Insulation CI/SfB Third Issue February 2019 (21.9) Rn7 M2 STANDARD DETAILS FOR 90 MM INSULATION BOARD IN A 100 MM CAVITY Low Energy – Low Carbon Buildings K106 Cavity Board
Transcript

Insulat ionCI/SfB

Third Issue February 2019

(21.9) Rn7 M2

STANDARD DETAILS FOR 90 MM INSULATION BOARD IN A 100 MM CAVITY

Low Energy – Low Carbon Buildings

K106 Cavity Board

2

Contents

Page

Introduction & How to Use This Guide 3 Heat Loss from Junctions 3 Junctions & Building Compliance 3 Thermal Modelling of Junctions 3 Critical Temperature Factors 4 Calculation Methodology 4 How to Use these Details 4 Limitations & Applicability of Modelling 4

Wall Details E1 Open Back Lintel (Insulated) with Perforated Steel Base Plate 6 E1 Open Back Lintel (Insulated) with Perforated Steel Base Plate and Insulated Reveal 8 E1 Open Back Lintel (Uninsulated) with Perforated Steel Base Plate 10 E1 Open Back Lintel (Uninsulated) with Perforated Steel Base Plate and Insulated Reveal 12 E2 Open Back Lintel (Insulated) without Base Plate 14 E2 Open Back Lintel (Insulated) with Insulated Reveal but without Base Plate 16 E2 Open Back Lintel (Uninsulated) without Base Plate 18 E2 Open Back Lintel (Uninsulated) with Insulated Reveal but without Base Plate 20 E2 Independent Steel Lintel externally and Independent Concrete Lintel internally 22 E2 Independent Steel Lintel externally and Independent Concrete Lintel internally with Insulated Reveal 24 E3 Sill (Normal) 26 E3 Sill (Normal) with Insulated Reveal 28 E4 Jamb (Normal) 30 E4 Jamb (Normal) with Insulated Reveal 32 E5 Ground Floor – Solid Concrete Slab 34 E5 Ground Floor – Beam & Block (Parallel) 36 E5 Ground Floor – Beam & Block (Perpendicular) 38 E5 Ground Floor – Suspended Timber Floor (Parallel) 40 E6 Intermediate Floor within a Dwelling – Concrete 42 E6 Intermediate Floor within a Dwelling – Timber 44 E7 Party Floor between Dwellings (in Blocks of Flats) 46 E10 Eaves (Insulation at Ceiling Level) 48 E11 Eaves (Insulation at Rafter Level) 50 E12 Gable (Insulation at Ceiling Level) 52 E13 Gable (Insulation at Rafter Level) 54 E14 Flat Roof 56 E15 Flat Roof with Parapet 58 E16 Corner (Normal) 60 E17 Corner (Inverted) 62 E18 Party Wall between Dwellings (Filled Cavity) 64 E18 Party Wall between Dwellings (Unfilled Cavity) 66

Additional Construction Details E2 Lintel (Checked Reveal) 68 E3 Sill (Checked Reveal) 69 E4 Jamb (Checked Reveal) 70 E5 Solid Ground Floor (Cavity Tray) 71 E5 Timber Floor – Perpendicular 72 E16 Corner – Normal (alternative Mitre Joint) 73 E17 Corner – Inverted (alternative Mitre Joint) 74 – Flue (Core Drilled, no Separation) 75 – Flue (Built in, no Separation) 76 – Flue (Built in, Separation) 77 – Wall Tie 78

3

Introduction

Heat Loss from JunctionsThermal bridging occurring at the junctions of a building’s planar elements (i.e. between roofs, walls, openings and floors) can add significantly to a building’s total fabric heat loss.

Higher heat flows occur at junctions due to complex geometries, or from the use of materials with a higher thermal conductivity than the adjacent materials. This can cause localised reductions of internal surface temperatures, which can lead to surface condensation and mould growth problems. Good design detailing can help to avoid these issues. The details in this guidance have been developed with the aim of being buildable, achieving good thermal performance and minimising risk.

Linear thermal bridging describes the heat–loss occurring at junctions between elements e.g. between a wall and floor, or around openings e.g. at sills, lintels and jambs. A ψ–value (psi–value) is the heat loss through a junction, which is additional to the heat flow through the adjoining plane elements, and is measured in W/m.K.

ψ–values are not taken into account in U–value calculations. Instead they are taken into account separately in the calculation methodologies used to assess the operational CO2 emissions of buildings e.g. SAP in the UK for domestic purposes, or SBEM for non–domestic.

Junctions & Building ComplianceThere are three possibilities for specifying thermal bridging:

a. details conform with Approved Design Details or another government approved source involving independent assessment of the construction method. In this case, use ψ–values from the approved column on Table K1, or from the approved source;

b. ψ–values calculated by a person with suitable expertise and experience in accordance with BRE IP 1/06 and BR 497 (Conventions for Calculating Linear Thermal Transmittance and Temperature Factors). In this case, use those calculated ψ–values along with the length of each junction; or

c. if neither of the above applies, use a global default value for overall heat losses in the energy calculation to take account of the heat loss due to thermal bridging (a value of 0.15 W/m².K is added to overall elemental losses, making it harder to achieve compliance).

A combination of details from a. and b. above can be used and where some details are missing, the ψ–values from the ‘default’ column in Table K1 can be used.

The ψ–values in this document have all been calculated by persons with suitable expertise and experience as per option b. above.

Thermal Modelling of Junctionsψ–values have been created for the major junctions involving Kingspan Kooltherm® K106 Cavity Board, following the guidelines in BR 497.

All thermal modelling work was undertaken by Competent Thermal Modellers, who have successfully completed training and portfolios with ACD Certification Ltd and are experienced in thermal modelling of junction heat losses, on behalf of Kingspan Insulation Ltd.

The assessors who undertook the thermal modelling in this document are:

• Mr Jonathan Ducker

• Miss Samantha Lloyd

All of the calculated ψ–values for the Kingspan Insulation junction details are better than the default ψ–values for the accredited details as given in BRE IP 1/06 and Table K1 of SAP 2012.

4

Critical Temperature FactorsReasonable provision to avoid surface condensation, or mould growth occurring as a result of thermal bridges, is to demonstrate that details achieve a temperature factor that is no worse than the performance set out in BRE IP 1/06.

The temperature factor is a property of the construction, surface resistances and internal and external temperatures. It is used to assess the risk of surface condensation or mould growth. This parameter has been provided for all of the junction variants.

In all cases the calculated values are higher than the critical temperature factor for dwellings (fCRsi of 0.75) as given in BRE IP 1/06, which limits the risk of surface condensation or mould growth. Higher humidity condition buildings, for example swimming pools (fCRsi of 0.90), may require alternative details and constructions.

All of the modelled Kingspan Kooltherm® K106 Cavity Board details achieve acceptable temperature factors in accordance with BRE IP 1/06.

Calculation MethodologyThe thermal modelling of the Kingspan Kooltherm® K106 Cavity Board details was undertaken using two transient and steady–state heat transfer software packages produced by Blocon (as appropriate for the detail). HEAT 2 was used for the two–dimensional details and HEAT 3 for the three–dimensional details.

The modelled U–values and underfloor temperatures for suspended and beam and block floors were determined using the STROMA U–value calculator.

Junctions were modelled using a 90 mm thickness of Kingspan Kooltherm® K106 Cavity Board in an overall 100 mm cavity, with a 10 mm residual cavity air–space, and with a variety of internal leaf blockwork types, including three variations of light–weight blockwork (0.11 W/m.K, 0.15 W/m.K and 0.19 W/m.K), a version with medium dense blockwork (0.51 W/m.K) and one with dense blockwork (1.13 W/m.K).

How to Use these DetailsAdditional modelling was undertaken, which looked at various external leaf and internal finishes (see section below).

The detail sheets include a process sequence and also guidance on how to achieve a good level of air–tightness.

The ψ–values and temperature factors are provided for different bands of internal leaf blockwork conductivity. Where a different conductivity blockwork is used, performance can be inferred from the poorest, closest blockwork modelled.

The ψ–values cited may be used in calculations of building heat loss, where the principles of construction and key element specifications have been followed.

Limitations & Applicability of ModellingThe ψ–values could be reasonably used whenever the external leaf of the construction is constructed either from external brickwork, or stonework, or where the external leaf is rendered blockwork, and when the external leaf is not less than 100 mm in thickness. The ψ–values can also be considered to be valid to two significant figures where the internal finish is either plaster or plasterboard on dabs, with or without skim.

For junctions around openings (windows and doors), variants have been included covering a 30 mm overlap, between the window frame and the cavity, and a full overlap (between the frame and cavity), or for a check reveal. Options for both full overlap and for a check reveal were thermally modelled and as the results were very similar, these details reflect the worst case result of the two.

Calculated ψ–values can be used by energy assessors for buildings constructed in accordance with associated details for buildings constructed in England, Scotland, Wales and Northern Ireland.

Where proposed constructions significantly differ from the enclosed process sequences, or use alternative materials, these ψ–values and temperature factors should not be used.

These details represent typical detailing to achieve a good level of thermal performance, however the details included in this document may not be suitable for use in all circumstances. Where there is any uncertainty, Building Control Body (BCB) requirements and advice should always be sought and followed. All other site requirements and relevant building regulations must be taken into consideration when implementing the details.

Kingspan Insulation Thermal Modelling

5

E1 – Open Back Lintel (Insulated) with Perforated Steel Base Plate

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / proprietary insulated lintel should be taped with a50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the insulated lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the insulated lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the joint between the window frame and the internal

linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.251 0.261 0.270 0.301 0.324

Temperature Factor (f) 0.845 0.846 0.851 0.862 0.868

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.231 0.247 0.259 0.283 0.337

Temperature Factor (f) 0.920 0.913 0.909 0.907 0.904

Detail

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

6

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary insulated lintel with a perforated base plate

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

7

8

E1 – Open Back Lintel (Insulated) with Perforated Steel Base Plate and Insulated Reveal

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / proprietary insulated lintel should be taped with a 50 mm(min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the insulated lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the insulated lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Kingspan Kooltherm® K118 Insulated Plasterboard

32.5 mm added to the window reveal with adhesive and supplementary fi xings. Ensure Kingspan Kooltherm® K118 Insulated Plasterboard butts the window frame. Seal the perimeter with fl exible sealant.

l Seal the joint between the window frame and the internal linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.179 0.197 0.210 0.258 0.288

Temperature Factor (f) 0.920 0.912 0.907 0.899 0.902

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.188 0.208 0.224 0.279 0.314

Temperature Factor (f) 0.911 0.904 0.899 0.891 0.894

Detail

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

9

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary insulated lintel with a perforated base plate

Kingspan Kooltherm® K118 Insulated Plasterboard adhered with acrylic sealant adhesive

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

10

E1 – Open Back Lintel (Uninsulated) with Perforated Steel Base Plate

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / lintel should be taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the joint between the window frame and the internal

linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.280 0.292 0.302 0.338 0.366

Temperature Factor (f) 0.829 0.829 0.828 0.855 0.861

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.265 0.284 0.300 0.359 0.397

Temperature Factor (f) 0.915 0.907 0.902 0.892 0.893

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

11

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary uninsulated lintel with a perforated base plate

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

E1 – Open Back Lintel (Uninsulated) with Perforated Steel Base Plate and Insulated Reveal

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / lintel should be taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Kingspan Kooltherm® K118 Insulated Plasterboard

32.5 mm added to the window reveal with adhesive and supplementary fi xings. Ensure Kingspan Kooltherm® K118 Insulated Plasterboard butts the window frame. Seal the perimeter with fl exible sealant.

l Seal the joint between the window frame and the internal linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.207 0.225 0.239 0.292 0.323

Temperature Factor (f) 0.919 0.911 0.907 0.897 0.897

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.203 0.230 0.251 0.320 0.364

Temperature Factor (f) 0.927 0.916 0.893 0.881 0.880

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

12

13

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary uninsulated lintel with aperforated base plate

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

Kingspan Kooltherm® K118 Insulated Plasterboard adhered with acrylic sealant adhesive

14

E2 – Open Back Lintel (Insulated) without Base Plate

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / proprietary insulated lintel should be taped with a50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the insulated lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the insulated lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the joint between the window frame and the internal

linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.200 0.211 0.220 0.261 0.293

Temperature Factor (f) 0.938 0.938 0.942 0.947 0.949

Full Overlap (Incl. Checked reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.184 0.196 0.206 0.266 0.303

Temperature Factor (f) 0.950 0.943 0.937 0.916 0.911

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

15

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary insulated lintel

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

E2 – Open Back Lintel (Insulated) with Insulated Reveal but without Base Plate

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / proprietary insulated lintel should be taped with a50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the insulated lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the insulated lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Kingspan Kooltherm® K118 Insulated Plasterboard

32.5 mm added to the window reveal with adhesive and supplementary fi xings. Ensure Kingspan Kooltherm® K118 Insulated Plasterboard butts the window frame. Seal the perimeter with fl exible sealant.

l Seal the joint between the window frame and the internal linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.149 0.171 0.184 0.236 0.273

Temperature Factor (f) 0.939 0.930 0.925 0.910 0.907

Full Overlap (Incl. Checked reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.143 0.160 0.182 0.243 0.285

Temperature Factor (f) 0.936 0.929 0.921 0.904 0.901

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

16

17

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary insulated lintel

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

Kingspan Kooltherm® K118 InsulatedPlasterboard adhered with acrylicsealant adhesive

18

E2 – Open Back Lintel (Uninsulated) withoutBase Plate

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / lintel should be taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the joint between the window frame and the internal

linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.286 0.299 0.311 0.359 0.395

Temperature Factor (f) 0.844 0.847 0.850 0.861 0.872

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.253 0.271 0.285 0.349 0.395

Temperature Factor (f) 0.937 0.928 0.921 0.897 0.891

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

19

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary uninsulated lintel

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

20

E2 – Open Back Lintel (Uninsulated) with Insulated Reveal but without Base Plate

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the lintel.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray / lintel should be taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the lintel by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the lintel fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Kingspan Kooltherm® K118 Insulated Plasterboard

32.5 mm added to the window reveal with adhesive and supplementary fi xings. Ensure Kingspan Kooltherm® K118 Insulated Plasterboard butts the window frame. Seall the perimeter with fl exible sealant.

l Seal the joint between the window frame and the internal linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.194 0.215 0.232 0.299 0.354

Temperature Factor (f) 0.927 0.917 0.910 0.890 0.885

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.181 0.206 0.226 0.305 0.371

Temperature Factor (f) 0.921 0.911 0.903 0.881 0.873

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

21

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Cavity tray DPC

Proprietary uninsulated lintel

Flexible sealant

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Perpend weep holes

Flexible sealant

Kingspan Kooltherm® K118 InsulatedPlasterboard adhered with acrylicsealant adhesive

22

E2 – Independent Steel Lintel externally and Independent Concrete Lintel internally

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the Kingspan Kooltherm® Cavity Closer. If required, fi ll gap with insulating expanding foam.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray should be taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the Kingspan Kooltherm® Cavity Closer by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the Kingspan Kooltherm® Cavity Closer fully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the joint between the window frame and the internal

linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.022 0.021 0.019 0.017 0.016

Temperature Factor (f) 0.983 0.983 0.983 0.984 0.984

Full Overlap (Incl. Checked reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.010 0.008 0.007 0.004 0.004

Temperature Factor (f) 0.981 0.982 0.982 0.982 0.982

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

23

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Independent concrete lintel

Flexible sealant

If required, fill gap with insulatingexpanding foam

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Wraptite tape, 50 mm overlap required above retaining clip, extended down to

cavity tray below

Perpend weep holes

Cavity tray DPC

Independent steel lintel

Flexible sealant

Kingspan Kooltherm® Cavity Closer

24

E2 – Independent Steel Lintel externally and Independent Concrete Lintel internally with Insulated Reveal

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board is in

contact with the Kingspan Kooltherm® Cavity Closer.If required, fi ll gap with insulating expanding foam.

l Kingspan Kooltherm® K106 Cavity Board and cavity tray should be taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps the Kingspan Kooltherm® Cavity Closer by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps the Kingspan Kooltherm® Cavity Closer / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Kingspan Kooltherm® K118 Insulated Plasterboard

32.5 mm added to the window reveal with adhesive and supplementary fi xings. Ensure Kingspan Kooltherm® K118 Insulated Plasterboard butts the window frame. Seal the perimeter with fl exible sealant.

l Seal the joint between the window frame and the internal linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.014 0.013 0.012 0.009 0.008

Temperature Factor (f) 0.979 0.979 0.979 0.979 0.980

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.007 0.006 0.005 0.002 0.001

Temperature Factor (f) 0.977 0.977 0.977 0.978 0.978

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

25

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Independent concrete lintel

Flexible sealant

If required, fill gap with insulatingexpanding foam

Kingspan Kooltherm® K106 Cavity Board

Outer leaf brickwork

Independent steel lintel

Wraptite tape, 50mm overlap required above retaining clip, extend down

to cavity tray

Cavity tray DPC

Perpend weep holes

Flexible sealant

Kingspan Kooltherm® Cavity Closer

Kingspan Kooltherm® K118 InsulatedPlasterboard adhered with acrylicsealant adhesive

E3 – Sill (Normal)

l For fully overlapped / checked reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closerfully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure Kingspan Kooltherm® K106 Cavity Board and Kingspan Kooltherm® Cavity Closer are taped with a50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Apply fl exible sealant to all interfaces between the internal

air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

l Seal the junction between the internal lining and the window sill board (if used).

l Seal the junction between the window sill board and the window frame member.

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® Cavity Closer should be installed to

close the cavity.

l Ensure Kingspan Kooltherm® K106 Cavity Board is in contact with the full length of Kingspan Kooltherm® Cavity Closer. If required, fi ll gaps with insulating expanding foam.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closer by no less than 30 mm (take values from the fi rst two rows of the table below).

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.015 0.014 0.014 0.013 0.013

Temperature Factor (f) 0.925 0.925 0.926 0.926 0.927

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.003 0.003 0.003 0.002 0.002

Temperature Factor (f) 0.959 0.961 0.961 0.964 0.966

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

NB The sill junction shown utilises a timber sill, however the modelled ψ–values also apply for the sill junction if a calcium silicate, cement–based or gypsum–based board of 12 mm thickness is included below the sill, with no loss of thermal performance, or if a greater thickness of timber sill were used.

26

27

Flexible sealant

Wall lining

Flexible sealant

If required, fill gap with insulatingexpanding foamWall tie with retaining clip

Brick outer leaf

Wraptite tape, 50 mm overlap required Kingspan Kooltherm® Cavity Closer

Inner leaf blockwork

Kingspan Kooltherm® K106 Cavity Board

28

E3 – Sill (Normal) with Insulated Reveal

l For fully overlapped / checked reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closerfully / by no less than 80 mm (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure Kingspan Kooltherm® K106 Cavity Board and Kingspan Kooltherm® Cavity Closer are taped with a50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Kingspan Kooltherm® K118 Insulated Plasterboard

32.5 mm added to the window reveal with adhesive and supplementary fi xings. Ensure Kingspan Kooltherm® K118 Insulated Plasterboard butts the window frame. Seal the perimeter with fl exible sealant.

l Seal the joint between the window frame and the internal linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® Cavity Closer should be installed to

close the cavity.

l Ensure Kingspan Kooltherm® K106 Cavity Board is in contact with the full length of Kingspan Kooltherm® Cavity Closer. If required, fi ll gaps with insulating expanding foam.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closer by no less than 30 mm (take values from the fi rst two rows of the table below).

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm Overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.004 0.003 0.003 0.002 0.002

Temperature Factor (f) 0.968 0.969 0.969 0.970 0.971

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) – 0.003 – 0.003 – 0.003 – 0.004 – 0.004

Temperature Factor (f) 0.983 0.984 0.985 0.988 0.989

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

NB The sill junction shown utilises a timber sill, however the modelled ψ–values also apply for the sill junction if a calcium silicate, cement–based or gypsum–based board of 12 mm thickness is included below the sill, with no loss of thermal performance, or if a greater thickness of timber sill were used.

29

Flexible sealant

Wall lining

Flexible sealant

Kingspan Kooltherm® K118 InsulatedPlasterboard adhered with acrylicsealant adhesive

If required, fill gap with insulatingexpanding foam

Wall tie with retaining clip

Brick outer leaf

Wraptite tape, 50 mm overlap required

Kingspan Kooltherm® Cavity Closer

Inner leaf blockworkKingspan Kooltherm® K106 Cavity Board

30

E4 – Jamb (Normal)

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure Kingspan Kooltherm® K106 Cavity Board and Kingspan Kooltherm® Cavity Closer are taped with a50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l At the vertical edges of openings and at vertical unreturned or unbounded edges (e.g. movement joints), additional wall ties should be used at a rate of one tie per 300 mm height or equivalent, placed not more than 225 mm from the edge.

l Alternatively, use an additional wall tie within 225 mm of the opening / vertical edge on each board course(450 mm) level to satisfy the structural requirements of the wall. Avoid penetrating the board, as this may introduce an unacceptable risk of water penetration. Place additional ties on each board course to compensate.

Air Barrier Process Sequencel Apply fl exible sealant to all interfaces between the internal

air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

l Seal the junction between the window sill board and the window frame member.

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® Cavity Closer should be installed to

close the cavity.

l Ensure Kingspan Kooltherm® K106 Cavity Board is in contact with the full length of Kingspan Kooltherm® Cavity Closer. If required, fi ll gaps with insulating expanding foam.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closer by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closer fully (take values from the last two rows of the table below).

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.015 0.015 0.014 0.014 0.014

Temperature Factor (f) 0.938 0.938 0.938 0.939 0.939

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.004 0.003 0.003 0.003 0.003

Temperature Factor (f) 0.967 0.968 0.968 0.971 0.972

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

31

Flexible sealant

Wall tie andretaining clip

Outer leafbrickwork

Wraptite tape, 50 mm overlap requiredExtra ties at jambs

of all openings

Kingspan Kooltherm®

K106 Cavity BoardWall liningInner leafblockwork

If required, fill gap with insulating expanding foam

Kingspan Kooltherm® Cavity Closer

225 mm max

32

E4 – Jamb (Normal) with Insulated Reveal

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure Kingspan Kooltherm® K106 Cavity Board and Kingspan Kooltherm® Cavity Closer are taped with a50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l At the vertical edges of openings and at vertical unreturned or unbounded edges (e.g. movement joints), additional wall ties should be used at a rate of one tie per 300 mm height or equivalent, placed not more than 225 mm from the edge.

l Alternatively, use an additional wall tie within 225 mm of the opening / vertical edge on each board course(450 mm) level to satisfy the structural requirements of the wall. Avoid penetrating the board, as this may introduce an unacceptable risk of water penetration. Place additional ties on each board course to compensate.

Air Barrier Process Sequencel Kingspan Kooltherm® K118 Insulated Plasterboard

32.5 mm added to the window reveal with adhesive and supplementary fi xings. Ensure Kingspan Kooltherm® K118 Insulated Plasterboard butts the window frame. Seal the perimeter with fl exible sealant.

l Seal the joint between the window frame and the internal linings.

l Apply fl exible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a fl exible sealant.

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® Cavity Closer should be installed to

close the cavity.

l Ensure Kingspan Kooltherm® K106 Cavity Board is in contact with the full length of Kingspan Kooltherm® Cavity Closer. If required, fi ll gaps with insulating expanding foam.

l Ensure there are no gaps between the insulation boards.

l For normal reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closer by no less than 30 mm (take values from the fi rst two rows of the table below).

l For fully overlapped / checked reveals, ensure the window / door frame overlaps Kingspan Kooltherm® Cavity Closer fully (take values from the last two rows of the table below).

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Normal 30 mm overlap*Linear Thermal Transmittance Ψ (W/m.K) 0.008 0.008 0.007 0.007 0.007

Temperature Factor (f) 0.965 0.965 0.965 0.966 0.966

Full Overlap (Incl. Checked Reveal)**

Linear Thermal Transmittance Ψ (W/m.K) 0.001 0.001 0.001 0.000 0.000

Temperature Factor (f) 0.982 0.983 0.984 0.986 0.988

* Normal – 30 mm overlap between an 80 mm frame and 100 mm cavity.

** Full overlap / checked reveal – 80 mm overlap between an 80 mm frame and 100 mm cavity. Where full overlap and checked reveal values differ, the poorer value has been taken.See page 68 for further details.

33

Flexible sealant

Wall tie andretaining clip

Outer leafbrickwork

Wraptite tape, 50 mm overlap requiredExtra ties at jambs

of all openings

Kingspan Kooltherm®

K106 Cavity Board

Kingspan Kooltherm® K118 Plasterboard adhered with acrylic sealant adhesive

Wall lining Inner leafblockwork

If required, fill gap with insulating expanding foam

Kingspan Kooltherm® Cavity Closer

225 mm max

34

E5 – Ground Floor – Solid Concrete Slab

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board is installed at least 150 mm (UK) / 225 mm (Republic of Ireland) below the top surface of Kingspan Kooltherm®

K103 Floorboard perimeter insulation.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

Air Barrier Process Sequencel Apply fl exible sealant between the wall lining and fl oor lining.

l Apply fl exible sealant between the skirting board and the fl oor screed / fi nish.

l Seal all penetrations through the air barrier using a fl exible sealant.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.07 0.07 0.081 0.126 0.19

Temperature Factor (f) 0.928 0.924 0.919 0.906 0.902

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with Kingspan Kooltherm®

K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 W/m.K & 1.13 W/m.K block)

Thermal Performance Process Sequencel Install 25 mm (min.) Kingspan Kooltherm® K103

Floorboard vertically around the perimeter of the fl oor. Install the upstand insulation so that it is fl ush with the fl oor screed. Kingspan Kooltherm® K103 Floorboard or vertical perimeter insulation must tightly abut the inner leaf of blockwork.

NB Calculations based on 100 mm Kingspan Kooltherm® K103 Floorboard insulation.

35

Kingspan KoolthermK106 Cavity Board

Brick outer leaf

Damp proof course

Weep holes atspecifi ed centres

Wall tie and retaining clip

Wraptite tape, 50 mmoverlap required

25 m

m (m

in.)

from

und

ersi

de o

fK

ings

pan

Kool

ther

m® K

106

Cavit

y Bo

ard

to s

tart

of c

avity

fi ll

Wall lining

Inner leaf blockwork

Floor screed

Vapour control layer /separation layer

Floor fi nish

100 mm concrete slab

Ensure Kingspan Kooltherm® K106Cavity Board is installed 150 mm /225 mm below top surface ofperimeter strip insulation

Damp proof membrane

150 mm (min.) compactedselected hard core

First run of ties at 600 mmhorizontal centres

Ensure cavity fi ll is at least 225 mm below DPC level

25 mm sand binding

Kingspan Kooltherm® K103 Floorboard

Kingspan Kooltherm® K103 Floorboard perimeter strip

Flexible sealant

Insulating expanding foam and / or fl exible sealant

36

E5 – Ground Floor – Beam & Block (Parallel)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.034 0.036 0.037 0.041 0.044

Temperature Factor (f) 0.945 0.946 0.947 0.950 0.955

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Install 25 mm (min.) Kingspan Kooltherm® K103

Floorboard vertically around the perimeter of the fl oor. Install the upstand insulation so that it is fl ush with the fl oor screed. Kingspan Kooltherm® K103 Floorboard or vertical perimeter insulation must tightly abut the inner leaf of blockwork.

NB Calculations based on 120 mm Kingspan Kooltherm® K103 Floorboard insulation.

Calculation conductivities are as follows; trenching block = 0.24 W/m.K, coursing block = 0.19 W/m.K and edge beam = 0.18 W/m.K.

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board is installed at least 150 mm below the top surface of the fl oor beam / bottom of the insulation.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

Air Barrier Process Sequencel Apply fl exible sealant between the wall lining and fl oor lining.

l Apply fl exible sealant between the skirting board and the fl oor screed / fi nish.

l Seal all penetrations through the air barrier using a fl exible sealant.

37

Kingspan Kooltherm®

K106 Cavity Board

Brick outer leaf

Damp proof course

Weep holes above DPC / cavity trayat specifi ed centres

Weep holes below DPC / cavity trayat specifi ed centres

Cranked vent and air brick

Wall tie and retaining clip

Wraptite tape, 50 mm overlap required

150

mm

Floor fi nish

75 mm screed

Vapour control layer/ separation layer

150 mm concrete beam

100 mm concrete block

Damp proof membrane

Kingspan Kooltherm® K106 Cavity Boardor approved / certifi ed full fi ll insulation

End block

Kingspan Kooltherm®

K103 Floorboard

150

mm

ve

ntila

tion

void

Wall lining

Inner leaf blockwork

Flexible sealant

Cavity tray over cranked vent only

Insulating expanding foam and / or fl exible sealant

Kingspan Kooltherm® K103 Floorboardperimeter strip

38

E5 – Ground Floor – Beam & Block (Perpendicular)

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board is installed at least 150 mm below the top surface of the fl oor beam / bottom of the insulation.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Apply fl exible sealant between the wall lining and fl oor lining.

l Apply fl exible sealant between the skirting board and the fl oor screed / fi nish.

l Seal all penetrations through the air barrier using a fl exible sealant.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.041 0.042 0.043 0.047 0.050

Temperature Factor (f) 0.944 0.945 0.945 0.949 0.952

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Install 25 mm (min.) Kingspan Kooltherm® K103

Floorboard vertically around the perimeter of the fl oor. Install the upstand insulation so that it is fl ush with the fl oor fi nish. Kingspan Kooltherm® K103 Floorboard or vertical perimeter insulation must tightly abut the inner leaf of blockwork.

NB Calculations based on 120 mm Kingspan Kooltherm® K103 Floorboard insulation.

Calculation conductivities are as follows; trenching block = 0.24 W/m.K, coursing block = 0.19 W/m.K and edge beam = 0.18 W/m.K.

39

150

mm

ve

ntila

tion

void

150

mm

Kingspan Kooltherm® K106 Cavity Board or approved / certified full fill insulation

Floor finish

75 mm screed

Vapour control layer / separation layer

150 mm concrete beam

100 mm concrete block

Damp proof membrane

Kingspan Kooltherm® K103 Floorboard

Wall lining

Inner leaf blockwork

Flexible sealant

Cavity tray over cranked vent only

Insulating expanding foam and / or flexible sealant

Kingspan Kooltherm®

K106 Cavity Board

Brick outer leaf

Damp proof course

Weep holes above DPC / cavity tray at specified centres

Weep holes below DPC / cavity tray at specified centres

Weep holes below DPC / cavity tray at specified centres

Wall tie with retaining clip

Wraptite tape, 50 mm overlap required

Kingspan Kooltherm® K103 Floorboard perimeter strip

40

E5 – Ground Floor – Suspended Timber Floor (Parallel)

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board is installed at least 200 mm below the top of the fl oor joist.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Apply fl exible sealant between the wall lining and fl oor lining.

l Apply fl exible sealant between the skirting board and the fl oor screed / fi nish.

l Seal all penetrations through the air barrier using a fl exible sealant.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.038 0.046 0.053 0.110 0.179

Temperature Factor (f) 0.846 0.840 0.835 0.856 0.843

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Install 25 mm (min.) Kingspan Kooltherm® K103

Floorboard vertically around the perimeter of the fl oor. Install the upstand insulation so that it is fl ush with the fl oor fi nish. Kingspan Kooltherm® K103 Floorboard or vertical perimeter insulation must tightly abut the inner leaf of blockwork.

NB Calculations based on 120 mm Kingspan Kooltherm® K103 Floorboard insulation.

41

Kingspan Kooltherm®

K106 Cavity Board

Brick outer leaf

Damp proof course

Weep holes above DPC / cavity tray at specified

centres

Weep holes below DPC / cavity tray at specified centres

Wall tie and retaining clip

200

mm

Air brick for ventilation

Treated floor joist

Floor finish

Treated timber battens supporting Kingspan Kooltherm® K103 Floorboard

Kingspan Kooltherm® K103 Floorboard between joists

Wall lining

Inner leaf blockwork

Flexible sealant

Cavity tray over air brick / vents

Insulating expanding foam and / or flexible sealant

Kingspan Kooltherm® K103 Floorboard perimeter strip

42

E6 – Intermediate Floor within a Dwelling – Concrete

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

Air Barrier Process Sequencel Seal between the wall lining and fl oor screed lining with

fl exible sealant or plaster / screed mortar.

l Seal between the wall lining and ceiling lining with fl exible sealant or plaster mortar.

l Apply fl exible sealant between the skirting board and the fl oor screed / fi nish.

l Seal all penetrations through the air barrier using a fl exible sealant or plaster mortar.

l Ensure a continuous bed of mortar between the fl oor slab and blockwork.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.011 0.009 0.008 0.005 0.004

Temperature Factor (f) 0.979 0.979 0.978 0.977 0.974

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be fi rmly

held against the inner leaf of blockwork.

l Continue Kingspan Kooltherm® K106 Cavity Boardacross the intermediate fl oor abutment zone.

NB Calculations based on 250 mm reinforced concrete intermediate fl oor.

43

Ceiling lining

Inner leaf blockwork

Insulating expanding foam and / or fl exible sealant

Wall tie with retaining clip

Wall lining

Insulating expanding foam and / or fl exible sealant

Flexible sealant

Floor fi nish

Reinforced concrete fl oor slab

Outer leaf brickwork

Kingspan Kooltherm® K106 Cavity Board

44

E6 – Intermediate Floor within a Dwelling – Timber

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Seal between the wall lining and fl oor screed lining with

fl exible sealant.

l Seal between the wall lining and ceiling lining with fl exible sealant.

l Apply fl exible sealant between the skirting board and the fl oor lining / fi nish.

l Seal all penetrations through the air barrier using a fl exible sealant or plaster mortar.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.000 0.000 0.000 0.000 0.000

Temperature Factor (f) 0.970 0.974 0.970 0.975 0.962

Detail

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be fi rmly

held against the inner leaf of blockwork.

l Continue Kingspan Kooltherm® K106 Cavity Boardacross the intermediate fl oor abutment zone.

NB Calculations based on 150 mm deep timber joists partially fi lled with 100 mm mineral wool (0.044 W/m.K).

45

Ceiling lining

Joist hanger

Inner leaf blockwork

Insulating expanding foam and / or fl exible sealant

Wall tie with retaining clip

Wall lining

Insulating expanding foam and / or fl exible sealant

Floor fi nish

150 mm timber fl oor joist(100 mm fi lled with mineral wool)

Outer leaf brickwork

Kingspan Kooltherm® K106 Cavity Board

Flexible sealant

46

E7 – Party Floor between Dwellings(e.g. in Blocks of Flats)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.031 0.031 0.031 0.031 0.031

Temperature Factor (f) 0.980 0.980 0.979 0.978 0.977

Detail

l Ensure Kingspan Kooltherm® K106 Cavity Board is fi rmly held against / butted lightly to the fi re stop & taped.

l Ensure Kingspan Kooltherm® K106 Cavity Board and fi re stop (if used instead of slate or Euroclass A1 rated building board) are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Seal between the wall lining and fl oor screed lining with

fl exible sealant or plaster / screed mortar.

l Seal between the wall lining and ceiling lining with fl exible sealant or plaster mortar.

l Apply fl exible sealant between the skirting board and the fl oor screed / fi nish.

l Seal all penetrations through the air barrier using a fl exible sealant or plaster mortar.

l Ensure a continuous bed of mortar between the fl oor slab and blockwork.

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be fi rmly

held against the inner leaf of blockwork.

l Continue Kingspan Kooltherm® K106 Cavity Boardacross the intermediate fl oor abutment zone.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

NB ψ–value applies for each dwelling.

Calculations based on a 215 mm reinforced concrete fl oor.

47

Wraptite tape, 50 mm overlap required

DPC cavity tray

Weep holes

Wraptite tape, 50 mm overlap required

Proprietary insulated fi re stop

Ceiling lining

Inner leaf blockwork

Insulating expanding foam and / or fl exible sealant

Wall tie with retaining clip

Wall lining

Insulating expanding foamand / or fl exible sealant

Floor fi nish

Reinforced concrete fl oor slab

Outer leaf brickwork

Kingspan Kooltherm® K106 Cavity Board

Flexible sealant

E10 – Eaves (Insulation at Ceiling Level)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.032 0.033 0.034 0.036 0.038

Temperature Factor (f) 0.933 0.935 0.936 0.938 0.940

Detail

l Ensure the full depth of ceiling insulation, between and over joist ceiling insulation, abuts the eaves insulation.

l Kingspan Kooltherm® K106 Cavity Board and eaves insulation should be fi rmly held against / butted tight against the fi re stop.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

l Ensure Kingspan Kooltherm® K106 and proprietary fi re stop (if used instead of slate / Euroclass A1 rated building board) are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Seal the wall plate on a continuous layer of mortar

l Seal the gap between the wall and ceiling linings with fl exible sealant / plaster mortar

l Seal all penetrations through the air barrier using a fl exible sealant / plaster mortar.

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be fi rmly

held against the inner leaf of blockwork.

l Ensure the gap between the wall plate and eaves ventilator is completely fi lled with fl exible insulation. The fl exible insulation is to have an R–value of 1.2 m2.K/W or higher.

l The fl exible insulation should be tucked down the head of the cavity to enable continuity of the fl exible insulation and Kingspan Kooltherm® K106 Cavity Board throughout the junction.

NB Calculations based on a ceiling with 100 mm mineral wool (0.039 W/m.K) between joists and 250 mm mineral wool (0.039 W/m.K) above joists.

48

49

Outer leaf brickwork

Wall tie with retaining clip

Wall lining

Inner leaf blockwork

Either use proprietary insulated fire stop,slate or Euroclass A1 rated building boardto close the cavity

Insulating expanding foamand / or flexible sealant

Ceiling lining

Vapour control layer

Kingspan Kooltherm® K106 Cavity Board

MembraneProprietaryeaves ventilation

Proprietary eavesventilation

Wraptite tape, 50 mm overlap required

Roof tiles on battens Ceiling insulation between and over

50

E11 – Eaves (Insulation at Rafter Level)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.030 0.032 0.033 0.036 0.038

Temperature Factor (f) 0.964 0.965 0.965 0.964 0.965

Detail

l Ensure the full depth of ceiling insulation, between and over joist ceiling insulation, abuts the eaves insulation.

l Kingspan Kooltherm® K106 Cavity Board and eaves insulation should be fi rmly held against / butted tight against the fi re stop.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Bed the wall plate on a continuous layer of mortar.

l Seal the gap between the wall and ceiling linings with fl exible sealant / plaster mortar.

l Seal all penetrations through the air barrier using a fl exible sealant / plaster mortar.

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be fi rmly

held against the inner leaf of blockwork.

l Ensure the gap between the wall plate and eaves ventilator is completely fi lled with fl exible insulation. The fl exible insulation is to have an R–value of 1.2 m2.K/W or higher.

l The fl exible insulation should be tucked down the head of the cavity to enable continuity of the fl exible insulation and Kingspan Kooltherm® K106 Cavity Board throughout the junction.

NB Calculations based on 150 mm Kingspan Kooltherm® K107 between rafters and 62.5 mm Kingspan Kooltherm® K118 Insulated Plasterboard beneath rafters.

51

Kingspan Kooltherm® K107 Pitched Roof Board

Roof tiles

Membrane

Proprietary eaves ventilator

Proprietary eaves ventilation

Kingspan Kooltherm® K118 Insulated plasterboard

Insulating expanding foam and / or flexible sealant

Flexible roof insulation

Wraptite tape, 50 mm overlap required

Either use proprietary insulated fire stop, slate or Euroclass A1 rated building board to close the cavity

Inner leaf blockwork

Outer leaf brickwork

Wall lining

Wall tie with retaining clip

Kingspan Kooltherm® K106 Cavity Board

52

E12 – Gable (Insulation at Ceiling Level)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.035 0.040 0.044 0.089 0.158

Temperature Factor (f) 0.926 0.923 0.909 0.892 0.867

Detail

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

l Ensure Kingspan Kooltherm® K106 Cavity Board and proprietary fire stop (if used instead of slate / Euroclass A1 rated building board) are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Kingspan Kooltherm® K106 Cavity Board is to be installed a minimum of 200 mm above the top surface of the ceiling insulation.

Air Barrier Process Sequencel Seal the gap between the wall and ceiling linings with

flexible sealant / plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant / plaster mortar.

General Construction Specificationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm Kingspan Kooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be firmly

held against the inner leaf of block work.

l Pack flexible insulation between the last truss / joist and gable wall.

l Ensure the ceiling insulation over the truss / joist tightly abuts the flexible insulation packed between the last truss / joists.

l Ensure the ceiling insulation between and over the truss / joists extends to the inner edge of the wall.

NB Calculations based on a ceiling with 100 mm mineral wool (0.039 W/m.K) between joists and 250 mm mineral wool (0.039 W/m.K) above joists.

53

Either use proprietary insulated fire stop, slate or Euroclass A1 rated building board to close the cavity

Ceiling insulation between and over

Inner leaf blockwork

Outer leaf brickwork

Wall lining

Wall tie with retaining clip

Kingspan Kooltherm® K106 Cavity Board

Weep holes

Cavity tray DPC

Wraptite tape, 50 mm overlap required

Insulation

200

mm

(min

.)

Ceiling lining

Vapour control layer

Insulating expanding foam and / or flexible sealant

54

E13 – Gable (Insulation at Rafter Level)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.052 0.057 0.062 0.079 0.089

Temperature Factor (f) 0.923 0.919 0.917 0.917 0.925

Detail

l Kingspan Kooltherm® K106 Cavity Board should be fi rmly held against / butted tight against the fi re stop and taped.

l Ensure Kingspan Kooltherm® K106 Cavity Board and proprietary fi re stop (if used instead of slate / Euroclass A1 rated building board) are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Bed the wall plate on a continuous layer of mortar.

l Seal the gap between the wall and ceiling linings with fl exible sealant or plaster mortar.

l Seal all penetrations through the air barrier using a fl exible sealant / plaster mortar.

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be fi rmly

held against the inner leaf of blockwork.

l Ensure the gap between the wall plate and eaves ventilator is completely fi lled with fl exible insulation. The fl exible insulation is to have an R–value of 1.2 m².K/W or higher.

l The fl exible insulation should be tucked down the head of the cavity to enable continuity of this and KingspanKooltherm® K106 Cavity Board throughout the junction.

l Ensure the full depth of ceiling insulation, between and over joist ceiling insulation, abuts the eaves insulation.

NB Calculations based on 150 mm Kingspan Kooltherm® K107 between rafters and 62.5 mm Kingspan Kooltherm® K118 Insulated Plasterboard beneath rafters.

55

Either use proprietary insulated fire stop, slate or Euroclass A1 rated building board to close the cavity

Inner leaf blockwork

Outer leaf brickwork

Wall lining

Wall tie with retaining clip

Kingspan Kooltherm® K118 Insulated Plasterboard

Wraptite tape, 50 mm overlap required

Insulation Timber rafter

Ceiling lining

Insulating expanding foam and / or flexible sealant

Timber battens

Kingspan Kooltherm® K107 Pitched Roof Board

Roof tiles

Soffit board

Kingspan Kooltherm® K106 Cavity Board

56

E14 – Flat Roof

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) Kingspan Thermaroof® TR27 LPC/FM 0.051 0.052 0.053 0.056 0.057

Temperature Factor (f) 0.956 0.960 0.955 0.957 0.958

Linear Thermal Transmittance Ψ (W/m.K) Kingspan Thermaroof® TR26 LPC/FM 0.050 0.051 0.052 0.055 0.057

Temperature Factor (f) 0.960 0.959 0.959 0.958 0.960

Detail

l Ensure Kingspan Thermaroof® TR26 / TR27 LPC/FMor Kingspan Thermataper® TT46 / TT47 LPC/FM warm deck roof insulation extends to the edge of the roof.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

l Ensure Kingspan Kooltherm® K106 Cavity Board and proprietary fi re stop (if used instead of slate / Euroclass A1 rated building board) are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Seal the gap between the wall and ceiling linings with

fl exible sealant or plaster mortar.

l Seal all penetrations through the air barrier using a fl exible sealant / plaster mortar.

General Construction Specifi cationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm KingspanKooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be fi rmly

held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board is taken up level with the top of the wall fi rmly held against / butted tight against the fi re stop and taped.

l Pack fl exible insulation between the last joist / gable ladder. Fully fi ll the void and ensure the insulation is in contact with the roof deck and cavity closer.

NB Calculations based on 160 mm Kingspan Thermaroof® TR27 / TR26 LPC/FM for the fl at roof.

If Kingspan Thermataper® TT47 / TT46 LPC/FM is used, a minimum thickness of 160 mm would need to be accommodated at the edge of the roof. This would allow the above Psi values to be used (TR27 for TT47 and TR26 for TT46).

57

Either use proprietary insulated fi re stop, slate or Euroclass A1 rated building board to close the cavity

Inner leaf blockwork

Outer leaf brickwork

Wall lining

Wall tie with retaining clip

Proprietary metal fl ashing Insulation

Ceiling liningFlat roof joist

Insulating expanding foamand / or fl exible sealant

Soffi t board

Kingspan Kooltherm® K106 Cavity Board

Kingspan Thermaroof® TR26 / TR27 LPC/FMor Kingspan Thermataper® TT46 / TT47 LPC/FM

Waterproofi ng

Wraptite tape, 50 mm overlap required

18 mm WBP plyboard

Vapour control layer

58

E15 – Flat Roof with Parapet

Detail

l Ensure there is a distance of at least 300 mm (min.) between the top of Kingspan Thermaroof® TR26 / TR27 LPC/FM upstand insulation and the bottom of Kingspan Thermaroof® TR26 / TR27 LPC/FM roof insulation or Kingspan Thermataper® TT46 / TT47 LPC/FM.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against / butted lightly against fire stop.

l Ensure Kingspan Kooltherm® K106 Cavity Board and proprietary fire stop (if used instead of slate / Euroclass A1 rated building board) are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Seal the gap between the wall and ceiling linings with

flexible sealant or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant / plaster mortar.

General Construction Specificationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm Kingspan Kooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be firmly

held against the inner leaf of blockwork.

l Install 25 mm (min.) Kingspan Thermaroof® TR26 / TR27 LPC/FM upstand insulation around the parapet.

l Ensure Kingspan Thermaroof® TR26 / TR27 LPC/FM roof or upstand Insulation tightly abuts the inner face of the parapet blockwork.

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) Kingspan Thermaroof® TR27 LPC/FM 0.062 0.071 0.078 0.127 0.198

Temperature Factor (f) 0.951 0.943 0.940 0.918 0.895

Linear Thermal Transmittance Ψ (W/m.K) Kingspan Thermaroof® TR26 LPC/FM 0.063 0.071 0.079 0.126 0.197

Temperature Factor (f) 0.950 0.946 0.943 0.922 0.898

NB Calculations based on 160 mm Kingspan Thermaroof® TR27 / TR26 LPC/FM for the flat roof.

If Kingspan Thermataper® TT47 / TT46 LPC/FM is used, a minimum thickness of 160 mm would need to be accommodated at the edge of the roof. This would allow the above Psi values to be used (TR27 for TT47 and TR26 for TT46).

59

Either use proprietary insulated fire stop, slate or Euroclass A1 rated building board to close the cavity

Inner leaf blockwork

Outer leaf brickwork

Wall lining

Wall tie with retaining clip

Cavity tray DPCCoping

Ceiling lining Flat roof joist

Insulating expanding foam and / or flexible sealant

300

mm

(min

.)

Kingspan Kooltherm® K106 Cavity Board

Kingspan Thermaroof® TR26 / TR27 LPC/FM or Kingspan Thermataper® TT46 / TT47 LPC/FM

Waterproofing

Wraptite tape, 50 mm overlap required

Proprietary metal flashing

Vapour control layer

Weep holes

Kingspan Thermaroof® TR26 / TR27 LPC/FM upstand insulation (25 mm min.)

150

mm

18 mm WBP plyboard roof deck

60

E16 – Corner (Normal)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.033 0.036 0.038 0.044 0.047

Temperature Factor (f) 0.930 0.940 0.940 0.940 0.950

Detail

l Ensure the exposed edges of Kingspan Kooltherm® K106 Cavity Board are taped, again ensuring a 50 mm (min.) overlap. This may require two or more strips of tape to cover the edges.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the gap between the wall and ceiling linings with

flexible sealant or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant / plaster mortar.

General Construction Specificationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm Kingspan Kooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board joints should be

staggered at the building corners.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

61

Inner leaf blockwork

Board joint

Outer leaf brickwork

Wall lining

Wall tie with retaining clip

Kingspan Kooltherm® K106 Cavity Board

Wraptite tape, 50 mm overlap required

50 m

m (m

in.)

over

lap

62

E17 – Corner (Inverted)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) –0.059 –0.061 –0.063 –0.068 –0.070

Temperature Factor (f) 0.980 0.979 0.979 0.978 0.977

Detail

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the gap between the wall and ceiling linings with

flexible sealant or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant / plaster mortar.

General Construction Specificationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm Kingspan Kooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board joints should be

staggered at the building corners.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

63

Inner leaf blockwork

Outer leaf brickwork

Wall lining

Wall tie with retaining clip

Kingspan Kooltherm® K106 Cavity Board

50 m

m (m

in.)

over

lap

Board joint

Wraptite tape, 50 mm overlap required

64

E18 – Party Wall between Dwellings (Filled Cavity)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.022 0.021 0.021 0.021 0.021

Temperature Factor (f) 0.954 0.953 0.953 0.953 0.955

Detail

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board and insulated fire stop material is continuous across the abutment zone.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the gap between the wall and ceiling linings with

flexible sealant or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant.

General Construction Specificationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm Kingspan Kooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be firmly

butted against the insulated fire stop.

l Ensure Kingspan Kooltherm® K106 Cavity Board and proprietary insulated fire stop are taped ensuring a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

NB ψ–value applies for each dwelling.

Ensure cavity wall qualifies for U=0.

Cavity must have effective sealing to the top, bottom and vertical edge to prevent air movement.

Cavity must be fully filled.

Calculations based on mineral wool (0.044 W/m.K) to fully fill the party wall cavity.

65

Inner leaf blockwork

Outer leafbrickwork

Wall lining

Blockwork

Full fill cavity wall insulationto separating wall

Wall tie with retaining clip

Kingspan Kooltherm® K106 Cavity Board

Wraptite tape, 50 mm overlap required

Proprietary insulated fire / acoustic stop with integral or separate DPC

50 mm overlap

66

E18 – Party Wall between Dwellings (Unfilled Cavity)

Internal Blockwork Conductivity (W/m.K)

Description 0.11 0.15 0.19 0.51 1.13

Linear Thermal Transmittance Ψ (W/m.K) 0.025 0.024 0.023 0.023 0.023

Temperature Factor (f) 0.953 0.954 0.951 0.954 0.955

Detail

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board and insulated fire stop material is continuous across the abutment zone.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Air Barrier Process Sequencel Seal the gap between the wall and ceiling linings with

flexible sealant or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant.

General Construction Specificationl Wall lining

l Inner leaf blockwork

l 100 mm overall cavity width with 90 mm Kingspan Kooltherm® K106 Cavity Board and 10 mm cavity

l Outer leaf brickwork

U–value Rangel 0.16 W/m2.K (0.11, 0.15 & 0.19 W/m.K block)

l 0.17 W/m2.K (0.51 & 1.13 W/m.K block)

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be firmly

butted against the insulated fire stop.

l Ensure Kingspan Kooltherm® K106 Cavity Board and proprietary insulated fire stop are taped ensuring a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

NB ψ–value applies for each dwelling.

Ensure cavity wall qualifies for U=2.

Cavity must have effective sealing to the top, bottom and vertical edge to prevent air movement.

67

Inner leaf blockwork

Outer leafbrickwork

Wall lining

Blockwork

Unfilled cavity wall insulationto separating wall

Wall tie with retaining clip

Kingspan Kooltherm® K106 Cavity Board

Wraptite tape, 50 mm overlap required

Proprietary insulated fire / acoustic stop with integral or separate DPC

50 mm overlap

68

E2 – Lintel (Checked Reveal)

Air Barrier Process Sequencel Seal the joint between the window frame and the internal

linings.

l Apply flexible sealant to all interfaces between the internal air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be in

contact with the lintel.

l Ensure Kingspan Kooltherm® K106 Cavity Board and cavity tray / proprietary insulated lintel are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure there are no gaps between the insulation boards.

l Ensure window / door frame fully overlaps into cavity. External brickwork should then overlap the face of the frame by 15mm to create a check reveal.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Detail

Inner leaf blockwork

Wall lining

Cavity tray DPC

Proprietary insulated lintel

Flexible sealant

Wall tie with retaining clip

Kingspan Kooltherm® K106 Cavity Board

Wraptite tape, 50 mm overlap required

Outer leaf blockwork

Weep holes

Flexible sealant

69

E3 – Sill (Checked Reveal)

Air Barrier Process Sequencel Apply flexible sealant to all interfaces between the internal

air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a flexible sealant.

l Seal the junction between the internal lining and the window sill board (if used).

l Seal the junction between the window sill board and the window frame member.

Thermal Performance Process Sequencel Kingspan Kooltherm® Cavity Closer should be installed to

close the cavity.

l Ensure Kingspan Kooltherm® K106 Cavity Board is in contact with the full length of Kingspan Kooltherm® Cavity Closer. If required, fill any gaps with insulating expanding foam.

l Ensure there are no gaps between the insulation boards.

l Ensure window / door frame fully overlaps into cavity. External brickwork should then overlap the face of the frame by 15mm to create a check reveal.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure Kingspan Kooltherm® K106 Cavity Board and Kingspan Kooltherm® Cavity Closer are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Detail

Inner leaf blockwork

Wall lining

If required, fill gap with insulating expanding foam

Flexible sealant

Wall tie with retaining clip

Brick outer leaf

Kingspan Kooltherm® K106 Cavity Board

Wraptite tape, 50 mm overlap required

Flexible sealant

Kingspan Kooltherm® Cavity Closer

70

E4 – Jamb (Checked Reveal)

l At the vertical edges of openings and at vertical unreturned or unbounded edges (for example at movement joints and up the sloping verge of gable walls), additional wall ties should be used at a rate of one tie per 300 mm height or equivalent, placed not more than 225 mm from the edge.

l Alternatively, an additional wall tie included within 225 mm of the opening / vertical edge on each board course (450 mm) level could be used to satisfy the structural requirements of the wall. As the boards are 450 mm in height, having ties at 300 mm centres will penetrate the board which may introduce an unacceptable risk of water penetration, therefore place additional ties on each board course to compensate.

Air Barrier Process Sequencel Apply flexible sealant to all interfaces between the internal

air barrier and the window / door frame.

l Seal all penetrations through the air barrier using a flexible sealant.

l Seal the junction between the internal lining and the window / door frame members.

Thermal Performance Process Sequencel Kingspan Kooltherm® Cavity Closer should be installed to

close the cavity.

l Ensure Kingspan Kooltherm® K106 Cavity Board is in contact with the full length of Kingspan Kooltherm® Cavity Closer. If required, fill any gaps with insulating expanding foam.

l Ensure there are no gaps between the insulation boards.

l Ensure window / door frame fully overlaps into cavity. External brickwork should then overlap the face of the frame by 15mm to create a check reveal..

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure Kingspan Kooltherm® K106 Cavity Board and Kingspan Kooltherm® Cavity Closer are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Detail

Inner leaf blockworkWall lining If required, fill gap with

insulating expanding foam

Wall tie withretaining clip

Kingspan Kooltherm®

K106 Cavity Board

Wraptite tape, 50 mm overlap required

Flexible sealant

Kingspan Kooltherm® Cavity Closer

225 mm max

Extra ties at jambs of all openings

Outer leaf brickwork

71

E5 – Solid Ground Floor (Cavity Tray)

Air Barrier Process Sequencel Apply flexible sealant between the wall lining and floor

lining.

l Apply flexible sealant between the skirting board and floor screed / finish.

l Seal all penetrations through the air barrier using a flexible sealant.

l Typically the DPM / Radon / Gas membrane will form the cavity tray detail.

Thermal Performance Process Sequencel Install 25 mm (min.) Kingspan Kooltherm® K103

Floorboard vertically around the perimeter of the floor. Install the upstand insulation so that it is flush with the floor screed. Kingspan Kooltherm® K103 Floorboard or vertical perimeter insulation must tightly abut the inner leaf of blockwork.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board insulation is installed at least 150 mm below the top surface of Kingspan Kooltherm® K103 Floorboard perimeter insulation.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

** Typically the DPM / Radon / Gas membrane will form the cavity tray detail.

Detail

Brick outer leaf

Wall tie with retaining clip

Damp proof course

Weep holes at specified centres

DPM / Radon / Gas cavity tray membrane**

Kingspan Kooltherm® K106 Cavity Board

25 m

m (m

in.)

from

und

ersi

de o

f Kin

gspa

n Ko

olth

erm

® K

106

Cavit

y Bo

ard

to s

tart

of c

avity

fill

Wall lining

Inner leaf blockwork

Flexible sealant

Insulating expanding foam and / or flexible sealant

Kingspan Kooltherm® K103 Floorboard perimeter strip

Floor finish

75 mm screed

Vapour control layer /separation layer

100 mm concrete slab

DPM / Radon / Gas membrane

25 mm sand binding

150 mm (min.) compactedselected hardcore

Ensure K106 is installed 150 mm / 225 mm below top surface of perimeter strip insulation

Ensure cavity tray is at least 225 mm in vertical height and laps fully across each masonry leaf

First row of wall ties to be at 600 mm centres horizontally

Kingspan Kooltherm® K103 Floorboard

72

E5 – Timber Floor – Perpendicular

Air Barrier Process Sequencel Apply flexible sealant between the wall lining and floor

lining.

l Apply flexible sealant between the skirting board and floor screed / finish.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Install 25 mm (min.) Kingspan Kooltherm® K103

Floorboard vertically around the perimeter of the floor. Install the upstand insulation so that it is flush with the floor screed. Kingspan Kooltherm® K103 Floorboard or vertical perimeter insulation must tightly abut the inner leaf of blockwork.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board wall insulation is installed at least 200 mm below the top of the floor joist.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

Detail

Brick outer leaf

Wall tie with retaining clip

Damp proof course

Weep holes above DPC / cavity tray at specified centres

Weep holes below DPC / cavity tray at

specified centres

Kingspan Kooltherm® K106 Cavity BoardWall lining

Inner leaf blockwork

Flexible sealant

Insulating expanding foam and / or flexible sealant

Cavity tray over air brick / vents

Kingspan Kooltherm® K103 Floorboard

200

mm

Treated timber battens

Timber floor joistAir brick forventilation

Joist hanger

Floor finish

Kingspan Kooltherm®

K103 Floorboard perimeter strip

73

E16 – Corner – Normal (alternative Mitre Joint)

Air Barrier Process Sequencel Seal the gap between the wall linings with flexible sealant

or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board joints

are staggered at the building corners.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure the exposed edges of Kingspan Kooltherm® K106 Cavity Board are taped, ensuring a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape to cover the edges.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Detail

Inner leaf blockwork

Outer leaf brickwork

Wall tie and retaining clip

Wraptite tape, 50 mm overlap required Board joint

Kingspan Kooltherm® K106 Cavity Board

Wall lining

50 m

m (m

in.)

over

lap

74

E17 – Corner – Inverted (alternative Mitre Joint)

Air Barrier Process Sequencel Seal the gap between the wall linings with flexible sealant

or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Ensure Kingspan Kooltherm® K106 Cavity Board joints

are staggered at the building corners.

l Kingspan Kooltherm® K106 Cavity Board should be firmly held against the inner leaf of blockwork.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

Detail

Inner leaf blockwork

Outer leaf brickwork

Wall tie and retaining clip

Wraptite tape, 50 mm overlap required

Board joint

Kingspan Kooltherm® K106 Cavity Board

Wall lining

50 m

m (m

in.)

over

lap

75

Flue (Core Drilled, no Separation)

Air Barrier Process Sequencel Seal the gap between the wall lining and flue with

insulating expanding foam and / or flexible sealant.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be

firmly held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board is snugly fitted around the pipe / flue. Kingspan Kooltherm® K106 Cavity Board may be core drilled to create the circumference required.

l Once the flue / pipe and sleeving (if required) has been installed, apply expanding foam and / or flexible sealant around the perimeter of the flue / pipe, internal and external.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap.

Detail

NB This detail may be used where a separation between the flue / air duct and Euroclass B - E rated material is not required, for example plastic flues serving appliances that operate under 100°C .

Always refer to the manufacturer of the heating system and obtain guidance from a competent person (Gas safe, OFTEC, HETAS or equivalent) to determine the requirements.

Manufacturer’s instructions may detail a specific clearance from the flue / air supply duct (s) and Euroclass B - E rated materials, irrespective of flue–gas or duct temperature, therefore see flue (built in, separation) detail on page 68.

Outer leaf brickwork

Inner leaf blockwork

Wall lining

Wall tie with retaining clip

Cement mortar

Sealed flue / sleeve collar

Proprietary sleeve (if required – possibly integral flue)

Flexible sealant around perimeter

Kingspan Kooltherm® K106 Cavity Board

Insulating expanding foam and / or sealant around perimeter of penetration

Flue

76

Flue (Built In, no Separation)

l Ensure Kingspan Kooltherm® K106 Cavity Board and cavity tray are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Seal the gap between the wall lining and flue with

insulating expanding foam and / or flexible sealant.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be firmly

held against the inner leaf of blockwork.

l Ensure Kingspan Kooltherm® K106 Cavity Board is snugly fitted around the pipe / flue. Kingspan Kooltherm® K106 Cavity Board may be core drilled to create the circumference required.

l Once the flue / pipe and sleeving (if required) has been installed apply expanding foam and / or flexible sealant around the perimeter of the flue / pipe, internal and external.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are lightly butted and taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Detail

NB This detail may be used where a separation between the flue / air duct and Euroclass B - E rated material is not required, for example plastic flues serving appliances that operate under 100°C .

Always refer to the manufacturer of the heating system and obtain guidance from a competent person (Gas safe, OFTEC, HETAS or equivalent) to determine the requirements.

Manufacturer’s instructions may detail a specific clearance from the flue / air supply duct (s) and Euroclass B - E rated materials, irrespective of flue–gas or duct temperature, therefore see flue (built in, separation) detail on page 66.

Outer leaf brickwork

Perpend weep holes

Cavity tray DPC

Inner leaf blockwork

Wall lining

Wall tie with retaining clip

Cement mortar

Wraptite tape 50 mm overlap required

Sealed flue / sleeve collar

Proprietary sleeve (if required – possibly integral flue)

Flexible sealant around perimeter

Kingspan Kooltherm® K106 Cavity Board

Insulating expanding foam and / or sealant around perimeter of penetration

Flue

77

Flue (Built In, Separation )

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

l Ensure Kingspan Kooltherm® K106 Cavity Board and cavity tray are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Air Barrier Process Sequencel Seal the gap between the wall lining and flue with

insulating expanding foam and / or flexible sealant.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be firmly

held against the inner leaf of blockwork.

l Terminate Kingspan Kooltherm® K106 Cavity Board so that it is the required separation distance away from the flue in all four directions.

l Ensure Kingspan Kooltherm® K106 Cavity Board is lightly butted up to the Euroclass A1 rated insulation layer.

l Once the flue / pipe and sleeving (if required) has been installed apply expanding fire foam and / or flexible fire sealant around the perimeter of the flue / pipe, internal and external.

l Ensure Kingspan Kooltherm® K106 Cavity Board and Euroclass A1 rated insulation infill are lightly butted and taped with self adhesive breather tape.

Detail

NB This detail illustrates when separation from the flue / air duct and Euroclass B - E rated material is required.

The appliance manufacturer’s instructions must be sought, which may detail a specific clearance from the flue / air supply duct (s) and Euroclass B - E rated materials, irrespective of flue–gas or duct temperature.

The dimension of Euroclass A1 rated insulation around flue pipes / terminal can vary, for example, all flues serving oil fired boilers require a 300 mm minimum area around the flue pipe / terminal free from Euroclass B - E rated material.

Outer leaf brickwork

Wraptite tape, 50 mm overlap required

Inner leaf blockwork

Wall lining

Wall tie with retaining clip

Wraptite tape, 50 mm overlap required

Cavity tray DPC

Weep holes

Euroclass A1 rated insulation infill

Sealed flue / sleeve collar

Mortar

Proprietary sleeve (if required – possibly integral flue)

Kingspan Kooltherm® K106 Cavity Board

Insulating expanding foam and / or sealant around perimeter of penetration

50 m

m (m

in.)

Dim

ensi

on v

arie

s, c

heck

with

app

lianc

e m

anuf

actu

rer o

r com

pete

nt p

erso

n

Flue

78

Wall Tie

Air Barrier Process Sequencel Seal the gap between the wall linings with flexible sealant

or plaster mortar.

l Seal all penetrations through the air barrier using a flexible sealant.

Thermal Performance Process Sequencel Kingspan Kooltherm® K106 Cavity Board should be firmly

held against the inner leaf of blockwork.

l The cavity and wall ties should be kept clean of mortar and other debris during construction.

l Ensure all Kingspan Kooltherm® K106 Cavity Board joints are taped with a 50 mm (min.) overlap. This may require two or more strips of Wraptite tape.

Detail

Outer leaf brickwork

Wraptite tape, 50 mmoverlap required

Inner leaf blockwork

Wall tie with retaining clip

Kingspan Kooltherm® K106Cavity Board

79

Customer ServiceFor quotations, order placement and details of despatches please contact the Kingspan Insulation Customer Service Department on the numbers below:

Tel: 01544 388 601email: [email protected]

Literature & SamplesKingspan Insulation produces a comprehensive range of technical literature for specifiers, contractors, stockists and end users. The literature contains clear ‘user friendly’ advice on typical design; design considerations; thermal properties; sitework and product data.

Kingspan Insulation technical literature is an essential specification tool. For copies please contact the Kingspan Insulation Marketing Department, or visit the Kingspan Insulation website, using the details below:

Tel: 01544 387 384email: [email protected] www.kingspaninsulation.co.uk/literature

Tapered RoofingFor technical guidance, quotations, order placement and details of despatches please contact the Kingspan Insulation Tapered Roofing Department on the numbers below:

Tel: 01544 387 383email: [email protected]

Technical Advice / DesignKingspan Insulation supports all of its products with a comprehensive Technical Advisory Service for specifiers, stockists and contractors.

This includes a computer–aided service designed to give fast, accurate technical advice. Simply phone the Kingspan Insulation Technical Service Department with your project specification. Calculations can be carried out to provide U–values, condensation / dew point risk, required insulation thicknesses etc… Thereafter any number of permutations can be provided to help you achieve your desired targets.

The Kingspan Insulation Technical Service Department can also give general application advice and advice on design detailing and fixing etc... Site surveys are also undertaken as appropriate.

The Kingspan Insulation British Technical Service Department operates under a management system certified to the BBA Scheme for Assessing the Competency of Persons to Undertake U–value and Condensation Risk Calculations.

Please contact the Kingspan Insulation Technical Service Department on the numbers below:

Tel: 01544 387 382 email: [email protected]

General EnquiriesFor all other enquiries contact Kingspan Insulation on the numbers below:

Tel: 01544 388 601email: [email protected]

Kingspan Insulation Ltd. reserves the right to amend product specifications without prior notice. Product thicknesses shown in this document should not be taken as being available ex–stock and reference should be made to the current Kingspan Insulation price–list or advice sought from Kingspan Insulation’s Customer Service Department (see above left). The information, technical details and fixing instructions etc. included in this literature are given in good faith and apply to uses described. Recommendations for use should be verified for suitability and compliance with actual requirements, specifications and any applicable laws and regulations. For other applications or conditions of use, Kingspan Insulation offers a Technical Advisory Service (see above), the advice of which should be sought for uses of Kingspan Insulation products that are not specifically described herein. Please check that your copy of this literature is current by contacting the Kingspan Insulation Marketing Department (see left).

Kingspan Insulation Ltd is a member of:

The National Insulation Association (NIA)

Contact Details

® Kingspan, Kooltherm, Thermaroof, Thermataper and the Lion Device are Registered Trademarks of the Kingspan Group plc in the UK, Ireland and other countries. All rights reserved.

Registered in England & Wales, No. 01882722. Registered Office: Pembridge, Leominster, Herefordshire HR6 9LA UK. VAT GB428602456.

Kingspan Insulation LtdPembridge, Leominster, Herefordshire HR6 9LA, UK

www.kingspaninsulation.co.uk

U Value Competency Scheme

CERTIFICATE CS/1004-4


Recommended