ELKRON. THE HI-PROTECTION COMPANY FIRE DETECTION
Transcript

ELKRON. THE HI-PROTECTION COMPANY

FIRE DETECTION

2

THE HI-PROTECTION COMPANYAnother safe and secure day. Since 1974 Elkron has been committed to guarantee Security to any type of application, from small home systems to large installations. As a leading company in its sector and confirming its position with 14 Quality marks in many different countries, 21 Inter-national Patents registered, 1600 different products designed and de-veloped, and 27 million products sold. Elkron has made a huge progress in research and innovation expressing new and unique solutions and gaining a steady international reputation in Security.

As a fundamental achievement for its constant commitment to total quality, Elkron has always complied with the strictest international stan-dards, generating a permanent process to check that such pro-fessional standards are constan-tly maintained as well as to ensu-re a continuous improvement of the products, respecting all the operating phases, from the ini-tial product concept, to design, manufacturing, sales and distri-bution, and finally to customer support. Last but not the least, Elkron is a leading participator as coordinators and experts, in do-mestic (CEI) and European (CENE-LEC) standardisation projects.

www.elkron.com

3

THE FIRE ELKRON OFFER

CONVENTIONAL FIRE SYSTEMS

Single Zone central unit, with micro-processor in polycarbonate, suitable for controlling fire stop doors.

C/302Compact central unit, with micro-processor, suitable for small size fire and gas systems. 4 detection lines 32 max detectors per zone.

C/54

Modular conventional fire detection central unit, with 16 bit micropro-cessor, 4 detection zones expanda-ble up to 16.

C/7000Optical smoke detectors, optical heat detectors, differential heat detectors, combustible gas detec-tors.

DETECTORS

Alarm push-buttons with recommis-soning, with glass breaking and un-breakable.

BUTTONS

ADDRESSED FIRE SYSTEMS

Analogue central unit, with 16 bit micro-processor, to manage fire systems with single detection line, where up to 128 out of smoke detectors, gas detectors, heat detectors, pushbuttons actuators and interfaces to control external equip-ment can be connected.

AREA 54/1Modular analogue central unit, with multiprocessor, having 4 LOOPs max. The unit is provided with base with 1 MR/128 module (128 ad-dresses). Expandable up to 512 addresses by 3 additional line mo-dules.

AREA 54/4

Modular analogue central unit, with multiprocessor, having 8 LOOPs max. The unit is provided with 1 MR/128 module (128 addresses).Expandable up to 1024 addresses by 7 additional line modules.

AREA 54/8Modular analogue central unit, with multiprocessor, having 16 LOOPs max. The unit is provided with base with 1 MR/128 module (128 addresses). Expandable up to 2048 addresses by 15 additional line modules.

AREA 54/16

Optical smoke detectors, optical heat detectors, differential heat de-tectors,

DETECTORSAlarm push-buttons with recommis-soning, with glass breaking and un-breakable.

BUTTONS

PAGE

13

PAGE

16

PAGE

19

PAGE

17

PAGE

14

PAGE

23

PAGE

25

PAGE

31PAGE

33

PAGE

26

PAGE

24

UNIVERSAL BASES

Universal connection bases with or without relay for conventional, digi-tal and analogic detectors.

DUCTED DETECTION

The analysis chamber for ducted detection was designed to check for the presence of smoke in air ducts and allows to timely detect a spre-ading fire.

PAGE

36PAGE

36

4

THE FIRE ELKRON OFFERFAP500 DIGITAL FIRE DETECTION SYSTEM

Microprocessor control unit with 1 loop line. Possibility of managing up to 128 points for loop (64 for open line).

FAP541Microprocessor control unit with 1 loop line expandable up to 4. Possibility of managing up to 128 points for loop (64 for open line).

FAP544

Microprocessor control unit with 1 loop line expandable up to 8. Possibility of managing up to 128 points for loop (64 for open line).

FAP548Microprocessor control unit with 1 loop line expandable up to 16. Possibility of managing up to 128 points for loop (64 for open line).

FAP5416

Optical smoke detectors, optical heat detectors, differential heat de-tectors, combustible gas detectors.

DETECTORSAlarm push-buttons with recommis-soning, with glass breaking and un-breakable.

BUTTONS

PAGE

40

PAGE

41

PAGE

44PAGE

43

PAGE

41

PAGE

41

FIRE EXSTINGUISHING

PAGE

48

Fire extinguishing control unit with one channel expandable up to 2.

CDS

GAS DETECTIONATEX CONTROL UNITS

ST/PL4Gas detection con-trol unit allowing the connection of max 8 detectors.

ST/MTLSBGas detection con-trol unit allowing the connection of max 108 detectors.PAGE

52

EXPLOSIVES AND TOXIC GAS DETECTORS

Petrol Vapour / Propane Gas / Butane Gas / Carbon MonoxideMethane Gas / GPL Gas

TYPE EX II 3GDPetrol Vapour / Propane Gas / Butane Gas / Carbon MonoxideMethane Gas / GPL Gas

TYPE EX II 2GD

PAGE

53PAGE

55

FLAME DETECTORS

PAGE

56

Flame detector immediately responding to infrared thermal radiation released by fire. The detector is tu-ned to flame pulses in order to ignore sunlight and lamps.

RU-ADPE

LIQUID DETECTOR

PAGINA

57

Electronic detector to detect the presence of (unin-flammable) liquids. Detecting the presence of water is through 4 support gilt feet, which put the detector into alarm by switching a relay placed inside it.

RA-209

5

THE FIRE ELKRON OFFER

SPECIAL HEAT DETECTOR

PAGE

57

IP65 Special heat detector based on the deformation of a bimetallic element which closes a dry contact as the tem-perature is reached.

RTS/2 - RTS/4 - RTS/6

PAGE

59

Thermosensitive linear detectors calibrated to 68° and 105° (certified).

RLB/1 - RLB/2

LINEAR DETECTORS

Linear detector suitable for all environ-ments characterised in high ceilings, where using smoke optical detectors results to be particularly hard.

S/2-100

PAGE

59

Fire and heat linear detector.The system includes three units: Tran-smitting unit (TX), Receiving unit (RX), co-ordination unit.

SF-100

PAGE

60

OPTICAL-ACOUSTIC INDICATORS

Optical/acoustic signalling single and double face panel.

PANELS

PAGE

64

Visual repeater allowing to show the alarm status of a detector installed in hidden spaces.

VISUAL REPEATER

PAGE

66

ELECTRONIC BELLS

PAGE

67

Bell with classic appearance for fire alarm systems and other warnings.

Outdoor red self-po-wered siren made in die-cast aluminium.

SOUNDERS

PAGE

68

Red siren for premises evacuation in complian-ce with with regulation 626/94.

Electromagnetic stop imple-mented in order to keep open fire or transit doors and rele-ase them in case of fire.

ELECTROMAGNETS

PAGE

68

EXPLOSION PROOF SYSTEMS

The optical/acoustic system in-cludes the body of siren T/800S and the body of visual repeater T/800L. These shells are made of a casting of cast iron G-20 uni 5007.

T/800Siren made of a casting of cast iron G-20 uni 5007 with a dif-fusing cone of plastic material (ABS);

T/800SVisual repeater made up of a shell made of a casting of cast iron G-20 uni 5007.

T/800L

PAGE

69

6

ALPHABETIC INDEXPRODUCT’S NAME CODE PAGE PRODUCT’S NAME CODE PAGE

1370/15 MM7100123 68

1370/30 MM7300123 68

1469 SB4600123 20

1471 SB5700123 20

2470 SB4400121 20

3465/24 HS1900123 67

3470 SB4300123 20

4460/24 HS1700123 67

4476/24 HS7300123 67

4479/24 HS7200123 67

82425 SBG PS7900123 70

82450 BG PS8000123 70

AREA 54/16L SC3800121 26

AREA54/1L SC3900121 23

AREA54/4L SC1900121 24

AREA54/8L SC4100121 25

ASD SC2R00123 62

AST AT7100123 62

BP/212 SD3700121 17

BP/212T SD8900121 18

BPA/212 SD3600121 31

BPA/212-T SD5800121 31

BPG/213 CH4 SD3300121 19

BPG/213 GPL SD1J00121 19

BPT/214 SD3500121 18

BTA/206 SD3400121 32

C/54 SC1800121 14

C/7000 SC5200121 16

C/7000-R SC5300121 16

C302 SC6000121 13

CDS SC3600121 49

CONSOLLE/54 KP3400121 32

DBS SD9H10123 62

DFS RT7100123 62

DRS SD8H10123 62

DSE/626 HS2100123 68

DTS RT7200123 62

EM100P MM9000123 68

EM50P MM7000123 68

ES50 SD8P00123 61

ES80 SD9R00123 61

ESPCDS SC3500121 49

FA128 SC3310121 42

FAP541 SC6100121 40

FAP5416 SC6700121 41

FAP544 SC6200121 41

FAP548 SC6600121 41

FDO500 SD4800121 44

FDOT500 SD9K00121 45

FDT500 SD5700121 44

FDTD500 SD9000121 45

FIRE TRACER SC4R00123 62

FKP500 KP5200121 42

FM500 SD6000121 43

FMR500 SB6100121 43

FOGLIO/54 SW2900121 34

HP500F HS5000121 68

INT8C/24V IL1010123 61

INT-SONG/54 HS1010121 15

IO500 SC3A00121 42

IOM500 SC3B00121 42

ISO ZB SC4200121 30

ISO/BASE SC4H00121 29

ISO/BASE-IP SC6G00121 30

ISO/BP SC6H00121 29

ISO/C SC2210121 30

ISO/MINI SC4000121 30

ITS500 IT1610121 43

KATA IL7500123 61

LAN/54 SC7910121 34

LAN/TCP/IP500 IT1510121 43

LR500 SR1100121 66

LR500SI SR1200121 66

MAPPA/54 SW2700121 34

MAPPE/FAP500 SW3600121 43

MAS/DIN-2000 SC2110121 28

MAS/IP-2000 SC8710121 28

MC/19 SC1C10121 27

MCR/DIN-2000 SC9110121 29

MCS/54 SC6810121 17

MGSM500 CT6010121 43

MI/410 SC2010121 28

MI/410-S SC9610121 28

ML7000 SC1A10121 17

MMS/54 SC1B10121 34

MOD/54-E SC2510121 15

MOD/54-R SC2410121 15

MODEM54 CT7300123 34

MPSTN500 CT5910121 43

MR/128 SC2810121 27

MR7000 SC7810121 17

MRS/232/485-DIN SC9310121 34

MSP/54 SC2B10121 23

P 445 SB3500121 20

P/406 SB3000121 70

P/406 SB4300123 20

P/410 SB3600121 33

P/420 SB2100121 33

P/430 SB2200121 33

P/435 SB3900121 33

7

ALPHABETIC INDEXPRODUCT’S NAME CODE PAGE PRODUCT’S NAME CODE PAGE

P 440 SB3800121 19

PICO SC3R00123 62

PUNTO/54 SW3100121 34

R/820 SD3L10121 36

RA/209 SD2B00121 57

RA/209-S SD7L00121 57

RB 1212 RB1110113 70

RB 15 RB0810113 70

RB 19 RB0310113 70

RB 24 RB0510113 70

RB 612 RB0910113 70

RB06 RB0410113 70

RB12 RB0210113 70

RLB/1 SD6P00121 59

RLB/2 SD5P00121 59

RS232/485 IT1410121 42

RTS/2 SD2C00123 57

RTS/4 SD4C00123 58

RTS/6 SD3C00123 58

RU-ADPE SD7100121 56

S/2-100 + INT8 C IL1500123 59

S1604VB SD2T00123 53

S1606CO SD7T00123 53

S1702VB SD3T00123 54

S1703CO SD8T00123 54

S2096BU SD6T00123 53

S2096GP SD4T00123 54

S2096ME SD9S00123 54

S2096PR SD5T00123 53

S2097BU SD4U00123 55

S2097GP SD2U00123 55

S2097ME SD9T00123 55

S2097PR SD3U00123 55

S2097VB SD1U00123 55

S2131CO SD5U00123 55

ADM IL1110123 61

SD500 SD4K00121 46

SD500M SD4S00121 46

SD500R SD5K00121 46

SD500-RM SD6S00121 46

SD515 SD2V00121 46

SF-100 + INT8 C IL1400123 60

SOFT/54 SW2300121

SOFT/FAP500 SW3500121 43

SONG/54 HS0910121 27

SP/410 SC2610121 28

SP/410-S SC4E10121 28

SPTB SF5000121 64

SSM SP7600123 61

ST/PL4 SC6R00123 52

ST/PL4/ESP SC7R10123 52

ST/S3REL SC5R10123 57

STG/BOX ST0510123 53

STG/IN8 SC9R10123 53

STG/MTSLB SC8R00123 52

STG/OUT16 SC1S10123 53

T/800 FH3500121 69

T/800L SR0200121 69

T/800S HS1800121 69

TB24 FH2700121 65

TLG/54 SW2800121 34

TM220 FH2800121 65

TM224 FH3100121 65

TM24 FH2600121 64

TMSV FH5400121 65

VAL TEST SI7100123 56

WMB/138V15 ST0610123 53

ZB/200 SD2700121 36

ZB/201 SD2800121 36

ZB/204 SD9D00121 36

ZB/210 SD4300121 36

ZB/212 SD1N00121 36

ZB/215 ZC7100121 36

8

CONVENTIONALFIRE DETECTIONSYSTEMS

C/302 .............................13C/54 ...............................14C/7000 ...........................16DETECTORS ...................17BUTTONS .......................20

ADDRESSEDFIRE DETECTION SYSTEMS

AREA 54/1 .....................23AREA 54/4 .....................24AREA 54/8 .....................25AREA 54/16 ...................26DETECTORS ...................31CENTRALIZATION............34

UNIVERSALBASESDUCTED DETECTION

UNIVERSAL BASES .........36DUCTED DETECTION .......36

FAP 500DIGITALSYSTEMS

FAP 541 .........................40FAP 544 .........................41FAP 548 .........................41FAP 5416 .......................41ACCESSORIES ................43DETECTORS ...................44

EXTINGUISHINGCONTROL UNIT

EXTINGUISHING C.U. .......48

SPECIALDETECTORS

GAS DETECTION C.U. ......52GAS DETECTORS ............53FLAME DETECTORS ........56SPECIAL HEAT DET .........57LINEAR DETECTORS .......59SUCTION SYSTEMS ........62

OPTICALACOUSTICINDICATORS

PANEL ............................64OPTICAL REPEATER ........66BELLS ............................67SOUNDERS ....................68ELECTROMAGNETS .........68EXPLOSION PROOF . .......69

IND

EX

10

CONVENTIONALFIRE DETECTION

SYSTEMSC/302 CONTROL UNIT ................pag. 13

C/54 CONTROL UNIT ..................pag. 14

C/7000 CONTROL UNIT ..............pag. 16

CONVENTIONAL DETECTORS .....pag. 17

CONVENTIONAL BUTTONS .........pag. 20

11

Conventional fire detection system by Elkron is proved to be the ideal system for all the systems which do not need a large extent to be available.Anyhow, central unit models, of which one is expandable up to 16 lines with 32 detectors, allow to implement systems fully covering any small to medium firm typology and are proved to be perfectly suitable for residential installations too.The system is completed by its wide range of smoke detectors, gas detectors, pushbuttons and relating signalling.

CONVENTIONAL SYSTEMS

CONVENTIONAL FIRE DETECTION SYSTEMS

1

32 MAX points per zone

2

3

4

1

2

3

CONTROL UNIT ZONES

EXPANSION MODULE (N.4)

4

32 MAX points per zone

ML70004 Zone

Expansion

MR70004 actuation

relays module

Bells/PanelsOutput

MCS/54PrinterModule

1

32 MAX points per zone

2

3

4

CONTROL UNIT ZONES (N.4)

MOD/54RActuators

module

Bells/PanelsOutput

MOD/54-EElectrovalve

OutputModule

C/54 SYSTEM

C/7000 SYSTEM

12

Control Unit C/302

C/302 cod. SC6000121Single Zone central unit, with microprocessor in polycarbonate, suitable for controlling fire stop doors.

Internally provided with a smoke optical detector and a heat probe having 60° •C intervention threshold.The unit is capable to manage either up to 15 (optic or heat) conventional •detectors or 2 gas detectors (BPG/213 model) on a conventional line set to single permission.Output for electromagnets; the output is capable to support up to 6 •electromagnets.Supply voltage: 230 Vac 50 Hz•Output voltage: 24 Vdc•Max current: 300 mA•Smoke detector: Optical with Tyndall effect•Heat detector: Heat probe calibrated to 60° C•Visual alarm: 1 red led, 1 24 V 2W lamp•Sound alarm: Buzzer•Operation temperature: -10°C to +50°C•Alarm relay output: 1A @ 30 Vdc•Protection degree: IP 32•Dimensions (HxLxD): 71 x 283 x 113mm•Weight (not including batteries): 700 g•

SINGLE ZONE CONTROL UNIT

C/302

CONVENTIONAL FIRE DETECTION SYSTEMS

13

C/54 Control Unit

C/54 cod. SC1800121Compact central unit, with microprocessor, suitable for small size fire and gas systems.

Composed of a red plastic enclosure made in ABS for wall mounting. •Italian or English language front side. •The unit has four independent detection lines, with maximum capacity of 30 •devices per line. Each detection line corresponds to a single zone and can be set to either single or double permission.The central unit is also equipped with a dry contact relay output for failure, •a controlled line for bells and sirens and an output for electromagnets control.The central unit is equipped with an electronic circuit to recharge and control •the batteries.Leak towards the earth signalling on central unit panel.•Mechanical key to enable programming functions and/or commands •(silencing, resetting, cutting off, etc.) Facility for adding, into the central unit, an optional module allowing to have •either 8 zone relay outputs or a module allowing to control a solenoid valve (MOD54E).Number of zones: 4, independent•Max number of detectors per zone: 30 (Smoke, heat, pushbuttons)•In compliance with EN 54 parts 2 – 4 •Supply voltage: 230 Vac 50 Hz•Output voltage: 23 Vdc – 27.6 Vdc•Max current: 500 mA•Assignable batteries: 2 x 12V – 7.5 Ah•Failure central repetition: 1 A 30Vdc relay•Controlled siren output•Output for electromagnets•Relative Humidity: 95 % Max RH non condensing•Operation temperature: -5° to +50° C•Protection degree: IP 32•Dimensions (HxLxD): 386 x 269 x 96 mm•Weight (not including batteries): 2,7 Kg•Accessories: control module for siren line (INT-SONG/54 or SONG/54)•Control board for solenoid valve (MOD/54-E), Board with 4 relays for line alarms (MOD/54-R)

FOUR ZONE CONTROL UNIT

CONVENTIONAL FIRE DETECTION SYSTEMS

C/54

14

Accessories for C/54 control unit

MOD/54-R cod. SC2410121Module allowing C/54 central unit to increment and differentiate actuation control for each zone.

The module has 4 aggregated relays (NC or NO max. 1A - 30 VDC): Alarm •1 - Alarm 2 - Exclusion - Mains failure. Each Zone has:•One controlled output for plates, sirens or bells. •One output for either electromagnets or self-powered siren. •One exchange dry contact relay (Closed - Normally Closed - Normally Open •max. 1 A - 30 VDC), that can be set on either Alarm 1 (Default) or Alarm 2 events.Max current which can be supplied by module: 500 mA•

MOD/54-E cod. SC2510121Module allowing C/54 central unit to have a dedicated output for controlling a solenoid valve by a programmable activation lag.

The module has 4 aggregated relays (NC or NO max. 1A - 30 VDC): Alarm •1 - Alarm 2 - Exclusion - Mains failure. The module also has following outputs:•

N° 1 line for manually resetting solenoid electrovalve N° 1 output line for the optical/acoustic signalling that cannot be silenced.

Max current which can be supplied by module: 500 mA•

SONG/54 cod. HS0910121Module to check and actuate bells/plates/sirens.

It is to be used on controlled outputs in central units.•The module is to be installed immediately near the device to be checked.•Dimensions (HxL): 25x30 mm•

INT-SONG/54 cod. HS1010121Intermediate module to check and actuate bells/plates/sirens.

It is to be used on controlled outputs in central units.•The module is to be installed immediately near the device to be checked.•Dimensions (HxL): 25x30 mm•

FOUR ZONE CONTROL UNIT

CONVENTIONAL FIRE DETECTION SYSTEMS

MOD/54-R

MOD/54-E

SONG/54

INT-SONG/54

15

C/7000

C/7000 cod. SC5200121Modular conventional fire detection central unit, with 16 bit microprocessor, 4 detection zones expandable up to 16.

Software in 2 languages (Italian and English), which can be selected by user.•Facility for connecting up to 32 devices per zone.•Facility for associating a 16-character text per zone / zone group.•Backlit alphanumeric display with 4 lines by 20 characters.•6 programmable access passwords.•Relay actuation control independent of the zones. •Central unit walk test with programmable self-resetting time.•Evacuation function (Master Alarm) which can be either actuated from •keyboard or associated to a single zone. Chronological history log with 50 events.•Programmable central unit alarm timing.•Auxiliary input which can be set by resetting, acquisition or Master Alarm.•Number of zones: 4, independent, expandable to 16 •Max number of detectors per zone: 32 (Smoke detectors, heat detectors, •pushbuttons)Backlit LCD display with 4 lines by 20 characters.•6 programmable access passwords•In compliance with EN 54 parts 2 – 4•Chronological history log with 50 events.•Supply voltage: 230 Vac 50 Hz •Output voltage: 27.6 Vdc •Max Current: 500mA•Assignable batteries: 2 x 12V – 7.5 Ah•Signalling outputs: 2 Alarm relays of 3 A 30Vdc prog. for Alarms 1 2 3•

1 Failure relay of 3 A 30Vdc (Closed /NO or Closed/NC) 1 Programmable relay of 3 A 30Vdc (C/NO or C/NC)

Controlled siren outputs•Operation temperature: -5° to +50° C•Relative humidity: 93 % non condensing •Protection: IP 31 •Dimensions (HxLxD): 454x377x132 mm•Weight (not including batteries): 9 Kg•

C/7000-R cod. SC5300121Same characteristics of C/7000 but with 4 relays freely programmable •on board

MODULAR CONTROL UNIT 4 UP TO 16 ZONES

CONVENTIONAL FIRE DETECTION SYSTEMS

C/7000

16

Accessories for C/7000 control unit

SONG/54 cod. HS0910121Control module for siren line.

INT-SONG/54 cod. HS1010121Intermediate control module for siren line.

ML7000 cod. SC1A10121Expansion module for 4 lines.

MR7000 cod. SC7810121Expansion module for 4 relays.

MCS/54 cod. SC6810121Module for connecting a printer.

MODULAR CONTROL UNIT 4 UP TO 16 ZONES

CONVENTIONAL FIRE DETECTION SYSTEMS

Optical Smoke Detector

BP/212 cod. SD3700121Low profile conventional optical smoke detector.

Correct operation signalling is from a flashing green led placed on the cap.•Alarm signalling is from a red led placed on the cap.•On the detector there are two open collector outputs, one for correct •operation signalling, the other for alarm signalling.A detector characteristic feature is its intervention threshold self-adjusting •capability on its being put on.Correct operation green led•Alarm red led •Alarm output: 100 mA (O.C.)•Operation principle: Tyndall effect•Supply voltage: 11 – 30 Vdc•Alarm repetition: O.C. 100 mA max•Operation repetition: O.C. 10 mA max•Absorption: 100 µA 18 Vdc at rest , 22 mA 18 Vdc on alarm status•Magnetic test •Operation temperature: da –20 a +50 °C•Relative humidity: 95% max non condensing•EN 54 part 7 certified. •Associable to following bases: ZB/200, ZB/201, ZB/204•Dimensions (HxLxD): Ø 100 x H 45 mm•

CONVENTIONAL DETECTORS

ML7000

MR7000

MCS/54

BP/212

17

Optical heat detector

BP/212 T cod. SD8900121Low profile conventional optic heat detector with heat probe having 70° C intervention temperature.

Correct operation signalling is from a flashing green led placed on the cap.•Alarm signalling is from a red led placed on the cap.•On the detector there are two open collector outputs, one for correct •operation signalling, the other for alarm signalling.Correct operation green led•Alarm red led •Alarm output: 100 mA (O.C.)•Operation principle: Tyndall effect•Supply voltage: 11 – 30 Vdc•Alarm repetition: O.C. 100 mA max•Operation repetition: O.C. 10 mA max•Absorption: 100 µA 18 Vdc at rest 22 mA 18 Vdc on alarm status•Magnetic test •Operation temperature: da –20 a +50 °C•Relative humidity: 95% max non condensing•EN 54 part 7 certified. •Associable to following bases: ZB/200, ZB/201, ZB/204•Dimensions: Ø 100 x H 45 mm•

Differential heat detector

BPT/214 cod. SD3500121Low profile conventional (thermo-speedometric) differential ratio of rise heat detector with 58°C maximum intervention temperature.

Correct operation signalling is from a flashing green led placed on the cap.•Alarm signalling is from a red led placed on the cap.•Correct operation green led•Alarm red led •Alarm output: 100 mA (O.C.)•Operation principle: pair of heat probes•Supply voltage: 11 – 30 Vdc•Alarm repetition: O.C. 100 mA max•Absorption: 100 µA 18 Vdc at rest 22 mA 18 Vdc on alarm status•In compliance with EN 54 part 5•Magnetic test •Operation temperature: –20 a +50 °C•Relative humidity: 95% max non condensing•Associable to following bases: ZB/200, ZB/201, ZB/204•Dimensions: Ø 100 x H 45 mm•

CONVENTIONAL DETECTORS

BP/212T

BPT/214

CONVENTIONAL FIRE DETECTION SYSTEMS

18

METHANE gas detector

BPG/213 CH4 cod. SD3300121Methane gas detector with semiconductor (semiconductor head FIGARO) ha-ving 2 intervention thresholds which can be calibrated and are independent.

Both alarm thresholds are stored and transmit, to control central unit, two •quite differentiated signals allowing to operate by steps on actuations on field.Operation voltage: 12 – 30 Vdc•Average absorption with fixed supply: 45 mA a 27 Vdc•Pre-alarm absorption: 20 mA a 18 Vdc•Alarm absorption: 40 mA a 18 Vdc•Alarm signal repetition: 100 mA (O.C.)•Pre-alarm visual repetition: yellow led•Visual alarm repetition: red led•Relative humidity: 95% max non condensing•Adjustable alarm threshold: 5% to 100% E.L.L.•Detectable gasses: methane•Dimensions: Ø 100 x H 45 mm•

GPL gas detector

BPG/213 GPL cod. SD1J00121GPL gas detector with semiconductor (semiconductor head FIGARO) having 2 intervention thresholds which can be calibrated and are independent.

Both alarm thresholds are stored and transmit, to control central unit, two •quite differentiated signals allowing to operate by steps on actuations on field.Operation voltage: 12 – 30 Vdc•Average absorption with fixed supply: 45 mA a 27 Vdc•Pre-alarm absorption: 20 mA a 18 Vdc•Alarm absorption: 40 mA a 18 Vdc•Alarm signal repetition: 100 mA (O.C.)•Pre-alarm visual repetition: yellow led•Visual alarm repetition: red led•Relative humidity: 95% max non condensing•Adjustable alarm threshold: 5% to 100% E.L.L.•Detectable gasses: GPL•Dimensions: Ø 100 x H 45 mm•

CONVENTIONAL DETECTORS

Buttons

P440 cod. SB3800121Red alarm conventional pushbutton with recommissioning.

Visual alarm repetition: red led•Weight: 100 g•Alarm absorption: 20 mA @ 18 Vdc•Actuation Type: Recommissioning•Dimensions (HxLxD): 110 x 110 x 42 mm•

CONVENTIONAL PUSH BUTTONS

BPG/213 CH4

BPG/213 GPL

P440

CONVENTIONAL FIRE DETECTION SYSTEMS

19

Buttons

P445 cod. SB3500121Red alarm conventional pushbutton with breaking.

Visual alarm repetition: red led•Alarm absorption: 20 mA @ 18 Vdc•Actuation Type: Breaking•EN54 part 1•Weight: 100 g•Dimensions (HxLxD): 110 x 110 x 42 mm•

1469 cod. SB4600123Break glass outdoor red alarm conventional pushbutton made in die-cast aluminium.

Alarm absorption: 20 mA @ 18 Vdc •Actuation Type: Breaking•Protection degree: IP 65•Alarm resistance: 820 ohm 2W•Weight: 400 g•Dimensions (HxLxD): 95x95x 42 mm•

2470 cod. SB4400121Break glass red alarm conventional pushbutton with transparent protection cover.

Visual alarm repetition: red led•Weight: 180 g•Alarm absorption: 20 mA @ 18 Vdc •Actuation Type: Breaking•Protection degree: IP 54•Alarm resistance: 820 ohm 2W•Dimensions (HxLxD): 85x85x52 mm•

3470 cod. SB4300123Break glass red alarm conventional pushbutton.

Visual alarm repetition: red led•Weight: 120 g•Alarm absorption: 20 mA @ 18 Vdc •Actuation Type: Breaking•Protection degree: IP 30•Alarm resistance: 820 ohm 2W•Dimensions (HxLxD): 84 x 120 x 31 mm•

P/406 cod. SB3000121Pushbutton for fire manual signalling, with explosion proof shell, for areas with a potentially explosive atmosphere.

Hammer for glass breaking provided. Pushbutton made of diecast material, •red colour epoxy painting.Cable entry holes: 2x3/4 gas•Classified: II 2GD EEx d IIB T6, EEx d IIB + H2 T6•Certified: CESI 03 ATEX 050•Operation temperature: -20 C° to + 50 C°•Weight: 1.1 kg•

1471 cod. SB5700123Hammer

CONVENTIONAL PUSH BUTTONS

CONVENTIONAL FIRE DETECTION SYSTEMS

P445

1469

2470

3470

P/406

20

ADDRESSEDFIRE DETECTION

SYSTEMSAREA 54/1 ................................pag. 23

AREA 54/4 ................................pag. 24

AREA 54/8 ................................pag. 25

AREA 54/16 ..............................pag. 26

ACCESSORIES ...........................pag. 27

DETECTORS ..............................pag. 31

BUTTONS ..................................pag. 33

CENTRALIZATION.......................pag. 34

21

A technological innovation from Elkron-Sira proposes a last generation multiprocessor fire analo-gue detection system. It is a system for all applications, even the widest ones, and for all environ-mental typologies. AREA54 series is provided with central units from 1 loop, for 128 addresses, up to 32 loops, for 4,096 addresses. The system can be fully managed and programmed either directly from local keyboard or smoothly by PC, via dedicated software (SOFT/54).

ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

BPA/212 + ZB200

AREA54/4

LR500

P430

BTA/206 + ZB200

LR500

MAS/DIN-2000 PANEL

MI/410

EXTERNALPOWER SUPPLY UNITS

BPA/212 + ZB200

SP/410 LINEARDETECTOR

PROGRAMMINGSOFTWAREMAPPINGSOFTWARE

REMOTEPANELS

RS232

RS485

MR/128

LOOP LINE128 MAXDEVICES

22

AREA54/1L Control Unit

AREA54/1L cod. SC3900121Analogue central unit, with 16 bit microprocessor, to manage fire systems with single detection line.

It is possibile to connect up to 128 out of smoke detectors, gas detectors, •heat detectors, pushbuttons actuators and interfaces to control external equipment can be connected.Detection line can be programmed in following configurations:•

4 open lines (max 32 devices per line) 1 loop line (max 128 devices) 2 loop lines (max 64 devices per line).

1 RS232 output towards PC•LCD display with 8 lines by 40 characters•Event log: 1000 events•Signalling outputs:•

Alarm Relay 1 or 3 (1A@30 Vdc), NO/NC contact Alarm Relay 2 (5A@30 Vdc) Failure or exclusion Relay (5A @ 30 Vdc) NO/NC contact Network in Relay (1A @ 30 Vdc) NO/NC contact

Controlled siren output for optical/acoustic indicators•Controlled output for self-powered sirens•In compliance with EN54/2-4•Input voltage: 230 Vdc 50 Hz•Ouput voltage: 27 Vdc 500 mA•Battery management, check and charge: 700 mA•Assignable batteries: max 2 x 12V – 15 Ah•Operation temperature: -5 to + 50°C•Base made in metal sheet and front side made in ABS.•Dimensions (HxLxD): 450 x 350 x 160 mm.•

Accessories for AREA54/1L control unit

MSP/54 cod. SC2B10121Module allowing Console 54, printer and a PC workstation to be connected to AREA54/1 central unit.

CENTRONICS opto-isolated port for connecting a printer•RS 232 opto-isolated output for connection to a personal computer•485 opto-isolated output for connecting remote panels•Dimensions (HxL): 160x65•

128 ADDRESSES CONTROL UNITS

ADDRESSED FIRE DETECTION SYSTEMS

MSP/54

AREA54/1L

23

AREA54/4L Control Unit

AREA 54/4L cod. SC1900121Modular analogue central unit, with multiprocessor, having 4 LOOPs max.

The unit is provided with base with 1 MR/128 module (128 addresses).•Expandable up to 512 addresses by 3 additional line modules.•By a two-lead closed or open loop detection line, up to 128 out of smoke •detectors, gas detectors, heat detectors, pushbuttons, actuators and interfaces to control external equipment can be connected to each module.1 RS232 opto-isolated bi-directional output towards PC.•1 RS485 opto-isolated serial output for communication from and to remote •keyboard.LCD display with 8 lines by 40 characters.•Programming from keyboard and PC. •120 software zones.•60 device groups.•60 zone assemblies.•Event log: 1000 events.•Signalling outputs:•

Alarm 1, Alarm 2, Alarm 3 relays Failure relay Exclusion relay Network in relay

Controlled output for self-powered external siren.•Controlled output for self-powered external siren.•Controlled siren output for optical/acoustic indicators.•In compliance with EN54/2-4.•Input voltage: 230 Vdc 50 Hz.•Ouput voltage: 27 Vdc max 1.5A.•Battery management, check and charge: 700 mA.•Casing: steel painted with epoxy powders.•Assignable batteries: max 2 x 12V – 15 Ah.•Operation temperature: -5 to + 50°C.•Available also in Rack 19” version.•LCD display with 16 lines by 40 characters.•Dimensions (HxLxD): 400 x 480 x 136 mm.•

4 LOOP CONTROL UNIT

ADDRESSED FIRE DETECTION SYSTEMS

AREA 54/4L

24

AREA54/8L Control Units

AREA54/8L cod. SC4100121Modular analogue central unit, with multiprocessor, having 8 LOOPs max.

The unit is provided with 1 MR/128 module (128 addresses).•Expandable up to 1024 addresses by 7 additional line modules.•By a two-lead closed or open loop detection line, up to 128 out of smoke •detectors, heat detectors, gas detectors, pushbuttons, actuators and interfaces to control external equipment can be connected to each module.1 RS232 opto-isolated bi-directional output towards PC.•1 RS485 opto-isolated serial output for communication from and to remote •keyboard.LCD display with 16 lines by 40 characters•Programming from keyboard and PC.•240 software zones.•120 device groups.•120 zone groups•Event log: 1000 events•Signalling outputs:•

Alarm 1 relay, Alarm 2, Alarm 3 Failure relay Exclusion relay Network in relay

Controlled output for self-powered external siren.•Controlled siren output for optical/acoustic indicators. •In compliance with EN54 part 4 N°1293 - CPD - 0040 and EN 54 part 2•Input voltage: 230 Vdc 50 Hz•Ouput voltage: 27 Vdc max 1.5A•Battery management, check and charge: 700 mA•Casing: steel painted with epoxy powders •Dimensions (hxlxd): 500x482x145 mm•Assignable batteries: max 2 x 12V – 15 Ah•Operation temperature: -5 to + 50°C•Available also in Rack 19” version•LCD display with 16 lines by 40 characters•1 MC/19 module for an independent repetition of the alarm, failure and •exclusion status of each line

EXPANDABLE CONTROL UNITS (UP TO 1024 ADDR.)

ADDRESSED FIRE DETECTION SYSTEMS

AREA 54/8L

25

AREA54/16L Control Unit

AREA54/16L cod. SC3800121Modular analogue central unit, with multiprocessor, having 16 LOOPs max. The unit is provided with base with 1 MR/128 module (128 addresses).

Expandable up to 2048 addresses by 15 additional line modules.•By a two-lead closed or open loop detection line, up to 128 out of smoke •detectors, gas detectors, heat detectors, pushbuttons, actuators and interfaces to control external equipment can be connected to each module.1 RS232 opto-isolated bi-directional output towards PC.•1 RS485 opto-isolated serial output for communication from and to remote •keyboard.LCD display with 16 lines by 40 characters.•Programming from keyboard and PC.•480 software zones.•240 device groups.•240 zone groups.•Event log: 1000 events•Signalling outputs:•

Alarm 1 relay, Alarm 2, Alarm 3 Failure relay Exclusion relay Network in relay

Controlled output for self-powered external siren.•Controlled siren output for optical/acoustic indicators. •In compliance with EN54/2-4•Input voltage: 230 Vdc 50 Hz•Ouput voltage: 27 Vdc max 1.5A•Battery management, check and charge: 700 mA•Casing: steel painted with epoxy powders •Assignable batteries: max 2 x 12V – 15 Ah•Operation temperature: -5 to + 50°C•Available also in Rack 19” version•LCD display with 16 lines by 40 characters•2 MC/19 module for an independent repetition of the alarm, failure and •exclusion status of each line.Dimensions (HxLxD): 770 x 482 x 155 mm•

EXPANDABLE CONTROL UNITS (UP TO 1024 ADDR.)

ADDRESSED FIRE DETECTION SYSTEMS

AREA 54/16L

26

Line Module

MR/128 cod. SC2810121Addressable line module allowing to acquire, pilot and check a closed or open type detection line on which up to 128 addressed devices can be mounted.

Fully managed by microprocessor.•RS485 57600 bps serial asynchronous communication.•Autonomous operation in case of control unit failure.•Managed by microprocessor.•Module addressing 1 – 32.•Relay for release from RS485 in case of failure.•27 Vdc supply.•Dimensions (hxl): 110 x 65 mm.•

Modules

MSP/54 cod. SC2B10121Module allowing a parallel 80 column printer with continuous form to be connected.

Dimensions (hxl): 185 x 45 mm•

SONG/54 cod. HS0910121Module to check and activate bells/plates/sirens. It is to be used on con-trolled outputs in central units.

The module is to be installed immediately near the device to be checked.•Dimensions (hxl): 25 x 30 mm.•

INT-SONG/54 cod. HS1010121Module to check and activate bells/plates/sirens. It is to be used on con-trolled outputs in central units.

The module is to be installed immediately near the device to be checked.•Dimensions (hxl): 25 x 30 mm.•

MC/19 cod. SC1C10121Independent display panel of the alarm, failure and exclusion status of each line.

The module only concerns AREA54 central units with 8 or 16 lines in Rack •19” version.Dimensions (hxlxp): 89 x 482 x 28 mm.•

ACCESSORIES FOR ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

MSP/54

MR/128

SONG/54

INT-SONG/54

MC/19

27

Modules

SP/410 cod. SC2610121Analogue addressed multi-purpose interface allowing to control dry contact equipment or input for impulsive contacts and to reset connected equipment, e.g. linear detectors, bathe tie rods or normally open pushbuttons, etc.

Working voltage: 18 Vdc modulated•Assorbimento medio: 150 µA.•Average absorption: 150 µA.•Operation temperature: -20° C to + 50° C. •Relative humidity: 95 % Max RH non condensing. •Dimensions (DIN guide) (HxLxD): 44 x 110 x 21 mm.•

SP/410-S cod. SC4E10121Same as SP/410 but in IP55 enclosure.

Dimensions (hxlxp): 105 x 170 x 82 mm.•

MI/410 cod. SC2010121Analogue addressed interface allowing to control equipment with dry and not impulsive contacts, e.g. pushbuttons, switches, technological contacts, heat sensing cables, by using proper connection.

Working voltage: 18 Vdc modulated.•Average absorption: 100 µA•Alarm repetition (O.C): 100 mA Max•Visual Alarm repetition: red led•Operation temperature: -20°C to + 50°C•Relative humidity: 95 % Max RH non condensing•Dimensions (HxLxD): 44 x 67 mm.•

MI/410-S cod. SC9610121Same as MI/410 but in IP55 version.

Dimensions (HxLxD): 90 x 130 x 58 mm.•

MAS/DIN-2000 cod. SC2110121Analogue addressed actuation module allowing to manage accessory devices arranged on field (plates, sirens, shutters, auxiliary relays, electromagnets, etc.).

The module has 4 open collector electronic repetitions (100mA) which define •fault, alarm 1, alarm 2, reset conditions and a repetition with the switching by a relay which can be preselected via a jumper in order that the module can operate in case of failure, alarm 1, alarm 2 or reset.Supply voltage: 20÷30Vdc•Working voltage: 18 Vdc modulated•Rest absorption: 200 mA•Alarm absorption: 30 mA •Alarm repetition (O.C): 100 mA max•Relay output: 1A @ 24Vdc•Operation temperature: -10 ÷ 50°C •Dimensions (HxLxD): 65 x 110 x 35 mm.•

MAS/IP-2000 cod. SC8710121Same as MAS/DIN-2000 but in IP55 version.

Dimensions (HxLxD): 105 x 170 x 82 mm.•

ACCESSORIES FOR ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

SP/410

MI/410

MAS/DIN-2000

28

Modules

MCR/DIN-2000 cod. SC9110121Analogue addressed module with collective addressing. The module allows to manage a secondary line, made up of conventional detectors. Max number of elements is 10.

The interface has 4 O.C. repetitions and 4 relays for failure, alarm 1, alarm •2 reset status.Supply voltage: 20÷30Vdc•Working voltage: 18Vdc modulated•Rest absorption: 1 mA•Alarm absorption: 20 mA per alarmed relay•Repetition outputs (O.C.): 100 mA max•Relay output: 1A @ 24Vdc •Operation temperature: -10÷50°C •Dimensions (HxLxD): 112 x 168 x 50 mm.•

ISO/BP cod. SC6H00121Short-circuit analyser module for lines for analogue detections; the module is designed to ensure the operation of the detectors and/or pushbuttons that are connected to the same line, in case a short-circuit occurs.

The module is contained in smoke detector cap. •On the two sides of the cap there are yellow leds having the task of signalling •the section where the short-circuit is being detected. For detection line connection, ZB/200 base is used.•The module needs no additional power supply.•Working voltage: 18 Vdc modulated•Average absorption: 250 µA•Operation temperature: -20°C to + 50°C•Protection degree: IP 43•Dimensions: Ø 100 mm H.45 mm•

ISO/BASE cod. SC4H00121Short-circuit analyser module for lines for analogue detections; the module is designed to ensure the operation of the detectors and/or pushbuttons that are connected to the same line, in case a short-circuit occurs.

Yellow leds having the task of signalling the section where the short-circuit is •being detected.The module is contained in ZB/215 connector block.•The module needs no additional power supply.•Working voltage: 18 Vdc modulated•Average absorption: 250 µA•Operation temperature: -20°C to + 50°C•Relative humidity: 95 % Max RH non condensing •Dimensions: Ø 100 mm H.45 mm•

ACCESSORIES FOR ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

MCR/DIN-2000

ISO/BP

ISO/BASE

29

Modules

ISO/C cod. SC2210121Short-circuit analyser module for lines for analogue detections; the module is designed to ensure the operation of the detectors and/or pushbuttons that are connected to the same line, in case a short-circuit occurs.

Yellow leds having the task of signalling the section where the short-circuit is •being detected.The module is contained in S/215 connector block.•The module needs no additional power supply.•Working voltage: 18Vdc modulated•Average absorption: 250 µA•Operation temperature: -20 to + 50°C•Relative humidity: 95 % Max RH non condensing •Dimensions: Ø 100 mm H 45 mm•

ISO/BASE-IP cod. SC6G00121Same as ISO/C but in IP55 version.

Dimensioni (hxlxp): 90x130x58 mm.•

ISO ZB cod. SC4200121Short-circuit analyser module for lines for analogue detections; the module is designed to ensure the operation of the detectors and/or pushbuttons that are connected to the same line, in case a short-circuit occurs.

The module is contained in a ZB200 base•The module needs no additional power supply.•Working voltage: 18Vdc modulated•Average absorption: 250 µA•Operation temperature: -20 to + 50°C•Relative humidity: 95 % Max RH non condensing •Dimensions: Ø 100 mm H 45 mm•

ISO/MINI cod. SC4000121Short-circuit analyser module for lines for analogue detections; the module is designed to ensure the operation of the detectors and/or pushbuttons that are connected to the same line, in case a short-circuit occurs.

The module is contained in S/215 connector block.•The module needs no additional power supply.•Working voltage: 18Vdc modulated•Average absorption: 250 µA•Operation temperature: -20 to + 50°C•Relative humidity: 95 % Max RH non condensing •Dimensions: Ø 100 mm H 45 mm•

ACCESSORIES FOR ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

ISO/C

ISO/BASE-IP

30

Optical Detector

BPA/212 cod. SD3600121Low profile smoke optical addressed analogue detector.

Visual operation signal is provided by two red leds placed on the cap, which •flashes at each call from the central unit. The alarm signal from the central unit puts leds on steady.•Operation principle: Tyndall effect•Supply voltage: 18 Vdc modulated•Absorption: 280 µA at rest•Alarm repetition: O.C. 100 mA max•Visual alarm repetition: 2 red leds•Dimensions: Ø 100 x H 45 mm•Magnetic test•Operation temperature: –20 to +55 °C•Relative humidity: 95% max non condensing•EN 54 part 7 certified•Associable to following bases: ZB/200, ZB/201, ZB/204•

Optical heat detector

BPA/212-T cod. SD5800121Low profile optic heat addressed analogue detector with heat probe with intervention temperature.

Visual operation signal is provided by two red leds placed on the cap, which •flashes at each call from the central unit. The alarm signal from the central unit puts leds on steady.•Operation principle: Tyndall effect+heat probe•Supply voltage: 18 Vdc modulated•Absorption: 280 µA at rest•Alarm repetition: O.C. 100 mA max•Visual alarm repetition: 2 red leds•Dimensions: Ø 100 x H 45 mm•Magnetic test•Operation temperature: –20 to +55 °C•Relative humidity: 95% max non condensing•Protection degree: IP 43•Associable to following bases: ZB/200, ZB/201, ZB/204•

DETECTORS FOR ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

BPA/212

BPA/212T

31

Differential HEAT DETECTOR

BTA/206 cod. SD3400121Low profile maximum temperature thermo-speedometric and heat addres-sed analogue detector.

Visual operation signal is provided by two red leds placed on the cap, which •flashes at each call from the central unit. The alarm signal from the central unit puts leds on steady.•Operation principle: Double heat probe•Supply voltage: 18 Vdc modulated•Absorption: 300 µA at rest•Alarm repetition: O.C. 100 mA max•Visual alarm repetition: 2 red leds•Size: Ø 100 x H 45 mm•Magnetic test•Operation temperature: –20 to +55 °C•Relative humidity: 95% max non condensing•EN 54 part 5 certified•Associable to following bases: ZB/200, ZB/201, ZB/204.•

DETECTORS FOR ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

Consolle 54

CONSOLLE/54 cod. KP3400121Remote Panel useful for repeating and displaying active events and comman-ds from and to the Central Units of AREA 54 series.

The panel is housed in a enclosure the design of which was studied in order •that the panel can be used both as a desk panel and wall panel.AREA 54 series can manage up to 32 remote panels placed at a maximum •distance of 1200 m.Backlit display with 8 lines by 20 characters displays and repeats all events •occurring at the central unit. A backlit keyboard provided with specific keys for commands from and to the •Central Unit is available to user.From the keyboard, events from the central unit can be acquired, lag time •for alarm can be incremented if programmed at the central unit, sirens can be entered /cut off, a general reset can be performed and a functional test can be made on all visual signalling (LED).Alarm and Fault status is acoustically signalled by a local buzzer, which is •disabled from the keyboard.Supply voltage: 17 to 30 Vdc•Absorption: 70 mA @ 24 Vdc at rest• 200 mA @ 24 Vdc with lit keyboard and display•Connection: 4-lead bus 485 •Alarm output: Relay 1 A @ 30Vdc•Operation temperature: -5° C to + 50° C•Relative humidity: 95 % maximum non condensing•Protection degree: IP 43•Dimensions (HxLxD): 195 x 290 x 50 mm.•

REMOTE PANEL

BTA/206

CONSOLLE/54

32

Buttons

P/430 cod.SB2200121Red alarm analogue pushbutton with recommissioning.

Visual alarm repetition: red led•Dimensions (HxLxD): 110 x 110 x 42 mm•Weight: 100 g•Average absorption: 100 µA @ 18 Vdc•Actuation Type: Recommissioning•

P/435 cod. SB3900121Red alarm conventional pushbutton with breaking.

Visual alarm repetition: red led•Dimensions (HxLxD): 110 x 110 x 42 mm•Weight: 100 g•Average absorption: 100 µA @ 18 Vdc•Actuation Type: Breaking•

P/410 cod. SB3600121Break glass addressed analogue pushbutton with accident-prevention glass red in colour.

Visual alarm repetition: red led•Average absorption: 100 µA @ 18 Vdc•Alarm repetition: 100 mA. Max. •Dimensions (HxLxD): 64x120x555 mm•Weight: 120 g•Protection degree: IP 30•

P/420 cod. SB2100121Break glass addressed red alarm analogue pushbutton with transparent protection cover.

Visual alarm repetition: red led•Dimensions (HxLxD): 85x85x52 mm•Weight: 180 g•Average absorption: 100 µA @ 18 Vdc •Actuation Type: Breaking•Protection degree: IP 54•

BUTTONS FOR ADDRESSED SYSTEMS

ADDRESSED FIRE DETECTION SYSTEMS

P/430

P/435

P/410

P/420

33

Centralisation

MRS/232/485-DIN cod. SC9310121Module to convert signals from RS232 to RS485 allowing serial communi-cation between apparatuses up to 1,200 mt distance.

Available also in IP 55 version, MRS/232/485-IP coded.•Power supply: 12 – 24 Vdc •Absorption: 50 mA •Operation: -5° C to + 50 °C •Dimensions (HxLxD): 67x112x45 mm•

MAPPA/54 cod. SW2700121Software for graphic map system, capable to connect up to 18 central units through serial line, LAN network or modem.

For system configuration it is necessary to insert graphic map sheets •(SHEET/54) and devices on field (POINT/54).

MMS/54 cod. SC1B10121Module enabling the central units of AREA54 series to following functions:- Connecting and managing a modem - Connecting central units in Master / Slave configuration.

Dimensions (hxl): 180X65 mm•1 serial connector 485 for connecting Master/Slave central units.•1 connector DB9 for connection to modem•

MODEM54 cod. CT730012356K analogue modem

LAN/54 cod. SC7910121Module allowing connection to a LAN (Local Area Network) of analogue cen-tral units of AREA 54 series.

Communication protocol is of TCP/IP UDP type.•Power Supply: 24 Vdc•Dimensions (HxLxD): 110x85 mm•

TLG/54 cod. SW2800121Program providing functions for unloading, displaying and printing the chro-nological history log of AREA54 central units.

The program allows to constantly keep under control the operation of central •units, to execute commands remotely and to inquire and modify the status of AREA54 central units. Communication between central units and PC can be implemented by serial •connections, by connections through the network, by connections via Modem (also simultaneously).

FOGLIO/54 cod. SW2900121Graphic map leaf from autocad support

PUNTO/54 cod. SW3100121Graphic map point from autocad support

SOFT/54 cod. SW2300121Software for local/remote AREA54 programming

ACCESSORIES FOR CENTRALISATION

ADDRESSED FIRE DETECTION SYSTEMS

MODEM54

LAN/54

34

UNIVERSAL CONNECTION

BASESDUCTED

DETECTION

35

ZB/200 cod. SD2700121Universal base for smoke and thermo-speedometric optical sensors for conventional analogue and digital systems.

ZB/201 cod. SD2800121Universal base with 12 Vdc dry contact relay for repeating the alarm status

The base is suitable for conventional systems and burglar-proof systems. The •base is also suitable for smoke and thermo-speedometric optical sensors.

ZB/204 cod. SD9D00121Universal base with 24 Vdc dry contact relay for repeating the alarm status.

The base is suitable for conventional systems and burglar-proof systems. The •base is also suitable for smoke and thermo-speedometric optical sensors.

ZB/210 cod. SD4300121Universal base with coding for connecting conventional detectors for analogue systems.

ZB/212 cod. SD1N00121Base with local alarm signalling.

The base can manage a LR500 visual repeater. The base must be supplied •through an external power.

ZB/215 cod. ZC7100121Base support for ZB series low profile bases.

FOR CONVENTIONAL AND AREA54 DETECTORS

UNIVERSAL CONNECTION BASES

UNIVERSAL CONNECTIONBASES

R/820 cod. SD3L10121The analysis chamber for ducted detection was designed to check for the presence of smoke in air ducts and allows to timely detect a spreading fire.

Inside the analysis chamber there can be located analogue and digital optical •smoke detectors, as well as conventional optical smoke detectors. Inside the chamber there is placed ZB/200 connection base.Container in thermoplastic material; on container cover there is a window in •plexiglas for sensor local alarm visual control.Two PVC probes 500 mm long.•Dimensions (HxLxD): 107x81x46 mm•

DUCTED DETECTION

DUCTEDDETECTION

R/820

36

FAP500DIGITAL

SYSTEMFAP 54/1 ...................................pag. 40

FAP 54/4 ...................................pag. 41

FAP 54/8 ...................................pag. 41

FAP 54/16 .................................pag. 41

ACCESSORIES ...........................pag. 42

BUTTONS ..................................pag. 43

DETECTORS ..............................pag. 44

37

FAP500 SYSTEM

FAP500 DIGITAL SYSTEM

From Elkron research, FAP 500 series is born, i.e. a new smoke detection digital system.Within Elkron fire system there is included from today FAP 500 series, i.e. a new modular, flexible digital system, EN54-approved and available in 4 control unit models with 1 to 8 loops, all with exten-sion capability. System main evolution, differentiating the system from anything else present on the market, is the capability of self-learning the address in any installation mode. In addition, the system is provided with a short circuit isolator integrated in all components. FAP 500 system enables both easily interface to shut off systems and assure an excellent protection level. This is why, with FAP 500, Elkron fire system is also a Hi-protection system.

System high flexibility.FAP500 system is a clear evolution over control units present on the market, as enabling to con-nect all control unit models to the network, interface to shut off systems and assure an excellent performance level joined to simple installation, programming and management. The system is modular, flexible and includes 4 control unit models:•controlunitwith1loop(FAP541)•controlunitwith2loopswithextensioncapabilityto4(FAP544)•controlunitwith4loopsewithextensioncapabilityto8(FAP548)•controlunitwith8loopswithextensioncapabilityto16(FAP5416)

The line can be connected in 3 different ways, guaranteeing the point (detector, device, pushbut-ton, etc...) to be automatically pre-learned:•linewithclosedloop•openlines(entering/exitingconnection)•openlines(parallelconnection)

Easy programming.Thanks to this flexibility, all system needs can be best met, so making installation step much ea-sier. Each configuration type can be easily programmed via either control unit keyboard or PC.All control units are prearranged for communicating within the network through a LAN TCP/IP interface, a communication port for Master/Slave functions, a printer connection port, an optically isolated RS485 port for interfacing repeater panels and shut off control units, an USB port for downloading data and system configuration via PC, a communication interface for tran-smitting events via GPRS/GSM/PSTN.All is under control, remotely too, thanks to new software platform enabling Elkron systems to interact among one another and remotely transmit all system information.

38

FAP 500 SERIES CONTROL UNITSThe new control unit FAP544 is modular that is possible to expand the standard configuration with functions and peripherics. It is possible to manage a minimum of 2 up to 4 addressed loop.

ConnectibilityRS485 communication port Communication port for LAN TCP/IP networkPrinter connection port Communication port for MASTER/SLAVE connectionConnection for 16 remote panelsManaging configuration / programming / remote assistance sw via PCManaging graphic maps / remote managementExternal communication via GPRSExternal communication via PSTN

FAP500 SYSTEM

FAP500 DIGITAL SYSTEM

CONTROL UNIT RELAY

CONTROLLED RELAY OUTPUTSELF-POWERED SOUNDER OUTPUTALARM RELAY 1ALARM RELAY 2FAULT RELAYPROGRAMMABLE RELAY

PRINTERMODULE

KEYPAD

RS232OUTPUT

FOR REMOTEPANELS (16 MAX)

MASTER/SLAVEFOR EXTINGUISHING CONTROL UNITS AND

FAP500 CONTROL UNITS

PC PROGRAMMING

USB

LAN

PS2

EXPANSIONMODULEFA128

FDOT500 + SD500R

LR500SI

FM500R

IO500MODULE

PANELO/A

FDT500 + SD500R

LR500SI

FDO500 + SD500

RS232/485MODULE

LOOP LINE128 POINTS MAX

IMO500MODULE

LINEAR DETECTORS

PANEL

ELECTROMAGNETS

EXTERNALPOWER SUPPLY

UNITSCONTROL

39

FAP541 Control Unit

FAP541 cod. SC6100121Microprocessor control unit with 1 loop line

Configuration: 1 loop line (class A) or 2 open lines (class B)•Possibility of managing up to 128 points for loop (64 for open line).•Point self-learning and point logic address.•Backlit graphic display 4 x 40 characters•Event log: 1000 events•Chronological history directly shown on display.•10 passwords programmable on 3 levels.•480 programmable zones.•USB port for local PC connection for programming via SW•Possibility of monitoring detector signal/noise ratio level •Real time clock with built-in buffer battery•Non volatile memory•Control unit outputs: 5 (alarm 1, alarm2, failure, programmable (mains •failure/exclusion) Internal buzzer•Programmable alarm threshold: for zone, for individual point•Exclusion of individual point /zone•Power supply: 230Vca•Max. current: 1.5A@24Vcc•Battery charge limit and battery charge check•Battery housing: 2 12 @12Vcc batteries•Possibility of implementing at least 2 Km loop with 2 x 1.5 mm• 2 screeened cable Noise immunity up to 30Vm•Common dialogue protocol for all system control units•Dimensions: 490 (L) x 350 (H) x 145 (D) mm•COMPLIANT WITH EN54 STANDARDS, part 2 and part 4•

1 LOOP LINE CONTROL UNIT

FAP500 DIGITAL SYSTEM

FAP541

40

FAP544 Control Unit

FAP544 cod. SC6200121Microprocessor control unit with 2 loop lines expandable to 4

Basic configuration: 2 loop lines (class A) or 4 open lines (class B)•Max. configuration: 4 loop lines (class A) or 8 open lines (class B)•Possibility of managing up to 128 points for loop (64 for open line).•Point self-learning and point logic address.•Backlit graphic display 240*128 - 4.7 “.•Event log: 1000 events•Chronological history directly shown on display.•10 passwords programmable on 3 levels.•480 programmable zones.•USB port for local PC connection for programming via SW•Possibility of monitoring detector signal/noise ratio level •Real time clock with built-in buffer battery•Non volatile memory•Control unit outputs: 5 (alarm 1, alarm2, failure, programmable (mains •failure/exclusion) Internal buzzer•Programmable alarm threshold: for zone, for individual point•Exclusion of individual point /zone•ON/OFF by password•Power supply: 230Vac•Max. current: 2A@24Vdc•Battery charge limit and battery charge check•Battery housing: two 12 @12Vdc batteries•Possibility of implementing at least 2 Km loop with 2 x 0.75 mmÇ cable •(screened and NOT screened) Noise immunity up to 30Vm•Common dialogue protocol for all system control units•Dimensions: 490 (L) x 350 (H) x 145 (D) mm•COMPLIANT WITH EN54 STANDARDS, part 2 and part 4•

FAP548 Control Unit

FAP548 cod. SC6600121Microprocessor control unit with 4 loop lines expandable to 8.

Same as FAP544•

FAP5416 Control Unit

FAP5416 cod. SC6700121Microprocessor control unit with 8 loop lines expandable to 16.

Same as FAP544•

4, 8 AND 16 LOOP LINE CONTROL UNITS

FAP500 DIGITAL SYSTEM

FAP544

41

Expansion module

FA128 cod. SC33101211 loop expansion module

The expansion module enables to expand the control unit by 1 loop line or •2 open lines. 128 points (detectors, push-buttons, interfaces, etc.) can be connected. The module, to be directly installed on the control unit backplane, enables the acquisition and control of the connected devices. Connection with devices can be implemented with closed loop line or with open loop line. Configuration is made during programming.

Accessories

FKP500 cod. KP5200121Remote Panel

The repeating panel enables active and constant monitoring of every event. •The FAP500 control unit can manage up to 16 remote panels; connection to the control unit and to other panels (if any) is made by means of RS485 opto-isolated port. Panel identification address is made via on board switch. Information is displayed through backlit display with 4 lines x 40 characters. Power supplies, exclusions/reset, alarms and failures are indicated by a series of leds. The user has a keypad fitted with dedicated keys for controls from/to the control unit.

IO500 cod. SC3A00121Multipurpose module 1 input/ 1 output

This module enables to interface on FAP500 digital system, stable conventional •detectors with dry contacts (NC/NO), to connect probes or other devices fitted with pulse controls. Moreover the same interface can pilot actuators (e.g.: panels, plates, electromagnets, sirens, etc.) and check the line control. Each input / output can be programmed.Power supply: 10 ÷ 24Vdc•Absorption: 250 mA @ 24Vdc•Relay output: 1A, 30Vdc, resistive load•Alarm repeat output: 12mA max •Working temperature: -5 ÷ 50 °C•Relative humidity: 95% max non condensing•

IOM500 cod. SC3B00121Multipurpose module 4 inputs/ 4 outputs

This interface features the same characteristics as module IO500, it •enables to connect stable conventional detectors with dry contacts (NC/NO), to connect probes or other devices fitted with pulse controls and to pilot actuators (e.g.: panels, plates, electromagnets, sirens, etc.) and check the line control, but it features 4 programmable inputs and 4 programmable outputs.

RS232/485 cod. IT1410121RS232/485 interface for MASTER/SLAVE and remote panel

FAP500 SYSTEM: MODULES AND ACCESSORIES

FAP500 DIGITAL SYSTEM

FA128

IO500

42

Accessories

SOFT/FAP500 cod. SW3500121Configuration SW

This software enables to acquire the system characteristics by reading •the control unit data; to unload and to programme the configuration and parameters of each individual point

MAPPE/FAP500 cod. SW3600121Supervision software with graphic maps

This software enables full network management of one or more control units. •It is possible to manage and assist the system in local or remotely.

LAN/TCP/IP500 cod. IT1510121LAN/TCP/IP interface

It enables to connect several control units on a LAN network.•

ITS500 cod. IT1610121Printer interface.

MGSM500 cod. CT6010121Modem interface for GSM.

MPSTN500 cod. CT5910121Modem interface for PSTN.

FAP500 SYSTEM: MODULES AND ACCESSORIES

FAP500 DIGITAL SYSTEM

Buttons

FM500 cod. SD6000121Break glass manual pushbutton, complete with self-learning circuit

Fire alarm pushbuttons are used for signalling an alarm manually. To use the •break glass pushbutton model just press the glass in the middle in order to break it and to operate the internal switch. These pushbuttons are provided with a special tool to be used to perform the TEST, to open the cover and to replace the glass. The alarm state is shown by the switching on of a red LED. Compliant with Standards: EN54 part 11

FMR500 cod. SB6100121Manual recommissioning pushbutton, complete with self-learning circuit and short-circuit isolator.

To use the recommissioning pushbutton model just press the glass in the •middle in order to push it inwards, thereby operating the switch. These pushbuttons are provided with a special tool to be used to perform the TEST and to replace the glass. The alarm state is shown by the switching on of a red LED. Compliant with Standards: EN54 part 11

FAP500 SYSTEM: BUTTONS

FM500

FMR500

43

RIVELATORI CONVENZIONALI

Photo-optical smoke detector

FDO500 cod. SD4800121Low profile photo-optical smoke detector, complete with self-learning circuit and short-circuit isolator.

Smoke detectors work according to the light scattering principle caused by •smoke particles present in the air. The smoke detector has the automatic gain control function; a microcontroller calculates reading compensation to keep constant sensitivity and corrects any level increase due to dust depositing into the analysis cell. Smoke detectors shall be installed in places protected against draughts which may divert the flow of combustion particles and in places where the common activities performed do not cause gas material fires. Power supply: 20Vdc (modulated voltage between -15% and + 10%)•Average absorption at rest: 250 mA@20Vdc•Absorption at alarm: 2mA@20Vdc•Two-colour led: red alarm - green regular operation•Relative humidity max: 93%•Working temperature: 0 ÷ 50°C•Weight: 70 g•Dimensions: ø 90 x 31 (H) mm•Certificato EN54 parte 7, certification number: 1293-CPD-0082•

Heat detector

FDT500 cod. SD5700121Low profile heat detector, complete with self-learning circuit and short-cir-cuit isolator.

Heat detectors monitor the temperature values in the area where they are •installed.A microcontroller analyses and compares the signal received from a NTC •type temperature detector and activates the alarm if the read temperature exceeds 58°C. Power supply: 20Vdc (modulated voltage between -15% and + 10%)•Average absorption at rest: 250 mA@20Vdc•Absorption at alarm: 2mA@20Vdc•Static alarm threshold: 58°•Two-colour led: red alarm - green regular operation•Relative humidity max: 93%•Working temperature: 0 ÷ 50°C•Weight: 70 g•Dimensions: ø 90 x 40 (H) mm•Compliant with EN54 Standards, part 5 class A1S, certification number: •1293-CPD-0084.

FAP500 SYSTEM: DETECTORS

FAP500 DIGITAL SYSTEM

FDO500

FDT500

44

Thermo-speedometric detector

FDTD500 cod. SD9000121Low profile thermo-speedometric detector, complete with self-learning circu-it and short-circuit isolator.

Thermo-speedometric detectors monitor temperature rise in the area where •they are installed. A microcontroller analyses and compares the signal received from a NTC type temperature detector and activates the alarm if the read temperature rise exceeds 5°C per minute.Power supply: 20Vdc (modulated voltage between -15% and + 10%)•Average absorption at rest: 250 mA@20Vdc•Absorption at alarm: 2mA@20Vdc•Static alarm threshold: 58°•Two-colour led: red alarm - green regular operation•Relative humidity max: 93%•Working temperature: 0 ÷ 50°C•Weight: 70 g•Compliant with EN54 Standards, part 5 class A1R, certification number: •1293-CPD-0085.

Optical- heat detector

FDOT500 cod. SD9K00121Low profile optical- heat detector, complete with self-learning circuit and short-circuit isolator.

Double technology detectors (smoke-heat) base their operating principle on •the light scattering principle caused by smoke particles present in the air (TYNDALL effect) and on temperature monitoring within the area where they are installed. A microcontroller analyses and compares the signal received from a NTC type temperature detector and activates the alarm if the read temperature exceeds 58°C. The smoke detector has the automatic gain control function; a microcontroller calculates reading compensation to keep sensitivity constant in time.Power supply: 20Vdc (modulated voltage between -15% and + 10%)•Average absorption at rest: 250 mA@20Vdc•Absorption at alarm: 2mA@20Vdc•Static alarm threshold: 58°•Two-colour led: red alarm - green regular operation•Relative humidity max: 93%•Working temperature: 0 ÷ 50°C•Weight: 70 g•Dimensions: ø 90 x 40 (H) mm•Compliant with EN54 standards part 7 and part 5 class A1, certification •number: 1293-CPD-0083

FAP500 SYSTEM: DETECTORS

FAP500 DIGITAL SYSTEM

FDTD500

FDOT500

45

Standard base

SD500 cod. SD4K00121Digital detector standard base.

The base is standard for all digital detectors of the FAP500 series.•Material: ABS•Colour: white•Dimensions: 90 mm•

SD500M cod. SD4S00121Digital detector standard base, FAP500 series - package with 10 pcs.

SD500R cod. SD5K00121Digital detector standard base with alarm repetition.

The base is standard for all digital detectors of the FAP500 series, its output •enables to directly pilot (through the loop supply) the outdoor gem LR500SIMaterial: ABS•Colour: white•Dimensions: 90 mm•Alarm repetition output: 12 mA@24Vdc•

SD500-RM cod. SD6S00121Digital detector standard base with alarm repetition, FAP500 series - package with 10 pcs

SD515 cod. SD2V00121Base support for series 500 bases

FAP500 SYSTEM: BASES FOR DETECTORS

FAP500 DIGITAL SYSTEM

46

EXTINGUISHING CONTROL

UNIT

47

EXTINGUISHINGCONTROL UNIT

EXTINGUISHING CONTROL UNIT

OUT 1OUT 2

LOOP 1

FMR500 FMR500

FDT500 FDT500

TM24

IO500

EXTINGUISHINGSYSTEMS

REMOTECONTROLSWITCH

UNBLOCKPUSHBUTTON

48

CDS cod. SC3600121Extinguishing control panel fitted with one module expandable to 2

CDS extinguishing control panel is a non-expandable, 1 loop, microprocessor-•based control panel that shares all FAP500 system devices and also incorporates a extinguishing module with provisions for expansion to 2.CDS has been designed so as to fully comply with EN 12094-1 and EN54-4 •European Norms.Certification No.: 0051-CPD-0177.•

FIRE EXTINGUISHING MODULE CHARACTERISTICSFlux meter input•Pressure switch input•Emergency extension input•Manual discharge activation input•Input for discharge activation through an external control panel•Release “ON” relay (NO or NC contact, 1A max)•Emergency extension relay (NO or NC contact ,1A max)•Evacuation siren output (250 mA max.)•Release output 1 (Pilot, 750mA max)•Release output 2 (Solenoid valve, 750mA max)•

DETECTION LINES CHARACTERISTICSConfiguration: 1 loop line (class A) or 2 open lines (class B).•Possibility of managing up to 128 points per loop.•Point self-addressing and point logic address.•Backlit display: 4 x 40 characters•Event log: 1.000 events•Chronological event log available on the display directly.•10 passwords programmable on 3 levels.•480 programmable zones.•USB port for connection to local PC for programming via SW•Possibility of monitoring detector signal/noise ratio level •Real time clock with built-in buffer battery•Non-volatile memory•Control panel outputs: 5 (alarm 1, alarm2, failure, programmable (mains •failure/exclusion) Internal buzzer•Programmable alarm threshold: for zone, for individual point•Exclusion of individual point /zone•Power supply: 230Vac•Max. current: 1.5A@24Vdc•Battery charge limit and battery charge check•Battery housing: two 12 @12Vdc batteries•Possibility of implementing max 2 Km loop with 2 x 0.75 mm² with screened •cableNoise immunity up to 30Vm•Common communication protocol for all system control panels•Dimensions: 490 (L) x 350 (H) x 145 (D) mm•

ESPCDS cod. SC3500121Expansion to 1 module for extinguishing control panel.

CDS CONTROL UNIT

EXTINGUISHING CONTROL UNIT

CDS

ESPCDS

49

50

GAS, LIQUIDS, HEAT AND

LINEARDETECTORS

AND CONTROLUNITS

GAS DETECTION CONTROL UNIT pag. 52

TOXIC AND EXPLOSIVES GAS DET. ..pag. 53

FLAME DETECTOR .....................pag. 56

LIQUID PRESENCE DETECTOR ....pag. 57

SPECIAL HEAT DETECTOR ..........pag. 57

LINEAR DETECTOR ....................pag. 59

SUCTION SYSTEMS ...................pag. 62

51

Gas Detection Control Units

ST/PL4 cod. SC6R00123Gas detection central unit allowing the connection of 4 minimum number to 8 maximum number of inflammable toxic gasses or oxygen detectors (throu-gh optional board) with 4-20 mA proportional output.

For each input it is possible to set the type of detector, suitable measure •range and alarm level values. Concentration values measured are shown on a backlit liquid crystal display.•The central unit has 5 relay outputs, 4 of which are associated to Failure, •Alarm 1, Alarm 2, Alarm 3 and one is an auxiliary relay output that can be associated to one of the four above statuses.By adding an optional module, in addition to the 4 inputs there are also •implemented 16 open collector outputs.Housing: Metallic enclosure•Dimensions (hxlxd): 225x360x110 mm•Display: backlit LCD with 16 characters for 2 lines•Power supplay: 230 Vac •Absorption: 80 mA at rest, 160 mA on alarm status, 240 mA with •expansion boardRelay outputs: 1 A @ 24 Vdc 5 A @ 24 Vdc (relay AUX)•Operation temperature: -0 to - 40°C•Relative humidity: 15-85% non condensing•

ST/PL4/ESP cod. SC7R10123Expansion module for 4 inputs, 16 O.C. outputs that can be set for Alarm 2 or Alarm 3 ST/PL4 for central unit.

O.C. outputs: 250 mA•

STG/MTSLB cod. SC8R00123Gas detection central unit allowing the connection of 8 minimum number to 104 maximum number of inflammable toxic gasses or oxygen detectors with 4-20 mA proportional output.

The connection is through (optional) remote concentrators arranged on •RS485 serial line.The central unit has inside it 4 output relays to interface towards the field, •and 4 open collector outputs.The unit can be configured with detectors that differ from one another as •both gas detected and activation thresholds.Both explosive and toxic gas detectors can be configured.•The central unit can store up to 800 events.•Housing: Metallic enclosure•Dimensions (hxlxd): 420x440x140 mm•Display: backlit LCD with 256x64 dots•Power supplay: 230 Vac •Expansibility: Up to 64 O.C. outputs with 8 STG/OUT16 optional modules •Operation temperature: -0 to - 40°C•Relative humidity: 15-85% non condensing•

ATEX VERSION CONTROL UNITS

DETECTORS AND CONTROL UNITS

ST/PL4

STG/MTSLB

52

Accessories for ATEX control units

STG/IN8 cod. SC9R10123Remote module for 8 board inputs

STG/OUT16 cod. SC1S10123Remote module for 16 open collector programmable board outputs

STG/BOX cod. ST0510123Metallic enclosure for containing a STG/IN8 or STG/OUT16 module

WMB/138V15 cod. ST0610123Metallic enclosure with 12 Vdc 1.5 A supply for containing a STG/IN8 or STG/OUT16 module.

ATEX VERSION CONTROL UNITS

DETECTORS AND CONTROL UNITS

Gas detectors are used to detect the presence of combustibles in concentrations that can be expressed as a percentage of Explosiveness Lower Limit (%ELL) and of toxics that can be expressed as parts per million (ppm) or in the detection of oxygen deficiency or excess.For explosive mixtures detectors a catalytic sensor is used, while for toxics detectors an electrochemical cell sensor is used.The detector is fully controlled by a 10 bit microprocessor. The detectors provide either a current proportional output (4-20 mA) or relay contacts through an optional board.

GAS DETECTORS, EX II 3GD TYPE

S1604VB cod. SD2T00123Petrol vapours detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc. •STS3REL relay board cannot be used.•

S2096PR cod. SD5T00123Propane gas detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc.•

S2096BU cod. SD6T00123Butane gas detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc. •

S1606CO cod. SD7T00123CO (Carbon Monoxide) detector 4-20 mA, 0-300 ppm

Electrochemical cell sensor.•Absorption: 30 mA@12Vcc.•STS3REL relay board cannot be used.•

TOXIC AND EXPLOSIVES GAS DETECTORS

EX II 3GD

53

GAS DETECTORS, EX II 3GD TYPE

S2096ME cod. SD9S00123Methane gas detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc. •

S1702VB cod. SD3T00123Petrol vapours detector 4-20 mA, 0-100% LEL

Pellistor sensor.•Absorption: 30 mA@12Vcc.•Alarm output: 2 relays 1A@30Vcc.•Fault output: 1 relay 1A@30Vcc.•Suitable for parking lots.•

S2096GP cod. SD4T00123LPG gas detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc. •

S1703CO cod. SD8T00123CO (Carbon Monoxide) detector 4-20 mA, 0-300 ppm

Electrochemical cell sensor.•Absorption: 30 mA@12Vcc.•Alarm output: 2 relays 1A@30Vcc.•Fault output: 1 relay 1A@30Vcc.•Suitable for parking lots.•

TOXIC AND EXPLOSIVES GAS DETECTORS

DETECTORS AND CONTROL UNITS

MAIN CHARACTERISTICS OF GAS DETECTORSPower supply 12 – 24Vcc – 20% + 15%

Auto-zero routine Zero drift compensation

Light indications Blinking LED

Precision ± 10% full scale

Warm-up time 5 minutes

Stabilization time < 2 minutes

Response time < 15 sec. T50; < 25 sec T90 (flammable gas version)

Air velocity < di 6 mS

Digital filter Sampled values variable averages

Resolution 1.024 points

IP protection IP55

Weight 350 g

Dimensions (L) x (H) x (D) mm 106 x 170 x 65

Reference Standards EN50014 EN50018 EN50021 (essential safetyrequirements EEx-n) / EN61779-1/4 (performances)

Atex marking CE 722 Ex II 3GD Ex nA d IIC T6 IP55 T85°C

54

GAS DETECTORS, Ex II 2GD TYPE

S2097VB cod. SD1U00123Petrol vapours detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc.•

S2097ME cod. SD9T00123Methane gas detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc.•

S2131CO cod. SD5U00123CO (Carbon Monoxide) detector 4-20 mA, 0-500 ppm

Electrochemical cell sensor.•Absorption: 30 mA@12Vcc.•

S2097PR cod. SD3U00123Propane gas detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc.•

S2097GP cod. SD2U00123LPG gas detector 4-20 mA, 0-100% LIE

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc. •

S2097BU cod.SD4U00123Butane gas detector 4-20 mA, 0-100% LEL

Catalytic sensor: Nemoto.•Absorption: 130 mA@12Vcc. •

TOXIC AND EXPLOSIVES GAS DETECTORS

DETECTORS AND CONTROL UNITS

MAIN CHARACTERISTICS OF GAS DETECTORSPower supply 12 – 24Vcc – 20% + 15%

Auto-zero routine Zero drift compensation

Light indications Blinking LED

Precision ± 10% full scale

Warm-up time 5 minutes

Stabilization time < 2 minutes

Response time < 15 sec. T50; < 25 sec T90 (flammable gas version)

Air velocity < di 6 mS

Digital filter Sampled values variable averages

Resolution 1.024 points

IP protection IP66

Weight 950 g

Dimensions (L) x (H) x (D) mm 110 x 135 x 80

Reference Standards EN50014 EN50018 EN50021 (essential safetyrequirements EEx-n) / EN61779-1/4 (performances)

Atex marking CE 722 Ex II 2GD Ex d IIC Ex tD A21 IP65 T85°C

EX II 2GD

55

Accessories for gas detectors

ST/S3REL cod. SC5R10123Board with three relays for gas detectors.

It allows to have contacts free from voltage. •The first output is associated to failure or Watch-Dog. The second output can •be associated to either alarm 1 or alarm 2 of detector. The third output can be associated to either alarm 2 or alarm 3 of detector.Relay contacts current carrying capacity: 50mA @ 24 Vdc; 100 mA @ 12 •Vdc.

VAL TEST cod. SI7100123Test kit containing instruments necessary to execute requested functiona-lity tests.

It contains a flowmeter valve and a fitting suitable to connect the tanks to the •detectors, in order to create a well defined titrated atmosphere.

TOXIC AND EXPLOSIVES GAS DETECTORS

DETECTORS AND CONTROL UNITS

RU-ADPE cod. SD7100121Flame detector immediately responding to infrared thermal radiation relea-sed by fire. The detector is tuned to flame pulses in order to ignore sunlight and lamps.

It is contained in IP66 explosion proof enclosure. •It needs 24 Vdc supply, with wide tolerance on its value, and provides two •types of outputs: a wide range switching contact SPDT and a static signal on NPN collector.Both outputs go into alarm after a certain lag and go back to a rest condition •as fire is over.Lag time is normally calibrated to 5 seconds; however, it can be ranging 1 •to 10 seconds.Sensitivity is calibrated to 2 - 3%, i.e. a 10 cm flame at a 5 m distance, or a •20 cm flame at a 10 m distance.View field is a 90° cone; however, beyond 90°, the detector can still see, •although with reduced sensitivity; and, by reflection, it can even see zones in shade behind obstacles.On detector front side, a red LED warns about test or alarm status.•Casing: explosion proof aluminium alloy.•Painting: epoxy, grey RAL7035.•Implementation: II 2 GD EEx-d IIC T6 IP66.•Certified: CESI 01 ATEX 036.•Compliance with: directive ATEX 94/9 CENELEC EN 50014 (CEI 31.8) EN •50018 (CEI 31.1)Dimensions (mm): 230 x 230 x 154h main body only.•Weight: 10 kg including detector.•Cables input: 1’’ Gas.•

INFRARED FLAME DETECTOR

56

Liquid detector

RA/209 cod. SD2B00121 Electronic detector to detect the presence of (uninflammable) liquids.

Detecting the presence of water is through 4 support gilt feet, which put the •detector into alarm by switching a relay placed inside it.For higher protection, RA/209 model is provided with a humidity detector •having a sensivity that can be regulated by an inner trimmer.Facility for connecting 10 external probes of RA/209S model.•Container material: Thermoplastic, white colour •Operation voltage: 12 - 27 Vdc•Average absorption: 3.5 mA at 27 Vdc•Operation temperature: +5 to +50 °C•Dimensions: 64 x 96 x 30 mm•

LIQUID DETECTOR

DETECTORS AND CONTROL UNITS

Heat Detectors

RTS/2 cod. SD2C00123 IP65 Special heat detector based on the deformation of a bimetallic element which closes a dry contact as the temperature is reached. This makes the detector easy to be interfaced with any board type.

The heat detector is suitable for detection in environments where potentially •explosive atmospheres may be present. Its construction is complying with sector specific regulations (ATEX).The detector can operate based on the type of heat probe being used as •follows:DF: Gradient detector. The intervention only occurs when temperature •increment is higher than 13 °C per minute.SD: Semidifferential detector. The intervention always occurs as calibration •temperature is reached; further, an intervention lead occurs when temperature increment is higher than 15°C per minute.MAX: Maximum temperature detector.The intervention only occurs when •calibration temperature is reached.Code SD2500123 is referred to a detector with a 60° C calibration •temperature. Different grades are available to specify in the command.Operation principle: Bimetallic element deformation•Protection degree: IP 65•Working temperature: 190 C° MAX•Relative humidity: 98%•Weight: 0,9 Kg•Bimetallic component: Nilvar-Brass•Regulation range: -40 + 190 C°•Intervention threshold: On Request /mod SD Max 88 C°•Alarm condition: Normally closed contact•Contacts current carrying capacity: 2,5 A•Working voltage: 48 Vdc •Enclosure material: Aluminium alloy•Dimensions: 110 x 13 x 70 mm•

SPECIAL HEAT DETECTOR

RTS72

57

Heat detector

RTS/4 cod. SD4C00123IP55 heat detector based on the deformation of a bimetallic element which closes a dry contact as the temperature is reached.

This makes the detector easy to be interfaced with any board type.•The detector can operate based on the type of heat probe being used as •follows:

DF: Gradient detector. The intervention only occurs when temperature increment is higher than 13 °C per minute.

SD: Semidifferential detector. The intervention always occurs as calibration temperature is reached; further, an intervention lead occurs when temperature increment is higher than 15°C per minute.

MAX: Maximum temperature detector. The intervention only occurs when calibration temperature is reached.Code SD4J00123 is referred to a detector with a 60° C calibration •temperature. Different grades are available to specify in the command.Operation principle: Bimetallic element deformation•Protection degree: IP 55•Working temperature: 190 C° MAX•Relative humidity: 98%•Weight: 0,4 Kg•Bimetallic component: Nilvar-Brass•Regulation range: -40 + 190 C°•Intervention threshold: On Request /mod SD Max 88 C°•Alarm condition: Normally closed contact•Contacts current carrying capacity: 2,5 A•Working voltage: 48 Vdc •Enclosure material: Aluminium alloy•Dimensions: 92x167x67 mm•

RTS/6 cod. SD3C00123IP65 Special heat detector based on the deformation of a bimetallic element which closes a dry contact as the temperature is reached. This makes the detector easy to be interfaced with any board type.

The heat detector is suitable for detection in environments where potentially •explosive atmospheres may be present. Its construction is complying with sector specific regulations (ATEX). Code SD7E00123 is referred to a detector with a 60° C calibration •temperature. Different grades are available to specify in the command.Heat probe is UL/FM certified. •Operation principle: Bimetallic element deformation•Relative humidity: 98%•Weight: 0,4 Kg•Bimetallic component: Nilvar•Regulation range: on order fixed calibration•Alarm condition: Normally closed contact•Contacts current carrying capacity: 2 A•Working voltage: 24 Vdc •Sensor material: steel•Enclosure material: Aluminium alloy•Dimensions: 100 x 193,5 x 70 mm•

SPECIAL HEAT DETECTOR

DETECTORS AND CONTROL UNITS

RTS/4

58

Heat Detector

RLB/1 cod. SD6P00121 Linear heat detector, 68°C calibration (certified)

Packaging: 100 m skein•

RLB/2 cod. SD5P00121 Linear heat detector, 105°C calibration (certified)

Packaging: 100 m skein•

Smoke Linear Detector

S/2-100 + INT8C cod. IL1500123 Linear detector suitable for all environments characterised in high ceilings, where using smoke optical detectors results to be particularly hard.

The system includes three units: Transmitting unit (TX), Receiving unit (RX), •co-ordination unit (not including INT8C/24V interface module).The operation principle of linear detector is based on TX units to emit a •beam of infrared rays. The beam runs through the zone to be monitored and radiates Receiving unit (RX). On running through monitored zone, the beam collects information about possible fire arising and carries it to RX. RX processes this information and draws from it a number of electrical signals, each corresponding to a single fire sign examination. Successive processing allows to diagnose the presence of smoke in monitored environment.On Transmitting unit there are present following leds: Power supply signalling •green led, Receiving unit status repetition yellow led.On Receiving unit there are present following leds: Power supply signalling •green led, Emitted and received IR intensity level yellow led, Fire alarm red led.Linear detector is suitable for lengths of 5 m to 150 m.•Maximum operative width: 15 m.•High aligning facility.•Brackets, for improved wall application, already included.•Obligatory connection interface INT/8C (not included).•Obligatory calibration instrument ADM (not included).•Operation voltage: 24 Vdc•Absorption in mA Tx: 5-15m 20,0 55-75m 24,0•

15-35m 21,8 75-100m 38,6 35-55m 22,7 100-150m 65,5

Absorption in mA Rx: Normal operation 47,7 - Fault 66,7 - Alarm 64,0.•Operation temperature: da -20 a + 55 C°•Operative homologation: EN 54/12•Protection degree: IP 44•Weight: Tx Unit 1,257 g, Rx Unit 1,447 g.•Dimensions with bracket: Tx 224 x 119 x 313 mm•

Rx 224 x 119 x 313 mmDimensions without bracket: Tx 220 x 119 x 148 mm. •

Rx 220 x 119 x 148 mmCertificate EN54 part 12 Certificate N° 0786 - CPD - 20215.•

SPECIAL HEAT DETECTOR

DETECTORS AND CONTROL UNITS

S/2-100

LINEAR DETECTORS

59

Fire and smoke linear detectors

SF-100 + INT8C cod. IL1400123 Fire and smoke linear detector.

The system includes three units: Transmitting unit (TX), Receiving unit (RX), •co-ordination unit (not including INT8C/24V interface module).The operation principle of linear detector is based on TX units to emit a •beam of infrared rays. The beam runs through the zone to be monitored and radiates Receiving unit (RX). On running through monitored zone, the beam collects information about possible fire arising and carries it to RX. RX processes this information and draws from it a number of electrical signals, each corresponding to a single fire sign examination. Successive processing allows to diagnose the presence of smoke in monitored •environment.On Transmitting unit there are present following leds: Power supply signalling •green led. Receiving unit status repetition yellow ledOn Receiving unit there are present following leds: Power supply signalling •green led. Emitted and received IR intensity level yellow led. Fire alarm red led.Linear detector is suitable for lengths of 5 m to 150 m.•Maximum operative width: 15 m.•High aligning facility.•Brackets, for improved wall application, already included.•Obligatory connection interface INT/8C (not included).•Obligatory calibration instrument ADM (not included).•Operation voltage: 24 Vdc•Absorption in mA Tx: 5-15m 20,0•

15-35m 21,8 35-55m 22,7 55-75m 24,0 75-100m 38,6 100-150m 65,5

Absorption in mA Rx: Normal operation 47,7 - Fault 66,7 - Alarm 64,0.•Operation temperature: from -20 to + 55 C°•Operative homologation: EN 54/12•Protection degree: IP 44•Weight: Tx Unit 1,257 g, Rx Unit 1,447 g.•Dimensions with bracket: Tx 224 x 119 x 313 mm•

Rx 224 x 119 x 313 mmDimensions without bracket: Tx 220 x 119 x 148 mm. •

Rx 220 x 119 x 148 mmCertificate EN54 part 12 N° 0786 - CPD - 20215.•

LINEAR DETECTORS

DETECTORS AND CONTROL UNITS

SF-100

60

Accessories

INT8C/24V cod. IL1010123 Interface module allowing the connection and operation of the Tx and Rx units of smoke linear detector.

The module has two relays inside it: one alarm relay and one failure relay •to be used for connecting the apparatus to conventional central units, or analogue or digital input modules.Failure relay can be either normally energised (active safety) or normally not •energised.Facility for delaying the failure by 0 to 90 seconds through a second jumper.•Operation principle: 24 Vdc •Absorption with not energised out of order relay: Normal operation 16,4mA •@ 24 Vdc, Alarm: 22,4mA @ 24 Vdc, Failure: 22,2mA @ 24 VdcAbsorption with energised out of order relay: Normal operation 25,0mA @ •24 Vdc, Alarm: 15,7mA @ 24 Vdc, Failure: 30,6mA @ 24 Vdc.Dimensions (hxlxp): 130 x 130 x 58 mm.•

ADM cod. IL1110123 ADM instrument, associated to an analogue tester, was designed in order to best perform the management functions of sensitivity thresholds required by the nature of environmental disturbances present in environments to be protected.

The use of ADM instrument is necessary for models: ES 25-1; ES 50; ES •100; S/2-100 and SF-100.Operation voltage: 8-12 V •Battery down indication: < 8 V•Typical absorption : 2 mA•Absorption: 1.6 – 2,2 mA max•Operation time: 300 hours•Dimensions: 60x36x18 mm•

ECO series reflexion linear detector

ES50 cod. SD8P00123Infrared ray linear smoke detector, for flush-mounting, working range: 50m

Consisting of ECO transmitting and receiving units and reflector with •articulated jointEN 54 certified - part 12 N. 0786-CPD-20214•Operating voltage: 12Vdc to 24Vdc•Outputs: alarm relay 1A@30Vdc•Optical failure relay 170mA@30Vcc•Working temperature: - 20° + 50°C•Protection: IP44•Dimensions: 103 (H) x 103 (L) x 63 (D) mm•

ES80 cod. SD9R00123Same as ES50 but with 80 m range.

KATA cod. IL7500123Reflexion unit

SSM cod. SP7600123Pair of articulated joints for TX and reflector for the detectors of ECO series.

LINEAR DETECTORS

DETECTORS AND CONTROL UNITS

KATA

ES50

ADM

INT8C/24V

61

ASD cod. SC2R00123Aspirating single-pipe sampling unit.

For PVC/ABS ø 3/4” pipe, max pipe length: 100 m. Power supply: 24Vdc, •smoke detectors not included.

PICO cod. SC3R00123Laser aspiration smoke detector, single-pipe.

For PVC/ABS ø 3/4” pipe, max length: 100 m. Power supply: 24Vdc. •

FIRE TRACER cod. SC4R00123Fire Tracer with 4 aspirating pipes, 1 detection zone.

For 4 aspirating pipes PVC/ABS ø 3/4” pipe sections, 50m each. Power •supply: 24Vdc, complete with diaphragm/ device control, event display.

PLEASE CONTACT THE SALE NETWORK FOR ACCESSORIES

ASPIRATING SYSTEMS

DETECTORS AND CONTROL UNITS

AST cod. AT7100123Fibreglass telescopic extension pole 6 m max

DFS cod. RT7100123Smoke detector tester.

(DBS bottle required) •

DBS cod. SD9H10123Smoke detector test bottle.

DTS cod. RT7200123Heat detector tester.

DRS cod. SD8H10123Universal tool for removing and refitting any type of detectors

ACCESSORIES FOR DETECTORS CHECK

ASD

FIRE TRACER

DRS

DFS

62

OPTICAL-ACOUSTIC

INDICATORSPOWER SUPPLY

BATTERIESPANELS ....................................pag. 64

OPTIC REPEATER .........................pag. 66

BELLS .......................................pag. 67

SOUNDERS ...............................pag. 68

ELECTROMAGNETS ....................pag. 68

EXPLOSION PROOF DEVICES .....pag. 69

POWER SUPPLY/BATTERIES ......pag. 70

63

Optical Acoustic Panels

TM24 cod. FH2600121Optical/acoustic signalling single face panel•Power supply : 12 – 24 Vdc•Max consumption: 100 mA•Lighting by high efficiency leds•Buzzer sound pressure: 85dB at 1m•Steady/flashing light, selectable •Continuous/intermittent sound, selectable•Protection against polarity reverse•Working temperature: -10°C ÷ + 50°C•Material: self-extinguishing ABS, class V0•Protection: IP 40•The following pictographs are available as standard: Fire alarm, Withdraw •from premises, Extinguishing in progress, Gas alarm, Fire alarm.

TB24 cod. FH2700121 Optical/acoustic signalling double face panel

Power supply : 12 – 24 Vdc•Max consumption: 100 mA•Lighting by high efficiency leds•Buzzer sound pressure: 85dB at 1m•Steady/flashing light, selectable •Continuous/intermittent sound, selectable•Protection against polarity reverse•Working temperature: -10°C ÷ + 50°C•Material: self-extinguishing ABS, class V0•Protection: IP 40•The following pictographs are available as standard: Fire alarm, Withdraw •from premises, Extinguishing in progress, Gas alarm, Fire alarm.

SPTB cod. SF5000121 Bracket for optical/acoustic signalling double face panel TB24

TM220 cod. FH2800121 230Vac self-powered optical/acoustic signalling single face panel

Power supply : 230Vac•Max consumption: 100 mA•Lighting by high efficiency leds•Buzzer sound pressure: 85dB at 1m•Steady/flashing light, selectable •Continuous/intermittent sound, selectable•Protection against polarity reverse•Buffer battery: 3.6 V 1.5Ah Ni-Cd•Alarm endurance: 1 hour•Working temperature: -10°C ÷ + 50°C•Material: self-extinguishing ABS, class V0•Protection: IP 40•The following pictographs are available as standard: Fire alarm, Withdraw •from premises, Extinguishing in progress, Gas alarm, Fire alarm.

PANELS

OPTICAL-ACOUSTIC INDICATORS

TM24

TB24

TM220

64

Optical Acoustic Panels

TM224 cod. FH310012124Vdc self-powered optical/acoustic signalling double face panel

Power supply : 24Vdc•Max consumption: 100 mA•Lighting by high efficiency leds•Buzzer sound pressure: 85dB at 1m•Steady/flashing light, selectable •Continuous/intermittent sound, selectable•Protection against polarity reverse•Buffer battery: 3.6 V 1.5Ah Ni-Cd•Alarm endurance: 1 hour•Working temperature: -10°C ÷ + 50°C•Material: self-extinguishing ABS, class V0•Protection: IP 40•The following pictographs are available as standard: Fire alarm, Withdraw •from premises, Extinguishing in progress, Gas alarm, Fire alarm.

TMSV cod. FH5400121Single-face optical/sound plate with speech synthesizer

Power supply: 24Vdc•Absorption: 180 mA•8 pre-recorded messages•3 voice alarm zones•free combination of pre-recorded messages•1 customized message•4 operating modes: SPEECH - SOUND - SOUND + SPEECH - SPEECH + •SOUNDDimensions (L) x (H) x (D) mm: 365 x 180 x 50•

PANELS

OPTICAL-ACOUSTIC INDICATORS

TM224

TMSV

65

Outdoor visual repeaters

LR500 cod. SR1100121Outdoor visual repeater

Visual repeater allowing to show the alarm status of a detector installed •in hidden spaces. Suitable for all ELKRON detectors with ZB204 base or SD500R base. Power supply: 12 – 24Vdc•Absorption: 11 mA•Terminal connection•Working temperature: -10°C ÷ + 55°C•Weight: 30 g•Protection: IP40•Case material: ABS, class VO•2 high efficiency red leds•Steady/flashing light, selectable•Dimensions: 65.5 (L) x 60.6 (H) x 23.6 (D) mm •

LR500SI cod. SR1200121 Outdoor visual repeater for FAP500 digital systems

Visual repeater allowing to show the alarm status of a detector installed in •hidden spaces and to indicate detector regular operation (green led flashing). Suitable for all ELKRON detectors with SD500R base. This repeater can only be used with FAP500 detectors.Power supply: 12 – 24Vdc•Absorption: 11 mA•Terminal connection•Working temperature: -10°C ÷ + 55°C•Weight: 30 g•Protection: IP40•Case material: ABS, class VO•2 high efficiency white leds•1 high efficiency green led •Steady/flashing light, selectable•Dimensions: 65.5 (L) x 60.6 (H) x 23.6 (D) mm •

VISUAL REPEATERS

OPTICAL-ACOUSTIC INDICATORS

LR500SI

LR500

66

Bells

4476/24 cod. HS7300123 Bell with classic appearance for fire alarm systems and other warnings.

The internal movement with motor, pinion and striker, jointly with the external •bell in steel produces a powerful sound with a low current consumption.Power supply: 24 Vdc •Average absorption: 25 mA•Sound pressure at 1 metre distance: 93/95 dB•Operation temperature: -10°C ÷ +50°C•Protection degree: IP 42•

4460/24 cod. HS1700123Electronic bell with sophisticated appearance and innovative technology fully covered with polyurethane resin ensuring high protection and resistance degree.

Maximum control of sound signal through 28 tones that can be selected •during installation by 5 internal dip-switches and through volume control by trimmer.Installation is made simple by siren bayonet joint on siren base and by double •pins allowing to shunt connections.Enclosure material: Thermoplastic body, red colour •Power supply: 24 Vdc •Average absorption: 16 mA•Sound pressure at 1 metre distance: 102 dB•Operation temperature: -10°C ÷ +70°C•Protection degree: IP 54•

4479/24 cod. HS7200123Electronic bell with sophisticated appearance and innovative technology for fire alarm systems and other warnings.

Combining a miniaturised solenoid to a built-in control circuit, excellent •acoustic performance, minimum current consumption and high reliability are allowed.Power supply doubled pins and cap latching make the bell particularly easy •to be installed.IP 55 protection degree allows bell outdoor use; however, the bell can also be •mounted in indoor environments.Power supply: 24 Vdc •Average absorption: 30 mA •Operation temperature: -10°C ÷ +55°C•Sound pressure at 1 metre distance: 93-95 dB•Protection degree: IP 55•

3465/24 cod. HS1900123Piezoelectric sounder for indoor with xenon lamp

Power Supply: 24Vcc.•Absorption: 170 mA.•Sound pressure at 1 m: 110 dB.•Colour: red.•

ELECTRONIC BELLS

OPTICAL-ACOUSTIC INDICATORS

4476/24

4460/24

4479/24

3465/24

67

HP500F cod. HS5000121 Outdoor red self-powered siren made in die-cast aluminium.Provided with signalling flash with incandescent lamp.

Operation voltage: 24 Vdc •Protection degree: IP 43•Sound pressure: 104 dB (A) at 3 mt distance•Operation temperature: -25° C / +55° C•Assignable accumulator: 12 V 2,1 Ah•Dimensions (hxlxd): 265x210x65 mm.•

DSE/626 cod. HS2100123 Red siren for premises evacuation in compliance with with regulation 626/94. Two-tone alarm, xenon visual signalling.

Operation voltage: 230 Vac •Protection degree: IP 44•Sound pressure: 104 dB (A) at 3 mt distance•Operation temperature: -25° C / +55° C•Assignable accumulator: 12 V 2,1 Ah•Dimensions (hxlxd): 265x210x65 mm•Weight: 2,1 Kg.•

SOUNDERS

OPTICAL-ACOUSTIC INDICATORS

Electromagnetic Stop

1370/15 cod. MM7100123Electromagnetic stop implemented in order to keep open fire or transit do-ors and release them in case of fire.

The magnet has two mounting positions on magnet body and, by bracket •provided (15 cm bracket), allows the stop to be installed both as a wall stop and as a floor stop. Complete with unlocking pushbutton. It is available a model with 30 cm bracket with code MM7300123.Hooking force: 50 kg, actual•Working voltage: 24 Vdc•Absorption: 65 mA •Operation temperature: -10 °C to + 55 C°•Weight: 1,2 Kg•

1370/30 cod. MM7300123Same as 1370/15 with 30cm bracket.

EM50P cod. MM7000123Door holder electromagnet with release button. Power 24 Vdc. Holding force 50 Kg.

EM100P cod. MM9000123Door holder electromagnet with release button. Power 24 Vdc. Holding force 100 Kg.

ELECTROMAGNETS

HP500F

DSE/626

1370/15

68

EXPLOSION PROOFDEVICES

EXPLOSION PROOF DEVICES

P/406 cod. SB3000121Manual fire alarm pushbutton, with explosion-proof casing, for areas with potentially explosive atmosphere.

Emergency break glass hammer provided as standard. Pushbutton in die-•cast material, red epoxy paint.Holes for cables: 2x3/4 gas thread.•Classification: II 2GD EEx d IIB T6, EEx d IIB+H2 T6.•Certification: CESI 03 ATEX 050.•Working temperature: –20°C/+50°C.•Weight: 1.1 Kg.•

BUTTON

T/800 cod. FH3500121The optical/acoustic system includes the body of siren T/800S and the body of visual repeater T/800L. These shells are made of a casting of cast iron G-20 uni 5007. The two bodies are connected to each other.

Working voltage: 27 Vdc•Alarm absorption: 180 mA •Weight: 3 kg•

T/800S cod. HS1800121Siren made of a casting of cast iron G-20 uni 5007 with a diffusing cone of plastic material (ABS); inside the body there is placed an electronic circuit for acoustic activation.

Working voltage: 27 Vdc•Alarm absorption: 180 mA •Sound level: 60 db at 1 mt at 24 V•Protection degree: IP 65•Weight: 3 kg•

T/800L cod. SR0200121Visual repeater made up of a shell made of a casting of cast iron G-20 uni 5007. The body of the visual repeater is provided with a gem on cover cap of unbreakable (polycarbonate) material.

Inside the body there are placed a bakelite lamp holder and a 30 Volt 5 •Watt lamp; on the lamp holder there are arranged the pins for connecting repeater activation system.Working voltage: 10,5 to 36 Vdc•Alarm absorption: 200 mA •Protection degree: IP 65•Weight: 3 kg•

OPTICAL-ACOUSTIC INDICATORS

P/406

T/800

T/800S

T/800L

69

POWER SUPPLY UNITSAND BATTERIES

POWER SUPPLY UNITS AND BATTERIES

82425 SBG cod. PS7900123Power supplier with 27.6 V output voltage in switching version and current 2.5 A.

High protection degree against overload, polarity inversions, short circuit. •Power supplier status is signalled by 4 external leds: network in (Green) led, battery charger functionality (Green) led, battery down (Red) led, failure (Red) led. Provided with key for opening and closing the front lid.Primary power supply: 230 Vac•Protection degree: IP 30•Operation temperature: +5 °C to +40 °C•EN 54-4 certified•

82450 BG cod. PS8000123Power supplier with 27.6 V output voltage in switching version and current 5 A

High protection degree against overload, polarity inversions, short circuit. •Power supplier status is signalled by 4 external leds: network in (Green) led, battery charger functionality (Green) led, battery down (Red) led, failure (Red) led. Provided with key for opening and closing the front lid.Primary power supply: 230 Vac•Protection degree: IP 30•Operation temperature: +5 °C to +40 °C•EN 54-4 certified•

POWER SUPPLY UNITS

RB06 cod. RB041011312 V 7,2 Ah Water Proof rechargeable battery

RB12 cod. RB02101136 V 1,3 Ah Water Proof rechargeable battery.

RB 19 cod. RB031011312 V 2,2 Ah Water Proof rechargeable battery.

RB 15 cod. RB081011312 V 18 Ah Water Proof rechargeable battery.

RB 24 cod. RB051011312 V 26 Ah Water Proof rechargeable battery.

RB 612 cod. RB09101136 V 12 Ah Water Proof rechargeable battery.

RB 1212 cod. RB111011312 V 12 Ah Water Proof rechargeable battery.