qualified person is one who has skills and knowledge related to the construction and operation of electrical equipment and its installation and has received safety training to recognize and avoid the hazards involved

DOCA0005EN 042012 5

DOCA0005EN 042012 6

About the Book

At a Glance

Document Scope

This manual is intended for use by designers system builders and maintenance technicians who are concerned with electrical distribution systems featuring monitoring devices

Validity Note

The energy meters are used to measure the amount of active energy consumed by an installation or a part of an installation

This function meets the requirements forz consumption monitoringz evaluation of energy items (cost accounting etc)

This function also satisfies the power-saving incentives implemented by many countries

Related Documents

Title of Documentation Reference Number

Instruction sheet iEM3100 iEM3110 iEM3115 S1B46581 S1B62907

Instruction sheet iEM3150 iEM3155 S1B46583 S1B62908

Instruction sheet iEM3200 iEM3210 iEM3215 S1B46598 S1B62910

Instruction sheet iEM3250 iEM3255 S1B46602 S1B62911

You can download these technical publications and other technical information from our website at wwwschneider-electriccom

User Comments

We welcome your comments about this document You can reach us by e-mail at techcommschneidershyelectriccom

DOCA0005EN 042012 7

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 6: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012 6

About the Book

At a Glance

Document Scope

This manual is intended for use by designers system builders and maintenance technicians who are concerned with electrical distribution systems featuring monitoring devices

Validity Note

The energy meters are used to measure the amount of active energy consumed by an installation or a part of an installation

This function meets the requirements forz consumption monitoringz evaluation of energy items (cost accounting etc)

This function also satisfies the power-saving incentives implemented by many countries

Related Documents

Title of Documentation Reference Number

Instruction sheet iEM3100 iEM3110 iEM3115 S1B46581 S1B62907

Instruction sheet iEM3150 iEM3155 S1B46583 S1B62908

Instruction sheet iEM3200 iEM3210 iEM3215 S1B46598 S1B62910

Instruction sheet iEM3250 iEM3255 S1B46602 S1B62911

You can download these technical publications and other technical information from our website at wwwschneider-electriccom

User Comments

We welcome your comments about this document You can reach us by e-mail at techcommschneidershyelectriccom

DOCA0005EN 042012 7

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 7: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

About the Book

At a Glance

Document Scope

This manual is intended for use by designers system builders and maintenance technicians who are concerned with electrical distribution systems featuring monitoring devices

Validity Note

The energy meters are used to measure the amount of active energy consumed by an installation or a part of an installation

This function meets the requirements forz consumption monitoringz evaluation of energy items (cost accounting etc)

This function also satisfies the power-saving incentives implemented by many countries

Related Documents

Title of Documentation Reference Number

Instruction sheet iEM3100 iEM3110 iEM3115 S1B46581 S1B62907

Instruction sheet iEM3150 iEM3155 S1B46583 S1B62908

Instruction sheet iEM3200 iEM3210 iEM3215 S1B46598 S1B62910

Instruction sheet iEM3250 iEM3255 S1B46602 S1B62911

You can download these technical publications and other technical information from our website at wwwschneider-electriccom

User Comments

We welcome your comments about this document You can reach us by e-mail at techcommschneidershyelectriccom

DOCA0005EN 042012 7

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 8: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012 8

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 9: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012

1

iEM3100 series iEM3200 series

Energy Meter Presentation

DOCA0005EN 042012

Presentation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 10

Physical Description 11

9

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 10: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Presentation

Presentation

Use of Energy Meters to Measure Electrical Systems

The energy meters provide combine accurate 3-phase energy measurement

The offer is composed of 10 commercial references described below

Functions of Energy Meters

The product functions of energy meters provide the essential measurement capabilities required to monitor an electrical installation such as current voltage and energy

The key features of energy meters arez measurements of active and reactive energiesz multi-tariffs (up to 4) controlled by internal clock digital inputs or communicationz MID compliant for many referencesz pulse outputsz display (currents voltage energies)z Modbus communication

Main Characteristics

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Direct measurement (up to 63 A)

radic radic radic radic radic ndash ndash ndash ndash ndash

Measurement inputs through CTs (1 A 5 A)

ndash ndash ndash ndash ndash radic radic radic radic radic

Measurement inputs through VTs

ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Active Energy measurements

radic radic radic radic radic radic radic radic radic radic

Four Quadrant Energy measurements

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Electrical measurements (I V P )

ndash ndash ndash radic radic ndash ndash ndash radic radic

Multi-tariff (internal clock)

ndash ndash 4 ndash 4 ndash ndash 4 ndash 4

Multi-tariff (controlled by digital inputs)

ndash ndash 4 ndash 2 ndash ndash 4 ndash 2

Measurement display

radic radic radic radic radic radic radic radic radic radic

Digital inputs ndash ndash 2 ndash 1 ndash ndash 2 ndash 1

Programmable digital outputs

ndash ndash ndash ndash 1 ndash ndash ndash ndash 1

Pulse output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Overload alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Modbus communication

ndash ndash ndash radic radic ndash ndash ndash radic radic

MID (legal metrology certification)

ndash radic radic ndash radic ndash radic radic ndash radic

Width (18 mm module in DIN Rail mounting)

5 5 5 5 5 5 5 5 5 5

DOCA0005EN 042012 10

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 11: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Presentation

Physical Description

iEM3100 iEM3110 iEM3115 - Direct Measurement up to 63 A

The various features of the listed energy meters (direct measurement up to 63 A) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3115)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3110)

4 Cancellation

5 Confirmation

6 Selection

7 Flashing yellow meter indicator (used to check the accuracy)

8 Green indicator onoff error

9 Current and voltage inputs (direct measurement up to 63 A)

10 Sealing points (three)

11 Sealable covers

DOCA0005EN 042012 11

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 12: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Presentation

iEM3150 iEM3155 - Direct Measurement up to 63 A and Modbus Communication

The various features of the listed energy meters (direct measurement up to 63 A with Modbus communication) are shown in the diagram below

1 Digital input (iEM3155)

2 Digital output (iEM3155)

3 Communication port

4 Flashing yellow indicator for active communication

5 Display for measurement and configuration

6 Cancellation

7 Confirmation

8 Selection

9 Flashing yellow meter indicator (used to check the accuracy)

10 Green indicator onoff error

11 Current and voltage inputs (direct measurement up to 63 A)

12 Sealing points (three)

13 Sealable covers

DOCA0005EN 042012 12

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 13: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Presentation

iEM3200 iEM3210 iEM3215 - Measurement With CTs

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3215)

2 Display for measurement and configuration

3 Pulse out for remote transfer (iEM3210)

4 Current inputs (CTs 1 A or 5 A)

5 Cancellation

6 Confirmation

7 Selection

8 Flashing yellow meter indicator (used to check the accuracy)

9 Green indicator onoff error

10 Voltage inputs

11 Sealing points (three)

12 Sealable covers

DOCA0005EN 042012 13

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 14: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Presentation

iEM3250 iEM3255 - Measurement With CTs and Modbus Communication

The various features of the listed energy meters (CTs 1 A or 5 A with Modbus communication) are shown in the diagram below

1 2 digital inputs for tariff control (iEM3255)

2 Digital output (iEM3255)

3 Communication port

4 Yellow indicator for communication diagnosis

5 Display for measurement and configuration

6 Current inputs (CTs 1 A and 5 A)

7 Cancellation

8 Confirmation

9 Selection

10 Flashing yellow meter indicator (used to check the accuracy)

11 Green indicator onoff error

12 Voltage inputs

13 Sealing points (three)

14 Sealable covers

DOCA0005EN 042012 14

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 15: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012

2

iEM3100 series iEM3200 series

Energy Meter Installation

DOCA0005EN 042012

Installation

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Measures 16

Dimensions 17

DIN Rail Mounting and Dismantling 18

Connection 20

Typical Applications 29

15

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 16: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Safety Measures

Specific Hazard Associated with Energy Meters

In the case of almost all electric and electronic devices the devicersquos power supply is the root cause of electrical hazards The hazard can be eliminated by disconnecting the power supply

Consequently this connection must be broken before carrying out any kind of work on the product

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Before carrying out work of any kind disconnect connection wires Disconnect all the power supplies running to the energy meter and the equipment on which it is installed

z Always use a correctly calibrated voltage tester to check that the power supply has been properly disconnected

Failure to follow these instructions will result in death or serious injury

Other Safety Measures

Carefully read through the safety measures described below You are always required to implement them fully before attempting to install repair or service electrical equipment

DANGER RISK OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions

z This equipment may only be installed by qualified electricians who have read all the relevant information

z NEVER work alone z Before performing visual inspections tests or maintenance on this equipment disconnect all

sources of electric power Assume that all circuits are live until they have been completely de-energized tested and tagged Pay particular attention to the design of the power system Consider all power supply sources particularly the potential for backfeed

z Before closing protective covers and doors carefully inspect the work area to ensure that no tools or objects have been left inside the equipment

z Take care when removing or replacing panels Take special care to ensure that they do not come into contact with live busbars To minimize the risk of injuries do not tamper with the panels

z The successful operation of this equipment depends upon proper handling installation and operation Failure to follow basic installation procedures can lead to personal injury as well as damage to electrical equipment or other property

z NEVER shunt an external fusecircuit breaker z The energy meters must be installed in a suitable electrical cabinet

Failure to follow these instructions will result in death or serious injury

DOCA0005EN 042012 16

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 17: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Dimensions

Dimensions of iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Dimensions of iEM3150 iEM3155 iEM3250 iEM3255

DOCA0005EN 042012 17

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 18: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

DIN Rail Mounting and Dismantling

Presentation

You can install the energy meter on a DIN rail The device must not be tilted following installation

When mounting the device on or dismantling it from a DIN rail you can keep the terminals wired up

DIN Rail Mounting

To install the energy meter on a DIN rail proceed as follows

Step Action

1 Position the 2 upper slots on the rear of the energy meter on the DIN rail

2 Press the device against the DIN rail until the locking mechanism engages The device is now attached to the rail

DOCA0005EN 042012 18

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 19: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Removal from a DIN rail

To remove the energy meter from a DIN rail proceed as follows

Step Action

1 Using a flat screwdriver (le65 mm) lower the locking mechanism to release the device

2 Lift the device up to free it from the DIN rail

DOCA0005EN 042012 19

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 20: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Connection

Overview

The diagrams below illustrate how to connect the energy meters to a single-phase or three-phase 3- or 4-wire power system

iEM31bullbull Associated With a Contactor

Connection requirements for iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 z When the energy meter is associated with a contactor connect the energy meter upstream of the

contactor z The energy meter must be protected by a circuit breaker

Connection Diagram of iEM3100 iEM3110 iEM3115

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3110 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

DOCA0005EN 042012 20

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 21: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Connection Diagram of iEM3150 iEM3155

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3155 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 21

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 22: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Wiring on Single Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH2W L-L z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH3W L-L-N z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

1PH4W multi L with N z iEM3150 z iEM3155

NOTICE RISK OF DAMAGE TO THE ENERGY METER

For 1PH4W multi L with N z Nrsquo must not be connected to the load z The current must not flow through the iEM315bull products Otherwise if In gt 63 A the energy meter

can blow up

Failure to follow these instructions can result in equipment damage

Wiring on Three-Phase Systems for Direct Measurement

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

3PH4W z iEM3100 z iEM3110 z iEM3115 z iEM3150 z iEM3155

DOCA0005EN 042012 22

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 23: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Connection Diagram of iEM3200 iEM3210 iEM3215

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The pulse output on the iEM3210 indicates the primary consumption with consideration of transformer

ratios z The pulse output on the iEM3210 can be directly connected to a 24 V DC (lt 30 V DC) input on a Zelio

or Twido PLC z For other concentrators if V DCRin gt 15 mA add a resistor Radd = (V DC001) - Rin Ω

Connection Diagram of iEM3250 iEM3255

NOTE The electrical wiring is explained in the table below

z The pulse output is compatible with S0 format z The digital output of iEM3255 is polarity-independent z The digital input and output are electrically independent

DOCA0005EN 042012 23

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 24: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Wiring on Single Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

1PH2W L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH2W L-L z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH3W L-L-N z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1PH4W multi L with N z iEM3250 z iEM3255

2 CTs

3 CTs

DOCA0005EN 042012 24

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 25: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Wiring on Three-Phase Systems with CTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs

3 CTs

DOCA0005EN 042012 25

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 26: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3200 z iEM3210 z iEM3215 z iEM3250 z iEM3255

1 CT (balanced)

2 CTs (for balanced 3-wire load)

3 CTs

DOCA0005EN 042012 26

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 27: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Wiring on Three-Phase Systems with CTs and VTs

Power System Energy Meter Energy Meter Wiring

3PH3W z iEM3250 z iEM3255

2 VTs 1 CT (balanced)

2 VTs 2 CTs

2 VTs 3 CTs

DOCA0005EN 042012 27

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 28: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Power System Energy Meter Energy Meter Wiring

3PH4W z iEM3250 z iEM3255

3 VTs 1 CTs (balanced)

3 VTs 2 CTs (for balanced 3-wire load)

3 VTs 3 CTs

1 Protection (to be adapted to suit the short-circuit current at the connection) 2 Shorting switch unit

DOCA0005EN 042012 28

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 29: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Typical Applications

iEM31bullbull series

This range is a cost effective solution to monitor more feeders It is ideal to monitor energy consumption by usage by zone or by feeder in the cabinet It could be used to monitor feeders in main switchboard or to monitor the main in distribution cabinet

Functions Advantages

Energies monitoring up to 63 A feeders

Embedded current transformers

Installation time saving and space saving in the cabinet No wiring to manage Clear distribution network

iEM31bullbull are adapted to be installed with iC60 circuit breakers Three phases support with or without neutral

iEM31bullbull can be used also for single phase multi-circuit monitoring 3 single feeders can be monitored with a unique product

iEM32bullbull series

This range allows to cover a large choice of applications

Functions Advantages

CTs and VTs connections support Adapted to LV or MV applications

Flexible configuration Can be adapted with any distribution network with or without neutral

DOCA0005EN 042012 29

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 30: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Installation

Typical applications

The following table presents some functions of the different iEM3bullbullbull series devices their advanteges and their main applications

Series Functions Advantages Applications

iEM3bull00 Total and partial counter Measurement campaign Sub-billing management Metering applications

iEM3bull10 Pulse output with pulse weight calibration up to 1 pulse per 1 Wh

Accurate monitoring Remote monitoring of energy consumption

Pulse output collecting by Smartlink system PLC or any basic acquisition system

Reducing the number of communication addresses

Monitoring of high number of meters

Internal clock Save date and time of last reset Knowledge of the period of the partial counter

iEM3bull15 Management of up to four energy registers By digital inputs and internal clock user can split his consumption on four periods at his convenience

Differentiation of Peak and Off Peak consumptions Working days and weekshyends or double source energies (from utilities or Genset)

Accurate sub-billing management

Identification of local energy consumption behavior It could be done by zone by usage or by feeder

iEM3bull50 Modbus communication on a RS485 port

A four connector pluggable terminal (+ - Shield Ground) helps to reach high distance communication

Advanced parameters are available by communication

Modbus network with daisy chain applications

Providing of essential electrical parameters like current average voltage and total power

Currents help monitoring the unbalance between phases

Power allows monitoring the feeder load level

Critical feeders or any sub-cabinet monitoring

iEM3bull55 All iEM3bull50 functions and iEM3bull15 functions

See above See above

Four quadrant calculation Identification and addition of In and Out energies active and reactive energies

Green power applications

Four tariff rates are managed in the product

Measurement of active reactive and apparent energy

Control energy consumption and make adapted investment at right place when necessary (ie Capacitor banks) to reduce energy bill or penalties

Digital Input (DI) with value saving Pulse collecting from other meters (gas water etc)

External status collecting like door opening circuit breaker status etc

The DI can be used to reset remotely the partial counters to start a measurement campaign

Intrusion preventing

Measurement campaign

Power overload alarm Detecting a critical load before the circuit breaker trips

User can reduce the consumption or prepare an extension

DOCA0005EN 042012 30

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 31: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012

3

iEM3100 series iEM3200 series

Energy Meter HMI

DOCA0005EN 042012

Use

What Is in This Chapter

This chapter contains the following topics

Topic Page

Presentation 32

Settings for all Energy Meters 34

Modifying Parameters 35

Clock Setting 36

Configuration 37

HMI Display 50

31

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 32: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Presentation

Introduction

The energy meter features a sophisticated and intuitive human machine interface (HMI) with signaling LEDs a graphic display and contextual menu buttons for accessing the information required to operate the energy meter and modify parameter settings

The navigation menu allows to display configure and reset parameters

For some energy meters Multi-Tariffs allows to select different tariffs mode and to configure them as illustrated in the table below

General Display

The general display of the energy meters is shown in the following picture

1 Configuration mode2 ValuesParameters3 Unit4 Cancellation5 Confirmation6 Selection7 Date and Time (except for iEM3100 and iEM3200)8 Tariff currently used (iEM3115 iEM3155 iEM3215 iEM3255)9 FunctionsMeasurements

Multi-Tariffs

Multi-Tariffs only applies to the following devicesz iEM3115z iEM3155z iEM3215z iEM3255

The following table describes the tariff repartition during the week according to the tariff selection (2 3 or 4 tariffs)

These tariffs are stored in 4 different registers T1 T2 T3 and T4

DOCA0005EN 042012 32

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 33: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Status Information

The display and the 2 two-color LEDs on the energy meters indicate the devicersquos current status

LEDs Description

ON 500 or 5000 flashes kWh

OFF OFF Off

ON ON (1s) then OFF On no counting

ON Flashing On with counting

OFF ON Error stop counting

Flashing Flashing Abnormal with counting

DOCA0005EN 042012 33

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 34: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Settings for all Energy Meters

The following settings have to be configured in configuration mode

Function iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Wiring radic radic radic radic radic radic radic radic radic radic

CT Ratio ndash ndash ndash ndash ndash radic radic radic ndash ndash

CT amp VT Ratio ndash ndash ndash ndash ndash ndash ndash ndash radic radic

Frequency radic radic radic radic radic radic radic radic radic radic

Date ndash radic radic radic radic ndash radic radic radic radic

Time ndash radic radic radic radic ndash radic radic radic radic

Multi Tariffs ndash ndash radic ndash radic ndash ndash radic ndash radic

Overload Alarm ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Output ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Digital Input ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Pulse Output ndash radic ndash ndash ndash ndash radic ndash ndash ndash

Communication ndash ndash ndash radic radic ndash ndash ndash radic radic

Contrast radic radic radic radic radic radic radic radic radic radic

Password ndash radic radic ndash radic ndash radic radic ndash radic

Reset Config radic radic radic radic radic radic radic radic radic radic

The default factory settings are listed in the following table

Function Factory settings

Wiring iEM31bullbull 3PH4W iEM32bullbull 3PH4W 3 CTs on I1 I2 and I3 Direct-No VT

CT Ratio CT Secondary = 5 A CT Primary = 5 A

CT amp VT Ratio CT Secondary = 5 A CT Primary = 5 A VT Secondary = 100 V VT Primary = 100 V (by communication) VT Secondary and Primary are not available on HMI

Frequency 50 Hz

Date 1-Jan-2000

Time 000000

Multi Tariffs Disable

Overload Alarm Disable

Digital Output Disable

Digital Input Input Status

Pulse Output 100 imp kWh

Communication Baud Rate = 19 200 Parity = EVEN Address = 1

Contrast 5

Password 0010

DOCA0005EN 042012 34

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 35: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Modifying Parameters

Presentation

To modify any of the values you must be thoroughly familiar with how the interface menus are structuredand the general navigation principles For more information about how the menus are structured refer to the section that relates specifically to your energy meter model (see page 34)

To modify the value of a parameter follow either of the 2 methods described belowz selecting an item in a listz modifying a numerical value digit by digit

The parameters listed below are the only ones which the numerical value can be modifiedz Datez Timez Pick Up Valuez Voltage Transformer (VT) Primaryz Current Transformer (CT) Primaryz Passwordz Modbus address of the energy meter

Selecting the Value in a List

The following table explains how to select a value in a list

Step Action

1 Use the until you re

contextual menu button to scroll through the parameter values ach the desired value

2 Press to confirm the new parameter value

Modifying the Numerical Value

The numerical value of a parameter is made up of digits The digit on the far right side is selected by default (except for DateTime)

To modify a numerical value use the contextual menu buttons as described below

Step Action

1 Use the button to modify the selected digit

2 Press to shift to next digit or to confirm the new parameter value

Aborting an Entry

To abort the current parameter entry press the button The screen reverts to the previous display

DOCA0005EN 042012 35

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 36: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Clock Setting

Description

The clock setting only applies to the following devicesz iEM3110z iEM3115z iEM3150z iEM3155z iEM3210z iEM3215z iEM3250z iEM3255

The time must be set when switching from winter to summer time

As soon as the power is interrupted the product iEM3110 iEM3150 iEM3210 and iEM3250 automatically display the screen to set Date and Time because the date and time are reset

The products iEM3115 iEM3155 iEM3215 and iEM3255 automatically display the screen to set Date and Time in case of loss of date and time when the power is interrupted for longer than 3 days

The energy meter retains the date and time settings before the interruption

Setting

To set the date and time please refer to the procedure for modifying a numerical value (see page 35)

DateTime Format

The date is displayed in the format DD-MMM-YYYY

The time is displayed using the 24-hour clock in the format hhmmss

Clock Setting Menu

DOCA0005EN 042012 36

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 37: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Configuration

Enter the Configuration Mode

The diagram below illustrates the various elements for operating the energy meters

Selection button to change or select parameter values

Confirmation button

Cancellation button

To enter the configuration mode hold and for 2 seconds

The pictures below describe in details the configuration navigation refer to Modifying Parameters(see page 35) to change the default selection

DOCA0005EN 042012 37

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 38: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Configuration Menu for iEM3100 iEM3110 iEM3115

DOCA0005EN 042012 38

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 39: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 39

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 40: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Configuration Menu for iEM3150 iEM3155

DOCA0005EN 042012 40

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 41: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 41

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 42: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

DOCA0005EN 042012 42

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 43: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Meter restarts 3 Password will not be reset

NOTE number of stop bits = 1

DOCA0005EN 042012 43

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 44: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Configuration Menu for iEM3200 iEM3210 iEM3215

DOCA0005EN 042012 44

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 45: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

1 Password will not be reset 2 Meter restarts

DOCA0005EN 042012 45

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 46: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

Configuration Menu for iEM3250 iEM3255

DOCA0005EN 042012 46

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 47: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

DOCA0005EN 042012 47

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 48: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

1 Input Status eg OF SD of a circuit breaker 2 Overriding appears when current selection impacts multi tariffs setting

DOCA0005EN 042012 48

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 49: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

1 If COM Protection is enable any configuration related to energy measurement such as wiring frequency etc can not be changed through communication

2 Password will not be reset 3 Meter restarts

NOTE number of stop bits = 1

DOCA0005EN 042012 49

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 50: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

HMI Display

Available Displayed Information

The following information is available in display mode

Information iEM3100 iEM3110 iEM3115 iEM3150 iEM3155 iEM3200 iEM3210 iEM3215 iEM3250 iEM3255

Total Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Total Active Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Total Reactive Energy Export

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Partial Active Energy Import

radic radic radic radic radic radic radic radic radic radic

Partial Reactive Energy Import

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Active Energy Import per Tariffs (T1 T4)

ndash ndash radic ndash radic ndash ndash radic ndash radic

Average voltage ndash ndash ndash radic radic ndash ndash ndash radic radic

Current per phase

ndash ndash ndash radic radic ndash ndash ndash radic radic

Active Power (kW)

ndash ndash ndash radic radic ndash ndash ndash radic radic

Reactive Power (kVAR)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Apparent Power (kVA)

ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Power Factor ndash ndash ndash radic radic ndash ndash ndash radic radic

Frequency ndash ndash ndash ndash radic ndash ndash ndash ndash radic

Operation Time ndash ndash ndash ndash radic ndash ndash ndash ndash radic

DOCA0005EN 042012 50

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 51: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

1 2 3 4 5

1 2 3 4 5

iEM3100 iEM3110 iEM3115 iEM3200 iEM3210 iEM3215

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

iEM3150 iEM3250

Date of last resetReset all energy measurements except total active energyDiagnosis screen appears on specific event see chapter troubleshootingDiagnosis code explained in chapter troubleshootingList of existing diagnosis

DOCA0005EN 042012 51

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 52: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter HMI

iEM3155 iEM3255

1 Import Export indicated for total active reactive (Ea Er) energy the other energy measurements are only Import energy measurements

2 Date of last reset 3 Reset all measurements except total active energy and total reactive energy 4 Diagnosis screen appears on specific event see chapter troubleshooting 5 Diagnosis code explained in chapter troubleshooting 6 List of existing diagnosis

DOCA0005EN 042012 52

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 53: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012

4

iEM3100 series iEM3200 series

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

DOCA0005EN 042012

Communication via Modbus RS-485

What Is in This Chapter

This chapter contains the following sections

Section Topic Page

41 Modbus Configuration 54

42 Modbus Functions 55

43 Command Interface 58

44 Modbus Register Table 65

45 Read Device Identification 70

53

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 54: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

41 Modbus Configuration

Configuration of RS-485 Communication Port

Communication Parameters

Before initiating any communication processes configure the Modbus communication port via the human machine interface (Config rarr Communication menu command)

Parameters Authorized Values Default Value

Baud rate z 9600 Baud z 19 200 Baud z 38 400 Baud

19 200 Baud

Parity z Odd z Even z None

NOTE number of stop bit = 1

Even

Address 1ndash247 1

Signaling of Communication Activity

The yellow communication LED indicates the status of communication between the Energy Meters (EMs) and the master as follows

If Then

The LED is flashing Communication with the device has been established NOTE If there is an error online the LEd is also flashing

The LED is off There is no active communication between the master and the slave

DOCA0005EN 042012 54

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 55: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

42 Modbus Functions

What Is in This Section

This section contains the following topics

Topic Page

Function List 56

Table Format 57

DOCA0005EN 042012 55

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 56: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Function List

Introduction

There are three different ways of using the Modbus communication z by sending commands using the command interface (see page 58) z by reading the Modbus registers z by reading Device Identification (see page 70)

Description

Sending commands using the command interface is supported by Modbus function 16

Reading Modbus registers is supported by Modbus function 3

Read Device Identification is supported by Modbus function 4314

The table below describes the three Modbus functions

Function Code Function Name

Decimal Hexadecimal

3 0x03 Read Holding Registers

16 0x10 Write Multiple Registers

4314 0x2B0x0E Read Device Identification

For examplez To read different parameters from the energy meter use the function 3 (Read)z To change the tariff use the function 16 (Write) by sending a command to the energy meter

DOCA0005EN 042012 56

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 57: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Table Format

Register tables have the following columns

Register Address Action (RWWC)

Size Type Units Range Description

z Register Address Modbus address of register encoded in the Modbus frame in decimal (dec) z Action The readwritewrite by command property of the register z Size The data size in Int16 z Type The encoding data type z Units The unit of the register value z Range The permitted values for this variable usually a subset of what the format allows z Description Provides information about the register and the values that apply

Unit Table

The following data types appear in the Modbus register list

Type Description Range

UInt16 16 bit unsigned integer 065535

Int16 16 bit signed integer -32768+32767

UInt32 32 bit unsigned integer 04 294 967 295

UTF8 8 bit field multibyte character encoding for Unicode

Float32 32 bit value Standard representation IEEE for floating number (with single precision)

Bitmap ndash ndash

DATETIME See below ndash

DATETIME format

Word Bits

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

1 Reserved (0) R4 (0) Year (0127)

2 0 Month (112) WD (0) Day (131)

3 SU (0) 0 Hour (023) iV 0 Minute (059)

4 Millisecond (059999)

R4 Year Month Day Hour Minute Millisecond WD (day of the week) SU (summer time) iV (validity of received data)

Reserved Bit 7 bits (year from 2000) 4 bits 5 bits 5 bits 6 bits 2 octets 1ndash7 SundayndashSaturday Bit to 0 if this parameter is not used Bit to 0 if this parameter is not valid or not used

DOCA0005EN 042012 57

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 58: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

43 Command Interface

What Is in This Section

This section contains the following topics

Topic Page

Presentation 59

Command List 60

DOCA0005EN 042012 58

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 59: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Presentation

Description

The command interface allows to configure the energy meter by sending specific command requests using Modbus function 16

Command Request

The following table describes a Modbus command request

Slave Function Code Command block CRC Number Register Address Command Description

1ndash247 16 (W) 5250 (up to 5374) The command is made of a command number and a set of parameters See the detailed description of each command in the command list NOTE All the reserved parameters can be considered as any value eg 0

Checking

The following table describes a command block

Register Address Content Size (Int16) Data (example)

5250 Command Number 1 2008 (Set Tariff)

5251 (Reserved) 1 0

5252ndash5374 Parameter n 4 (Tariff=4) NOTE Command number 2008 supports only one parameter with the size of 1

Command Result

The command result can be obtained by reading registers 5375 and 5376

The following table describes the command result

Register Address Content Size (Int16) Data (example)

5375 Requested Command Number 1 2008 (Set Tariff)

5376 Result(1) 1 0 (Valid Operation)

(1)List of Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

DOCA0005EN 042012 59

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 60: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command List

The following commands are available

Command Relevant Command Number Page

Set DateTime 1003 (see page 61)

Set Wiring 2000 (see page 61)

Set Pulse Output (iEM3155 iEM3255) 2003 2038 (see page 62)

Set Tariff (iEM3155 iEM3255) 2008 2060 (see page 63)

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255) 6017 (see page 62)

Input Metering Setup (iEM3155 iEM3255) 6014 (see page 63)

Overload Alarm Setup (iEM3155 iEM3255) 7000 20000 20001 (see page 63)

Communications Setup 5000 (see page 64)

Reset Partial Energy Counters 2020 (see page 64)

Reset Input Metering Counter (iEM3155 iEM3255) 2023 (see page 64)

DOCA0005EN 042012 60

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 61: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set DateTime

Command Number

Action (RW)

Size Type Unit Range Description

1003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 2000ndash2099 Year

W 1 UInt16 ndash 1ndash12 Month

W 1 UInt16 ndash 1ndash31 Day

W 1 UInt16 ndash 23 Hour

W 1 UInt16 ndash 0ndash59 Minute

W 1 UInt16 ndash 0ndash59 Second

W 1 UInt16 ndash ndash (Reserved)

Set Wiring

Command Number

Action (RW)

Size Type Unit Range Description

2000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 3 1113 Power System Configuration 0 = 1PH2W L-N 1 = 1PH2W L-L 2 = 1PH3W L-L-N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W L-N

W 1 UInt16 Hz 50 60 Nominal Frequency

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 V VT Secondaryndash 10000000

(1) VT Primary

W 1 UInt16 V 100 110 115 120

(1) VT Secondary

W 1 UInt16 ndash 1 2 3 (1) Number of CTs

W 1 UInt16 A 1ndash32767 (1) CT Primary

W 1 UInt16 A 1 5 (1) CT Secondary

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 (1) VT Connection type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs)

(1) For iEM3250 iEM3255 Reserved by iEM3150 iEM3155

DOCA0005EN 042012 61

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 62: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Set Pulse Output (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2003 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash (Reserved)

W 1 UInt16 ndash 0 1 Pulse Output 0 = Disable 1 = Enable

W 2 Float32 pulsekWh (1) (2)

Pulse Frequency

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

2038 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ms 50 100 200 300

Energy Pulse Duration

(1) iEM3155 1 10 20 100 200 1000 (2) iEM3255 001 01 1 10 100 500

Set Tariff (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2060 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 2 4 Multi-Tariff Mode 0 = Disable Multi-Tariff 1 = Use COM as Tariff Control (maximum 4 tariffs) 2 = Use 1 Digital Input as Tariff Control (2 tariffs) 4 = Use RTC as Tariff Control (maximum 4 tariffs)

2008 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash4 Tariff(1)

1 = T1 2 = T2 3 = T3 4 = T4

(1)Only if Multi-Tariff is controlled by COM

Set Digital Input as Partial Energy Reset (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6017 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input to Associate 0 = Disable 1 = Enable

DOCA0005EN 042012 62

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 63: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Input Metering Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

6014 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1 Input Metering Channel

W 20 UTF8 ndash string size lt= 40

Label

W 2 Float32 ndash 1ndash10000 Pulse Weight

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 Digital Input Association 0 = Disable 1 = Enable

Overload Alarm Setup (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

7000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 9 Alarm ID

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 0 1 0 = Disable 1 = Enable

W 2 Float32 ndash 00ndash1e10 Pickup Setpoint

W 2 UInt32 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 4 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

20000 W 1 UInt16 ndash ndash (Reserved)

W 2 Float32 ndash ndash (Reserved)

W 2 UInt32 ndash ndash (Reserved)

W 1 Bitmap ndash 01 Digital Output to Associate 0 = Unassociated 1 = Associated

20001 W 1 UInt16 ndash ndash Acknowledge the Overload Alarm

DOCA0005EN 042012 63

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 64: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Communications Setup

Command Number

Action (RW)

Size Type Unit Range Description

5000 W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash ndash (Reserved)

W 1 UInt16 ndash 1ndash247 Address

W 1 UInt16 ndash 0 1 2 Baud Rate 0 = 9600 1 = 19200 2 = 38400

W 1 UInt16 ndash 0 1 2 Parity 0 = Even 1 = Odd 2 = None

W 1 UInt16 ndash ndash (Reserved)

Reset Partial Energy Counters

Command Number

Action (RW)

Size Type Unit Range Description

2020 W 1 UInt16 ndash ndash (Reserved) (1) (2)

(1)iEM3150iEM3250 Partial Active Energy and Phase Energy registers will be reset (2)iEM3155iEM3255 Partial Active Reactive Energy Energy by tariff and Phase Energy registers will be reset

Reset Input Metering Counter (iEM3155 iEM3255)

Command Number

Action (RW)

Size Type Unit Range Description

2023 W 1 UInt16 ndash ndash (Reserved)

DOCA0005EN 042012 64

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 65: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

44 Modbus Register Table

Register List

The following table lists the accessible registers

Register Page

System (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255) (see page 66)

Energy Pulse Output Setup (iEM3155 iEM3255) (see page 66)

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Communication (iEM3150 iEM3155 iEM3250 iEM3255) (see page 67)

Input Metering Setup (iEM3155 iEM3255) (see page 67)

Digital Input (iEM3155 iEM3255) (see page 67)

Digital Output (iEM3155 iEM3255) (see page 68)

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255) (see page 68)

Overload Alarm (iEM3155 iEM3255) (see page 69)

DOCA0005EN 042012 65

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 66: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

System (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC

Size Type Units Description

30 R 20 UTF8 ndash Meter Name

50 R 20 UTF8 ndash Meter Model

70 R 20 UTF8 ndash Manufacturer

130 R 2 UInt32 ndash Serial Number

132 R 4 DATETIME ndash Date of Manufacture

136 R 5 UTF8 ndash Hardware Revision

1637 R 1 UInt16 ndash Present Firmware Version (DLF format) XYZTT

1845ndash 1848

RWC 1 X 4 UInt16 ndash DateTime Reg 1845 Year (b6b0) 0ndash99 (year from 2000 to 2099) Reg 1846 Month (b11b8) Weekday (b7b5) Day (b4b0) Reg 1847 Hour (b12b8) Minute (b5b0) Reg 1848 Millisecond

Meter Setup and Status (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2004 R 2 UInt32 Secon d

Meter Operation Timer Not applicable for iEM3150 iEM3250

2014 R 1 UInt16 ndash Number of Phases

2015 R 1 UInt16 ndash Number of Wires

2016 RWC 1 UInt16 ndash Power System 0 = 1PH2W LndashN 1 = 1PH2W LndashL 2 = 1PH3W LndashL with N 3 = 3PH3W 11 = 3PH4W 13 = 1PH4W multi L with N

2017 RWC 1 UInt16 Hz Nominal Frequency

2025 R 1 UInt16 ndash Number VTs Not applicable for iEM3150 iEM3155

2026 RWC 2 Float32 V VT Primary Not applicable for iEM3150 iEM3155

2028 RWC 1 UInt16 V VT Secondary Not applicable for iEM3150 iEM3155

2029 RWC 1 UInt16 ndash Number CTs Not applicable for iEM3150 iEM3155

2030 RWC 1 UInt16 A CT Primary Not applicable for iEM3150 iEM3155

2031 RWC 1 UInt16 A CT Secondary Not applicable for iEM3150 iEM3155

2036 RWC 1 UInt16 ndash VT Connection Type 0 = Direct Connect 1 = 3PH3W (2 VTs) 2 = 3PH4W (3 VTs) Not applicable for iEM3150 iEM3155

Energy Pulse Output Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

2129 RWC 1 UInt16 Millisecond Energy Pulse Duration

2131 RWC 1 UInt16 ndash Digital Output Association 0 = Disable 1 = DO1 enable for active energy pulse output

2132 RWC 2 Float32 pulsekWh Pulse Weight

DOCA0005EN 042012 66

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f00630068007700650072007400690067006500200044007200750063006b006500200061007500660020004400650073006b0074006f0070002d0044007200750063006b00650072006e00200075006e0064002000500072006f006f0066002d00470065007200e400740065006e002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 67: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Command Interface (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

5250 RW 1 UInt16 ndash Requested Command

5252 RW 1 UInt16 ndash Command Parameter 001

5374 RW 1 UInt16 ndash Command Parameter 123

5375 R 1 UInt16 ndash Command Status

5376 R 1 UInt16 ndash Command Result codes z 0 = Valid Operation z 3000 = Invalid Command z 3001 = Invalid Parameter z 3002 = Invalid Number of Parameters z 3007 = Operation Not Performed

5377 RW 1 UInt16 ndash Command Data 001

5499 R 1 UInt16 ndash Command Data 123

Communication (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

6500 R 1 UInt16 ndash Protocol 0 = Modbus

6501 RWC 1 UInt16 ndash Address

6502 RWC 1 UInt16 ndash Baud Rate 0 = 9600 1 = 19 200 2 = 38 400

6503 RWC 1 UInt16 ndash Parity 0 = Even 1 = Odd 2 = None

Input Metering Setup (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7032 RWC 20 UTF8 ndash Label

7052 RWC 2 Float32 pulseunit Pulse Constant

7055 RWC 1 UInt16 ndash Digital Input Association 0 = Disable for input metering 1 = Enable for input metering

Digital Input (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

7274 R 1 UInt16 ndash Digital Input Control Mode 0 = Normal (Input Status) 2 = Multi-tariff Control 3 = Input Metering 5 = All Energy Reset

8905 R 2 Bitmap ndash Digital Input Status (only Bit 1 is used) Bit 1 = 0 relay open Bit 1 = 1 relay closed

DOCA0005EN 042012 67

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002000740069006c0020006b00760061006c00690074006500740073007500640073006b007200690076006e0069006e006700200065006c006c006500720020006b006f007200720065006b007400750072006c00e60073006e0069006e0067002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 68: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Digital Output (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

9673 R 1 UInt16 ndash Digital Output Control Mode Status 2 = Alarm 3 = Energy 0xFFFF = Disable

Meter Data (iEM3150 iEM3155 iEM3250 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

Current

3000 R 2 Float32 A I1 phase 1 current

3002 R 2 Float32 A I2 phase 2 current

3004 R 2 Float32 A I3 phase 3 current

3010 R 2 Float32 A Current Avg

Voltage

3020 R 2 Float32 V Voltage L1ndashL2

3022 R 2 Float32 V Voltage L2ndashL3

3024 R 2 Float32 V Voltage L3ndashL1

3026 R 2 Float32 V Voltage LndashL Avg

3028 R 2 Float32 V Voltage L1ndashN

3030 R 2 Float32 V Voltage L2ndashN

3032 R 2 Float32 V Voltage L3ndashN

3036 R 2 Float32 V Voltage LndashN Avg

Power

3054 R 2 Float32 kW Active Power Phase 1

3056 R 2 Float32 kW Active Power Phase 2

3058 R 2 Float32 kW Active Power Phase 3

3060 R 2 Float32 kW Total Active Power

3068 R 2 Float32 kVAR Total Reactive Power Not applicable for iEM3150 iEM3250

3076 R 2 Float32 kVA Total Apparent Power Not applicable for iEM3150 iEM3250

Power Factor

3084 R 2 Float32 ndash Total Power Factor -2 lt PF lt -1 = Quad 2 active power negative capacitive -1 lt PF lt 0 = Quad 3 active power negative inductive 0 lt PF lt 1 = Quad 1 active power positive inductive 1 lt PF lt 2 = Quad 4 active power positive capacitive

Frequency

3110 R 2 Float32 Hz Frequency

Total Energy (cannot be reset)

3204 R 4 Int64 Wh Total Active Energy Import

3208 R 4 Int64 Wh Total Active Energy Export Not applicable for iEM3150 iEM3250

3220 R 4 Int64 VARh Total Reactive Energy Import Not applicable for iEM3150 iEM3250

3224 R 4 Int64 VARh Total Reactive Energy Export Not applicable for iEM3150 iEM3250

Energy Reset (Partial Energy Energy by Tariff Phase Energy)

3252 R 4 DATETIME ndash Energy Reset Date and Time

Partial Energy

3256 R 4 Int64 Wh Partial Active Energy Import

DOCA0005EN 042012 68

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 69: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

Register Address

Action (RWWC)

Size Type Units Description

3272 R 4 Int64 VARh Partial Reactive Energy Import Not applicable for iEM3150 iEM3250

Phase Energy

3518 R 4 Int64 Wh Active Energy Import Phase 1

3522 R 4 Int64 Wh Active Energy Import Phase 2

3526 R 4 Int64 Wh Active Energy Import Phase 3

Input Metering Counter

3554 R 4 DATETIME ndash Input Metering Accumulation Reset Date and Time Not applicable for iEM3150 iEM3250

3558 R 4 Int64 Unit Input Metering Accumulation Not applicable for iEM3150 iEM3250

Energy by Tariff (Not applicable for iEM3150 iEM3250)

4191 RWC 1 UInt16 ndash MultiTariffs Energy Active Rate 0 multi tariff disabled 1 to 4 rate A to rate D NOTE Only modifiable by command in case of COM Control Mode

4196 R 4 Int64 Wh Rate A Active Energy Import

4200 R 4 Int64 Wh Rate B Active Energy Import

4204 R 4 Int64 Wh Rate C Active Energy Import

4208 R 4 Int64 Wh Rate D Active Energy Import

Overload Alarm (iEM3155 iEM3255)

Register Address

Action (RWWC)

Size Type Units Description

45001 RWC 1 Bitmap ndash Overload Alarm Setup 0x0000 = Disabled 0x0100 = Enabled

45002 RWC 2 Float32 kW Pickup Setpoint

45004 RWC 1 Bitmap ndash Digital Output to Associate 0x0000 = Digital Output unassociated to overload alarm 0x0100 = Digital Output associated to overload alarm

45005 R 1 Bitmap ndash Activated Status 0x0000 = Alarm is inactive 0x0100 = Alarm is active

45006 R 1 Bitmap ndash Unacknowledged Status 0x0000 = Historic alarm is acknowledged by the user 0x0100 = Historic alarm is unacknowledged by the user

45007 R 4 DATETIME ndash Last Alarm - Time Stamp

45011 R 2 Float32 kW Last Alarm - Value

DOCA0005EN 042012 69

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f007500720020006400650073002000e90070007200650075007600650073002000650074002000640065007300200069006d007000720065007300730069006f006e00730020006400650020006800610075007400650020007100750061006c0069007400e90020007300750072002000640065007300200069006d007000720069006d0061006e0074006500730020006400650020006200750072006500610075002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 70: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

iEM3150 iEM3155 iEM3250 iEM3255 - Communication

45 Read Device Identification

Register List

Read Device Identification

The energy meters supports the Basic Device Identification with the mandatory objects z VendorName z ProductCode z Revision Number

ObjectID Object NameDescription Object Length Object Value Note

0x00 VendorName 16 SchneiderElectric ndash

0x01 ProductCode 09 A9MEM3100 A9MEM3110 A9MEM3115 A9MEM3150 A9MEM3155 A9MEM3200 A9MEM3210 A9MEM3215 A9MEM3250 A9MEM3255

The ProductCode is identical to the catalogue number of each reference

0x02 MajorMinorRevision 04 V10 Equivalent to XY in register 1637

The Read Device ID code 01 and 04 are supportedz 01 = request to get the basic device identification (stream access)z 04 = request to get one specific identification objective (individual access)

The Modbus request and response are compliant with ldquoChapter 620 43 14 (0x2B 0x0E) Read DeviceIdentificationrdquo of Modbus Application Protocol Specification

DOCA0005EN 042012 70

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200066006f00720020007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c00690074006500740020007000e500200062006f007200640073006b0072006900760065007200200065006c006c00650072002000700072006f006f006600650072002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 71: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012

5

iEM3100 series iEM3200 series

Energy Meter Specifications

DOCA0005EN 042012

Technical Characteristics

Specifications

Electrical Characteristics

Characteristic Value Energy Meters

Voltage range U 3x100173 V AC3x277480 V AC (plusmn20 5060Hz) iEM31bullbull iEM32bullbull

Current In 5 A withstanding 10 A continuously iEM32bullbull

Imax 63 A iEM31bullbull

Maximum device consumption lt 10 VA iEM31bullbull iEM32bullbull

One solid state relay output

Voltage 540 V DC iEM3155 iEM3255

Current 50 mA iEM3155 iEM3255

Output resistance 0150 Ohm iEM3155 iEM3255

One optical coupler output for remote transfer

Pulses per kWh Configurable iEM3110 iEM3210

Voltage 530 V DC iEM3110 iEM3210

Current 115 mA iEM3110 iEM3210

Pulse width Configurable the minimum width is 50 ms iEM3110 iEM3210

Standard IEC 62053-31 compatible (S0 format output) iEM3110 iEM3210

One optical coupler input

Maximum input

Voltage 40 V DC iEM3155 iEM3255

Current 4 mA burden iEM3155 iEM3255

Voltage off 05 V DC iEM3155 iEM3255

Voltage on 1140 V DC iEM3155 iEM3255

Standard IEC61131-2 compatible (TYPE 1) iEM3155 iEM3255

Two optical coupler inputs for tariff control

Maximum input

Voltage 40 V DC iEM3115 iEM3215

Current 4 mA burden iEM3115 iEM3215

Voltage off 05 V DC iEM3115 iEM3215

Voltage on 1140 V DC iEM3115 iEM3215

Standard IEC61131-2 compatible (TYPE 1) iEM3115 iEM3215

Internal clock Quartz crystal based

Time error lt 25 sday (30 ppm) at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

Backup by super capacitor

Backup time

gt 3 days at 25deg C iEM3115 iEM3155 iEM3215 iEM3255

71

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 72: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meter Specifications

Measurement Accuracy

Characteristic Value Energy Meters

Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=004 A

iEM31bullbull

Class B conforming to EN 50470-3 Imax=63 A lref=10 A Imin=05 A and Ist=004 A

iEM31bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD DD) Imax=63 A lb=10 A and Ist=005 A

iEM3155

for x1A current input Active energy Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD SD) Imax=12 A ln=1 A and Ist=0002 A

iEM3200 iEM3210 iEM3215

Class 1 conforming to IEC 62053-21 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0002 A

iEM3250 iEM3255

Class B conforming to EN 50470-3 Imax=12 A ln=1 A Imin=001 A and Ist=0002 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=12 A ln=1 A and Ist=0003 A

iEM3255

for x5A current input Active energy Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD SD) Imax=6 A ln=5 A and Ist=0005 A

iEM32bullbull

Class 05S conforming to IEC 62053-22 and IEC 61557shy12 (PMD Sx) Imax=6 A ln=5 A and Ist=0005 A

iEM3250 iEM3255

Class C conforming to EN 50470-3 Imax=6 A ln=5 A Imin=005 A and Ist=0005 A

iEM32bullbull

Reactive energy Class 2 conforming to IEC 62053-23 and IEC 61557-12 (PMD Sx) Imax=6 A ln=5 A and Ist=0015 A

iEM3255

Mechanical Characteristics

Characteristic Value Energy Meters

Degree of protection

Front panel IP40 iEM31bullbull iEM32bullbull

Casing IP20 iEM31bullbull iEM32bullbull

Recommended terminal tightening torque

Power 16 mm2 18 Nm iEM31bullbull

Pulse output 25 mm2 05 Nm iEM3110 iEM3210

Tariff control 15 mm2 05 Nm iEM3115 iEM3215

Voltage input 25 mm2 05 Nm iEM32bullbull

Current input 6 mm2 08 Nm iEM32bullbull

Digital inputoutput 15 mm2 05 Nm iEM3155 iEM3255

RS 485 25 mm2 05 Nm iEM3150 iEM3155 iEM3250 iEM3255

Other Characteristics

Characteristic Value Energy Meters

Operating temperature ndash25deg C+55deg C (K55) iEM31bullbull iEM32bullbull

Degree of pollution 2 iEM31bullbull iEM32bullbull

Overvoltage and measurement category III iEM31bullbull iEM32bullbull

Active energy display In kWh or MWh up to 99999999 MWh iEM32bullbull

In kWh 8 + 1 digits up to 999999999 iEM31bullbull

Meter indicator 500 flashes kWh iEM31bullbull

5000 flashes kWh without consideration of transformer ratios

iEM32bullbull

DOCA0005EN 042012 72

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f0074002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a00610020006c0061006100640075006b006100730074006100200074007900f6007000f60079007400e400740075006c006f0073007400750073007400610020006a00610020007600650064006f007300740075007300740061002000760061007200740065006e002e00200020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740020006600f600720020006b00760061006c00690074006500740073007500740073006b0072006900660074006500720020007000e5002000760061006e006c00690067006100200073006b0072006900760061007200650020006f006300680020006600f600720020006b006f007200720065006b007400750072002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 73: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN 042012

6

iEM3100 series iEM3200 series

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012

Maintenance and Troubleshooting

What Is in This Chapter

This chapter contains the following topics

Topic Page

Safety Precautions 74

Troubleshooting 75

73

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN ltFEFF9ad854c18cea51fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e30593002537052376642306e753b8cea3092670059279650306b4fdd306430533068304c3067304d307e3059300230c730b930af30c830c330d730d730ea30f330bf3067306e53705237307e305f306f30d730eb30fc30d57528306b9069305730663044307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e30593002gt KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 74: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meters - Maintenance and Troubleshooting

Safety Precautions

Presentation

The following safety precautions must be thoroughly implemented before attempting to repair electrical equipment or carry out maintenance Carefully read and follow the safety precautions described below

DANGER RISK OF ELECTRIC SHOCK ARC FLASH OR BURNS

z Wear suitable personal protective equipment and follow the currently applicable electrical safety instructions See for example standard NFPA 70E when carrying out work in the USA

z Only qualified personnel should maintain this equipment Such work should be performed only after reading all the installation instructions

z Turn off all power supplying this equipment before working on or inside it z NEVER work alone z Beware of potential hazards and wear personal protective equipment

Failure to follow these instructions will result in death or serious injury

NOTICE RISK OF DAMAGE TO THE ENERGY METER

z Never open the energy meter unit z Do not attempt to repair any components in the energy meter range either in the unit or an

accessory

Failure to follow these instructions can result in equipment damage

DOCA0005EN 042012 74

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 75: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meters - Maintenance and Troubleshooting

Troubleshooting

Presentation

Diagnostic code

iEM3100 iEM3200

iEM3110 iEM3210

iEM3115 iEM3215

iEM3150 iEM3250

iEM3155 iEM3255

Description Possible solution

ndash radic radic radic radic radic

LCD display is not visible Check and adjust LCD contrast settings or contact Schneider-Electric service

ndash

radic radic radic radic radic

Push button failure Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

101 102

radic radic radic radic radic

Metering stops due to internal error Total energy consumption can be displayed by

pressing

Enter the configuration mode and implement Reset Config or contact Schneider-Electric service

201

radic radic radic radic radic

Metering continues Mismatch between frequency settings and frequency measurements

Correct frequency settings according to the nominal frequency of the network

202 radic radic radic radic radic

Metering continues Mismatch between wiring settings and wiring inputs

Correct wiring settings according to wiring inputs

203 radic radic radic radic radic Metering continues Phase sequence reverse

Check wire connections or correct wiring settings

204

radic radic radic radic ndash

Metering continues Total active energy negative due to incorrect voltage and current connections

Check wire connections

205 ndash radic radic ndash radic

Metering continues Date and Time are reset due to last power failure

Set Date and Time

206

ndash radic ndash ndash radic

Metering continues Pulse missing due to overspeed of energy pulse output

Set the suitable parameters of the energy pulse output

207

ndash ndash radic ndash radic

Metering continues Abnormal internal clock function

Restart the energy meter by power off and power on again If there is still no response contact Schneider-Electric service

DOCA0005EN 042012 75

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f006200650020005000440046002000700065007200200075006e00610020007300740061006d007000610020006400690020007100750061006c0069007400e00020007300750020007300740061006d00700061006e0074006900200065002000700072006f006f0066006500720020006400650073006b0074006f0070002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 76: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

Energy Meters - Maintenance and Troubleshooting

DOCA0005EN 042012 76

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f0073002000640065002000410064006f0062006500200050004400460020007000610072006100200063006f006e00730065006700750069007200200069006d0070007200650073006900f3006e002000640065002000630061006c006900640061006400200065006e00200069006d0070007200650073006f0072006100730020006400650020006500730063007200690074006f00720069006f00200079002000680065007200720061006d00690065006e00740061007300200064006500200063006f00720072006500630063006900f3006e002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB 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 SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice

Page 77: Energy Meters User Manual - Schneider Electric · PDF fileEnergy Meters User Manual 04/2012 DOCA000 5EN-01 . The information provided in this documentation contain s general descr

DOCA0005EN-01

Schneider Electric Industries SAS As standards specifications and designs change from time to time please ask for confirmation 35 rue Joseph Monier of the information given in this publication CS30323 F - 92506 Rueil Malmaison Cedex

wwwschneider-electriccom 042012

  • iEM3100 series iEM3200 series
  • Table of Contents
  • Safety Information
  • About the Book
  • Presentation
    • Presentation
    • Physical Description
      • Installation
        • Safety Measures
        • Dimensions
        • DIN Rail Mounting and Dismantling
        • Connection
        • Typical Applications
          • Use
            • Presentation
            • Settings for all Energy Meters
            • Modifying Parameters
            • Clock Setting
            • Configuration
            • HMI Display
              • Communication via Modbus RS-485
                • Modbus Configuration
                  • Configuration of RS-485 Communication Port
                    • Modbus Functions
                      • Function List
                      • Table Format
                        • Command Interface
                          • Presentation
                          • Command List
                            • Modbus Register Table
                              • Register List
                                • Read Device Identification
                                  • Register List
                                      • Technical Characteristics
                                        • Specifications
                                          • Maintenance and Troubleshooting
                                            • Safety Precautions
                                            • Troubleshooting
                                                • ltlt ASCII85EncodePages false AllowTransparency false AutoPositionEPSFiles true AutoRotatePages All Binding Left CalGrayProfile (Dot Gain 20) CalRGBProfile (sRGB IEC61966-21) CalCMYKProfile (US Web Coated 050SWOP051 v2) sRGBProfile (sRGB IEC61966-21) CannotEmbedFontPolicy Warning CompatibilityLevel 14 CompressObjects Tags CompressPages true ConvertImagesToIndexed true PassThroughJPEGImages true CreateJDFFile false CreateJobTicket false DefaultRenderingIntent Default DetectBlends true DetectCurves 00000 ColorConversionStrategy LeaveColorUnchanged DoThumbnails false EmbedAllFonts true EmbedOpenType false ParseICCProfilesInComments true EmbedJobOptions true DSCReportingLevel 0 EmitDSCWarnings false EndPage -1 ImageMemory 1048576 LockDistillerParams false MaxSubsetPct 100 Optimize true OPM 1 ParseDSCComments true ParseDSCCommentsForDocInfo true PreserveCopyPage true PreserveDICMYKValues true PreserveEPSInfo true PreserveFlatness true PreserveHalftoneInfo false PreserveOPIComments false PreserveOverprintSettings true StartPage 1 SubsetFonts true TransferFunctionInfo Apply UCRandBGInfo Preserve UsePrologue false ColorSettingsFile () AlwaysEmbed [ true ] NeverEmbed [ true ] AntiAliasColorImages false CropColorImages true ColorImageMinResolution 300 ColorImageMinResolutionPolicy OK DownsampleColorImages true ColorImageDownsampleType Bicubic ColorImageResolution 300 ColorImageDepth -1 ColorImageMinDownsampleDepth 1 ColorImageDownsampleThreshold 150000 EncodeColorImages true ColorImageFilter DCTEncode AutoFilterColorImages true ColorImageAutoFilterStrategy JPEG ColorACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt ColorImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000ColorACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000ColorImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasGrayImages false CropGrayImages true GrayImageMinResolution 300 GrayImageMinResolutionPolicy OK DownsampleGrayImages true GrayImageDownsampleType Bicubic GrayImageResolution 300 GrayImageDepth -1 GrayImageMinDownsampleDepth 2 GrayImageDownsampleThreshold 150000 EncodeGrayImages true GrayImageFilter DCTEncode AutoFilterGrayImages true GrayImageAutoFilterStrategy JPEG GrayACSImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt GrayImageDict ltlt QFactor 015 HSamples [1 1 1 1] VSamples [1 1 1 1] gtgt JPEG2000GrayACSImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt JPEG2000GrayImageDict ltlt TileWidth 256 TileHeight 256 Quality 30 gtgt AntiAliasMonoImages false CropMonoImages true MonoImageMinResolution 1200 MonoImageMinResolutionPolicy OK DownsampleMonoImages true MonoImageDownsampleType Bicubic MonoImageResolution 1200 MonoImageDepth -1 MonoImageDownsampleThreshold 150000 EncodeMonoImages true MonoImageFilter CCITTFaxEncode MonoImageDict ltlt K -1 gtgt AllowPSXObjects false CheckCompliance [ None ] PDFX1aCheck false PDFX3Check false PDFXCompliantPDFOnly false PDFXNoTrimBoxError true PDFXTrimBoxToMediaBoxOffset [ 000000 000000 000000 000000 ] PDFXSetBleedBoxToMediaBox true PDFXBleedBoxToTrimBoxOffset [ 000000 000000 000000 000000 ] PDFXOutputIntentProfile () PDFXOutputConditionIdentifier () PDFXOutputCondition () PDFXRegistryName () PDFXTrapped False Description ltlt CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000500044004600206587686353ef901a8fc7684c976262535370673a548c002000700072006f006f00660065007200208fdb884c9ad88d2891cf62535370300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef653ef5728684c9762537088686a5f548c002000700072006f006f00660065007200204e0a73725f979ad854c18cea7684521753706548679c300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt DAN 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 DEU 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 ESP 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 FRA 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 ITA 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 JPN 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 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020b370c2a4d06cd0d10020d504b9b0d1300020bc0f0020ad50c815ae30c5d0c11c0020ace0d488c9c8b85c0020c778c1c4d560002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken voor kwaliteitsafdrukken op desktopprinters en proofers De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger) NOR 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020007000610072006100200069006d0070007200650073007300f5006500730020006400650020007100750061006c0069006400610064006500200065006d00200069006d00700072006500730073006f0072006100730020006400650073006b0074006f00700020006500200064006900730070006f00730069007400690076006f0073002000640065002000700072006f00760061002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt SUO 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 SVE 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 ENU (Use these settings to create Adobe PDF documents for quality printing on desktop printers and proofers Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later) gtgt Namespace [ (Adobe) (Common) (10) ] OtherNamespaces [ ltlt AsReaderSpreads false CropImagesToFrames true ErrorControl WarnAndContinue FlattenerIgnoreSpreadOverrides false IncludeGuidesGrids false IncludeNonPrinting false IncludeSlug false Namespace [ (Adobe) (InDesign) (40) ] OmitPlacedBitmaps false OmitPlacedEPS false OmitPlacedPDF false SimulateOverprint Legacy gtgt ltlt AddBleedMarks false AddColorBars false AddCropMarks false AddPageInfo false AddRegMarks false ConvertColors NoConversion DestinationProfileName () DestinationProfileSelector NA Downsample16BitImages true FlattenerPreset ltlt PresetSelector MediumResolution gtgt FormElements false GenerateStructure true IncludeBookmarks false IncludeHyperlinks false IncludeInteractive false IncludeLayers false IncludeProfiles true MultimediaHandling UseObjectSettings Namespace [ (Adobe) (CreativeSuite) (20) ] PDFXOutputIntentProfileSelector NA PreserveEditing true UntaggedCMYKHandling LeaveUntagged UntaggedRGBHandling LeaveUntagged UseDocumentBleed false gtgt ]gtgt setdistillerparamsltlt HWResolution [2400 2400] PageSize [612000 792000]gtgt setpagedevice