Date post: | 23-Oct-2015 |
Category: |
Documents |
Upload: | ieremeiov-vladimir |
View: | 177 times |
Download: | 10 times |
Low Voltage offerPower Factor Correction and harmonic filtering
Catalog2009
Contents
Chapter 1Discover Energy Efficiency p. 1
Chapter 2Reactive energy p. 2The basis p. 3Energy Effiiciency with Power Factor Correction p. 5Practical calculation of an installation p. 6Reactive energy correction in an electrical installation p. 8Power Factor Correction type: fixed or automatic p. 10
Chapter 3How to select power factor correction devices p. 15General information about harmonics p. 16Causes and effects of harmonics p. 18Choosing power factor correction devices p. 20Choosing the frequency of detuned reactors p. 22
Chapter 4Capactors p. 24
Chapter 5Detuned reactors p. 40
Chapter 6Power factor controllers p. 45
Chapter 7Power factor correction modules p. 50
Chapter 8Power factor correction solutions p. 60
Chapter 9Filtering solutions p. 78
What do we call Energy Efficiency ?
P.1
>
Energy Efficiency: a common concern!As electricity is the major contributor to greenhouse gases, Energy Efficiency is now a common concern for of all actors in the market. Reduce electricity consumption and costs and improve power quality and availability are now growing demands, more particularly due to:● the commitment of many industrialised countries to reduce their collective emissions of greenhouse gases as well as the implementation of local regulations and incentive schemes● the increasing use of electronic devices leading to power quality issues and energy consumption rise
Energy Efficiency thanks to power factor correctionImplementing power factor correction and harmonic filtering solutions enable to:● reduce your electricity bill● increase available power● reduce the impacts of harmonics
Moreover, energy savings produced by power factor correction help protecting the environment by reducing CO2 emissions related to power generation.
Achieve more with a successful optimizationThere are three steps for a successful optimization of your installation: ● measure and/or gather the electrical network data● understand, establish diagnostic and decide the corrective action to be taken ● act, clean up, correct power factor, install backup networks
In any case, the most important factor is to correct and monitor over time the effectiveness of the solution.
Reduction of energy consumption
CO2 emissions savings
Improvement of power quality
1
Reactive energy
The basis p. 3
Energy Effiiciency with Power Factor Correction p. 5
Practical calculation of an installation p. 6
Reactive energy correction in an electrical installation p. 8
Power Factor Correction type: fixed or automatic p. 10
Q (kVAr)
PM
V
I
PM
V
I
P
P
SQ
P
cos ϕ = P / S
S = P + Q
(kVA)
P (kW)
M M A
ϕ
Fig. 2a: power flow in an installation where cosine φ = 0.78
Fig. 2b: power flow in an installation where cosine φ = 0.98
P.3
Q (kVAr)
PM
V
I
PM
V
I
P
P
SQ
P
cos ϕ = P / S
S = P + Q
(kVA)
P (kW)
M M A
ϕ
Fig. 1: reactive energy is consumed between the inductive loads and the source
Fig. 3: cosine φ as a representation of the electrical efficiency of an installation
The basis
The nature of energy
● Active energy All electrical devices powered by AC current convert the electrical energy supplied into mechanical work and heat. This energy is measured in kWh and is called active energy. The loads absorbing only this type of energy are called resistive loads.
● Reactive energy Some loads require magnetic fields to operate (motors, transformers, etc.) and consume another type of energy called reactive energy. This can be explained as follows: these loads (called inductive loads) absorb energy from the network when the magnetic fields required to operate them are generated and they discharge it when these fields are destroyed. This transfer of energy between the loads and the source (fig. 1) causes voltage losses and drops in conductors and therefore consumption of extra energy that cannot be directly used by loads.
Power flow in an installation
The available power output of an installation increases indirectly as cosine φ increases. The instantaneous power of an installation consists of two components: the oscillating power whose frequency is twice the fundamental frequency and the average power (Pm = VI cos φ), which represents the output or active power of the installation and which is constant. Fig. 2 shows that the more the cos φ of an installation increases (and the closer it is to 1), the greater the average power of the installation.
Power factor (Cosine φ)
The presence of inductive loads in an installation causes a phase shift between the current wave and the voltage. The angle φ represents this phase shift and gives the ratio between the reactive current (inductive) of an installation and its active current. The same ratio exists between the active and reactive energies or powers.The cosine φ therefore indicates the ratio between the active and apparent power of the installation (the maximum number of kVA that it can use). That is why cosine φ indicates the «electrical efficiency» of an installation (fig. 3).
S
Q
P
cos j = P/S
j
2
Q (kVAr)
S = √P² + √Q²
(kVA)
P (kW)
M M A
The basis (continued)
Practical calculation of reactive power
Calculations in the three-phase example were as follows: ○ Pn = power supplied to the rotary axis = 51 kW ○ P = active consumed power = Pn/µ = 56 kW ○ S = apparent power = P/cos φ = P/0.86 = 65 kVA hence:
Q = (√S2 + P2) = (√652 +562)6 = 33 kVAr
The average power factor values for various loads are given below.
Power factor of the most common loads
P. 4
Type of circuit Apparent power S (kVA) Active power P (kW) Reactive power Q (kVAr)
Single-phase (Ph + N)Single-phase (Ph + Ph)
S = V x IS = U x I
P = V x I x cos φP = U x I x cos φ
P = V x I x sin φP = U x I x sin φ
Example: 5 kW load Cos φ= 0.5
10 kVA 5 kW 8,7 kVAr
Three-phase (3 Ph or 3 Ph + N)
S = √3 x U x I P = √3 U I cos φ Q = √3 U I sin φ
Device Load Cos φ Tan φ
Ordinary asynchronous motor 0 % 0.17 5.8
25 % 0.55 1.52
50 % 0.73 0.94
75 % 0.8 0.75
100 % 0.85 0.62
Incandescent lamps 1 0
Fluorescent lamps 0.5 1.73
Discharge lamps 0.4 à 0.6 2.29 à 1.33
Resistance furnaces 1 0
Induction furnaces 0.85 0.62
Dielectric heating furnaces 0.85 0.62
Resistance welding machine 0.8 à 0.9 0.75 à 0.48
Single-phase static arc-welding centres 0.5 1.73
Rotary arc-welding sets 0.7 à 0.9 1.02
Arc-welding transformers/rectifiers 0.7 à 0.9 1.02 à 0.75
Arc furnaces 0.8 0.75
Fig. 4: cos φ of the most commonly-used devices
2
Increased available power
A high power factor optimises the components of an electrical installation by increasing their electrical efficiency. Installing capacitors reduces reactive energy consumption between the source and the loads. The capacitors supply reactive energy by discharging into the installation from their upstream connection point. The power available at the secondary of an MV/LV transformer can therefore be increased by fitting a power factor correction device in the low voltage part. The table in figure 5 shows the increased active power (kW) that can be supplied by a transformer by correcting the power factor up to cos φ = 1.
P.5
Fig.5: increase in the power available at a transformer secondary according to the cos φ of the load
Fig. 6: multiplying factor for the conductor cross-section according to the cos φ of the installation
Fig. 7: loss reduction due to the Joule effect.
Initial cos φ Increased available power
1 0 %
0.98 + 2.0 %
0.95 + 5.2 %
0.90 + 11.1 %
0.85 + 17.6 %
0.80 + 25 %
0.70 + 42.8 %
0.65 + 53.8 %
0.50 + 100 %
Initial cos φ Cable cross-section multiplying factor
1 1
0.80 1.25
0.60 1.67
0.40 2.50
Smaller conductor cross-section
Installing a power factor correction device in an installation allows the cross-section of the conductors to be reduced, as less current is output from the compensated installation for the same active power. The table in figure 6 shows the multiplying factor for the cross-section of the conductor according to the cos φ of the installation.
Reduced losses
● Reduced Joule effect lossesInstalling capacitors allows the Joule effect losses to be reduced (temperature rise) in the conductors and transformers. The meter records these losses as consumed energy (kWh). The losses are proportional to the square of the current. The following formula can be used to determine the loss reduction according to the cos φ of the installation:
Final losses = (initial cos φ)² Initial losses final cos φ
● Example: Loss reduction in a 630 kVA transformer, Pcu = 6,500 W with an initial cos φ of 0.7. When by power factor correction, we obtain final cos φ = 0.98, the new losses become: 3.316 W.
Reduced voltage drops
Installing capacitors allows the voltage drops to be reduced upstream of the point where the power factor correction device is connected.
0 %
–10 %
–20 %
–30 %
–40 %
–50 %
–60 %
–70 %
–80 %
0,5 0,55 0,6 0,65 0,7 0,75 0,8 0,85 0,9 0,95 1
REDUCTION DES PERTES QUAND COS φ = 1
RED
UC
TIO
N D
ES P
ERTE
S (%
)
COS ϕ INITIAL
2Energy efficiency with Power Factor Correction
LOSSES REDUCTON WhEN COS φ = 1
LOS
SE
S R
ED
UC
TON
Wh
EN
CO
S φ
= 1
P.6
Calculation for an electrical installation
General method From the data supplied by the manufacturers of the various loads, such as the active power, load factor, cos φ, etc. and if the simultaneity factor of each load in the installation is known, the levels of the active and reactive power consumed throughout the installation can be determined.
Simplified method A simplified method of calculating the power factor correction requirements of an installation can be used provided that the following data is known: ○ the initial average cos φ, ○ the cos φ required, ○ the average active power of the installation.
This data can be obtained: ○ by calculation, as indicated for the general method ○ by estimation, according to the installed power They are used to perform the calculation with the help of the table.
Calculation using the table
● Example: Calculation of the reactive power required to compensate the following installation: ○ P = 500 kW, ○ initial cos φ = 0.75, ○ cos φ required = 0.98. From the table on the next page, we obtain a factor = 0.679. Multiplying this factor by the active power of the installation (500 kW) gives the reactive power to be installed: Q = 500 x 0.679 = 340 kVAr
Fig. 8: graphical representation of the calculation table (next page)
From measurements
Take several measurements downstream of the main circuit breaker with the installation under normal load conditions. Measure the following data: ○ active power (kW), ○ inductive power (kVAr), ○ cos φ. From this data, choose the average cos φ of the installation and check this value in the most unfavourable situation.
Cos φ cos φ to be obtained
0,9 0,92 0,94 0,96 0,98 1
0,4 1,805 1,861 1,924 1,998 2,085 2,288
0,45 1,681 1,784 1,988
0,5 1,248 1,529 1,732
0,55 1,035 1,316 1,519
0,6 0,849 1,131 1,334
0,65 0,685 0,966 1,169
0,7 0,536 0,811 1,020
0,75 0,398 0,453 0,519 0,591 0,679 0,882
0,8 0,266 0,321 0,387 0,459 0,541 0,750
0,85 0,02 0,191 0,257 0,329 0,417 0,620
0,9 0,058 0,121 0,192 0,281 0,484
Q = P × factor Q = P × 0,679
2
Calculation for an electrical installation (continued) From the power in kW and the cos φ of the installation
The table gives a coefficient, according to the cos φ of the installation before and after power factor correction. Multiplying this figure by the active power gives the reactive power to be installed.
P.7
Avant la Puissance du condensateur en kVAr à installer pa kW de charge, pour élever le facteur de puissancecompensation (cos φ ou tg φ ) à une valeur donnée
tg φ cos φ tg φ 0,75 0,59 0,48 0,45 0,42 0,39 0,36 0,32 0,29 0,25 0,14 0,00cos φ 0,8 0,86 0,9 0,91 0,92 0,93 0,94 0,95 0,96 0,97 0,99 1
2,29 0,40 1,541 1,698 1,807 1,836 1,865 1,896 1,928 1,963 2,000 2,041 2,149 2,2912,22 0,40 1,475 1,631 1,740 1,769 1,799 1,829 1,862 1,896 1,933 1,974 2,082 2,2252,16 0,42 1,41 1 1,567 1,676 1,705 1735 1,766 1,798 1,832 1,869 1,910 2,018 2,1612,10 0,43 1,350 1,506 1,615 1,644 1,674 1,704 1,737 1,771 1,808 1,849 1,957 2,1002,04 0,44 1,291 1,448 1,557 1,585 1,615 1,646 1,678 1,712 1,749 1,790 1,898 2,0411,98 0,45 1,235 1,391 1,500 1,529 1,559 1,589 1,622 1,656 1,693 1,734 1,842 1,9851,93 0,46 1,180 1,337 1,446 1,475 1,504 1,535 1,567 1,602 1,639 1,680 1,788 1,9301,88 0,47 1,128 1,285 1,394 1,422 1,452 1,483 1,515 1,549 1,586 1,627 1,736 1,8781,83 0,48 1,078 1,234 1,343 1,372 1,402 1,432 1,465 1,499 1,536 1,577 1,685 1,8281,78 0,49 1,029 1,186 1,295 1,323 1,353 1,384 1,416 1,450 1,487 1,528 1,637 1,7791,73 0,5 0,982 1,139 1,248 1,276 1,306 1,337 1,369 1,403 1,440 1,481 1,590 1,7321,69 0,51 0,937 1,093 1,202 1,231 1,261 1,291 1,324 1,358 1,395 1,436 1,544 1,6871,64 0,52 0,893 1,049 1,158 1,187 1,217 1,247 1,280 1,314 1,351 1,392 1,500 1,6431,60 0,53 0,850 1,007 1,116 1,144 1,174 1,205 1,237 1,271 1,308 1,349 1,458 1,6001,56 0,54 0,809 0,965 1,074 1,103 1,133 1,163 1,196 1,230 1,267 1,308 1,416 1,5591,52 0,55 0,768 0,925 1,034 1,063 1,092 1,123 1,156 1,190 1,227 1,268 1,376 1,5181,48 0,56 0,729 0,886 0,995 1,024 1,053 1,084 1,116 1,151 1,188 1,229 1,337 1,4791,44 0,57 0,691 0,848 0,957 0,986 1,015 1,046 1,079 1,113 1,150 1,191 1,299 1,4411,40 0,58 0,655 0,81 1 0,920 0,949 0,969 1,009 1,042 1,076 1,113 1,154 1,262 1,4051,37 0,59 0,618 0,775 0,884 0,913 0,942 0,973 1,006 1,040 1,077 1,118 1,226 1,3681,33 0,6 0,583 0,740 0,849 0,878 0,907 0,938 0,970 1,005 1,042 1,083 1,191 1,3331,30 0,61 0,549 0,706 0,815 0,843 0,873 0,904 0,936 0,970 1,007 1,048 1,157 1,2991,27 0,62 0,515 0,672 0,781 0,810 0,839 0,870 0,903 0,937 0,974 1,015 1,123 1,2651,23 0,63 0,483 0,639 0,748 0,777 0,807 0,837 0,873 0,904 0,941 1,982 1,090 1,2331,20 0,64 0,451 0,607 0,716 0,745 0,775 0,805 0,838 0,872 0,909 0,950 1,058 1,2011,17 0,65 0,419 0,672 0,685 0,714 0,743 0,774 0,806 0,840 0,877 0,919 1,027 1,1691,14 0,66 0,388 0,639 0,654 0,683 0,712 0,743 0,775 0,810 0,847 0,888 0,996 1,1381,11 0,67 0,358 0,607 0,624 0,652 0,682 0,713 0,745 0,779 0,816 0,857 0,996 1,1081,08 0,68 0,328 0,576 0,594 0,623 0,652 0,683 0,715 0,750 0,878 0,828 0,936 1,0781,05 0,69 0,299 0,545 0,565 0,593 0,623 0,654 0,686 0,720 0,757 0,798 0,907 1,0491,02 0,7 0,270 0,515 0,536 0,565 0,594 0,625 0,657 0,692 0,729 0,770 0,878 1,0200,99 0,71 0,242 0,485 0,508 0,536 0,566 0,597 0,629 0,663 0,700 0,741 0,849 0,9920,96 0,72 0,214 0,456 0,480 0,508 0,538 0,569 0,601 0,665 0,672 0,713 0,821 0,9640,94 0,73 0,186 0,427 0,452 0,481 0,510 0,541 0,573 0,608 0,645 0,686 0,733 0,794 0,9360,91 0,74 0,159 0,398 0,425 0,453 0,483 0,514 0,546 0,580 0,617 0,658 0,706 0,766 0,9090,88 0,75 0,739 0,8820,86 0,76 0,105 0,343 0,371 0,400 0,429 0,460 0,492 0,526 0,563 0,605 0,652 0,713 0,8550,83 0,77 0,079 0,316 0,344 0,373 0,403 0,433 0,466 0,500 0,537 0,578 0,626 0,686 0,8290,80 0,78 0,052 0,289 0,318 0,347 0,376 0,407 0,439 0,574 0,51 1 0,552 0,559 0,660 0,8020,78 0,79 0,026 0,262 0,292 0,320 0,350 0,381 0,413 0,447 0,484 0,525 0,573 0,634 0,7760,75 0,8 0,235 0,266 0,294 0,324 0,355 0,387 0,421 0,458 0,449 0,547 0,608 0,7500,72 0,81 0,209 0,240 0,268 0,298 0,329 0,361 0,395 0,432 0,473 0,521 0,581 0,7240,70 0,82 0,183 0,214 0,242 0,272 0,303 0,335 0,369 0,406 0,447 0,495 0,556 0,6980,67 0,83 0,157 0,188 0,216 0,246 0,277 0,309 0,343 0,380 0,421 0,469 0,530 0,6720,65 0,84 0,131 0,162 0,190 0,220 0,251 0,283 0,317 0,354 0,395 0,443 0,503 0,6460,62 0,85 0,105 0,135 0,164 0,194 0,225 0,257 0,291 0,328 0,369 0,417 0,477 0,6200,59 0,86 0,079 0,109 0,138 0,167 0,198 0,230 0,265 0,302 0,343 0,390 0,451 0,5930,56 0,87 0,053 0,082 0, 111 0,141 0,172 0,204 0,238 0,275 0,316 0,364 0,424 0,5670,53 0,88 0,029 0,055 0,084 0,114 0,145 0,177 0,21 1 0,248 0,289 0,337 0,397 0,5400,51 0,89 0,028 0,057 0,086 0,117 0,149 0,184 0,221 0,262 0,309 0,370 0,5120,48 0,90 0,029 0,058 0,089 0,121 0,156 0,193 0,234 0,281 0,342 0,484
0,132 0,370 0,398 0,426 0,456 0,487 0,519 0,553 0,590 0,631 0,679
0,200,982,0882,0221,9581,8971,8381,7811,7271,6751,6251,5761,5291,4841,4401,3971,3561,3151,2761,2381,2011,1651,1301,0961,0621,0300,9980,9660,9350,9050,8750,8460,8170,7890,761
2
P.8
Reactive energy correction in an electrical installation
Where should the capacitors be installed?
The location of the capacitors in an electrical network is determined according to: ○ the required objective: eliminate penalties, discharge lines and transformers, increase end-of-line voltage, ○ the method of electrical power distribution, ○ the load rating, ○ the estimated effect of the capacitors on the network, ○ the cost of the installation.
The reactive energy compensation can be: ○ a high-voltage capacitor bank on the high-voltage distribution network (1), ○ a medium-voltage capacitor bank, regulated or fixed for the medium-voltage subscriber (2), ○ a low-voltage capacitor bank, regulated or fixed for the low-voltage subscriber (3), ○ fixed power factor correction for a medium-voltage motor (4), ○ fixed power factor correction for a low-voltage motor (5).
Example: Customers can choose the location of the power factor correction devices according to the characteristics of their installation and the objectives they require it to meet. Type 2 equipment can, for example, be used to compensate the consumption of the lift station on a wind turbine farm; another example is to compensate a motor control centre, for which automatic equipment is recommended. Type 1 equipment can be used to compensate the power transport line of an electrical company.
2
Compensated network
● On the LV outputs (MGDB) Position no. 1 Global power factor correction Advantages: ○ eliminates penalties for the excessive use of reactive energy ○ adapts the apparent power (S) in kVA to the actual needs of the installation ○ discharges the transformation centre (available power in kW) Comments: ○ the reactive current (Ir) is present in the installation from level 1 to the loads ○ there is no reduction in the Joule effect losses in the
P.9
● At the input to each workshop Position no. 2 Partial power factor correction Advantages: ○ eliminates penalties for the excessive use of reactive energy ○ optimises part of the installation, the reactive current is not carried between levels 1 and 2 ○ discharges the transformation centre (available power in kW) Comments: ○ the reactive current (Ir) is present in the installation from level 2 to the loads ○ Joule effect losses are reduced in the cables.
● At the terminals of each inductive-type load Position no. 3 Individual power factor correction Advantages: ○ eliminates penalties for the excessive use of reactive energy ○ optimises the entire electrical installation: the reactive current Ir is supplied at the very place where it is consumed ○ discharges the transformation centre (available power in kW) Comments: ○ there is no reactive current in the cables in the installation ○ the Joule effect losses are completely eliminated from the cables
Reactive energy correction in an electrical installation (continued)
The capacitors can be installed at three different levels:
2
Fig. 11: individual power factor correction
Fig. 9: global power factor correction Fig. 10: local power factor correction
When should fixed power factor correction be used?
Fixed transformer power factor correction
A transformer consumes a reactive power that can be determined approximately by adding:○ a fixed part that depends on the magnetising off-load current lo:
Qo = I0 x Un x √3
○ a part that is proportional to the square of the apparent power that it conveys: Q = Usc S²/Sn
Usc: short-circuit voltage of the transformer in p.u.S: apparent power conveyed by the transformerSn: apparent nominal power of the transformerUn: nominal phase-to-phase voltage
The total reactive power consumed by the transformer is: Qt = Qo + Q.
If this correction is of the individual type, it can be performed at the actual terminals of the transformer.
If this correction is performed globally with load correction on the busbar of the main switchboard, it can be of the fixed type provided that total power does not exceed15% of transformer nominal power(otherwise use banks with automatic regulation).
The individual correction values specific to the transformer, depending on transformer nominal power, are listed in the table below.
Fig. 12: power flow in an installation with an uncompensated transformer
Fig. 13: power flow in an installation where the transformer is compensated by a fixed power factor correction device
P.10
2
Transformer Oil bath Dry
S (kVA) Usc (%) No-load Load No-load Load
100 4 2.5 5.9 2.5 8.2
160 4 3.7 9.6 3.7 12.9
250 4 5.3 14.7 5.0 19.5
315 4 6.3 18.3 5.7 24
400 4 7.6 22.9 6.0 29.4
500 4 9.5 28.7 7.5 36.8
630 4 11.3 35.7 8.2 45.2
800 4 20.0 66.8 10.4 57.5
1000 6 24.0 82.6 12 71
1250 5.5 27.5 100.8 15 88.8
1600 6 32 126 19.2 113.9
2000 7 38 155.3 22 140.6
2500 7 45 191.5 30 178.2
● Case of parallel-mounting of capacitors with separate operating mechanismTo avoid dangerous overvoltages due to self-excitation or in cases in which the motor starts by means of special switchgear (resistors, reactors,autotransformers), the capacitors will only be switched after starting. Likewise, the capacitors must be disconnected before the motor is de-energised. In this case, motor reactive power can be fully corrected on full load. Caution: if several banks of this type are connected in the same network, inrush current limiting reactors should be fitted.
2
P.11
When should fixed power factor correction be used? (continued)
Correction of asynchronous motors
The cos φ of motors is normally very poor off-load and when slightly loaded, and poor in normal operating conditions. Installationof capacitors is therefore recommended for this type of load.The table opposite gives, by way of an example, the values for capacitor bank power in kvar to be installed according to motor power.
Rated power
Number of revolutions per minute
Reactive power in kVAr
kW hP 3000 1500 1000 750
11 15 2.5 2.5 2.5 5
18 25 5 5 7.5 7.5
30 40 7.5 10 11 12.5
45 60 11 13 14 17
55 75 13 17 18 21
75 100 17 22 25 28
90 125 20 25 27 30
110 150 24 29 33 37
132 180 31 36 38 43
160 218 35 41 44 52
200 274 43 47 53 61
250 340 52 57 63 71
280 380 57 63 70 79
355 485 67 76 86 98
400 544 78 82 97 106
450 610 87 93 107 117
When a motor drives a high inertia load, it may, after breaking of supply voltage, continue to rotate using its kinetic energy and be self-excited by a capacitor bank mounted at its terminals.The capacitors supply the reactive energy required for it to operate in asynchronous generator mode. Such self-excitation results in voltage holding and sometimes in high overvoltages.
Correction requirements of asynchronous motors● Case of mounting capacitors at the motor terminals To avoid dangerous overvoltages caused by the self-excitation pheno-menon, you must ensure that capacitor bank power verifies the following equation:
Qc ≤ 0,9 √3 Un I0
○ Io : motor off-load currentI o can be estimated by the following expres-sion: l0 = 2 In (l - cos φn)○ ln: value of motor nominal current○ Cos φ n: cos φ of the motor at nominal power○ Un: nominal phase-to-phase voltage
Parallel-mounting of capacitors with seperate opera-ting mechanism
Mounting capacitors at motor terminals
Automatic power factor correction
Automatic power factor correction equipment
● Internal components An automatic power factor correction device must be adapt to the variations in reactive power of the installation in order to maintain the target cos φ of the installation.
An automatic power factor correction device consists of three main components: ○ The controller: Its function is to measure the cos φ of the installation and send orders to the contactors to ensure that the power factor is as close as possible to the target cos φ by linking the various reactive power steps. Besides this function, Schneider Electric’s Varlogic controllers incorporate additional functions to assist with maintenance and installation.
○ Capacitors: Capacitors are the components that supply reactive energy to the installation. Capacitors are normally connected internally in a delta configuration.
● External components An automatic power factor correction device cannot work unless the installation data is collected; the external components ensure that the device operates correctly:
○ Current measurement: A current transformer that can measure the consumption of the entire installation must be connected.
○ Voltage measurement: Normally, this device is built into the capacitor bank itself so that this value is generated by the power connection of the capacitor bank. This information about the installation (voltage and current) allows the controller to calculate the cos of the installation at any time and to take the decision to activate or deactivate the power steps.
○ The 230 V supply is also required for the capacitor bank control circuit.
Note: except for the Varset models, which are fitted with a transformer.
P.12
REGULATEUR
Calcul du cos φ del’installation
CONTACTEURLC1-D-K-
Limitation
Connexion pôles principaux
TI
V
2
2 Automatic power factor correction (continued)
What is control used for?
The Varlogic controllers continually measure the reactive power of the installation and switch the capacitor steps ON and OFF to obtain the required power factor. Their ten step combinations allow them to control capacitors of different powers.
● Step combination :1.1.1.1.1.1 1.2.3.3.3.31.1.2.2.2.2 1.2.3.4.4.41.1.2.3.3.3 1.2.3.6.6.61.1.2.4.4.4 1.2.4.4.4.41.2.2.2.2.2 1.2.4.8.8.8These combinations ensure accurate control, by reducing: ○ the number of power factor correction modules ○ labour Optimising control in this way generates considerable financial savings.
● Explanations: Q1: power of the first step Q2: power of the second step Q3: power of the third step Q4: power of the fourth step Qn: power of the nth step (maximum 12)
● Examples: 1.1.1.1.1.1 : Q2 = Q1, Q3 = Q1,..., Qn = Q11.1.2.2.2.2 : Q2 = Q1, Q3 = 2Q1,..., Qn = 2Q11.2.3.4.4.4 : Q2 = 2Q1, Q3 = 3Q1, Q4 = 4Q1,...., Qn = 4Q11.2.4.8.8.8 : Q2 = 2Q1, Q3 = 4Q1, Q4 = 8Q1,..., Qn = 8Q1
● Calculation of the number of electrical steps: The number of electrical steps (e.g. 13) depends on: ○ the number of controller outputs used (e.g. 7) ○ the chosen combination, according to the power of the various steps (e.g. 1.2.2.2).
P.13
Combinations Number of controller outputs used
1 2 3 4 5 6 7 8 9 10 11 12
1.1.1.1.1.1... 1 2 3 4 5 6 7 8 9 10 11 12
1.1.2.2.2.2... 1 2 4 6 8 10 12 14 16 18 20 22
1.2.2.2.2.2... 1 3 5 7 9 11 13 15 17 19 21 23
1.1.2.3.3.3... 1 2 4 7 10 13 16 19 22 25 28 31
1.2.3.3.3.3... 1 3 6 9 12 15 18 21 24 27 30 33
1.1.2.4.4.4... 1 2 4 8 12 16 20 24 28 32 36 40
1.2.3.4.4.4... 1 3 6 10 14 18 22 26 30 34 38 42
1.2.4.4.4.4... 1 3 7 11 15 19 23 27 31 35 39 43
1.2.3.6.6.6... 1 3 6 12 18 24 30 36 42 48 54 60
1.2.4.8.8.8... 1 3 7 15 23 31 39 47 55 63 71 79
Automatic power factor correction (continued)
● Example: 150 kVAr 400 V 50 hz
Solution 1: physical control 10 x 15 kVAr 15 + 15 + 15 +15 +15 + 15 + 15 + 15 + 15 +15, combination: 1.1.1.1.1.1 ○ 10 physical steps ○ 10 contactors ○ 12-step controllers Labour, high cost: non-optimised solution
Solution 2: electrical control 10 x 15 kVAr 15 + 30 + 45 + 60 = 10 x 15 electrical kVAr, combination 1.2.3.4 ○ 4 physical steps allowing for 10 different powers ○ 4 contactors ○ 6-step controllers
Power factor correction cubicle optimisation
Possible powers (kVAr) Physical steps Physical steps
15 30 45 60
15 x
30 x
45 x x (x)
60 x x (x)
75 (x) x x (x)
90 x x (x) x (x)
105 x x (x) x (x)
135 x x x
150 x x x x
(x) Other possible combinations.
● Other solutions: 10 x 15 electrical kVAr Combination: 1.1.2.2.2: 15 + 15 + 30 + 30 + 30 kVAr Combination: 1.1.2.3.3: 15 + 15 + 30 + 45 + 45 kVAr
P.14
2
How to select power factor correction devices?
General information about harmonics p.16
Causes and effects of harmonics p.18
Choosing power factor correction devices p.20
Choosing the frequency of detuned reactors p.22
General information about harmonics
Introduction
In electrical systems, the voltage or current waves, whose frequency is an integral multiple of the fundamental frequency of the network (50 hz), are called harmonics. The waves of different orders that make up a harmonic spectrum and result in distorted waves are generally found simultaneously. Fig. 25 shows the breakdown of a distorted wave into a sinusoidal wave at the fundamental frequency (50 hz) and a wave at another frequency. harmonics are usually defined by two main characteristics: ○ their amplitude: value of the harmonic voltage or current ○ their order: value of their frequency with respect to the fundamental frequency (50 hz). Under such conditions, the frequency of a 5th order harmonic is five times greater than the fundamental frequency, i.e. 5 x 50 hz = 250 hz.
The root mean square value
The rms value of a distorted wave is obtained by calculating the quadratic sum of the different values of the wave for all the harmonic orders that exist for this wave: Rms value of I: I(A) = √ I1 2 + I2 2 + … + In 2 The rms value of all the harmonic components is deduced from this calculation: Ih (A) = √ I2 2 + … + In 2 This calculation shows one of the main effects of harmonics, i.e. the increased rms current passing through an installation, due to the harmonic components with which a distorted wave is associated. Usually, the switchgear and cables or the busbar trunking of the installation is defined from the rated current at the fundamental frequency; all these installation components are not designed to withstand excessive harmonic current.
Detecting the problem in the installation
Instruments that measure the true root mean square value (TRMS) must be used to detect any harmonic problems that may exist in the installations, since instruments that measure the average value (AVG) only give the correct values when the waves are perfectly sinusoidal. When the wave is distorted, the measurements can be as much as 40% below the true rms value.
Fig. 14 : decomposition of a distorted wave
Fig.15 : Typical graph of the frequency spectrum
The frequency spectrum, also known as the spectral analysis, indicates the types of harmonic generator present on the network
P.16
+1 2 3 4 5 6 7 8 9 10 11
0
10
20
30
40
50
60
70
80
90
100
3
Fig.17 : Harmonic spectrum for variable speed drives for asynchronous motors or direct current motors.
General information about harmonics (continued)
harmonic measurement: distortion
The presence of varying amounts of harmonics on a network is called distortion. It is measured by the harmonic distortion rates: ○ Th: individual distortion rate It indicates, as a %, the magnitude of each harmonic with respect to the value of the fundamental frequency: Th (%) = Ah / A1where Ah = the value of the voltage or current of the h-order harmonic. A1 = the value of the voltage or current at the fundamental frequency (50 hz).
○ ThD: Total harmonic Distortion It indicates, as a %, the magnitude of the total distortion with respect to the fundamental frequency or with respect to the total value of the wave.
The operating values used to find the true situation of the installations with respect to the degree of harmonic contamination are: ○ The total harmonic voltage distortion [ThD(U)] indicating the voltage wave distortion and the ratio of the sum of the harmonic voltages to the fundamental frequency voltage, all expressed as a %.
○ The total harmonic current distortion [ThD(I)] determining the current wave distortion and the ratio of the sum of the harmonic currents to the fundamental frequency current, expressed as a %.
○ The frequency spectrum (TFT) is a diagram that gives the magnitude of each harmonic according to its order. By studying it, we can determine which harmonics are present and their respective magnitude.
Interharmonics
Interharmonics are sinusoidal components with frequencies that are not integral multiples of the fundamental frequency (and therefore situated between the harmonics). They are the result of periodic or random variations of the power absorbed by different loads such as arc furnaces, welding machines and frequency converters (variable speed drives, cycloconvertors).
Example :
Fig.16 : Harmonic spectrum for industrial devices: arc furnaces, induction furnaces, welding machines, rectifiers, etc.
P.17
2
30
8 8
0
20
40
60
80
100
1 2 3 4 5 6 7 8 9 10 11
%
n
100
2
30
8 8
0
20
40
60
80
100
1 2 3 4 5 6 7 8 9 10 11
%
n
4
0
20
40
60
80
100
1 2 3 4 5 6 7 8 11 10 13
%
4
100
52
34
4
0
20
40
60
80
100
1 2 3 4 5 6 7 8 11 10 13
%
n
4
3
Causes and effects of harmonics
harmonic generators
harmonics are generally produced by non-linear loads which, although powered by a sinusoidal voltage, absorb a non-sinusoidal current. In short, non-linear loads are considered to behave as current sources that inject harmonics into the network. The most common non-linear harmonic loads are those found in devices fed by power electronics, such as variable speed drives, rectifiers, converters, etc. Loads such as saturable reactors, welding equipment, arc furnaces etc. also inject harmonics. Other loads have a linear behaviour and do not generate harmonics: inductors, resistors and capacitors.
Main harmonic sources
We differentiate between these loads, according to whether they are used for industrial or residential applications: ● Industrial loads: ○ power electronics devices: variable speed drives, rectifiers, UPS, etc. ○ loads using an electric arc: arc furnaces, welding machines, lighting (fluorescent lamps, etc.); harmonics (temporary) are also generated when motors are started with an electronic starter and when power transformers come into service.
Residential loads: TVs, microwave ovens, induction plates, computers, printers, fluorescent lamps, etc.
Type of load harmonics generated Comments
Transformer Even and odd order DC component
Asynchronous motors Odd order Interharmonics and subharmonics
Discharge lamp 3.° + odd Can reach 30% of l1
Arc welding 3.°
AC arc furnaces Unstable variable spectrum Non linear – asymmetric
Inductive filter rectifier h = K x P ± 1lh = l1/h
UPS - variable speed drives V
Capacitive filter rectifier h = K x P ± 1lh = l1/h
Electronic device power supply
Cycloconvertor Variables Variable speed drives V
PWM controllers Variables UPS - DC - AC converter
The following table is a guide to the various loads with information on the injected harmonic current spectrum.
Fig.18 : linear loads such as inductors, capacitors and resistors do not generate harmonics
Fig. 19 : non-linear loads are those that generate harmonics
P.18
3
3
Effects of the harmonics Causes Consequences
On the conductors ○ the harmonic currents cause the Irms to increase ○ the skin effect reduces the effective cross-section of the conductors as the frequency increases
○ unwanted tripping of the protection devices ○ overheated conductors
On the neutral conductor ○ a balanced three-phase + neutral load generates 3rd order multiple odd harmonics
○ closure of homopolar harmonics on the neutral, causing overheating and overcurrents
On the transformers ○ increased IRMS ○ Foucault losses are proportional to the frequency
○ increased overheating due to the Joule effect in the windings ○ increased losses in iron
On the motors ○ similar to those for the transformers and generation of a field added to the main one
○ analogues à celles des transformateurs plus pertes de rendement
Causes and effects of harmonics (continued)
The effects of harmonics on loads
The following two types of effects appear in the main equipment: immediate or short-term effects and long-term effects.
Immediate or short-term effects: ● Unwanted tripping of protection devices, ● Induced interference from LV current systems (remote control, telecommunications), ● Abnormal vibrations and noise,● Damage due to capacitor thermal overload, ● Faulty operation of non-linear loads.
Long-term effects associated with current overload that causes overheating and premature deterioration of the equipment.
Affected devices and effects: ● Power capacitors: ○ additional losses and overheating, ○ fewer possibilities of use at full load, ○ vibrations and mechanical wear, ○ acoustic disComfort.
● Motors: ○ additional losses and overheating, ○ fewer possibilities of use at full load, ○ vibrations and mechanical wear, ○ acoustic disComfort.
● Transformers: ○ additional losses and overheating, ○ mechanical vibrations, ○ acoustic disComfort. ○ automatic switch: ○ unwanted tripping due to the peak current being exceeded.
● Cables: ○ additional dielectric and chemical losses, especially on the neutral, when 3rd order harmonics are present, ○ overheating.
● Computers: ○ functional disruptions causing data losses or faulty operation of control equipment.
● Power electronics: ○ waveform interference: switching, synchronisation, etc.
Fig. 20: summary table of effects, causes and consequences of harmonics
P.19
Choosing power factor correction devices
Impact of harmonics on capacitors
Some loads (variable speed motors, static converters, welding machines, arc furnaces, fluorescent lamps, etc.) pollute the electrical network by reinjecting harmonics.
To take account of the effects of the harmonics on the capacitors, the type of compensation equipment must be correctly determined:
Gh / Sn < 15% 15% < x < 25 % 25% < x ≤ 50%
range Classic Comfort harmony
Choosing equipment according to the harmonic pollution level
Equipment can be chosen: ● Either theoretically from the Gh/Sn ratio if the data is available. Gh: apparent power of harmonic-generating loads (variable speed motors, static converters, power electronics, etc). Sn: apparent power of the transformer. The Gh/Sn rule is valid for a ThD(I) of all the harmonic generators < 30% and for a pre-existing ThD(U) < 2%. If these values are exceeded, a harmonic analysis of the network or measurements are required.
Example 1: U = 400 V, P = 300 kW, Sn = 800 kVA, Gh = 150 kVA Gh/Sn = 18.75 % φ Comfort equipment
Example 2: U = 400 V, P = 100 kW, Sn = 800 kVA, Gh = 300 kVA Gh/Sn = 37.5 % φ harmony equipment
● Or from the total harmonic current distortion ThD(I) measured at the transformer secondary, at full load and without capacitors:
ThD(I) % Classic Comfort harmony Filters
≤ 5 %
5 % < ... ≤ 4%
10 % < ... ≤ 20%
> 20 %
● Or from the total harmonic voltage distortion ThD(U) measured at the transformer secondary, at full load and without capacitors:
ThD(U) % Classic Comfort harmony Filters
≤ 3 %
3 % < ... ≤ 4%
4 % < ... ≤ 7 %
> 7 %
● If both ThD(I) and ThD(U) are measured and do not result in the same type of power factor correction, the most rigorous solution must be chosen.
For example, a measurement gives: ○ ThD(I) = 15 % harmony solution ○ ThD(U) = 3.5 % Comfort solution The harmony solution must be chosen.
P.20
3
3 Choosing power factor correction devices (continued)
Operating limits
The rules described below are for information only. Please contact us in case of doubt or if the values are higher than those indicated below.
All the components and applications recommended in this catalogue are only valid if the operating limits given below are met, in order to prevent the detuned reactors and capacitors from being overloaded.
The ThD(U) must be measured at the transformer secondary with the capacitor banks. The lmp current must be measured in the capacitors.
Operating limits ThD (U) max. %
Order voltage measurement lmp/l1 max.
U3 U5 U7 U11 U13
Classic power factor correction 5 % 1.3
Comfort power factor correction 7 % 3 % 8 % 7 % 3.5 % 3 % 1.12
harmony power factor correc-tion (tuning order 2.7)
8 % 0.5 % 6 % 7 % 3.5 % 3 % 1.19
P.21
Choosing the detuned reactor tuning frequency
General:
The purpose of the detuned reactors (DR) is to prevent the harmonics present on the network from being amplified and to protect the capacitors (this corresponds to our harmony range). They must be connected in series with the capacitors. Caution: as the detuned reactors generate an overvoltage at the capacitor terminals, capacitors of at least 480 V must be used for a 400 V network.
Technical data:
● Choice of tuning The tuning frequency fr corresponds to the resonance frequency of the L-C assembly. fr = 1/ (2�√LC) We also speak of tuning order n. For a 50 hz network, we have: n = fr / 50 hz
● The tuning order chosen must ensure that the harmonic current spectrum range is outside the resonance frequency. ● It is also important to ensure that no remote-control frequencies are disturbed. The most common tuning orders are 3, 8 or 4.3 (2.7 is used for 3rd order harmonics).
DR, 400 V, 50 hz tuning frequency selection table
harmonic generators (Gh) Remote control frequency
None 165 < Ft ≤ 250 hz 250 < Ft ≤ 350 hz Ft > 350 hz
Three-phase Tuning frequency
Variable speed drives, rectifiers, UPS, starters 135 hz 135 hz (1) 190 hz 215 hz
Single-phase Gh > 10% Sn Tuning frequency
Discharge lamps, electronic ballast lamp, fluorescent lamps, UPS, variable speed drives, welding machines
135 hz 135 hz 135 hz 135 hz
Single-phase Gh: power of single-phase harmonic generators in kVA. (1): a tuning frequency of 215 hz can be used in France with a remote control frequency of 175 hz
Concordance between tuning frequency and relative impedance (50 hz network)
Tuning frequency (lr) Tuning order (n = fr/f) Relative impedance (P = 1/n2) as a %
135 hz 2.7 13.7 %
190 hz 3.8 6.92 %
P.22
3
3 Typical solutions depending on applications
Customer requirements
The table below shows the solutions most frequently used in different types of applications.
Very frequently
Usually
Occasionally
In all cases, it is strongly recommended that measurements be carried out on site in order to validate the solution.
Classic type Comfort type harmony type
Industry
Food and drink
Textiles
Wood
Paper
Printing
Chemicals - pharmaceuticals
Plastics
Glass - ceramics
Steel production
Metallurgy
Automotive
Cement works
Mining
Refineries
Microelectronics
Tertiary
Banks - insurance
Supermarkets
hospitals
Stadiums
Amusement parks
hotels - offices
Energy and infrastructure
Substations
Water distribution
Internet
Railway transport
Airports
Underground train systems
Bridges
Tunnels
Wind turbines
P.23
P.28
Varplus2 presentation p. 25
Our products according to network p. 27
Varplus2 p. 28
Dimensions p. 38
Capacitors
Varplus2 presentation
What are the advantages of Varplus²?
● Easy installation: ○ extensive choice of installation positions ○ no assembly limitations ○ no earth connection needed ○ mounting holes allow capacitors to be fixed easily and securely with two M6 screws ○ connection on top of the capacitor: very easy to access ○ several capacitors can be assembled quickly and easily ○ 360° cable connection on top of the capacitor.
● high flexibility: ○ the total modularity of Varplus2 provides greater stock management flexibility ○ covers all the electrical steps that may be required, according to the voltage and frequency and the level of harmonic pollution present in the network○ the total modularity of the capacitor provides greater stock management flexibility.
● A unique technology: ○ the discharge resistors are already mounted in the capacitors. They reduce the voltage to less than 50 V in one minute and can be used in an automatic power factor correction cubicle without an additional discharge system. ○ high fire resistance ○ high quality protection system. Varplus² are the only capacitors using this technology that can prevent 100% of all possible faults thanks to the disconnection system with its suppressor and hBC fuses
They can be installed in several positions
P.25
Recommended installation
Acceptable
Recommended installationRecommended installation
Wrong Wrong
4
Air flow Air flow
Air flow Air flow
Air flow
Varplus2 presentation (continued)
Technical data
● hQ protection system built into each single phase element :○ high current fault protection by hRC cartridge fuse○ low current fault protection by combination of single phase internal overpressure device with the hRC fuse
● A fully modular offer with only one size for installation and connection
● Maximum power per unit: 20 kvar for 400V-50 hz network.
● Possibility of wiring connection at 360°.
● Three phase connection
● With internally fitted discharge resistors: residual voltage less than 50 V in 1 minute.
● Total losses (discharge resistor included) : ≤ 0,5 W/kvar
● Capacitance value tolerance : -5 %, +10 %.
● Voltage test : 2,15 Un (rated voltage) for 10 s.
● Maximum permissible overloads at service voltage network as per IEC 60831 1/2:○ current: 30 % permanently○ voltage: 10 % (8 hours over 24 hours).
● Temperature class D (+55°C):○ Maximum temperature: 55°C○ Average temperature over 24 h: 45°C○ Average temperature over a year: 35°C○ Minimum temperature: - 25°C.
● Colour :○ elements: RAL 9005○ base and cover: RAL 7030.
● Execution: indoor.
● Protection :○ IP00 without cover (option)○ IP20 or 42 see accossories.
● Standards : IEC 60831 1/2, CSA 22-2 No190, UL810
P.26
Installation
All positions are convenient except vertical one with connecting terminals upside down. Fixing holes for M6 screwsavec des vis M6.
Accessories pour Varplus² References
1 set of three phase copper bars for connection and assembly of 2 and 3 capacitors
51459
1 set of protective cover (IP20) and cable glands (IP42) for 1,2 and 3 capacitors
51461
1 protective cover (IP20) 51299
Accessories
Varplus²
Varplus² accesso-
4
4
P.27
Our products according to network
Find the page corresponding to your network thanks to the table below.
50 hz network
230 V network voltage p.28
400/415 V network voltage p.29 et p.30
525 V network voltage p.31
690 V network voltage p.32
60 hz network
230/240 V network voltage p.33
400/415 V network voltage p.34
440 V network voltage p.35
480 V network voltage p.36
600 V network voltage p.37
Varplus2
230 V - 50 hz network
● Classic & Comfort range
Useful power (kvar) References
2,5 51301
5 51303
6,5 51305
7,5 51307
10 51309
Advised assembly
15 2 x 51307
20 2 x 51309
30 3 x 51309
40 4 x 51309
Maximum mechanical assembly: 4 capacitors and 40 kVAr.Assembly > 40 kvar : see conditions to respect in Varplus² user manual.
● Harmony rangeSame capacitors can be used with detuned reactors.
P.28
4
4 Varplus2
400/415 V - 50 hz network
● Classic range
Useful power (kvar) References
400 V 415 V
5 5,5 51311
6,25 6,5 51313
7,5 7,75 51315
10 10,75 51317
12,5 13,5 51319
15 15,5 51321
20 21,5 51323
Advised assembly
25 27 2 x 51319
30 31 2 x 51321
40 43 2 x 51323
50 53,5 2 x 51321 + 51323
55 58,5 2 x 51323 + 51321
60 64,5 3 x 51323
65 3 x 51323 + 51311
Maximum mechanical assembly: 4 capacitors and 65 kVAr.Assembly > 65 kvar : see conditions to respect in Varplus² user manual.
● Comfort range
Capacitors rated voltage: 480 V.
Useful power References
400 V (kvar) 415 V (kvar)
5 5,5 51325
6,25 6,5 51327
7,5 8 51329
10 11 51331
12,5 13,5 51333
15 16,5 51335
Advised assembly
20 23 2 x 51331
25 25 2 x 51333
30 34 2 x 51335
45 51 3 x 51335
60 68 4 x 51335
Maximum mechanical assembly: 4 capacitors and 60/68 kVAr for 400/415V - 50 hz network.Assembly > 60 kvar : see conditions to respect in Varplus² user manual.
P.29
Varplus2
400/415 V - 50 hz network
● Harmony range
This range corresponds to the association of 480 V rated capacitors with detuned reactors.
Tuning order Useful power (kvar) References
400 V (kvar) 415 V (kvar)
2,7 (135 hz - 13,7 % ) 6,5 7 51337
12,5 13,5 51331
Advised assembly
25 27 2 x 51331
50 54 2 x 51335 + 51333
Maximum mechanical assembly: 4 capacitors and 50/54 kVAr 400/415 V.Assembly > 50 kvar : see conditions to respect in Varplus² user manual.
3,8 (190 hz - 6,92 % ) ou
4,3 (215 hz - 5,4 % )
6,5 7 51327
7,75 8,25 51329
10 11 51345
12,5 13,5 51333
16,5 17,75 51335
Advised assembly
25 27 2 x 51333
30 31,25 51333 + 51335
50 53,25 3 x 51335
Maximum mechanical assembly: 4 capacitors and 65 kVAr.Assembly > 65 kvar : see conditions to respect in Varplus² user manual.
P.30
4
4
Example of Varplus² IP00 assembly
Varplus2
525 V - 50 hz network
● Classic range
Useful power (kvar) References
11 51351
13 51353
17 51357
Advised assembly
22 2 x 51351
26 2 x 51353
34 2 x 51357
51 3 x 51357
62 3 x 51357 + 1 x 51351
68 4 x 51357
Maximum mechanical assembly: 4 capacitors and 68 kVAr.Assembly > 68 kvar : see conditions to respect in Varplus² user manual.
● Comfort range
Capacitor rated voltage: 690V
Useful power (kvar) References
6 51359
8 51361
10 51363
Advised assembly
20 2 x 51363
30 3 x 51363
40 4 x 51363
Maximum mechanical assembly: 4 capacitors and 40 kVAr.Assembly > 40 kvar : see conditions to respect in Varplus² user manual.
● harmony range
Capacitors rated 690 V will be used with detuned reactors 190/215 hz, 135 hz on request.
P.31
Varplus2
690 V - 50 hz network
● Classic range
Useful power (kvar) References
11 51359
15 51361
17 51363
Advised assembly
22 2 x 51359
34 2 x 51363
45 3 x 51361
60 4 x 51361
68 4 x 51363
Maximum mechanical assembly: 4 capacitors and 68 kVAr.Assembly > 68 kvar : see conditions to respect in Varplus² user manual.
● Comfort & Harmony range
On request
P.32
4
4 Varplus2
230/240 V - 60 hz network
● Classic & Comfort range
Useful power (kvar) References
230 V (kvar) 240 V (kvar)
3 3 51301
6 6,5 51303
8 8,5 51305
9 10 51307
12 13 51309
Advised assembly
18 20 2 x 51307
24 26 2 x 51309
36 39 3 x 51309
Maximum mechanical assembly: 4 capacitors and 40 kVAr.Assembly > 40 kvar : see conditions to respect in Varplus² user manual.
● Harmony range
Same capacitors can be used with detuned reactors.
P.33
Varplus2
400/415 V - 60 hz network
● Classic range
Useful power (kvar) References
400 V (kvar) 415 V (kvar)
6 6,25 51311
7,5 8 51313
9 9 51315
12 13 51317
15 16 51319
18 19 51321
Advised assembly
24 26 2 x 51317
30 32 2 x 51319
36 38 2 x 51321
45 48 3 x 51319
54 57 3 x 51321
60 64 4 x 51319
Maximum mechanical assembly: 4 capacitors and 65 kVAr.Assembly > 65 kvar : see conditions to respect in Varplus² user manual.
● Comfort rangeCapacitors rated 480 V are necessary.
Useful power (kvar) References
400 V (kvar) 415 V ( kvar)
6 6,25 51325
7,5 8 51327
9 9 51329
12,75 13,5 51331
14 15 51333
18,5 51335
Advised assembly
25,5 27 2 x 51331
32,5 51333 + 51335
37 2 x 51335
42 45 3 x 51333
51 2 x 51335 + 51333
55 3 x 51335
61 3 x 51335 + 51325
Maximum mechanical assembly: 4 capacitors and 61 kVAr.Assembly > 61 kvar : see conditions to respect in Varplus² user manual.
P.34
4
4
P.35
Varplus2
400/415 V - 60 hz network (continued)
● Harmony range
Capacitors rated 480 V will be used with detuned reactors.
Tuning order Useful power (kvar) References
400 V (kvar) 415 V (kvar)
2,7 (135 hz - 13,7 % ) 7,75 8,25 51337
15 16,25 51331
Maximum mechanical assembly: 4 capacitors and 60/65 kVAr 400/415 V.Assembly > 60 kvar : see conditions to respect in Varplus² user manual.
Tuning order Useful power (kvar) References
400 V (kvar) 415 V (kvar)
3,8 (190 hz - 6,92 % ) ou
4,3 (215 hz - 5,4 % )
7,75 8,3 51327
9,25 10 51329
12 13 51345
15 16 51333
20 51335
Maximum mechanical assembly: 4 capacitors and 60/65 kVAr 400/415 V.Assembly > 60 kvar : see conditions to respect in Varplus² user manual.
P.36
4 Varplus2
440 V - 60 hz network
● Classic range
Useful power (kvar) References
7.5 51325
9 51327
11 51329
15 51331
17 51333
22 51335
Advised assembly
30 2 x 51331
44 2 x 51335
51 3 x 51333
59 2 x 51335 + 51331
66 3 x 51335
75 3 x 51335 + 51327
Maximum mechanical assembly: 4 capacitors and 76 kVAr.Assembly > 76 kvar : see conditions to respect in Varplus² user manual.
● Comfort range
Capacitors rated 550V are necessary.
Useful power (kvar) References
9 51351
11 51353
12.5 51383
14 51357
Advised assembly
28 2 x 51357
42 3 x 51357
56 4 x 51357
● Harmony range
Capacitors rated 550 V will be used with detuned reactors.
4 Varplus2
480 V - 60 hz network
● Classic range
Useful power (kvar) References
9 51325
11 51327
13 51329
18 51331
20 51333
Advised assembly
36 2 x 51331
54 3 x 51331
72 4 x 51331
Maximum mechanical assembly: 4 capacitors and 72 kVAr.Assembly > 72 kvar : see conditions to respect in Varplus² user manual.
● Comfort range
Capacitor rated 550V are necessary
Useful power (kvar) References
10 51351
12.5 51353
15 51383
17 51357
Advised assembly
20 2 x 51351
25 2 x 51353
34 2 x 51357
44 2 x 51353 + 1 x 51351
51 3 x 51357
68 4 x 51357
Maximum mechanical assembly: 4 capacitors and 68 kVAr.Assembly > 68kvar : see conditions to respect in Varplus² user manual.
● Harmony range
Capacitors rated 550 V will be used with detuned reactors.
P.37
P.38
4 Varplus2
600 V - 60 hz network
● Classic & Comfort range
Useful power (kvar) References
600 V (kvar)
10 51359
13,5 51361
15 51363
Advised assembly
20 2 x 51359
30 2 x 51363
45 3 x 51363
60 4 x 51363
Maximum mechanical assembly: 4 capacitors and 60 kVAr.Assembly > 60 kvar : see conditions to respect in Varplus² user manual.
● Harmony range
On request for association with detuned reactors
Dimensions
from 5 to 15 kvar 20 kvar 50 kvar 60 kvar
Weight 219 219 219 219
Width 220 220 220 220
Length 114,7 114,7 308,7 308,7
Three conditions are to be respected for assembly:● adapted busbar section is expected to connect capacitors assembly● minimum space of 25mm is expected between 2 groups of capacitors● specific precautions must be taken in order not to exceed temperature category of -25°C/D inside the cubicle.
P.39
4
Detuned reactors
Presentation p. 41
Our range p. 42
Dimensions p. 43
Detuned reactor / capacitor / contactor combination tables p. 44
Presentation
General information
Detuned reactors (DR) are designed to protect capacitors and prevent amplification of harmonics existing on the network.
Technical data
● Three phase, dry, magnetic circuit, impregnated● Cooling: natural● Degree of protection: IP00● Inslation class : h● Standards : IEC 60289, EN 60289● Rated voltage: 400/415 V, triphasé 50 hz● Tuning order (relative impedance) : 4,3 (5,4 %), 3,8 (6,9 %), 2,7 (13,7 %)● Inductance tolerance per phase : -5, +5 %● harmonic current spectrum:
As a % of the current of the fundamental (l1)
4,3 tuning order 3,8 tuning order 2,7 tuning order
Courant l3 2 % 3 % 6 %
Courant l5 69 % 44 % 17 %
Courant l7 19 % 13 % 6 %
Courant l11 6 % 5 % 2 %
● Insulation level: 1.1 kV● Thermal withstand Isc: 25 x le, 2 x 0,5 second● Dynamic withstand: 2,2 lcc (peak value)● Dielectric test 50 hz between windings and windings/earth: 3,3 kV, 1 mn● Thermal protection restored on terminal block 250 V AC, 2 A.
Operating conditions
● Use: indoor● Storage temperature: - 40°C, + 60°C● Relative humidity in operation: 20 à 80 %● Saline mist withstand: 250 hours ●Operating temperature / Altitude:
Altitude Minimun Maximun highest average over any period of
m °C °C 1 year 24 hours
1000 0 55 40 50
> 1000, ≤ 2000 0 50 35 45
Installation
● Forced ventilation required ● Vertical detuned reactor winding for better heat dissipation● Electrical connection:
○ to a screw terminal block for 6.25 and 12.5 kvar detuned reactors○ to a drilled pad for 25, 50 and 100 kvar detuned reactors
● 480 V capacitors must be used with the detuned reactors in case of a 400/415 V - 50 hz network.
As the detuned reactor is fitted with thermal protection, the normally closed dry contact must be used to disconnect the step in the event of overheating.
5
P.41
P.42
5 Our range
Tuning order: 4,3 (215 hz)
Power restored by the DR/capacitor assembly Power losses References
L (mh) l1 (A) (W)
6,25 kvar/400 V - 50 hz 4,71 9 100 51573
12,5 kvar/400 V - 50 hz 2,37 17,9 150 52404
25 kvar/400 V - 50 hz 1,18 35,8 200 52405
50 kvar/400 V - 50 hz 0,592 71,7 320 52406
100 kvar/400 V - 50 hz 0,296 143,3 480 52407
Tuning order: 3,8 (180 hz)
Power restored by the DR/capacitor assembly Power losses References
L (mh) l1 (A) (W)
6,25 kvar/400 V - 50 hz 6,03 9,1 100 51568
12,5 kvar/400 V - 50 hz 3 18,2 150 52352
25 kvar/400 V - 50 hz 1,5 36,4 200 52353
50 kvar/400 V - 50 hz 0,75 72,8 300 52354
100 kvar/400 V - 50 hz 0,37 145,5 450 51569
Tuning order: 2,7 (135 hz)
Power restored by the DR/capacitor assembly Power losses References
L (mh) l1 (A) (W)
6,25 kvar/400 V - 50 hz 12,56 9,3 100 51563
12,5 kvar/400 V - 50 hz 6,63 17,6 150 51564
25 kvar/400 V - 50 hz 3,14 37,2 200 51565
50 kvar/400 V - 50 hz 1,57 74,5 400 51566
100 kvar/400 V - 50 hz 0,78 149 600 51567
For other voltages and/or frequancy, please contact us.
5 Dimensions
Tuning order: 4,3 (215 hz)
Power restored by the DR / capacitors assembly
Fixing centre distance (mm)
Maximum dimensions (mm) Weight (kg)
h W D
6,25 kvar/400 V - 50 hz 110 x 87 230 200 140 8,6
12,5 kvar/400 V - 50 hz 205 x 110 230 245 140 12
25 kvar/400 V - 50 hz 205 x 110 230 240 140 18,5
50 kvar/400 V - 50 hz 205 x 120ou
205 x 130
270 260 160 25
100 kvar/400 V - 50 hz 205 x 120 330 380 220 42
Tuning order: 3,8 (190 hz)
Power restored by the DR / capacitors assembly
Fixing centre distance (mm)
Maximum dimensions (mm) Weight (kg)
h W D
6,25 kvar/400 V - 50 hz 110 x 87 230 200 140 8,5
12,5 kvar/400 V - 50 hz 205 x 110 230 245 140 10
25 kvar/400 V - 50 hz 205 x 110 230 240 140 18
50 kvar/400 V - 50 hz 205 x 120or
205 x 130
270 260 160 27
100 kvar/400 V - 50 hz 205 x 120 330 380 220 42
Tuning order: 2,7 (135 hz)
Power restored by the DR / capacitors assembly
Fixing centre distance (mm)
Maximum dimensions (mm) Weight (kg)
h W D
6,25 kvar/400 V - 50 hz 110 x 87 230 200 140 9
12,5 kvar/400 V - 50 hz 205 x 110 230 245 145 13
25 kvar/400 V - 50 hz 205 x 110 230 240 140 22
50 kvar/400 V - 50 hz205 x 120
or205 x 130
270 260 160 32
100 kvar/400 V - 50 hz 205 x 120 330 380 220 57
P.43
5 Detuned reactors / capacitor / contactor combination tables
Maximum temperature 40°C et maximum altitude 2000 m, for 400 V - 50 hz network
480 V capacitors fr =135 hz
Qc = 400 V Qc = 480 V
Capacitor reference
DR reference Specific contactors
Standard contactor
6,25 kvar 8 kvar 51337 x 1 51563 x 1 LC1-DFK11M7 x1 LC1D12 x1
12,5 kvar 15,5 kvar 51331 x1 51564 x 1 LC1-DFK11M7 x 1 LC1D25 x 1
25 kvar 31 kvar 51331 x 2 51565 x 1 LC1-DMK11M7 x 7 LC1D38 x 1
50 kvar 62 kvar 51335 x 2 + 51333 51566 x 1 LC1-DWK12M7 x 1 LC1D95 x 1
100 kvar 124 kvar 51335 x 4 + 51333 x 2 51567 x 1 LC1D115 x 1
480 V capacitors fr =215hz fr = 190 hz
Qc = 400 V
Qc = 480 V
Capacitor reference
DR reference
DR reference
Specific contactors
Standard contactor
6,25 kvar 9 kvar 51327 x 1 51573 x 1 51568 x 1 LC1-DFK11M7 x1 LC1D12 x1
12,5 kvar 17 kvar 5133 x 1 52404 x 1 52352 x 1 LC1-DFK11M7 x 1 LC1D25 x 1
25 kvar 34 kvar 51333 x 2 52405 x 1 52353 x 1 LC1-DMK11M7 x 7 LC1D38 x 1
50 kvar 68 kvar 51335 x 3 52406 x 1 52354 x 1 LC1-DWK12M7 x 1 LC1D95 x 1
100 kvar 136 kvar 51335 x 6 52407 x 1 51569 x 1 LC1D115 x 1
Maximum temperature 50°C et maximum altitude 1000 m, for 400 V - 50 hz network
550 V capacitors fr =135 hz
Qc = 400 V Qc = 550 V Capacitor reference
DR reference Specific contactors
Standard contactor
6,25 kvar 10,5 kvar 51363 x 1 51563 x 1 LC1-DFK11M7 x1 LC1D12 x1
12,5 kvar 21 kvar 51363 x 2 51564 x 1 LC1-DGK11M7 x 1 LC1D25 x 1
25 kvar 40,5 kvar 51353 x 3 51565 x 1 LC1-DPK11M7 x 7 LC1D40x 1
50 kvar 81 kvar 51357 x 3 + 51353 x 2 51566 x 1 LC1-DWK12M7 x 1 LC1D95 x 1
100 kvar 162 kvar 51357 x 9 51567 x 1 LC1F185 x 1
550 V capacitors fr =215hz fr = 190 hz
Qc = 400 V Qc = 550 V Capacitor reference
DR reference
DR reference
Specific contactors
Standard contactor
6,25 kvar 11,5 kvar 51351 x 1 51573 x 1 51568 x 1 LC1-DFK11M7 x1 LC1D12 x1
12,5 kvar 23 kvar 51351 x 2 52404 x 1 52352 x 1 LC1-DGK11M7 x 1 LC1D25 x 1
25 kvar 46 kvar 51357 x 1 + 51353 x 2 52405 x 1 52353 x 1 LC1-DPK11M7 x 7 LC1D40 x 1
50 kvar 90 kvar 51357 x 5 52406 x 1 52354 x 1 LC1-DWK12M7 x 1 LC1D95 x 1
100 kvar 180 kvar 51357 x 10 52407 x 1 51569 x 1 LC1F185 x 1
P.44
Varlogic power factor
Presentation p. 46
Our range p. 48
Dimensions p. 49
P.46
6 Presentation
General information
Varlogic N power factor controller:● analyses and provides information on network characteristics● controls the reactive power required to obtain the target power factor● monitors and provides information on equipment status● communicates on the Modbus network (Varlogic NRC12 only)
Varlogic NR6 and NR12
● User-friendly interfaceThe backlignted display allows:○ direct viewing of installation electrical information and capacitor stage condition○ direct reading of set-up configuration○ intuitive browsing in the various menus (indication, commisioning, configuration)○ alarm indication
● Performance○ access to a wealth of network and capacitor bank data○ new control algorithm designed to reduce the number of switching operations and quickly attain the required power factor
● Simplified installation and set-up○ quick and simple mounting and wiring○ insensitive to current transformer polarity and phase rotation polarity○ a special menu allows controller self-configuration
Varlogic NRC12
● An even greater level of information and controlIn addition to the functions of Varlogic NR6/NR12, the Varlogic NRC12 provides the following features:○ measurement of total current harmonic distortion○ spectral analysis of network harmonic currents and voltages○ immediate display of network’s main parameters○ possibility of a dual target power factor ○ possible configuration with fixed step○ step condition monitoring (capacitance loss)
Presentation
Technical data
General data ● Operating temperature: 0...60° C● Storage temperature : - 20°C...60°C● Colour: RAL 7016● Standards:○ EMC : IEC 61326○ electrical: IEC/EN 61010-1● Panel mounting● Mounting on 35 mm DIN rail (EN 50022)● Protection class in panel mounting: ○ Front face: IP41○ rear face: IP20● Display :○ NR6, NR12: backlighted screen 65 x 21 mm○ NRC12: backlighted graphic screen 55 x 28 mm○ langues : allemand, anglais, espagnol, français et portugais● Alarm contact● Temperature internal probe● Seperate contact to control fan inside the power factor correction bank● Access to history of alarms
Inputs● Phase to phase or neutral to phase connection● Insensitive to CT polarity● Insensitive to phase rotation polarity● Current input:○ NR6, NR12: CT...X/5 A○ NRC12: CT...X/5 A and X/1 A
Outputs● Potential free output contacts:○ AC : 1 A/400 V, 2 A/250 V, 5 A/120 V○ DC : 0,3 A/110 V, 0,6 A/60 V, 2 A/24 V
Settings and parameters● Target cos φ: 0,85 ind...0,9 cap● Possibility of dual target cos φ (NRC12)● Manual or automatic parameter setting of power factor controller● Choice of different stepping programs:○ linear○ normal○ circular○ optimal● Main step sequences:○ 1.1.1.1.1○ 1.2.2.2.2○ 1.2.3.4.4○ 1.1.2.2.2○ 1.2.3.3.3○ 1.2.4.4.4○ 1.1.2.3.3○ 1.2.4.8.8● Customized sequences for NRC12 type● Delay between 2 successive switch on of a same step:○ NR6, NR12 : 10...600 s○ NRC12 : 10...900 s● Step configuration programming (fixed/automatic/disconnected) (NRC12)● 4 quadrant operation for generator application (NRC12)● Manual control for operating test
P.47
6
P.48
6 Our range
Type Number of step output contacts
Supply voltage (V) network 50-60 hz
Measuring voltage (V) References
NR6 6 110-220/240-380/415 110/220/240-380/415 52448
NR12 12 110-220/240-380/415 110-220/240-380/415 52449
NRC12 12 110-220/240-380/415 110-220/240-380/415-690 52450
Varlogic NRC12 accessories
Communication RS485 Modbus set for NRC12 52451
Temperature external probe for NRC12 type. In addition to internal probe, allows measurement at the lowest point inside the capacitor bank. Better tuning of alarm and/or disconnection level. 52452
Information supplied NR6/NR12 NRC12
Cos φ X X
Connected steps X X
Switching cycles and connecting time counter X X
Step configuration (fixed step, automatic, disconnected) X
Step output contacts X
Network technical data: load and reactive currents, voltages, powers (S, P, Q) X X
Ambiant temperature inside the cubicle X X
Total voltage harmonic distortion ThD (U) X X
Total current harmonic distortion ThD (I) X
Capacitor current overload Irms/I1 X
Voltage and curretn harmonic spectrum (orders 3, 5, 7, 11, 13) X
history of alarms X X
Alarms Threshold Actions NR6/NR12 NRC12
Low power factor message and alarm contact X X
hunting (unstable regu-lation)
message and alarm contact disconnection (2) X X
Abnormal cos φ < 0,5 ind. or 0,8 cap. message and alarm contact X X
Overcompensation message and alarm contact X X
Overcurrent > 115 % I1 message and alarm contact X X
Low voltage < 80 % U0 within 1 s message and alarm contact disconnection (2) X X
Overvoltage > 110 % U0 message and alarm contact disconnection (2) X X
Overtemperature θ ≥ θo (θo = 50°C max) (1) message and alarm contactdisconnection (2)
X X
θ ≥ θo- 15°C contact ventilateurdisconnection (2) X X
Total harmonic distorsion > 7 % (1) message and alarm contactdisconnection (2)
X X
Capacitor current overload (Irms/I1)
> 1,5 (1) message and alarm contact disconnection (2)
X
Capacitor capacitance loss - 25 % message and alarm contactdisconnection (2)
X
Low current < 25 % message X X
Dimensions
Varlogic N height (h) Width (W) Depth 1 (P1) Depth 2 (P2)
Varlogic NR6/NR12 150 150 70 60
Varlogic NRC12 150 150 80 70
6
P.48
Power factor correction modules
Varpact presentation p. 51
Our range according to the network p. 53
Varpact p. 54
Accessories for Varpact power factor correction modules p. 58
Varpact presentation
General information
Varpact power factor correction modules form a prewired automatic compensation subassembly designed for fixing in stand-alone cubicles or inside Main Low Voltage Switchboard.
What are the advantages of Varpact?
● Time saving thanks to a simple installation: ○ Connection points are reduced○ Busbar option → easier installation○ Only 1 product to order instead of many (capacitors, contactors, wires, protection...)○ Fastening crosspieces to install Varpact in the cubicle
Technical data
● Available voltage and frequency:○ 50 hz : 400 V, 415 V○ Other networks on request
● Capacitance value tolerance : - 5, +10 %
● Insulation level: ○ 0,69 kV ○ withstand 50 hz, 1 min : 2,5 kV.
● Maximum permissible overloads:○ current : Varpact Classic range: 30 % max. (400 V) Varpact Comfort range: 50 % max. (400 V) Varpact harmony range: - accord 2,7 : 12 % max. (400 V) - accord 3,8 : 19 % max. (400 V) - accord 4,3 : 30 % max. (400 V).○ voltage : 10 %
● Ambient temperature around the capacitor bank (electrical room):○ Maximum temperature: 40°C○ Average temperature over 24 hours: 35°C○ Average annual temperature: 25°C○ Minimum temperature: -5°C.
● Losses :○ Varpact Classic : - with cable connection: < 1,9 W / kvar - with busbar connection: < 2 W / kvar○ Varpact Comfort : - with cable connection: < 2,3 W / kvar - with busbar connection: < 2,4 W / kvar○ Varpact harmony : < 8 W / kvar
● Protection degree: accidentals front face direct contact protection device
● Busbar withstand Isc: 35 kA.
● Colour : RAL 7016
● Standards : ○ IEC 60439-1○ EN 60439-1○ IEC 61921
P.51
7
P.52
7 Varpact presentation (continued)
Installation
● Varpact modules can be installed in the following type of cubicles:○ Prisma, Prisma plus○ Universal
● horizontal fixing in functional and universal cubicles, 400 and 500 mm deep:○ in cubicle W = 650, 700, 800 using fastening crosspieces ans extension pieces○ en cubicles de largeur L = 600 mm using fastening crosspieces
● Vertical fastening every 300 mm (maximum 5 modules) directly to cubicle uprights using sliding crosspieces or to intermediate upright support
● Control circuit power supply: 230 V 50 hz.
Accessories
Accessories for Varpact Maximum reactive power References
Connection module with fixing kit (600, 650, 700, 800 wide cubicle)
52800
Fastening crosspieces*: set of 2 cross-pieces
51670
Extension pieces* :○ for Prisma Plus cubicle W = 650 mm○ for universal cubicle W = 700 mm○ for universal cubicle W = 800 mm
516355163751639
Circuit breaker (CB) protection* :○ Additional CB 60/63 A protection kit○ Additional CB 100 A protection kit○ Additional CB 160 A protection kit○ Additional CB 250 A protection kit
until 30 kvarfrom 31 to 50 kvarfrom 51 to 80 kvarfrom 81 to 120 kvar
51626516275162851629
Our range according to the network
Classic range Comfort range harmony range
50 hz network
400/415 V network p.49 p.51 p.52
Find the page corresponding to your network thanks to the table below.
Other voltages / frequency: on request.
7
P.53
P.54
7 Varpact
400 V - 50 hz network
● Varpact Classic with cable connection
Power (kvar) Step References
12,5 single 51775
25 single 51776
30 single 51777
40 single 51778
45 single 51779
50 single 51780
60 single 51781
80 single 51719
90 single 51782
100 single 51783
120 single 51784
6,25 + 12,5 double 51785
12,5 + 12,5 double 51786
10 + 20 double 51787
15 + 15 double 51788
20 + 20 double 51789
15 + 30 double 51790
30 + 30 double 51791
20 + 40 double 51792
25 + 50 double 51793
30 + 60 double 51794
40 + 40 double 51795
45 + 45 double 51729
50 + 50 double 51796
40 + 80 double 51797
60 + 60 double 51798
Varpact Classic ”with cable connection”
Varpact Classic ‘‘with busbar connection’’
Varpact (continued)
400 V - 50 hz network
● Varpact Classic with busbar connection
Power (kvar) Step References
12,5 single 51950
25 single 51951
30 single 51952
40 single 51953
45 single 51954
50 single 51977
60 single 51978
80 single 51967
90 single 51979
100 single 51980
120 single 51981
6,25 + 12,5 double 51982
12,5 + 12,5 double 51983
10 + 20 double 51984
15 + 15 double 51985
20 + 20 double 51986
15 + 30 double 51987
30 + 30 double 51988
20 + 40 double 51989
25 + 50 double 51990
30 + 60 double 51991
40 + 40 double 51992
45 + 45 double 51970
50 + 50 double 51993
40 + 80 double 51994
60 + 60 double 51995
7
P.55
P.56
7 Varpact (continued)
400 V - 50 hz network
● Varpact Comfort with cable connection
Power (kvar) Step References
15 single 51801
20 single 51803
25 single 51805
30 single 51807
35 single 51809
45 single 51811
60 single 51813
70 single 51816
90 single 51817
15 + 15 double 51818
15 + 30 double 51819
15 + 45 double 51820
30 + 30 double 51821
30 + 60 double 51822
45 + 45 double 51823
● Varpact Comfort with busbar connection
Power (kvar) Step References
15 single 51740
20 single 51741
25 single 51742
30 single 51743
35 single 51744
45 single 51745
60 single 51746
70 single 51747
90 single 51748
15 + 15 double 51749
15 + 30 double 51750
15 + 45 double 51751
30 + 30 double 51752
30 + 60 double 51753
45 + 45 double 51754
Varpact Comfort ”with cable connection”
Varpact Comfort ”with busbar connection”
Varpact (continued)
400 V - 50 hz network
● Varpact Harmony with cable connection
Rang d’accord Power (kvar) Step References
2,7 (135 hz) 6,25 + 6,25 double 51916
6,25 + 12,5 double 51917
12,5 + 12,5 double 51918
12,5 single 51919
25 single 51920
50 single 51921
3,8 (190 hz) 6,25 + 6,25 double 51925
6,25 + 12,5 double 51926
12,5 + 12,5 double 51927
12,5 single 51928
25 single 51929
50 single 51930
4,3 (215 hz) 6,25 + 6,25 double 51934
6,25 + 12,5 double 51935
12,5 + 12,5 double 51936
12,5 single 51937
25 single 51938
50 single 51939
● Varpact Harmony with busbar connection
Rang d’accord Power (kvar) Step References
2,7 (135 hz) 6,25 + 6,25 double 51757
6,25 + 12,5 double 51759
12,5 + 12,5 double 51761
12,5 single 51763
25 single 51765
50 single 51767
3,8 (190 hz) 6,25 + 6,25 double 51653
6,25 + 12,5 double 51654
12,5 + 12,5 double 51655
12,5 single 51656
25 single 51657
50 single 51658
4,3 (215 hz) 6,25 + 6,25 double 51501
6,25 + 12,5 double 51503
12,5 + 12,5 double 51505
12,5 single 51509
25 single 51511
50 single 51512
Varpact harmony “with cable connection”
7
P.57
P.58
7 Accessories for Varpact modules
Connection moduleRef. 52800It is used to connect:○ the power and control cables for the power factor correction module contactors ( maximum 5 power factor correction modules)○the cubicle supply cables
a → cubicle W = 600b → cubicle W = 650 ou 700c → cubicle W = 800
O → 3 power connection bars (800 A max.) marked L1, L2, L3P → Voltage transformer supplying the contactor coils 400/230 V, 250 VAQ → Control circuit safety fusesR → Contactor control distribution terminal block S → Sliding crosspieces for mounting in cubicles 400 et 500 mm deepT → Extension pieces for mounting in cubicles 650, 700 ou 800 mm wideU → Power factor correction module connection: 5 holes Ø 10 per phaseV → Customer’s incoming cable connection: 2 x M12 bolts per phase
To make it easier to connect the supply cables, we recommended that the connection module be installed at least 20 cm from the ground.
It is supplied with:○ 4 crosspieces○ 2extension pieces
Fastening crosspieces for Varpact Classic et ComfortRef. 51670Specially designed horizontal crosspieces allow easy installation of power factor correction modules in all types of functional and universal cubicles 400 or 500 mm deep.Crosspoieces automatically ensure that the module is correctly positioned at the right depth and maintain a distance of 55 mm between modules. Crosspieces are sold in pairs and must be ordered separately.
Extension pieces for cubicles W = 700 et W = 800 with Varpact Classic and ComfortRef. 51637 and 51639They are used to extend power factor correction modules for use in cubicle of 700 and 800 mm wide.Extension pieces are supplied with the 4 screws required to attach them to the module.
Extension pieces for Prisma Plus cubicle W = 650 with Varpact Classic and ComfortRef. 51635It allows module to be attached directly to Prisma Plus cubicle uprights.Extension piece is supplied with the 4 screws required to attach it to the module.
2 fastening crosspieces (ref. 51670)
Extension pieces for cubiclesW = 650 (ref. 51635)W = 700 (ref. 51637)W =800 (ref. 51639)
Accessories for Varpact modules
Circuit breaker kit for Varpact Classic and Comfort
Ref. 51626, 51627, 51628, 51629It enables to ensures individual and visible circuit breaking of each capacitor step.
Retrofit kit
Ref. 51617, 51619, 51633Set of pieces using for installation and connection of Varpact in functional and universal existing cubicles. It is necessary to choose a Varpact module and to order separately associated retrofit kit
Retrofit kit References
For P400 power factor correction module 51617
For P400 DR power factor correction module 51619
For L600 power factor correction modules on request
For Rectimat 2 capacitor bank in cubicle Standard and h type 51633
Circuit breaker kitRetrofit kit
7
P.59
Power factor correction
Varset presentation p. 61
Our range according to the network p. 63
Varset Direct p. 64
Varset p. 68
Varset fast p. 76
Dimensions p. 77
Varset presentation
Varset is a capacitor bank composed of Varplus² capacitors protected or not by an incoming circuit breaker. It is presented in enclosures or cubicles with different height. It is available in Classic, Comfort and harmony range.
What are the advantages of Varset?
● An easy installation: ○ complete solution ready to be connected and used on site○ no additional power supply needed
● A safe technology: ○ protection against direct contacts thanks to the protection plate○ each capacitor bank is 100% tested in the manufacturing plant (following IEC standard)
● A specific solution according to your need:○ fixed power factor correction → Varset direct○ automatic power factor correction → Varset○ fast automatic power factor correction → Varset fast
Technical data
● Capacitance value tolerance : -5, +10 %● Maximum permissible overcurrent: ○ 30 % under 400 V for Classic, Comfort and harmony 4.3 ranges○ 19 % under 400 V for harmony 3.8 range○ 12 % under 400 V for harmony 2.7 range● Maximum permissible over voltage (8 h over 24 h according to IEC 60831) : 10 %● Insulation level : ○ 0.69 kV○ withstand 50 hz 1 min : 2.5 kV● Ambient temperature around the equipment (electrical room):○ maximum temperature: 40°C○ Average temperature over 24 hours : 35°C○ Average annual temperature: 25°C○ Minimum temperature: -5°C● Degree of protection: IP31 (except on outlet fan: IP21D)● Protection against direct contacts (opened door)● Load shedding (main-standby)● Transformer 400/230 V included● Colour : RAL 9001● Standards : IEC 60439-1, EN 60439-1, IEC 61921
P.61
8
P.62
8 Varset presentation (continued)
Installation
● Enclosure: wall mounting or by free standing plinth (accessory) with top connection of power cables● Cubicle: free standing cubicle with bottom connection of power cables to the busbar pads● The CT (not supplied) has to be placed upstream from the capacitor bank and loads● It is not necessary to provide a 230 V - 50hz power supply to supply the contactor coils.
Options
● Top connection● Extension● Fixed base compensation (for automatic capacitor banks)● Please consult us for other options
Accessoires pour Varset Références
Socle pour fixation au sol des enclosures C1 et C2 65980
Fixed power factor correction Automatic power factor correction Fast power factor correc-
tion
Varset Direct Classic
Varset Direct Comfort
Varset Direct harmony
Varset Classic Varset Com-fort
Varset harmony
Varset Fast
Réseau 50 hz
230 V network p.59
400/415 V network p.60 p.61 p.62 p.63 p.65 p.67 p.71
Our products according to the network
Find the page corresponding to your network thanks to the table below.
8
P.63
P.64
8 Varset Direct
230 V - 50 hz network, fixed compensation
● Varset Direct Classic without incoming circuit breaker
Power (kvar) Type References
10 enclosure C1 65884
15 enclosure C1 65886
20 enclosure C1 65888
25 enclosure C1 65890
30 enclosure C1 65892
40 enclosure C1 65894
50 enclosure C2 65896
60 enclosure C2 65898
● Varset Direct Classic with incoming circuit breaker
Power (kvar) Type Circuit breaker References
10 enclosure C1 NS100 65885
15 enclosure C1 NS100 65887
20 enclosure C1 NS100 65889
25 enclosure C1 NS100 65891
30 enclosure C1 NS160 65893
40 enclosure C1 NS160 65895
50 enclosure C2 NS250 65897
60 enclosure C2 NS250 65899
Varset Direct (continued)
400/415 V - 50 hz network, fixed compensation
● Varset Direct Classic without incoming circuit breaker
Power (kvar) Type References
5 enclosure C1 65666
7,5 enclosure C1 65668
10 enclosure C1 65670
15 enclosure C1 65672
20 enclosure C1 65674
25 enclosure C1 65676
30 enclosure C1 65678
40 enclosure C1 65680
50 enclosure C1 65682
60 enclosure C1 65684
80 enclosure C1 65686
100 enclosure C2 65688
120 enclosure C2 65690
140 enclosure C2 65692
160 enclosure C2 65694
● Varset Direct Classic with incoming circuit breaker
Power (kvar) Type Circuit breaker References
5 enclosure C1 NS100 65667
7,5 enclosure C1 NS100 65669
10 enclosure C1 NS100 65671
15 enclosure C1 NS100 65673
20 enclosure C1 NS100 65675
25 enclosure C1 NS100 65677
30 enclosure C1 NS100 65679
40 enclosure C1 NS100 65681
50 enclosure C1 NS100 65683
60 enclosure C1 NS160 65685
80 enclosure C1 NS160 65687
100 enclosure C2 NS250 65689
120 enclosure C2 NS250 65691
140 enclosure A1 NS400 65693
160 enclosure A1 NS400 65695
8
P.65
P.66
8 Varset Direct (continued)
400/415 V - 50 hz network, fixed compensation
● Varset Direct Comfort without incoming circuit breaker
Power (kvar) Type References
10 enclosure C1 65766
15 enclosure C1 65768
20 enclosure C1 65770
25 enclosure C1 65772
30 enclosure C1 65774
40 enclosure C1 65776
50 enclosure C2 65778
60 enclosure C2 65780
75 enclosure C2 65782
90 enclosure C2 65784
105 enclosure C2 65786
120 enclosure C2 65788
● Varset Direct Comfort with incoming circuit breaker
Power (kvar) Type Circuit breaker References
10 enclosure C1 NS100 65767
15 enclosure C1 NS100 65769
20 enclosure C1 NS100 65771
25 enclosure C1 NS100 65773
30 enclosure C1 NS100 65775
40 enclosure C1 NS100 65777
50 enclosure C2 NS160 65779
60 enclosure C2 NS160 65781
75 enclosure C2 NS250 65783
90 enclosure C2 NS250 65785
105 enclosure C2 NS250 65787
120 enclosure C2 NS250 65789
Varset Direct (continued)
400/415 V - 50 hz network, fixed compensation
● Varset Direct harmony without incoming circuit breaker
Power (kvar) Type References
6,25 cubicle A2 65866
12,5 cubicle A2 65888
25 cubicle A2 65870
37,5 cubicle A2 65872
50 cubicle A2 65874
75 cubicle A2 65876
100 cubicle A2 65878
125 cubicle A2 65880
150 cubicle A2 65882
● Varset Diirect harmony with incoming circuit breaker
Power (kvar) Type Circuit breaker References
6,25 cubicle A2 NS100 65867
12,5 cubicle A2 NS100 65869
25 cubicle A2 NS100 65871
37,5 cubicle A2 NS100 65873
50 cubicle A2 NS100 65875
75 cubicle A2 NS250 65877
100 cubicle A2 NS250 65879
125 cubicle A2 NS250 65881
150 cubicle A2 NS400 65883
8
P.67
P.68
8 Varset
400/415 V - 50 hz network, automatic compensation
● Varset Classic without incoming circuit breaker
Power(kvar) Step (kvar) Type References Power(kvar) Step (kvar) Type References
7,5 2.5 enclosure C1 52831 225 15 cubicle A2 52909
10 2.5 enclosure C1 52833 240 30 cubicle A2 52911
12,5 2.5 enclosure C1 52835 40 cubicle A1 52913
15 5 enclosure C1 52837 270 15 cubicle A3 52915
17,5 2.5 enclosure C1 52839 30 cubicle A2 52917
20 5 enclosure C1 52841 280 40 cubicle A2 52919
22,5 7.5 enclosure C1 52843 300 60 cubicle A2 52921
25 5 enclosure C1 52845 30 cubicle A3 52923
27,5 2.5 enclosure C2 52847 320 40 cubicle A2 52925
30 10 enclosure C1 52849 330 30 cubicle A2 52927
5 enclosure C1 52851 360 30 cubicle A3 52929
35 5 enclosure C1 52853 40 cubicle A2 52931
40 10 enclosure C1 52855 390 30 cubicle A3 52933
5 enclosure C2 52857 400 10 cubicle A3 52935
45 15 enclosure C1 52859 420 60 cubicle A3 52937
5 enclosure C2 52861 30 cubicle A3 52939
50 10 enclosure C1 52863 450 30 cubicle A3 52941
55 5 enclosure C2 52865 480 60 cubicle A3 52943
60 10 enclosure C2 52867 40 cubicle A3 52945
5 enclosure C2 52869 510 30 cubicle A3 52947
65 5 enclosure C2 52871 520 40 cubicle A3 52949
70 10 enclosure C2 52873 540 60 cubicle A3 52951
75 15 enclosure C2 52875 570 30 cubicle A3 52953
80 20 enclosure C2 52877 600 40 cubicle A3 52955
90 15 enclosure C2 52879 60 cubicle A3 52957
10 enclosure C2 52881 660 60 cubicle A4 52959
100 20 enclosure C2 52883 720 60 cubicle A4 52961
105 15 enclosure C2 52885 780 60 cubicle A4 52963
120 15 cubicle A1 52887 840 60 cubicle A4 52965
20 enclosure C2 52889 900 60 cubicle A4 52967
135 15 cubicle A1 52891 960 120 cubicle A4 52969
140 20 cubicle A1 52893 60 cubicle A4 52971
150 15 cubicle A1 52895 1020 60 cubicle A4 52973
160 20 cubicle A1 52897 1080 60 cubicle A4 52975
165 15 cubicle A1 52899 120 cubicle A4 52977
180 20 cubicle A1 52901 1140 60 cubicle A4 52979
195 15 cubicle A2 52903 1200 60 cubicle A4 52981
200 40 cubicle A1 52905 120 cubicle A4 52983
210 15 cubicle A2 52907
Varset (continued)
400/415 V - 50 hz network, automatic compensation
● Varset Classic with incoming circuit breaker
Power(kvar) Step (kvar) Type References Power(kvar) Step (kvar) Type References
7,5 2.5 enclosure C1 52832 225 15 cubicle A3 52910
10 2.5 enclosure C1 52834 240 30 cubicle A3 52912
12,5 2.5 enclosure C1 52836 40 cubicle A1 52914
15 5 enclosure C1 52838 270 15 cubicle A3 52916
17,5 2.5 enclosure C1 52840 30 cubicle A3 52918
20 5 enclosure C1 52842 280 40 cubicle A3 52920
22,5 7.5 enclosure C1 52844 300 60 cubicle A3 52922
25 5 enclosure C1 52846 30 cubicle A3 52924
27,5 2.5 enclosure C2 52848 320 40 cubicle A3 52926
30 10 enclosure C1 52850 330 30 cubicle A3 52928
5 enclosure C1 52852 360 30 cubicle A3 52930
35 5 enclosure C1 52854 40 cubicle A3 52932
40 10 enclosure C1 52856 390 30 cubicle A3 52934
5 enclosure C2 52858 400 10 cubicle A3 52936
45 15 enclosure C1 52860 420 60 cubicle A3 52938
5 enclosure C2 52862 30 cubicle A3 52940
50 10 enclosure C1 52864 450 30 cubicle A3 52942
55 5 enclosure C2 52866 480 60 cubicle A3 52944
60 10 enclosure C2 52868 40 cubicle A3 52946
5 enclosure C2 52870 510 30 cubicle A3 52948
65 5 enclosure C2 52872 520 40 cubicle A3 52950
70 10 enclosure C2 52874 540 60 cubicle A3 52952
75 15 enclosure C2 52876 570 30 cubicle A3 52954
80 20 enclosure C2 52878 600 40 cubicle A3 52956
90 15 enclosure C2 52880 60 cubicle A3 52958
10 enclosure C2 52882 660 60 cubicle A4 52960
100 20 enclosure C2 52884 720 60 cubicle A4 52962
105 15 enclosure C2 52886 780 60 cubicle A4 52964
120 15 cubicle A2 52888 840 60 cubicle A4 52966
20 enclosure C2 52890 900 60 cubicle A4 52968
135 15 cubicle A2 52892 960 120 cubicle A4 52970
140 20 cubicle A2 52894 60 cubicle A4 52972
150 15 cubicle A2 52896 1020 60 cubicle A4 52974
160 20 cubicle A2 52898 1080 60 cubicle A4 52976
165 15 cubicle A2 52900 120 cubicle A4 52978
180 20 cubicle A2 52902 1140 60 cubicle A4 52980
195 15 cubicle A3 52904 1200 60 cubicle A4 52982
200 40 cubicle A2 52906 120 cubicle A4 52984
8
P.69
P.70
8 Varset (continued)
400/415 V - 50 hz network, automatic compensation
● 400/415 V network
● Varset Comfort without incoming circuit breaker
Power(kvar) Step (kvar) Type References
30 7,5 enclosure C1 65501
45 7,5 enclosure C2 65503
60 7,5 enclosure C2 65505
75 15 enclosure C2 65507
90 15 enclosure C2 65509
105 15 cubicle A1 65511
120 15 cubicle A1 65513
150 15 cubicle A1 65515
180 30 cubicle A1 65517
210 30 cubicle A2 65519
240 30 cubicle A2 65521
270 30 cubicle A2 65523
315 45 cubicle A3 65525
360 45 cubicle A3 65527
405 45 cubicle A3 65529
450 90 cubicle A3 65531
495 45 cubicle A4 65533
540 90 cubicle A4 65535
585 45 cubicle A4 65537
630 90 cubicle A4 65539
675 45 cubicle A4 65541
720 90 cubicle A4 65543
765 45 cubicle A4 65545
810 90 cubicle A4 65547
855 45 cubicle A4 65549
900 90 cubicle A4 65551
Varset (continued)
400/415 V - 50 hz network, automatic compensation
● Varset Comfort with incoming circuit breaker
Power(kvar) Step Type References
30 7,5 enclosure C1 65500
45 7,5 enclosure C2 65502
60 7,5 enclosure C2 65504
75 15 enclosure C2 65506
90 15 enclosure C2 65508
105 15 cubicle A2 65510
120 15 cubicle A2 65512
150 15 cubicle A2 65514
180 30 cubicle A2 65516
210 30 cubicle A3 65518
240 30 cubicle A3 65520
270 30 cubicle A3 65522
315 45 cubicle A3 65524
360 45 cubicle A3 65526
405 45 cubicle A3 65528
450 90 cubicle A3 65530
495 45 cubicle A4 65532
540 90 cubicle A4 65534
585 45 cubicle A4 65536
630 90 cubicle A4 65538
675 45 cubicle A4 65540
720 90 cubicle A4 65542
765 45 cubicle A4 65544
810 90 cubicle A4 65546
855 45 cubicle A4 65548
900 90 cubicle A4 65550
8
P.71
P.72
8
Tuning order Power(kvar) Step (kvar) Type References2,7 (135 hz) 12 6,25 cubicle A2 65601
25 12,5 cubicle A2 65603
37 12,5 cubicle A2 65639
50 12,5 cubicle A2 65607
62 12,5 cubicle A2 65609
75 25 cubicle A2 65611
12,5 cubicle A3 65613
100 25 cubicle A2 65615
12,5 cubicle A3 65617
125 25 cubicle A2 65619
137 12,5 cubicle A3 65621
150 25 cubicle A3 65623
50 cubicle A2 65625
175 25 cubicle A3 65627
200 50 cubicle A3 65629
225 25 cubicle A3 65631
250 50 cubicle A3 65633
275 25 cubicle A3 65635
300 50 cubicle A3 65637
350 50 cubicle A4 65639
375 25 cubicle A4 65641
400 50 cubicle A4 65643
450 50 cubicle A4 65645
500 50 cubicle A4 65647
550 50 cubicle A4 65649
600 50 cubicle A4 65651
100 cubicle A4 65653
700 10 cubicle A4 + A3 65655
800 100 cubicle A4 + A3 65657
900 100 cubicle A4 + A3 65659
1000 100 cubicle A4 +A4 65661
1100 100 cubicle A4 + A4 65663
1200 100 cubicle A4 +A4 65665
3,8 (190 hz) 12 6,25 cubicle A2 65701
25 12,5 cubicle A2 65703
37 12,5 cubicle A2 65705
50 12,5 cubicle A2 65707
62 12,5 cubicle A2 65709
75 25 cubicle A2 65711
12,5 cubicle A3 65713
100 25 cubicle A2 65715
12,5 cubicle A3 65717
125 25 cubicle A2 65719
137 12,5 cubicle A3 65721
150 25 cubicle A3 65723
50 cubicle A3 65725
175 25 cubicle A3 65727
200 50 cubicle A3 65729
225 25 cubicle A3 65731
250 50 cubicle A3 65733
Varset (continued)
400/415 V - 50 hz network, automatic compensation● Varset harmony without incoming circuit breaker
Tuning order Power(kvar) Step Type References3,8 (190 hz) 275 25 cubicle A3 65735
300 50 cubicle A3 65737
350 50 cubicle A4 65739
375 25 cubicle A4 65741
400 50 cubicle A4 65743
450 50 cubicle A4 65745
500 50 cubicle A4 65747
550 50 cubicle A4 65749
600 50 cubicle A4 65751
100 cubicle A4 65753
700 10 cubicle A4 +A3 65755
800 100 cubicle A4 + A3 65757
900 100 cubicle A4 +A3 65759
1000 100 cubicle A4 + A4 65761
1100 100 cubicle A4 + A4 65763
1200 100 cubicle A4 +A4 65765
4,3 (215 hz) 12,5 6,25 cubicle A2 65801
25 12,5 cubicle A2 65803
37,5 12,5 cubicle A2 65805
50 12,5 cubicle A2 65807
62,5 12,5 cubicle A2 65809
75 25 cubicle A2 65811
12,5 cubicle A3 65813
100 25 cubicle A2 65815
12,5 cubicle A3 65817
125 25 cubicle A2 65819
137 12,5 cubicle A3 65821
150 25 cubicle A3 65823
50 cubicle A2 65825
175 25 cubicle A3 65827
200 50 cubicle A3 65829
225 25 cubicle A3 65831
250 25 cubicle A3 65833
275 50 cubicle A3 65835
300 50 cubicle A3 65837
350 25 cubicle A4 65839
375 50 cubicle A4 65841
400 50 cubicle A4 65843
450 50 cubicle A4 65845
500 50 cubicle A4 65847
550 50 cubicle A4 65849
600 100 cubicle A4 65851
10 cubicle A4 65853
700 100 cubicle A4 +A3 65855
800 100 cubicle A4 +A3 65857
900 100 cubicle A4 + A3 65859
1000 100 cubicle A4 +A4 65861
1100 100 cubicle A4 + A4 65863
1200 100 cubicle A4 + A4 65865
Varset (continued)
400/415 V - 50 hz network, automatic compensation
● Varset harmony without incoming circuit breaker (continued)
8
P.73
P.74
8
Tuning order Power(kvar) Step Type References2,7 (135 hz) 12 6,25 cubicle A2 65600
25 12,5 cubicle A2 65602
37 12,5 cubicle A2 65604
50 12,5 cubicle A2 65606
62 12,5 cubicle A2 65608
75 25 cubicle A2 65610
12,5 cubicle A3B 65612
100 25 cubicleA2 65614
12,5 cubicle A3B 65616
125 25 cubicle A2 65618
137 12,5 cubicle A3B 65620
150 25 cubicle A3B 65622
50 cubicle A2 65624
175 25 cubicle A3B 65626
200 50 cubicle A3B 65628
225 25 cubicle A3B 65630
250 50 cubicle A3B 65632
275 25 cubicle A3B 65634
300 50 cubicle A3B 65636
350 50 cubicle A4B 65638
375 25 cubicle A4B 65640
400 50 cubicle A4B 65642
450 50 cubicle A4B 65644
500 50 cubicle A4B 65646
550 50 cubicle A4B 65648
600 50 cubicle A4B 65650
100 cubicle A4B 65652
700 10 cubicle A4B + A3B 65654
800 100 cubicle A4B + A3B 65656
900 100 cubicle A4B + A3B 65658
1000 100 cubicle A4B +A4B 65660
1100 100 cubicle A4B + A4B 65662
1200 100 cubicle A4B + A4B 65664
3,8 (190 hz) 12 6,25 cubicle A2 65700
25 12,5 cubicle A2 65702
37 12,5 cubicle A2 65704
50 12,5 cubicle A2 65706
62 12,5 cubicle A2 65708
75 25 cubicle A2 65710
12,5 cubicle A3B 65712
100 25 cubicle A2 65714
12,5 cubicle A3B 65716
125 25 cubicle A2 65718
137 12,5 cubicle A3B 65720
150 25 cubicle A3B 65722
50 cubicle A2 65724
175 25 cubicle A3B 65726
200 50 cubicle A3B 65728
225 25 cubicle A3B 65730
250 50 cubicle A3B 65732
Varset (continued)
400/415 V - 50 hz network, automatic compensation● Varset harmony with incoming circuit breaker
Tuning order Power(kvar) Step Type References3,8 (190 hz) 275 25 cubicle A3B 65734
300 50 cubicle A3B 65736
350 50 cubicle A4B 65738
375 25 cubicle A4B 65740
400 50 cubicle A4B 65742
450 50 cubicle A4B 65744
500 50 cubicle A4B 65746
550 50 cubicle A4B 65748
60050 cubicle A4B 65750
100 cubicle A4B 65752
700 10 cubicle A4B + A3B 65754
800 100 cubicle A4B + A3B 65756
900 100 cubicle A4B + A3B 65758
1000 100 cubicle A4B + A4B 65760
1100 100 cubicle A4B + A4B 65762
1200 100 cubicle A4B + A4B 65764
4,3 (215 hz) 12 6,25 cubicle A2 65800
25 12,5 cubicle A2 65802
37 12,5 cubicle A2 65804
50 12,5 cubicle A2 65806
62 12,5 cubicle A2 65808
7525 cubicle A2 65810
12,5 cubicle A3B 65812
10025 cubicle A2 65814
12,5 cubicle A3B 65816
125 25 cubicle A2 65818
137 12,5 cubicle A3B 65820
15025 cubicle A3B 65822
50 cubicle A2 65824
175 25 cubicle A3B 65826
200 50 cubicle A3B 65828
225 25 cubicle A3B 65830
250 50 cubicle A3B 65832
275 25 cubicle A3B 65834
300 50 cubicle A3B 65836
350 50 cubicle A4B 65838
375 25 cubicle A4B 65840
400 50 cubicle A4B 65842
450 50 cubicle A4B 65844
500 50 cubicle A4B 65846
550 50 cubicle A4B 65848
60050 cubicle A4B 65850
100 cubicle A4B 65852
700 10 cubicle A4B +A3B 65854
800 100 cubicle A4B + A3B 65856
900 100 cubicle A4B +A3B 65858
1000 100 cubicle A4B +A3B 65860
1100 100 cubicle A4B + A4B 65862
1200 100 cubicle A4B + A4B 65864
8
P.75
Varset (continued)
400/415 V - 50 hz network, automatic compensation● Varset harmony with incoming circuit breaker
P.76
8
D
Varset Fast
General information
Varset Fast capacitor bank is designed to supply reactive power needed in less than 40 ms.
Advantages
● Improves equipment service life● Reduces electricity consumption
Characteristics● Network voltage 400 V● Frequency 50 hz● Degree of protection IP21D● Capacitor rated voltage: 480 V - 50 hz● Rang d’accord diponible : 4,3 (215 hz), 3,8 (150 hz), 2,7 (135 hz)● Load shedding (main - standby)● Insulation level : 690 V, tenue 50 hz 1 min : 2,5 kV● Protection against direct contact (opened door))
Installation
● Cubicle: free standing cubicle with bottom connection of power cables to the busbar pads● The CT (not supplied) has to be placed upstream from the capacitor bank and loads● It is not necessary to provide a 230 V - 50hz power supply to supply the contactor coils.
Our range
● 400/415 V network
Power (kvar)
Step (kvar) Type References
4,3 (215 hz) 3,8 (190 hz) 2,7 (135 hz)
100 25 cubicle A3 65941 65927 65913
125 25 cubicle A3 65942 65928 65914
150 25 cubicle A3 65943 65929 65915
150 50 cubicle A3 65944 65930 65916
175 25 cubicle A3 65945 65931 65917
200 50 cubicle A3 65946 65932 65918
250 50 cubicle A3 65947 65933 65919
300 50 cubicle A3 65948 65934 65920
350 20 cubicle A4 65949 65935 65921
400 50 cubicle A4 65950 65936 65922
450 50 cubicle A4 65951 65937 65923
500 50 cubicle A4 65952 65938 65924
550 50 cubicle A4 65953 65939 65925
600 50 cubicle A4 65954 65940 65926
Dimensions
Type height Width Depth
enclosure C1 450 500 275
enclosure C2 800 500 275
cubicle A1 1100 550 600
cubicle A2 1100 800 600
cubicle A3 2000 800 600
cubicle A4 2000 1600 600
cubicle A4 + A3 2000 2400 600
cubicle A4 +A4 2000 3200 600
cubicle A3B 2000 1350 600
cubicle A4B 2000 2150 600
cubicle A4B + A3B 2000 3500 600
cubicle A4B + A4B 2000 4300 600
Enclosure C1 without incoming circuit breaker
Cubicles A1 et A2 without incoming circuit Cubicle A3 without incoming circuit Cubicle A4 without incoming circuit
P.77
Enclosure C2 without incoming circuit breaker
W D DW
W W WD D
8
Harmonic filtering solutions
Presentation p. 79
Presentation
General information
harmonic filtering equipment are presented in cubicles.harmonic filtering solutions comply with IEC 604-39 standard.
Three types of solutions are available:
● Passive filterIt is made up of detuned reactors and capacitors tuned on the harmonic frequency of the order to be suppressed. In other words, they are designed to absorb harmonic currents at a particular frequency.In case of more than one order to eliminate, several unit can be associated.A passive filter enables to:○ correct the power factor○ benefit from a high capacity of filtering
● Active filterAn active filter cancels harmonics by dynamically injecting out of phase harmonic current.It reduces current distortion that, in turn, reduces voltage distortion
● hybrid filterIt is made up of a passive filter combined with an active filter in the same cubicle.
Characteristics
● Passive filter
Network voltage 400 V three phase
harmonic order cancelled 5th to 11th
Reactive power from 100 kvar to 350 kvar
Other voltages and powers on request.
● Active filter
Network voltage from 208 to 480 V three-phase
harmonic order cancelled from 2nd to 50th
Power ratingsup to 300 A per unitExpandable capabilities : parallel up to 10 units with different ratings on one set of current transformer
● hybrid filter
Network voltage 400 V three phase
Passive filter 5th order
Active filter from 20 A
Reactive power up to 350 kvar (other power on request)
harmonic order treated 2nd to 25th
P.79
9
03/2009
En raison de l’évolution des normes et du matériel, les caractéristiques indiquées par les textes et les images de ce document ne nous engagent qu’après confirmation par nos services.
Ce document a été imprimé sur du papier écologique.
Conception, réalisation : Schneider ElectricImpression :
Schneider Electric Industrie SASRECTIPhASE399, rue de la GareF-74371 Pringy CedexFranceTél. : 33 (0)4 76 57 60 60www.schneider-electric.com
RCS Nanterre B 954 503 439