NYC Department of Education Building Condition Assessment Survey 2018-2019 X044 Architectural Inspection Inspection Type Last Edited Time In InspectionId P.S. 44 - BRONX, 1825 PROSPECT AVENUE, BRONX, NY, 10457 School: 4970 2019-05-22 08:52AM 2019-05-28 08:45AM ARCHITECTURAL - SENIOR 5004 2019-05-22 08:38AM 2019-05-28 10:13AM ARCHITECTURAL - ASSOCIATE Asset Data Question Answer Was the Building Fully Accessible for Inspection? No The building is surrounded by scaffolding, Sidewalk Shed and netting for the ongoing work at the Security Lights, Roof, Parapet and Exterior Walls, so these components weren’t accessible for inspection . Comments on Inaccessible Inspection Principal(s) Information Principal Name Melissa Harrow Principal Organization C.S. 44 David C. Farragut - Bronx Meeting with Principal? Yes Principal Feedback The Principal provided the following comments: 1.The PA System is deficient and need replacement. 2. The Auditorium Seating is deteriorated and requires renovations. 3. The Corridor Floors are deteriorated and need refinishing . Principal Name Lariely Sanchez Principal Organization 84X598 - Kipp Freedom Middle School Meeting with Principal? Yes Principal Feedback The Principal provided the following comments: 1. The Interior Plumbing fixtures are deficient and need repairs or replacement. 2. The Heating and Cooling in the building is inconsistent from room to room and requires control adjustments or upgrades. 3. The Ceiling on 4th Floor and Auditorium are deteriorated and need refinishing. Custodian Was not present Fireman Toni Cubi Building Square Footage 72,000 Comments on the Area (Square Feet) N/A Comments on the Stories (Floors) plus Basements 4+B+PH Comments on the Year Built 1911 Comments on the Student Population 385 Comments on the Staff Population 61 Comments on the Number of Classrooms 49 Weather Fair Facade Photo Corner of Prospect Avenue and E 176th Street - West View Page 1 of 25 Print Date: 7/3/2019 Mobile Validity Version 2.0 (P)
Transcript
Page 1: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Inspection Type Last EditedTime InInspectionId

P.S. 44 - BRONX, 1825 PROSPECT AVENUE, BRONX, NY, 10457School:

4970 2019-05-22 08:52AM 2019-05-28 08:45AMARCHITECTURAL - SENIOR

5004 2019-05-22 08:38AM 2019-05-28 10:13AMARCHITECTURAL - ASSOCIATE

Asset DataQuestion Answer

Was the Building Fully Accessible for Inspection? No

The building is surrounded by scaffolding, Sidewalk Shed and

netting for the ongoing work at the Security Lights, Roof,

Parapet and Exterior Walls, so these components weren’t

accessible for inspection .

Comments on Inaccessible Inspection

Principal(s) Information

Principal Name Melissa Harrow

Principal Organization C.S. 44 David C. Farragut - Bronx

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comments:

1.The PA System is deficient and need replacement.

2. The Auditorium Seating is deteriorated and requires

renovations.

3. The Corridor Floors are deteriorated and need refinishing .

Principal Name Lariely Sanchez

Principal Organization 84X598 - Kipp Freedom Middle School

Meeting with Principal? Yes

Principal Feedback The Principal provided the following comments:

1. The Interior Plumbing fixtures are deficient and need repairs or

replacement.

2. The Heating and Cooling in the building is inconsistent from

room to room and requires control adjustments or upgrades.

3. The Ceiling on 4th Floor and Auditorium are deteriorated and

need refinishing.

Custodian Was not present

Fireman Toni Cubi

Building Square Footage 72,000

Comments on the Area (Square Feet) N/A

Comments on the Stories (Floors) plus Basements 4+B+PH

Comments on the Year Built 1911

Comments on the Student Population 385

Comments on the Staff Population 61

Comments on the Number of Classrooms 49

Weather Fair

Facade Photo

Corner of Prospect Avenue and E 176th Street - West View

Page 1 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 2: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural InspectionMain Entrance Photo

Facade A - Prospect Avenue

Roof Photo

Roof 1 - North View

Have any Systems/Major Building Components been upgraded? Systems: Foundation Wall/ Slab waterproofing (Electrical Panel

Room), Exterior Stair repairs (partial), Schoolyard

repaying (partial )

Years: 2013

Systems: Exterior Stair repairs (partial )

Years: 2009

Systems: HC Student Toilet Room upgrades

Years: 2008

Systems: Parapet, Exterior Masonry repairs (partial )

Years: 2004

Systems: Roofing,Windows/Guards replacement (full)

Years: 1999

Have there been any New Building Additions? No New Construction

Tandem No Tandem

Leased Space? No

Priority ConditionExist

Last Year?

Priority

Category

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

Missing Interior Fire

DoorsMissing door poses a

potential safety hazard

Classrooms/C

orridors/Admi

n Space

Door(s)

Corridor near

Room 105

Toni CubiYes Fireman

Page 2 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 3: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Structural Engineer Required

Structural

Condition Type

Condition

Description

Component

Affected

Location

Description

Person(s)

Notified

Person(s)

Title

Photo

Image

No condition recorded

Accessibility

Accessibility Status Question Response

Physical Breakdown Structure Exists Complies Required Deficiency

FUNCTIONAL ACCESSIBILITY

Exterior Routes

NoExterior Entrances & Exits

DOOR WIDTH < 36"

NoNoExterior H/C Lifts

NoNoExterior Ramps and Railings

Interior Routes

NoNoCorridor and Lobby H/C Lifts

NoYesInterior Corridor Doors And Hardware

YesInterior Corridors & Lobbies

NoInterior Elevators

YesInterior Lobby Doors And Hardware

NoInterior Ramps

Rooms & Spaces

Art Rooms

Yes NoRoom 312 (C.S. 44), 404 (Kipp Freedom

M.S.)

NOT ON ACCESSIBLE ROUTE

Auditorium

Yes No1st Floor

NOT ON ACCESSIBLE ROUTE

Cafeteria

Yes YesBasement

Classrooms

Yes NoNone on Accessible Route

NOT ON ACCESSIBLE ROUTE

Computer Rooms

Yes NoRoom 308

NOT ON ACCESSIBLE ROUTE

Gymnasium

Yes No4th Floor

NOT ON ACCESSIBLE ROUTE

NoLibrary

Main Office

Yes NoRoom 155(C.S. 44), 402(Kipp Freedom

M.S.)

NOT ON ACCESSIBLE ROUTE

Multi-purpose Room

Yes YesBasement

Nurse's Office

Yes NoRoom 158

NOT ON ACCESSIBLE ROUTE

NoPool

NoScience Lab

Page 3 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 4: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Physical Breakdown Structure Exists Complies Required Deficiency

Toilet Rooms (boys)

Yes YesRoom B18

Toilet Rooms (girls)

Yes YesRoom B4

Toilet Rooms (staff)

Yes NoNone on Accessible Route

NOT ON ACCESSIBLE ROUTE

Building Template

Inspection

Question Response

Architectural

ATHLETIC FIELDS Does not exist

EXTERIOR Inspected

Does not existAREAWAY

Does not existAWNINGS AND CANOPIES

InspectedCHIMNEY

MasonryMaterial Type(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Under constructionCOPING

Under constructionCORNICE

InspectedDOORS

InspectedDOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedDOORS AND FRAMES

Condition 3- Fair

METAL CLAD:DETERIORATED DOOR AND FRAME -

MINOR DETERIORATION

Deficiency

Page 4 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 5: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

EXTERIOR

DOORS

DOORS AND FRAMES

Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A - Main Entrance

Violations No violations recorded

InspectedLINTELS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedTRANSOM/SIDE LIGHT

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existEXTERIOR SOFFITS

Under constructionEXTERIOR WALLS

Does not existLOADING DOCK

InaccessibleLOUVER

Under constructionPARAPETS

Does not existPLAZA DECK

Under constructionROOF

InspectedSTAIRS/RAMPS: EXTERIOR

InspectedBUILDING CHEEK/FLANK WALLS

Condition 5- Poor

STONE:CRACKS/SPALLING - MAJORDeficiency

Deficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Page 5 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 6: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

BUILDING CHEEK/FLANK WALLS

Deficiency Photo 1

Facade A - Main Entrance

Violations No violations recorded

InspectedRAILINGS

Condition 3- Fair

RUST - MINORDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom L.F.

Potential Action MAINTENANCE

PRIORITY 2Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A - Main Entrance

Violations No violations recorded

InspectedSTAIRS/RAMPS

Condition 4- Between Fair and Poor

STONE:DETERIORATED SUBSTRATEDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE SUBSTRATE AND RESET

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Page 6 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 7: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo 1

Facade F

Violations No violations recorded

STONE:WORN-OUT TREAD/RISER/NOSINGDeficiency

Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Facade A

Violations No violations recorded

STONE:OPEN JOINTSDeficiency

Deficiency Location/Instance

5Deficiency Quantity

Quantity Uom L.F.

Potential Action REPOINT

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 7 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 8: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

EXTERIOR

STAIRS/RAMPS: EXTERIOR

STAIRS/RAMPS

Deficiency Photo 1

Facade F

Violations No violations recorded

InspectedWINDOWS

11,000Replacement Quantity

Replacement Uom S.F.

InaccessibleEXTERIOR GUARDS

InaccessibleLINTELS

InspectedWINDOWS

Material Type(s) Aluminum

Instance on Aluminum - Double Hung:All Facades Inspected

3- FairInstance Condition

Instance Quantity 11,000

Instance Quantity Uom S.F.

Installation Year 1999

Source of Installation Year Documented

No deficiencies recordedDeficiency

INTERIOR Inspected

AUDITORIUM

Instance on 1st Floor (409 Seats) Inspected

Ceiling

Instance on 1st Floor (409 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on 1st Floor (409 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed H/C Lift

Instance on 1st Floor (409 Seats) Does not exist

Fixed Seating

Instance on 1st Floor (409 Seats) Inspected

3- FairInstance Condition

DAMAGED/BROKEN/INOPERABLEDeficiency

Seats A/101, B/214, F/202, H/111, J/106 and other locationsDeficiency Location/Instance

24Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 8 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 9: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

AUDITORIUM

Fixed Seating

Deficiency Photo 1

Seat F/202

Violations No violations recorded

Floor Finish

Instance on 1st Floor (409 Seats) Inspected

2- Between Good and FairInstance Condition

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Near Stage, Near Entrance, Center AisleDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Stage

Violations No violations recorded

Sliding-folding Partition

Instance on 1st Floor (409 Seats) Does not exist

Stage

Instance on 1st Floor (409 Seats) Inspected

Stage

Instance on 1st Floor (409 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Stage Curtain Rigging

Instance on 1st Floor (409 Seats) Does not exist

Stage Curtains

Instance on 1st Floor (409 Seats) Does not exist

Walls

Instance on 1st Floor (409 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on 1st Floor (409 Seats) Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

CAFETERIA

Page 9 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 10: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

CAFETERIA

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Instance on Basement Does not exist

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

VINYL TILES:DETERIORATED SUBSTRATEDeficiency

Near Stair A, Exit, KitchenDeficiency Location/Instance

100Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Stair A

Violations No violations recorded

Sliding-folding Partition

Instance on Basement Does not exist

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

InspectedCLASSROOMS/CORRIDORS/ADMIN SPACES

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 4- Between Fair and Poor

WOOD:DETERIORATED DOORDeficiency

Room 301, 312Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

Page 10 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 11: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 301

Violations No violations recorded

METAL:DETERIORATED DOORDeficiency

Room 108Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Room 105

Deficiency Photo 2

Room 108

Violations No violations recorded

METAL:MISSING DOORDeficiency

Corridor near Room 105Deficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Corridor near Room 106

Page 11 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 12: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

CLASSROOMS/CORRIDORS/ADMIN SPACES

Door(s)

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Main Entrance Lobby, Corridor near Room 106, 212, 317, 406

and other locations

Deficiency Location/Instance

500Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Main Entrance Lobby

Violations No violations recorded

VINYL TILES:DETERIORATED SUBSTRATEDeficiency

Room 305, Corridor near Stair E/3, Corridor near Auditorium,

Corridor near Room 305

Deficiency Location/Instance

300Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Corridor near Stair E/3

Violations No violations recorded

Does not existSpecialties

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

GYMNASIUM

Instance on 4th Floor Inspected

Ceiling

Instance on 4th Floor Under construction

Door(s)

Instance on 4th Floor Inspected

3- FairInstance Condition

WOOD:DETERIORATED DOORDeficiency

EntranceDeficiency Location/Instance

Page 12 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 13: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

GYMNASIUM

Door(s)

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Entrance

Violations No violations recorded

Fixed Equipment

Instance on 4th Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on 4th Floor Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Seating

Instance on 4th Floor Does not exist

Sliding-folding Partition

Instance on 4th Floor Does not exist

Stage

Instance on 4th Floor Does not exist

Walls

Instance on 4th Floor Inspected

2- Between Good and FairInstance Condition

WALL PADDING:DETERIORATEDDeficiency

Southwest, Northeast of RoomDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Southwest of Room

Violations No violations recorded

Window Curtains/Shades/Blinds

Instance on 4th Floor Does not exist

InspectedINTERIOR DOOR HARDWARE

Page 13 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 14: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

INTERIOR DOOR HARDWARE

Condition 3- Fair

No deficiencies recordedDeficiency

InspectedINTERIOR GUARDS

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

KITCHEN

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

METAL PAN:DAMAGED/MISSINGDeficiency

Prep, Near SinkDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Prepare

Violations No violations recorded

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Does not existLIBRARY

Does not existLOCKER ROOM

MULTI-PURPOSE ROOM

Instance on Basement Inspected

Ceiling

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Door(s)

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Fixed Equipment

Page 14 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 15: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

MULTI-PURPOSE ROOM

Fixed Equipment

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Floor Finish

Instance on Basement Inspected

2- Between Good and FairInstance Condition

VINYL TILES:BROKEN/DETERIORATED/MISSING TILESDeficiency

Near ExitDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Near Exit

Violations No violations recorded

Sliding-folding Partition

Instance on Basement Does not exist

Stage

Instance on Basement Does not exist

Walls

Instance on Basement Inspected

2- Between Good and FairInstance Condition

No deficiencies recordedDeficiency

Window Curtains/Shades/Blinds

Instance on Basement Does not exist

Does not existPOOLS

SCIENCE DEMO ROOM

Instance on Room 313 Inspected

NoAlternative Use

Fixed Equipment

Instance on Room 313 Inspected

2- Between Good and FairInstance Condition

CABINETRY:MISSING/DAMAGEDDeficiency

Room 313Deficiency Location/Instance

2Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 15 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 16: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

SCIENCE DEMO ROOM

Fixed Equipment

Deficiency Photo 1

Near Room 313

Violations No violations recorded

Does not existSCIENCE LAB

Does not existSCIENCE PREP ROOM

Does not existSHOWER ROOM

InspectedSTAIRS/RAMPS: INTERIOR

Do Letter Stair Signs Exist? 1

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 3- Fair

METAL:DETERIORATED DOORDeficiency

Stair C/BasementDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/Basement

Violations No violations recorded

InspectedPartition

Condition 2- Between Good and Fair

GLASS PANEL:DAMAGED/DETERIORATEDDeficiency

Stair A/BasementDeficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Page 16 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 17: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Partition

Deficiency Photo 1

Stair A/Basement

Violations No violations recorded

METAL FRAME:DAMAGED/DETERIORATEDDeficiency

Stair A/Basement, C/4Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair A/Basement

Violations No violations recorded

METAL PANEL:DAMAGED/DETERIORATEDDeficiency

Stair C/3Deficiency Location/Instance

10Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/3

Violations No violations recorded

InspectedRailings

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStairs and Landings

Condition 2- Between Good and Fair

ROLLED ASPHALT:CRACKSDeficiency

Stair B/3, C/4, Main Entrance Vestibule, F/Basement and other

locations

Deficiency Location/Instance

Page 17 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 18: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

STAIRS/RAMPS: INTERIOR

Stairs and Landings

80Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair B/3

Violations No violations recorded

InspectedWalls

Condition 2- Between Good and Fair

PLASTER:CRACKS/SPALLINGDeficiency

Stair C/1, 4, E/1, 4Deficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair C/1

Violations No violations recorded

CERAMIC TILE:BROKEN/ MISSINGDeficiency

Stair A/Basement, B/2, E/1, 3, F/Basement and other locationsDeficiency Location/Instance

60Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Stair E/3

Violations No violations recorded

InspectedSTRUCTURAL

Page 18 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 19: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

InspectedCOLUMNS/BEAMS/BEARING WALLS

Condition 3- Fair

STEEL COLUMNS/BEAMS:DETERIORATED MASONRY

FIREPROOFING

Deficiency

Basement - Storage AreaDeficiency Location/Instance

30Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 4Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Basement- Storage Area

Violations No violations recorded

InspectedFLOOR STRUCTURE

Condition 3- Fair

CINDER CONCRETE ARCH:METAL PAN DETERIORATED,

SPALLED

Deficiency

Basement - Storage Area, Boiler RoomDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 4Urgency of Action

LEVEL 5Purpose of Action

Deficiency Photo 1

Basement - Storage Area

Violations No violations recorded

CONCRETE SLAB ON GRADE:MINOR CRACKSDeficiency

Gas Meter Room, Boiler RoomDeficiency Location/Instance

40Deficiency Quantity

Quantity Uom S.F.

Potential Action REPAIR

PRIORITY 3Urgency of Action

LEVEL 5Purpose of Action

Page 19 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 20: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

STRUCTURAL

FLOOR STRUCTURE

Deficiency Photo 1

Gas Meter Room

Violations No violations recorded

InspectedFOUNDATION WALLS

Material Type(s) Concrete

Condition 4- Between Fair and Poor

CONCRETE:WATER INFILTRATION IN ELECTRICAL

PANEL ROOM

Deficiency

Electrical Meter RoomDeficiency Location/Instance

150Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL WATERPROOFING

PRIORITY 5Urgency of Action

LEVEL 6Purpose of Action

Deficiency Photo 1

Electrical Meter Room

Violations 35213756R

InspectedROOF STRUCTURE

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existVAULTS-BUNKERS

InspectedTOILET ROOMS - STAFF

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Page 20 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 21: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

INTERIOR

InspectedTOILET ROOMS - STUDENTS

InspectedCeiling

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedDoor(s)

Condition 2- Between Good and Fair

METAL:DETERIORATED DOORDeficiency

3rd Floor BoysDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action MAINTENANCE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

InspectedFloor Finish

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedStalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

InspectedWalls

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

LIFE SAFETY Inspected

Does not existF.D. HOLDING AREA

Does not existSTEEL STAIRS

SITE Inspected

InspectedCONTAINERIZATION

Condition 4- Between Fair and Poor

CONTAINER DAMAGEDDeficiency

Parking LotDeficiency Location/Instance

1Deficiency Quantity

Quantity Uom EACH

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Parking Lot

Violations No violations recorded

CONCRETE PAD MISSINGDeficiency

Parking LotDeficiency Location/Instance

300Deficiency Quantity

Quantity Uom S.F.

Potential Action INSTALL NEW

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Violations No violations recorded

Page 21 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 22: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

SITE

InspectedDRAINAGE SYSTEM FOR ASPHALT

InspectedCatch Basins/Manhole - Surrounded by Asphalt

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Asphalt Covering

InspectedDRAINAGE SYSTEM FOR CONCRETE

InspectedCatch Basins/Manhole - Surrounded by Concrete

Condition 2- Between Good and Fair

No deficiencies recordedDeficiency

Does not existCulverts - Concrete Covering

Does not existDRAINAGE SYSTEM FOR SOIL

Does not existDRINKING FOUNTAINS

InspectedFENCES

Condition 4- Between Fair and Poor

WROUGHT IRON:DAMAGED/DETERIORATEDDeficiency

Along Prospect Avenue, East 176 StreetDeficiency Location/Instance

360Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Prospect Avenue

Violations No violations recorded

WROUGHT IRON:RUST - MAJORDeficiency

Along Prospect Avenue, East 176 StreetDeficiency Location/Instance

560Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along East 176 Street

Violations No violations recorded

CONCRETE CURB:DAMAGED/DETERIORATEDDeficiency

Along Prospect Avenue, East 176 Street, Southwest of BuildingDeficiency Location/Instance

25Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

Page 22 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 23: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

SITE

FENCES

LEVEL 2Purpose of Action

Deficiency Photo 1

Southwest of Building

Violations No violations recorded

CHAIN LINK:DAMAGED POST/RAILDeficiency

Southwest of BuildingDeficiency Location/Instance

20Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Southwest of Building

Violations No violations recorded

CHAIN LINK:DAMAGED/DETERIORATEDDeficiency

Southwest of BuildingDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Southwest of Building

Violations No violations recorded

Does not existIRRIGATION SYSTEM

InspectedPAVING

InspectedDOT Sidewalk

Does not existAsphalt

InspectedConcrete

3- FairCondition

DAMAGED CURBSDeficiency

Along Prospect Avenue, East 176 StreetDeficiency Location/Instance

Page 23 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 24: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

SITE

PAVING

DOT Sidewalk

Concrete

25Deficiency Quantity

Quantity Uom L.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Prospect Avenue

Violations No violations recorded

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along Prospect Avenue, East 176 StreetDeficiency Location/Instance

225Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along East 176 Street

Violations No violations recorded

HEAVINGDeficiency

Along East 176 StreetDeficiency Location/Instance

50Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along East 176 Street

Violations No violations recorded

Does not existPavers

InspectedSite Sidewalks & Walkways

Page 24 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)

Page 25: NYC Department of Education Building Condition ...NYC Department of Education Building Condition Assessment Survey 2018-2019 Architectural Inspection X044 InspectionId Inspection Type

NYC Department of Education

Building Condition Assessment Survey 2018-2019

X044Architectural Inspection

Question Response

SITE

PAVING

Site Sidewalks & Walkways

InaccessibleAsphalt

InspectedConcrete

2- Between Good and FairCondition

No deficiencies recordedDeficiency

Does not existPavers

InspectedStudent Non-Use

Gravel Exists? No

InspectedAsphalt

2- Between Good and FairCondition

No deficiencies recordedDeficiency

InspectedConcrete

3- FairCondition

DAMAGED/DETERIORATED/MISSING SECTIONSDeficiency

Along Prospect Avenue, East 176 StreetDeficiency Location/Instance

150Deficiency Quantity

Quantity Uom S.F.

Potential Action REPLACE

PRIORITY 3Urgency of Action

LEVEL 2Purpose of Action

Deficiency Photo 1

Along Prospect Avenue, East 176 Street

Violations No violations recorded

Does not existPavers

Does not existStudent Use

Does not existPLAYGROUNDS

Does not existPLAYING SURFACE

InaccessibleRETAINING WALLS

Does not existSEATING

Does not existSITE WALLS (NOT RETAINING WALLS)

Does not existSTAIRS/RAMPS: EXTERIOR

Page 25 of 25 Print Date: 7/3/2019Mobile Validity Version 2.0 (P)


Recommended