OMNIPOWER® direct andCT meters
Technical description
2/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Disclaimer
All information provided in this document is copyright of Kamstrup. Licence is granted to the user to freely use anddistribute the information in complete and unaltered form, provided that the purpose is to use or evaluate Kamstrupproducts. Distribution rights do not include public posting or mirroring on Internet websites. Only a link to the Kamstrupwebsite can be provided on such public websites.
Kamstrup shall in no event be liable to any party for direct, indirect, special, general, incidental, or consequential damagesarising from the use of this information or any derivative works thereof. The information is provided on an as-is basis, andthus comes with absolutely no warranty, either express or implied. No right or licence is granted under any intellectualproperty right, hereunder copyright, patent or trademark, of Kamstrup to any other party. This disclaimer includes, but isnot limited to, implied warranties of merchantability, fitness for any particular purpose, and non-infringement.
Information in this document is subject to change without notice and should not be construed as a commitment byKamstrup. While the information contained herein is believed to be accurate, Kamstrup assumes no responsibility for anyerrors and/or omissions that may appear in this document.
Copyright Information
Copyright ® Kamstrup A/SIndustrivej 28 StillingDK-8660 Skanderborg, Denmark
All Rights Reserved
The graphics and content in this document are the copyrighted work of Kamstrup and contain proprietary trademarks andtrade names of Kamstrup.
Third Parties
This document may contain links to other parties. Kamstrup makes no warranty or representation regarding any linkedinformation appearing therein. Such links do not constitute an endorsement by Kamstrup of any such information and areprovided only as a convenience. Kamstrup is not responsible for the content or links displayed by third parties.
Industrivej 28, Stilling • 8660 Skanderborg • Denmark • Tel: +45 89 93 10 00 • Fax: +45 89 93 10 01 • [email protected] • www.kamstrup.com
3/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Contents1 ...................................................................................................................... 8Revision history
2 ...................................................................................................................... 10Introduction to OMNIPOWER®
3 ...................................................................................................................... 11Technical specification
................................................................................................................ 113.1 Electrical specifications
............................................................................................................... 113.1.1 Technical data for OMNIPOWER® direct meters
............................................................................................................... 123.1.2 Technical data for OMNIPOWER® CT meters
................................................................................................................ 133.2 Mechanical specifications
................................................................................................................ 153.3 Type number overview
................................................................................................................ 163.4 Approvals
................................................................................................................ 163.5 Connection diagrams
................................................................................................................ 193.6 Terminal numbering
4 ...................................................................................................................... 21How to use OMNIPOWER®
................................................................................................................ 214.1 Installation and power-up
................................................................................................................ 214.2 Power-up/start-up sequence
................................................................................................................ 224.3 Display functions
................................................................................................................ 234.4 Push button functionalities
................................................................................................................ 244.5 Tamper
................................................................................................................ 244.6 Meter logger events
............................................................................................................... 244.6.1 Meter status logger (1.1.99.98.2.255)
................................................................................................................ 244.7 Time management
............................................................................................................... 244.7.1 Backup
............................................................................................................... 254.7.2 Hour counters
............................................................................................................... 254.7.3 Calendar and daylight-saving time plan
......................................................................................................... 254.7.3.1 Daylight saving time logger behavior
............................................................................................................... 254.7.4 RTC setting and adjustment using push button
............................................................................................................... 254.7.5 RTC adjustment logger (1.1.99.98.3.255)
................................................................................................................ 264.8 Power and energy measurements
............................................................................................................... 264.8.1 Limitations for OMNIPOWER® three-phase, three-wire (Aron) CT and
direct meters............................................................................................................... 274.8.2 Power measurements
............................................................................................................... 284.8.3 Energy registration
4/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
............................................................................................................... 304.8.4 Calculation methods of an OMNIPOWER® three-phase meter
............................................................................................................... 324.8.5 Mean power values
............................................................................................................... 334.8.6 Peak power values
............................................................................................................... 334.8.7 Energy tariff/TOU registers
......................................................................................................... 344.8.7.1 Hardware-controlled – 230 VAC input
......................................................................................................... 344.8.7.2 On-demand – system-controlled
......................................................................................................... 344.8.7.3 Internal tariff plan in the meter
................................................................................................................ 354.9 Data loggers
............................................................................................................... 354.9.1 Load profile logger (1.1.99.1.0.255)
............................................................................................................... 364.9.2 Monthly debiting logger (1.1.98.1.0.255) (2)
............................................................................................................... 384.9.3 Daily/weekly/monthly debiting logger (1.1.98.2.0.255)
............................................................................................................... 394.9.4 Daily Logger (1.1.98.128.0.255)
............................................................................................................... 414.9.5 Analysis logger (1.1.99.1.1.255)
................................................................................................................ 464.10 Meter readout
............................................................................................................... 464.10.1 Manual display readout
............................................................................................................... 474.10.2 9-digit value field
............................................................................................................... 474.10.3 Unit field
............................................................................................................... 474.10.4 Object identification field
............................................................................................................... 474.10.5 Quadrant reading
............................................................................................................... 474.10.6 Text field
............................................................................................................... 484.10.7 Module indication
............................................................................................................... 484.10.8 Error symbol
............................................................................................................... 484.10.9 Breaker symbol
............................................................................................................... 484.10.10 Tamper symbol
............................................................................................................... 484.10.11 Radio network symbol
............................................................................................................... 484.10.12 Prepayment symbol
............................................................................................................... 484.10.13 Tariff/TOU indication
............................................................................................................... 494.10.14 Mains voltage reading
............................................................................................................... 494.10.15 Phase current indication
............................................................................................................... 494.10.16 Phase sequence indication
............................................................................................................... 504.10.17 Protocols
......................................................................................................... 504.10.17.1 Kamstrup Meter Protocol (KMP)
......................................................................................................... 504.10.17.2 DLMS
......................................................................................................... 504.10.17.3 1107
5/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
............................................................................................................... 504.10.18 Local readout via optical interface – METERTOOL OMNIPOWER®
............................................................................................................... 504.10.19 Integrated OMNICON® radio mesh connectivity
............................................................................................................... 514.10.20 Integrated OMNICON® point-to-point connectivity
............................................................................................................... 514.10.21 Full encryption on all interfaces
............................................................................................................... 514.10.22 M-Bus and RS-485 connectivity
................................................................................................................ 524.11 Modularity options
............................................................................................................... 524.11.1 Primary modules
............................................................................................................... 524.11.2 CCC modules
................................................................................................................ 534.12 Disconnect functionality
............................................................................................................... 544.12.1 Disconnect function
............................................................................................................... 544.12.2 Manual disconnection and reconnection
............................................................................................................... 554.12.3 Remote disconnection from a smart metering system
............................................................................................................... 554.12.4 Smart disconnect
............................................................................................................... 554.12.5 Disconnection basis
............................................................................................................... 564.12.6 Current-controlled disconnection
............................................................................................................... 564.12.7 Power-controlled disconnection
............................................................................................................... 564.12.8 Overvoltage disconnection
............................................................................................................... 574.12.9 Delayed disconnection
............................................................................................................... 584.12.10 Reconnection
............................................................................................................... 594.12.11 Disconnection on meters with APS
............................................................................................................... 594.12.12 Event logger for disconnect/connect history (1.1.99.98.5.255)
............................................................................................................... 594.12.13 Prepayment
............................................................................................................... 594.12.14 Prepayment principle
................................................................................................................ 614.13 Power quality measurements
............................................................................................................... 614.13.1 Frequency measurements
............................................................................................................... 614.13.2 Voltage variations
......................................................................................................... 624.13.2.1 Long-term deviations
......................................................................................................... 624.13.2.2 Short-term deviations
............................................................................................................... 634.13.3 Voltage outage
............................................................................................................... 644.13.4 Configuration of voltage quality measurements
......................................................................................................... 654.13.4.1 Voltage sags and swells with a duration 100 ms – 1 second
............................................................................................................... 654.13.5 Rapid voltage change
............................................................................................................... 664.13.6 Supply voltage unbalance
............................................................................................................... 664.13.7 Total harmonic distortion (THD)
6/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
............................................................................................................... 664.13.8 Readout of the power quality measurements
......................................................................................................... 664.13.8.1 Voltage quality logger (1.1.99.98.16.255)
......................................................................................................... 684.13.8.2 Occurrence counter logger (1.1.99.98.17.255)
............................................................................................................... 694.13.9 Power factor
............................................................................................................... 694.13.10 Neutral fault detection
......................................................................................................... 724.13.10.1 Neutral fault logger (1.1.99.98.12.255)
............................................................................................................... 724.13.11 Earth fault detection
......................................................................................................... 734.13.11.1 Earth fault detction logger (1.1.99.98.19.255)
................................................................................................................ 744.14 Other smart grid functionalities
............................................................................................................... 744.14.1 Firmware upload
............................................................................................................... 744.14.2 Alarm handling/push alarms
............................................................................................................... 744.14.3 All phase power outage alarm ("last gasp")
............................................................................................................... 754.14.4 Control of external load relays
............................................................................................................... 754.14.5 Multi-utility options
............................................................................................................... 764.14.6 Miscellaneous use
............................................................................................................... 764.14.7 Pulse inputs in the module area
......................................................................................................... 774.14.7.1 Example of pulse input from a water meter
......................................................................................................... 774.14.7.2 Example of pulse input from an electricity meter
............................................................................................................... 784.14.8 Pulse outputs in module area
............................................................................................................... 784.14.9 S0 output
............................................................................................................... 794.14.10 Auxiliary power supply (APS)
5 ...................................................................................................................... 81Ordering specification
................................................................................................................ 815.1 Meter configuration
................................................................................................................ 815.2 Hardware configuration
................................................................................................................ 845.3 Software configuration
................................................................................................................ 905.4 Display configuration
................................................................................................................ 985.5 Tariff control configuration
................................................................................................................ 985.6 Load control configuration
................................................................................................................ 985.7 Smart disconnect setup
................................................................................................................ 985.8 Sealable push button configuration
................................................................................................................ 995.9 1107 protocol configuration
................................................................................................................ 995.10 Customer labels
................................................................................................................ 1005.11 Sealing
................................................................................................................ 1015.12 Packing
7/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
............................................................................................................... 1025.12.1 Box solution
............................................................................................................... 1025.12.2 Pallet solution
................................................................................................................ 1035.13 Accessories
8/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
1 Revision history______________________________________________________________
Rev. Description Meter software revision
A1 First release of this technical description for OMNIPOWER®
direct meters. Does not include OMNIPOWER® CT meters.
OMNIPOWER® direct meters:
· SW no.: 5098736, rev. B1 > P1
A2 Update of the power quality measurements section. OMNIPOWER® direct meters:
· SW no.: 5098736, rev. B1 > P1
A3 Includes OMNIPOWER® ST variant (symmetric terminals)
meters.
OMNIPOWER® direct meter:
· SW no.: 5098736, rev. P1 > P1
B1 Includes OMNIPOWER® CT meters. OMNIPOWER® direct meters:
· SW no.: 5098736, rev. Q1
OMNIPOWER® CT meters:
· SW no.: 50981040, rev. Q1
C1 Includes new overvoltage disconnect functionality. OMNIPOWER® direct meters:
· SW no.: 5098736, rev. R1, S1, T1,
U1
OMNIPOWER® CT meters:
· SW no.: 0981040, rev. R1, S1, T1,
U1
D1 Includes new OMNIPOWER® variant with last gasp and
encryption.
OMNIPOWER® direct meters:
· SW no.: 5098736, rev. R1, S1, T1,
U1
· SW no.: 50981173 rev. D1, E1 (No
DLMS)
· SW no.: 0981165 rev. D1 (No
DLMS)
OMNIPOWER® CT meters:
· SW no.: 50981040, rev. R1, S1, T1,
U1
E1 Updates:
· New registers for analysis logger.
· New register for voltage quality (VQ1) logger.
· Introduction of daily logger (only for 50981173, 50981165).
OMNIPOWER® direct meters:
SW no.: 5098736, No updates
SW no.: 50981173 rev. F1, G1, K1
SW no.: 50981165 rev. F1, L1
OMNIPOWER® CT meters:
SW no.: 50981040, rev. R1, S1, T1,
U1
F1 Updates:
· OMNIPOWER® three-phase DIN rail meter.
· Interpretation of voltages for three-phase, three-wire meters
(Aron).
· Description of earth fault detection and earth fault logger.
· Limitations for Aron meters according to current and power
values.
OMNIPOWER® direct meters:
SW no.: 5098736, No updates
SW no.: 50981173 rev. > AB1
SW no.: 50981165 rev. > AB1
OMNIPOWER® CT meters:
SW no.: 50981040, rev. > S1
9/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Rev. Description Meter software revision
G1 Updates:
· Detailed description of earth fault detection and event
logging.
· Description of 8-channel load profile logging.
OMNIPOWER® direct meters:
SW no.: 5098736, rev. > X2
SW no.: 50981173 rev. > AE6
SW no.: 50981165 rev. > AE6
OMNIPOWER® CT meters:
SW no.: 50981040, rev. > X2
SW no.: 50981251, rev. > V6
H1 Updates:
· Added "Use dayligt saving time as midnight logger trigger "section.
· Updated "Monthly debiting logger " section with newlysupported registers.
· Updated "Daily logger " section with newly supportedregisters.
· Updated "Daily/weekly/monthly debiting logger " sectionwith newly supported registers.
· Added description of behavior for maximum/minimumregisters and associated RTC values for Monthly debitinglogger , Daily logger and Analysis logger .
OMNIPOWER® direct meters:
SW no.: 50981173 rev. AF1
SW no.: 50981165 rev. AF1
OMNIPOWER® CT meters:
SW no.: 50981251, rev. W1
25
36
39
38
36 39 41
10/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
2 Introduction to OMNIPOWER®______________________________________________________________OMNIPOWER® is a smart electricity meter prepared for the future demands required by smart grid
implementations. It provides a detailed insight into consumption patterns at the low-voltage part of
the power grid. It is also a grid sensor for collection of relevant power quality information.
OMNIPOWER® offers a list of features, for example:
· Optimized functionalities for smart metering systems
· Communication for smart home applications
· Security against tampering
· Ultra-low power consumption
· Remote firmware update (approved according to WELMEC 7.2).
From the factory, the meter can be configured to measure both imported and exported energy. The
measurements are saved in a permanent memory. As default, OMNIPOWER® can generate load
profiles in all four quadrants. A load profile provides detailed information about consumed and
produced energy. An additional logger with 16 channels contains data for analysis purposes.
Part of OMNIA® OMNIPOWER® with integrated OMNICON® radio communication is an essential part of the
OMNIA® all-comprising smart grid platform shown in the figure below. OMNIA® offers a full line of
smart technology, support and knowledge.
OMNIA® overview
As part of OMNIA®, OMNIPOWER® can be used as the gateway for collecting other consumption
types such as water, gas, heating and cooling. It is also prepared for Home Area Network (HAN)
communication via a Consumer Communication Channel (CCC) module which can be inserted on
the meter front by the consumer.
11/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
3 Technical specification______________________________________________________________This chapter describes the technical specifications for OMNIPOWER®.
OMNIPOWER® provides a range of technical and mechanical features with high performance and
reliability. The following technical specifications are both valid for OMNIPOWER® direct and CT
meters.
3.1 Electrical specifications
OMNIPOWER® is constructed with independent and galvanically separated measuring systems
(the number of measuring systems depends on the meter type). This ensures a correct
measurement irrespective of how many and which measurement systems are used.
A switch mode supply feeds the measuring circuits and main processor with voltage. Furthermore,
the switch mode supply functions as an excellent transient protection (in combination with varistors
and power resistors).
The use of shunt and switch mode supply also ensures that OMNIPOWER® direct meters are
immune to magnetic influence. Measured and calculated data is safely stored in an integrated non-
volatile memory (EEPROM).
Technical data
Nominal frequency, fn 50 or 60 Hz ± 5 %
Phase displacement Unlimited
Data storage EEPROM; > 10 years without voltage.
Display LCD, 7 mm digit height (value field).
LCD, 5 mm digit height (identification readings).
LCD, 3 mm digit height (voltage readings).
Real-time clock (RTC) accuracy Typically 5 ppm at 23°C.
Backup battery lifetime > 10 years at normal operation.
Supercap lifetime > 10 years at normal operation.
Supercap backup time 5 days at fully charged.
3.1.1 Technical data for OMNIPOWER® direct meters
Technical data
Measuring principle:
Current:
Voltage:
One-phase current measurement via current shunt.
One-phase voltage measurement via voltage divider.
Nominal voltage, Un 3x230 VAC -20 % - +15 % (for Aron meter only)
1x230 VAC -20 % - +15 %
2x230/400 VAC -20 % - +15 %
3x230/400 VAC -20 % - +15 %
12/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Technical data
Current, Itr - Ib (Imax) OMNIPOWER® three-phase and single-phase meter
Without breaker With breaker
0.25-5(60)A 0.25-5(60)A
0.25-5(80)A 0.25-5(80)A
0.25-5(100)A 0.25-5(100)A
Accuracy class,
Active energy
Reactive energy
MID: Class A, Class B
IEC: Class 2, Class 1
IEC: Class 3, Class 2
Own consumption (per phase)* OMNIPOWER® three-phase Without breaker With breaker
Current circuit 0.01 VA 0.01 VA
Voltage circuit 0.4 VA
0.1 W
0.4 VA
0.1 W
OMNIPOWER® single-phase Without breaker With breaker
Current circuit 0.01 VA 0.01 VA
Voltage circuit 0.6 VA
0.2 W
0.6 VA
0.2 W
Meter constant 1000 imp/kWh
S0 pulse diode 1000 imp/kWh, kvarh
Pulse time 30 ms ± 10 %
S0 pulse output
(Not on DIN rail meter)
1000 imp/kWh
Pulse time 30 ms ± 10 %
* Measured on phase L1 according to MID type approval
3.1.2 Technical data for OMNIPOWER® CT meters
Technical data
Measuring principle:
Current:
Voltage:
One-phase current measurement via current transformers.
One-phase voltage measurement via voltage divider.
Nominal voltage, Un 3x230 VAC -20 % - +15 % (for Aron meter only)
3x230/400 VAC -20 % - +15 %
Current, Imin - In (Imax) OMNIPOWER® CT meter
0.01-1(6)A
0.05-5(6)A
Accuracy class,
Active energy
Reactive energy
MID: Class B, Class C
IEC: Class 1, Class 0.5
IEC: Class 2
Own consumption (per phase)* OMNIPOWER® CT meter
Current circuit 0.02 VA
13/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Technical data
Voltage circuit 0.2 VA
0.1 W
Meter constant 10000 imp/kWh
S0 pulse diode 10000 imp/kWh, kvarh
Pulse time 30 ms ± 10 %
S0 pulse output 5000 imp/kWh
Pulse time 30 ms ± 10 %
* Measured on phase L1 according to MID type approval
3.2 Mechanical specifications
OMNIPOWER® is designed as a two-piece plastic construction, consisting of housing and meter
cover, both made of fire resistant plastic. The housing is constructed in such a way that it protects
the metrological functions. It is not possible to open the housing without breaking the metrological
seal.
Technical data
Operating temperature -40°C - +70°C
-40°C - +55°C (DIN rail meter)
Storage temperature -40 °C - +85 °C
Protection class IP54
IP 51 DIN rail meter
Protection class II
Relative humidity < 75 % year’s average at 21 °C
< 95 % less than 30 days/year at 25 °C
Weight OMNIPOWER® Without breaker With breaker
Single-phase meter 550g 700g
Single-phase meter (ST) 550g 700g
Three-phase meter 900g 1100g
Three-phase DIN rail 1000g
CT meter 900g NA
Application area Indoor or outdoor in suitable meter cabinet
Materials Glass reinforced polycarbonate
DimensionsThe dimensions of OMNIPOWER® can be seen in the figures below.
14/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OMNIPOWER® CT and three-phase meter
Dimensional sketch of OMNIPOWER® CT and three-phase meter with/without breaker
OMNIPOWER® single-phase OMNIPOWER® single-phase ST-meter
Dimensional sketch of OMNIPOWER® single-phase meter with/without breaker
The meter cover can be ordered with different lengths. A short version allows pre-mounted
terminal pins or wires to be mounted, while the longer version covers the terminal inputs and
outputs.
15/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OMNIPOWER® three-phase DIN rail
Dimensional sketch of OMNIPOWER® three-phase DIN rail meter with breaker
3.3 Type number overview
OMNIPOWER® is available with a range of optional hardware features depending on the
application for which it is used. The meter can, for example, be delivered with an internal
disconnect function for disconnection and connection of the consumer’s supply, configured for the
measurement of energy in all four quadrants, with integrated radio transceiver and auxiliary power
supply (APS). The choice between these options defines the meter type number.
The OMNIPOWER® type numbers consist of 18 characters that describe the configuration of the
meter regarding hardware and mechanical options. The type numbers for the different
OMNIPOWER® meters have the following structure:
OMNIPOWER® meter Type Type number
OMNIPOWER® three-phase
meter
Three-phase, four-wire meter 684-1X-3XX-NxX-XXXX-XXX.
OMNIPOWER® three-phase
meter
Three-phase, three-wire meter
(Aron)
684-1X-2XX-NxX-XXXX-XXX.
OMNIPOWER® three-phase
DIN rail meter
Three-phase, four-wire meter 684-14-39X-NxX-XXXX-XXX.
OMNIPOWER® single-phase
meter
Single-phase, two-wire meter 686-1X-1XX-NxX-XXXX-XXX.
OMNIPOWER® CT meter Three-phase, four-wire meter 685-11-3XX-DxX-0X11-XXX.
OMNIPOWER® CT meter Three-phase, three-wire meter
(Aron)
685-11-2XX-DxX-0X11-XXX.
For the complete configuration of the OMNIPOWER® type number, please see "Ordering
specification ". 81
16/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
3.4 Approvals
OMNIPOWER® is type approved according to the Measuring Instruments Directive (MID) for active
positive energy and according to the national requirements for other energy types, where required.
Type approval Norm
Active energy EN 50470-1
EN 50470-3
Reactive energy and active energy IEC 62052-11
IEC 62053-21
IEC 62053-22
IEC 62053-23
Various Norm
Terminal DIN 43857
BS 7856
S0 pulse output DIN 43864
(DIN rail meter does not have S0)
Optical reading EN 62056-21 mode C
OBIS codes IEC 62056-61
Breaker EN 62055-31, Annex C
3.5 Connection diagrams
The valid connection diagram appears from the type label on the front of the meter and can be
seen below.
OMNIPOWER® three-phase, four-wire (S0)
17/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OMNIPOWER® three-phase, four-wire (APS version)
OMNIPOWER® three-phase, three-wire (Aron)
OMNIPOWER® three-phase DIN rail meter, four-wire
18/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OMNIPOWER® single-phase, two-wire
OMNIPOWER® single-phase, two-wire – symmetric terminals – ST-meter
OMNIPOWER® CT three-phase, four-wire
19/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OMNIPOWER® CT three-phase, three-wire (Aron)
Connect the meter in accordance with the installation diagram on the type label of the meter.
3.6 Terminal numbering
Terminal numbering for OMNIPOWER® three-phase meter with S0 or APS
Terminal numbering for OMNIPOWER® three-phase meter with S0
20/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Terminal numbering for OMNIPOWER® single-phase meter with S0
Terminal numbering for OMNIPOWER® single-phase ST-meter with S0
Terminal numbering for OMNIPOWER® CT-meter
Terminal numbering for OMNIPOWER® three-phase DIN rail meter
21/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4 How to use OMNIPOWER®______________________________________________________________This chapter describes the use of OMNIPOWER® in details, the features implemented and the
benefits which the meter provides to the users.
4.1 Installation and power-up
It is essential that OMNIPOWER® is installed and connected as described in the installation
guides
For the connection diagrams of the specific meter types, please see the previous sections.
4.2 Power-up/start-up sequence
The display power-up sequence is shown below.
In the first five seconds after powering OMNIPOWER®, the ROM checksum is displayed with its
corresponding OBIS code.
In the next five seconds, the software type number and revision number of the meter is shown. The
value field describes the software number while the software revision is shown in the text field in
the upper right corner of the display.
The phase indicators L1, L2 and L3 show whether voltage is applied to each phase. The arrows
indicate any direction of the power flow for each phase. The phase sequence is also indicated. The
sequence is defined in the table below.
22/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Symbol Phase sequence
L1-L2-L3
L1-L3-L2
After additional 5 seconds, the meter starts operational mode and begins displaying its automatic
display list.
If the meter is part of OMNIA® Suite, the integrated radio module starts searching for a network.
This is indicated by a flashing antenna symbol. When a network is located, and the meter is in
contact and recognized by a concentrator, the antenna symbol will be constantly “On”.
It is possible to delay the start-up of the integrated radio for 5 minutes, if the left push button is
pushed for approximately 5 seconds immediately after power is applied to the meter. The RF
symbol will turn off to indicate that the start-up is delayed.
The radio will automatically start searching for a radio network when the 5 minutes are passed, or
immediately after a re-power of the meter.
4.3 Display functions
OMNIPOWER® provides the possibility of up to four display lists to which a number of meter
values/parameters can be attached. The table below gives an overview of the available display
lists.
Display view Description Shifting Maximum
values
Automatic display list A list of registers that is shown automatically
in the display.
Automatically
10 seconds
(fixed)
16
Manual consumer display listA list of registers that can be seen by pushing
the left push button on the meter front.
Manually
via left push
button
30
Manual utility display list As manual consumer display list, but this list
can only be seen by pushing the sealable push
button.
Manually
via right push
button
16
Supply backup display list In case the meter is disconnected from the
main supply, this display list still allows the
user to read out a number of meter values. The
display is only activated by pushing the left
push button.
Manually
via left push
button
8
Available display lists in OMNIPOWER®
Each list can be customized at ordering, and can also be reconfigured after installation. OMNIA®
also provides the possibility to update the display lists remotely.
23/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.4 Push button functionalities
Two push buttons are available on the front of OMNIPOWER® as shown in the figure below.
OMNIPOWER® push buttons
The left push button is used for manual display scrolling and manual connect/disconnect of internal
breakers if the meter is configured for this.
The right push button is sealable, and the following functionalities can be enabled via configuration:
· Set time and date
· Adjust time
· Execute debiting stop
· Disable/enable optical port
· Change meter number
· Set tariff plan and load control plan
· Test load control relays.Each function can be enabled independently in the setup. Configuration of the sealable push buttonmust be done at the time of ordering the meter.
The right push button can only be activated when the slot is in a vertical position. The button can be
locked by turning it 90° to horizontal position; in this position a sealing can be mounted to lock the
push button.
Release of sealable push button
24/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.5 Tamper
OMNIPOWER® has registration of magnetic field detection and meter cover tampering. Any
registration can be accompanied by indication in the display. This indication can be configurable to
be temporary (i.e. it disappears when the source to tamper disappears), or permanently until a
tamper release command is received either from a smart metering system or by activating the
sealable push button.
With OMNIPOWER® meters implemented in OMNIA®, it is also possible to receive tamper
registrations as push alarms to the meter data management (MDM) system.
4.6 Meter logger events
The following sections describe the complete lists of events that are detected in the
OMNIPOWER® meter, and in which loggers the different events are registered.
4.6.1 Meter status logger (1.1.99.98.2.255)
OMNIPOWER® has a status logger which contains information about the status events of the
meter. A registration in the logger can be triggered by the following events:
· EEPROM access failure
· ROM checksum fail
· Tamper detection
· Magnetic field detection
· Meter reset
The meter status logger is circular and will therefore contain the 200 newest meter status events.
4.7 Time management
OMNIPOWER® has an integrated real-time clock (RTC) to provide measured data with an
accurate time stamp (typically 5 ppm at 23 °C). The RTC is used to generate time stamps on load
profile values and event registrations and to keep any tariff and load control plans on track.
4.7.1 Backup
In case of power supply outage, the RTC function is supplied by either a battery or rechargeable
backup unit (supercap). The backup time depends on the period of time that the meter is without
mains supply. In addition, the backup gives access to further functions such as display views
despite the lack of mains supply.
The lifetime of the backup unit also depends on the mains voltage supply to the meter and the
ambient temperature.
25/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.7.2 Hour counters
As the RTC manages the date and time in the meter, an hour counter register manages the
number of operating hours of the meter, i.e. the number of hours where main voltage are supplied
to the meter.
As a supplement to the total hour counter, the meter also contains separate counters for all eight
tariffs available in the meter.
4.7.3 Calendar and daylight-saving time plan
It is possible to set up a calendar plan useable for tariff and load control. The calendar plan can
contain up to four different seasons, and each season can have different weekly plans. For details
about how a weekly plan is divided into working days, non-working days and holidays, please see
“Internal tariff plan in the meter ”.
In addition to the “regular” calendar plan, a list of exceptions days can be added to the calendar.
The list can contain up to 200 days 20 years ahead in time. Exceptions days will have the same
tariff plan as holidays.
Finally, OMNIPOWER® also has an option for a daylight saving time plan which can be
programmed in the meter with corresponding configuration of start and end dates for up to 20
years ahead in time. However, all time stamps in data loggers and event loggers are done in
normal time and does not take any daylight light saving time into account.
4.7.3.1 Daylight saving time logger behavior
The OMNIPOWER® RTC can be configured to follow a defined daylight saving time plan, if the
daylight saving time register (1.1.96.52.11.255) is enabled. Enabling of a daylight saving time plan
will not change the behavior of any logger, i.e. midnight loggers will continue to do log entries at
00:00 normal time all year. If, however, the register
"UseDstAsDailyLoggerTrigger" (1.1.96.52.12.255) is also enabled (i.e. set to "1"), midnight loggers
will change behavior and do log entries at 23:00 normal time (00:00 local time) in the defined
daylight saving period.
Note Time stamps in data loggers are always in normal time.
4.7.4 RTC setting and adjustment using push button
It is possible to configure OMNIPOWER® to enable RTC setting/adjustment using the right push
button.
4.7.5 RTC adjustment logger (1.1.99.98.3.255)
The time is adjustable via the configuration program METERTOOL OMNIPOWER® or via a smart
metering system like OMNIA®. Changes are registered in a dedicated RTC adjustment logger, and
34
26/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
if needed, the registration can be filtered to avoid insignificant adjustments, e.g. less than 7
seconds, to fill the log.
4.8 Power and energy measurements
Energy consumption is calculated as an expression of the phase current, the phase voltage and
time. The energy registration per measuring system is communicated to the legal processor of the
meter via the internal bus system of the meter; and is accumulated in the main registers of the
meter.
4.8.1 Limitations for OMNIPOWER® three-phase, three-wire (Aron) CT and direct meters
In "Power and energy measurements " and "Data loggers ", the information is valid for all
meter types and variants, with a few exceptions for OMNIPOWER® three-phase three-wire (Aron)
CT and direct meters.
The CT meter type only has two available measuring systems as shown in "Connection
diagrams ". Therefore, it does not measure the current in phase L2 and the value will always be
“0” in case this register is read out or used in any data logger. Instead, the current in L2 is
measured either by the system in L1 or the system in L3. The same counts for power registers (P,
Q and S). The total power consumption is split accordingly to the two measuring systems in L1
and L3, respectively.
The direct meter type also has two measuring systems for energy registration. However, due to
the implementation of earth fault detection, the current in L2 is measured and the value is available
for readout or in the data loggers. The power registration is, like for CT meters, measured by the
systems in L1 and L3 and the phase values for P, Q and S, and is therefore ”0” for L2.
26 35
16
27/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.8.2 Power measurements
OMNIPOWER® is constructed as a four-quadrant meter, which means active, reactive and
apparent power and energy measurements in the flow directions shown in the figure below.
Energy and power measurement in four quadrants
All power values in OMNIPOWER® are measured in kW (P), kvar (Q) and KVA (S), and are
available for readout or in data loggers with three decimals.
The available power registers in OMNIPOWER® are listed in the table below with the
corresponding OBIS codes according to EN 62056-61.
28/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Designation Quadrant
illustration
Description Unit Display
OBIS code
P+
P14
The active positive power consists of active power from
quadrants 1 and 4.
kW 1.7.0
P-
P23
The active negative power consists of active power from
quadrants 2 and 3.
kW 2.7.0
Q+
Q12
The reactive positive power consists of positive inductive
power from quadrant 1 and positive capacitive power from
quadrant 2.
kvar 3.7.0
Q-
Q34
The reactive negative power consists of negative inductive
power from quadrant 3 and negative capacitive power from
quadrant 4.
kvar 4.7.0
S+
S14
The positive apparent power from quadrant 1 and 4. kVA 9.7.0
S-
S23
The negative apparent power from quadrant 2 and 3. kVA 10.7.0
Main power registers in OMNIPOWER®
All the values in the table are instantaneous values with an update frequency of 1 Hz. In addition to
these instantaneous power registers, OMNIPOWER® also contains a range of derived power
registers, e.g. mean values and peak values. These different values are described in "Mean power
values " and "Peak power values ".
4.8.3 Energy registration
OMNIPOWER® is available as an import/export meter for active, reactive and apparent energy.
The possible energy registers are described in the table below with the corresponding OBIS code
according to EN 62056-61.
Designatio
n
Quadrant
illustration
Description Unit Display
OBIS code*
A+
A14
The active positive energy consists of active energy
from quadrants 1 and 4.
kWh 1.8.0
1.8.x (tariff)
A-
A23
The active negative energy consists of active energy
from quadrants 2 and 3.
kWh 2.8.0
2.8.x (tariff)
R+
R12
The reactive positive energy consists of positive
inductive energy from quadrant 1 and positive
capacitive energy from quadrant 2.
kvarh 3.8.0
3.8.x (tariff)
R-
R34
The reactive negative energy consists of negative
inductive energy from quadrant 3 and negative
capacitive energy from quadrant 4.
kvarh 4.8.0
4.8.x (tariff)
R1
R+i
The positive inductive energy from quadrant 1. kvarh 5.8.0
32 33
29/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Designatio
n
Quadrant
illustration
Description Unit Display
OBIS code*
R2
R+c
The positive capacitive energy from quadrant 2. kvarh 6.8.0
R3
R-i
The negative inductive energy from quadrant 3. kvarh 7.8.0
R4
R-c
The negative capacitive energy from quadrant 4. kvarh 8.8.0
E+
E14
The positive apparent energy from quadrant 1 and 4. kVAh 9.8.0
9.8.x (tariff)
E-
E23
The negative apparent energy from quadrant 2 and 3. kVAh 10.8.0
10.8.x (tariff)
* The x indicates the corresponding tarif f for the energy type.
Main energy registers in OMNIPOWER®
Some of the energy registers in the table are used as the legal energy registration in
OMNIPOWER®. Configuration of the meter decides which energy registers to be legal.
The legal energy registers are automatically used as values for the load profile data logger, which
is described in detail in “Load profile logger ".
In addition to energy registers, a number of deviated energy registers are also available in the
meter. These are listed in the table below.
For OMNIPOWER® CT meters, the registers 1.8.x, 2.8.x, 3.8.x, 4.8.x, 5.8.0 and 8.8.0 are available
as both secondary and primary values. The secondary values can be configured for use in display
and load profile logger.
Designation Description Unit Display
OBIS code
A1234 A register that sums the active positive and negative energy
numerically. Can be used as a control register for a one-way (A+)
meter.
kWh 1.15.8
A+ trip A resettable trip counter that accumulates total active positive energy
and resets via left push button (6 sec).
kWh 1.1.128
A- trip A resettable trip counter that accumulates total active positive energy
and resets via left push button (6 sec).
kWh 2.1.128
R+ trip A resettable trip counter that accumulates total active positive energy
and resets via left push button (6 sec).
kvarh 3.1.128
R- trip A resettable trip counter that accumulates total active positive energy
and resets via left push button (6 sec).
kvarh 4.1.128
E+ trip A resettable trip counter that accumulates total apparent positive
energy and resets via left push button (6 sec).
kVAh 9.1.128
35
30/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Designation Description Unit Display
OBIS code
E- trip A resettable trip counter that accumulates total apparent negative
energy and resets via left push button (6 sec).
kVAh 10.1.128
A-net
= |A+|-|A-|
A net calculation register that counts backwards if |A-| > |A+|. The
register is useable as informative register in the display, for
installations with microgeneration, e.g. solar cells. The register is not
available as a legal register in the load profile logger.
kWh 1.16.8
A*prepayment A prepayment register that counts down the kWh value which is
preset in the register. Used to disconnect the internal breaker when it
reaches zero.
kWh 0.130.0
A*prepayment,c
redit
Used as a credit register in case the exception time is active in the
prepayment functionality. Can only be reset by adding kWhs to the
meter.
kWh 0.130.1
* The register is not available in OMNIPOWER® CT meters.
Additional energy registers in OMNIPOWER®
The resolution by which all the energy readings are shown in the display can be set to the
following:
Display resolution Single-phase and
three-phase meters
CT meters
6.1 (000000.0) kWh/kvarh ü -
6.3 (000000.000) kWh/kvarh ü -
7.0 (0000000) kWh/kvarh ü ü
7.1 (0000000.0) kWh/kvarh - ü
7.2 (0000000.00) kWh/kvarh ü ü
Resolution for energy registers in OMNIPOWER®
Furthermore, it is possible to select or deselect leading zeroes. The configuration of the display
resolution and leading zeros are done when ordering the meter and cannot be reconfigured
afterwards due to legal requirements.
All secondary energy registers in OMNIPOWER® CT are shown with the display relosution 5.2
(00000.00) kWh/kvarh.
4.8.4 Calculation methods of an OMNIPOWER® three-phase meter
OMNIPOWER® provides three methods for calculating the energy in three-phase meters. Three
similar meters can therefore obtain different results for energy measurement depending on the
configuration of the calculation method.
31/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Two examples of energy consumption in a three-phase meter
If energy is imported on phases L1 and L2 (shown as red), and energy is exported on phase L3
(shown as blue) as shown to the left in the figure above, the calculation can be made according to
the methods described below.
The table below describes the different calculation methods of the total energy dependent on the
applied calculation method.
Calculation
method
Three-phase examples Description
Phase energy
consumption
Total energy
registration
Individual
import/export
The individual import/export calculation
method has one register for the positive
contributions and one for the negative
contributions.
Vector
summation
When using the vector summation
calculation, the positive contributions are
added and the negative contributions are
subtracted in the same way as by
electromechanical meters. Contributions
from e.g. solar energy installations will be
set off in the total energy calculation. This
calculation method is sensitive to incorrect
installation and manipulation.
Total
summation
The total summation calculation adds all
contributions to the positive register whether
one or more phases contributes with
negative energy.
32/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Calculation methods in OMNIPOWER®
The calculation method for the two reactive energy types R+ (R12) and R- (R34) follows the same
principles as described in the table above for A+ and A-.
For the four reactive energy types R1, R2, R3 and R4, which can also be part of the load profile
logger, the calculation method is always based on the individual measuring principles independent
of the ordered calculation method for the four main energy types A+, A-, R+ and R-.
Therefore, if the meter is ordered with vector summation as calculation method, situations may still
occur where the meter, for example, records energy in both R1 and R4, but at the same time only
records energy in R12 and not in R34.
Important The configuration of the energy calculation method must be done when ordering the
meter and cannot be reconfigured afterwards.
Note For three-phase, three-wire meters (Aron), both direct and indirect meters, vector
summation must always be used, due to the physical design of the meters with only two
measuring systems, see "Connection diagrams ".
4.8.5 Mean power values
In the table "Main power registers in OMNIPOWER® ", the instantaneous values for the different
power registers in OMNIPOWER® are listed. Some of these values are also available as mean
values. The values are either averaged during the corresponding integration time for the load profile
or during the configurable log interval for the analysis logger.
Designation Description Unit Display
OBIS code
P+mean The mean value of the positive active power during the legal integration
period.
kW 1.25.0
P-mean The mean value of the negative active power during the legal integration
period.
kW 2.25.0
Q+mean The mean value of the positive reactive power during the legal integration
period.
kvar 3.25.0
Q-mean The mean value of the negative reactive power during the legal integration
period.
kvar 4.25.0
S+mean The mean value of the positive apparent power during the legal integration
period.
kVA 9.25.0
S-mean The mean value of the negative apparent power during the legal integration
period.
kVA 10.25.0
Mean power values in OMNIPOWER®
16
27
33/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
The above mean values are also available for each phase L1-3.
4.8.6 Peak power values
OMNIPOWER® also registers the peak value for the power measurements. The measuring period
of the peak calculation follows the load profile integration period. For every integration period, the
mean power is calculated and then compared to the present peak value. If the new value exceeds
the present value, it replaces the present value.
Designation Description Unit Display
OBIS code
P+max The active positive power consists of active power from quadrants 1 and 4. kW 1.6.0
1.6.x (tariff)
P-max The active negative power consists of active power from quadrants 2 and 3
(incl. Tariff 1 & 2).
kW 2.6.0
2.6.1
2.6.2
Q+max The reactive positive power consists of positive inductive power from
quadrant 1 and positive capacitive power from quadrant 2.
kvar 3.6.0
3.6.x (tariff)
Q-max The reactive negative power consists of negative inductive power from
quadrant 3 and negative capacitive power from quadrant 4 (incl. Tariff 1 &
2).
kvar 4.6.0
4.6.1
4.6.2
S+max The positive apparent power from quadrants 1 and 4. kVA 9.6.0
9.6.x (tariff)
S-max The negative apparent power from quadrants 2 and 3 kVA 10.6.0
Peak power values in OMNIPOWER®
The peak power values are reset at every debiting stop executed in the meter. For further
information about debiting stop and the debiting logger, please see “Monthly debiting logger”.
4.8.7 Energy tariff/TOU registers
For each main energy register; A+, A-, R+, R-, E+ and E-, OMNIPOWER® contains up to eight
deviated tariff registers. The use of tariff registers enables the possibility for time segmentation of
the total energy consumption. This is relevant when electricity is price differentiated according to
the time of use during a day, week or season. Which tariff that is to be active, can be controlled in
different ways:
· by hardware using a 230 VAC input signal
· by an on-demand remote command sent from a smart metering system
· by an internal tariff plan configuration in the meter
These options are described in the following sections.
34
34
34
34/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.8.7.1 Hardware-controlled – 230 VAC input
The available Kamstrup modules for OMNIPOWER® includes a 230 VAC input that provides a 2-
tariff or 4-tariff control option. The modules are:
· Tariff stand-alone (4-tariff)
· M-Bus module (2-tariff)
· RS485 module (2-tariff)
Tariff control by use of modules use the I/O ports of the module connector for changing the tariffs,
e.g. if a tariff control module prepared for 230 VAC is connected to 230 VAC. The inverted function
can also be selected. The control table is shown in this table:
Port 1:
Terminals 13 and 15
Port 2:
Terminals 33 and 15
Active tariff Active tariff
inverted
0 VAC 0 VAC T1 T4
230VAC 0 VAC T2 T3
0 VAC 230VAC T3 T2
230VAC 230VAC T4 T1
Tariff control table
Whether or not the active tariff is inverted, it is configured as part of the meter order form (Software
configuration , parameter Z3).
4.8.7.2 On-demand – system-controlled
With OMNIPOWER® is connected to a smart metering system, the actual tariff can be set by a
single remote command.
4.8.7.3 Internal tariff plan in the meter
OMNIPOWER® can contain up to three different tariff plans which can be selected on-site via the
sealable push button or remotely, e.g. via OMNIA®.
Each tariff plan can have one, two, three or four different season plans available. In one year, the
meter can shift up to eight times between the available season plans. Each season plan consists
of one, two or three types of days:
· Working days
· Non-working days
· Holidays.
A daily tariff plan can be made individually for each of the three different types of days. The tariff
plan setup is illustrated below:
84
35/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Tariff plan setup for OMNIPOWER®
A daily tariff plan in the meter can contain up to 10 tariff shifts per day. The resolution of the shifting
is 1 minute.
4.9 Data loggers
OMNIPOWER® has a number of different data loggers:
· Load profile logger (15 minutes, half-hourly or hourly energy logger)
· Monthly debiting logger
· Daily, weekly or monthly debiting logger
· Daily logger
· Analysis logger
The loggers are different regarding the number of registers to be logged, the time interval between
the logs and the configuration possibilities. Each logger is described in the following sections.
Note All time stamps in data loggers are done in normal time and do not take any daylight light
saving time into account.
4.9.1 Load profile logger (1.1.99.1.0.255)
The load profile logger is based on energy readings, where the types of energy to be logged are
based on the meter configuration selected when ordering the meter. The load profile in
OMNIPOWER® is implemented according to the WELMEC software guide 11.2.
The integration period of the meter is changeable and can be set to 15, 30 or 60 minutes. The
period can be reconfigured after installation.
35
38
38
41
36/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Depending on the chosen integration period and the number of energy types to be measured,
OMNIPOWER® contains a number of log entries which are converted to a number of days and
listed in the table below.
For OMNIPOWER® CT meters, the meter can be ordered to register either secondary or primary
values in the load profile logger.
Important This cannot be reconfigured afterwards.
Integration period
Energy type
15 min.
[Days]
30 min.
[Days]
60 min.
[Days]
A+ 275 550 1100
A+/A- 231 462 924
A+/R+ 231 462 924
A+/R1 231 462 924
A+/A-/R+/R- 175 350 700
A+/A-/R+/R- (hardware variant 2 meters) 180 360 720
A+/A-/R+/R-/R1/R2/R3/R4 122 244 488
Logging depth of load profile logger
Each log entry is also marked with a status marking, which is also implemented according to
WELMEC 11.2. It contains information regarding the quality of each specific log entry, e.g. any
voltage outage, overvoltages and undervoltages and any RTC adjustments executed during the
integration period.
For OMNIPOWER® direct meters, all energy registrations are made in kWh with two or three
decimals.
For OMNIPOWER® CT meters, it is possible to configure the load profile to register energy based
on either primary or secondary energy with reference to the current transformers. If primary energy
is chosen, the resolution is with two decimals, if secondary energy is chosen, the resolution is with
four decimals.
4.9.2 Monthly debiting logger (1.1.98.1.0.255) (2)
OMNIPOWER® has a debiting logger where the instantaneous values of a number of registers are
logged every time a debiting stop is executed. The registers that can be part of the debiting logger
are listed in the table below.
Various OBIS codes Energy registers OBIS codes Power registers OBIS codes
RTC w/quality
info1
0.1.1.0.0.255 Active energy A+1 1.1.1.8.0.255 P+ max1 1.1.1.6.0.255
Hour counter1 0.1.96.8.0.255 Active energy A-1 1.1.2.8.0.255 P+ max RTC1 1.1.1.6.0.255
Number of debiting
periods1,4
1.1.0.1.0.255 Reactive energy R+1 1.1.3.8.0.255 P+ max
accumulated1
1.1.1.2.0.255
Power threshold
counter11.1.96.51.2.255 Reactive energy R-1 1.1.4.8.0.255 P+ max Tariff 1-2
accumulated1
1.1.1.2.x.255
37/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Various OBIS codes Energy registers OBIS codes Power registers OBIS codes
Pulse input1 1.1.0.128.1.255 A+ Tariff 1-41 1.1.1.8.x.255 Q+ max1 1.1.3.6.0.255
Current
transformer ratio1,2
1.1.0.4.2.255 R+ Tariff 1–41 1.1.3.8.x.255 Q+ max RTC1 1.1.3.6.0.255
Apparent energy E+1 1.1.9.8.0.255 Q+ max
accumulated1
1.1.3.2.0.255
Apparent energy E-1 1.1.10.8.0.255 P+ max Tariff 1-41,3 1.1.1.6.x.255
P+ max Tariff 1-4
RTC1,3
1.1.1.6.x.255
Q+ max Tariff 1-41,3 1.1.3.6.x.255
Q+ max Tariff 1-4
RTC1,3
1.1.3.6.x.255
S+ max1 1.1.9.6.0.255
S+ max RTC1 1.1.9.6.0.255
S- max1 1.1.10.6.0.255
S- max RTC1 1.1.10.6.0.255
P- max 1.1.2.6.0.255
P- max RTC 1.1.2.6.0.255
P- max Tariff 1-4 1.1.2.6.x.255
P- max Tariff 1-4
RTC
1.1.2.6.x.255
P- max accumulated 1.1.2.2.0.255
P- max accumulated
Tariff 1-2
1.1.2.2.x.255
Q- max 1.1.4.6.0.255
Q- max RTC 1.1.4.6.0.255
Q- max Tariff 1-4 1.1.4.6.x.255
Q- max Tariff 1-4
RTC
1.1.4.6.x.255
Actual power
(P1234)
1.1.15.7.0.255
Average power
(P1234)
1.1.15.25.0.255
Available registers in monthly debiting logger1 Included in the default monthly debiting logger setup.2 Register in OMNIPOWER® CT meter only.3 Only tarif f 1 and tarif f 2 are included in the default monthly logger setup.
38/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4 The maximum value for this register is 99, after w hich the counter starts again at "0".
The interval between each debiting stop/debiting log can be controlled by the meter and can be set
to make an automatic log of the registers every month, every second month, every third month,
every half year or once a year.
The debiting stop can also be done on request, either by a command from a meter data
management (MDM) system, like OMNISOFT® VisionAir, or manually by using the sealable push
button if the meter is configured accordingly. The maximum number of log entries in the meter with
the default setup is 36. When the maximum number of logs has been reached, the meter
overwrites the oldest entries.
Maximum registers and associated RTC values are reset after each log entry. Maximum values
are reset to 0 and associated RTC values to 07-02-2136 06:28:15. If no new value is registered
during a log interval, the previously mentioned values will be logged.
4.9.3 Daily/weekly/monthly debiting logger (1.1.98.2.0.255)
In the same way, OMNIPOWER® also has a daily/weekly/monthly based debiting logger. The
registers that can be logged are listed in the table below.
Various OBIS codes Energy registers OBIS codes
RTC w/quality info 0.1.1.0.0.255 Active energy A+ 1.1.1.8.0.255
Hour counter 0.1.96.8.0.255 Active energy A- 1.1.2.8.0.255
Reactive energy R+ 1.1.3.8.0.255
Reactive energy R- 1.1.4.8.0.255
Reactive energy R1 1.1.5.8.0.255
Reactive energy R2 1.1.6.8.0.255
Reactive energy R3 1.1.7.8.0.255
Reactive energy R4 1.1.8.8.0.255
Apparent energy E+ 1.1.9.8.0.255
Apparent energy E- 1.1.10.8.0.255
Active energy A+ Tariff 1 - 4 1.1.1.8.x.255
Active energy A- Tariff 1 - 4 1.1.2.8.x.255
Reactive energy R+ Tariff 1 - 4 1.1.3.8.x.255
Reactive energy R- Tariff 1 - 4 1.1.4.8.x.255
Reactive energy R1 Tariff 1-4 1.1.5.8.x.255
Reactive energy R2 Tariff 1-4 1.1.6.8.x.255
Reactive energy R3 Tariff 1-4 1.1.7.8.x.255
Reactive energy R4 Tariff 1-4 1.1.8.8.x.255
Apparent energy E+ Tariff 1-4 1.1.9.8.x.255
Apparent energy E- Tariff 1-4 1.1.10.8.x.255
Registers stored in debiting logger 2
39/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
The interval between each debiting stop is controlled by the meter and must be set to either daily,
weekly or monthly logging. The maximum number of entries in the logger is 175.
4.9.4 Daily Logger (1.1.98.128.0.255)
The daily logger contains a list of registers and has a fixed daily logging period. It is intended for
conventional data in automatic meter data readout in OMNIA®. The logger is configurable with
respect to the registers that shall be logged.
The registers available for the daily logger is shown in the table below.
Note For three-phase, three-wire meters (Aron), the interpretation of phases is: UL1=UL1-L2 (i.e.
the voltage between meter terminal 1 and 4), UL3=UL2-L3 (the voltage between meter
terminal 4 and 7) and UL2=UL1-L3 (i.e. the voltage between meter terminal 1 and 7). See
the connection diagram for Aron meters in "Connection diagrams ".
Note The registers marked with * are part of the default daily logger setup.
Registers OBIS codes
RTC w/quality info 0.1.1.0.0.255*
Number of debiting periods 1.1.0.1.0.255
Energy A1234 (|A+| + |A-|) 1.1.15.8.0.255*
Energy A-Net (|A+| - |A-|) 1.1.16.8.0.255*
Apparent energy import E+ 1.1.9.8.0.255*
Apparent energy export E- 1.1.10.8.0.255*
A+ Prepayment 1.1.130.0.0.255*
A+ Prepayment credit 1.1.130.0.1.255*
KMP energy format 1.1.134.0.1.255*
P+ max1 1.1.1.6.0.255*
P+ max RTC1 1.1.1.6.0.255*
P+ max accumulated2 1.1.1.2.0.255
P+ max Tariff 1-2 accumulated2 1.1.1.2.x.255
P- max1 1.1.2.6.0.255*
P- max RTC1 1.1.2.6.0.255*
P- max accumulated2 1.1.2.2.0.255
P- max Tariff 1-21 1.1.2.6.x.255
P- max Tariff 1-2 RTC1 1.1.2.6.x.255
P- max Tariff 1-2 accumulated2 1.1.2.2.x.255
UL1,24h minimum 1.1.32.3.130.255
UL1,24h minimum RTC 1.1.32.3.130.255
P+L1 @ UL1, 24h minimum 1.1.21.7.130.255
16
40/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Registers OBIS codes
S+L1 @ UL1, 24h minimum 1.1.29.7.130.255
IL1 @ UL1, 24h minimum 1.1.31.7.130.255
UL1,24h maximum 1.1.32.6.131.255
UL1,24h Maximum RTC 1.1.32.6.131.255
P+L1 @ UL1, 24h maximum 1.1.21.7.131.255
S+L1 @ UL1, 24h maximum 1.1.29.7.131.255
IL1 @ UL1, 24h maximum 1.1.31.7.131.255
UL2,24h minimum 1.1.52.3.130.255
UL2,24h minimum RTC 1.1.52.3.130.255
P+L2 @ UL2, 24h minimum 1.1.41.7.130.255
S+L2 @ UL2, 24h minimum 1.1.49.7.130.255
IL2 @ UL2, 24h minimum 1.1.51.7.130.255
UL2,24h maximum 1.1.52.6.131.255
UL2,24h Maximum RTC 1.1.52.6.131.255
P+L2 @ UL2, 24h maximum 1.1.41.7.131.255
S+L2 @ UL2, 24h maximum 1.1.49.7.131.255
IL2 @ UL2 , 24h maximum 1.1.51.7.131.255
UL3,24h minimum 1.1.72.3.130.255
UL3,24h minimum RTC 1.1.72.3.130.255
P+L3 @ UL3, 24h minimum 1.1.61.7.130.255
S+L3 @ UL3, 24h minimum 1.1.69.7.130.255
IL3 @ UL3, 24h minimum 1.1.71.7.130.255
41/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Registers OBIS codes
UL3,24h maximum 1.1.72.6.131.255
UL3,24h maximum RTC 1.1.72.6.131.255
P+L3 @ UL3, 24h maximum 1.1.61.7.131.255
S+L3 @ UL3, 24h maximum 1.1.69.7.131.255
IL3 @ UL3, 24h maximum 1.1.71.7.131.255
Available registers for daily logger1 Register is only reset once a debiting stop is executed. 2 Register is only updated once a debiting stop is executed.
Maximum/minimum registers and associated RTC values are reset after each log entry. Maximum
values are reset to 0, minimum values to 4.294.967.295 and associated RTC values to 07-02-2136
06:28:15. If no new maximum/minimum value is registered during a log interval, the previously
mentioned values will be logged.
4.9.5 Analysis logger (1.1.99.1.1.255)
The analysis logger allows you to configure the registers to be logged and the log interval. You can
configure:
· Up to 24 different registers*. * Firmware revisions earlier than J1 for direct meters only support 16 different registers.
· The log intervals: 5 minutes, 10 minutes, 15 minutes, 30 minutes, 60 minutes or daily(independent of the load profile settings).
Registers OBIS codes
Pulse input 1.1.0.128.1.255
Hour counter 0.1.96.8.0.255
Active energy A+ 1.1.1.8.0.255
Active energy A- 1.1.2.8.0.255
Reactive energy R+ 1.1.3.8.0.255
Reactive energy R- 1.1.4.8.0.255
Reactive energy R1 1.1.5.8.0.255
Reactive energy R2 1.1.6.8.0.255
Reactive energy R3 1.1.7.8.0.255
Reactive energy R4 1.1.8.8.0.255
A+ Tariff 1-8 1.1.1.8.x.255
A- Tariff 1-8 1.1.2.8.x.255
R+ Tariff 1-8 1.1.3.8.x.255
R- Tariff 1-8 1.1.4.8.x.255
42/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Registers OBIS codes
Active energy A1423 1.1.15.8.0.255
Active energy A+Net 1.1.16.8.0.255
Apparent energy E+ 1.1.9.8.0.255
Apparent energy E- 1.1.10.8.0.255
Actual power P+ 1.1.1.7.0.255
Actual power P- 1.1.2.7.0.255
Actual power Q+ 1.1.3.7.0.255
Actual power Q- 1.1.4.7.0.255
Power Factor Avg 1.1.13.25.0.255
A+L1A+L2A+L3
1.1.21.8.0.255
1.1.41.8.0.255
1.1.61.8.0.255
A-L1A-L2A-L3
1.1.22.8.0.255
1.1.42.8.0.255
1.1.62.8.0.255
P+L1, average
P+L2, average
P+L3 average
1.1.21.25.0.255
1.1.41.25.0.255
1.1.61.25.0.255
P+L1, minimum +RTC
P+L2, minimum +RTC
P+L3 minimum +RTC
1.1.21.3.128.255
1.1.41.3.128.255
1.1.61.3.128.255
P+L1, maximum +RTC
P+L2, maximum +RTC
P+L3 maximum +RTC
1.1.21.6.128.255
1.1.41.6.128.255
1.1.61.6.128.255
P-L1,
P-L2,
P-L3
1.1.22.25.0.255
1.1.42.25.0.255
1.1.62.25.0.255
Q+L1,
Q+L2,
Q+L3
1.1.23.25.0.255
1.1.43.25.0.255
1.1.63.25.0.255
Q-L1,
Q-L2,
Q-L3
1.1.24.25.0.255
1.1.44.25.0.255
1.1.64.25.0.255
43/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Registers OBIS codes
S+L1, average
S+L2, average
S+L3, average
1.1.29.25.0.255
1.1.49.25.0.255
1.1.69.25.0.255
S+L1, minimum +RTC
S+L2, minimum +RTC
S+L3 minimum +RTC
1.1.29.3.128.255
1.1.49.3.128.255
1.1.69.3.128.255
S+L1, maximum +RTC
S+L2, maximum +RTC
S+L3 maximum +RTC
1.1.29.6.128.255
1.1.49.6.128.255
1.1.69.6.128.255
S-L1, average
S-L2, average
S-L3, average
1.1.30.25.0.255
1.1.50.25.0.255
1.1.70.25.0.255
Cut-off state 1.1.128.0.0.255
P+ max, daily 1.1.1.16.0.255
P+ min., daily 1.1.1.13.0.255
P+ max, daily – RTC 1.1.1.16.0.255
P- min.,daily – RTC 1.1.1.13.0.255
IL1, average
IL2, average
IL3 average
1.1.31.25.0.255
1.1.51.25.0.255
1.1.71.25.0.255
IL1, minimum + RTC
IL2, minimum + RTC
IL3, minimum + RTC
1.1.31.3.128.255
1.1.51.3.128.255
1.1.71.3.128.255
IL1, maximum + RTC
IL2, maximum + RTC
IL3, maximum + RTC
1.1.31.6.128.255
1.1.51.6.128.255
1.1.71.6.128.255
UL1, average
UL2, average
UL3 average
1.1.32.25.0.255
1.1.52.25.0.255
1.1.72.25.0.255
UL1, minimum + RTC 1.1.32.3.128.255
44/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Registers OBIS codes
UL2, minimum + RTC
UL3 minimum + RTC
1.1.52.3.128.255
1.1.72.3.128.255
P+L1 @UL1,minP+L2 @UL2,minP+L3 @UL3,min
1.1.21.7.128.255
1.1.41.7.128.255
1.1.61.7.128.255
S+L1 @UL1,minS+L2 @UL2,minS+L3 @UL3,min
1.1.29.7.128.255
1.1.49.7.128.255
1.1.69.7.128.255
IL1 @UL1,minIL2 @UL2,minIL3 @UL3,min
1.1.31.7.128.255
1.1.51.7.128.255
1.1.71.7.128.255
UL1, maximum + RTC
UL2, maximum + RTC
UL3 maximum + RTC
1.1.32.6.129.255
1.1.52.6.129.255
1.1.72.6.129.255
P+L1 @UL1,maxP+L2 @UL2,maxP+L3 @UL3,max
1.1.21.7.129.255
1.1.41.7.129.255
1.1.61.7.129.255
S+L1 @UL1,maxS+L2 @UL2,maxS+L3 @UL3,max
1.1.29.7.129.255
1.1.49.7.129.255
1.1.69.7.129.255
IL1 @UL1,maxIL2 @UL2,maxIL3 @UL3,max
1.1.31.7.129.255
1.1.51.7.129.255
1.1.71.7.129.255
PFL1,
PFL2,
PFL3
1.1.33.25.0.255
1.1.53.25.0.255
1.1.73.25.0.255
THDUL1,
THDUL2,
THDUL3
1.1.32.24.124.255
1.1.52.24.124.255
1.1.72.24.124.255
THDIL1,
THDIL2,
1.1.31.24.124.255
1.1.51.24.124.255
1.1.71.24.124.255
45/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Registers OBIS codes
THDIL3
Frequency 1.1.14.25.0.255
Available registers for analysis logger
For three-phase, three-wire meters (Aron), the interpretation of phases is: UL1=UL1-L2 (i.e. the
voltage between meter terminal 1 and 4), UL3=UL2-L3 (the voltage between meter terminal 4 and
7) and UL2=UL1-L3 (i.e. the voltage between meter terminal 1 and 7). See the connection diagram
for Aron meters in "Connection diagrams ".
The logging depth of the analysis logger depends on the log interval and the number of registers in
the analysis logger. The meter is preconfigured from the factory regarding the registers to be
logged and the interval by which they are logged. These settings can, however, be reconfigured. By
default, the log interval is set to 15 minutes.
You can see the default setup of the analysis logger in the table below.
Meter type OMNIPOWER® single-phase OMNIPOWER® three-phaseRegisters in the
load profile logger
1
register
2
registers
4
registers
1
register
2
registers
4
registers
Default registers in
the analysis logger
A+ A+/A A+/R+ A+/A-/R+/R- A+ A+/A A+/R+ A+/A-/R+/R
-
Actual power P+ X X X X X X X X
Actual power P- X X X X
Actual power Q+ X X X X
Actual power Q- X X
Average voltage
L1
X X X X X X X X
Average voltage
L2
X X X X
Average voltage
L3
X X X X
Average current
L1
X X X X X X X X
Average current
L2
X X X X
Average current
L3
X X X X
Logging depth of
analysis logger
- - - - - - - -
16
46/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Meter type OMNIPOWER® single-phase OMNIPOWER® three-phase
[Days]
Default setup for analysis logger
The mean phase voltage and mean phase current are calculated as the mean value during the log
interval period configured for the analysis logger. The phase currents are shown as absolute
values without indicating the direction of the current.
Maximum/minimum registers and associated RTC values are reset after each log entry. Maximum
values are reset to 0, minimum values to 4.294.967.295 and associated RTC values to 07-02-2136
06:28:15. If no new maximum/minimum value is registered during a log interval, the previously
mentioned values will be logged.
4.10 Meter readout
OMNIPOWER® offers a range of options regarding meter data readout. It spans from simple
display reading to advanced remote readout for smart metering systems.
4.10.1 Manual display readout
The OMNIPOWER® display can show all relevant meter data, e.g. power and energy, phase
currents and voltages, meter number, etc. Even the load profile and the debiting logger can be read
out in the display. The complete design of the available segments in the display is shown in the
figure below and the different display segments are described in the following sections.
OMNIPOWER® display
47/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.10.2 9-digit value field
This field is used for displaying all kinds of register values.
· Meter energy is stated in [6.1], [6.3] [7.0] or [7.2] format with either “kWh” or “kvar” as unit.
· Power is shown with [2.3] format (00.000) and either “kW” or “kvar” as unit.
· Date/time can also be shown in the display and is stated according to the formats YYYY:MM:DDand HH:MM:SS, respectively. In both cases without any units shown.
· Register values like meter number, special data, etc. are indicated by eight digits also withoutany unit.
· The value field can be configured to show leading zeroes of all energy readings. What isshown in the value fields depends on the configuration of the display.
The configuration of the display is explained further in "Display configuration ". The display
configuration can also be remotely updated after installation of the meter (from the meter data
management (MDM) system OMNISOFT® VisionAir).
4.10.3 Unit field
This field is used for displaying the units of registers in the value field.
4.10.4 Object identification field
This field is used for identifying the value in the value field. OBIS codes are used in connection with
the identification.
4.10.5 Quadrant reading
The total current load is indicated by the arrows for +P (imported active power), -P (exported active
power), +Q (inductive reactive power) and –Q (capacitive reactive power), respectively.
The quadrant reading is an instantaneous total value for all three phases. The reading is not active
when the load is below the minimum limit of 10 mA RMS.
It is configurable whether the quadrant indication is visible in the display.
4.10.6 Text field
This field is used either for additional information about the unit field regarding values in the value
field or for text information. In the latter case, text messages are shown as scrolling text in the
field.
90
48/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.10.7 Module indication
This indicates whether a module is communicating with the meter, and if this is the case which
module, e.g. internal radio, primary module or CCC-module.
Note This feature is not yet activated.
4.10.8 Error symbol
This is only used internally by Kamstrup A/S.
4.10.9 Breaker symbol
If the meter is configured with an internal breaker, the position of the breaker is indicated as either
connected or disconnected. However, if the smart disconnect functionality is disabled, both
symbols are off.
Note This is not available for OMNIPOWER® CT meters.
4.10.10 Tamper symbol
This indicates either a magnetic field near the meter or if the meter cover has been removed from
the meter.
4.10.11 Radio network symbol
If a meter is to be used in an OMNICON® Radio Mesh Network, this indicates the connection status
of the meter with the network.
4.10.12 Prepayment symbol
This indicates whether the prepayment functionality is activated.
Note This is not available for OMNIPOWER® CT meters.
4.10.13 Tariff/TOU indication
This indicates the currently active tariff, i.e. either T1, T2, T3, T4, T5, T6, T7 or T8. The tariff
reading is updated every 10 seconds. This means that it may take up to 10 seconds from a tariff
shift has been carried out until the current tariff is displayed.
The tariff indication is switched off if display configuration without tariff reading has been selected.
49/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.10.14 Mains voltage reading
The mains voltage readings per phase L1, L2 and L3 indicates whether voltage is applied to the
individual phase input terminal or not.
For three-phase, three-wire meters (Aron), the interpretation of phases is: UL1=UL1-L2 (i.e. the
voltage between meter terminal 1 and 4), UL3=UL2-L3 (the voltage between meter terminal 4 and
7) and UL2=UL1-L3 (i.e. the voltage between meter terminal 1 and 7). See the connection diagram
for Aron meters in "Connection diagrams ".
Indications L1, L2, L3 Indicates that
On The voltage is above minimum limit (160VAC).
Off The voltage is below minimum limit (160VAC).
Main phase voltage indication
The minimum voltage limit is 160 VAC ±5 %. If the voltage remains below the minimum limit for
more than 1 second in all phases, the processor shuts down and the meter is reset.
4.10.15 Phase current indication
The direction of the current for each phase is shown with these indicators. It can be useful when
checking if inputs and outputs have been installed correctly.
Indications
Indicates that
On The load is above minimum limit.
Off The load is below minimum limit.
Phase current indication
The minimum load limit for the phase current indication is approximately 2.3 W (0.6W for
OMNIPOWER® CT meters). If the phase current is lower than this value, the energy registration
stops, and the phase current indication turns off in the display.
Note Due to the special design of three-phase, three-wire meters with only two measuring
systems, i.e. Aron meters, the phase current indicators can in some situations (with high
phase angle between current and voltage) show misleading information.
4.10.16 Phase sequence indication
This shows the phase sequence of the input phases. If both symbols are off, this indicates that no
sequence could be clearly recognized. The reason could be that one or two phases are missing on
the input.
16
50/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.10.17 Protocols
The following communication protocols are available with OMNIPOWER®.
· Kamstrup Meter Protocol (KMP)
· DLMS/COSEM
· EN 62056-21 (1107) Mode A & C
4.10.17.1 Kamstrup Meter Protocol (KMP)
Kamstrup Meter Protocol (KMP) is a communication protocol that is suited for communication with
OMNIPOWER®. It provides access to all registers in the meter and enables programming and
setup.
For further information about this protocol, please contact Kamstrup A/S.
4.10.17.2 DLMS
The DLMS protocol provides access to most registers and loggers in the meter and to most of the
configuration options as well. For details, please see the “DLMS Protocol description” (document
no. 5512-1424). For further information about the DLMS protocol for OMNIPOWER®, please
contact Kamstrup A/S.
4.10.17.3 1107
The 1107 protocol provides access to most registers in the meter and enables configuration and
setup. For details, please see the IEC 1107 Protocol description (document no. 5512-1458). For
requesting the 1107 protocol for OMNIPOWER® meters, please contact Kamstrup A/S.
Note The protocol is not supported for meter firmware number 50981173, 50981165 and
50981251.
4.10.18 Local readout via optical interface – METERTOOL OMNIPOWER®
With METERTOOL OMNIPOWER®, it is possible to read out all meter relevant data via the optical
interface. This tool is also suitable for configuration of the meter. For details, please see the
installation and user guide "METERTOOL OMNIPOWER®” (doc. 5512-1213).
For more information about METERTOOL OMNIPOWER®, please contact KAMSTRUP A/S.
4.10.19 Integrated OMNICON® radio mesh connectivity
Meters are delivered with integrated OMNICON® radio mesh connectivity. When connected to the
OMNIA® smart grid platform, the full range of advanced features becomes available.
50
50
50
51/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.10.20 Integrated OMNICON® point-to-point connectivity
Meters are delivered with OMNICON® point-to-point connectivity modules as shown in the figure
below. When connected to the OMNIA® smart grid platform, the full range of advanced features
becomes available.
Point-to-point communication in OMNIA® Suite
The communication module can be delivered pre-mounted in the meter, or it can be mounted after
the meter is installed. The post-mounting of the modules can be done without removing the power
to the meter terminal connection.
4.10.21 Full encryption on all interfaces
OMNIPOWER® with software number 55981173, 50981165 and 50981251 introduces full data
encryption on all communication interfaces including the primary module port, the CCC module
port and the optical interface. The encryption method used is AES 128-bit.
It covers readout of all consumption/production data, read and write possibilities of configuration
parameters and control commands like disconnect/reconnect of the internal breaker of the meter.
OMNIA® Suite supports full readout, configuration and control of encrypted OMNIPOWER®
meters. For 3rd party meter data management (MDM) systems to be able to support encrypted
meters, it is required that the systems connect to OMNISOFT® Key Management Service (KMS),
which will allow the MDM system to access all unique encryption keys for the relevant meters.
For more information about encrypted meters and KMS, please contact Kamstrup A/S.
4.10.22 M-Bus and RS-485 connectivity
As an option, OMNIPOWER® can be delivered with M-Bus or RS-485 connectivity modules. The
M-Bus module communicates through the EN13757-2/3 protocol. The RS-485 module can be
used with the KMP, DLMS and 1107 protocols.
52/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.11 Modularity options
OMNIPOWER® has two independent module areas available for communication. By default, both
module areas are available on all OMNIPOWER® meter types.
4.11.1 Primary modules
The primary module area can be used for communication modules as described in the previous
section, but it can also be used for tariff control modules, load control modules, etc.
4.11.2 CCC modules
The second module area, which is shown in the figure below, offers access to the Consumer
Communication Channel (CCC).
CCC-module area in OMNIPOWER®
CCC-modules are intended for in-home communication as shown below. The communication can
be one way, e.g. to an in-home display, or it can be two-way for intelligent control of e.g. relays in
the home.
CCC-modules also enable the utilities to send consumer-related information, e.g. price signals, to
in-home displays directly from their meter data management (MDM) system or other business
systems.
53/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
CCC-module in OMNIA® Suite
A suitable technology for in-home communication is ZigBee® Smart Energy or similar.
4.12 Disconnect functionality
The following description applies to OMNIPOWER® direct meters with integrated breakers.
Meters with integrated breakers can disconnect and reconnect the consumer’s supply. All meters
with integrated breaker are marked on the front of the meter as shown below.
The breaker is controlled by the main processor of the meter and is bistable, i.e. it maintains its
status (connected/disconnected) independently of the main supply status of the meter.
The integrated breaker disconnects all the output phases in the meter while the neutral connection
is not disconnected.
Important The breaker must not be used for safety cut-off.
54/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
For both OMNIPOWER® three-phase and OMNIPOWER® single-phase meters, the integrated
breakers are approved according to EN 62055-31, Annex C for UC3 breaking capabilities. This
means that the meter fulfills following:
· 10.000 makes-and-breaks cycles @ 100A (5.000 @ PF=1.0 and 5.000 @ PF=0.5 inductive).
· Short circuit current carrying capacity 6kA/3kA (Test1/Test2).
The UC3 approval documents can be handed out by Kamstrup A/S on request.
The OMNIPOWER® three-phase DIN rail meter is approved according to EN62055-31 for UC2
breaking capabilities.
4.12.1 Disconnect function
OMNIPOWER® can be delivered with integrated breakers. It is possible to disconnect the breaker
in the following ways:
· Manually by activating the left push button.
· Remotely from a smart metering system.
· By smart disconnect, i.e. intelligent disconnection when voltage, current or power exceeds apreconfigured limit.
· By the integrated prepayment option.
When the breaker is disconnected, it is possible to reconnect the breaker in the following ways:
· Manually by activating the left push button.
· Remotely via a release command and an additional reconnect command.
· With a combination of a release command sent from a smart metering system and a manualreconnect on the push button.
· Automatically after current and power level are back to normal or credit (if prepayment isactivated) is restored.
Independently of the way of reconnect, the reconnection time is minimum 5 seconds. It is
configurable which of these options are available in a meter.
The different control options are described in details in the following sections.
4.12.2 Manual disconnection and reconnection
It is possible to disconnect and reconnect the breakers manually. This is done in the following
ways:
Manual disconnection1. On the meter, select the shown display reading by activating the left push button.
55/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
2. Activate the left push button for approx. 6 seconds. This disconnects the relays, and the redLED turns on.
Manual reconnection1. On the meter, select the primary display reading when the red LED is flashing.
2. Activate the left push button for 6 seconds until the relays are connected and the red LED turnsoff.
4.12.3 Remote disconnection from a smart metering system
For OMNIPOWER® meters with integrated breakers, it is also possible to disconnect, release and
reconnect the breaker remotely. As a safety precaution, the remote disconnect functionality in
OMNIA® is securely protected by encrypted communication.
4.12.4 Smart disconnect
OMNIPOWER® includes a smart disconnect feature that disconnects the breakers if either the
total current or power exceeds a preconfigured limit.
4.12.5 Disconnection basis
The “disconnection basis” setup choice defines whether smart disconnect is enabled or disabled,
and (if enabled) on which basis the smart disconnect is affected. It is possible to select:
· No function: The smart disconnect function is disabled.
· Current-controlled: Smart disconnect is affected when a configured current limit is exceeded.
· Power-controlled: Smart disconnect is affected when a configured power limit is exceeded.
· Voltage-controlled: Smart disconnect is affected when a configured phase voltage limit isexceeded.
· Prepayment: The prepayment function controls the disconnection.
The disconnection basis is selected as part of the smart disconnect configuration. By default,
OMNIPOWER® is provided with the smart disconnect functionality disabled. If the function is to be
used, it can either be enabled from the factory at delivery, activated remotely or locally with
METERTOOL OMNIPOWER®.
56/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.12.6 Current-controlled disconnection
Current-controlled disconnection is based on RMS current with average calculation every 1
second. Disconnection is affected if one of the phase currents IL1, IL2 or IL3 exceeds the limit
Id*kx for a configured time period; t1, t1+t2 or t1+t2+t3.
4.12.7 Power-controlled disconnection
Power-controlled disconnection is based on the total power in all phases. Disconnection is
affected if the total phase power exceeds the limit Id*kx for a configured time period; t1, t1+t2 or
t1+t2+t3.
At smart disconnect configuration, the disconnect current Idisconnect (Id) or the disconnect power
Pdisconnect (Pd) is set, and it must be determined whether the smart disconnect is to be based
on either current or power. The breaker then disconnects the supply when Id or Pd is exceeded.
OBIS code Register Min. value Max. value
1.1.128.0.13.255 Idisconnect 0 A 80 A
1.1.128.0.13.255 Pdisconnect 0 kW 80 kW
Configuration limits for smart disconnect
4.12.8 Overvoltage disconnection
OMNIPOWER® also offers an option for automatic disconnection in case of an overvoltage. The
overvoltage disconnection and reconnection are based on average values of the phase voltages,
and the activations can therefore be delayed by configuration of the sample time parameters called
“Sample-time disconnect” and “Sample-time reconnect”. The voltage thresholds for disconnection
and reconnection are also configurable.
Example:
In the example shown below, the four configuration parameters are set to following values:
· Overvoltage disconnect level: 270V
· Overvoltage reconnect level: 260V
· Overvoltage sample-time for disconnect: 2 sec.
· Overvoltage sample-time for reconnect: 5 sec.
57/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Example of overvoltage disconnect and reconnect
The configuration parameters have the range and resolution shown in the table below.
OBIS code Parameter Value range (resolution) Default value
1.1.128.0.19.255 Overvoltage disconnect threshold 260-320V (1 V) 285V
1.1.128.0.20.255 Overvoltage sample time for
disconnect
1 – 3600 sec (1 sec) 1 sec
1.1.128.0.21.255 Overvoltage reconnect threshold 250-270V (1 V) 265V
1.1.128.0.22.255 Overvoltage sample time for reconnect 1 – 3600 sec (1 sec) 60 sec
Overvoltage disconnect configuration parameters
Note By default, the overvoltage disconnect functionality is deactivated. It can be activated for
METERTOOL OMNIPOWER®.
4.12.9 Delayed disconnection
OMNIPOWER® can be configured to delay the disconnection and to differentiate the disconnection
characteristics. This is done with configurable multiplication factors for both time : t1, t2, t3 and
current/power factors: k1, k2, k3.
OBIS code Register Min. value Max. value
1.1.128.0.2.255
1.1.128.0.3.255
1.1.128.0.4.255
k1,
k2,
k3
0 9.9
1.1.128.0.5.255 t1, 0 65535
58/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OBIS code Register Min. value Max. value
1.1.128.0.6.255
1.1.128.0.7.255
t2,
t3 [sec.]
Multiplication factors for smart disconnect
The following conditions for the factors must be met at configuration:
t1 =< t2 =< t3 and k3 =< k2 =< k1
The meter disconnects the supply if one of the below conditions is met for current or power,
respectively.
Current Power
I > Id * k3 and t > t1 + t2 + t3 P > Pd * k3 and t > t1 + t2 + t3
I > Id * k2 and t > t1 + t2 P > Pd * k2 and t > t1 + t2
I > Id * k1 and t > t1 P > Pd * k1 and t > t1
Disconnect conditions for OMNIPOWER®
The conditions in the table above are also illustrated in this figure:
Differentiation of smart disconnection
4.12.10 Reconnection
Reconnection can be configured to be either manual or automatic. In OMNIPOWER® meters that
are part of a smart metering system, the meters can be configured to allow manual reconnection
(provided that the meter is first released for manual reconnection by the utility). The meter is
released by sending a remote command to the meter.
59/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
It is possible to configure a mandatory time delay called TConnectWait which indicates the
minimum time before a reconnect can be executed.
OBIS code Register Min. value Max. value Default value
1.1.128.0.8.255 TConnectWait 0 A 80 A
The setup for TConnectWait used for delay in reconnection of breakers
4.12.11 Disconnection on meters with APS
For OMNIPOWER® with auxiliary power supply (APS), the disconnection functionality differs from
the description in the previous sections.
If OMNIPOWER® with APS is supplied by main terminals L1, L2 and L3, the functionality is the
same as mentioned earlier. When, however, this meter is supplied from the APS input, no breaker
activation is possible, neither disconnection nor reconnection.
4.12.12 Event logger for disconnect/connect history (1.1.99.98.5.255)
OMNIPOWER® with breaker includes a logger that registers all events related to the disconnect
functionality. For each event, either a disconnection, a release or a reconnection, the meter logs an
ID, a time stamp, the disconnect state and the connection feedback.
The size of this logger is 200 log entries.
4.12.13 Prepayment
The prepayment functionality is to be used with a smart metering system. By default, the
prepayment function is disabled, but it can be activated and deactivated as required.
Note Prepayment is only possible for meters with internal breaker and will not work together
with tariffs.
4.12.14 Prepayment principle
Prepayment is based on the specific prepayment register A14prepayment.
When enabling the prepayment functionality, A14prepayment must be “loaded” with a number of
kWh. This can only be done by using a system that supports the functionality.
As soon as the register contains a number of kWh and the functionality is enabled in the meter, the
register starts counting down as the energy is consumed.
When A14prepayment has reached 0 kWh, the supply is disconnected, and a new value must be
programmed for the register.
60/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
When prepayment is activated, the prepayment register A14prepayment must be activated in the
display settings by activating a display setup that includes the prepayment register. If a display
setup with the prepayment register is activated, the register is, however, only shown when
prepayment is enabled.
When prepayment is activated in the meter, the “PP” symbol is shown in the display.
The “PP” symbol shown in the meter display
The unit in the display is “kWh”, and “PAY” is shown in the text field.
The prepayment is based on total energy consumption and does not support tariffs. Therefore, the
functionality is disregarded if the meter is configured for tariffs.
A14prepayment can be configured to disconnect only on working days, i.e. not on non-working
days, holidays or exception days. It is also possible to set a time slot, e.g. from 10:00 PM to 8:00
AM the following day where the disconnection will not happen.
If A14prepayment reaches zero within one of the above mentioned exceptions, the disconnection
happens on the next working day. In the meantime, the credit register A14prepayment,credit starts
registering the energy that is consumed until disconnection takes place. When adding new kWh to
the meter, the meter takes any consumption in the credit register into account. The meter
subtracts the value in A14prepayment,credit from the added amount of kWh and put the remaining
kWh in A14prepayment.
If A14prepayment has reached 0 kWh, and the breakers are disconnected, it is possible to
reconnect under certain conditions. First, the load must be decreased below a defined limit called
Iexception or Pexception. The limits are configurable within the range given in the table below.
After the load is limited, it is possible to reconnect the meter and by that still be able to use a
minimum of power. Be sure to keep the consumption below the limit, or the meter will disconnect
again. The duration in which the exception for current and power, respectively, can be active is
however limited by a configurable number called tprepayment. When the limit is exceeded, the
consumer is disconnected until new kWh are added to the meter. In the intervening period, the
consumed energy is also registered in A14prepayment,credit.
OBIS code Register Min. value Max. value
1.1.128.0.12.255 Iexception 0 A 80 A
1.1.128.0.12.255 Pexception 0 kW 80 kW
61/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OBIS code Register Min. value Max. value
1.1.128.0.9.255 tprepayment 0 255 days
Configurable parameters for smart disconnect
4.13 Power quality measurements
OMNIPOWER® is equipped with a supply power quality measurement tool. It is based on the
requirements in EN50160 regarding power quality delivered from utilities and includes
measurement of the following:
· Frequency variations
· Long-term and short-term overvoltage and undervoltage
· Power outages
· Rapid voltage change
· Supply voltage unbalance
· Total harmonic distortion (THD)
· Neutral fault detection
· Power factor
These quality measurements are described in the following sections. The power quality detection
and registration in OMNIPOWER® is based on events, i.e. information is only registered if an
unexpected situation appears. Some events are registered with detailed information like time
stamp and voltage level information, while other events are registered as a counting number in an
occurrence counter.
4.13.1 Frequency measurements
Normally, frequency variations will not be relevant as most grids are synchronous connected to an
interconnected grid system. However, in special cases where the grid is isolated, frequency
measurements are relevant.
OMNIPOWER® measures a 10-second mean value of the line frequency and compares this value
with the limits given in EN50160. The total number of events where this 10-second mean value is
outside the limits is registered in the occurrence counter in the meter.
It is also possible to include the line frequency in the analysis logger, where the meter will log an
average value according to the log interval configured for the analysis logger.
4.13.2 Voltage variations
OMNIPOWER® continuously (every second) updates the supply voltages at each phase and
detects and registers any deviations from a set of user-defined voltage limits, i.e. a deviation can
be either an overvoltage or an undervoltage.
For three-phase, three-wire meters (Aron), the interpretation of phases is: UL1=UL1-L2 (i.e. the
voltage between meter terminal 1 and 4), UL3=UL2-L3 (the voltage between meter terminal 4 and
62/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
7) and UL2=UL1-L3 (i.e. the voltage between meter terminal 1 and 7). See the connection diagram
for Aron meters in "Connection diagrams ".
4.13.2.1 Long-term deviations
Long-term deviations are related to a mean value of the phase voltage. Therefore, it is also called
mean time deviation. The average time, Utime-period,mean is configurable in the span from 10
seconds and up to 30 minutes. The mean value is calculated for every window and for each time
the value is outside the limits, i.e >Uhigh,mean or <Ulow,mean, the event is registered in the
voltage quality logger.
The figure below shows an example of a phase voltage that varies in time. In this period, the
average time is set to 10 seconds and the first and the third period is registered as deviations.
Example of long-term voltage deviation. Average time period is 10 seconds
A long-term deviation is registered in the voltage quality logger in the form of a time stamp (start
time), a mean value, a maximum value and a minimum value for the period.
4.13.2.2 Short-term deviations
OMNIPOWER® also detects and registers deviations that last shorter than the average time for
mean value deviations. For a description, please see "Long-term deviations ". This is described
as short-term or single value deviation.
Three examples of short-term voltage deviations are shown in the figure below. In a case, where
the voltage is outside the limits for several seconds, the first value, maximum/minimum value and
last value is registered. Every value is registered with a time stamp.
16
62
63/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Example of short-term voltage deviations
Deviations that last shorter than 1 second is registered as sags and swells, which is described in
"Voltage sags and swells with a duration 100 ms – 1 second ".
4.13.3 Voltage outage
OMNIPOWER® detects all voltage outages, whether they are happening on one, two or three
phases. All events are registered in the voltage quality logger as two events; one for outage of the
voltage and one for reestablishment of the voltage.
The voltage detection level depends on the event. If the outage is on one or two phases (i.e. the
meter is still powered by the third phase), the registration level is a configurable value between 50-
160 V. If the power outage is on all phases, the detection level is approximately 160 V. The
detection levels are illustrated in the figure below.
Detection levels for one phase and three phase voltage outage
It is possible to configure the time the voltage outage shall be present before the event is logged.
The value can be configured in the interval from 0 second – 30 minutes.
65
64/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
All detected voltage outages are also registered in one of two occurrence counters that register the
number of voltage outages. According to EN50160, voltage outages are divided into short voltage
registered in one of the two categories.
Note For three-phase, three-wire meters (Aron), the voltage outage detection is only 100% valid
for outages on phase L1 or phase L3. As the phase L2 voltage is the voltage between pin 1
and pin 7, it is not measured by its own measuring system (according to the connection
diagrams in "Connection diagrams "). Depending on the actual load on the installation, a
removal of L2 wire can be therefore detected as a phase voltage outage on either phase
L1 or phase L3, or it can be detected an all phase outage.
4.13.4 Configuration of voltage quality measurements
As described in the previous sections, the voltage quality measurements require that a list of
configurable parameters is set. The list is given in the table below and the figure shows the visual
function of the parameters.
Parameter Description Min.
value
Max.
value
Defaul
t
value
Uhigh,mean The voltage level for overvoltage detection according to
mean voltage deviation (in +% of nominal voltage).
232.3 V
+1%
276 V
+20%
253 V
+10%
Ulow,mean The voltage level for undervoltage detection according to
mean voltage deviation (in % of nominal voltage).
184 V
- 20%
227.7 V
-1%
207 V
-10%
Utime-period,mean The time period for calculating the mean voltage. 10 sec. 30 min. 10
min.
Uhigh,sv The voltage level for overvoltage detection according to
short-term deviation (in +% of nominal voltage).
232.3 V
+1%
276 V
+20%
253 V
+10%
Ulow,sv The voltage level for undervoltage detection according to
short-term deviation (in -% of nominal voltage).
184 V
- 20%
227.7 V
-1%
207 V
-10%
Uoutagelevel The voltage level for a voltage outage that happens on one
or two phases (for three-phase meters)
50 V 160 V 50 V
Uoutage,timethreshold The time that a voltage outage has to be present before it
is registered in the voltage quality logger.
0 sec. 30 min. 10
sec.
Configurable parameters for voltage quality measurements
16
65/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Configurable parameters for voltage quality measurements
The parameters can be configured remotely by using an automatic meter reading (AMR) system or
locally using METERTOOL OMNIPOWER®.
4.13.4.1 Voltage sags and swells with a duration 100 ms – 1 second
OMNIPOWER® also detects and registers the number of voltage sags (dips) and voltage swells,
which are events where phase voltage drops below 20% of Un or rises above 20% of Un for a
period shorter than one minute.
Sags and swells that last for more than 1 second are registered in the voltage quality logger as
described in "Short-term deviations ". Sags and swells that last from 100 milliseconds to 1
second are detected and registered in one of two occurrence registers.
Voltage sags and swell are not registered with a time stamp or any indication of voltage level.
Instead, the number of each event is registered in the meter. OMNIPOWER® can register one sag
and swell per second.
4.13.5 Rapid voltage change
A rapid voltage change is defined as a change in the phase voltage within the limits set for
overvoltage and undervoltage detection. For OMNIPOWER®, a rapid voltage change is defined as
a change of 5% or more, between two subsequent samples of the phase voltage, i.e. DV > 11.5 V.
Every rapid voltage change is registered in an occurrence counter register and this register is
logged in the occurrence counter logger.
62
66/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.13.6 Supply voltage unbalance
Supply voltage unbalance is a number for the balance between the three-phase voltage according
to voltage level for each phase and the phase shift between the three voltages. EN50160 describes
that the supply voltage unbalance must not exceed 2% when calculated as a 10-minute mean
value.
OMNIPOWER® continuously measures the supply voltage unbalance. If the mean value exceeds
the limit, the event is registered in an occurrence counter register and the register is logged in the
occurrence counter logger.
4.13.7 Total harmonic distortion (THD)
OMNIPOWER® also measures the total harmonic distortion (THD) for each phase, i.e. current
THDI and voltage THDU. According to EN50160, a 10-minute mean value for THDU for each phase
is calculated. If one of these values exceed 8 %, which is the maximum limit in EN50160, the event
is registered in an occurrence counter register for the specific phase. The calculation of THD
includes up to the 40th harmonics.
In total, OMNIPOWER® has six occurrences counter registers for THD, three for THDU and three
for THDI (one for each phase). All six registers are logged in the occurrence counter logger.
Both THDU and THDI is also available in the analysis logger for continuously logging of the mean
value according to the integration period for the analysis logger.
4.13.8 Readout of the power quality measurements
As described in the previous sections, OMNIPOWER® continuously makes a number of power
quality measurements. The result of the measurements is registered in two loggers:
1. A voltage quality logger : Logs overvoltage, undervoltage and voltage outage events.
2. An occurrence counter logger : Logs the number of events of different power qualityparameters.
In the following sections, some examples are given of the information that the two loggers provide
when they are readout from the meter.
4.13.8.1 Voltage quality logger (1.1.99.98.16.255)
The figure below shows how the mean voltage is calculated in terms of a 10-seconds sample
period. Normally, the sample period will be longer, e.g. 1 minute or 10 minutes. The corresponding
value for the actual consumed power, measured as a mean value in the same period as the
voltage event, is also logged.
66
68
67/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Example of long-term voltage deviations
For the example above, the corresponding information in the logger is shown in the table below.
For every period the mean value is outside the limits, there is a log entry.
Log
ID
Time Phase Event Mean value Max value Min Value Actual Power
1 13:50:10
(Start time)
1 (L1) 0
(Undervoltage)
215 V 230 V 204 V 10.80 kW
2 13:50:30
(Start time)
1 (L1) 1
(Overvoltage)
244 V 260 V 220 V 3.39 kW
Examples of a registration of long time voltage deviations in the voltage quality logger
Examples of a registration of long time voltage deviations in the voltage quality logger
Similarly, you can see a different short-term voltage deviations in the figure below.
Example of short-term voltage deviations
68/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
For the example above, the corresponding information in the readout is shown in the table below.
For every period where several values are outside the limits, the first value, the
minimum/maximum value and the last value is registered.
Log
ID
Time Phase Event Mean
value
Max
value
Min Value Actual
Power
3 14:32:17 1 (L1) 6 (Single value min start) 0 V 0 V 210 V 9.87 kW
4 14:32:19 1 (L1) 2 (Single value min peak) 0 V 0 V 204 V 10.25 kW
5 14:32:20 1 (L1) 7 (Single value min stop) 0 V 0 V 208 V 10.10 kW
6 14:32:27 1 (L1) 6 (Single value min start) 0 V 0 V 204 V 12.41 kW
7 14:32:34 1 (L1) 8 (Single value max start) 0 V 253 V 0 V 4.78 kW
8 14:32:39 1 (L1) 3 (Single value max peak) 0 V 262 V 0 V 2.67 kW
9 14:32:40 1 (L1) 9 (Single value max stop) 0 V 252 V 0 V 2.44 kW
Examples of a registration of short time voltage deviations in the voltage quality logger
4.13.8.2 Occurrence counter logger (1.1.99.98.17.255)
A large number of occurrence counter registers are described in the previous sections. In the table
below, these registers are all listed in an example of a readout of the occurrence counter logger
with a log interval of one day. That is, every midnight, the numbers in the occurrence counter
registers are logged.
With this information, it is possible to calculate the total percentage of time that conditions have
been outside the limits given in EN 50160. The table shows these calculations to the right. In the
example, it can be seen that the THDU_L2 is above the requirements (THDI higher than 8% for
more than 5 % of the time in a week).
Log ID (Daily) 1 2 3 4 5 6 7 No. of
events in
a week
Total
time in a
week
RTC (example with daily log interval) 22/01 23/01 24/01 25/01 26/01 27/01 28/01
VQ_Counter_F1 (50Hz – 2%) 0 0 0 0 0 0 0 0 0
VQ_Counter_F2 (50Hz + 2%) 0 0 0 0 0 0 0 0 0
VQ_Counter_VoltageVariation_Low1
(<10% of Un for a 10-minute mean value)
2 3 5 2 9 6 4 31 3.1 %
VQ_Counter_VoltageVariation_Low2
(<15% of Un for a 10-minute mean
value)
0 0 0 0 1 0 1 2 0.2 %
69/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Log ID (Daily) 1 2 3 4 5 6 7 No. of
events in
a week
Total
time in a
week
VQ_Counter_VoltageVariation_High
(>10% of Un for a 10-minute mean
value)
1 1 2 1 1 2 1 9 0.9 %
VQ_Counter_RapidVoltageChanges 3 4 4 5 1 2 2 21
VQ_Counter_Voltage_Unbalance 1 1 2 7 2 1 1 15 1.5 %
VQ_Counter_Interupts_Long 0 0 0 0 0 0 0 0
VQ_Counter_Interupts_Short 0 0 0 1 2 0 0 3
VQ_Counter_THD_U_L1 2 3 1 2 3 2 2 15 1.5 %
VQ_Counter_THD_U_L2 9 8 12 8 14 7 10 68 6.7 %
VQ_Counter_THD_U_L3 1 1 4 3 1 2 1 13 1.3 %
VQ_Counter_THD_I_L1 4 2 1 2 1 1 2 13 1.3 %
VQ_Counter_THD_I_L2 2 1 2 2 3 4 1 15 1.5 %
VQ_Counter_THD_I_L3 1 2 3 1 2 2 1 12 1.2 %
VQ_Counter_Sags 6 7 4 1 5 7 3 33
VQ_Counter_Swells 0 1 2 1 1 0 2 7
An example of readout of the occurrence counter logger
The interval of logging can be configured to daily, weekly or monthly.
4.13.9 Power factor
OMNIPOWER® also measures the power factor for each phase. The values are available for
display readout and the instantaneously values can also be read on request. It is also possible to
add power factor measurement in the analysis logger.
4.13.10 Neutral fault detection
OMNIPOWER® can detect whether the neutral connection (N) on the supply side is disconnected.
This is also called neutral fault. The purpose of the neutral fault detection is to register if the
attached electronic equipment could be exposed to overvoltage which can damage the equipment
and/or cause injury. Neutral fault detection only applies to the three-phase, four-wire meter type.
The figures below illustrate how OMNIPOWER® detects neutral faults related to the supply side,
but not on the demand (or consumer) side.
70/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Neutral fault detection for three-phase meters and CT meters
The neutral fault detection functionality is based on voltage measurements and voltage thresholds,
which is described in the following.
The figures below show a situation without neutral fault and one with neutral fault.
Neutral fault measurement principle
71/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
When the neutral fault is present, the load is asymmetric, and the neutral fault voltage VN occurs.
The green vectors indicate the phase voltages on the grid. The yellow vectors indicate the phase
voltages measured by the meter.
The neutral fault is detected when the following three conditions are present:
1. Two of the phase voltages VL1, VL2 and VL3 are above the threshold voltage VLhiTh. The
default value is 253 V.
2. One of the phase voltages VL1, VL2 and VL3 is below the threshold voltage VLloTh. VLloTh is
equal to 230V – VNTh, where – VNTh is set to 40, i.e. VLloTh = 190 V.
3. Condition 1 and 2 must be present in a time period longer than the time period called “neutralfault time”. The default value is 60 seconds.
Under some conditions, a neutral fault is not detected. In a situation with symmetric load, the
neutral fault voltage VN will theoretically be zero volts and neutral fault will not be detected, even if
the neutral is missing.
In the figure below, a neutral fault is not detected in the white areas.
Neutral fault detection range
In the figure to the left, the yellow areas indicate when the neutral fault will be detected. In the figure
to the right, a situation is shown where the neutral fault is detected since the conditions are as
follows:
· VL1 < VLloTh
· VL2 > VLhiTh
· VL3 > VLhiTh
The parameters VNTh, VLhiTh and the neutral fault time can be configured with the registers
(shown with default values):
OBIS code Parameter Description Default value
1.1.134.0.9.255 NeutralFaultVNThreshold The threshold for neutral voltage in neutral
fault detection.
40 VAC
72/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
OBIS code Parameter Description Default value
1.1.134.0.10.255 NeutralFaultVLThreshold The threshold for line voltage in neutral fault
detection.
253 VAC
1.1.134.0.11.255 NeutralFaultTime The time for neutral fault to be detected
before the event.
60 sec.
4.13.10.1 Neutral fault logger (1.1.99.98.12.255)
OMNIPOWER® has a logger for neutral fault events where every event is registered with a time
stamp. The neutral fault event logger has a depth of 45 log entries.
In a smart metering system, it is possible for the meter, in case of a neutral fault, to send a push
alarm to the meter data management (MDM) system and in this way warn the utility of the situation
as quickly as possible.
In meters with integrated breakers, there is also the possibility to disconnect the breaker in the
meter in case of neutral fault detection.
4.13.11 Earth fault detection
For three-phase, three-wire meters (Aron) and some specific single-phase meters, which are
installed in IT- and TT-distribution network, it is possible to activate an integrated earth fault
detection functionality.
Earth fault detection is based on current summation of the three phase currents. The sum of
currents for all phases is called IIearth as shown in the figure below.
Earth fault current
The meter samples the value of this current in the sample period called tearth_average. If the
sampled value, called Iearth_average is above the threshold, Ithreshold, the meter detects the
event as an earth fault. Each event is identified with a start, a peak and a stop, as shown in the
figure below.
73/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Earth fault detection by the meter
The values of tearth_average and Ithreshold are configurable in the range from 1-3600 sec. and 1-
2000 mA, respectively. Changing the configuration values will change the behaviour of earth fault
detection as shown in the figure below.
Configurable parameters for earth fault detection will change the behaviour of the function
4.13.11.1 Earth fault detction logger (1.1.99.98.19.255)
The OMNIPOWER® meters mentioned in the previous section have a logger for earth fault
detection, which can be activated and deactivated as required.
When the logger is activated, the meter will register the event where Iearth_average > Ithreshold
the event in the earth fault detection logger (Start). The event is registered with a time stamp and
an actual value of Iearth_average.
The meter will also make a registration when Iearth_average < Ithreshold (Stop). At the same time,
the meter also makes a registration of the maximum value of Iearth_average, which is measured
during the period between the start and the stop time for the earth fault (peak).
74/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.14 Other smart grid functionalities
OMNIPOWER® is developed to meet the future smart grid requirements. This is underlined by the
power quality measurements, but also by a number of additional functionalities, such as meter
firmware upload, integration of push alarms, and control of in-home relays and the implementation
of Multi-Utility Controller in the meter.
The functions are described in the following sections.
4.14.1 Firmware upload
It is possible to upload new meter firmware remotely with OMNIA®. This functionality is developed
according to the WELMEC Software guide 7.2 and is approved in accordance with the MID type
approval of the meter.
For further information regarding the firmware upload functionality, please contact Kamstrup A/S.
4.14.2 Alarm handling/push alarms
OMNIPOWER® can be configured to give an alarm when specific events are registered by themeter. As the alarm is pushed from the meter, the term “push alarm” is used.
The following events can be configured to generate push alarms:
· Magnetic detection
· Tamper detection
· Internal meter error
· Undervoltage and overvoltage detection
· Missing phase voltage detection
· Neutral fault detection
· Earth fault detection
· Disconnection and manual reconnection of breakers
The alarms are transmitted through the OMNICON® communication network or to the module port.
For further details about alarms and alarm configurations, please contact Kamstrup A/S.
4.14.3 All phase power outage alarm ("last gasp")
In addition to the previous section, OMNIPOWER® Variant 2 introduces an alarm notification called
“last gasp” in case of a total power outage, i.e. a power outage on all phases on the grid side of the
meter.
If an all phase power outage occurs, the affected OMNIPOWER® meters with internal radio will
broadcast a “last gasp” alarm, which is relayed through the radio network to the OMNIA® System.
Note A meter which is affected itself by the power outage will not be able to repeat “last gasp”
alarms from nearby located meters.
75/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
4.14.4 Control of external load relays
As an option, it is possible to install a two-relay load control module in the meter. The load control
relays can be used to control the consumer’s installation. The control of the relays on the module
can be done in two ways:
· By predefined (configurable) load control plans managed by the meter.
The plan can be set independently for each meter and can also be set to follow a specific tariffplan. Load control plans can be remotely updated from OMNISOFT® VisionAir.
Note Due to any preprogrammed delay in the meter on the relay-shift, it is important torestart the meter (on/off) when the time is set correctly in the meter. This place therelays in the correct position and stops the delay timer.
· By remote on-demand commands sent from a smart metering system.
For more details about how the load control relay is configured, please see “Load control
configuration ”.
4.14.5 Multi-utility options
It is possible to install a Multi-Utility Controller (MUC) module in OMNIPOWER®. With this module,
consumption data from nearby flow meters as heat, water or gas meters can be read out.
Afterwards, the data can be sent to OMNISOFT® VisionAir using the OMNICON® network. The
setup is shown below.
98
76/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Multi-Utility Controller in OMNIPOWER®
For more information about the Multi-Utility Controller module and the flow meter data which can be
accessed, please contact Kamstrup A/S.
4.14.6 Miscellaneous use
As default, OMNIPOWER® has an S0 pulse output (described in “S0 output ”) and two available
I/O (input/output) ports on the module interface. The use of one or both I/O ports in the module
area requires that the meter is equipped with a module that supports the wanted functionality.
4.14.7 Pulse inputs in the module area
The pulse inputs in the module area (module I/O) can be configured with the following
functionalities:
· Tariff control, see also the table "Tariff control table "
· Pulse input from other units
· Alarm input for the registration of an external alarm
78
34
77/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
The pulse input accumulates pulses in the pulse input register. If this register is shown in the
display, it is updated every 10 seconds. It is possible to scale the reading of the pulse input by a
”pulse factor” in the range from 0.1 to 1000 units per pulse.
The maximum permissible frequency for input pulses is 25 Hz.
In relation to the pulse input register, the unit for the register can be set to the following:
· kWh
· m3
· l
· “None”
4.14.7.1 Example of pulse input from a water meter
A water meter emits 1 pulse per 25 l. The required reading in the electricity meter’s display is m3
without decimals.
1000 l = 1 m3, 1000 / 25 = 40 > pulse division factor to be set to 40.
The electricity meter count will be incremented by one at every 40 pulses, i.e. indication in m3
without decimals. The most frequently used pulse values appear from the table below.
Pulse value
l/Imp
Pulse value
Imp/m3
Pulse division factor
Display indication in ”m3
”
Pulse division factor
Display indication in ”l”
100 10 10 -
50 20 20 -
25 40 40 -
10 100 100 0.1
5.0 200 200 5
2.5 400 400 2.5
1.0 1000 1000 1
1000 1 1 1000
Pulse values for water meters
4.14.7.2 Example of pulse input from an electricity meter
The table below shows a similar list of pulse values for electricity meters.
Pulse value
Wh/imp
Pulse value
Imp/kWh
Pulse division factor
Display indication in kWh
100000 0.01 -
10000 0.1 0.1
1000 1 1
16.67 60 60
78/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Pulse value
Wh/imp
Pulse value
Imp/kWh
Pulse division factor
Display indication in kWh
13.33 75 75
8.333 120 120
4.167 240 240
2.941 340 340
2.083 480 480
1.667 600 600
1.000 1000 1000
0.100 10000 -
Pulse values for electricity meters
4.14.8 Pulse outputs in module area
The pulse outputs in the module area can be configured for pulse outputs for both active and
reactive energy.
By default, the pulse outputs send 1 pulses/kWh. It can, however, be configured between 1 – 1000
pulse/kWh. In addition, the pulse width can be configured for 30 or 80 msecs.
Note When selecting pulse/kWh-factor and pulse width, be aware that the number of pulses at
maximum load do not exceed the number which the meter is able to send via the pulse
output.
Pulse value
Imp/kWh, Imp/kvar
Pulse duration/
pulse pause
30 msecs. 80 msecs.
1 100A 100A
10 100A 100A
100 100A 100A
1000 86A 32A
Maximum load current at different pulse/kWh values
4.14.9 S0 output
The S0 output provides pulses/kWh permanently. The pulses are synchronized with the S0 LED.
For number of pulses/kWh, please see "Electrical specifications" .
The S0 output is specified according to the DIN 43864 standard. The figures below show the
placement of the S0 output connector.
The maximum voltage that can be connected to the S0 output is 27 V DC (at 1 kW), and the
maximum current through the output is 27 mA.
11
79/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
The S0 output on a three-phase and a CT meter
The S0-LED will in normal operation always flash according to the consumption, i.e. A+. However,
it can change if the meter switches to verification mode. Then it will follow the activated quadrant.
The table below lists the technical specification for the S0 output.
The status of the
pulse sensor
Test conditions Test data
Supply voltage
UB
Internal resistance
RV
Current through the
S0 output
On (active) 18 V DC 1 kΩ i > 10 mA
Off (inactive) 27 V DC 1 kΩ i < 2 mA
S0 technical specification
On the three-phase direct meter with auxilliary power supply (APS), the S0 output is not available.
The S0 output can then only be achieved as a module interface.
4.14.10 Auxiliary power supply (APS)
As an option, the three-phase direct meter can be configured with auxiliary power supply (APS)
functionality. This allows to supply the meter with 230VAC on a separate input as shown in the
figure below.
The functionality is useful when an external breaker is installed before the meter in an installation.
80/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
APS functionality
Important It is important that the APS is connected to phase L3.
Note When the meter is configured for APS, it does not have an S0 output as the connector is
used for the 230 V APS.
81/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
5 Ordering specification______________________________________________________________This chapter contains order information on all aspects of OMNIPOWER®, including hardware,
software and all other relevant configurations such as customer label, sealing, packaging, etc.
5.1 Meter configuration
The configuration of OMNIPOWER® is divided into two main parts:
· Hardware configuration
Specifies the meter regarding number of phases, current specification, internal breaker,integrated radio, etc. It also defines the meter type number which is printed on the meter front.
· Software configuration
Specifies the configurable setup and meter variables including display setup, smart disconnectsettings, tariff and load control plans, voltage quality parameters, etc.
A number of related extended software configuration options are available:
· Display setup
· Tariff setup
· Load control setup
· Smart disconnect
· Sealable push button setup
· Analysis logger setup
· 1107 setup
Each of them has a related separate order form. The different order forms are shown in the
following sections.
5.2 Hardware configuration
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14-X16
68
X1 – Meter type
OMNIPOWER® single-phase
6
OMNIPOWER® CT 5
OMNIPOWER® three-phase
4
X2 – Type no. version
OMNIPOWER® 1
82/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14-X16
X3 – Housing
Standard 1
ST-meter (BS7856)Single-phase
2
DIN rail meter 4
X4 – Measuring
systems
1 system 1
2 systems (Aron) 2
3 systems 3
X5 – Current range
Directmeters
CT meters
5(100)A 1(6)A 1
5(65)A 4
5(6)A 5
10(60)A 6
10(80)A 7
5(80)A 8
5(63)A 9
X6 – Accuracy class
Directmeters
CT meters
Class A A
Class B Class B B
Class C C
Class 2 2
Class 1 Class 1 1
Class 0,5 5
X7 – Generation
Generation D** D
Generation N*** N
X8 – Variant
1st Variant 1
2nd variant* 2
X9 – Energy type
A+ 1
A+/A- 2
A+/R+** 3
A+/A-/R+/R 4
X10 – Breaker
83/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14-X16
No breaker 0
Dual breaker*** (single-phase only)
2
Standard breaker*** 3
DIN rail breaker 4
X11 – Communication
No radio 0
Radio (For OMNIA®) 1
X12 – Supply back-up
Supercap*** 0
Supercap + battery 1
X13 – Interface
S0 output 1
APS*** 2
X14X15X16 – Country
code
Denmark 010
Denmark 011
Denmark 012
Russia 025
Spain 031
Turkey 035
Croatia 036
Serbia 037
Norway 040
Slovakia 042
Czech Republic 043
Hungary 044
Latvia 045
Lithuania 049
United Kingdom 050
Austria 055
Austria 056
Switzerland (Italian part) 059
Estonia 061
Switzerland (Germanpart)
063
Poland 064
Switzerland (French part) 065
Iceland 067
Germany 070
Belgium 078
The Netherlands 080
Finland 084
Finland (Aland island) 086
84/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10 X11 X12 X13 X14-X16
Sweden 090
Saudi Arabia 110
South Africa 120
Ghana 121
Chile 151
* Does not support 1107 communication protocol.
** OMNIPOWER® CT meters only.
*** OMNIPOWER® direct meters only.
5.3 Software configuration
Z1 Z2 Z3 Z4
Z1 – Decimals in display
Direct meters CT meters
7.0 7.0 1
6.1 7.1 2
7.2 7.2 3
6.3 NA 4
Z2 – LED configuration
LED off at no consumption 1
LED on at no consumption 2
Z3 – Primary module configuration I/O 1 I/O 2
No function _ _ 00
4-tariff Input Input 01
4-tariff inverted Input Input 02
Pulse in / Alarm in Input Input 03
Pulse in / Alarm in inverted Input Input 04
Pulse in / A+ out Input Output 05
R+ out / A+ out Output Output 06
2-tariff / Alarm in Input Input 07
2-tariff inverted / Alarm in Input Input 08
2-tariff / Alarm in inverted Input Input 09
2-tariff inverted / Alarm in inverted Input Input 10
2-tariff / A+ out Input Output 11
2-tariff inverted / A+ out Input Output 12
Pulse in / 2-tariff Input Input 13
Pulse in / 2-tariff inverted Input Input 14
Debiting stop pulse / - Input _ 15
A- out / A+ out Output Output 16
Load control load / Status control Input Output 17
Pulse in / Load tariff sync Input Output 18
Pulse in inv. / Load tariff sync Input Output 19
Pulse in / Load tariff sync inverted Input Output 20
Pulse in inv. / Load tariff sync inverted Input Output 21
85/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Z1 Z2 Z3 Z4
4-tariff sync load control Input Input 22
4-tariff sync load control inverted Input Input 23
Load control 1 / Load control 2 Output Output 26
Pulse in / Load control Input Output 27
Pulse in / Toggle Load control 1 & 2 Input Output 28
Earth fault I2C I2C 29
Z4 - Integration period / load profile period
15 min. 2
30 min. 3
60 min. 4
Z5 Z6 Z7 Z8
Z5 - Display configuration
See the display order form or contact Kamstrup A/S
Z6 - Debiting stop date
1 012 023 034 045 0523 2324 2425 2526 2627 2728 28Z7 - Debiting logging interval
None (externally controlled) 00Monthly 01Every second month, January 02Every second month, February 03Every third month, January 04Every third month, February 05Every third month, March 06Every six month, January 07Every six month, February 08Every six month, March 09Every six month, April 10Every six month, May 11Every six month, June 12Yearly, January 13Yearly, February 14Yearly, March 15
86/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Z5 Z6 Z7 Z8
Yearly, April 16Yearly, May 17Yearly, June 18Yearly, July 19Yearly, August 20Yearly, September 21Yearly, October 22Yearly, November 23Yearly, December 24Z8 - Pulse out length / alarm input
30 ms pulse length / alarm input deactivated 130 ms pulse length / alarm input active 280 ms pulse length / alarm input deactivated 380 ms pulse length / alarm input active 4
Z9 Z10 Z11 Z12
Z9 - Disconnect setup
See the disconnect order form or contact Kamstrup A/S No disconnect setup 000Default setup 001Z10 - Analysis logger setup
See the analysis logger order form or contact Kamstrup A/SDefault setup 000Z11 - GMT
0 London time 001 + 1 Hour (DK/NO/SE/DE/FR/ES) 012 + 2 Hours ( FI) 023 + 3 Hours 034 + 4 Hours 045 + 5 Hours 056 + 6 Hours 067 + 7 Hours 078 + 8 Hours 089 + 9 Hours 0910 + 10 Hours 1011 + 11 Hours 1112 + 12 Hours 12-11 - 11 Hours 13-10 - 10 Hours 14-9 - 9 Hours 15-8 - 8 Hours 16-7 - 7 Hours 17-6 - 6 Hours 18-5 - 5 Hours 19
87/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Z9 Z10 Z11 Z12
-4 - 4 Hours 20-3 - 3 Hours 21-2 - 2 Hours 22-1 - 1 Hours 23Z12 - Unit pulse input
None 00kWh 01m3 02L 03
Z13 Z14 Z15 Z16 Z17 Z18 Z19 Z20
Z13 - Tariff control plan
See the tariff order form or contactKamstrup A/STariff disabled 000Module port Control (used for 230VAC input tariff control)
001
Register control 002Customized tariff control table xxxZ14 – Load control plan
See the load control order form or contactKamstrup A/SLoad control disabled 000Register control 001Customized load control table xxxZ15 - Daylight saving time /
summer/winter time table
None 000EU 001Z16 - Frequency code protocol
None (only for meters without radio) 000CH 318 RF 318EU 319 RF 319SE 326 RF 326SE 328 RF 328SE 329 RF 329NO 338 RF 338NO 339 RF 339DK 348 RF 348DK 349 RF 349FI 359 RF 359PL 369 RF 369AT 379 RF 379
88/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Z13 Z14 Z15 Z16 Z17 Z18 Z19 Z20
Z17 – Push button 2 setup
See the PB2 order form or contactKamstrup A/SNo PB2 setup 000Z18 - 1107 configuration (only for FW
5098-736 and 50981040)
See the 1107 order form or contactKamstrup A/SDisabled 000Mode A and C, UD1 001Mode A and C, UD2 002Z19 - Breaker position
Undefined (only for meters withoutbreakers)
0
Connected 1Disconnected 2Z20 – Calendar Setup
See Calendar setup order form or contactKamstrup A/SNo exception days 000Customized exception day setup xxx
Z21 Z22 Z23 Z24 Z25
Z21 Transformer ratio14
5A / 5A 1A / 1A 00110A / 5A 2A / 1A 00215A / 5A 3A / 1A 00320A / 5A 4A / 1A 00450A / 5A 10A / 1A 01075A / 5A 15A / 1A 015100A / 5A 20A / 1A 020120A / 5A 24A / 1A 024150A / 5A 30A / 1A 030160A / 5A 32A / 1A 032200A / 5A 40A / 1A 040300A / 5A 60A / 1A 060500A / 5A 100A / 1A 1001000A / 5A 200A / 1A 2001500A / 5A 300A / 1A 3002000A / 5A 400A / 1A 4003000A / 5A 600A / 1A 600Z22 Transformer ratio (unlocked / locked)**
Unlocked 1
89/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Z21 Z22 Z23 Z24 Z25
Locked 2Z23 Load profile, based on**
Primary energy 1Secondary energy 2Z24 Pulse output (module)**
Based on secondary energy 0Based on primary energy 1Z25 Debiting 2 interval
Daily 1Weekly 2Monthly 3** OMNIPOWER® CT meter only.
Z26 Z27 Z28 Z29 Z30
Z26 Alarm Configuration
No alarms enabled 000
Customized alarm configuration xxxZ27 Load Profile Data (DLMS)
Absolute values 1Delta values 2Z28 Local Interface Encryption
Enabled 1Disabled 2Partly enabled 3Z29 Load Profile Configuration
A+ 1A+/A- 2A+/A-/R+/R- 3A+/A-/R1/R2/R3/R4 4A+/A-/R+/R-/R1/R2/R3/R4 5P+/P-/Q+/Q- 6Z30 Debit2 Logger Configuration
Profile 01 – Default 4Q 1Profile 04 – Default 2Q (A+/A-) 4Profile 05 – Default 2Q (A+/R+) 5Profile 06 – Default 1Q 6
Z31 Z32 Z33 Z34
Z32 Analysis Logger Configuration
Profile 01 – Default 4Q 01
90/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Z31 Z32 Z33 Z34
Profile 01 – Default 2Q (A+/A-) 02Profile 01 – Default 2Q (A+/R+) 03Profile 01 – Default 1Q 04Z32 Analysis Logger Configuration
Profile 01 – Default 3P-4Q 01Profile 02 – Default 1P-4Q 02Profile 03 – Default 3P-2Q (A+/A-) 03Profile 04 – Default 1P-2Q (A+/A-) 04Profile 05 – Default 3P-2Q (A+/R+) 05Profile 06 – Default 1P-2Q (A+/R+) 06Profile 07 – Default 3P-1Q 07Profile 08 – Default 1P-1Q 08Z33 Daily Logger Configuration
Profile 01 – Default 01Z34 Energy Format
Energy registers with 2 decimals 2Energy registers with 3 decimals 3
5.4 Display configuration
The possible display readings depend on the chosen energy. In addition, it must be considered
whether leading zeroes should be indicated in the energy display, and whether OBIS codes and
actual quadrant indication are required. Display readings are shown with OBIS codes.
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Active positive energy A+ 1.8.0
Active negative energy A- 2.8.0
Reactive positive energy R+ 3.8.0
Reactive negative energy R- 4.8.0
A+, A- active energy numerical
(A1423)
_ 15.8.0 _
Nett active energy(|A+| - |A-|) NET 16.8.0
Reactive energy R1 R1 5.8.0
Reactive energy R2 R2 6.8.0 _ _ _ _
Reactive energy R3 R3 7.8.0 _ _ _ _
Reactive energy R4 R4 8.8.0
91/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Apparent positive energy E+ 9.8.0
Apparent negative energy E- 10.8.0
Active positive energy, T1 A+/T1 1.8.1 _
Active positive energy, T2 A+/T2 1.8.2 _
Active positive energy, T3 A+/T3 1.8.3 _
Active positive energy, T4 A+/T4 1.8.4 _
Active positive energy, T5 A+/T5 1.8.5 _
Active positive energy, T6 A+/T6 1.8.6 _
Active positive energy, T7 A+/T7 1.8.7 _
Active positive energy, T8 A+/T8 1.8.8 _
Active negative energy, T1 A-/T1 2.8.1 _
Active negative energy, T2 A-/T2 2.8.2 _
Active negative energy, T3 A-/T3 2.8.3 _
Active negative energy, T4 A-/T4 2.8.4 _
Active negative energy, T5 A-/T5 2.8.5 _
Active negative energy, T6 A-/T6 2.8.6 _
Active negative energy, T7 A-/T7 2.8.7 _
Active negative energy, T8 A-/T8 2.8.8 _
Reactive positive energy, T1 R+/T1 3.8.1 _
Reactive positive energy, T2 R+/T2 3.8.2 _
Reactive positive energy, T3 R+/T3 3.8.3 _
Reactive positive energy, T4 R+/T4 3.8.4 _
Reactive positive energy, T5 R+/T5 3.8.5 _
Reactive positive energy, T6 R+/T6 3.8.6 _
Reactive positive energy, T7 R+/T7 3.8.7 _
92/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Reactive positive energy, T8 R+/T8 3.8.8 _
Reactive negative energy, T1 R-/T1 4.8.1 _
Reactive negative energy, T2 R-/T2 4.8.2 _
Reactive negative energy, T3 R-/T3 4.8.3 _
Reactive negative energy, T4 R-/T4 4.8.4 _
Reactive negative energy, T5 R-/T5 4.8.5 _
Reactive negative energy, T6 R-/T6 4.8.6 _
Reactive negative energy, T7 R-/T7 4.8.7 _
Reactive negative energy, T8 R-/T8 4.8.8 _
Resettable counter, Active positive
energy
A+/TRIP 1.128.0 _
Resettable counter, Active negative
energy
A-/TRIP 2.128.0 _
Resettable counter, Reactive positive
energy
R+/TRIP 3.128.0 _
Resettable counter, Reactive
negative energy
R-/TRIP 4.128.0 _
Resettable counter, Apparent positive
energy
E+/TRIP 9.128.0 _
Resettable counter, Apparent
negative energy
E-/TRIP 10.128.0 _
Active positive energy phase L1 A+/L1 21.8.0 _
Active positive energy phase L2 A+/L2 41.8.0 _
Active positive energy phase L3 A+/L3 51.8.0 _
Active negative energy phase L1 A-/L1 22.8.0 _
Active negative energy phase L2 A-/L2 42.8.0 _
Active negative energy phase L3 A-/L3 52.8.0 _
Actual active positive power P+ 1.7.0 _
Actual active negative power P- 2.7.0 _
Actual reactive positive power Q+ 3.7.0 _
93/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Actual reactive negative power Q- 4.7.0 _
Apparent positive power S+ 9.7.0 _
Apparent negative power S- 10.7.0 _
Active positive max power P+M 1.6.0 _
Time stamp active positive max
power
TIME/DAT
E
1.6.0 _
Active negative max power P-M 2.6.0 _
Reactive positive max power Q+M 3.6.0 _
Time stamp reactive positive max
power
TIME/DAT
E
3.6.0 _
Reactive negative max power Q-M 4.6.0 _
Active positive max power tariff 1 P+M/T1 1.6.1 _
Time stamp active positive max
power tariff 1
TIME/DAT
E
1.6.1 _
Active positive max power tariff 2 P+M/T2 1.6.2 _
Time stamp active positive max
power tariff 2
TIME/DAT
E
1.6.2 _
Reactive positive max power, T1 Q+M/T1 3.6.1 _
Time stamp reactive positive max
power, T1
TIME/DAT
E
3.6.1 _
Reactive positive max power, T2 Q+M/T2 3.6.2 _
Time stamp reactive positive max
power, T2
TIME/DAT
E
3.6.2 _
Accumulated active positive max
power
P+M/ACC 1.2.0 _
Accumulated active negative max
power
P-M/ACC 2.2.0 _
Accumulated reactive positive max
power
Q+M/ACC 3.2.0 _
Accumulated reactive negative max
power
Q-M/ACC 4.2.0 _
Accumulated active positive max
power tariff 1
P+M1/ACC1.2.1 _
Accumulated active positive max
power tariff 2
P+M2/ACC1.2.2 _
94/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Pulse input _ 0.128.1 _
Display test _ _ _
Meter number 1 NUM/1 0.0.1 _
Meter number 2 NUM/2 0.0.2 _
Meter number 3 NUM/3 0.0.3 _
Meter serial number SER/NUM 96.1.0 _
Special data 1 SPC/1 0.130.1 _
Actual voltage phase L1 U-L1 32.7.0 _
Actual voltage phase L2 U-L2 52.7.0 _
Actual voltage phase L3 U-L3 72.7.0 _
Actual current phase L1 I-L1 31.7.0 _
Actual current phase L2 I-L2 51.7.0 _
Actual current phase L3 I-L3 71.7.0 _
Date and Time TIME/DAT
E
1.0.0 _
Number of debiting periods RST 0.1.0 _
Actual positive power phase L1 P+/L1 21.7.0 _
Actual positive power phase L2 P+/L2 41.7.0 _
Actual positive power phase L3 P+/L3 61.7.0 _
Historical data _ 98.1.0 _ _
Load profile data _ 99.1.0 _ _
Power threshold value PTH 96.51.1 _
Power threshold counter PTH/CNT 95.51.2 _
Hour counter HRS 96.8.0 _
Call CALL _ _ _
ROM checksum CSUM 96.54.1 _
95/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Software number _ 0.2.0 _
Meter status INFO 97.97.0 _
Active positive max. power per day MAX 1.16.0 _
RTC active positive max. power per
day
TIME/DAT
E
1.16.0 _
Active positive min. power per day MIN 1.13.0 _
RTC active positive min. power per
day
TIME/DAT
E
1.13.0 _
Load profile event status _ _ _
Power factor L1 PF-1 33.7.0 _
Power factor L2 PF-2 53.7.0 _
Power factor L3 PF-3 73.7.0 _
Power factor Total PF 13.7.0 _
Frequency FREQ 14.7.0 _
Total harmonic distortion, Voltage L1 THD/U-L1 32.7.124 _
Total harmonic distortion, Voltage L2 THD/U-L2 52.7.124 _
Total harmonic distortion, Voltage L3 THD/U-L3 72.7.124 _
List of available display readings from the order form "Display configuration OMNIPOWER®" (doc.5811-2371)
For direct meters only
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Manual disconnect _ _ _ _
Active positive energy
Prepayment
_ 130.0.0 _
Active positive energy
Prepayment - credit
_ 130.0.1 _
Total harmonic distortion, Current
L1
THD/I-L1 31.7.124 _
Total harmonic distortion, Current
L2
THD/I-L2 51.7.124 _
96/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Total harmonic distortion, Current
L3
THD/I-L3 71.7.124 _
List of available display readings from the order form "Display configurationOMNIPOWER®" (doc.5811-2371)
For CT meters only
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Transformer ratio CTR 0.4.2 _
Secondary active positive energy A+ S 1.8.0
Secondary active negative
energy
A- S 2.8.0
Secondary reactive positive
energy
R+ S 3.8.0
Secondary reactive negative
energy
R- S 4.8.0
Secondary reactive energy R1 R1 S 5.8.0
Secondary reactive energy R4 R4 S 8.8.0
Secondary active positive energy,
T1
A+ S/T1 1.8.1 _
Secondary active positive energy,
T2
A+ S/T2 1.8.2 _
Secondary active positive energy,
T3
A+ S/T3 1.8.3 _
Secondary active positive energy,
T4
A+ S/T4 1.8.4 _
Secondary active positive energy,
T5
A+ S/T5 1.8.5 _
Secondary active positive energy,
T6
A+ S/T6 1.8.6 _
Secondary active positive energy,
T7
A+ S/T7 1.8.7 _
Secondary active positive energy,
T8
A+ S/T8 1.8.8 _
Secondary active negative
energy, T1
A- S/T1 2.8.1 _
97/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Secondary active negative
energy, T2
A- S/T2 2.8.2 _
Secondary active negative
energy, T3
A- S/T3 2.8.3 _
Secondary active negative
energy, T4
A- S/T4 2.8.4 _
Secondary active negative
energy, T5
A- S/T5 2.8.5 _
Secondary active negative
energy, T6
A- S/T6 2.8.6 _
Secondary active negative
energy, T7
A- S/T7 2.8.7 _
Secondary active negative
energy, T8
A- S/T8 2.8.8 _
Secondary reactive positive
energy, T1
R+ S/T1 3.8.1 _
Secondary reactive positive
energy, T2
R+ S/T2 3.8.2 _
Secondary reactive positive
energy, T3
R+ S/T3 3.8.3 _
Secondary reactive positive
energy, T4
R+ S/T4 3.8.4 _
Secondary reactive positive
energy, T5
R+ S/T5 3.8.5 _
Secondary reactive positive
energy, T6
R+ S/T6 3.8.6 _
Secondary reactive positive
energy, T7
R+ S/T7 3.8.7 _
Secondary reactive positive
energy, T8
R+ S/T8 3.8.8 _
Secondary reactive negative
energy, T1
R- S/T1 4.8.1 _
Secondary reactive negative
energy, T2
R- S/T2 4.8.2 _
Secondary reactive negative
energy, T3
R- S/T3 4.8.3 _
Secondary reactive negative
energy, T4
R- S/T4 4.8.4 _
98/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description OBIS Auto
scroll
Manual
scroll
Battery Manual
Utility
Secondary reactive negative
energy, T5
R- S/T5 4.8.5 _
Secondary reactive negative
energy, T6
R- S/T6 4.8.6 _
Secondary reactive negative
energy, T7
R- S/T7 4.8.7 _
Secondary reactive negative
energy, T8
R- S/T8 4.8.8 _
List of available display readings from the order form "Display configuration OMNIPOWER®" (doc.5811-2371)
5.5 Tariff control configuration
For further information about configuration of tariffs, please contact Kamstrup A/S.
5.6 Load control configuration
For further information about configuration of load control, please contact Kamstrup A/S.
5.7 Smart disconnect setup
For further information about configuration of smart disconnect, please contact Kamstrup A/S.
5.8 Sealable push button configuration
As an option, the meter push buttons have a number of functionalities (as described in "Push
button functionalities ").
The right side positioned push button can be configured regarding which functions are enabled or
not. The configuration must be done when ordering of the meter. The configuration options for right
side positioned sealable push button are listed in the table below.
Description Enable/Disable
PB2 functionality
Subfunctions
Debiting stop
Set date and time
Adjust time
Set optical interface
View manual utility display list Remember to configure the display list
Set meter number
23
99/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Description Enable/Disable
Release permanent tamper This function is for future use and is not available yet
Module installation mode This function is for future use and is not available yet
Manual selection of tariff plan
Manual selection of load control
plan
Test of load control plan
List of available functions attached to the sealable push button
This list is part of the OMNIPOWER® meter configuration order form.
5.9 1107 protocol configuration
For further information about configuration of the 1107 protocol, please contact Kamstrup A/S.
5.10 Customer labels
The label consists of two parts:
· a meter label describing the choices made under type number.
· a customer label created on basis of the customer's wishes.
Note The customer label must be approved by the customer before an order can be createdto the customer.
Both label parts are engraved with laser on front of the meter.
Four standard customer labels without customer logo are available:
2019000 No bar code No meter number
2019001 Code 128 Meter number = serial number
2019002 2 of 5 interleaved Meter number = serial number
2019003 Code 39 Meter number = serial number
The following information is required for the creation of a new customer label:
· The customer logo must be provided to the Electricity Product Group at Kamstrup A/S. The logomust be in black/white and in one of the following formats: JPG or WMF.
· Information about the bar code type to use and its content, serial number, meter number,installation number, and the position of numbers and bar code must also be provided.
When all information is available, a draft is prepared which must be approved by the customer.
The bar code should also be read by the customer in order to secure that his bar code reading
device can read the bar code.
100/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
After approval, a customer label no. 2019XXX is selected, and the number is released in the
Kamstrup ordering systems.
The customer label 2019xxx for OMNIPOWER® three-phase and single-phase meters
The customer label 2019xxx is of the same size on all meter types. This means that the same
customer label can be used both on the single-phase and the three-phase meters.
5.11 Sealing
The meter is/can be sealed on different levels. The verification cover is “lifetime” sealed, i.e. the
cover cannot be unsealed without damaging the cover and the meter. The meter cover can be
sealed by the utility as can the CCC module slot. Finally, the right push button also offers sealing of
its push action. Only authorized personnel is allowed to break the utility sealing.
101/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Sealing options for OMNIPOWER® single-phase and three-phase meter
5.12 Packing
OMNIPOWER® can be delivered in three ways:
· Boxes – 1 meter per box
· Boxes – 4 meters per box
· Pallets – 160 three-phase meters or 250 single-phase meters on a pallet.
102/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
5.12.1 Box solution
The meters are packed in boxes with either 1 or 4 in each box. 4-piece boxes are placed on pallets
with 40 boxes on each pallet as shown below.
5.12.2 Pallet solution
103/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
5.13 Accessories
SOFTWARE TOOL
METERTOOL OMNIPOWER® (configuration software) 68 99 570
VARIOUSThree-phase covers
Standard meter cover (for three-phase meters) 59 60 315
Long meter cover, 60 mm (for three-phase meters) 59 60 316
Extra long meter cover, 100 mm (for three-phase meters) 59 60 317
Single-phase covers
Standard meter cover (for single-phase meters) 59 60 322
Long meter cover, 60 mm (for single-phase meters) 59 60 323
Extra long meter cover, 100 mm (for single-phase meters) 59 60 xxx
(not availab le yet)
Single-phase covers for ST-meter
Standard meter cover (for single-phase meters) 59 60 617
Long meter cover, 60 mm (for single-phase meters) 59 60 323
104/104Kamstrup A/S • 5512-1235_GB_H1_07-2020_AZL_Original version
Optical reading head with USB connector 66 99 099
Optical reading head with 9-pole D-sub connector 66 99 102
METERTOOL OMNIPOWER® kit (RS232 module with USB connector) 68 30 017
Pins, 50 pcs. 68 50 102
Cable sockets, 50 pcs. 68 50 103