Date post: | 28-Mar-2015 |
Category: |
Documents |
Upload: | michelle-armstrong |
View: | 217 times |
Download: | 3 times |
NBS-3B1Y Strategic Corporate Sustainability 3rd/4th December 2012
Keith Tovey (杜伟贤 ) M.A., PhD, CEng, MICE, CEnvReader Emeritus in Environmental Sciences [email protected]
Recipient of James Watt Gold Medal5th October 2007
1
Low Carbon Strategies at the University of East Anglia
2
NBS-3B1Y Strategic Corporate Sustainability
Access to this presentation and numerous links relating to Energy may be found at http://www2.env.uea.ac.uk/energy/energy.htm or http://www.uea.ac.uk/~e680/energy/energy.htm
• Links to Energy Related Sites
• Powerpoint Presentation of Energy Supply at UEA and Strategies for Low Carbon at UEA [this presentation]
• Video Clips of Biomass System and also Carbon Footprinting of BBC Studios - [given today]
• Supplementary Powerpoint of challenges facing UK Energy Supply – [given tomorrow if time permits]
• Recent Government Documents on Energy including Consultations and responses by N.K.Tovey
• Papers written by N.K. Tovey relating to Energy and Carbon including reports on UEA Energy
• Sustainability Report relating to several branches of an International Bank.
• Return to Main UEA Energy Page
3
NBS-3B1Y Strategic Corporate Sustainability
• Introduction and Background to Energy Supply at UEA
• Low Energy Buildings and their Management
• Low Carbon Energy Provision– Photovoltaics– CHP– Adsorption chilling– Biomass Gasification
• The Energy Tour – Meet in CD Annexe 1.26 @ 11:00 tomorrow – ensure you are not wearing open sandals/shoes– Elizabeth Fry building & ZICER– Central Boiler House– ?? Biomass Plant
• Questions & Answers
• If time permits: - Energy Security: Hard Choices facing the UK
Low Carbon Strategies at the University of East Anglia
4
5
Original buildings
Teaching wall
Library
Student residences
History of Energy Supply at UEA• Early 1960s: central boiler house built with three 8MW boilers
providing water at 105 – 115o C at 10 bar pressure to circulate around the campus.
• Fuel used: heavy residual oil• 1984: small 4 MW boiler was added• 1987: interruptible gas was provided so boiler could run on
either heavy fuel oil or gas.• 1997/8: one 8 MW boiler removed and 3 1 MW CHP plants
installed• 2002: remaining heavy fuel oil provision converted to light oil• 2006: Absorption Chiller installed• 2010: Biomass Plant installed• Most buildings on campus have heat provision from central boiler
house.– Exceptions: Elizabeth Fry, Queens, EDU, Nelson Court,
Constable Terrace.
6
7
Nelson Court 楼
Constable Terrace 楼
7
8
Low Energy Educational Buildings
Elizabeth Fry Building
ZICER
Nursing and Midwifery
School
Medical School8
Medical School Phase 2
Thomas Paine Study Centre
9
Constable Terrace - 1993
• Four Storey Student Residence
• Divided into “houses” of 10 units each with en-suite facilities• Heat Recovery of body and cooking
heat ~ 50%.
• Insulation standards exceed 2006 standards
• Small 250 W panel heaters in individual rooms.
Electricity Use
21%
18%
17%
18%
14%
12%
Appliances
Lighting
MHVR Fans
MHVR Heating
Panel Heaters
Hot Water
Carbon Dioxide Emissions - Constable Terrace
0
20
40
60
80
100
120
140
UEA Low Medium
Kg
/m2 /y
r
10
Educational Buildings at UEA in 1990s
Queen’s Building 1993 Elizabeth Fry Building 1994
Elizabeth Fry Building Employs Termodeck principle and uses ~ 25% of Queen’s Building
11
Cost ~6% more but has heating requirement ~20% of average building at time.Significantly outperforms even latest Building Regulations.Runs on a single domestic sized central heating boiler.
The Elizabeth Fry Building 1994
0
20
40
60
80
100
120
140
1995 1996 1997 1998 1999 2000 2001 2002 2003 2004Top
lam
Ene
rji T
üket
imi (
kWh/
m2 /y
ıl)
Heating/Cooling Hot Water Electricity
12
Conservation: management improvements
Careful Monitoring and Analysis can reduce energy consumption.
.
0
50
100
150
200
250
Elizabeth Fry Low Energy Average
kW
h/m
2 /yıl
gaselectricity
13
Comparison with other buildings
Energy Performance Carbon Dioxide Performance
thermal comfort +28%
air quality +36%
lighting +25%
noise +26%
User Satisfaction
A low Energy Building is also a better place to work in.
ZICER Building
• Heating Energy consumption as new in 2003 was reduced by further 57% by careful record keeping, management techniques and an adaptive approach to control.
• Incorporates 34 kW of Solar Panels on top floor
Won the Low Energy Building of the Year Award 2005
14
The ground floor open plan office
The first floor open plan office
The first floor cellular offices
15
The ZICER Building –
Main part of the building
• High in thermal mass • Air tight• High insulation standards • Triple glazing with low emissivity ~ equivalent to quintuple glazing
16
Operation of Main Building Mechanically ventilated that utilizes hollow core ceiling slabs as supply air ducts to the space
Regenerative heat exchangerIncoming
air into the AHU
17
Air enters the internal occupied space空气进入内部使用空间
Operation of Main Building
Air passes through hollow cores in the
ceiling slabs空气通过空心的板层
Filter过滤器
Heater加热器
18
Operation of Main Building
Recovers 87% of Ventilation Heat Requirement.
Space for future chilling
将来制冷的空间 Out of the building出建筑物
Return stale air is extracted from each floor 从每层出来的回流空气
The return air passes through the heat
exchanger空气回流进入热交换器 19
Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures
Heat is transferred to the air before entering the room
Slabs store heat from appliances and body heat.
热量在进入房间之前被传递到空气中 板层储存来自于电器以及人体发出的热量
Winter Day
Air Temperature is same as building fabric leading to a more pleasant working environment
Warm air
Warm air
20
Heat is transferred to the air before entering the room
Slabs also radiate heat back into room
热量在进入房间之前被传递到空气中
板层也把热散发到房间内
Winter Night
In late afternoon
heating is turned off.
Cold air
Cold air
Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures
21
Draws out the heat accumulated during the day
Cools the slabs to act as a cool store the following day
把白天聚积的热量带走。
冷却板层使其成为来日的冷存储器
Summer night
night ventilation/ free cooling
Cool air
Cool air
Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures
22
Slabs pre-cool the air before entering the occupied space
concrete absorbs and stores heat less/no need for air-conditioning
空气在进入建筑使用空间前被预先冷却混凝土结构吸收和储存了热量以减少 / 停止对空调的使用
Summer day
Warm air
Warm air
Fabric Cooling: Importance of Hollow Core Ceiling Slabs
Hollow core ceiling slabs store heat and cool at different times of the year providing comfortable and stable temperatures
23
0
200
400
600
800
1000
-4 -2 0 2 4 6 8 10 12 14 16 18
Mean |External Temperature (oC)
En
ergy
Con
sum
pti
on (
kW
h/d
ay)
Original Heating Strategy New Heating Strategy
Good Management has reduced Energy Requirements
800
350
Space Heating Consumption reduced by 57%
原始供热方法 新供热方法 24
建造209441GJ
使用空调384967GJ
自然通风221508GJ
Life Cycle Energy Requirements of ZICER compared to other buildings
与其他建筑相比 ZICER 楼的能量需求
Materials Production 材料制造 Materials Transport 材料运输On site construction energy 现场建造Workforce Transport 劳动力运输Intrinsic Heating / Cooling energy
基本功暖 / 供冷能耗Functional Energy 功能能耗Refurbishment Energy 改造能耗Demolition Energy 拆除能耗
28%54%
34%51%
61%
29%
25
0
50000
100000
150000
200000
250000
300000
0 5 10 15 20 25 30 35 40 45 50 55 60
Years
GJ
ZICER
Naturally Ventilated
Air Conditrioned
Life Cycle Energy Requirements of ZICER compared to other buildings
Compared to the Air-conditioned office, ZICER as built recovers extra energy required in construction in under 1 year.
0
20000
40000
60000
80000
0 1 2 3 4 5 6 7 8 9 10
Years
GJ
ZICER
Naturally Ventilated
Air Conditrioned
26
• Low Energy Buildings and their Management• Low Carbon Energy Provision
– Photovoltaics– CHP– Adsorption chilling– Biomass Gasification
• The Energy Tour• Energy Security: Hard Choices facing the UK
Low Carbon Strategies at the University of East Anglia
27
• Mono-crystalline PV on roof ~ 27 kW in 10 arrays• Poly- crystalline on façade ~ 6.7 kW in 3 arrays
ZICER Building
Photo shows only part of top
Floor
28
02040
6080
100120140
160180200
9 10 11 12 13 14 15Time of Day
Wh
01020
3040506070
8090100
%
Top Row
Middle Row
Bottom Row
radiation
0
10
20
30
40
50
60
70
80
90
100
9 10 11 12 13 14 15Time of day
Wh
0
10
20
30
40
50
60
70
80
90
100
%
Block1
Block 2
Block 3
Block 4
Block 5
Block 6
Block 7
Block 8
Block 9
Block 10
radiation
All arrays of cells on roof have similar performance respond to actual solar radiation
The three arrays on the façade respond differently
Performance of PV cells on ZICER
29
0
2
4
6
8
10
12
14
16
18
20
8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 16.00
Elev
ation
in th
e sky
(deg
rees)
120 150 180 210 240Orientation relative to True North 30
0
5
10
15
20
25
6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 16.00Time (hours)
Elev
ation
in th
e sky
(deg
rees)
January February March AprilMay June July AugustSeptember October November DecemberP1 - bottom PV row P2 - middle PV row P3 - top PV row
31
323232
Arrangement of Cells on Facade
Individual cells are connected horizontally
As shadow covers one column all cells are inactive
If individual cells are connected vertically, only those cells actually in shadow are affected.
Cells active
Cells inactive even though not covered by shadow
32
Use of PV generated energy
Sometimes electricity is exported
Inverters are only 91% efficient
• Most use is for computers• DC power packs are inefficient typically less than 60% efficient
• Need an integrated approach
Peak output is 34 kW 峰值 34 kW
33
EngineGenerator
36% Electricity
50% Heat
Gas
Heat Exchanger
Exhaust Heat
Exchanger
11% Flue Losses3% Radiation Losses
86%
Localised generation makes use of waste heat.
Reduces conversion losses significantly
Conversion efficiency improvements – Building Scale CHP
61% Flue Losses
36%
34
UEA’s Combined Heat and Power
3 units each generating up to 1.0 MW electricity and 1.4 MW heat 35
36
Conversion efficiency improvements
1997/98 electricity gas oil Total
MWh 19895 35148 33
Emission factor kg/kWh 0.46 0.186 0.277
Carbon dioxide Tonnes 9152 6538 9 15699
Electricity Heat
1999/2000
Total site
CHP generation
export import boilers CHP oil total
MWh 20437 15630 977 5783 14510 28263 923Emission
factorkg/kWh -0.46 0.46 0.186 0.186 0.277
CO2 Tonnes -449 2660 2699 5257 256 10422
Before installation
After installation
This represents a 33% saving in carbon dioxide
36
3737
Conversion efficiency improvements
Load Factor of CHP Plant at UEA
Demand for Heat is low in summer: plant cannot be used effectivelyMore electricity could be generated in summer
37
A typical Air conditioning/Refrigeration Unit
节流阀Throttle Valve
冷凝器
绝热
Condenser
Heat rejected
蒸发器
为冷却进行热提取
Evaporator
Heat extracted for cooling
高温高压
High TemperatureHigh Pressure
低温低压
Low TemperatureLow Pressure
Compressor
压缩器
38
Absorption Heat Pump
Adsorption Heat pump reduces electricity demand and increases electricity generated
节流阀Throttle Valve
冷凝器
绝热
Condenser
Heat rejected
蒸发器
为冷却进行热提取
Evaporator
Heat extracted for cooling
高温高压
High TemperatureHigh Pressure
低温低压
Low TemperatureLow Pressure
外部热
Heat from external source
W ~ 0
吸收器
吸收器
热交换器
Absorber
Desorber
Heat Exchanger
39
A 1 MW Adsorption chiller
1 MW 吸附冷却器
• Reduces electricity demand in summer
• Increases electricity generated locally
• Saves ~500 tonnes Carbon Dioxide annually
• Uses Waste Heat from CHP
• provides most of chilling requirements in summer
40
The Future: Biomass Advanced Gasifier/ Combined Heat and Power
• Addresses increasing demand for energy as University expands
• Will provide an extra 1.4MW of electrical energy and 2MWth heat• Will have under 7 year payback• Will use sustainable local wood fuel mostly from waste from saw
mills• Will reduce Carbon Emissions of UEA by ~ 25% despite increasing student numbers by 250%
41
42 4242
• Low Energy Buildings
• Effective Adaptive Energy Management
• Photovoltaics
• Combined Heat and Power
• Absorption Chilling
• Advanced CHP using Biomass Gasification
• World’s First MBA in Strategic Carbon Management
Low Energy Buildings
Photo-Voltaics
Efficient CHP Absorption Chilling
Trailblazing to a Low Carbon Future
Low Energy Buildings
43 4343
Photo-Voltaics
Advanced Biomass CHP using GasificationEfficient CHP Absorption Chilling
Trailblazing to a Low Carbon Future
44 4444
1990 2006 Change since 1990
2010 Change since 1990
Students 5570 14047 +152% 16000 +187%
Floor Area (m2) 138000 207000 +50% 220000 +159%
CO2 (tonnes) 19420 21652 +11% 14000 -28%
CO2 kg/m2 140.7 104.6 -25.7% 63.6 -54.8%
CO2 kg/student 3490 1541 -55.8% 875 -74.9%
Efficient CHP Absorption Chilling
Trailblazing to a Low Carbon Future
45
Conclusions• Effective adaptive energy management can reduce heating
energy requirements in a low energy building by 50% or more.
• Heavy weight buildings can be used to effectively control energy consumption
• Photovoltaic cells need to take account of intended use of electricity use in building to get the optimum value.
• Building scale CHP can reduce carbon emissions significantly
• Adsorption chilling should be included to ensure optimum utilisation of CHP plant, to reduce electricity demand, and allow increased generation of electricity locally.
• Promoting Awareness can result in up to 25% savings
• When the Biomass Plant is fully operational, UEA will have cut its carbon emissions per student by over 70% since 1990.
Lao Tzu (604-531 BC) Chinese Artist and Taoist philosopher
"If you do not change direction, you may end up where you are heading."
Finally!