+ All Categories
Home > Documents > New Chapter 8 Harmonic Limits and Filtering

New Chapter 8 Harmonic Limits and Filtering

Date post: 03-Jun-2018
Category:
Upload: -
View: 229 times
Download: 0 times
Share this document with a friend

of 46

Transcript
  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    1/46

    Chapter 8 Page 1 Harmonic Limits and Filtering

    CHAPTER 8

    HARMONIC LIMITS AND

    FILTERING

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    2/46

    Chapter 8 Page 2 Harmonic Limits and Filtering

    INTRODUCTION

    As the number and power ratings of nonlinear loads connected to the utilitysystem increases, so does the concern over harmonics. This concern is, first,with the effect of harmonics on the quality of power being furnished to the

    customer and, second, with the effects of harmonics on the operation of othersystems such as the telephone.

    These concerns have lead to the formulation of utility guidelines for the followingitems:

    Voltage Distortion Factor

    Current Distortion Factor

    Telephone Interference

    Moreover, each utility may specify additional harmonic limitations.

    SUMMARY OF THE IEEE 519 STANDARD

    The following is a summary of the content of the IEEE 519-1992 Standard.

    Scope

    "This Recommended Practice intends to establish goals for the design of

    electrical systems which include both linear and nonlinear loads. The voltage and

    current waveforms which may exist throughout the system are described andwaveform distortion goals for the system designer are established. The interface

    between sources and loads is described as the point of common coupling, and

    observance of the design goals will minimize interference between electrical

    equipment."

    "The recommended practice addresses steady-state limitation. Transient

    conditions exceeding these limitations may be encountered. It sets the

    quality of power that is to be provided at the point of common coupling. This

    document does not cover the effects of radio-frequency interference, but does

    include electromagnetic interference with communications systems."

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    3/46

    Chapter 8 Page 3 Harmonic Limits and Filtering

    Applicat ion of the Standard

    "This standard is to be used for guidance in the design of power systems with

    nonlinear loads. The limits set are for steady-state operation and are

    recommended for the 'worst case' conditions. Transient conditions exceeding

    these limits may be encountered."

    IEEE 519-1992 STANDARD - TERMS

    TDD - Total Demand Distortion (RMS), harmonic current distortion in % of

    maximum demand load current (15 or 30 minute demand).

    Point of Common Coupling (PCC) -A point of metering, or any point as long

    as both the utility and the consumer can either access the point for direct

    measurement of the harmonic indices meaningful to both or estimate the

    harmonic indices at the point of interference through mutually agreeable

    methods. Within an industrial load, the point of common coupling is the point

    between the nonlinear load and other loads.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    4/46

    Chapter 8 Page 4 Harmonic Limits and Filtering

    VOLTAGE DISTORTION FACTOR

    DEFINITION

    The voltage distortion factor is defined as follows:

    VDFV

    Vnn

    =

    =

    1

    1

    2

    2

    1 2/

    where: VDF = Voltage Distortion Factor

    V1= rms Value of the fundamental voltage

    Vn= rms Value of the nthharmonic voltage

    LIMITSLimits on voltage distortion for medium and high voltage systems are listed inTable 8-1.

    Bus Voltage at PCCIndividual Voltage

    Distortion (%)

    Total Voltage

    Distortion THD (%)

    69 kV and below

    69 001 kV through 161 kV

    161 001 kV and above

    3.0

    1.5

    1.0

    5.0

    2.5

    1.5Note: High-voltage systems can have up to 2.0% THD where the cause is an

    HVDC terminal that will attenuate by the time it is tapped for a user.

    Table 8-1. Limi ts on Voltage Distortion

    These limits should be used for worst case continuous operation lasting longerthan one hour. For shorter periods, during startup or unusual conditions, theselimits may be exceeded by 50%.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    5/46

    Chapter 8 Page 5 Harmonic Limits and Filtering

    CURRENT DISTORTION FACTOR

    DEFINITION

    The current distortion factor is defined as follows:

    CDFI

    Inn

    =

    =

    1

    1

    2

    2

    1 2/

    where: CDF = Current Distortion Factor

    I1= rms value of the fundamental current

    In= rms value of the nth

    harmonic current

    LIMITS

    The following limits should be used for worst case continuous operation lastinglonger than one hour. For shorter periods, during startup or unusual conditions,these limits may be exceeded by 50%.

    These limits are permissible provided the transformer connecting the user to theutility will not be subjected to harmonics in excess of 5% CDF.

    The harmonic current limits are based on the power requirements of the user withrespect to the size of the utility power system.

    As the size of user load decreases with respect to the utility, the larger is thepercentage of harmonic current that can be injected into the utility system.

    When the CDF limit exceeds 5%, the heating effect in the transformer should be

    evaluated by applying the methodology contained in IEEE Standard 57.110-1986.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    6/46

    Chapter 8 Page 6 Harmonic Limits and Filtering

    CURRENT DISTORTION LIMITS

    FOR GENERAL DISTRIBUTION SYSTEMS

    (120 V - 69 KV)

    MAXIMUM HARMONIC CURRENT DISTORTION IN % OF IL

    INDIVIDUAL HARMONIC ORDER (ODD HARMONICS)

    Isc/IL

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    7/46

    Chapter 8 Page 7 Harmonic Limits and Filtering

    CURRENT DISTORTION LIMITS FOR

    GENERAL SUBTRANSMISSION SYSTEMS

    MAXIMUM HARMONIC CURRENT DISTORTION IN % OF IL

    INDIVIDUAL HARMONIC ORDER (ODD HARMONICS)

    Isc/IL

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    8/46

    Chapter 8 Page 8 Harmonic Limits and Filtering

    CURRENT DISTORTION LIMITS

    FOR HIGH VOLTAGE SYSTEMS (>161 KV)

    AND DISPERSED GENERATION AND COGENERATION

    MAXIMUM HARMONIC CURRENT DISTORTION IN % OF IL

    INDIVIDUAL HARMONIC ORDER (ODD HARMONICS)

    Isc/IL

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    9/46

    Chapter 8 Page 9 Harmonic Limits and Filtering

    TELEPHONE INTERFERENCE

    INTRODUCTION

    Harmonic currents flowing in a utility transmission system produce magnetic fieldsthat induce extraneous currents into adjacent telephone lines. These extraneouscurrents interfere with telephone transmission if they are in the audio frequencyrange and of appreciable magnitude.

    Telephone interference is expressed by an IT value

    ( )=

    ==1

    2**

    n

    nnWITIFITI

    where Inis the rms value of the nth

    harmonic current flowing in the utility system andWnis a TIF weighting factor that is dependent on frequency.

    TIF WEIGHTING FACTORS

    TIF weighting factors, Wn, are listed in Table 8-2.

    FREQ TIF FREQ TIF FREQ TIF FREQ TIF

    60

    180

    300

    360

    420

    540

    660

    720

    780

    900

    1000

    0.5

    30

    225

    400

    650

    1320

    2260

    2760

    3360

    43505000

    1020

    1080

    1140

    1260

    1380

    1440

    1500

    1620

    1740

    1800

    -

    5100

    5400

    5630

    6050

    6370

    6650

    6680

    6970

    7320

    7570-

    1860

    1980

    2100

    2160

    2220

    2340

    2460

    2580

    2820

    2940

    -

    7820

    8330

    8830

    9080

    9330

    9840

    10340

    10600

    10210

    9820-

    3000

    3180

    3300

    3540

    3660

    3900

    4020

    4260

    4380

    5000

    -

    9670

    8740

    8090

    6730

    6130

    4400

    3700

    2750

    2190

    840-

    Table 8-2. TIF Weight ing Factors

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    10/46

    Chapter 8 Page 10 Harmonic Limits and Filtering

    Figure 8-1. TIF Weight ing Factors

    Example A: A hypothetical load on the primary side of a 115 kV-rated transformer islisted in Table 8-3. Calculate the I * T factor.

    HARMONI

    C

    NO.

    FREQ.

    (HZ)

    IN

    (AMPS) WN INWN (INWN)2

    1 60 50.0 0.5 25 625

    5 300 5.0 225 1125 1265625

    7 420 2.5 650 1625 2640625

    11 660 1.0 2260 2260 5107600

    13 780 1.0 3220 3220 10368400

    17 1020 0.5 5100 2550 6502500

    19 1140 0.5 5630 2815 10660225

    23 1380 0.5 6370 3185 10144225

    25 1500 0.5 6680 3340 11155600

    Table 8-3. Example A Answer

    I T ( I W )n

    n n* , ,= =

    =

    1

    252 57 845 425 7606=

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    11/46

    Chapter 8 Page 11 Harmonic Limits and Filtering

    LIMITS

    Limits on telephone interference are presented below

    Category Descript ion I * T

    I Levels most unlikely tocause interference

    Up to 10,000

    II Levels that might causeinterference

    10,000 to 25,000

    III Levels that probably willcause interference

    greater than 25,000

    Note: These values of I*T product are for circuits with an exposurebetween overhead systems, both power and telephone.Within an industrial plant or commercial building, the

    exposure between power distribution in cables andtelephone lines in cable with twisted pairs is extremely lowand no interference is normally encountered. I*T productssimilar to those of Table 8-4 should be used within plantsand buildings.

    For some areas that use a ground retrun for eithertelephone or power circuits, this value may be as low as1500.

    Table 8-4. Balanced I*T Guidelines for Converter Installations,Tie (Supply) Lines

    Balanced I * T is the I * T value of the phase currents.

    Residual I * T is the I * T value of the neutral (ground return) currents.

    The above guidelines are applicable to balanced rather than residual I * Tvalues.IEC 555-2

    Disturbances in Supply Systems Causes by Household and Similar Equipment

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    12/46

    Chapter 8 Page 12 Harmonic Limits and Filtering

    This standard defines limits for harmonic production of individual loads having an

    input current up to 16 A. It classifies equipment into four categories:

    Class A Balanced three phase equipment and that equipment that

    does not fit any other class as defined below.

    Class B Portable and similar tools.

    Class C Lighting equipment, including dimmers.

    Class D Equipment having an input current with a special waveshape

    (electronic power supplies).

    Both absolute and relative harmonic limits are specified, see Tables below. Note for

    Class A the absolute limits allow impose severe restrictions on larger equipment.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    13/46

    Chapter 8 Page 13 Harmonic Limits and Filtering

    HARMONIC CURRENT LIMITS FOR CLASS A EQUIPMENT AND CERTAIN

    CLASS C EQUIPMENT WITH PHASE CONTROLLED LAMP DIMMERS

    HARMONIC ORDER MAXIMUM PERMISSIBLE

    HARMONIC CURRENT (A)

    Odd Harmonics

    3 2.3

    5 1.14.

    7 0.77

    9 0.4

    11 0.33

    13 0.21

    15-39 0.15 x (15/n)

    Even Harmonics

    2 1.08

    4 0.43

    6 0.30

    8-40 0.23 x ( 8/n)

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    14/46

    Chapter 8 Page 14 Harmonic Limits and Filtering

    HARMONIC LIMITS FOR CLASS C EQUIPMENT

    LARGER THAN 25 WATTS

    HARMONIC ORDER MAXIMUM PERCENT

    2 2

    3 30

    5 10

    7 7

    9 5

    11-39 3

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    15/46

    Chapter 8 Page 15 Harmonic Limits and Filtering

    HARMONIC LIMITS

    FOR CLASS D AND CLASS C EQUIPMENT

    LARGER THAN 25 WATTS (RELATIVE LIMITS 300 WATTS)

    HARMONIC ORDER RELATIVE mA/W ABSOLUTE (A)

    Odd Harmonic

    3 3.6 1.08

    5 2.0 0.60

    7 1.5 0.45

    9 1.0 0.30

    11-39 0.6 x (11/n) 0.18 x (11/n)

    Even Harmonic

    2 1.0 0.30

    4 0.5 0.15

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    16/46

    Chapter 8 Page 16 Harmonic Limits and Filtering

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    17/46

    Chapter 8 Page 17 Harmonic Limits and Filtering

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    18/46

    Chapter 8 Page 18 Harmonic Limits and Filtering

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    19/46

    Chapter 8 Page 19 Harmonic Limits and Filtering

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    20/46

    Chapter 8 Page 20 Harmonic Limits and Filtering

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    21/46

    Chapter 8 Page 21 Harmonic Limits and Filtering

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    22/46

    Chapter 8 Page 22 Harmonic Limits and Filtering

    NON-FILTER METHODS

    ALTER SYSTEM OPERATING CONDITIONS

    Simplest and least expensive.

    Often impractical or undesirable.

    CHANGE LOCATION OR SIZE OF POWER FACTOR CAPACITOR

    Changes resonant frequency.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    23/46

    Chapter 8 Page 23 Harmonic Limits and Filtering

    ACTIVE FILTERS

    use IGBTs (Insulated Gate Bipolar Transistor) switching up to 20 kHz

    supply a current waveform (opposite polarity) that is added to the harmonic

    current to produce a nearly sinusoidal wave shape

    advantages

    instant adaptation to changing load and source conditions

    can be located in close proximity to the non-linear load

    can be used on single or three phase systems

    eliminates a broad spectrum of harmonics (up to 50th

    )

    harmonics in the system are nearly zero

    increases system capacity

    Figure 8-4. Active Filter

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    24/46

    Chapter 8 Page 24 Harmonic Limits and Filtering

    ACTIVE FRONT ENDS

    active filter attached to the input of a VFD

    uses IGBTs instead of diode rectifier

    ensures good power quality over the drives complete operating range

    advantages

    sinusoidal line current drawn from system, thus low harmonics

    power factor adjustable from 0.8 capacitive to 0.8 inductive

    can compensate for line supply undervoltage

    no interference with p.f. correction equipment (no resonance)

    can be installed without a detailed analysis of power system

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    25/46

    Chapter 8 Page 25 Harmonic Limits and Filtering

    PHASE MULTIPLICATION

    Harmonics can be canceled by phase multiplication (Figure 8-5). For cancellation tooccur using m six-pulse rectifiers the following five conditions must exist:

    (1) Transformers must have the same turn ratios.

    (2) Transformers must have identical impedances.

    (3) Secondary voltages must be phase shifted 360/6m degrees from each other.

    (4) Rectifiers must be controlled at the same delay angle.

    (5) Rectifiers must share the dc load equally.

    Because no two rectifiers are exactly the same, cancellation is not complete.Assume that 10 percent of the uncancelled harmonic will remain.

    Figure 8-5. Phase Multip lication

    12 Phase

    6- Pulse 6- Pulse

    (a) 12 Pulse

    24 Pulse

    (a) 24 Phase

    Bus C

    6- Pulse

    12 Pulse

    6- Pulse

    Bus D

    6- Pulse

    12 Pulse

    6- Pulse

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    26/46

    Chapter 8 Page 26 Harmonic Limits and Filtering

    FILTER METHODS

    PROVIDE SHUNT LC FILTERS

    Located near the harmonic source.

    Tuned to most troublesome harmonics (lowest order).

    Provides low impedance path for harmonic current flow.

    For large systems separate filter sections may be required for major harmonics(e.g., 2

    nd, 3

    rd, 4

    th, 5

    th, etc.).

    Various filter arrangements can be employed.

    Arrangement 8-6a - Simplest, least expensive, generally tuned to N =

    4.7 - 4.8 harmonic.

    Arrangement 8-6b - Bypass resistor added to provide high frequencyfiltering.

    Arrangement 8-6c - Required when stringent harmonic specifications areimposed. Includes separate filter sections tuned to each of the lowestorder harmonics plus a high frequency section.

    Figure 8-6. Band Pass Filters

    SINGLE-TUNED FILTERS

    IMPEDANCE

    The impedance of single-tuned filters consists of a capacitor and an inductor that areconnected in series, as represented by the following formula.

    Z Rf = + j ( L -1

    C )

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    27/46

    Chapter 8 Page 27 Harmonic Limits and Filtering

    where: XL= L is the inductance of the reactor in ohms at 60 Hz

    XC= 1/(C) is the reactance of the capacitor in ohms at 60 Hz

    R = filter resistance in ohms

    n= 2fn=1

    LC = tuned angular frequency in radians/second

    Figure 8-7. Single-Tuned Filter

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    28/46

    Chapter 8 Page 28 Harmonic Limits and Filtering

    QUALITY FACTOR

    The quality factor or sharpness of the filter tuning (larger Q, sharper tuning) isrepresented by the following formula.

    Q = = =X

    R

    L

    R R Cn n

    n

    1

    FREQUENCY DEVIATION (DETUNING)

    In practice a filter is not always tuned exactly to the frequency of the harmonic that itis intended to suppress. This is the result of several factors.

    (1) The power system frequency may change, which causes the harmonic frequencyto change proportionally.

    (2) The inductance and capacitance values may change. Of the two values, the

    capacitance value can change the most because of aging and changes in ambienttemperature or self-heating.

    (3) The initial tuning may be off because of finite size capacitor units.

    The total detuning or equivalent frequency deviation is represented by the followingformula:

    =

    = + +

    n

    n

    f

    f

    L

    L

    C

    C

    12

    A change of L or C of 2% causes the same detuning as a change of 1% in thesystem frequency.

    A plot of filter impedance versus detuning is shown in Figure 8-8.

    Figure 8-8. Filter Impedance vs. Detuning

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    29/46

    Chapter 8 Page 29 Harmonic Limits and Filtering

    The filter passband, PB, is bounded by frequencies at which Zf = 2 R, as

    represented by the following formula.

    = = =

    1

    2 2 2Q

    R

    L

    R C

    n

    n

    A tuned filter can be made less susceptible to changes in f, L, or C by (1) increasingC and (2) reducing Q.

    DOUBLE-TUNED FILTERS

    CONFIGURATION

    A double-tuned filter can be achieved in two configurations, as shown in Figures 8-9(a) or (b). Because of the reduction in the number of inductors subjected to full lineimpulse voltages, the main advantage of the configuration shown in Figure 8-9(b) is

    for high voltage applications.

    Figure 8-9. Double-Tuned Filter

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    30/46

    Chapter 8 Page 30 Harmonic Limits and Filtering

    COMPOSITE FILTERS

    CONFIGURATION

    Composite filters (Figure 8-10) are made up of various tuned filters and a high pass

    filter. For example, F1 and F2 would each be tuned to an individual low orderharmonic, while F3would be designed to provide high frequency filtering. Compositefiltering is the most popular method of filtering.

    Figure 8-10. Composi te Filter

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    31/46

    Chapter 8 Page 31 Harmonic Limits and Filtering

    Figure 8-11 shows a typical composite filter that is used with 6-pulse rectifiers.

    Figure 8-11. Filter for 6-Pulse Recti fiers

    Figure 8-12 shows a typical composite filter that is used with an arc furnaceinstallation.

    Figure 8-12. Filter for an Arc Furnace Installation

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    32/46

    Chapter 8 Page 32 Harmonic Limits and Filtering

    At

    Resonant

    Frequency

    At

    Fundament

    al

    FrequencyReactor

    Voltage

    Capacitor

    Voltage

    Reactor

    Voltage

    Capacitor

    Voltage

    Capacitor Voltage

    Reactor Voltage

    System

    Voltage

    hXL

    (-hXL)

    XL

    (-h2XL)

    h2

    h2-1* VF

    1

    h2-1* VF

    VF

    VF

    I

    CAPACITOR VOLTAGE

    VERSUS SYSTEM

    VOLTAGE

    At

    Resonant

    Frequency

    At

    Fundament

    al

    FrequencyReactor

    Voltage

    Capacitor

    Voltage

    Reactor

    Voltage

    Capacitor

    Voltage

    Capacitor Voltage

    Reactor Voltage

    System

    Voltage

    hXL

    (-hXL)

    XL

    (-h2XL)

    h2

    h2-1* VF

    1

    h2-1* VF

    VF

    VF

    I

    CAPACITOR VOLTAGE

    VERSUS SYSTEM

    VOLTAGE

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    33/46

    Chapter 8 Page 33 Harmonic Limits and Filtering

    13.8

    14.091.027

    14.191.036

    14.381.045

    14.721.074

    15.531.133

    18.401.332

    be rated for (kV)of System VoltageFilter is Tuned

    shouldin P.U.To Which

    CapacitorCapacitor VoltageHarmonic Frequency

    13.8

    14.091.027

    14.191.036

    14.381.045

    14.721.074

    15.531.133

    18.401.332

    be rated for (kV)of System VoltageFilter is Tuned

    shouldin P.U.To Which

    CapacitorCapacitor VoltageHarmonic Frequency

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    34/46

    Chapter 8 Page 34 Harmonic Limits and Filtering

    SYSTEM WITH NO FILTERING

    1 2 3 4 5 6 7

    ParallelReactance

    Parallel

    Reactance

    System Reactance

    Capacitor

    Reactance

    Harmonic

    Reactance

    System Reactance

    (a) Typical System One Line Diagram

    (b) System Representation

    (c) Frequency Plot

    of

    System

    Impedance

    SYSTEM WITH NO FILTERING

    1 2 3 4 5 6 7

    ParallelReactance

    Parallel

    Reactance

    System Reactance

    Capacitor

    Reactance

    Harmonic

    Reactance

    System Reactance

    (a) Typical System One Line Diagram

    (b) System Representation

    (c) Frequency Plot

    of

    System

    Impedance

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    35/46

    Chapter 8 Page 35 Harmonic Limits and Filtering

    SYSTEM WITH FILTERING

    1 2 3 4 5 6 7

    Parallel

    Reactance

    (no filter)

    Parallel

    Reactance

    (no filter)

    System Reactance

    Capacitor

    Reactance

    Harmonic

    Reactance

    System Reactance

    (a) Typical System One Line Diagram

    (b) System Representation

    (c) Frequency Plot

    of

    System

    Impedance

    Filter

    Reactance

    Parallel

    Reactance

    (with filter)

    Critical Area

    SYSTEM WITH FILTERING

    1 2 3 4 5 6 7

    Parallel

    Reactance

    (no filter)

    Parallel

    Reactance

    (no filter)

    System Reactance

    Capacitor

    Reactance

    Harmonic

    Reactance

    System Reactance

    (a) Typical System One Line Diagram

    (b) System Representation

    (c) Frequency Plot

    of

    System

    Impedance

    Filter

    Reactance

    Parallel

    Reactance

    (with filter)

    Critical Area

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    36/46

    Chapter 8 Page 36 Harmonic Limits and Filtering

    TUNED FILTER DESIGN

    GENERAL

    Filter design is a step-by-step procedural process. The remainder of this tab will

    describe that process by following an example problem.

    SAMPLE CALCULATION

    A 6600 kVAR capacitor bank is required to provide power factor correction on a 34.5kV power system. To avoid possible resonance problems, an inductor is connectedin series with the capacitor to form a filter that is tuned to N = 4.7. The filter is wye-connected. See Figure 8-13. The step-by-step design process is as follows.

    Figure 8-13. Sample Calculation One-Line Diagrams

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    37/46

    Chapter 8 Page 37 Harmonic Limits and Filtering

    Step 1: At the nominal system voltage of 34.5 kvLL:

    kV

    kV

    LL

    LN

    VN

    Nx V x kVCF F LL=

    =

    =

    = =

    2

    2

    2

    21

    4 7

    4 7 134 5

    36136

    36136

    32086

    ( . )

    ( . ).

    .

    ..

    Use a standard 21.6 kV capacitor can.

    The rated capacitor voltage is then

    VC= 21.6 x 3 = 37.4 kVLL

    Step 2: Tuning reactor required for power factor correction:

    kVARN

    x kVAC

    x

    =

    =

    1

    1

    1

    4 7 1

    2

    2

    6600 = 313 kVAR( . )

    Step 3: Required capacitor operating kVAR :

    kVAR = 6600 + 313 = 6913 kVAR at 36.136 kVLL

    At rated capacitor voltage:

    kVAR =37 4

    361366913 7405

    2.

    .

    =x kVAC

    Conclusion: One needs 7405 kVAR @ 37.4 kV to get the required6913 kVAC @ 36.136 kV

    Step 4: Capacitor bank electrical parameters:

    Choose 7.5 MVAR at 37.4 kVLL.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    38/46

    Chapter 8 Page 38 Harmonic Limits and Filtering

    Step 5: Capacitor reactance @ 50 Hz :

    Step 6: Tuning Reactor reactance @ 50 Hz :

    Step 7: Actual capacitor operating MVAC @ 36.136 kV:

    MVAC x MVAC=

    =

    36136

    37 4

    7 5 7 0

    2

    .

    .

    . .Note: 6913 kVAR of capacitors was initially required.

    Capacitor operating current = reactor operating current

    I VA

    = = =3

    7000

    3112

    V * 36.136amperes

    LL

    Step 8: The tuning reactor electrical parameters are as follows:

    1. Voltage rating = 37.4 kV (L-L)

    2. XL= 8.44 at 50 Hz

    3. L = 26.9 mH

    4. Q = minimum of 50 at 50 Hz

    5. Current carrying duty

    Fundamental = 112 amperes

    For harmonic currents, a harmonic analysis study should beperformed to determine total current rating.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    39/46

    Chapter 8 Page 39 Harmonic Limits and Filtering

    ACTIVE FILTER DESIGN AND SPECIFICATION

    FOR CONTROL OF HARMONICS IN INDUSTRIAL AND COMMERCIAL

    FACILITIES

    Mark McGranaghan

    Electrotek Concepts, Inc.

    Knoxville TN, USA

    The increasing use of power electronics-based loads (adjustable speed drives,switch mode power supplies, etc.) to improve system efficiency and controllability isincreasing the concern for harmonic distortion levels in end use facilities and on the

    overall power system.

    The application of passive tuned filters creates new system resonances which aredependent on specific system conditions. Also, passive filters often need to besignificantly overrated to account for possible harmonic absorption from the powersystem.

    Passive filter ratings must be coordinated with reactive power requirements of theloads and it is often difficult to design the filters to avoid leading power factoroperation for some load conditions. Active filters have the advantage of being able tocompensate for harmonics without fundamental frequency reactive power concerns.

    This means that the rating of the active power can be less than a conquerablepassive filter for the same nonlinear load and the active filter will not introducesystem resonances that can move a harmonic problem from one frequency toanother.

    The active filter concept uses power electronics to produce harmonic componentswhich cancel the harmonic components from the nonlinear loads. These active filtersare relatively new and a number of different topologies are being proposed.

    Active Filter Configuration

    The active filter uses power electronic switching to generate harmonic currents thatcancel the harmonic currents from a nonlinear load. The active filter configurationinvestigated in this paper is based on a pulse-width modulated (PWM) voltagesource inverter that interfaces to the system through a system interface filter asshown in Figure 1. In this configuration, the filter is connected in parallel with theload being compensated. Therefore, the configuration is often referred to as anactive parallel filter.

    Figure 1 illustrates the concept of the harmonic current cancellation so that thecurrent being supplied from the source is sinusoidal.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    40/46

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    41/46

    Chapter 8 Page 41 Harmonic Limits and Filtering

    The active filter does not need to provide any real power to cancel harmonic currentsfrom the load. The harmonic currents to be canceled show up as reactive power.Reduction in the harmonic voltage distortion occurs because the harmonic currentsflowing through the source impedance are reduced.

    Therefore, the dc capacitors and the filter components must be rated based on thereactive power associated with the harmonics to be canceled and on the actualcurrent waveform (rms and peak current magnitude) that must be generated toachieve the cancellation.

    The current waveform for canceling harmonics is achieved with the voltage sourceinverter and an interfacing filter. The filter consists of a relatively large isolationinductance to convert the voltage signal created by the inverter to a current signal forcanceling harmonics. The rest of the filter provides smoothing and isolation for highfrequency components. The desired current waveform is obtained by accuratelycontrolling the switching of the insulated gate bipolar transistors (IGBTs) in the

    inverter. Control of the current wave shape is limited by the switching frequency ofthe inverter and by the available driving voltage across the interfacing inductance.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    42/46

    Chapter 8 Page 42 Harmonic Limits and Filtering

    Example System for Act ive Filter Performance Evaluation

    A simple example system was modeled to evaluate the active filter performance fordifferent types of loads and to evaluate the impact of system switching events on thedesign requirements for the active filter. A typical distribution circuit as shown in

    Figure 4 was selected for this evaluation. Important parameters are as follows:

    Source strength at transmission supply point = 200 MVA

    138/13.8 kV Transformer: 10 MVA, 7% impedance

    Substation capacitor bank size = 3.0 Mvar (switched)

    Equivalent load for parallel feeders = 3.0 MW

    Modeled feeder circuit: 3.0 miles to example customer

    Feeder capacitor bank on 13.8 kV side at example customer: different sizesevaluated

    Customer low voltage capacitor bank: varied

    Customer service transformer: 1500 kVA, 6% impedance

    Customer load = 1.0 MW

    Active Filter size = 400 Vrms, 30 Arms

    Nonlinear load: different loads evaluated

    Determining Active Filter Ratings for Nonlinear Load Types

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    43/46

    Chapter 8 Page 43 Harmonic Limits and Filtering

    One of the confusing aspects of applying active filters is trying to figure out the activefilter rating that is required to compensate for the harmonics from a particular load. Aparallel-connected active filter should be rated in terms of the rms current it canprovide. Then the task is to figure out the rms current required to compensate for theharmonics from different types of loads. Simulations were performed for a number of

    typical nonlinear loads to develop some guidelines for active filter ratings.

    One advantage of the parallel-connected active filter, as compared to passive filters,is that it is self-limiting in terms of the harmonic cancellation provided. there is noconcern for overloading the filter due to harmonics from the utility supply system orunder-rating the filter for the loads involved. The worst case scenario if the filter isunder-rated is that it just wont completely compensate for all the nonlinear loadcurrent harmonics. In fact, it may not be necessary to compensate for all theharmonics from a nonlinear load. With the active filter, the size can be selected toachieve any desired level of cancellation. One good way to use this concept wouldbe to provide only enough compensation so that the load/filter compensation waswithin some specified guidelines for harmonic generation (e.g. IEEE 519-1992).

    Effect of Load Waveform on Filtering Effectiveness

    The effectiveness of the active filter in compensating for harmonic components ofthe load current depends on the specific load current waveform involved. Twodifferent waveforms may have the same rms harmonic content but the active filtermay do a better job of compensating for one of the waveforms because of the waveshapes involved.

    An ac voltage regulator is used for illustration. Two cases are compared in Figure 5.The only difference between the two cases is the load of the ac regulator.

    In the waveforms on the left side of the figure, the load is a pure resistance. Thewaveforms on the right side are for the case where the load is a series combinationof resistance and reactance. The performance is much better for the smoother loadcurrent waveform (RL load). It is worthwhile to note that the majority of applicationsfor the active filter will involve waveforms like those on the right hand side of Figure 6(e.g. adjustable speed drives with diode bridge rectifiers or single phase electronicloads), rather than the left side.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    44/46

    Chapter 8 Page 44 Harmonic Limits and Filtering

    In general, the current waveform of an ac regulator with resistive load is an exampleof the wave shape that poses the severest challenge for an active filter.

    The problem is the high di/dt that is required of the filter to compensate for the highdi/dt at turn on of the regulator. The problem is most severe when the regulator isturned on with a firing angle close to 90 degrees because this is when the availabledriving voltage stored on the dc capacitor is at a minimum.

    The output di/dt capability can be raised either by increasing the dc voltage settingor by reducing the size of the interfacing inductance. The limiting factor forincreasing the dc voltage is the voltage withstand capability of the IGBT devices.The limiting factors for reducing the interfacing inductance include the IGBT di/dtwithstand capability, control requirements, the interface passive filter requirement,and overall system stability. If the interfacing inductance becomes too small, the dcvoltage cannot be kept constant for normal operation.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    45/46

    Chapter 8 Page 45 Harmonic Limits and Filtering

    Steady-State Rating Requirements and Act ive Filter Effectiveness

    The best way to provide a rating for an active filter is in terms of the rms current thatit must provide to compensate for harmonics from nonlinear loads.

    Table 1 provides a convenient summary of different nonlinear load types withexample waveforms and typical levels of harmonic current distortion associated witheach load. Using these typical waveforms, it is possible to calculate a theoreticalvalue for the required harmonic compensation from the active filter. The summaryincludes the THD for each nonlinear load waveform and the required active filterrating in rms amps per kVA of load rating. These ratings assume that the active filterrating should be based on the total rms harmonic current content of the load. Asimulation waveform illustrating the active filter effectiveness for each of thesewaveforms is also provided. The ratings in Table 1 assume ideal active filtercharacteristics. That is, they assume that the active filter can compensate for everyamp of harmonic current created by the nonlinear load. It is clear from the simulation

    result waveforms also included in the table that the harmonic cancellation is notperfect. The distortion in the supply current is also provided in the table to illustratethe effectiveness of the active filter.

    It is important to note that these simulations were for steady state conditions (loadwas not changing).

    Therefore, the effect of the response time associated with the FFT control was not afactor.

    A number of important observations can be made based on the results summarizedin Table 1:

    The overall filtering effectiveness depends significantly on the types ofloads being compensated. There is no simple relationship between theload current THD and the filter effectiveness.

    The active filter is most effective when the load current waveform does nothave abrupt changes. As a result, it is very effective for most voltagesource inverter-type loads, even when the distortion is high.

    The active filter effectiveness was not as good for 12 pulse loads. This iscaused by the fact that the higher frequency components are moredominant in these loads.

    The rating requirement for the passive filter capacitor is also dependent onthe load current characteristics. Load current waveforms with more highfrequency content (e.g. ac regulator with resistive load or 12 pulseconverters) result in higher duties on the filter capacitor.

  • 8/12/2019 New Chapter 8 Harmonic Limits and Filtering

    46/46


Recommended