Page 1: GUNON-Janus-Novec1230 Presentation R00

PT. GUNON INTENATIONALTAMAN TEKNO H3 NO. 1-2BSD CITY – TANGERANG

INDONESIA 15134PHONE : +62 21 7562680 FAX : +62 21 7562685

[email protected]@gunon.com

1

Page 2: GUNON-Janus-Novec1230 Presentation R00

PT. GUNON INTENATIONALWe are dealing in the Fire Protection and Detection System. Weprovide the systems based on Guideline Standards and ApprovalBodies :

2

Page 3: GUNON-Janus-Novec1230 Presentation R00

PT. GUNON INTENATIONALWe are also a distributor and agent of famous brands in the worldas follows :

3

Page 4: GUNON-Janus-Novec1230 Presentation R00

PT. GUNON INTENATIONALBased on the standard design guidelines, approval bodies,factory’s supports and our experiences, we provide :

* Consultation

* System Design

* Budget Estimation

* Sales

* Maintenance

* and after sales services

4

Page 5: GUNON-Janus-Novec1230 Presentation R00

PT. GUNON INTENATIONALOn the markets :

* High Rise Building

* Telecommunication and Data Centre

* Industrial, Petrochemical and Power Plant

* Oil and Gas

5

Page 6: GUNON-Janus-Novec1230 Presentation R00

PT. GUNON INTENATIONALProjects Reference

6

Page 7: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®

YOUR GATEWAY TO A NEW KIND OF SERVICE

Established by four leading experts in the fire protection industry with a combinedexperience of over 120 years, Janus Fire Systems is based on the principle of offering

its clients superior products and services.

Address: 1102 Rupcich, Crown Point, IN 46307, United States

Phone:(219) 663-16007

Page 8: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®Janus Fire Systems® fire suppression products are availableworldwide :

8

Page 9: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®Janus Fire Systems® fire suppression products are availableworldwide :

9

Page 10: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®Janus Fire Systems® fire suppression products are availableworldwide :

10

Page 11: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

Typical Clean Agent System Layout

11

Page 12: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

When to use Clean Agents ?

* Protecting high value assets

- Energized electrical areas

- Artifacts and archived data

* Continuous operations must be

maintained

* Life safety is a concern

- Emergency communications

- Occupied or may be occupied

* Must be a clean agent

12

Page 13: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

Typical areas of fire protection:

* Computer Rooms

* Data Storage Facilities

* Telecommunications

* Oil & Gas Petrochemical Facilities

* Museums

* Libraries and Archives

* Medical Facilities

* Manufacturing Facilities

* Storage Areas

13

Page 14: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components:

* NovecTM 1230 Fire Protection Fluid

* Agent Storage Components and Accessories

*Agent Fluid Distribution Components

* Control Panels

* Detection and Alarm Devices

* Flow Calculation Software

14

Page 15: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

What are Clean Agents?

Electrically non-conducting, volatile, or gaseous fire extinguishant that does not leave aresidue upon evaporation

(NFPA 2001, Sec. 3.3.6)

* Does not conduct electricity

* Gaseous

* Does not leave a residue behind

* Is not carbon dioxide

15

Page 16: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Novec 1230 is a highly-efficient clean agent :

* Won’t Damage Equipment:

- Electrically non-conductive

- Non-corrosive

* No Downtime or Cleanup:

- Evaporates cleanly, leaving no residue

- Does not damage electronics

- Can be safely used on energized equipment,

helping to ensure continuity of operations

during a fire emergency16

Page 17: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Novec 1230 is a highly-efficient clean agent :

17

Page 18: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Designed to Provide a Large Margin of Human Safety

Clean agents fire suppression applications often include the presence of people, sosafety to human life is a critical issue when selecting a fire suppression product. 3M™Novec™ 1230 Fire Protection Fluid is a highly efficient fire extinguishant that's safe foruse in occupied spaces. The large margin between Novec 1230 fluid's useconcentration and "Non Observed Adverse Effects Level" provides the largest marginof safety relative to other chemical clean agents, CO2, and inert gas mixtures.

18

Page 19: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Designed to Provide a Large Margin ofHuman Safety

19

Page 20: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Novec 1230 Fluid Performance

Don’t Just Manage a Fire. Extinguish It.3M™ Novec™ 1230 Fire Protection Fluid is a highly-effective clean agent firesuppressant, designed to extinguish a fire in its incipient stage before it has a chance tospread. It is applied as a gas, but is liquid at room temperature, and can be effectivelyused in streaming, flooding systems, or for use in inerting and explosion suppressionapplications. 20

Page 21: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Novec 1230 Fluid Performance

Knocks down fires fast

Novec 1230 Fluid has a very low heat of vaporization, approximately 25 times less thanthat of water. This, along with a higher vapor pressure, causes Novec 1230 Fluid toevaporate more than 50 times faster than water. It also allows the clean agent totransition from a liquid to a gaseous state very rapidly when discharged through anozzle, and readily achieve vapor extinguishing concentrations in air. With highextinguishing efficiency and a wide margin of safety, Novec 1230 fluid is a greatalternative to water sprinkler systems, foam and dry chemicals due to:

* Low toxicity (no harm to personnel)

* Extinguishes fires in less than half the time of CO2 & inert gases

* No damage to sensitive equipment

* Not targeted for emission reduction or phaseout 21

Page 22: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Sustainability :From its inception, 3M™ Novec™ 1230 Fire Protection Fluidwas designed to address the global demand for a sustainableclean agent. It is effective at extinguishing fires andis not targeted for emission reduction, phase-out orphase-down. Novec 1230 fluid offers the sustainable cleanagent properties you need, such as:* Zero ozone depletion potential (ODP)* An atmospheric lifetime of 5 days, compared to 65 years for halons* A global warming potential (GWP) of less than 1 – about the same as naturally-

occurring carbon dioxide 22

Page 23: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : NovecTM 1230 Fire Protection Fluid

Sustainability :

23

Page 24: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Agent Storage Components

Janus Fire Systems provides 500 Series Novec 1230 Clean Agent Cylinders.

Cylinders are charged with the clean agent to a maximum filling density of up to 70lb./ft.3 (1121 kg/m3) of cylinder volume.

Each cylinder is super-pressurized with dry nitrogen to 500 psi (34.48 bar)

All cylinders are equipped with an identification nameplate indicating the initial fillquantity of the clean agent.

24

Page 25: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Agent Storage Components

Janus Fire Systems have 3 (three) cylinder series :

* Sv Series : filling capacity 10.00 - 59.40 kg

* Mv Series : filling capacity 57.20 – 191.40 kg

* Lv Series : filling capacity 137.9 – 453.6 kg

Sv Mv Lv

25

Page 26: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Agent Storage Components

500 Series Novec 1230 Clean Agent Cylinders offer Enhanced Design Capabilitycompared with 360 psig (25 bars) cylinders :

* Less required Clean Agent

An additional Clean Agent required when the pressure and flow rate of agent in the pipeand nozzles has been met the limitation of Pipe Size and Flow Rate

* Smaller Size and Lower Quantity of Cylinders

Increasing Size and Quantity of Cylinders is required to get more pressure as thesmaller size and lower quantity of cylinders can not meet the requirement of listedsystem such as Discharge Time, Design Concentration, Flow Rate and Pressure at thedistribution pipe and nozzles

* Longer Pipe Length and Larger Pipe Network

* Smaller Pipe Diameters26

Page 27: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Agent Storage Components

* Other features provided and affixed to the cylinders :

- Cylinder Low Pressure Supervisory Switch

- Level Liquid Indicator

The features is designed to monitor Pressure and Agent are in good condition andready for used when it’s needed. With this features, no need to do daily inspectiontherefore more effective and efficient on maintenance purpose.

* Janus Fire Systems 500 Series offer more effective, efficienct

and flexibility

27

Page 28: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Sv Series Agent Storage Components

28

Page 29: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Sv Series Agent Storage Components

29

Cylinder Valve: Controls release of the clean agent Differential pressure operated valve Forged brass body and cap Shipped with anti-recoil safety plug installed in

the discharge outlet

Dip Tube: Extends from cylinder neck down to the bottom of

the cylinder

Cylinder Bracket One strap and rail with accompanying twirl nuts

and cap screws

Cylinder: Welded seam cylinder Manufactured to requirements of USDOT

(Department of Transportation) and TransportCanada for compressed gas

Designed for vertical mounting only

CylinderValve

Dip Tube

CylinderBracket

Cylinder

Page 30: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Sv Series Agent Storage Components

30

Valve Actuation Connection (1) —Attachment point for electric (primary) orpneumatic (slave) valve actuator. Pressure Gauge (2) — Monitors

cylinder pressure.

Low-Pressure Supervisory Switch (3) — Mountedto cylinder valve. Monitor and annunciates lowcylinder pressure.

Rupture Disc (4) —Protects cylinderfrom over pressure.Rupture pointbetween 850 psi(58.6 bar) and 1000psi (68.9 bar)

Discharge Outlet (5)— Connects valve todischarge piping. 1-1/4 in (32 mm) femaleNPT connection.

Pilot Actuation Port(6) — Appliesactuation pressure toslave cylinders ordischarge pressureswitch. 3/8 in (10 mm)female NPTconnection.

Page 31: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Mv Series Agent Storage Components

31

Page 32: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Mv Series Agent Storage Components

32

Liquid Level Indicator: Nonmagnetic tube

containing a measurementtape attached to a magnet

As tape is removed, magnetengages at the liquid surfacewhere a floating metallic ballsits

Measurement can becompared with theappropriate chart in thedesign manual to determinethe current fill

DipTube

CylinderValve

CylinderBracket

Cylinder

LiquidLevelIndicator

Has features identical to SvSeries Cylinder Assembly

Page 33: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Mv Series Agent Storage Components

33

Valve Actuation Connection (1) —Attachment point for electric (primary) orpneumatic (slave) valve actuator. Pressure Gauge Connection (2) — Attachment point for

pressure gauge

Low-Pressure SupervisorySwitch Connection (3) —

Attachment point for low-pressure supervisory switch.

Rupture Disc (4) —Protects cylinder fromover pressure. Rupturepoint between 850 psi(58.6 bar) and 1000 psi(68.9 bar)

Discharge Outlet (5)— Connects valve todischarge piping. 2 in(50 mm) groovedconnection

Pilot Actuation Port(6) — Appliesactuation pressure toslave cylinders ordischarge pressureswitch. ¼ in (8 mm)female NPTconnection

Page 34: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Lv Series Agent Storage Components

34

Page 35: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Lv Series Agent Storage Components

35

Rupture Disc: Protects cylinder from overpressure Rupture point is between 850 psi (58.6 bar)

and 1000 psi (68.9 bar)

CylinderValve

Dip Tube

CylinderBracket

Cylinder

Liquid LevelIndicator

Rupture Disc

Has features identical to Mv SeriesCylinder Assembly except:

Lv Series 1000 lb Cylinder notTransport Canada approved.

Page 36: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Lv Series Agent Storage Components

36

Valve Actuation Connection (1) —Attachment point for electric (primary) orpneumatic (slave) valve actuator.

Pressure Gauge Connection (2) — Attachment point forpressure gauge

Low-Pressure SupervisorySwitch Connection (3) —

Attachment point for low-pressure supervisory switch.

Discharge Outlet (4)— Connects valve todischarge piping. 3 in(80 mm) groovedconnection.

Pilot Actuation Port(5) — Appliesactuation pressure toslave cylinders ordischarge pressureswitch. ¼ in (8 mm)female NPTconnection

Page 37: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Multi Cylinders Application

Multi Cylinders application is provided for the enclosures with the volume is larger thancan be covered by single cylinder.

37

* Up to fifteen slave cylinders may be actuated from one primary cylinder* Maximum length of 100 ft (30.4 m) of pilot hose or ¼” (8 mm) copper

tubing on either side of the primary cylinder* Maximum length of 25 ft (7.62 m) of ¼” (8 mm) pilot piping on either

side of the primary cylinder

Page 38: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Multi Cylinders Application

38

Page 39: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Multi Zones Application

Multiple hazards can often be protected with a common set of cylinders by usingselector valves. Selector valves components are required in these specific cylinderarrangements that utilize selector valves to allow the protection of multiple hazards orhazard zones by one set of clean agent cylinder.

39

Page 40: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Multi Zones Application

40

Page 41: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Agent Fluid Distribution Components

These components consist of the discharge nozzles used to atomize the liquid Novec1230 fluid and introduce it into a protected hazard along with the associated pipingsystem.

* Discharge Nozzle Ports : 4, 6, or 8 port (90°, 180°, 360°)

* Maximum nozzle height for a protected space is 18 ft 4 in (5.59 m) per tier of nozzles.

* Additional tiers are required for nozzle heights greater than 18 ft 4 in.

* Nozzles must be mounted within 4 ft 5 in (1.35 m) of the ceiling

41

Page 42: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Components : Agent Fluid Distribution Components

42

Page 43: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Component : Control Panel

* For systems requiring UL listing, the control panel must be UL listed and compatible

with the electrical valve actuator as indicated in the control panel manual.

* For systems requiring FM approval, the control panel must be FM approved and

compatible with the electric valve actuator as indicated in the control panel manual.

* The control panel should be located in an accessible area and installed in compliance

with NFPA 72 (National Fire Alarm Code).

43

Page 44: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Component : Control Panel

44

Page 45: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Component : Detection and Alarm Devices

* Detector selection is dependent upon hazard occupancy and environmental

conditions.

* Systems are designed to extinguish a fire rapidly in its incipient stage. The use of

smoke detectors of appropriate type must be considered to provide the earliest

possible indication of a fire detection with a low susceptibility to false alarms.

* For systems requiring UL listing, detectors must be UL listed and compatible with the

control panel as indicated in the control panel manual.

* Air sampling detection systems can also be utilized.

* In most applications, the detection devices are installed in a cross-zone (double

knock) or voting configuration. Cross-zoning of early warning detectors affords

stability yet provides early detection. 45

Page 46: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Component : Detection and Alarm Devices

* Audible and visual devices may be utilized to indicate alarm conditions, system

status, or trouble conditions within the system.

* Audible alarm devices must be of a sufficient decibel level to be heard over the

maximum noise level in the protected hazard.

46

Page 47: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System

System Component : Flow Calculation Software

47

Page 48: GUNON-Janus-Novec1230 Presentation R00

JANUS FIRE SYSTEMS®NovecTM 1230 Clean Agent Suppression System