3 June 2010 Solar Air Conditioning 1 K. Gommed & G. Grossman Faculty of Mechanical Engineering, Technion, I. I. T. Haifa 32000, ISRAEL "Solar Air Conditioning Based on Liquid Desiccant Open Absorption Cycle".
Transcript
Page 1: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 1

K. Gommed & G. GrossmanFaculty of Mechanical Engineering, Technion, I. I. T.

Haifa 32000, ISRAEL

"Solar Air Conditioning Based on Liquid Desiccant Open Absorption Cycle".

Page 2: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 2

Direct Utilization of Solar Heat to Perform Some of the Air Conditioning Tasks

Why Air Conditioning ?Air conditioners are big electric consumersAvailability of solar energy when air conditioning (cooling) is needed

Direct Vs. IndirectHigh efficiency (COP) Vs. low efficiency Example: Solar Power (thermal) Electric Power Cooling Power (thermal)

What Tasks & Benefits ?

The Objective

Page 3: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 3

Air Conditioning ??

• Temperature control

Sensible Heat Load

• Humidity control

Latent Heat Load

Conventional AC: Air is (over) cooled below dew-point,

Then the dry-air is reheated to supply conditions

�������� a Coupled AC-process - where w = w (T)

���� Complex control of T & w

���� Need Low Coil Temperature (below dew-point)

Hybrid AC: Air is first dried to optimal humidity level,

Using the Proposed Liquid Desiccant Open Absorption Cycle

to deal with Latent Heat Load by Solar

Then air is cooled to optimal convenient conditions

Using Conventional High Temperature Cooling Coil

to deal with Sensible Heat load Electrically

�������� an inherent Decoupled & optimized AC-process

Prior artPrior art

* O2 in , CO2 out

* Dust particles filtration

* Air-born microbes filtration

• Clean/Fresh air supply*

Page 4: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 4

Page 5: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 5

European approach to A/C

• Quality central air conditioning

– Minimum air circulation

– Maximum dryness

– Independent control of humidity and temp

• Method of implementation

– Radiant cooling (chilled ceiling) to handle sensible load

– Deep dehumidification of make-up air and low-velocity distribution to handle latent load

It is different from common US practice…

Page 6: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 6

Liquid Desiccant Cooling System Diagram

Absorber

Solution Pump

M

C

Blower Fresh Air

Option "B" Diagram

Auxiliaryelectrical

heat pump

HX

Desorber

Solution Pump

H

M

Air-Air HX

Exhaust Air

Exhaust Air

Blower

Fresh Air

SupplyAir

Air-Air HX

Hybrid approach to A/C

Page 7: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 7

Typical Liquid Desiccant Dehumidification System

Page 8: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 8

Page 9: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 9

Page 10: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 10

0.00

5.00

10.00

15.00

20.00

25.00

30.00

35.00

40.00

10:19:12 12:43:12 15:07:12 17:31:12 19:55:12

Time

Hu

mid

ity

Win Wout_1 Wout_2

Results – Humidity

Page 11: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 11

The New Dehumidification System

Ambient Air

Supply

Air

Absorber

Blower

Solution Pump

Cold-Water

Pump

Water/Solution H.X.

Cold Water

From Cooling

Tower

to Cooling

Tower

78

5 6

13

12

14

Air/Air H.X.

Ambient

Air

Exhaust

AirBlower

Solution Pump

Hot-Water

Pump

Water/Solution H.X.

Hot Water

From Storage

Tank

to Storage

Tank

3 4

12

FA15

11

GA 16

Desorber

Concentration Driven Mass

Exchanger

910

Page 12: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 12

Reactor Assembly

ריאק טור . 1

ת ע לת כניס ת אוו יר. 2

מת א� למח לי� חו� . 4

מח לי� חו� . 5

ת ע לת יצי את אוו יר . 3

Page 13: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 13

Regenerator Reactor

Page 14: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 14

Regenerator & Dehumidifier

Page 15: Solar Air Conditioning Based on Liquid Desiccant Open ...surveys.sni.technion.ac.il/files/events/energy... · 6/3/2010  · Hybrid AC : Air is first dried to optimal humidity level,

3 June 2010 Solar Air Conditioning 15

Thank you