Date post: | 04-Apr-2018 |
Category: |
Documents |
Upload: | ashutoshmech |
View: | 248 times |
Download: | 5 times |
of 249
7/29/2019 Turbine Operation Manual
1/249
1 1
Table of Content
Part I Turbine Mainframe Operation .................................................................................. 4
Chapter I Overview and Specifications of Unit Equipment.................................................4
1. Overview of Steam Turbine and Auxiliaries....................................................................4
2. Main Design Specifications of the Unit ..........................................................................8
2.1 Main Design Specifications of the Steam Turbine................................................. 8
2.2 Index of Steam and Water Quality ......................................................................13
3. Main auxiliaries and system specifications..................................................................14
3.1 Feed water pump set..........................................................................................14
3.2 High and low-pressure bypass ........................................................................... 22
3.3 Condenser..........................................................................................................26
3.4 Condensate pump ............................................................................................27
3.5 Oil purifier ......................................................................................................... 29
3.6 Performance of water-ring vacuum pump unit....................................................31
Chapter II Protection, Control and Test of the Unit .......................................................... 32
1. General Rules of Interlock Protection Test...................................................................32
1.1 Purpose and Division of Interlock Protection ...................................................... 32
1.2 Test Method of Interlock Protection ....................................................................32
1.3 Verification for Interlock Protection Test Results.................................................32
2. Interlock Protection of Mainframe ................................................................................ 32
2.1 Main Thermal Protection of Steam Turbine ........................................................ 323. Thermal Interlock Protection of Auxiliaries...................................................................43
4. Unit Control and Manual Devices ................................................................................ 65
4.1 Sequence Control System (SCS) .......................................................................65
4.2 Analogue Control System (MCS)........................................................................66
4.3 Turbine Digital Electro-hydraulic Control System (DEH).....................................75
5. Main Test of the Unit....................................................................................................84
5.1 Static Test of the Control System........................................................................84
5.2 Manual Trip Test .................................................................................................84
5.3 Trip Protection Test of Turbine Emergency Trip System (ETS)........................... 85
5.4 Turbine Main Trip Solenoid Valve Test................................................................86
5.5 Power-load Unbalance Relay (PLU) Loop Test ..................................................87
5.6 Eccentric Ring Oil Spray Test of Emergency Governor ...................................... 87
5.7 Emergency Governor Minimum Oil Spray Action Speed Test .............................88
5.8 Turbine Mechanical Over-speed Test .................................................................89
5.9 Electric Over-speed Test of Steam Turbine ........................................................ 91
5.10 Valves Activity Test ...........................................................................................93
5.11 MSV and CV Leak Test.....................................................................................93
7/29/2019 Turbine Operation Manual
2/249
2
5.12 Mainframe Low Lube Oil Pressure Interlock Protection Test ............................93
5.13 Vacuum Leakage Test ......................................................................................94
5.14 Extraction Check Valve Activity Test ................................................................. 94
5.15 Load Rejection Test ..........................................................................................94
Chapter III Start-up and Outage of the Unit and Operating Maintenance Thereof ...........97
1 Start-up of the Unit........................................................................................................97
1.1 Start-up Specifications and Requirements..........................................................97
1.2 Start-up Prohibition Conditions of the Unit..........................................................98
1.3 Start-up State Classification of the Unit ............................................................ 100
1.4 Inspection before the Steam Turbine Start-up ..................................................100
1.5 Operation of Auxiliaries and Systems before the Unit Start-up .........................101
1.6 Unit Start-up Parameters and Mode Selection Principal...................................103
1.7 Cold Start-up of the Unit ................................................................................... 104
1.8 Warm and Hot Start-up of Unit.......................................................................... 115
1.9 Extreme Hot Start-up of Unit........................................................................... 1177
2. Normal Operation and Maintenance of Unit............................................................. 1188
2.1 Routine Maintenance and Requirements ....................................................... 1188
2.2 Operational Parameters of Unit ...................................................................... 1199
2.3 Adjustment and Maintenance for Normal Operational Parameters of Unit .....1222
3. Normal Shutdown of Unit...........................................................................................125
3.1 Preparations before Shutdown ......................................................................... 1253.2 Shutdown with Variable Parameter...................................................................125
3.3 Operations after Generator Disconnection ....................................................... 127
3.4 Cautions for Unit Shutdown............................................................................1288
3.5 Regular work for steam turbine ........................................................................130
Chapter Accident Management of Unit..................................................................1333
1. General Principles ................................................................................................... 1333
2. Manual on the Handling of Unit Accidents...............................................................1344
2.1 Emergency Outage Conditions of Unit ........................................................... 1344
2.2 Fault Shutdown Conditions of Unit .................................................................1388
2.3 Comprehensive Accident Management of Unit............................................... 1400
3. Abnormal Operation and Accident Management of Steam Turbine......................... 1466
3.1 Condenser Vacuum Drop ............................................................................... 1466
3.2 Steam Turbine Water Attack ........................................................................... 1488
3.3 Abnormal Vibration of Steam Turbine ............................................................. 1500
3.4 Increased Axial Displacement ........................................................................1522
3.5 Damaged or Broken Blade ............................................................................. 1532
3.6 Lubricating Oil System Failure........................................................................ 1533
7/29/2019 Turbine Operation Manual
3/249
3
3.7 EH Oil System Failure .................................................................................... 1577
3.8 Feed Pump Failure.........................................................................................1588
3.9 Deaerator Failure ...........................................................................................1622
3.10 Heater Failure...............................................................................................1644
3.11 Generator Sealing Oil System Failure .......................................................... 1655
3.12 Generator Hydrogen Cooling System Failure...............................................1677
3.13 Generator Stator Cooling Water System Failure.............................................168
Part II Auxiliary System Operation ............................................................................... 1722
Chapter General Rules on Start-up (in operation) and Shutdown (out of service) of Auxiliaries
and systems ................................................................................................................1722
1. General Operating Rules of Auxiliaries.................................................................... 1722
2 General Outage Rules of Auxiliaries......................................................................... 1744
Chapter II Auxiliaries and Systems .............................................................................. 1765
1. Lubricating Oil System.............................................................................................1765
2. EH Oil System .........................................................................................................1799
3. Unit Bypass System.................................................................................................1833
4. Gland Sealing System ............................................................................................. 1855
5. Vacuum System.........................................................................................................190
6. Circulating Water System ........................................................................................1933
7 Open Circulating Cooling Water System .................................................................. 1955
8. Condensate System .................................................................................................. 1979. Regeneration and extraction Steam System..............................................................200
10. Feed pump System ............................................................................................... 2111
11. Auxiliary Steam System .........................................................................................2199
12. Generator Sealing Oil System ............................................................................... 2222
13. Generator Hydrogen Cooling System.................................................................... 2244
14. Generator stator water cooling system ..................................................................229
Appendix ...................................................................................................................... 232
7/29/2019 Turbine Operation Manual
4/249
4
Part I Turbine Mainframe Operation
Chapter I Overview and Specifications of Unit Equipment
1. Overview of Steam Turbine and AuxiliariesThe N600-16.7/538/538/-3 steam turbine used in this project is a subcritical, single reheat,
condensing, tandem, three-cylinder four-exhaust, impulse steam turbine produced and
designed by Dongfang Steam Turbine Works. The main and reheat steam of it is configured to
unit system in form of two-one-two. Its high pressure (HP) cylinder contains one
single-governing stage and eight-pressure stage; the intermediate pressure (IP) cylinder has
five-pressure stage; the high and intermediate pressure (HIP) flow passages are designed to
two-layer countercurrent with a common casing; and the low pressure (LP) is two-layer
double-flow LP cylinder with 2*2*7 pressure stages. Through four pieces of admission pipe
that are vertically and symmetrically arranged at the middle of the HIP outer casing, the main
steam enters into the steam turbine, and then to the boiler reheater after experiencing HP
9-stage work. Similarly, the reheat steam enters into the IP part of the steam turbine in the
same way as the main steam, and then enters into two LP two-pass cylinders separately
through a piece of reducing connector after IP five-stage work; at last it is exhausted into a
double-back pressure condenser through the bi-directionally arranged exhaust pipe of the two
cylinders after the 7-stage work.The steam turbine is equipped with two HP main stop valves that are used for contacting the
sealing surface well so as to prevent steam leak at the status of wide open. There are steam
strainers inside the valves for purpose of preventing foreign substances from flowing into the
flow passage. The unit is provided with four main steam control valves for regulating steam
volume entering the steam turbine. They are equipped with a balance chamber for preventing
from vibrating and arranged into a shared valve casing in the form of straight line. The valve
casing is independent of the steam turbine proper. The IP main steam valves and control
valves are union valves with a common valve seat, wherein the former two are sleeve valves
and the later four are spherical valves. Both of them are able to move independently during
the total stroke, and opened, closed by hydraulic pressure and spring separately. The unit is
also provided with two IP union valves each of which has a steam strainer for preventing
foreign substances from entering the flow passage. Under normal condition, the IP main stop
valves and control valves are widely open. The main stop valves, control valves and union
valves are equipped with on-off testers solely used after overhaul and the remote test can be
performed in operation of them on the condition that the load is not subject to large fluctuation.
The structure of HIP cylinder with common casing and double-shell is used. It consists of four
parts, including an integrated HIP outer casing divided into upper and low half casings from
7/29/2019 Turbine Operation Manual
5/249
5
the split, a HP inner casing divided into upper and lower half casings, an IP inner casing
divided into upper and lower half casings and an IP outer casing. Two LP cylinders are
symmetrical double split flow structure with the function of middle steam admission and
divided into upper and lower parts from the split. The LP cylinders are designed to three-layer
with the first layer served as inner casing for accommodating the elements of the flow
passage, the second one as a heat insulating layer and the third one as an outer casing for
exhausting steam and supporting the elements in the inner casing. The LP cylinder is
connected with the condenser by a stainless steel elastic expansion joint.
The shaft system of the unit is composed of a steam turbine HP rotor and IP rotor, LP rotor A
and B and a generator rotor. Each of them is connected by a solid coupling. The steam
turbine rotors without center holes are totally integral rotor.
The steam turbine is supported by six pieces of bearing blocks; the HIP rotors are supported
by two titling-pad bearings with #1 and #2 numbers of bearing block; two LP rotors are
supported by two elliptical bearing with #3, #4, #5 and #6 numbers of bearing block, horizontal
split and spherical types, and automatic alignment and manual functions. A thrust bearing with
the capability of withstanding much high axial thrust load, whereas resulting in little loss on
any loads is structured to bevel dual thrust disc and located in a middle bearing housing
beside the #2 bearing block.
The expansion dead points of the HIP cylinder locates near the center line of the #2 bearing
block, the LP cylinder A and B, respectively. A transverse pin at the dead point restricts the
axial displacement of the cylinder, and longitudinal pins in front and back of the front bearinghousing and the longitudinal center line of the two low pressure cylinders guide the cylinders
to expand freely along the axial direction and restrict the deviation laterally.
An automatic-meshing turning gear of the steam turbine consisting of a motor and gear train
is equipped between the steam turbine and the generator. Its revolution is 1.5r/min and it is
able to automatically operate and trip.
To avoid water and steam from returning back the steam turbine, the drainage and exhaust
steam systems of the steam turbine are designed to able to exhaust condensate in all of
devices, pipelines and valves and steam in the HIP cylinder and HIP gland sealing system
discharged at the time of unit trip. Their pneumatic drain valves are able to be automatically
and widely opened at the time of lacking compressed air resource. To prevent steam from
arriving at the intermediate and low pressure parts to do work through the steam sealing gland
located between the high and intermediate pressure parts at the time of load rejection, an
emergency discharge valve is set at the place of the steam sealing gland. In case that the IP
control valve is closed, it automatically opens and reliefs most of leaked steam into the
condenser. In order to avoid overheat at the HP steam exhaust part resulting from windage
loss in case that the unit is started by the IP cylinder or high and low pressure bypass on low
load, a vent valve (VV) is equipped on the exhaust pipeline of the HP cylinder to connect with
7/29/2019 Turbine Operation Manual
6/249
6
the condenser. There are no drain points on the high and intermediate pressure cylinders, and
so water can be drained solely through the drain point on an extraction steam pipe. Water of
the LP cylinder is drained to a condenser hot well level and water of the HP main steam pipes
and valves is drained to a drain flash tank of the condenser. The unit is provided with two sets
of rectangular drain flash tank located at lateral outer walls of the HP condenser and the LP
condenser, respectively, and a spray de-superheating device that is used for spraying water
while the unit is in operation.
The regenerative system of the steam turbine has 8-stage non-regulatory extraction for three
sets of HP heater, one deaerator and four sets of LP heater, respectively. Water of the HP and
LP heaters reflows to the deaerator and the condenser, respectively by means of cascaded
drain. Drain water can flow into the condenser directly in case of accident or low load. Steam
source of the steam turbine for feed water pump is from four-stage extraction under normal
conditions; in case of startup of the unit and low load, it is automatically switched to reheat
steam. Its exhaust steam is discharged into a main condenser. Besides, for regenerative
extraction steam and steam of the steam turbine of the feed water pump, four-stage extraction
of the steam turbine is able to provide auxiliary steam for others. To meet the demand of
connecting the steam exhaust pipe and the drain pipe, the #7 and #8 LP heaters are designed
to compound heaters with a common shell and horizontally configured at throat part of the
condenser with part of which out of the shell.
The condensate system employs an IP condensate polishing system each of which is
provided with a vertical condensate pump with 2*100% volume and one of which is served asstandby. Condensate after boosting pressure enters into the deaerator through a polishing
unit, a gland heater and four LP heaters.
The gland sealing system of the steam turbine is a self-sealing system, i.e. in normal
operation of the unit, steam leakage from the shaft-end steam gland of the HIP cylinder, and
the steam leakage from HIP main stop valve and valve stems of the control valves after being
sprayed and de-superheated is provided for the LP shaft-end steam gland. The redundant
steam flows to the LP heater or condenser through an overflow station. During startup or
operation of unit on low load, the auxiliary steam station is used for providing steam for the
steam gland. The unit is provided with one set of gland heater with 100% volume and two sets
of gland extraction fan with 100% volume. The gland cooler and the steam turbine of the feed
water pump shares the gland steam. During startup and operation of the unit with low load,
gland steam is fresh or auxiliary steam and pressure of the gland main pipe is maintained by a
gland steam supply valve and an overflow valve. During operation of the unit with 25%-60% of
load, its gland steam is provided by the gland cooler; while the load is over 60%, the unit is
self-sealed and the gland steam supply valve is closed. The set value of the gland pressure is
maintained by the overflow valve and the redundant steam is discharged into #8 A LP heater
through the overflow valve. The redundant steam is discharged into the condenser through a
7/29/2019 Turbine Operation Manual
7/249
7
conversion valve in case of #8 A LP heater failures.
The emergency governing system is the actuating mechanism of the HP fire-resistant oil DEH,
which works on instruction reception from the DEH and completion of latching, meets the
requirements of combined startup of high and intermediate pressure cylinders, startup of the
IP cylinder and activity test of the valves, and has the functions of over-speed limitation, fast
reliable steam admission interruption and over-speed protection. The system comprises a LP
governing system and a HP fire-resistant oil system. The LP governing system is composed
of an emergency governor, an emergency governor device and its link lever, a manual stop
mechanism, a reset test valve block, a mechanical shutdown electromagnet and an oil guide
ring, etc. Main functions of it comprise latch, interruption, oil spray and speed hoisting. The
HP fire-resistant oil system consists of a hydraulic servo system, a HP trip system and a
fire-resistant oil supply system. The hydraulic servo system, consisting of a valve control
stage and a servomotor, is used for controlling opening of the valves and completing fast
shutdown of them. This unit is provided with four sets of servomotor for HP control valves, two
for HP main stop valves, IP main stop valves and IP control valves, respectively. All of said
servomotors, with unilateral oil feed, are started up by fire-resistant oil pressure and closed by
spring force of the control stage, so as to guarantee all of them can be shut down in case of
pressure oil loss. The oil supply system, mainly consisting of two sets of
pressure-compensated variable plunger pump, a regenerative device, an accumulator, oil
filtering components, etc., is used for supplying HP working oil for every actuating
mechanisms of the emergency governing system.The lubricating oil system is served as main oil pump-oil turbine system driven by the major
axis of the steam turbine. In addition to all bearings of the turbine generators, it supplies oil for
the hydrogen sealing system of the generators, the lubricating device of the turning gear and
the jacking oil pump as well. It comprises a packaged oil container, a main oil pump (MOP), an
AC auxiliary oil pump (TOP), a DC emergency oil pump (EOP), a boiler oil pump (BOP), a
jacking oil device, an oil purification and regeneration device, six sets of electric heater, two
sets of oil cooler with 100% volume, a change-over valve, a flume extractor, etc. The strainers
in the lubricating oil system are able to be replaced to clean. In view from the head, the
lubricating oil system locates on the right.
For the purpose of successfully putting the turning gear into operation, the jacking oil system
is applied to providing HP oil for every bearing at the time of startup and shutdown of the unit.
Therefore, two sets of jacking oil pump, with the advantages of high efficiency, low heat value
and noise, reliable performance and no leakage under continuous HP operation, and high
volumetric efficiency, etc., are applied in the system.
The unit employs a HLP two-stage series-wound pneumatic bypass system, in which the
capacity of high pressure bypass is 60%BMCR. This system is able to make the unit optimally
start and shut down, realize two operating modes in accordance with the operating conditions,
7/29/2019 Turbine Operation Manual
8/249
8
startup and stop curves of the steam turbine, shorten the starting time of the unit in
cooperation of setting up a steam temperature of the steam turbine suitable for the boilers. In
case that the unit load is variable, the system can be applied to regulating it so as to improve
the stability of the boiler in operation.
The feed water system is configured to unit system, with two sets of 50% BMCR turbo-feed
pump and one set of 50% BMCR electro-driven variable-speed feed water pump for one set
of unit. The turbo-feed pump is put into normal operation and the electro-driven
variable-speed feed water pump is served as standby or startup. The turbo-feed pump is
provided with HP and LP steam sources and configured at the operating floor of the steam
turbine, and its steam is exhausted into the condenser of the turbine mainframe. The feed
water system also provides attemperating water for overheat and reheat attemperators, and
the bypass system.
The unit adopts a distributed control system (DCS) that has the functions of monitoring the
DEH, MEH operator stations and other control systems (data communication interface) and
meeting the requirements of various operating conditions. The DEH produced by Dongfang
Electric Automatic Control Cooperation Limited for controlling the rotating speed and load of
the steam turbine is employed in the turbine governing system.
Startup mode of the unit: IP cylinder startup, combined startup of the HP, IP cylinders,
whereas IP cylinder startup in priority. The combined startup mode is solely used in case that
the bypass system is cut off due to failure.
Operating mode of the unit: constant pressure, and constant pressure-to-slidingpressure-to-constant pressure
Load character: with the main functions of bearing base load, and peak load manual function
Arrangement of the unit: the turbine generating set is indoors longitudinal sequential
arrangement. The lubricating oil system is configured on the right in view from the head to the
generating set.
Cooling mode of the unit: unit system with counter-flow circulating water system
2. Main Design Specifications of the Unit
2.1 Main Design Specifications of the Steam Turbine
2.1.1 Steam Turbine Proper Specifications
S/N Item Unit Data
Unit specifications
7/29/2019 Turbine Operation Manual
9/249
9
S/N Item Unit Data
1 Unit model Sub-critical,
single reheat,
three-cylinder
four-exhaust,
tandem and
condensing
2 Steam turbine model N600-16.7/538/5
38-3
3 TMCR output MW 600
4 VWO output MW 640.647
5 HP heater and omni-segmentation
output
MW 600
6 TMCR main steam pressure MPa(a) 16.7
7 TMCR main steam temperature 538
8 TMCR HP cylinder exhaust steam
pressure
Mpa(a) 3.849
9 TMCR inlet pressure of reheat steam Mpa(a) 3.464
10 TMCR inlet temperature of reheat steam 538
11 TMCR main steam throttle flow t/h 1876
12 Maximum throttle flow of main steam t/h 2028
7/29/2019 Turbine Operation Manual
10/249
10
S/N Item Unit Data
13 TMCR throttle flow of reheat steam t/h 1596.377
14 TMCR exhaust steam pressure Mpa(a) 0.01013
15 Steam distribution mode Composite
(nozzle/throttle)
16 Design temp of cooling water Open
32.4/closed 38
17 TMCR feed temperature 277.2
18 Rated speed R/Min 3000
19 TMCR heat consumption kJ/kW.
h
kcal/kW
8130/1942
20 Regenerative heat grade of feed water 3+1+4 (high
pressure plus
de-oxidation plus
low pressure)
21 Length of low pressure last stage blade mm 851
22 Total internal efficiency of steam turbine %
High pressure cylinder efficiency %
Intermediate pressure cylinder
efficiency
%
7/29/2019 Turbine Operation Manual
11/249
11
S/N Item Unit Data
Low pressure cylinder efficiency %
23 Series of flow passage
High pressure cylinder Grade 9
Intermediate pressure cylinder Grade 5
Low pressure cylinder Grade 2*2*7
24 Critical speed
25 Shafting torsion frequency Hz
26 Dimensions (Length, width and height) m 27.82*10.68*6.29
2.1.2 Operational parameter
Item Unit Data
Full vacuum idle time
min 6Idle time without vacuum min 3
Max. load in case of main switch disconnection and
over-speed trip
k
W
640647
Rotating speed of over-speed trip r.p.m 3330
3360(mechanical)33
00electronic
Max. o erational back ressure KPa a 18.6
Alarm back ressure of steam turbine KPa a 19.7
Turbine tri back ressure KPa a 25.3
Max. allowable o erational exhaust tem 12
7/29/2019 Turbine Operation Manual
12/249
12
Alarm exhaust temp 8
Exhaust tem of manual shutdown 12
S ra flow of LP c linder t/h 4
Allowable min. continuous ratin M 9
Allowable runtime under min. continuous rating min No limit
Max. back pressure at allowable min. continuous rating MPa(a) 0.0186
Max. main steam pressure at allowable min. continuous MPa(a) 16.67
Max. main steam tem at allowable min. continuous ratin 53
Vibration limit value of shaft relative to double amplitude of
vibration at rated revolution
m Not greater
than 34
Vibration limit value of shaft block relative to double amplitu
of vibration at over-critical revolution
m Not greater
than 80
Load limit at the time of stopping one set of LP heater M 60
Revolution of turnin ear r. .m 1.5
Max. cylinder temp at turning gear shutdown 15
Max. rotor temp at turning gear shutdown 15
Requirements for other short-term abnormal condition -
2.1.3 Combined critical speed of every rotor in shaft system
First critical speed (r/min) Second critical speed (r/min)
Name Shafting design
value
Tandem design
value
Shafting design
value
Tandem design value
HIP rotor 17222 1621 Greater than 4000 Greater than 4000
LP rotor A 1839 1723 3521 Greater than 4000
LP rotor B 1903 1750 Greater than 4000 Greater than 4000
Generator
rotor
984 1070 Greater than 3400 3338
7/29/2019 Turbine Operation Manual
13/249
13
2.1.4 Allowable load variation rate of the unit
10050MCR Not less than 5/min.
5030MCR Not less than 3/min.
Less than 30MCR Not less than 2/min.
2.2 Index of Steam and Water Quality
Item Unit Index Remarks
Electrical
conductivity s/cm 0.3
After hydrogen ion
exchange at 25
Sodium g/kg 10
Silicon dioxide g/kg 20
Iron g/kg 20
Steam
Copper g/kg 5
Hardness mol/L 0
Less than or equal to
5.0 when boiler
startup
Silicon dioxide QualifiedLess than or equal to
80 boiler startup
Dissolved oxygen g/L 7
Less than or equal to
30 when boiler
startup
Iron g/L 20
Less than or equal to
75 when boiler
startupCopper g/L 5
Hydrazine g/L 1050
pH 9.0-9.5
Oil mg/L 0.3
Feed water
Electrical
conductivitys/cm 0.3
After hydrogen ion
exchange at 25
Hardness mol/L 0Condensate
Electrical
conductivity of
S/cm 0.3
7/29/2019 Turbine Operation Manual
14/249
14
Item Unit Index Remarks
Electrical
conductivitys/cm 0.3
After hydrogen ion
exchange at 25
Sodium g/kg 10
Silicon dioxide g/kg 20
Iron g/kg 20
Steam
Copper g/kg 5
Hardness mol/L 0
Less than or equal to
5.0 when boiler
startup
hydrogen
Dissolved oxygen g/L 30Sodium g/L 10
3. Main auxiliaries and system specifications
3.1 Feed water pump set
3.1.1 General introduction
There are two 50% BMCR-capacity steam-driven feed water pumps in each unit and one 50%
BMCR-capacity electric feed water pump for start (standby). The steam-driven feed water pump is
made up by the main feed water pump and its forepump providing a continuous water supply to theboiler and desuperheating water to the superheater, reheater of the boiler and the HP-bypass of the
steam turbine. The electric feed water pump (including its forepump) is used when the unit starts,
the main feed water pump is maintained or an accident occurs. When the main feed water pump
set and the electric feed water pump set are operating in parallel, the characteristic curves of the
two coordinate with each other within a certain speed adjustable range to enable the two pump sets
run in parallel. If one set of the feed water pump fails, the electric feed water pump set can be put
into operation within 30 seconds and achieve the required pressure, running with another main
feed water pump set in parallel.
3.1.2 Equipment specifications
3.1.2.1 Technical data of the main pump forepump
Operation condition
Item UnitRating
(efficiency point
Design rate
Maximum
flow for
Minimum
flow for
Pump model SQ300-670
7/29/2019 Turbine Operation Manual
15/249
15
Water inlet 178.5 181.5 178.5 178.5
Water inlet pressure MPa(g) 1.079 1.12 1.079 1.079
Flow m3/h 1104.8 1347.4 1500 305
Pump delivery m 135 131 130 144.9
Efficiency % 84 84 82 39
NPSH required m 2.9 4.6 6 1.6
Seal form mechanical seal
Speed r/min 1485 1485 1485 1485
Outlet pressure MPa(g) 2.26 2.26 2.21 2.34
Shaft power kW 429.6 506.5 575.4 274.2
Weight kg 1598
inlet MPa(g) 4.0Interface
flange outlet MPa(g) 4.0
inlet mm DN400Specifications
of the
interface pipe
outlet mm DN350
Rotation direction clockwise (C.W.)(from the drive end to the pump)
Bearing type inlet rolling bearing
Drive mode electric motor
Note: (g) refers to gauge pressure in the table
3.1.2.2 Technical data of the main feed water pump
Operation condition
Item UnitRating
(efficiency point
Design rate
Maximum
flow for
Minimum
flow for
pump model CHTC6/5
Water inlet
tem erature
178.5 181.5 178.5 178.5
Water inlet density kg/m3
887.9 884.6 887.9 887.9
Water inlet pressure MPa(g) 2.15 2.15 2.08 2.21
Water inlet flow m3/h 1104.8 1347.4 1350 270
7/29/2019 Turbine Operation Manual
16/249
16
Water outlet flow m3/h 1056.4 1298.8 1350 270
Pump delivery m 2111 2248 1820 2550
Efficiency % 82.5 83 81 36
NPSH required m 34 43 40 22
Seal form inlet Burgmann mechanical seal
Speed r/min 4673 5008 4678 4678
Outlet pressure MPa(g) 20.519 21.64 17.93 24.42
Shaft power kW 6626.5 8609.7 7339 4627.4
Tap pressure MPa(g) 9.34 9.96
Tap flow m3/h 48.5 48.6
Supercharging MPa(g) no superchargingSupercharging flow m
3/h no supercharging
Shaft vibration mm 0.03 0.03 0.03 0.03
Weight kg 7220
Rotation direction clockwise (C.W.)(from the feed water turbine to the feed water
Bearing type Rolling bearing+ Kingsbury-type thrust bearing
Drive mode turbine
3.1.2.3 Technical data of the electric pump forepump
Operation condition
Item UnitRating
(efficiency point
Design rate
Maximum
flow fo
Minimum
flow for
Pump model SQ300-670
Water inlet
temperature
178.5 181.5 178.5 178.5
Water inlet pressure MPa(g) 1.079 1.12 1.079 1.079
Flow m3/h 1104.8 1347.4 1500 305
Pump delivery m 135 131 130 144.9
Efficiency % 84 84 82 39
NPSH required m 2.9 4.6 6 1.6
Seal form Mechanical seal
7/29/2019 Turbine Operation Manual
17/249
17
Speed r/min 1485 1485 1485 1485
Outlet pressure MPa(g) 2.26 2.26 2.21 2.34
Shaft power kW 429.6 506.5 575.4 274.2
Rotation direction clockwise (C.W.)(from the drive end to the
Bearing type Inlet trolling bearing
Drive mode electric motor (driven by the same axle with
3.1.2.4 Technical data of the electric feed water pump
Operation condition
Item UnitRating
(efficiency point
Design rate
Maximum
flow for
Minimum
flow for
Pump model CHTC6/5
Water inlet 178.5 181.5 178.5 178.5
Water inlet density kg/m3
887.9 884.6 887.9 887.9
Water inlet pressure MPa(g) 2.15 2.15 2.08 2.21
Water inlet flow m3/h 1104.8 1347.4 1350 270
Water outlet flow m3/h 1056.4 1298.8 1350 270
Pump delivery m 2111 2248 1820 2550
Efficiency % 82.6 83 81 36
NPSH required m 34 43 40 22
Seal form Inlet Burgmann mechanical seal
Speed r/min 4673 5008 4678 4678
Outlet pressure MPa(g) 20.519 21.64 17.93 24.42
Shaft power kW 6626.5 8609.7 7339 4627.4
Tap pressure MPa(g) 9.34 9.96
Tap flow m3/h 48.5 48.6
Shaft vibration mm 0.03 0.03 0.03 0.03
Rotation direction clockwise (C.W.)(from the feed water pump turbine to the feed
water pump)
Bearing type Rolling bearing+ Kingsbury-type thrust bearing
7/29/2019 Turbine Operation Manual
18/249
18
Drive mode turbine
3.1.2.5 Electric motor parameter
Equipment
Item Unit Motor of the forepum
of the main feed wate
Motor of the electric
feed water pump
Rated power kW 560 10050
Rated voltage kV 6.6 11
Synchronous speed. r/min 1500 1500
Frequency Hz 50 50
Rotation direction Anticlockwise (from the
forepump to the motor)
Anticlockwise (from the
forepump to the motor)
3.2 High and low-pressure bypass
3.2.1 General Introduction
Every unit is equipped with a B-MCR high-pressure bypass with 60% capacity and two
low-pressure bypasses whose capacity is coordinate with the high-pressure bypass. The actuator
is hydraulic. Bypass device can improve the start-up facility of the unit. When the unit starts in a
variety of operating conditions (cold, warm state, hot and very hot), we can use the bypass system
to control the temperature of the boiler steam to make the temperature of the steam match with
that of the metal of the cylinder in short period of time, thus to reduce the time for the unit to start,
the quantity of the steam as well as loss of steam turbine cycle life to achieve the best
performance of start-up. When the unit operates normally, the high-pressure bypass device has
over-pressure safety protection features. Once the pressure of main steam exceeds the setted
value of the high-pressure bypass, the valve of the high-pressure bypass will open quickly to
reduce the take off of PCV valve and safety valve and automatically adjust the pressure of the
main stream till it returns to be normal. Low-pressure bypass device should have the function of
reheater overpressure protection and condenser protection. Bypass can run in two ways: constant
pressure matching appropriate unit operation and sliding pressure operation. The bypass
installation can work together with the unit to achieve the role of regulation. When the power grid
or the unit appears load rejection because of the fault trip, the bypass device will operate quickly
to maintain the minimum load operation function of the boiler by using belting factory electricity,
idling or shutdown thus the unit can be ready to re-grid to resume normal operation. Reducing the
load while starting up and load rejection can prevent the reheater setting in the area with highergas temperature from burning out. High pressure and low pressure bypass device are in the hot
7/29/2019 Turbine Operation Manual
19/249
19
standby state under normal conditions. The water which High temperature bypass uses to reduce
the temperature comes from the high-pressure water; the water of low pressure bypass comes
from the condensing water. This machine consists of high-pressure bypass (main steam) and
low-pressure bypass (re-heat steam) two series bypass system devices. High-pressure bypass
system device consists of high-pressure bypass valve (high side valve), water-jet control valve
and water isolating valve etc. Low pressure bypass system device consists of low-pressure
bypass valve (low side valve), water-jet control valve and water isolating valve etc. Water
temperature control valve and reducing isolating valve are both hydraulic enforcement agency. HP
bypass and LP bypass are both with the same pattern.
The fuel supply device (petrol station) of the Bypass systems hydraulic actuator allocated
one set (high pressure bypass and low pressure bypass share a set). The time of automatically
using petrol station is 1 second, after 60 seconds, the working hydraulic can be achieved. There is
storage accumulator of petrol station to store energy, in case of power failure; it can still provide
sufficient hydraulic power to all system valves of the bypass to complete two-time All-trip on or off.
Petrol station sets up with one accumulator and high-pressure bypass device sets up a separate
accumulator as well. The working media of the Hydraulic actuator is anti-burning oil. Oil system
consists of two parts of pressure oil: 16MPa control-oil and 13.5MPa pilot oil.
3.2.2 Technical Parameter of the Equipment
Parameter table of the turbine bypass of medium-pressure tank start-up (IP) operation
condition
Name of the Technical
ParameterUnit
Starting
up in
cold
state
Starting
up in
warm
state
Starting
up in hot
state
Startin
g up
in
very
hot
Stop
the
machin
e
without
stoppin
Designe
d
conditio
n
Steam
Pressure of
the Entry
MPa(a) 6 8.62 8.62 12.9 8.77 17.5High
Pressure
Steam
Transformin
g ValveSteam
Temperatur
e of the
Entry
390 420 440 510 541 541
7/29/2019 Turbine Operation Manual
20/249
20
Steam
Flow of
the Entry
t/h 240 240 320 320 608.4 1216.8
Steam
Pressure
of the
Exit
MPa(a) 1.3 1.3 1.3 1.3 1.2 4.1
Steam
Temperat
ure of the
Exit
~200 ~235 ~255 ~330 291.433
5
Steam
Flow of
the Exit
t/h 27542 26849 35811 35086 7179 13992
Pressure MPa(a) ~10 ~12 ~12 ~16.5 ~122
2
Temperat
ure 110 110 110 110 110 185
High
Pressure
Water-jet
Control
Valve
Flow t/h 3542 2849 3811 3086 1095 18248
Low Pressure
Steam
Transforming
Valve
Steam
Pressure
of the
Entry
MPa(a) 1.1 1.1 1.1 1.1 1.19 3.7
7/29/2019 Turbine Operation Manual
21/249
21
Steam
Temperat
ure of the
Entry
340 400 420 480 540 540
Steam
Flow of
the Entryt/h 138 134 179 175
358
9570
0
Steam
Pressure
of the
Exit
MPa(a) 0.6 0.6 0.6 0.6 0.6 0.6
Steam
Temperat
ure of the
Exit
160 160 160 160 16016
0
Steam
Flow of
the Exit
t/h 15829 16037 2172 22111471
6591307
Pressure MPa(a) 3.3 3.3 3.3 3.3 3.3 3.3
Temperat 46.3 46.3 46.3 46.3 46.3 46.3Low Pressure
Water-jet
Control
Valve Flow t/h 2029 2637 382 4611 1127 21307
7/29/2019 Turbine Operation Manual
22/249
22
3.2 High and Low Pressure Heater and Deaerator
3.2.1 General introduction
The heat extraction system of the unit consists of 3 high-pressure heaters, 4 low-pressure
heaters and 1 deaerator.
High-pressure feed-water heaters are horizontal heat exchanger with surface condenser which
consists of drain cooler, condenser and steam cooler. The shell of high-pressure feed-water heater
is with all welded structure. At the side of the heater installs the pressure relief valve to prevent the
shell from damaging while the pipe is damaged. Water side also equips with pressure relief valve to
prevent the heater from overpressure due to heat expansion when the heaters inlet valve and outlet
valve is closed and the side has extraction stream. High-pressure feed-water heaters equips with
normal drain and emergent drain as well as related accessories. During the process of starting up
and continuous operation of the unit, in order to remove the non-condensing gas gathered in the
steam dead zone, there is enough vent connection and internal baffle equipped in the heater whose
displacement is designed according to 0.5 % of the steam into the heater. The drain cooler of the
heater has sufficient depth to ensure water seal is not damaged when the water level reaches
minimum. When high-pressure heater is put into operation, it can meet the requirement of the speed
to unit load as well as meet the water temperature change rate reaches 3 / min while loading up
and 2 / min while loading down without affec ting the safety and duration of the heater.
Low-pressure heaters are horizontal all welded which can withstand the change of full vacuum,
extraction pressure, the reaction of connected pipeline and thermal stress. When the adjacent
heater failure is removed, the water heater can adapt to the increase of the gas-side flow and
operate continuously. At the side of the tuber of the heater and shell separately sets up with
pressure relief valve, (delete, ) and the shell-side pressure relief valve (No. 7,8 dont equip with
pressure relief valve) to ensure the safety of the shell when the tube is damaged. The material of
the bundle of heater is stainless steel. When the steam turbine trip, to prevent excessive flash steam
come into the steam turbine, the No. 7, 8 (part of exhaust device) equips with stainless steel
anti-flash baffles .To prevent the bundle from shocking, vibrating and scouring, in the inner side of
steam trap inlet connection equips with stainless steel anti-shock plate. All low-pressure feed-water
heaters equips with normal drain and emergent drain. Normal drain connects with drain cooler while
emergent drain connects with condenser.
Deaerator is horizontal and inner setting. It is installed in the 24m layer, B-C column of the steam
room. The deaerator operation mode is constant pressure - sliding pressure - constant pressure.
Deaerator has 3 low-pressure water pipe interfaces. The diameter of each pipe is designed
according to 50% of the largest water flow. The water tank of the inner setting deaerator equips with
overflow electric valve to maintain the water level of the tank
3.2.2 Equipment parameter3.2.2.1 Design parameter of the high-pressure heater
7/29/2019 Turbine Operation Manual
23/249
23
Heater No. Unit 1 # 2 # 3 #
1 Heater model horizontal typeU-tube
2 Heater quantity 1 1 1
3 Bypass type of high-pressure
heater(largesmall bypass)
small
bypass
I Operation condition of adjusting valve wide open (VWO) of the steam turbine
Feed water
1 Flow t/h 2028 2028 2028
2 Inlet pressure MPa(a) / / /
3 Inlet temperature 250.5 219.3 185.2
4 Inlet enthalpy kJ/kg 1088.5 946.1 795.6
5 Outlet temperature 282.3 250.5 219.3
6 Outlet enthalpy kJ/kg 1242.6 1088.6 946.1
7 Maximum allowable pressure drop MPa 0.1 0.1 0.1
8 Maximum allowable flow rate m/s 3 3 3
9 Design pressure (interim) MPa(g) 28 28 28
10 Design temperature 310 280 250
11 Test pressure MPa(g) Refer toASME-
Steam extraction
12 Flow t/h 152.166 127.47 101.295
13 Inlet pressure MPa(a) 6.672 4.133 2.36
14 Inlet temperature 400.6 335.1 469.6
15 Inlet enthalpy kJ/kg 3169.2 3053.8 3396.2
16 Maximum allowable pressure drop MPa 0.07 0.07 0.07
17 Design pressure MPa(g) 7.3 4.65 2.5
18 Design temperature 415/290 355/260 485/230
19 Test pressure MPa(g) Refer to ASME-
Drainage entering in the heater
20 Source of the Drainage / 1 # 2 #
21 Flow t/h / 152.164 279.634
22 Temperature / 256.1 224.9
23 Enthalpy kJ/kg / 1115.4 966.3
Drainage drained from the heater
7/29/2019 Turbine Operation Manual
24/249
24
Heater No. Unit 1 # 2 # 3 #
24 Flow t/h 152.164 279.634 380.93
25 Temperature 256.1 224.9 190.8
26 Enthalpy KJ/kg 1115.4 966.3 811
27 Drain approach 5.6 5.6 5.6
II Operation condition of turbine maximum continuous output (T-MCR)
Feed water
1 Flow t/h 1876 1876 1876
2 Inlet pressure MPa / / /
3 Inlet temperature 246.3 215.7 182.1
4 Inlet enthalpy kJ/kg 1068.9 929.9 782.3
5 Outlet temperature 277.2 246.3 215.7
6 Outlet enthalpy kJ/kg 1217.5 1068.9 929.9
Steam extraction
7 Flow t/h 135.3 115.215 91.82
8 Inlet pressure MPa 6.183 3.849 2.2
9 Inlet temperature 391.7 327.7 469.9
10 Inlet enthalpy kJ/kg 3155.2 3042.1 3398.9
Drainage entering in the heater
11 Source of the Drainage / 1 # 2 #
12 Flow t/h / 135.3 250.516
13 Temperature / 251.9 221.3
14 Enthalpy kJ/kg / 1094.8 949.4
Drainage drained from the heater
15 Flow t/h 135.3 250.516 342.345
16 Temperature 251.9 221.3 187.7
17 Enthalpy KJ/kg 1094.8 949.4 797.4
3.2.2.2 Design parameter of low-pressure heater (T-MCR operation condition)
Heater No. Unit
5 # 6 # 7 # 8 #
1Heater model U-tubehorizontal type
2Heater quantity 1 1 2 2
Condensate
7/29/2019 Turbine Operation Manual
25/249
25
1 Flow t/h 1434.493 1434.493 1434.493 1434.493
2 Inlet pressure (working pressure,
interim)
MPa(a) 4 4 4 4
3
Inlet temperature
118.8 100.8 83.6 474 Inlet enthalpy KJ/Kg 500.7 424.7 352.6 199.4
5 Outlet temperature 137.4 118.8 100.8 83.6
6 Outlet enthalpy KJ/Kg 579.6 500.7 424.7 352.6
Steam extraction
7 Flow t/h 46.546 44.003 41.067 79.658
8 Inlet pressure MPa(a) 0.382 0.22 0.121 0.064
9 Inlet temperature 245.3 186.6 129.1 87.8
10Inlet enthalpy KJ/Kg 2955.4 2842.2 2732.8 2631.8
Drainage entering in the heater
11Flow t/h 0 46.547 90.550 131.616
12Temperature 0 124.4 106.4 89.2
13Enthalpy KJ/Kg 0 522.7 446.2 373.7
Drainage drained from the heater
14Flow t/h 46.547 90.550 131.616 213.836
15Temperature 124.4 106.4 89.2 52.6
16Enthalpy KJ/Kg 522.7 446.2 373.7 220.2
3.2.2.3 Design parameter of deaerator
Item Built-in deaerator
Type Built-in horizontal type
Model
YC-1876
Shell material
SA-516 Gr.70
Head material
SA-516 Gr.70
Design pressureMPa.g
1.27/-0.1
Design temperature steam connection371/bulk: 250
Diameter / length / thicknessmm
~3860/28300/30
7/29/2019 Turbine Operation Manual
26/249
26
Total height after installation (including
supports)mm ~5700
Weld joint factor
1
Corrosion allowance cm vessel head 0.25/connection pipe0.15
Weight (net)kg
107300
Full water weight kg
469000
Operating weight kg
350900
3.3 Condenser
3.3.1 General introduction
The condenser is with double shells, single process and double-pressure surface. It is with side by
side horizontal layout. The condenser is with all welded steel structure which includes two oblique
throats, two shells (hot well, water room and reheating pipe system), recycled water connecting
pipe and fixed bearing. The condenser not only accepts the drain of the host, jack-engine and
ontology, but also accepts that of low pressure bypass, high-pressure and low-pressure accident as
well as that of deaerator overflow. The throat part of the condenser equips with No. 7, 8 low
pressure heater, water-feed pump turbine as well as triple desuperheating station at the side of
Bypass system of steam turbine. When the condensed water, drained water and supplementary
water come into the condenser, they can be effectively heated and sprinkled to achieve the best
effect of deaerating. The condenser can be hemi-run, under this condition, the steam turbine can
reach 60% of the rated power.
3.2.2 Parameter of the condenser
No. Item Unit Data
1 The total valid area of the condenser m2 30500
2 The drained valid area m2 1830
3 Flow number/shell number 1/2
4 Net heat brought away by circulating
water of VWO operation condition
kJ/s 795300.3
5 Heat transfer coefficient W/m2. 3234.4/3303.3
6 Circulatin water flow t/h 71500
7 Maximum flow rate of circulating water in m/s 2.3
8 Design flow rate of the cooling tube m/s 2.3
9 Cleanin coefficient 0.85
7/29/2019 Turbine Operation Manual
27/249
27
10 Increase of the circulatin water of VWO 10.2
11 The degree of supercooling of condensate 0.5
12 Desi n terminal tem erature difference of 6.02/5.85
13 Desi n ressure of water chamber MPa. 0.4
14 Desi n ressure of shell side MPa. Vac.0.15
15 Oxygen content required of the g/l 3016 Total water resistance of tube kPa 61
17 Condenser steam resistance kPa 0.1
18 Circulating ratio (design operation 55
19 Weight of water chamber(each) kg 15000
20 Net wei ht of the condenser k 750000
21 Condenser wei ht o eratin k 1350000
22 Condenser wei ht full water k 2550000
23 Test pressure of water chamber 1.5 times of the design
pressure
3.4 Condensate pump
3.4.1 General introduction of condensate pump
Transfer the condensate in the turbine condenser to the deaerator, and provide the turbinelow-pressure bypass and desuperheater with desuperheating water and other things. Each unit is
equipped with two condensate pumps, one for work and the other for standby. The condensate
pumps are vertical and vessel type multistage centrifugal pumps with 4-stage impeller. The
condensate pump is constituted by shell, outlet connection pipe, pump spindle, 4-stage impeller,
coupling, sealing element, pump base, etc.
3.4.2 Operating parameter of the condensate pump
Mode of pump
NLT500-570X4S
Pump operation condition
point
Item Unit
Nameplate operation
condition
Rating operatio
conditionTMCR
(efficiency point
required)
Water inlet
temperature
46.3 46.3
Water inlet
pressure MP
0.01 0.01
7/29/2019 Turbine Operation Manual
28/249
28
a
-
a
Flow
t
/
h
1693 1434.493
Total outlet
pressure M
p
a
-
a
3.25 3.41
Pump
lift M 333 350
efficiency
% 83.6 83
NPSH
m
H
2
O
5.2 5
Speed
r
/
m
i
n
1480 1480
Shaft
power
K
w 1835.8 1646.7
Total outlet pressure
M
P
a
3.25 3.41
inlet/outlet nominal
diameter mm/mm
800/500 800/500
inlet/outlet nominal
pressure M
1.6/5.0 1.6/5.0
7/29/2019 Turbine Operation Manual
29/249
29
P
a
-
g
Design pressure of
pump MPa(g)
5 5
Rotation direction Anticlockwise (from the motor to the condensate
pum)
3.5 Oil purifier
Each unit is equipped with an oil purifier, which is able to purify the steam turbine lubricating oil
while on-line or shutdown, to remove impurities particles, moisture, break emulsification, so that the
main steam turbine or feed water pump would drive the small steam turbine lubricating oil to be
reborn.
No. Item Unit Data
1 Manufacturer Made by Alfa Laval, Sweden
Assembled by Beijing Touping New Technology Development
2Manufacturing
Made by Alfa Laval, Sweden, assembled in Beijing
M MAB206
4 Type Offcenter pattern
5Purification devices rated
outputL/h 10600
6 Suitable oil 3246 or 68
7 Filtration m 3
moistu 33PPm
8 The quality of treated oil particle
countNAS standard 7 or Morgan 6
9 Oil-providing pump model KFUG42
10 Oil-providing pump type horizontal type gear pump
11Oil-providing pump m
3/h 13
12 Oil-providing pump delivery M a 0.15
13 Shaft power of oil-providing KW 11
14 oil-providing pump speed r/min 1500
7/29/2019 Turbine Operation Manual
30/249
30
15Motor model of
oil-providing Made by ABB company, provided byAlfa Laval, Sweden
16Rated power of
KW 12
17 Rated voltage of V 415
18 Speed of oil-providing r/min 1500
19 Centrifuge model MAB206
20 Centrifuge type vertical type
21 Centrifuge capacity m3/h 10.6
22 Centrifuge shaft power KW 11
23 Centrifuge speed r/min 8425
24 Centrifuge motor model Share the same motor with oil-providing pump
25 Rated power of centrifuge K 12
26Rated power of centrifuge
V 415
27 Centrifuge motor speed r/min 1500
28 Maximum noise level dB(A) 85
29Equipment dimensions
(length, width, height)
Mm 180014001300
oil inlet Mm DN40
oil outlet Mm DN40
drain outlet Mm DN2030
The interface
size
water sealedMm 1/2 inch internal thread
31 The interface pressure M a 16
32 Net weight of the K 1000
33 Weight of running Kg 1020
34 Maximum maintenance Kg 1020
35 Material of centrifuge oil pum cast steel
36 Material of centrifuge oil pump lid cast steel
37Material of centrifuge oil pum
im eller stainless steel
38Material of centrifuge oil pum
stainless steel
39 Power of electric heater KW 96
7/29/2019 Turbine Operation Manual
31/249
31
Oil purifier specifications
3.6 Performance of water-ring vacuum pump unit:
(1) Minimum suction pressure (ultimate vacuum) of the water-ring vacuum pump: 2900 Pa(a)
(2) Pump speed: 490r/min
(3) Impeller nominal diameter: 76.5cm
(4) Speed: 19.62m/s
(5) Shaft power: (maximum) 150 kW (minimum): 94kW Shaft power: 10.13kPa: 113KW;
11.8kPa: 117KW
(6) Starting power: 94KW
(7) Pumping capacity100 kg/h (inlet pressure is 10.13kPa and cooling water temperature is
32.5 )
(8) Electric motor model: Y450S-12 rated power: 185 KW speed: 490r/min voltage: 415Vmotor protection level: IP54 motor insulation level: F motor temperature rise: B
(9) The cooling water amount of pump heat exchanger: 40m3/h, water quality: seawater, water
temperature: 32.5 , separator make -up water flow:
7/29/2019 Turbine Operation Manual
32/249
32
Chapter II Protection, Control and Test of the Unit
1. General Rules of Interlock Protection Test
1.1 Purpose and Division of Interlock Protection
1.1.1 Test purposes: check thermal interlock protection circuit action for correctness, including the
action of primary single circuit and interlock protection.
1.1.2 Division of test
1.1.2.1 Inspection associated with thermal device, and thermal technicians in responsible of
forcing, stimulating and resetting of thermal single
1.1.3.2 Field apparatus inspection associated with the test, and operators in responsible of the
operation of the electric switches and OPR
1.2 Test Method of Interlock Protection
1.2.1 Single imitation
1.2.2 Transmission test
1.3 Verification for Interlock Protection Test Results
1.3.1 Hard wired circuit test
1.3.2 Interlock protection test
1.3.2.1 Mainframe protection test (see thermal protection of the mainframe)
1.3.2.2 Auxiliary protection test
2. Interlock Protection of Mainframe
2.1 Main Thermal Protection of Steam Turbine
2.1.1 Turbine DEH and ETS trip protection
ETS over-speed protection
TST over-speed protection
DEH over-speed protection
High metal temperature (left and right) protection for inner walls of the HP cylinder exhaust
1. Send an alarm signal of high metal temperature in case that the metal temperature of the
HP cylinders exhaust is greater than or equal to 420 degrees centigrade.
2. Shut down by the action of protection in case that the metal temperature of the HPcylinders exhaust is greater than or equal to 432 degrees centigrade.
7/29/2019 Turbine Operation Manual
33/249
33
High metal temperature (back and right) protection for LP cylinder exhaust
3. Send an alarm signal of high metal temperature in case that the metal temperature of the
LP cylinders exhaust is greater than or equal to 80 degrees centigrade.
4. Shut down by the action of protection in case that the metal temperature of the LP
cylinders exhaust is greater than or equal to 107 degrees centigrade.
Low vacuum protection of condenser: Shut down by the action of protection in case of low
vacuum of condenser.
Low lube oil pressure protection:
5. Send an alarm signal of low lube oil pressure in case that the lube oil pressure is less
than 0.115MPa;
6. Shut down by the action of protection in case that the lube oil pressure is less than
0.069MPa;
Shut down by the action of projection in case of low EH oil pressure (one of two logic) (1, 3
and/or 2, 4).
Large vibration protection of bearings
Send an alarm signal of large vibration in case that the vibration of any bearing is greater
than or equal to 125um; Shut down by the action of protection in case that the vibration is
greater than or equal to 250um.
1. Send an alarm signal of large axial displacement in case that the axial displacement of
the steam turbine is less than negative 1.05mm or greater than positive 0.6mm.
2. Shut down by the action of protection in case that the axial displacement of the steamturbine is less than negative 1.65mm or greater than positive 1.2 mm.
Differential expansion protection of HIP cylinders
1. Send alarm signal of large differential expansion in case that the differential expansion is
less than negative 5.3mm or greater than positive 10.3mm;
2. Shut down by the action of protection in case that the differential expansion is less than
negative 6.6mm or greater than positive 11.6mm.
Differential expansion protection of LP cylinder
1. Send alarm signal of large differential expansion in case that the differential expansion is
less than negative 4.6mm or greater than positive 19.8mm;
2. Shut down by the action of protection in case that the differential expansion is less than
negative 8mm or greater than positive 30mm.
DEH electricity loss protection
Generator protection
Malfunction of a trip protection button on the console
Trip by the action of protection in case that temperature of any bearing shell of #1-#8
journal bearings is high (5 seconds delay) (alarm when temperature of #1-#6 bearing shells
reaches 110 degrees centigrade and trip when reaching 115 degrees centigrade;
7/29/2019 Turbine Operation Manual
34/249
34
meanwhile, alarm and trip temperatures of the #7 and #8 bearing shells are 110 and 115
degrees centigrade, respectively);
Trip by the action of protection in case that the temperatures of #1-#8 working thrust pads
are high (time delay 5s) (alarm and trip temperatures of them are 85 and 110 degrees
centigrade, respectively);
Trip by the action of protection in case that the temperatures of #1-#8 locating thrust pads
are high (time delay 5s) (alarm and trip temperatures of them are 85 and 110 degrees
centigrade, respectively);
Shut down by the action of protection in case that the steam temperature of the main stop
valve at the inlet is LL (low, low);
Shut down by the action of protection in case that cooling water inlet flow of the generator
stator is LL;
Shut down by the action of protection in case that inlet cooling water pressure of the
generator stator is LL;
Shut down by the action of protection in case that outlet cooling water temperature of the
generator stator is HH (high, high).
2.1.2 Over-speed protection
2.1.2.1 Over-speed protection control system (OPC): the momentary speed of the steam turbine
will reach maximum in case that the trip signal of the generator main switch does not send out due
to control single lag and residual steam at the time of load rejection of the unit. In order to prevent
the unit from tripping for a rotating speed capable of causing tripping, the HIP control valve mustbe closed fast and immediately to prevent speed rise when the rotating speed reaches 103% of
the rated.
2.1.2.2 When the rotating speed of the steam turbine reaches 110%-111% of the rated speed, the
eccentric ring mechanical emergency governor drives the mechanical trip valve into action to drain
the oil in the emergency trip system (ETS), to close the high pressure main stop valve and the high
pressure control valve and to open the vent valve. And then the steam turbine is stopped after
closing the intermediate pressure main stop and control valves, the extraction check valves and
exhaust check valve of the HP cylinder at all levels and opening the dump valve.
2.1.2.3 Electric over-speed protection: immediately close the HIP MSV and CV to stop feeding
steam while the rotating speed of the unit reaches 111% of the rated speed; meanwhile, the DEH
sends out a stop signal.
2.1.3 Manual shutdown
2.1.3.1 Manual field tripper: it is set at the front box of the steam turbine. While operating, the
tripper is first drawn out after counter-clockwise rotating 90, and then the HP MSV and HP CV, IP
MSV and IP CV, the exhaust check valve of the HP cylinder and check valves at all level are
closed and the vent valve is opened after the safety oil is drained by the action of the mechanical
trip valve.
7/29/2019 Turbine Operation Manual
35/249
35
2.1.3.2 Manual remote tripper: it is of double-button and equipped on the control desk of the
central control room. Pressing the buttons will bring the mechanical solenoid and the main trip
solenoid A and B into action to close HP MSV and HP CV, IP MSV and IP CV, the exhaust check
valve of the HP cylinder and check valves at all level and open the vent valve.
2.1.4 Protection system for preventing water induction
Principal for classification of water induction-preventing control
Divide the turbine steam source piping, steam turbine proper and drain valves of every
extraction piping into HP, IP, LP drain valves;
Exclude every extraction check valves for the reason that the said valves are totally used for
preventing water into steam turbine;
Open and close the said three valves in accordance with the load level, they are divided into
10%, 20% and 30% MCR;
Set one operating button for three of them;
The said three drain valves include the drain valves of 1-6 segments extraction pipeline.
LBA41AA560VC
Pneumatic drain valve of the main steam pipe LBA41AA560VC
Open conditions of interlock
Load less than or equal to 10%
Steam turbine trip
Generator trip
Closure conditions of interlockLoad greater than 10%
Low-low condenser vacuum (similarly to the said drain valves) (with the use of an
analogue value less than 50kpa)
Pneumatic drain valves of main steam pipe on the left and right sides LBA21AA560VC/
LBA31AA560VC
Open conditions of interlock
Load less than or equal to 10%
Steam turbine trip
Generator trip
Closure conditions of interlock
Load greater than 10%
Low-low condenser vacuum (similarly to the said drain valves) (with the use of a
analogue value less than 50kpa)
Pneumatic drain valves of main steam pipe on the left and right sides LBA21AA560VC/
LBA31AA560VC
Closure conditions of interlock
Load less than or equal to 20%
7/29/2019 Turbine Operation Manual
36/249
36
Steam turbine trip
Generator trip
Closure conditions of interlock
Steam turbine more than 20%
Low-low condenser vacuum
Pneumatic drain valves of upper and lower valve blocks of right and left main steam
valves MAL70AA560VO/ MAL30AA560VO/ MAL60AA560VO/ MAL40AA560VO
Closure conditions of interlock
Load less than or equal to 10%
Steam turbine trip
Generator trip
Closure conditions of interlock
Steam turbine greater than 10%
Low-low condenser vacuum
Pneumatic drain valves of right and left RSV 1/2 MAL10AA560VO/ MAL20AA560VO
Closure conditions of interlock
Load less than or equal to 10%
Steam turbine trip
Generator trip
Closure conditions of interlock
Steam turbine greater than 10%Low-low condenser vacuum
Pneumatic drain valve for outlet of the HP control valve MAL50AA560VO
Closure conditions of interlock
Load less than or equal to 10%
Steam turbine trip
Generator trip
Closure conditions of interlock
Steam turbine greater than 10%
Low-low condenser vacuum
Over-speed protection control system action (OPCACT for short)
Steam turbine trip
Generator trip
Following valves will automatically open in case that the load is less than 10% of the rated.
Steam turbine trip
Generator trip
Over-speed protection control system action (OPCACT for short)
Drain valve of the left main steam pipe
7/29/2019 Turbine Operation Manual
37/249
37
Drain valve of the right main steam pipe
Drain valve of HP steam conduit
Drain valve for the left upper valve block of the HP MSV
Drain valve for the left lower valve block of the HP MSV
Drain valve for the right upper valve block of the HP MSV
Drain valve for the right lower valve block of the HP MSV
Drain valve for the left exhaust pipe of the HP cylinder
Drain valve for the right exhaust pipe of the HP cylinder
Drain valve for the exhaust manifold of the HP cylinder
Outlet drain valve for the 1st extraction electric valve
Inlet drain valve for the 1st extraction electric valve
Outlet drain valve for the 2nd extraction electric valve
Inlet drain valve for the 2nd extraction electric valve
Drain valve of HP bypass pipe
Following valves will automatically close in case that the load is greater than 10%:
Low-low condenser vacuum
Drain valve of the left main steam pipe
Drain valve of the right main steam pipe
Drain valve of HP steam conduit
Drain valve for the left upper valve block of the HP MSV
Drain valve for the left lower valve block of the HP MSVDrain valve for the right upper valve block of the HP MSV
Drain valve for the right lower valve block of the HP MSV
Drain valve for the left exhaust pipe of the HP cylinder
Drain valve for the right exhaust pipe of the HP cylinder
Drain valve for the exhaust manifold of the HP cylinder
Outlet drain valve for the 1st extraction electric valve
Inlet drain valve for the 1st
extraction electric valve
Outlet drain valve for the 2nd extraction electric valve
Inlet drain valve for the 2nd extraction electric valve
Drain valve of HP bypass pipe
Following valves will automatically open in case that the load is less than 20%:
Steam turbine trip
Generator trip
Over-speed protection control system action (OPCACT for short)
Drain valve of left reheat steam pipe
Drain valve of right reheat steam pipe
Drain valve of left IP union valve
7/29/2019 Turbine Operation Manual
38/249
38
Drain valve of right IP union valve
Inlet drain valve of 3ird extraction electric valve
Outlet drain valve of 3ird extraction electric valve
Inlet drain valve of 4th extraction electric valve
Outlet drain valve of 4th extraction electric valve
Following valves will automatically close in case that the load is greater than 20%:
Low-low condenser vacuum
Drain valve of left reheat steam pipe
Drain valve of right reheat steam pipe
Drain valve of left IP union valve
Drain valve of right IP union valve
Inlet drain valve of 3ird extraction electric valve
Outlet drain valve of 3ird extraction electric valve
Inlet drain valve of 4th extraction electric valve
Outlet drain valve of 4th
extraction electric valve
Following valves will automatically open in case that the load is less than 30%:
Steam turbine trip
Generator trip
Over-speed protection control system action (OPCACT for short)
Inlet drain valve of 5th extraction electric valve
Outlet drain valve of 5th extraction electric valveInlet drain valve of 6th extraction electric valve
Outlet drain valve of 6th extraction electric valve
Following valves will automatically close in case that the load is greater than 30%:
Low-low condenser vacuum
Inlet drain valve of 5th
extraction electric valve
Outlet drain valve of 5th extraction electric valve
Inlet drain valve of 6th
extraction electric valve
Outlet drain valve of 6th
extraction electric valve
Drain valve for the left exhaust pipe of the HP cylinder
High-high water level in the drain pot triggers the drain valve to open, whereas to close.
Drain valve for the right exhaust pipe of the HP cylinder
High-high water level in the drain pot triggers the drain valve to open, whereas to close.
Drain valve for the exhaust manifold of the HP cylinder
High-high water level in the drain pot triggers the drain valve to open, whereas to close.
Drain valve for the exhaust pipe at the inlet A of the LP bypass valve
High-high water level in the drain pot triggers the drain valve to open, whereas to close.
Drain valve for the exhaust pipe at the inlet B of the LP bypass valve
7/29/2019 Turbine Operation Manual
39/249
39
High-high water level in the drain pot triggers the drain valve to open, whereas to close.
Drain valve for the exhaust pipe at the outlet A of the LP bypass valve
High-high water level in the drain pot triggers the drain valve to open, whereas to close.
Drain valve for the exhaust pipe at the outlet B of the LP bypass valve
High-high water level in the drain pot triggers the drain valve to open, whereas to close.
Steam turbine trip or generator asynchronous protection or OPC action will close the left
exhaust check valve of the HP cylinder.
Steam turbine trip or generator asynchronous protection or OPC action will close the right
exhaust check valve of the HP cylinder.
2.1.5 Interlock protection for lubricating oil system of mainframe
2.1.5.1 The turbine AC auxiliary pump is self-driven in case of meeting one of following conditions:
1) Low outlet pressure of the main oil pump
2) The period before turbine rotating speed down to 2900r/min
3) Low lube oil
4) Steam turbine trip
2.1.5.2 The manual shutdown of the turbine AC auxiliary pump is available in case of meeting one
of following conditions:
1) Zero rotating speed of steam turbine
2) Stable and constant rotating speed of the steam turbine up to 3000r/min and normal lube oil
pressure2.1.5.3 The mainframe startup pump (MSP) is self-driven in case of meeting one of following
conditions:
1Turbine rotating speed less than or equal to 2850 r/min
2Low inlet pressure of the main oil pump (MOP) (less than Mpa)
3Steam turbine trip.
2.1.5.4 The manual shutdown of the mainframe startup pump (MSP) is available in case of
meeting one of following conditions:
1) Stable and constant rotating speed of the steam turbine up to 3000r/min
2) Zero rotating speed of steam turbine.
2.1.5.5 The DC emergency oil pump (EOP) is self-driven in case of meeting one of following
conditions:
1) Non-zero rotating speed of the steam turbine and low-low lube oil pressure of the mainframe
(less than Mpa)
2) Standby AC lube oil pump startup with the AC lube oil pump trip
3Low inlet pressure of the MOP and TOP.
2.1.5.6 The manual shutdown of the DC emergency oil pump (EOP) is available in case of meeting
one of following conditions:
7/29/2019 Turbine Operation Manual
40/249
40
1) Zero rotating speed of steam turbine
2) Normal lube oil pressure (0.137Mpa- 0.176Mpa).
2.1.5.7 The startup of the mainframe jacking oil pump is allowable under the following condition:
1) Inlet pressure of the jacking oil pump more than 0.03Mpa
2.1.5.8 The mainframe jacking oil pump is allowable for shutdown in case of meeting one of
following conditions:
1) The AC auxiliary oil pump out of service
2) The turbine rotating speed is greater than or equal to 2000r/min (tentative speed)
3) Allowable for one standby in two sets of jacking oil pump
2.1.5.9 The jacking oil pump is self-driven in case of meeting one of following conditions:
1When the rotating speed of the steam turbine MAA00CS002 is less than 2000, a specified
standby pump will bring into action; if the standby delays 10s, the other one will be put into
operation;
2When the rotating speed of the steam turbine MAA00CS002 is less than 2000, the working
pump is in operation and the outlet manifold pressure of the jacking oil pump is low, the standby
jacking oil pump is put into operation;
3When the rotating speed of the steam turbine MAA00CS002 is less than 2000 and the
working pump trips, the standby jacking oil pump is brought into action.
2.1.5.10 the jacking oil pump automatically stops in case of meeting one of following conditions:
1) Rotating speed of the steam turbine is greater than or equal to 2000r/min (tentative speed);
260s delay time of the steam turbine at zero rotating speed2.1.5.11 the electric heater of the lube oil box is self-driven in case of meeting one of following
conditions:
1) Lube oil temperature in the main oil tank less than 32
2Surface temperature of the electric heater of the main oil tank less than 100
2.1.5.12 the electric heater of the main lube oil automatically stops in case of meeting one of
following conditions:
1) High lube oil temperature in the main oil tank greater than 37
2) High surface temperature of the electric heater of the main oil tank greater than 150
2.1.6 Interlock protection for EH oil system of the mainframe
2.1.6.1 The EH oil pump is allowable for starting in case of full meeting following conditions:
1) Main EH oil pump allowable for being operated
2) Normal oil level of the EH oil tank
320 Oil temperature of the EH oil tank higher than 20
2.1.6.2 The standby EH oil pump will automatically start in case of meeting one of following
conditions:
1) One set in operation and pressure of the EH oil manifold less than or equal to Mpa
2) Motor trip of a EH oil process pump
7/29/2019 Turbine Operation Manual
41/249
41
2.1.6.3 The EH oil pump will automatically stop in case of meeting one of following conditions:
1Excessively low oil level of the EH oil tank (less than negative 200mm)
2Breaker trip of the EH oil pump or overload protection of the motor in action
2.1.6.4 The electric heater of the EH oil tank will automatically start in case of full meeting following
conditions:
1Normal oil level of the oil tank
2#1 and #2 circulating pumps of the oil tank in operation
3The breaker of the heater at on-position
4Oil temperature less than or equal to 20
2.1.6.5 The electric heater of the EH oil tank will automatically stop in case of meeting one of
following conditions:
1The oil temperature greater than or equal to 35
2The breaker of the heater tripped
3Excessively low oil level
4Both the #1 circulating pump and #2 circulating pump of the oil tank out of service
2.1.7 Turning gear interlocks protection of the mainframe
2.1.7.1 The turning gear will automatically start in case of full meeting following conditions:
1) The interlock switch of its motor at AUTO position
2) Lube oil pressure of the bearing greater than 0.103MPa
3) Jacking oil pressure of every bearing greater than or equal to 3.43MPa
4) A manual turning interlock switch in standby5) Both of the MSV in fully closed state
6) Zero rotating speed of the steam turbine and 30s delay time
2.1.7.2 The turning gear will automatically trip in case of meeting one of following conditions:
1) Jacking oil pressure of any bearing less than 2.7Mpa
2) Lube oil pressure less than or equal to 0.07Mpa
3) Overload protection for the turning motor in action
2.1.8 Control and interlock protection of HP and LP bypass system
2.1.8.1 Control mode of the HP and LP bypass system
Decentralized control system (DCS) control modes of the HP bypass system: minimum opening,
boost, fixed pressure and follow modes
DCS control modes of the LP bypass system: minimum opening, fixed pressure and track
modes
2.1.8.2 Bypass attemperating water control
1) The control modes include AUTO and MAN; in the AUTO mode, the outlet temperature of the
bypass valve is able to be automatically regulated by setting the inlet temperature of the HP
bypass valve; in another case, the outlet temperature is maintained through manually controlling
the opening of an attemperating water valve by the operator. Meanwhile, automatic control mode
7/29/2019 Turbine Operation Manual
42/249
42
of the HP bypass pressure into operation is to bring the HP bypass attemperating water control
mode automatically into operation.
2) The control modes of the LP bypass attemperating water include AUTO and MAN; in the
AUTO mode, the outlet temperature of it is automatically controlled at 160 ; in another case,
the outlet temperature is maintained through manually controlling the opening of an
attemperating water valve by the operator. Meanwhile, the automatic control mode of the LP or
HP bypass pressure into operation is to bring the LP bypass attemperating water control mode
automatically into operation.
2.1.8.3 Interlock protection of bypass
1HP bypass pressure reducing valve
Allowable fast-opening conditions:
Pressure to be regulated to greater than or equal to 30% prior to triggering the
fast-opening action
In HP cylinder control before triggering the fast-opening action
Bypass in operation
No fast-closing condition (the fast-closing in prior to the fast-closing)
Trigger conditions of fast-opening
A changeover switch has already put into operation. The HP cylinder control is put
into operation and the steam turbine trips.
Fast-closing conditions:
5s duration at an outlet temperature of the HP bypass valve higher than 3800% opening
2HP bypass spray valve (set temperature ranging from 250 to 330 )
Fast-opening condition: The fast-opening of the HP bypass pressure valve is
available.
Fast-closing condition: The fast-closing of the HP bypass pressure valve is
available.
Less than 2.5% opening of the HP bypass pressure control valve (PCV) is to jointly
close the LP bypass PCV after 5s delay time.
3HP bypass spray isolation valve
1. The spray isolation valve is triggered to open in case that the opening of the HP bypass
valve is greater than or equal to 2.5%;
2. The spray isolation valve is triggered to close after 15s delay in case that the opening of the
HP bypass valve is less than 2.5%.
4LP bypass pressure reducing valve
Fast-closing conditions include but not limit to, the following:
1. Low condenser vacuum
2. High condenser temperature
7/29/2019 Turbine Operation Manual
43/249
43
3. Low spray pressure of the LP bypass spray valve
4. High outlet steam temperature of the LP bypass spray valve
Fast-closing opening: 0
Fast-opening conditions (the fast-closing in prior to the fast-opening) include, but not limit to,
the following:
1. Reheater pressure more than 4.4Mpa
2. Fast-opening of the HP bypass valve is available.
Opening: The LP bypass pressure valve is put into control mode as it is pre-opened to 80%
and in automatic operation.
5LP bypass spray valve
Fast-closing condition: Fast-closing of the LP bypass pressure reducing valve is available.
Fast-closing opening: 0
Fast-opening condition: Fast-Opening of the LP bypass pressure reducing valve is available.
Opening: The LP bypass pressure valve is put into control mode as it is pre-opened to 80%
and in automatic operation.
6LP bypass spray isolatio