    Inspection of Shop FabricatedASTs per the SPCC Rule

    Inspection of Shop FabricatedInspection of Shop Fabricated

    ASTs per the SPCC RuleASTs per the SPCC Rule

    Wayne B. Geyer, P.E.

    Steel Tank InstituteA Division of STI/SPFA

    Wayne B. Geyer, P.E.Wayne B. Geyer, P.E.

    Steel Tank InstituteSteel Tank InstituteA Division of STI/SPFAA Division of STI/SPFA

  • 7/29/2019 Inspection of ASTs

    2/60

    Few states have any certifications for ASTinstallers and it shows in the creativeways the tank systems are installed.

    - J ohn Cignatta, course instructor forSTI AST inspector certification

  • 7/29/2019 Inspection of ASTs

    3/60

    Doorways in dikes No overfill alarms

    ..

    adequatecontainment

    Leaking tank

    Major Facility

    Review of 28 tanks at a

    Nearly 90% lackedadequate venting

    Over 50% lacked

  • 7/29/2019 Inspection of ASTs

    4/60

    Review of 28 tanks at aMajor Facility

    0 20 40 60 80 100

    Serious Other

    Emergency Vent

    Overfill

    UL Listing

    Containment

    Normal Vent

    Spill Control

    % of tanks

    Missing i

    tem

  • 7/29/2019 Inspection of ASTs

    5/60

    API 653 or STISP001

    Requires Integrity

    Revised SPCC Rules

    References industrystandards

    Tank inspection per

    Testing

    Visual inspectionalone no longersufficient

  • 7/29/2019 Inspection of ASTs

    6/60

    Test Each AbovegroundContainer for Integrity

    Section 112.8(c)(6) On a regular schedule

    Combine visual inspection withanother testing technique Hydrostatic testing Radiographic testing

    Ultrasonic testing Other nondestructive shell testing

    Frequently inspect the outside of

    Acoustic emissions testing

    container

  • 7/29/2019 Inspection of ASTs

    7/60

    Show me some tanks!!!

  • 7/29/2019 Inspection of ASTs

    8/60

  • 7/29/2019 Inspection of ASTs

    9/60

  • 7/29/2019 Inspection of ASTs

    10/60

  • 7/29/2019 Inspection of ASTs

    11/60

  • 7/29/2019 Inspection of ASTs

    12/60

  • 7/29/2019 Inspection of ASTs

    13/60

  • 7/29/2019 Inspection of ASTs

    14/60

  • 7/29/2019 Inspection of ASTs

    15/60

  • 7/29/2019 Inspection of ASTs

    16/60

  • 7/29/2019 Inspection of ASTs

    17/60

    AST Standardsfor Shop Fabricated Tanks

    API - American Petroleum Institute

    UL - Underwriters Laboratories

    SwRI - Southwest Research Institute

  • 7/29/2019 Inspection of ASTs

    18/60

    API Specifications

    API 12F Specification for Shop Welded Tanks for

    Storage of Production Liquids

    Vertical, cylindrical only API 650, Appendix J

    Shop Assembled Welded Steel Tanks

    for Oil Storage

    Vertical, cylindrical only

  • 7/29/2019 Inspection of ASTs

    19/60

    API Vertical Tanks

  • 7/29/2019 Inspection of ASTs

    20/60

    API Vertical-UL Horizontal Tanks

  • 7/29/2019 Inspection of ASTs

    21/60

    Underwriters Laboratories

    UL 142 SteelAboveground Tanks forFlammable and

    Combustible Liquids UL 2085 Protected

    Aboveground Tanks for

    Flammable andCombustible Liquids

  • 7/29/2019 Inspection of ASTs

    22/60

    UL 142 Steel thickness

  • 7/29/2019 Inspection of ASTs

    23/60

    UL 142 type tanks

  • 7/29/2019 Inspection of ASTs

    24/60

    UL 142 type tanks

  • 7/29/2019 Inspection of ASTs

    25/60

  • 7/29/2019 Inspection of ASTs

    26/60

    STI SP001-03

    Standard for Inspection ofInService Shop

    Fabricated AbovegroundTanks for Storage of

    Combustible andFlammable Liquids

  • 7/29/2019 Inspection of ASTs

    27/60

    How STI SP001 differs fromAPI 653

    API 653 emphasis is the large, fieldconstructed tanks per API 650.

    Strictly vertical tanks.

    The bottom of the tank is not visible.

    API 653 requirements are needed

    because Large volume

    Large pressure

  • 7/29/2019 Inspection of ASTs

    28/60

    How STI SP001 differs fromAPI 653

    API 650 includes equations forcalculating the steel thickness neededfor a particular tank.

    API 653 allows for / requires more

    judgement by inspector

  • 7/29/2019 Inspection of ASTs

    29/60

    Shop fabricated tanks Tables that specify the steel thickness

    Manufactured in controlled shopenvironments

    How STI SP001 differs fromAPI 653

    based on tank diameter and capacity.

    Smaller capacities and smaller hydrostaticpressures

    Capacity up to 50,000 gallons.

  • 7/29/2019 Inspection of ASTs

    30/60

    50,000 gallon tank

  • 7/29/2019 Inspection of ASTs

    31/60

    Corrosion concerns

    Check corroded

    areas to findminimum thickness

  • 7/29/2019 Inspection of ASTs

    32/60

    Single wall tanks restingdirectly on the ground are a

    concern!!

  • 7/29/2019 Inspection of ASTs

    33/60

    Periodic Inspection by tank owner

    >Water inside tank

    > Vents> Pipe connections> Exterior paint> Foundation

    www.steeltank.com/library/pubs/waterinfueltanks.htm

  • 7/29/2019 Inspection of ASTs

    34/60

    Certified Inspection

    Performed by Qualified Tank Inspector STI Trained and Certified

    API Certified

    Every 10 Years

    All types of tanks (single and double

    wall, on ground and elevated)

  • 7/29/2019 Inspection of ASTs

    35/60

    September 20 - 24 Tennessee

    J une 14 - 18 California

    J uly 19 - 23

    STI AST Inspector Training

    Michigan May 24 - 28

    New York

    NEW for 2004 Level 1

    Tank inspector

    Level 2 Tank system

    inspector

  • 7/29/2019 Inspection of ASTs

    36/60

    Level 2 Tank System

  • 7/29/2019 Inspection of ASTs

    37/60

    Tank type dictates inspection method:Single wall not in contact with

    ground

    Single wall in contact withground

    Double wall or double-bottom

    STI Certified Inspection

  • 7/29/2019 Inspection of ASTs

    38/60

    Double wall or double-bottom

    Check leak

    detection system

    Check for water orfuel in interstice

  • 7/29/2019 Inspection of ASTs

    39/60

    STI Certified Inspection UT Testing by

    scanning if possible Most reliable method

    for determining wallthickness

    Qualified UT inspectornecessary (ASNTSpecifications)

  • 7/29/2019 Inspection of ASTs

    40/60

    Must compare remaining wallthickness to original thickness

    6. Certified Inspection Criteria

  • 7/29/2019 Inspection of ASTs

    41/60

    STI SP031-04

    Standard for Repair ofInService ShopFabricated

    Aboveground Tanksfor Storage of

    Combustible andFlammable Liquids

  • 7/29/2019 Inspection of ASTs

    42/60

    Patches New bottoms

    SupervisingPersonnel

    STI inspectors

    SP031 Repair Standard

    Adding openings

    Supportmodifications

    API inspectors

    Repair Personnel

    Tank manufacturer Testing of repairs

    ASME welders

    AWS welders

  • 7/29/2019 Inspection of ASTs

    43/60

    Tank owner surprises

    Not all that meets the eye!

  • 7/29/2019 Inspection of ASTs

    44/60

    Tank #1

  • 7/29/2019 Inspection of ASTs

    45/60

    Tank #1

    No grounding anywhere

    Unsecured AST's in a flood plain (Not a single anchorbolt)

    Many Electric Code Violations

    Improperly Secured Conduits

    OSHA Access Issue on the back stairs and topplatform

    PVC Caps atop various nozzles (No Fire Rating forPVC)

    Labeling Issues

  • 7/29/2019 Inspection of ASTs

    46/60

    Tank #2

  • 7/29/2019 Inspection of ASTs

    47/60

    Tank #2

    Fuel Piping

    Unsupported Pipes

    Leaking SubmersibleTurbine Pump

    No CP on buried fuelpipe runs

    Electric Code Violations

    Kinked Flex Connector

    Improperly Installed

    Combustible Materialsstored inside dike

    Poor Control on Tank

    Pipes and conduits too

    close in pipe trench Unsupported Conduits

    Missing Fire Diamonds

    Filling Routine Spillage

    Conduits between fuelpipes in pipe trench

  • 7/29/2019 Inspection of ASTs

    48/60

    Tank #3

  • 7/29/2019 Inspection of ASTs

    49/60

    Tank #3

    Unsupported conduits

    Valve on Return Piping

    tank's annular space

    No Vehicle Damage

    PVC Caps on various tanknozzles

    Flex Fuel lines secured toUnistrut with conduitclamps

    Normal vent on secondary

    No fire diamonds

    Improper labeling ofnozzles

    bottom)

    Veeder-Root bottomwater floats can get hungup on shafts if rustymuck/mud forms in

    Tank not being stickedto check either ATGSaccuracy oraccumulation of water

    Protection (i.e., bollards)

  • 7/29/2019 Inspection of ASTs

    50/60

    Get the BIG picture first

  • 7/29/2019 Inspection of ASTs

    51/60

    Enough openings ontop?

    underground? Tank next to river, is

    it anchored?

    Supports more than12 in. high?

    Condition offoundation?

    From 20 feet away.

    Dirt spots on tank,fuel spilled?

    Coated for Adequate

    containment? Paint condition?

    Level gauge visible?

  • 7/29/2019 Inspection of ASTs

    52/60

    Adequate supports?

    condition? Weep holes? Use

    UV light here

    Closer inspection

    Emergency ventcondition?

    Normal vent

    Look inside tank, butwith proper trainingonly.

  • 7/29/2019 Inspection of ASTs

    53/60

    New STI StandardsCommittee

    To review inspection standards

    SP001

    SP031

  • 7/29/2019 Inspection of ASTs

    54/60

    Does this Comply?

  • 7/29/2019 Inspection of ASTs

    55/60

  • 7/29/2019 Inspection of ASTs

    56/60

  • 7/29/2019 Inspection of ASTs

    57/60

  • 7/29/2019 Inspection of ASTs

    58/60

  • 7/29/2019 Inspection of ASTs

    59/60

    I ti f T k

  • 7/29/2019 Inspection of ASTs

    60/60

    Inspection of TanksKeeps Things Happy