48
—suitable for homes, offices, shops, and middle-sized buildings Cooling Only 50 Hz Single outdoor unit series VRV indoor units combine with residential indoor units, all in one system PCV1131
Transcript
Page 1: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

—suitable for homes, offices, shops, and middle-sized buildings

Cooling Only 50 Hz

Single outdoor unit series

VRV indoor units combine with residential indoor units, all in one system

PCV1131

Page 2: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

11

Meet the new single outdoor unit series, connectable to both VRV and residential indoor units

First launched in Japan in 1982, the Daikin VRV system has been embraced by world markets for nearly 30 years. Now, Daikin proudly introduces the new VRVIII single outdoor unit series which enables a mixed combination of VRV indoor units and residential indoor units all in one system, opening the door to stylish and quiet indoor units.

Page 3: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

2

HOMES

OFFICES

SHOPS

Contents

Main Features................................page 3

Control Systems...........................page 39

Indoor Unit Lineup.........................page 9

Outdoor Unit Lineup......................page 4

Specifications...............................page 24

Indoor units.............................page 24

Outdoor units...........................page 34

• V R V.....................................page 9• Residential............ ........ ....page 19

• V R V.....................................page 35• Residential............ .......... ....page 37

• V R V.....................................page 24• Residential............ .......... ....page 31

BP units.......... ................. ........page 33

Option List....................................page 35

Indoor units.............................page 35

Outdoor units...........................page 38

BP units.......... ................ .........page 38

Page 4: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Wide range of choices

Main Features

3

VRV indoor units 15 types 73 models

VRV indoor units

Ceiling MountedCassette (Round Flow)

Type Model Name Capacity Range

Capacity Index 20

0.8 HP

40

1.6 HP

62.5

2.5 HP

80

3.2 HP

100

4 HP

125

5 HP

140

6 HP

200

8 HP

250

10 HP

50

2 HP

31.25

1.25 HP

25

1 HP

20 40 63 80 100 125 140 200 250503225

Ceiling Mounted Cassette(Double Flow)

FXCQ-MVE

Ceiling MountedCassette (Compact Multi Flow)

FXZQ-MVE

Slim CeilingMounted Duct

Ceiling MountedDuct

Ceiling Suspended

Wall Mounted

Floor Standing

ConcealedFloor Standing

Ceiling MountedCassette Corner

FXDQ-NBVE(with drain pump)

FXDQ-NBVET(without drain pump)

FXMQ-PVE

FXMQ-MAVE

FXHQ-MAVE

FXAQ-MAVE

FXLQ-MAVE

FXNQ-MAVE

FXKQ-MAVE

FXDQ-PBVET(without drain pump)

FXDQ-PBVE(with drain pump)

(900/1,100 mm width type)

(700 mm width type)

R-410A VRV system indoor units are not compatible with the R-22 VRV system.Note:

Note:

VRV indoor units connection unit series

Ceiling Suspended Cassette

Type Model Name

FXUQ-MAV1

BEVQ125MAVE

5 HP

BEVQ100MAVEBEVQ71MAVE

4 HP3 HP

12510071

Capacity Range

12510071

Connection Unit

Capacity Index

FXFQ-PVE

Indoor unitsIndoor units can be selected from 2 lineups, both VRV and residential indoor units, to match rooms and preferences.

BEV units are necessary for Connection unit series indoor units. Refer to the Engineering Data Book for details.Note:

Connection unit

Page 5: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Wall Mounted

Slim CeilingMounted Duct

Ceiling MountedCassette (Compact Multi Flow)

Type Model Name Rated Capacity 2.5 kW 6.0 kW 7.1 kW5.0 kW3.5 kW

Capacity Index 29 68 795540

25 60 715035

FFQ-BV1B

FDKS-EAVMB

FDKS-C(A)VMB

Ceiling Mounted Cassette FCQ-BVE

Ceiling MountedBuilt-in FBQ-BV1

FTKS-DVM

FTKS-FVM

(700 mm width type)

(900/1,100 mm width type)

4

Residential indoor units with connection to BP units 7 types 21 models

Outdoor units

8, 10 HP 12, 14, 16, 18 HP

The new VRVIII single outdoor unit series offers 6 models to select from, providing the power that suits your needs.

Model Name

CapacityRange

Capacity Index

RSXQ8PY1 RSXQ10PY1 RSXQ12PY1 RSXQ14PY1

8 HP 10 HP 12 HP

200 250 300

Outdoor unit lineup

RSXQ16PY1 RSXQ18PY1

16 HP 18 HP

22.4 kW

HP

kW 28.0 kW 33.5 kW

14 HP

350

40.0 kW 45.0 kW 49.0 kW

400 450

Residential indoor units

BP units are necessary for residential indoor units. Refer to page 33 for BP unit details.Note:

BP unit BP unit

single outdoor unit series

Page 6: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Energy efficiency and quiet operation

Main Features

5

Nighttime quiet operation function

Set on the outdoor PCB. Time of maximum temperature is memorised. The low operating mode will initiate 8 hours*1 after the peak temperature in the daytime, and normal operation will resume 10 hours*2 after that. The operation sound level for the night mode can be selected from 55 dB(A) (Step 1),50 dB(A) (Step 2) and 45 dB(A) (Step 3).

Automatic mode

Operation sound level selectable from 3 steps for the night mode

Mode 1.

Automatic modeMode 1.

Starting time and ending time can be input. (An external control adaptor for outdoor unit, DTA104A53/61/62, and a locally obtained timer are necessary.)

Manual modeMode 2.

Combinations of modes 1 and 2 can be used depending on your needs.

Combined modeMode 3.

*1. Initial setting. Can be selected from 6, 8 and 10 hours.*2. Initial setting. Can be selected from 8, 9 and 10 hours.

High COPsIt has become essential for air conditioning manufacturers to develop systems that provide high energy savings. We at Daikin have made great efforts in this field, and the VRVIII delivers highly efficient performance, contributing to high energy savings.

We have reached a high level of efficiency, thanks to advanced features such as the heat exchanger, the grille and the dual DC fans.

Achieving a high COP

• Cooling operating conditions: Indoor temp. of 27°CDB, 19.0 °CWB, and outdoor temp. of 35°CDB.

1

8 HP 10 HP 12 HP

2

3

4

4.27

3.54 3.75

Outdoor units use Daikin’s unique scroll compressor to realise energy saving performance and quiet operation.

• This function is available in setting at site.

• The relationship of outdoor temperature (load) and time shown in the graph is just an example.

The capacity reduction rate differs depending on the operation sound level step selected.

Notes:

Peak in outdoor temperature (For 10 HP outdoor unit)

Cap

acity

%

8 hrs 10 hrs

Ope

ratio

n so

und

dB(A

)

50

8:00 12:00 16:00 20:00 0:00 4:00 8:00

50

100

5855

0

Load

%

Night mode Night mode endsendsNight mode Night mode startsstarts Night mode endsNight mode starts

Night Mode

45

(Initial setting)(Initial setting)

Step 2 max. - 8dB(A)

Step 1 max. - 3dB(A)

Step 3 max. - 13dB(A)

Step 2: 50 dB(A)

Step 1: 55 dB(A)

Step 3: 45 dB(A)

Page 7: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

A collection of cutting-edge technologiesrealises efficient and quiet operation

1

5 DC fan motor

3 Compact aero box

Realises a compact casing by stacking the Inverter and control PCBs plus optimising the internal design to suit airflow speed. This achieves low noise and reduces the power required by the large-diameter fanned outdoor unit.

• Efficiency improvement by approximately 40% especially at low speed.

4 Smooth sine wave DC Inverter

By adoption of the Sine Wave, which smoothes the rotation of the motor, operation efficiency is improved sharply. DC fan motor

structure

ReluctanceDC motor

High efficiency compressor

Reluctance DC scroll compressorDaikin’s unique scroll compressor reduces heat loss, and is driven by a high efficiency motor to achieve significant energy savings.

By introducing high pressure oil, the reactive force from the fixed scroll is added to the internal force, thereby reducing thrust losses. This results in improved efficiency and suppressed sound levels.

High-performance, low-noise scroll compressor operates at a fast rate. The speed increase has been achieved through advanced stress analysis for increased strength and utilisation of the advantages (oil film control) of the high thrust mechanism.*

*High thrust mechanism

200 300 400 500 600 700 800 900 1000

0

20

40

80

60

100

Eff

icie

ncy

(%

)

Motor speed (rpm)

AC motorAC motorAC motorAC motorAC motor

DC motor efficiency (comparison with AC motor)

Approx.Approx.

40%40%increaseincrease

Approx.

40%increase

DC motorDC motorDC motorDC motorDC motor

High torque and efficiency is attained with the adoption ofneodymium magnets.

Neodymium magnets are well known for their powerfulness compared to commonly used ferrite magnets.

Use of neodymium magnets in the motor enables efficient generation of high torque.

Powerful magnets

Note: Data are based on studies conducted under controlled conditions at a Daikin laboratory.

Thanks to an optimised e-Pass heat exchanger, heat change effectiveness has been increased, thus contributing to a high COP.

2 Heat exchanger

6

2 4

3

1

5

Page 8: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Design flexibility

Main Features

Long piping length offers flexibility during installation.

When only VRV indoor units are connected

When only VRV indoor units are connected

Maximum allowablelevel difference

Maximum allowablepiping length

Maximum allowablepiping length

Minimum allowable piping length

Between the outdoor unitand the indoor unit

Between the indoor units

Between the first indoor branch and the farthest indoor unit

Total piping length

Refrigerant piping length

15 m

j

a+b+c+d+e+f+g+h+i

a+b+c+d+i

b+c+d+i

100 m 125 m

250 m

40 m

Actualpiping length

Equivalentpiping length Example

Level Difference Example

50 m kIf the outdoor unit is above.

If the outdoor unit is below. 40 m k

When a mixed combination of VRV and residential indoor units is connectedor when only residential indoor units are connected

Maximum allowablelevel difference Between the outdoor unit

and the indoor unit

Between BP unitand indoor unit

Between the indoor units

Between BP units

Between the first indoor branch and the farthest BP unit orbetween the first indoor branch and the farthest VRV indoor unit

Total piping length

Refrigerant piping length

Between outdoor unit and the first indoor branch

15 m

15 m

l

m

n

n

o

a+b+c+d+e+f+g+h+i+j+k

b+c+g, b+c+d

a+b+c+g+k, a+b+c+d

h, i, j, k

a

100 m

250 m

2 m–15 m

2 m–12 m

2 m–8 m

50 m*1

5 m

Actualpiping length Example

Level Difference Example

50 mIf the outdoor unit is above.

If the outdoor unit is below.

If indoor unit capacity index < 68.

If indoor unit capacity index is 68.

If indoor unit capacity index is 79.

40 m

40 m

Long piping length

*1. When the piping length exceeds 20 m, the size of the main pipes (the gas side and the liquid side) must be increased. Please refer to Engineering Data Book for details.

Max.

50 m

Max.

15 m

Max.

50 m

Max.

40 mMax.

15 m

Max.

15 m

Actual piping length

Max. 100 m

Total piping length

Max. 250 m

a

o

l

n

dcb

gfeFirst indoor branch

mh i

a

i

j

k

dcb

hgfeFirst indoor branch

Colours in the diagram below are merely for identifyingpipes referenced with symbols such as a .

Colours in the diagram below are merely for identifyingpipes referenced with symbols such as a .

VRV: VRV indoor unitRA: Residential indoor unitBP: BP unit

When a mixed combination of VRV andresidential indoor units is connected

j

k

Between the outdoor unit and the BP unit

BP

RA RA

RA

RA

VRV

VRV

BP

7

Page 9: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Easy Installation High reliability

High external static pressure of 78.4 PaHigh external static pressure has been achieved thanks to the fan grilles and the dual DC fans that reduce internal pressure loss. Daikin offers 78.4 Pa (8 mm H2O) external static pressure by field setting to meet the requirements for installation on each floor.

VRVIII single outdoor unit series enables a mixed combination of VRV and residential indoor units by connecting BP units. As many as 29 indoor units can be connected, making this series a highly versatile system.

78.4 Pa

Small and light, significantly reducingconstraints during carry-inCarry-in possible using ordinary elevators

Can be carried on a fork-lift without a pallet

Easy belt suspension

Automatic test operationSimply press the test operation button and the unit performs an automatic system check, including wiring, shutoff valves, and sensors. The results are returned automatically after the check finishes.

Backup operationIf one of the multiple compressors malfunctions, the other compressors take over for emergency operation.*1

Less chances of refrigerant leakageThe shutoff valve connections for outdoor unit are brazed, meaning less chance of refrigerant leakage compared with flanged or flared connections.

*1. Possible only with single outdoor unit systems that are equipped with two or more compressors. Local setting of the outdoor unit is necessary.

If one compressor malfunctions...

Emergency operation occurs.*1

Note: Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit. Refer to page 34 for the maximum number of connectable indoor units.

Indoorunits29

Max.

8

As many as 29 indoor units can be connected

VRV indoor units

Residential indoor units

BP unit BP unit

Page 10: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

9

360° airflow improves temperature distributionand offers a comfortable living environment.

FXFQ25P/FXFQ32P/FXFQ40P

FXFQ50P/FXFQ63P/FXFQ80P

FXFQ100P/FXFQ125P

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.

3-way flow L-shaped 2-way flowAll-round flow 4-way flow

850 mm

The industry’s first* Round Flow Ceiling Mounted Cassette type offers 360° airflow with improved temperature distribution.

All models are lighter than the conventional ones.Ex: Models FXFQ25P-50P are 4.5 kg lighter (reduced from 24 kg to 19.5 kg).

A modern sophisticated decoration panel has been applied, with a panel surface that has been treated with a dirt-repellant coating.

An antibacterial treatment that uses silver ions has been applied to the drain pan, preventing the growth of slime, mould and bacteria that cause blockages and odours.

The horizontal louvres prevent dew condensation. Their non-flocking surfaces, which repel dirt, are easy to clean.

The air filter has an anti-mould and antibacterial treatment that prevents the growth of mould generated from dust or moisture that may adhere to the filter.

Example of airflow patterns:360° airflow is available, as well as 2- to 4-way flows, so you can choose the most suitable airflow pattern depending on location or room layout.

Drain pump is equipped as standard accessory, and the lift height has been improved from 750 mm to 850 mm.

Treated surface Untreated surface

Resists soiling

• Condition after exposure to the smoke of 600 cigarettes in 1 m3 enclosed space.

Dirt andgrime

Control of the airflow rate has been improved from 2-step to 3-step control.

4-way flow Round Flow

There are areas of uneven temperature.

There are much fewerareas of uneven temperature.

* As of April 2004, the release date for Japan.

Indoor Unit Lineup

Low operation sound level (dB(A))

44/39/34

125

43/37.5/32

100

36/33.5/31

80

34/31/28

63

32/29.5/27

50

31/29/27

4025/32

30/28.5/27Soundlevel

(HH/H/L)

FXFQ-P

VRV Indoor Units

Ceiling Mounted Cassette (Round Flow) Type

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Page 11: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

10

Quiet, compact, and designed for user comfort

Dimensions correspond with 600 mm X 600 mm architectural module ceiling design specifications.

Wide discharge angle: 0° to 60°

2-, 3-, and 4-way airflow patterns are available, enabling installation in the corner of a room.

Comfortable airflow

Low operation sound level(dB(A))

60°

60°

Auto swing Fixed angles: 5 levels

Angles can be also set on site to prevent drafts (0°-35°) or soiling of the ceiling (25°-60°), other than standard setting (0°-60°).

For 3-way or 2-way flow installation, the sealing member for air dischargeoutlet (option) must be used to close each unused outlet.

30/25

20/25 32 40 50

32/26 36/28 41/33

32/26 34/28 37/29 42/35

FXZQ-M

750 mm

Drain pump is equipped as standard accessory with 750 mm lift.

4-way flow 3-way flowL-shaped

2-way flow

1

2

0° 0°

60° 60°

FXZQ20M/FXZQ25M/FXZQ32M

FXZQ40M/FXZQ50M

230 V

240 V

Sound level (H/L)

Ceiling Mounted Cassette (Compact Multi Flow) Type

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Page 12: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

11

Thin, lightweight, and easy to install in narrow ceiling spaces

FXCQ-M 20

32/27

25/32

34/28

63

37/32

40/50

34/29

80

39/34

125

44/38

34/29 36/30 39/3437/32 41/36 46/40

(dB(A))

305 mm

The thin unit (only 305 mm high) can be installed in a ceiling space as narrow as 350 mm. All models feature a compact design with a depth of only 600 mm.

(When a high-efficiency filter is attached, the unit's height is 400 mm.)

Low operation sound level

Designed with higher airflow suitable for high ceiling application up to 3 metres.

Providing 2 different settings of standard and ceiling soiling prevention, the auto swing mechanism realises even distribution of airflow and room temperature.

Two types of optional high-efficiency filter are available (65% and 95%, colourimetric method).

A long-life filter (maintenance free up to one year*) is equipped as standard accessory.

Drain pump is equipped as standard accessory with 600 mm lift.

Major maintenance work can be performed by removing the panel. A flat-type suction grille and a detachable blade make cleaning easy.

220 V

240 V

Sound level (H/L)

600 mm

600 mm

Indoor Unit Lineup

VRV Indoor Units

Ceiling Mounted Cassette (Double Flow) Type

FXCQ20M/FXCQ25M/FXCQ32M

FXCQ40M/FXCQ50M/FXCQ63M

FXCQ80M/FXCQ125M

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Page 13: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

12

Slim design for flexible installation

Main body

Air discharge grille (Option)

Set for front discharge using a suspended ceiling.

Downward discharge is shut off and air is blown straight out (front discharge).

Front discharge is possible with an air discharge unit (option), which allows the installation in the drop-ceiling or sagging wall.

Single-flow type allows effective air discharge from corner or from drop-ceiling.

Providing 3 different settings of standard, draft prevention and ceiling soiling prevention, the auto swing mechanism realises even distribution of airflow and room temperature.

Main body

Downward discharge

Air discharge grille (Option)

3

32˚C 30˚C28˚C 26˚C 24˚C

22˚C

20˚C

2

1

0 1 2 3 4 5 6 (m)

(m)

500 mm

Drain pump is equipped as standard accessory with 500 mm lift.

Slim body needs only 220 mm space above the ceiling. If you use a panel spacer (option), the unit can be installed in the minimum space of 195 mm.

A long-life filter (maintenance free up to one year*) is equipped as standard accessory.

Panel spacer

20 mm

Min.195 mm

Ceiling Mounted Cassette Corner Type

FXKQ25MA/FXKQ32MA

FXKQ40MA/FXKQ63MA

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Page 14: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Indoor Unit Lineup

VRV Indoor Units

Slim Ceiling Mounted Duct Type

13

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Slim design, quietness and static pressure switching

FXDQ40NB/FXDQ50NB/FXDQ63NB

External static pressure selectable by remote controller switching make this indoor unit a very comfortable and flexible model.10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.

Only 200 mm in height, this model can be installed in rooms with as little as 240 mm depth between the drop-ceiling and ceiling slab.

Only 700 mm in width and 23 kg in weight, this model is suitable to install in limited spaces like drop-ceilings in hotels.

Low operation sound level (dB(A))

The values of operation sound level represent those for rear-suction operation.Sound level values for bottom-suction operation can be obtained by adding 5 dB(A). Values are based on the following conditions:FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.

1,100 mm in width for the FXDQ63NB model.

200 mm900 mm

Suction grille*AIR

AIR

Discharge grille*

Air filterSuspension bolt*

240 mm

* To be obtained locally

FXDQ-PB and FXDQ-NB models are available in two types to suit different installation conditions.FXDQ-PB/NBVE: with a drain pump (750 mm lift)

as a standard accessory

FXDQ-PB/NBVET: without a drain pump

Only 700 mm

200 mm

Great for hotel use!

Suited to use in drop-ceilings!

750 mm

Ceiling

Control of the airflow rate has been improved from 2-step to 3-step control.

36/34/32

63

35/33/31

50

34/32/30

40

33/31/29

20/25/32

Sound level(HH/H/L)

FXDQ-PB/NB

FXDQ20PB/FXDQ25PB/FXDQ32PB

Page 15: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Ceiling Mounted Duct Type

14

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Middle and high static pressureallows for flexible duct design

FXMQ20P/FXMQ25P/FXMQ32PFXMQ40P/FXMQ50P/FXMQ63PFXMQ80P/FXMQ100P/FXMQ125PFXMQ140P

Built-in Drain Pump (Option)Housing the drain pump inside the unit reduces the space required for installation.

All models are only 300 mm in height, an improvement over the 390 mm height of conventional models. The weight of the FXMQ40P has been reduced from 44 kg to 28 kg.

A DC fan motor increases the external static pressure capacity range to include middle to high static pressures, increasing design flexibility.

Indoor unit

470 mm

Indoor unit

470 mm

0–250mm

222 mm

Without drain pump With drain pump

Simplified Static Pressure ControlExternal static pressure can be easily adjusted using a change-over switch inside the electrical box to meet the resistance in the duct system.

Drain pump is equipped as standard accessory with 700 mm lift.

Control of the airflow rate has been improved from 2-step to 3-step control.

(dB(A))

46/45/43

140

42/40/38

63

43/41/39

80/100

41/39/37

50

39/37/35

40

34/32/30

32

33/31/29

20/25

Soundlevel

(HH/H/L)

FXMQ-P

700 mm

Ceiling

30 Pa–100 Pa for FXMQ20P-32P30 Pa–160 Pa for FXMQ40P50 Pa–200 Pa for FXMQ50P-125P50 Pa–140 Pa for FXMQ140P

Low operation sound level

Improved ease of installation

Improved ease of maintenance

The airflow rate can be controlled using a remote controller during test operation. With the conventional model, the airflow rate was controlled from the PC board. It is automatically adjusted to the range between approximately ±10% of the rated HH tap airflow for FXMQ20P–125P.

The drain pan can be detached for easy cleaning. An antibacterial treatment that uses silver ions has been applied to the drain pan, preventing the growth of slime, mould and bacteria that cause blockages and odours.

Energy-efficientThe adopted DC fan motor is much more efficient than the conventional AC motor, yielding an approximate 20% decrease in energy consumption (FXMQ125P).

25 mm

44/42/40

125

FXMQ200MA/FXMQ250MA

Page 16: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Indoor Unit Lineup

VRV Indoor Units

Ceiling Suspended Type

15

Slim body with quiet and wide airflow

Adoption of QUIET STREAM FAN

Drain pump kit (option) can be easily incorporated.

Easy-to-clean flat design

Maintenance is easier because everything can be performed from below the unit.

Non-dew Flap with no implanted bristles

FXHQ-MA

Sound level(H/L)

32

36/31

63

39/34

100

45/37

(dB(A))Low operation sound level

Uses the quiet stream fan and many more advanced technologies.

Sound absorptionmember

Turbulent flow is produced

Straightening vane

Quiet stream fan

Installation is easy

Maintenance is easy

Drain pump kit(built inside main unit)

600 mm

Bristle-free Flap minimises contamination and makes cleaning simpler.

Non-dew Flap

100°

Wide air discharge openings produce a spreading 100° airflow.

A long-life filter (maintenance free up to one year*) is equipped as standard accessory.

FXHQ32MA/FXHQ63MA

FXHQ100MA

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Page 17: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Wall Mounted Type

16

Sophisticated design and compact casing harmonised with your interior décor

Drain pan and air filter can be kept clean by mildew-proof polystyrene.

Compact and stylish design that does not detract from the décor of the room.

Drain pump kit is available as optional accessory, which lifts the drain 1,000 mm from the bottom of the unit.

Auto-swing realises efficiency of air distribution. The louvre closes automatically when the unit stops.

5 steps of discharge angle can be set by remote controller.

Washable grille, the front grille can be easily removed for washing.

Discharge angle is automatically set at the same angle as the previous operation when restarting. (Initial setting: 10˚ for cooling)

Flexible installationDrain pipe can be fitted to from either left or right sides.

Low operation sound level

46/39

63

42/36

50

39/34

40

37/29

32

36/29

25

35/29

20

Sound level(H/L)

FXAQ-MA

(dB(A))

FXAQ20MA/FXAQ25MA

FXAQ32MA/FXAQ40MA

FXAQ50MA/FXAQ63MA

Drain pump kit

1,000 mm

Height of drain-up

Indoor unit

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Page 18: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Indoor Unit Lineup

VRV Indoor Units

Floor Standing Type

17

Suitable for perimeter zone air conditioning

Wall hanging Floor installation

Floor Standing types can be hung on the wall for easier cleaning. Running the piping from the back allows the unit to be hung on walls. Cleaning under the unit, where dust tends to accumulate, is considerably easier.

A long-life filter (maintenance free up to one year*) is equipped as standard accessory.

The adoption of a fibre-less discharge grille featuring an original design to prevent condensation also helps prevent staining and makes cleaning easier.

Concealed Floor Standing Type

Designed to be concealed in the perimeter skirting-wall

Connecting port

Refrigerant piping

Applies also to Floor Standing type (FXLQ-MA).

The unit is concealed in skirting-wall of perimeter, that enables to create high class interior design.

The connecting port faces downward, greatly facilitating on-site piping work.

A long-life filter (maintenance free up to one year*) is equipped as standard accessory.

FXNQ20MA/FXNQ25MA

FXNQ32MA/FXNQ40MA

FXNQ50MA/FXNQ63MA

FXLQ20MA/FXLQ25MA

FXLQ32MA/FXLQ40MA

FXLQ50MA/FXLQ63MA

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

* 8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Page 19: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Ceiling Suspended Cassette Type

18

Connection unit series indoor units

FXUQ71MA/FXUQ100MA

FXUQ125MA

This thin indoor unit achievesoptimum air distribution, and can be installed

without the need for ceiling cavity.

Depending on installation site requirements or room conditions, 2-way, 3-way and 4-way discharge patterns are available.

4-way airflowfrom the centre of the store.

The 3-way airflow can distributecomfortable air throughout the room.

Only one unit is needed to distribute comfortable airthroughout an L-shaped store.

Connection unit Connection unit is the device for connecting above indoor unit to VRV III.

BEVQ-MA

Connection unit for indoor unit

Indoor unitPiping length*1

Indoor unit

Remote controller

Super wiring (DIII-NET)

Single-phase 220-240 Vpower supply

Refrigerant piping layout External wiring layout

Notes:

Gas pipeLiquid pipe

ModelMaximum piping lengthbetween the BEV unitand the indoor unit.

FXUQ-MA 5 m

*1

• When connecting centralised-control device, it is necessary to install an interface adaptor for an indoor unit (DTA102A52).

• Connection unit BEVQ-MA is necessary for each indoor unit.

• The refrigerant piping height difference between the indoor units and the BEV unit must be within 4 m.

• The BEV unit must be installed within a maximum height difference between indoor units of 15 m.

• Branching of the refrigerant piping is not possible downstream of the BEV unit.

VRV series outdoor unit

BEVQ71MA/BEVQ100MA/BEVQ125MA

* Remote controllers are an optional accessory. Refer to page 39 for remote controller details.

Page 20: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Indoor Unit Lineup

Residential Indoor Units

19

FCQ35B/FCQ50B/FCQ60B/FCQ71B

Option

Option

Signal receiver unitNote: Remote controller cables not included. Cables should beobtained locally.

Note: Wireless remote controllers and signal receiver units are sold as a set.

Specially designed for false ceilings—for a smooth, modern interior finish

All models feature a decoration panel with the same size and simple design in consideration of harmonised interior décor.

The indoor units weigh only 24 kg and require an installation space with a height of just 245 mm.

950 mm

950

mm

Same for all models

Decoration panel is optional

Min. 245 mm

Standard

Draft prevention

Soiling prevention

FCQ35B

33/29 dB (A)

FCQ50B

33/29 dB (A)

FCQ60B

35/30 dB (A)

FCQ71B

35/30 dB (A)

(H/L)

Drain pump is equipped as standard with 750 mm.

Three convenient patterns for auto-swing operation

These models have the power to provide a comfortable airflow even with a ceiling height of up to 3.8 m.

750 mm

Max. 3.8 m

Low operation sound level

Ceiling Mounted Cassette Type

with connectionto BP units

Page 21: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

20

Quiet, compact, and designed for user comfort

T-bar grid does not need to be cut.

Designed to fit 600 mm wide ceiling grids Low draft performance is designed for your comfort.

Comfortable across all areas

Low operation sound level

Option

Signal receiver unitNote: Wireless remote controllers and signal receiver units are sold as a set.

OptionNote: Remote controller cables not included. Cables should beobtained locally.

FFQ25B/FFQ35B/FFQ50B/FFQ60B

575 mm

575 mm

700 mm

700 mm

286 mm

Compact

decorative panel

T-bar

600 mm600 mm

Ceiling panel

FFQ25B

29.5/24.5 dB (A)

FFQ35B

32/25 dB (A)

FFQ50B

36/27 dB (A)

FFQ60B

41/32 dB (A)

(H/L)

Horizontal Flow0° 0°

Less draught

Settable to 5 different levels between 0° and 35°

Settable to 5 different levels between 0° and 60°

Settable to 5 different levels between 25° and 60°

Auto-swing between 0° and 35°

Auto-swing between 0° and 60°

Auto-swing between 25° and 60°

Draft prevention setting(Set on site)

(Set on site)

Standard setting

Setting to prevent soiling of ceiling

Conditioned air is distributed evenly by Auto-swing operation.

Adjustable airflow angle to suit all room conditions.

AUTO-SWING

0° 0°

25°

60° 60°

35°

25°

60°

35°

60°

5 direction

Note: Angles shown above are provided as a guide. They may differ depending on the installation site.

Ceiling Mounted Cassette (Compact Multi Flow) Type

750 mm

Drain pump is equipped as standard accessory with 750 mm lift.

Page 22: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Indoor Unit Lineup

Ceiling Mounted Built-in Type

21

FBQ60B

41/35 dB (A)

FBQ71B

41/35 dB (A)

(H/L)

The indoor unit can be installed in rooms with as little as 350 mm between the drop ceiling and ceiling slab. It also works with both flexible and ordinary ducts.

To cope with the challenges of L-shaped or U-shaped spaces, it is possible to install the air discharge unit away from the main unit. This extends the possibilities for coping with human gathering patterns or sun lighting. At the same time, different types of architectural space can be kept comfortable.

1

3

7

1

11

2

3

3

4

8

9

7911

5

10

46

5

Air conditioner

Long-life filter

Air blow Air intake

425 mm or more46

5

2 2Air conditioner

Long-life filterAir blowAir intake

350 mm or more

Standard installation examples With high-efficiency filter

Ceiling return

In crawl space With canvas bellows and air intake panel (sold separately)

45 mm

46

5

Air conditioner

Long-life filter

Air blow

Air intake450 mm or more

8

Air conditioner Ordinary duct(procured locally)

Ordinary duct(procured locally)

Air blow Air intake

460 mm or more

8

Air intake

Ceiling return with high-efficiency filter With ordinary ducts

46

5

Air conditioner

Air blow Air intake

540 mm or more13

946

5

Air conditioner

Air blow

540 mm or more

Options

Air discharge opening adaptorDecorative panel

Canvas bellows and air intake panelFlexible ductAir discharge grille

Air discharge opening flangeRear intake blocking pad

6

7

8

Air discharge chamber

Inspection panelHigh-performance filter

11

12

13 Low-draft filter chamberBranch ductRear intake filter chamber

1011

2

2

2

Flexible air discharge unit to fit various forms of space

Note: Remote controller cables not included. Cables should beobtained locally.

Option

Drain pump is equipped as standard accessory with 250 mm lift.

250 mm

L-shaped room U-shaped room Long room

Low operation sound level

FBQ60B/FBQ71B

Residential Indoor Units with connectionto BP units

Page 23: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Slim Ceiling Mounted Duct Type

22

Slim and smooth design suits your shallow ceiling

700 mm width type

900/1,100 mm width type

Signals from the wireless remote controller aretransmitted to the signal receiver.

240 mm

200 mm

Only 700 mm

FDKS-EA

Dimensions (H x W x D)WeightAirflow rate (H)External static pressure

200 x 700 x 620 mm21 kg

8.7 m3/min30 Pa

200 x 900 x 620 mm25 kg

40 Pa

FDKS25EA FDKS35EA FDKS25CA FDKS35CA

9.5 m3/min 10 m3/min

FDKS25

35/31/29 dB (A)

FDKS35

35/31/29 dB (A)

FDKS50

37/33/31 dB (A)

FDKS60

38/34/32 dB (A)

(H/L/SL)Low operation sound level

Home Leave Operation prevents large rises or falls in the indoor temperature by continuing operation* while you are sleeping or out of your home. This means that an air-conditioned welcome awaits when you wake or return. It also means that the indoor temperature can quickly return to your favourite comfort setting.

Models in the FDKS-EA series are only 700 mm in width and 21 kg in weight, so are easily installed in limited spaces. Just 200 mm in height, all models can be installed in rooms with as little as 240 mm depth between the drop ceiling and ceiling slab, making them ideal for even shallow ceilings.

Notes: 1. To prevent an increase in operation noise, avoid

installing the air suction grille directly below the suction chamber.

2. Grilles, piping connections, ducts, and installation parts should be obtained locally. Slim Ceiling Mounted Duct type FDKS models do not have drain-up pumps.

3. The signal receiver unit must be located near the air suction inlet, because the unit includes a sensor that detects room temperature.

Suction grille (KDGF19A45)

Option

* Locally obtained partsAIRAir suction grille*

Suction duct*

Signal receiver

Air discharge duct* Suspension bolt*

Air discharge grille*

Signal receiver wireLength = 1,900 mm

Chamber

AIR

Air filter

* Home Leave Operation can be selected for any temperature from 18 to 32˚C for cooling operation and 10 to 30˚C for heating operation.

* Home Leave Operation function must be set using the remote controller when going to sleep or leaving the house, and after waking up or returning home.

Standard accessoryNote: Remote controllers other than the standard accessory wireless remote controller cannot be used.

FDKS25EA/FDKS35EA

FDKS25CA/FDKS35CA/FDKS50C/FDKS60C

Great for hotel use!

Page 24: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Indoor Unit Lineup

Wall Mounted Type

23

Wall Mounted indoor units achieve quiet sound levels of 22 dB (A).

Intelligent Eye with its infrared sensor automatically controls air conditioner operation according to human movement in a room. When there is no movement, it adjusts the temperature by 2˚C for energy savings.

Titanium apatite is a photocatalytic material with high adsorption power. Titanium apatite also effectively adsorbs and decomposes bacteria across its entire surface. The photocatalyst is activated simply by exposure to light.

These filters are not medical devices. Benefits such as the adsorption and decomposition of bacteria are only effective for substances that are collected on and in direct contact with the Titanium Apatite Photocatalytic Air-Purifying Filter.

Bacteria Removal TestTesting method: dropping methodResult certificate: No. 012553-1 and 012553-2Testing organisation: Japan Spinners Inspecting Foundation

3-D Airflow combines Vertical and Horizontal Auto-Swing to circulate air to every part of a room for uniform cooling of even large spaces.* This function is available for

FTKS50/60/71F.

FTKS25D/FTKS35D

FTKS50F/FTKS60F/FTKS71F

FTKS25D

37/25/22 dB (A)

FTKS35D

39/26/23 dB (A)

FTKS50F

43/34/31 dB (A)

FTKS60F

45/36/33 dB (A)

FTKS71F

46/37/34 dB (A)

(H/L/SL)

When you are in the room When you go out

A uniform temperatureis achieved throughout the entire room.

Titanium Apatite Photocatalytic Air-purifying Filter

catches dustAir filter

Stylish flat panel harmonises with your interior décor

* Remote controllers other than the standard accessory wireless remote controller cannot be used.

Residential Indoor Units with connectionto BP units

Standard accessory*

Standardaccessory*

Page 25: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

24

Ceiling Mounted Cassette (Round Flow) Type

FXFQ25PVE

2.9

9,900

2,500

Galvanised steel plate

246X840X840

19.5

6.4

12.7

VP25 (External Dia, 32/Internal Dia, 25)

BYCP125K-W1

Fresh white

50X950X95050X950X95050X950X95050X950X95050X950X95050X950X95050X950X95050X950X950

5.55.55.55.55.55.55.55.5

246X840X840

19.5

6.4

12.7

FXFQ32PVE

3.7

12,600

3,200

15/13/1113/11.5/10 13/11.5/10

30/28.5/27 30/28.5/27

530/459/388

31/29/27

246X840X840

19.5

6.4

12.7

FXFQ40PVE

4.7

16,000

4,000

16/13.5/11

565/477/388459/406/353 459/406/353

32/29.5/27

246X840X840

19.5

6.4

12.7

FXFQ50PVE

5.8

19,800

5,000

19/16.5/13.5

671/583/477

34/31/28

246X840X840

22

9.5

15.9

FXFQ63PVE

7.3

24,900

6,300

21/18/15

742/636/530

36/33.5/31

246X840X840

22

9.5

15.9

FXFQ80PVE

9.3

2.8 3.6 4.5 5.6 7.1 9.0

31,700

8,000

FXFQ100PVE

11.6

39,600

10,000

FXFQ125PVE

14.5

11.2 14.0

49,500

12,500

32/26/20

1,130/918/706

43/37.5/32

288X840X840

25

9.5

15.9

33/28/22.5

1,165/989/794

44/39/34

288X840X840

25

9.5

15.9

1-phase, 220-240 V/220 V, 50/60 Hz

Casing

Airflow rate (HH/H/L)m3/min

cfm

MODEL

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Power supply

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Panel(Option)

Model

Colour

mmDimensions (HXWXD)

Weight kg

Liquid (Flare)

Gas (Flare) mm

dB(A)Sound level (HH/H/L)

0.033 0.033 0.047 0.052 0.066 0.093 0.187 0.209kWPower consumption

kWPower consumption

Ceiling Mounted Cassette (Compact Multi Flow) Type

Galvanised steel plate

VP20 (External Dia, 26/Internal Dia, 20)

BYFQ60B8W1

White (6.5Y9.5/0.5)

55X700X700

2.7

9/7

318/247

30/25-32/26

286X575X575

18

6.4

12.7

FXZQ20MVE

2.3

7,800

2,000

2.2

1-phase, 220-240 V/220 V, 50/60 Hz

55X700X700

2.7

9/7

318/247

30/25-32/26

6.4

12.7

55X700X700

2.7

9.5/7.5

335/265

32/26-34/28

6.4

12.7

55X700X700

2.7

11/8

388/282

36/28-37/29

6.4

12.7

55X700X700

2.7

0.073 0.073 0.076 0.089 0.115

14/10

493/353

41/33-42/35

6.4

12.7

FXZQ25MVE

2.9

9,900

2,500

2.8

FXZQ32MVE

3.7

12,600

3,200

3.6

FXZQ40MVE

4.7

16,000

4,000

4.5

FXZQ50MVE

5.8

19,800

5,000

5.6

Casing

Airflow rate (H/L)m3/min

cfm

MODEL

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Power supply

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Panel(Option)

Model

Colour

mmDimensions (HXWXD)

Weight kg

Liquid (Flare)

Gas (Flare) mm

dB(A)Sound level (H/L) 230 V-240 V

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.•Equivalent piping length: 7.5 m•Level difference: 0 m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Specifications

VRV Indoor Units

Page 26: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

25

Ceiling Mounted Cassette Corner Type

Ceiling Mounted Cassette (Double Flow) Type

FXKQ25MAVE

2.9

9,900

2,500

Galvanised steel plate

11/9

FXKQ32MAVE

3.7

12,600

3,200

FXKQ40MAVE

4.7

16,000

4,000

FXKQ63MAVE

7.3

2.8 3.6 4.5 7.1

24,900

6,300

11/9 13/10 18/15

388/318 388/318 459/353 635/530

215X1,110X710

31.0

6.4

12.7

VP25 (External Dia, 32/Internal Dia, 25)

BYK45FJW1

White (10Y9/0.5)

70X1,240X800

8.5

215X1,110X710

31.0

6.4

12.7

70X1,240X800

8.5

215X1,110X710

31.0

6.4

12.7

70X1,240X800

8.5

215X1,310X710

34.0

9.5

15.9

BYK71FJW1

70X1,440X800

9.5

38/33 38/33 40/34 42/37

40/35 40/35 42/36 44/39

1-phase, 220-240 V/220 V, 50/60 Hz

Airflow rate (H/L)m3/min

cfm

Sound level (H/L) dB(A)220 V

240 V

0.066 0.066 0.076 0.105

kW(*1)

Btu/h(*1)

kcal/h(*1)

(*2)

Power supply

Cooling capacity

MODEL

Casing

Power consumption kW

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Panel(Option)

Model

Colour

mm

kg

Dimensions (HXWXD)

Liquid (Flare)

Gas (Flare) mm

Weight

Galvanised steel plate

7/5

247/177

32/27

305X775X600

26.0

6.4

12.7

VP25 (External Dia, 32/Internal Dia, 25)

BYBC32G-W1

White (10Y9/0.5)

53X1,030X680

8.0

9/6.5

318/230

34/28

305X775X600

26.0

6.4

12.7

53X1,030X680

8.0

9/6.5

318/230

34/28

305X775X600

26.0

6.4

12.7

53X1,030X680

8.0

12/9

424/318

34/29

305X990X600

31.0

6.4

12.7

BYBC50G-W1

53X1,245X680

8.5

12/9

424/318

34/29

305X990X600

32.0

6.4

12.7

53X1,245X680

8.5

16.5/13

582/459

37/32

305X1,175X600

35.0

9.5

15.9

BYBC63G-W1

53X1,430X680

9.5

26/21

918/741

39/34

305X1,665X600

47.0

9.5

15.9

BYBC125G-W1

53X1,920X680

12.0

33/25

1,165/883

44/38

34/29 36/30 36/30 37/32 37/32 39/34 41/36 46/40

305X1,665X600

48.0

9.5

15.9

53X1,920X680

12.0

FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE

2.3

7,800

2,000

2.9

9,900

2,500

3.7

12,600

3,200

4.7

16,000

4,000

5.8

19,800

5,000

7.3

24,900

6,300

9.3

31,700

8,000

14.5

2.2 2.8 3.6 4.5 5.6 7.1 9.0 14.0

49,500

12,500

1-phase, 220-240 V/220 V, 50/60 Hz

0.077 0.092 0.092 0.130 0.130 0.161 0.209 0.256

Casing

Airflow rate (H/L)m3/min

Sound level (H/L)220 V

240 VdB(A)

cfm

Power consumption kW

MODEL

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Power supply

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Panel(Option)

Model

Colour

mmDimensions (HXWXD)

Weight kg

Liquid (Flare)

Gas (Flare) mm

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.•Equivalent piping length: 7.5 m •Level difference: 0 m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: (FXCQ-M) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

(FXKQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Specifications

VRV Indoor Units

Page 27: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

26

Slim Ceiling Mounted Duct Type (700 mm width type)

Galvanised steel plate

7,800

2,000

9,900

2,500

12,600

3,200

2.2

0.086 0.086 0.089

8.0/7.2/6.4

282/254/226

8.0/7.2/6.4

282/254/226

8.0/7.2/6.4

282/254/226

33/31/29 33/31/29 33/31/29

Airflow rate (HH/H/L)m3/min

cfm

Casing

1-phase, 220-240 V/220 V, 50/60 Hz

200X700X620

23.0

6.4

12.7

200X700X620

23.0

6.4

12.7

200X700X620

23.0

6.4

12.7

2.8 3.6

2.3 2.9 3.7

VP20 (External Dia, 26/Internal Dia, 20)

30-10 1

FXDQ20PBVET FXDQ25PBVET FXDQ32PBVETMODEL without

drain pump

FXDQ20PBVE FXDQ25PBVE FXDQ32PBVEwith drain pump

Power consumption(FXDQ-PBVE) kW

0.067 0.067 0.070Power consumption(FXDQ-PBVET) kW

0.160 0.165 0.181Power consumption(FXDQ-NBVE) kW

0.147 0.152 0.168Power consumption(FXDQ-NBVET) kW

Power supply

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Liquid (Flare)

Gas (Flare) mm

dB(A)Sound level (HH/H/L)

PaExternal static pressure

32

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)

Galvanised steel plate

1-phase, 220-240 V/220 V, 50/60 Hz

VP20 (External Dia, 26/Internal Dia, 20)

44-15 1

16,000

4,000

19,800

5,000

24,900

6,300

10.5/9.5/8.5

371/335/300

12.5/11.0/10.0

441/388/353

16.5/14.5/13.0

583/512/459

34/32/30 35/33/31 36/34/32

200X900X620

27.0

6.4

12.7

200X900X620

28.0

6.4

12.7

200X1,100X620

31.0

9.5

15.9

4.5 5.6 7.1

4.7 5.8 7.3

FXDQ40NBVET FXDQ50NBVET FXDQ63NBVET

FXDQ40NBVE FXDQ50NBVE FXDQ63NBVE

Airflow rate (HH/H/L)m3/min

cfm

Casing

MODEL without drain pump

with drain pump

Power supply

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Liquid (Flare)

Gas (Flare) mm

dB(A)Sound level (HH/H/L)

PaExternal static pressure

32

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. 1 : External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting

is 10 Pa for FXDQ-PB models and 15 Pa for FXDQ-NB models.) 2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be obtained by adding 5 dB(A). 3: Values are based on the following conditions: external static pressure of 10 Pa.•Equivalent piping length: 7.5 m •Level difference: 0 m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Page 28: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

27

Ceiling Mounted Duct Type

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. 1: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50-

125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P.

•Equivalent piping length: 7.5 m •Level difference: 0 m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

FXMQ40PVE FXMQ50PVE

4.7

16,000

4,000

Galvanised steel plate

565/459/388

300X700X700

28.0

VP25 (External Dia, 32/Internal Dia, 25)

5.8

19,800

5,000

635/582/530

300X1,000X700

36.0

4.5 5.6

cfm

External static pressure

Casing

1-phase, 220-240 V/220 V, 50/60 Hz

6.4

12.7

6.4

12.7

Power consumption kW 0.194 0.215

Airflow rate (HH/H/L)16/13/11 18/16.5/15m3/min

Pa 30-160 50-2001 1

39/37/35

FXMQ20PVE

2.3

7,800

2,000

318/265/230

300X550X700

25.0

2.2

6.4

12.7

0.081

9/7.5/6.5

30-100

33/31/29

FXMQ25PVE

2.9

9,900

2,500

318/265/230

300X550X700

25.0

2.8

6.4

12.7

0.081

9/7.5/6.5

30-100

33/31/29

FXMQ32PVE

3.7

12,600

3,200

335/282/247

300X550X700

25.0

3.6

6.4

12.7

0.085

9.5/8/7

30-100

34/32/30 41/39/37Sound level (HH/H/L) dB(A)

(*1)

(*2)

MODELPower supply

Cooling capacity

kW

Btu/h(*1)

kcal/h(*1)

Drain

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Liquid (Flare)

Gas (Flare) mm

1 1 1

FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE

Galvanised steel plate

VP25 (External Dia, 32/Internal Dia, 25)

7.3

24,900

6,300

688/618/565

300X1,000X700

36.0

9.5

15.9

9.3

31,700

8,000

883/794/706

300X1,000X700

36.0

9.5

15.9

11.6

39,600

10,000

1,130/953/812

300X1,400X700

46.0

9.5

15.9

14.5

49,500

12,500

1,377/1,165/988

300X1,400X700

46.0

9.5

15.9

7.1 9.0 11.2 14.0

cfm

External static pressure

Casing

1-phase, 220-240 V/220 V, 50/60 Hz

Power consumption kW 0.230 0.298/ 0.376 0.461

Airflow rate (HH/H/L)19.5/17.5/16 25/22.5/20 32/27/23 39/33/28m3/min

Pa 50-200 50-200 50-200 50-200 1 1 1 1

42/40/38 43/41/39 43/41/39 44/42/40

FXMQ140PVE

16.7

57,000

14,300

1,624/1,377/1,130

300X1,400X700

47.0

9.5

15.9

16.0

0.461

46/39/32

50-140 1

46/45/43Sound level (HH/H/L) dB(A)

(*1)

(*2)

MODELPower supply

Cooling capacity

kW

Btu/h(*1)

kcal/h(*1)

Drain

Dimensions (HXWXD) mm

Machine weight kg

Liquid (Flare)

Gas (Flare) mmPipingconnections

Specifications

VRV Indoor Units

Page 29: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

28

Ceiling Mounted Duct Type

Ceiling Suspended Type

FXMQ200MAVE FXMQ250MAVE

23.0

78,500

19,800

28.8

22.4 28.0

98,300

24,800

1-phase, 220-240 V/220 V, 50/60 Hz

MODELPower supply

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Power consumption kW

External static pressure Pa

Galvanised steel plate

58/50

2,047/1,765

470X1,380X1,100

137.0

9.5

19.1

PS1B

72/62

2,542/2,189

470X1,380X1,100

137.0

9.5

22.2

132-221 191-270 1 1

1.294 1.465

48/45 48/45

49/46 49/46

Casing

m3/min

cfm

Dimensions (HXWXD) mm

Machine weight kg

Airflow rate (H/L)

Sound level(H/L)

dB(A)220 V

240 V

Pipingconnections

Drain

Liquid (Flare)

Gas (Brazing) mm

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB.

(*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB. 1 : External static pressure is changeable to change over the connectors inside electrical box, this pressure means "Standard-High static pressure".•Equivalent piping length: 7.5 m•Level difference: 0 m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: (FXMQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.

(FXHQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.During actual operation, these values are normally somewhat higher as a result of ambient conditions.

MODELPower supply

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

cfm

Dimensions (HXWXD) mm

Machine weight kg

m3/minAirflow rate (H/L)

dB(A)Sound level (H/L)

Pipingconnections

Drain

Liquid (Flare)

Gas (Flare) mm

FXHQ32MAVE

3.7

12,600

3,200

White (10Y9/0.5)

FXHQ63MAVE

7.3

24,900

6,300

FXHQ100MAVE

11.6

3.6 7.1 11.2

39,600

10,000

424/353 618/494 883/688

195X960X680

24.0

6.4

12.7

VP20 (External Dia, 26/Internal Dia, 20)

195X1,160X680

28.0

9.5

15.9

195X1,400X680

33.0

9.5

15.9

Casing

1-phase, 220-240 V/220 V, 50/60 Hz

36/31 39/34 45/37

kW 0.111 0.115 0.135

12/10 17.5/14 25/19.5

Power consumption

Page 30: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

29

Wall Mounted Type

FXAQ25MAVE

2.9

White (3.0Y8.5/0.5)

36/29

290X795X230

11.0

Casing

1-phase, 220-240 V/220 V, 50/60 Hz

37/29

290X795X230

11.0

FXAQ40MAVE

4.7

39/34

290X1,050X230

14.0

9,900 16,000

2,500 4,000

282/177 318/194 424/318

m3/minAirflow rate (H/L)

cfm

8/5 9/5.5

FXAQ32MAVE

3.7

12,600

3,200

2.8

FXAQ20MAVE

2.3

35/29

290X795X230

11.0

7,800

2,000

265/159

7.5/4.5

2.2 4.53.6

12/9

VP13 (External Dia, 18/Internal Dia, 13)

6.4 6.4 6.4 6.4

12.7 12.7 12.7 12.7

42/36

290X1,050X230

14.0

FXAQ63MAVE

7.3

24,900

6,300

15/12 19/14

530/424

46/39

290X1,050X230

14.0

671/494

5,000

FXAQ50MAVE

5.8

19,800

7.15.6

6.4 9.5

12.7 15.9

0.022 0.027 0.020 0.027 0.0500.016

MODELPower supply

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Dimensions (HXWXD) mm

Machine weight kg

dB(A)Sound level (H/L)

Pipingconnections

Drain

Liquid (Flare)

Gas (Flare) mm

Power consumption kW

Floor Standing Type/Concealed Floor Standing Type

FXLQ

FXNQ

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.•Equivalent piping length: 7.5 m•Level difference: 0 m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: (FXAQ-MA) Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.

(FXLQ-MA, FXNQ-MA) Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.During actual operation, these values are normally somewhat higher as a result of ambient conditions.

FXLQ20MAVE

2.3

7,800

2,000

FXLQ: Ivory white (5Y7.5/1)/FXNQ: Galvanised steel plate

Airflow rate (H/L)m3/min

cfm

7/6

247/212

600X1,000X222

25.0

6.4

12.7

21O.D.

2.2

FXLQ25MAVE

2.9

9,900

2,500

7/6

247/212

600X1,000X222

25.0

6.4

12.7

282/212 388/300 494/388 565/424

2.8

FXLQ32MAVE

3.7

12,600

3,200

8/6

600X1,140X222

30.0

6.4

12.7

3.6

FXLQ40MAVE

4.7

16,000

4,000

11/8.5

600X1,140X222

30.0

6.4

12.7

4.5

FXLQ50MAVE

5.8

19,800

5,000

14/11

600X1,420X222

36.0

6.4

12.7

5.6

FXLQ63MAVE

FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE

7.3

24,900

6,300

16/12

600X1,420X222

610X930X220 610X930X220 610X1,070X220 610X1,070X220 610X1,350X220 610X1,350X220

36.0

19.0 19.0 23.0 23.0 27.0 27.0

9.5

15.9

7.1

35/32 35/32 35/32 38/33 39/34 40/35

37/34 37/34 37/34 40/35 41/36 42/37

1-phase, 220-240 V/220 V, 50/60 Hz

Sound level (H/L) dB(A)220 V

240 V

0.049 0.049 0.090 0.090 0.110 0.110

Casing

kWPower consumption

MODEL

Power supply

Cooling capacity

kW(*1)

(*2)

Btu/h(*1)

kcal/h(*1)

Dimensions (HXWXD)

Machine weight

mmFXLQ

FXNQ

kgFXLQ

FXNQ

Pipingconnections

Drain

Liquid (Flare)

Gas (Flare) mm

Specifications

VRV Indoor Units

Page 31: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

30

Ceiling Suspended Cassette Type

Connection unit series indoor units

* A type of BEV unit is necessary for each Connection unit series indoor unit. Refer to the Engineering Data for details.* Group control between Connection Unit series equipment within one system is possible. However, group control with the other

VRV indoor units is not possible.

cfm

kW(*1)

(*2)

Kcal/h(*1)

Power supply

8.3

7,100

1-phase, 220-240 V, 50 Hz

Btu/h(*1) 28,300

Ind

oo

r u

nit Airflow rate (H/L)

Casing

mmDimensions (HXWXD)

kgMachine weight

Piping connections

Liquid

Gas

Drain VP 20 (External Dia. 26/Internal Dia. 20)

25

White (10Y9/0.5)

671/494

165X895X895

9.5 (Flare)

15.9 (Flare)

11.6

10,000

39,600

31

1,024/741

230X895X895

14.5

8.0 11.2 14.0

12,500

49,500

Sound level (H/L) dB(A) 40/35 43/38 44/39

31

1,130/812

230X895X895

mm

Cooling capacity

MODELIndoor unit

Connection unit BEVQ71MAVE

FXUQ71MAV1

BEVQ100MAVE

FXUQ100MAV1

BEVQ125MAVE

FXUQ125MAV1

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.•Equivalent piping length: 7.5 m •Level difference: 0 m•Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. (See Engineering Data Book for details.)•Sound level: Anechoic chamber conversion value, measured at a point 1.5 m below the unit centre. During actual operation, these values are normally somewhat higher as a result of ambient conditions.

kWPower consumption 0.189 0.298 0.298

m3/min 19/14 29/21 32/23

230 V

Page 32: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

31

Ceiling Mounted Cassette (Compact Multi Flow) Type

1-phase, 220-240 V/220 V, 50/60 Hz

2 steps

FCQ71BVE

35/30

19.0 (671)

ø9.5

ø15.9

FCQ60BVEFCQ50BVE

15.0 (530)

ø12.7

FCQ35BVE

33/29

14.0 (494)

ø6.4

ø9.5

MODELPower supply

Both liquid and gas pipesHeat insulation

Fan speed

Microcomputer control

I.D ø25XO.D ø32

230X840X840

Temperature control

Airflow rates (H)

Sound levels (H/L)* dB (A)

m3/min (cfm)

Dimensions (HXWXD) mm

24Machine weight kg

40X950X950

BYC125K-W1

White

mm

5kg

Pipingconnections

Panel(Option)

Drain

Liquid (Flare)

Model

Colour

Dimensions (HXWXD)

Weight

Gas (Flare) mm

Note: * For 220 V operation.

600 x 600

Ceiling Mounted Cassette Type

1-phase, 220-240 V, 50 Hz

2 steps

FFQ60BV1B

41/32

15.0 (530)

ø12.7

FFQ50BV1BFFQ35BV1B

10.0 (353)

FFQ25BV1B

9.0 (318)

ø6.4

ø9.5

MODELPower supply

Both liquid and gas pipesHeat insulation

Fan speed

Microcomputer control

VP20 (External Dia. 26/Internal Dia. 20)

286X575X575

Temperature control

Airflow rates (H)

Sound levels (H/L)* dB (A)

m3/min (cfm)

Dimensions (HXWXD) mm

17.5Machine weight kg

55X700X700

BYFQ60B8W1

White

mm

2.7kg

Pipingconnections

Panel(Option)

Drain

Liquid (Flare)

Model

Colour

Dimensions (HXWXD)

Weight

Gas (Flare) mm

36/2732/2529.5/24.5

12.0 (424)

Note: * Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

Specifications

Residential Indoor Units with connectionto BP units

Residential indoor units with connection to BP unitsResidential indoor units can be connected to the VRVIII single outdoor unit series by BP units.

Page 33: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

32

1-phase, 220-240 V, 50 Hz

2 steps

41/35

FBQ71BV1

19.0 (670)

FBQ60BV1

17.0 (600)

ø9.5ø6.4

ø15.9ø12.7

MODELPower supply

Both liquid and gas pipesHeat insulation

Fan speed

Microcomputer control

I.D ø25XO.D ø32

300X1,000X800

Temperature control

Airflow rates (H)

Sound levels (H/L)* dB (A)

m3/min (cfm)

Dimensions (HXWXD) mm

41Machine weight kg

55X1,100X500

BYBS71DJW1

White

mm

4.5kg

Pipingconnections

Panel(Option)

Drain

Liquid (Flare)

Model

Colour

Dimensions (HXWXD)

Weight

Gas (Flare) mm

Note: * For 220 V operation.

Ceiling Mounted Built-in Type

Slim Ceiling Mounted Duct Type

1-phase, 220-240 V/220 V, 50/60 Hz

5 steps, quiet and automatic

FDKS25EAVMB

8.7 (307)

ø6.4

MODELPower supply

Both liquid and gas pipesHeat insulation

Fan speed

Microcomputer control

VP20 (External Dia. 26/Internal Dia. 20)

Temperature control

Airflow rates (H)

Sound levels (H/L/SL)* dB (A)

m3/min (cfm)

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Liquid (Flare)

Gas (Flare) mm

Note: * The operation sound level values represent those for rear-suction operation and an external static pressure of 30 Pa for FDKS-EA and 40 Pa for FDKS-C. Sound level values for bottom-suction operation can be obtained by adding 6 dB (A) for FDKS-EA and 5 dB (A) for FDKS-C.

35/31/29

FDKS35EAVMB FDKS25CAVMB

9.5 (335)

FDKS35CAVMB

10.0 (353)

FDKS50CVMB

12.0 (424)

37/33/31

FDKS60CVMB

16.0 (565)

21 25 27 30

200X700X620 200X900X620 200X1,100X620

External static pressure Pa 30 40

38/34/32

ø9.5 ø12.7 ø15.9

1-phase, 220-240 V/220 V, 50/60 Hz

FTKS71FVMFTKS60FVMFTKS35DVMFTKS25DVMMODELPower supply

WhiteFront panel colour

5 steps, quiet and automatic

46/37/34

17.4 (614)

ø15.9

8.9 (314)

ø12.7

37/25/22 39/26/23

8.7 (307)

ø6.4

ø9.5

Both liquid and gas pipesHeat insulation

Fan speed

Microcomputer control

ø18.0

283X800X195

Temperature control

Airflow rates (H)

Sound levels (H/L/SL) dB (A)

m3/min (cfm)

Dimensions (HXWXD) mm

Machine weight kg

Pipingconnections

Drain

Liquid (Flare)

Gas (Flare) mm

Wall Mounted Type

45/36/33

16.2 (572)

FTKS50FVM

43/34/31

14.7 (519)

290X1,050X238

9 12

Page 34: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

33

1-phase, 220-240 V/220 V, 50/60 Hz

BPMKS967B2BBPMKS967B3BMODELPower supply

3 (connectable to 1-3 indoor units) 2 (connectable to 1-2 indoor units)Number of ports

0.05

3 for power supply (including earth wiring), 2 for interunit wiring (outdoor unit-BP, BP-BP), 4 for interunit wiring (BP-indoor unit)Number of wiring connections

ø9.5X1

ø19.1X1

Liquid

Gas

mm

mm

mm

mm

Pipingconnections(Brazing)

Both liquid and gas pipesHeat insulation

2.5 kW class to 7.1 kW class residential indoor unitsConnectable indoor units

Running current A

2.5Min. rated capacity of connectable indoor units kW

180X294 (+356*)X350Dimensions (HXWXD) mm

8Machine weight kg

10Power consumption W

Note: * Total auxiliary piping length.

7.5

Max. rated capacity of connectable indoor units kW 20.8 14.2

ø6.4X3 ø6.4X2

ø15.9X3 ø15.9X2

Main

Branch

Main

Branch

Specifications

BP units for connection to residential indoor units• A BP unit is an innovative development which allows VRVIII single outdoor unit series to be connected to residential indoor units.

• A BP unit has the ability to precisely vary refrigerant volume to meet the cooling requirements of individual room spaces.

• A BP unit is easy to disassemble, making repairing and recycling simple.

for connection toresidential indoor unitsBP Units

Page 35: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

34

Specifications—Indoor Units

•Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m.

During actual operation, these values are normally somewhat higher as a result of ambient conditions.

Note: Specifications are based on the following conditions;•Cooling: (*1) Indoor temp. of 27°CDB, 19.5°CWB, and outdoor temp. of 35°CDB. (*2) Indoor temp. of 27°CDB, 19°CWB, and outdoor temp. of 35°CDB.•Equivalent piping length: 7.5 m•Level difference: 0 m

RSXQ8PY1 RSXQ18PY1

MODEL

22.5

76,800

19,400

22.4

3-phase 4-wire system, 380–415 V, 50 Hz

49.3

168,000

42,400

49.0

R-410A

3.6X1

188

57

1,680X930X765

180

20-100

Hermetically sealed scroll type

Ivory white (5Y7.5/1)

4.7

9.5 (Brazing)

19.1 (Brazing)

324

63

239

9-100

6.7

15.9 (Brazing)

28.6 (Brazing)

(2.8+4.5+4.5)X1

5.24

RSXQ10PY1

28.2

96,200

24,300

28.0

(1.4+4.5)X1

4.9

232

58

185

14-100

9.5 (Brazing)

22.2 (Brazing)

7.90

RSXQ12PY1

33.7

115,000

29,000

33.5

268

60

233

14-100

6.0

12.7 (Brazing)

28.6 (Brazing)

(1.8+4.5)X1

1,680X1,240X765

8.93

RSXQ14PY1

40.2

137,000

34,600

40.0

(1.4+4.5+4.5)X1

312

60

233

10-100

6.3

12.7 (Brazing)

28.6 (Brazing)

12.4

RSXQ16PY1

45.3

155,000

39,000

45.0

312

60

233

10-100

6.5

12.7 (Brazing)

28.6 (Brazing)

(2.7+4.5+4.5)X1

14.2 16.4

Cooling capacity (*1)(*2) Btu/h(*1)

(*1)kW

(*2)

Power supply

kcal/h(*1)

Refrigerant

Machine weight kg

dB(A)

Dimensions (HXWXD) mm

m3/min

Capacity control

Compressor

Sound level

–5 to 43°CDBOperation range

%

Airflow rate

Casing colour

Pipingconnections

Motor output kW

Type

Charge kg

Type

Liquid

Gasmm

Power consumption (*2) kW

single outdoor unit series

SpecificationsOutdoor Units

Outdoor unit combinations

Maximum number ofconnectable indoor units

Total capacity index of connectable indoor units*

Combination (%)*

50% 100% 130%

kW

260

325

390

455

520

200

250

300

350

400

100

125

150

175

200

22.4

28.0

33.5

40.0

45.0

13

16

19

22

26

Capacityindex

200

250

300

350

400

58545022549.0

HP

8 HP

10 HP

12 HP

14 HP

16 HP

18 HP 29450

* Total capacity index of connectable indoor units must be 50%–130% of the capacity index of the outdoor unit.

Model name

RSXQ8PY1

RSXQ10PY1

RSXQ12PY1

RSXQ14PY1

RSXQ16PY1

RSXQ18PY1

Combination ratio =Total capacity index of the indoor units

Capacity index of the outdoor unit

Page 36: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

35

Ceiling Mounted Cassette (Round Flow) Type

Ceiling Mounted Cassette (Double Flow) Type

No.

1

2

Decoration panelHigh efficiency filter 65% 1

High efficiency filter 90% 1

Long life replacement filter

Filter related bottom suction

FXCQ20MFXCQ25MFXCQ32M

FXCQ40M FXCQ50M FXCQ63M FXCQ80M FXCQ125M

KAFJ532G36 KAFJ532G56 KAFJ532G160KAFJ532G80KAFJ533G36 KAFJ533G56 KAFJ533G160KAFJ533G80KDDFJ53G36Filter chamber KDDFJ53G56 KDDFJ53G160KDDFJ53G80KAFJ531G36 KAFJ531G56 KAFJ531G160KAFJ531G80

Type

ItemBYBC32G-W1 BYBC50G-W1 BYBC125G-W1BYBC63G-W1

Note: 1 Filter chamber is required if installing high efficiency filter.

No. FXDQ25PB FXDQ32PBFXDQ20PB

1 KDT25N32Insulation kit for high humidity

Slim Ceiling Mounted Duct Type (700 mm width type)Type

Item

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)No.

1 KDT25N50 KDT25N63Insulation kit for high humidity

TypeItem FXDQ63NBFXDQ50NBFXDQ40NB

Ceiling Mounted Cassette Corner TypeNo.

TypeItem FXKQ25MA FXKQ32MA FXKQ40MA FXKQ63MA

1

2

BYK45FJW1 BYK71FJW1KPBJ52F56W KPBJ52F80WKAFJ521F56 KAFJ521F80

K-HV7AW K-HV9AWKDBJ52F56W KDBJ52F80WKFDJ52FA56 KFDJ52FA80

Panel related

Air inlet and air discharge outlet related

Decoration panelPanel spacerLong life replacement filterAir discharge grilleAir discharge blind panelFlexible duct (with shutter)

Ceiling Mounted Cassette (Compact Multi Flow) Type

FXFQ25P FXFQ32P FXFQ40P FXFQ50P FXFQ63P FXFQ80P FXFQ100P FXFQ125P1

4

BYCP125K-W1

KAFP556B80 KAFP556B160KAFP557B80 KAFP557B160KAFP552B80 KAFP552B160KAFP553B80 KAFP553B160

KDTP55K160

KDJP55B160

Filter related

5 Fresh air intake kit

Decoration panel2 KDBH55K160FSealing member of air discharge outlet3 KDBP55H160FAPanel spacer

High efficiency filter unit 65%High efficiency filter unit 90%Replacement high efficiency filter 65%Replacement high efficiency filter 90%Filter chamberLong life replacement filter Non-woven type

Chamber typeWithout T shape and fanWith T shape without fan

KDDFP55B160

Ultra long-life filterReplacement ultra long-life filter

Direct installation type

KAFP551K160KAFP55B160

KAFP55H160HKDDP55B160

KDDP55B160KKDDP55X160

No. Type

Item

6 KDJP55B80Branch duct chamber7 KKSJ55KA160Chamber connection kit8 KDTP55K80Insulation kit for high humidity

No.

FXZQ20M FXZQ25M FXZQ32M FXZQ40M FXZQ50M1 Decoration panel2 Sealing member of air discharge outlet3 Panel spacer4 Replacement long-life filter

BYFQ60B8W1KDBH44BA60

KDBQ44BA60AKAFQ441BA60

5 Fresh air intake kit Direct installation type KDDQ44XA60

TypeItem

Option List

VRV Indoor Units

Page 37: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

36

Ceiling Suspended Type

Wall Mounted TypeFXAQ25MAFXAQ20MA

1 Drain pump kit K-KDU572EVE

FXAQ32MA FXAQ40MA FXAQ50MA FXAQ63MANo. Type

Item

Floor Standing TypeFXLQ20MA

1 Long life replacement filter

FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA

KAFJ361K28 KAFJ361K45 KAFJ361K71

No. TypeItem

Concealed Floor Standing TypeFXNQ20MA

1 Long life replacement filter

FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA

KAFJ361K28 KAFJ361K45 KAFJ361K71

No. TypeItem

Ceiling Suspended Cassette Type

Ceiling Mounted Duct TypeNo. FXMQ40P

FXMQ50PFXMQ63PFXMQ80P

FXMQ20PFXMQ25PFXMQ32P

FXMQ100PFXMQ125PFXMQ140P

FXMQ200MAFXMQ250MA

KDU30L250VE—

KAFJ372L280KAF372AA80 KAF372AA160

KAFJ373L280KAF373AA80 KAF373AA160

KDJ3705L280KDDF37AA80 KDDF37AA160

KAFJ371L280KAF371AA80 KAF371AA160

KAF375AA80

KAF372AA56

KAF373AA56

KDDF37AA56

KAF371AA56

KAF375AA56

KAF372AA36

KAF373AA36

KDDF37AA36

KAF371AA36

KAF375AA36 KAF375AA160

KTB25KA80W KTB25KA160W

KTBJ25K80F KTBJ25K160F

KTBJ25K80T

KTB25KA56W

KTBJ25K56F

KTBJ25K56T

KTBJ25K36W

KTBJ25K36F

KTBJ25K36T KTBJ25K160T

KDAJ25K71AKDAJ25K56AKDAJ25K36A KDAJ25K140A

Item1 Drain pump kit

3 Filter chamber

2 High efficiency filter65%

90%

4 Long life replacement filter

5 Long life filter chamber kit

6 Service panel

White

Fresh white

Brown

7 Air discharge adaptor

Type

FXHQ32MA

1 Drain pump kit

2 Replacement long-life filter (Resin net)

KDU50N60VE

KAF501DA56

3 L-type piping kit (for upward direction) KHFP5MA63

FXHQ63MA

KDU50N125VE

KAF501DA80

KHFP5MA160

FXHQ100MA

KAF501DA112

No. Type

Item

No.

Replacement long-life filter12345

Sealing member of air discharge outlet (*1)

Decoration panel for air dischargeVertical flap kitL-shape piping kit

FXUQ71MA

KDBH49FA80KDBT49FA80KDGJ49FA80

KHFP49MA140

KDBH49FA140KDBT49FA140KDGJ49FA140

FXUQ100MA FXUQ125MA

KAF495FA140

(*1): This option is necessary for setting up 2-way (opposing directional) airflow when the air conditioner is installed.Note:

TypeItem

Page 38: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

37

Ceiling Mounted Cassette TypeFCQ35BVE FCQ50BVE FCQ60BVE FCQ71BVE

1

4

BYC125K-W1

High-efficiency filter

Decoration panel2 KDBP55H160WAPanel spacer

3KDDP55D160

KDDP55D160KKDDJ55X160KAFP556D80KAFP557D80

Fresh air intake kitDirect installation type*3

(Colourimetric method 65%) (Colourimetric method 90%)

5Replacement high-efficiency filter

(Colourimetric method 65%) (Colourimetric method 90%)

Chambertype

Without T-shaped pipe and fan*1

With T-shaped pipe, without fan*2

KAFP552H80 KAFP553H80

KDDF55DA160KAF551KA160

KDJ55K80

No. Type

Item

6 High-efficiency filter chamber7 Replacement long-life filter 8 Branch duct chamber

Notes: *1. With a suction chamber. Fresh air intake is from 2 holes on the sides of the connection chamber. (This method should be selected if a wireless remote controller is used.)*2. Without a suction chamber. Fresh air intake is from 2 holes on the connection chamber via a T-shaped pipe connection. (A wireless remote controller cannot be used in this case.)*3. Without a suction chamber. Fresh air intake is directly from a hole on the main unit.

Ceiling Mounted Cassette (Compact Multi Flow) TypeFFQ25BV1B FFQ35BV1B FFQ50BV1B FFQ60BV1B

1 BYFQ60B8W1Decoration panel

No. Type

Item

KAFQ441BA602 Replacement long-life filterKDDQ44XA603 Fresh air intake kitKDBH44BA604 Sealing member for air discharge outlet

KDBQ44BA60A5 Panel spacer

FDKS35EAVMBFDKS25EAVMB

1 Suction grille KDGF19A45

2 Insulation kit for high humidity KDT25N32

FDKS25CAVMB FDKS35CAVMB FDKS50CVMB FDKS60CVMBNo. Type

Item

Slim Ceiling Mounted Duct Type

Direct installation type

Ceiling Mounted Built-in TypeFBQ60BV1 FBQ71BV1

1 BYBS71DJW1Decoration panel2 KTBJ25L80WService access panel

4 KAFJ251K80Replacement long-life filter Resin netKAF253LA80KAF252LA80

KAJ25LA80DKAJ25LA80B

No. Type

Item

5 Filter chamber for bottom suction 6 Filter chamber for rear suction

KSAJ25K807 Canvas duct

KDJ2507K8014 Flange for suction

KBBJ25KA8012 Blind boardKDAJ25K7113 Adaptor for discharge

3 High-efficiency filter(Colourimetric method 65%)(Colourimetric method 90%)

K-DG9DWK-DG5DW

8 Discharge grilleø150ø200

K-DDV20A10 Branch duct ø150 ø200

K-FDS201C(1m)/K-FDS202C(2m)/K-FDS203C(3m)/K-FDS204C(4m)/K-FDS205C(5m)/K-FDS206C(6m)K-FDS151C(1m)/K-FDS152C(2m)/K-FDS153C(3m)/K-FDS154C(4m)/K-FDS155C(5m)/K-FDS156C(6m)

11 Flexible ductø150ø200

K-DGC9DK-DGC5D

9 Discharge chamberø150ø200

KDT25N50 KDT25N63

Option ListResidential Indoor Units with connection

to BP units

Page 39: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

38

BPMKS967B2B

1 REFNET joint KHRP26A22T

BPMKS967B3BNo. Type

Item

FTKS35DVMFTKS25DVM

1 Titanium apatite photocatalytic air-purifying filter KAF970A46

FTKS50FVM FTKS60FVM FTKS71FVMNo. Type

Item

Wall Mounted Type

KAF952B42

REFNET headerDistributive piping

RSXQ8PY1 RSXQ10PY1 RSXQ12PY1

Auxiliary pipe set*1 KHFP22B16P

RSXQ14PY1 RSXQ16PY1 RSXQ18PY1

KHRP26M22H (Max. 4 branch)KHRP26M33H (Max. 8 branch)KHRP26M72H (Max. 8 branch)

KHRP26M22H (Max. 4 branch)KHRP26M33H (Max. 8 branch)

REFNET jointKHRP26A22TKHRP26A33TKHRP26A72T

KHRP26A22TKHRP26A33T

Type

Item

KHFP22B8P KHFP22B10P KHFP22B12P KHFP22B18P

Central drain pan kit KWC26C280 KWC26C450

Digital pressure gauge kit BHGP26A1

Specifications—Indoor UnitsOutdoor Units

for connection toresidential indoor unitsBP Units

Note: Filter is a standard accessory. It should be replaced approximately 3 years.

Note: A single BP unit does not require a REFNET joint. 2 BP units require only 1 REFNET joint, and 3 BP units require only 2 REFNET joints.

Note: *1. Auxiliary pipe sets are not attached to the outdoor units. If neccesary, use the optional accessories.

Page 40: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

39

Control Systems

Individual Control Systems for VRV Indoor Units

Large buttons and arrow keys for easy operation.

Guide on display gives an explanation of each setting.

Backlight and dot matrix LCD display for easy viewing.

Weekly schedule timer can be set up easily.

10 display languages are available.(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian and Turkish)

Wired remote controller (Option)

BRC1C62

BRC1E61

Displays current airflow, swing, temperature, operating mode and timer settings.

Outdoor unit

Indoor unit

Forced OFF input

Remote controllerRemote controller

Remote controllerRemote controller

Remote controllerRemote controller

Remote controller

Remote controller

Heat Reclaim Ventilator

The indoor unit can be connected by the two remote controller, for example one in the room and the other one in the control room, which can control the operation of indoor unit freely.(The last command has a priority.) Of course, the group control by two remote controller is also possible.

Control by two remote controller

The system can be expanded to add several controllers, such as BMS, Forced OFF input and etc.

Expansion of system control

One remote controller can control the operation of max.16 indoor units at the same time.

Group control

Equipment related to the central control

1 2 3

The wiring of remote controller can be extended to max. 500 m and it is possible to install the remote controllers for the different indoor units in one place.

Remote control

The operation of the Heat Reclaim Ventilator can be controlled by the remote controller of the indoor unit. Of course, the remote controller can display the time to clean the filter.

Control for the combined operation

44

3

2

1

Wide variation of remote controllers for indoor unitsThe wired remote controller supports a wide range of control functions

Navigation remote controller (Wired remote controller) (Option)

Wired remote controllerwith weekly schedule timer (Option)

BRC1D61

Adds weekly schedule timer function.

Notes: 1. Standard remote controllers (BRC1C62) not required.2. If the BRC1D61 is connected to the centralised remote controllers

(DCS303A51, DCS302CA61, DCS301BA61, DST301BA61), the schedule function is not available.

Page 41: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

40

Wireless remote controller (Option)

Wired remote controller(BRC1C62)

Wired remote controller with weekly schedule timer

(BRC1D61)

Wireless remote controller*(Installed type signal receiver unit)

Wireless remote controller*(Separate type signal receiver unit)

Simplified remote controller(Exposed type)

(BRC2C51)

Simplified remote controller(Concealed type: for Hotel use)

(BRC3A61)

FXFQ FXZQ FXCQ FXDQ FXMQ FXHQ FXAQ FXL(N)QFXKQ

Wide variation of remote controllers for indoor unitsWide variation of remote controllers for VRV indoor units

*Refer to page 43 for the name of each model.

FXUQ

Signal receiver unit(Separate type)

Wireless remote controller

*Wireless remote controller and signal receiver unit are sold as a set. *Refer to page 43 for the name of each model.

Signal receiver unit(Installed type)

Signal receiver unit can be installed on the panel ex. Ceiling Mounted Cassette (Round Flow) type

The same operation modes and settings as with wired remote controllers are possible.

A compact signal receiver unit (separate type) to be mounted into a wall or ceiling is included.

• A signal receiver unit (installed type) for a Ceiling Mounted Cassette (Round Flow, Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted type is mounted into the indoor unit.

The remote controller has centralised its frequently used operation selectors and switches (on/off, operation mode, temperature setting and airflow volume), making itself suitable for use in hotel rooms or conference rooms.

The exposed type remote controller is fitted with a thermostat sensor.

The concealed type remote controller smartly fits into a night table or console panel in a hotel room.

Exposed type(BRC2C51)

Concealed type(For hotel use)

(BRC3A61)

Simplified remote controller (Option)

Navigation remote controller(Wired remote controller)

(BRC1E61)

Page 42: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Control Systems

41

Up to 64 groups of indoor units (128 units) can be centrally controlled.

Optional controllers for centralised control can be combined freely, and

system can be designed in accordance with building scale and purpose.

System integration with various air-conditioning peripheral

equipment, such as a Heat Reclaim Ventilator, is easy.

Wiring can be run up to a total length of 2 km, and adapts easily to

large-scale system expansion.

Centralised Control Systems for VRV Indoor Units

Central control adaptor kit (DTA107A55)

Central remote controller(DCS302CA61)

Up to 2 units connectable

Unified on/off controller(DCS301BA61)

Connection of up to 8 unitspossible

Schedule timer (DST301BA61)1 unit connection possible ; 8 weekly schedule control patterns possible

Forced shut-down input

Independent and centralised control of a Heat Reclaim Ventilator is possible.

Unification adaptor for computerised control (DCS302A52)

Interlink Building Management System (host computer monitor panel) also possible

6 cores 7 cores max.

Address setting of central control can be performed from the remote controller.

Group control of up to 16 units is possible (group control via automatic address setting)

System without remote control is also available.

Interface adaptor for SkyAir series (built-in indoor unit) (DTA102A52)

Connectable number of centralised control equipment

Central remotecontroller 2 units

Unified on /offcontroller 8 units

Schedule timer 1 unit

Wiring adaptorfor other air-conditioners (DTA103A51)

For more details, please refer to the Engineering Data Book.

Outdoor-air processing unit can be connected.

• Certain indoor units limit the functions of some control systems.

Input (Lights)

Input (Key signal -General purpose ADP)

Dio UnitDEC102A51(Option)

Di UnitDEC101A51(Option)

System

Set temperature change command

OFFcommand

Pi Port

• Connection to power consumption metre when using power proportional distribution function. (Option)

RS-232C

Air Conditioning NetworkService System modemfor connections

• CSV output of power proportional distribution results (Option)

PCMCIAFlash

Memory

Remote monitor-ing and control

Mobile Phone PCD -NET Plus AdaptorDCS601A52 (Option)

Number of indoor units expanded from 64 to 128.

D -NET

Function 1

Function 2Function 3

Function 4

Function 5

Function 6

Indoor UnitHeat Reclaim Ventilator

ACC centre• Air Conditioning Network Service System (Optional Maintenance Service)

System Components

Via internet

DCS601C51

Malfunction reportby E-mail

Advanced Control Systems for VRV Indoor Units

Page 43: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

42

Max. 16 groups of indoor units can be easily controlled with the large LCD panel.• Max. 16 groups (128 indoor units) controllable• Backlight and large LCD panel for easy readability• ON/OFF, temperature settings and scheduling can

be controlled individually for indoor units.

• Max. 16 groups (128 indoor units) controllable• 2 remote controllers can be used to control from 2

different places.• Operating status indication (Normal operation, Alarm)• Centralised control indication

• Max. 128 indoor units controllable• When used in combination with a central remote

controller, a maximum of 8 weekly schedule patterns can be set, while the central controller can be used to select desired zones. Up to 2 ON/OFF pairs can be set per day.

DCS303A51

DCS301BA61

DST301BA61

• Max. 64 groups (128 indoor units) controllable• Max. 128 groups (128 indoor units) are controllable by

using 2 central remote controllers, which can control from 2 different places.

• Zone control• Malfunction code display• Max. wiring length 1,000 m (Total: 2,000 m)• Connectable with Unified ON/OFF controller, schedule

timer and BMS system

DCS302CA61

* For residential use only. Cannot be used with other centralised control equipment.

Max. 128 indoor units can be operated as programmed schedule.

Schedule timer (Option)

Max. 16 groups of indoor units can be operated simultaneously/individually.

Unified ON/OFF controller (Option)

Max. 64 groups (zones) of indoor units can be controlled individually same as LCD Remote controller.

Central remote controller (Option)

Residential central remote controller* (Option)

• Max. 48 hours back up power supply• Max. wiring length 1,000 m (Total: 2,000 m)• Compact size casing (Thickness: 16 mm)• Connectable with Central Remote controller,

Unified ON/OFF controller and BMS system

• Max. wiring length 1,000 m (Total: 2,000 m)• Compact size casing (Thickness: 16 mm)• Connectable with Central Remote controller, • Schedule timer and BMS system

• Airflow volume and direction can be controlled individually for indoor units in each group operation.

• Ventilation volume and mode can be controlled for the Heat Reclaim Ventilator.

• Up to 4 ON/OFF pairs can be set per day by connecting a schedule timer.

• All indoor units can be turned on or off at once with “ALL” button.

• Each group has a dedicated button for convenience.• Outside temperature display

Support for centralised control from elsewhere using a PC with a Web browser (Option)Function 1

Sending of e-mail alerts to a specified address when malfunctions occur (Option)

Function 2

Built-in modem for connecting to Air Conditioning Network Service System (Option)

Function 3

Function 4

Management of facilities/equipment other than A/C units (By adding Dio unit or Di unit)

Function 5

Simple Interlock FunctionFunction 6

Doubling of number of connectable indoor units by adding a D -NET Plus Adaptor (Option)

• Colour LCD touch panel icon display• Small manageable size • Simplified engineering• Multi language (English, French, Italian, German, Spanish, Dutch,

Portuguese, Chinese and Korean)• Yearly schedule• PPD (Power Proportional Distribution function) (Option)• Auto heat/cool change-over• Temperature limitation• Enhanced history function • Air Conditioning Network Service System (Optional Maintenance Service)• Simple Interlock Function

Communication functions in the user-friendly icon-based multilingual controller simplify centralised control of the VRV system.

Page 44: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

—— — DTA114A61 DTA114A61 DTA114A61

43

Operation Control System Optional Accessories

For VRV indoor unit use

For Residential indoor unit use

No. FXFQ-P FXCQ-M FXKQ-MA FXDQ-PBFXDQ-NB FXAQ-MA FXLQ-MA

FXNQ-MA

Remote controller

Type

Item

No. Type

Item

BRC7F635F BRC7C67 BRC4C63 BRC7EA619 BRC4C64BRC4C66

FXMQ-P

BRC4C66

FXUQ-MA

BRC7CA529W

FXHQ-MA

BRC7EA66

FXMQ-MA

BRC4C64

FXZQ-M

BRC7E531W1

BRC1C62

Wired remote controller with weekly schedule timer BRC1D613

Navigation remote controller (Wired remote controller) BRC1E612

Notes: 1. Installation box is necessary for each adaptor marked .2. Up to 2 adaptors can be fixed for each installation box.

4

5

Simplified remote controller (Exposed type)

6 Adaptor for wiring

7-1 Wiring adaptor for electrical appendices (1)

7-2 Wiring adaptor for electrical appendices (2)

Remote controller for hotel use (Concealed type)

8 Remote sensor (for indoor temperature)

10 External control adaptor for outdoor unit

— —

BRC3A61

BRC2C51

9 Installation box for adaptor PCB

BRC2C51

BRC3A61 —

5. Installation box is necessary for second adaptor.6. Installation box is necessary for each adaptor.

3. Only one installation box can be installed for each indoor unit.4. Up to 2 installation boxes can be installed for each indoor unit.

KRP1B61

DTA104A61

KRCS01-1B KRCS01-1B

KRP1C63

KRP2A61 KRP2A62

KRP4AA51 KRP4AA53

KRP2A61

KRP1B61

DTA104A62

Notes 2, 3KRP1B96

DTA104A62

Notes 4, 6KRP1BA101 —Note 3

KRP1CA93Notes 2, 3 KRP4AA93

Notes 2, 3KRP1H98

KRP1C64

KRP2A61 KRP2A61

KRP4AA51 KRP4AA51

KRP2A62 KRP2A61

KRP4AA52 KRP4AA51 KRP4AA51

Notes 2, 3KRP4A96— Notes 4, 6

KRP1BA101

DTA104A61

KRP2A62

KRP1BA97

KRP4AA53

—DTA104A53DTA104A61 DTA104A61 DTA104A62 DTA104A61 DTA104A61

KRP1BA57

KRP2A62

KRP4AA53

—KRP1BA54

KRP1B61KRP1B56

KRP2A53

KRP4A54

KRP1B61

KRP2A61

KRP4AA51

KRCS01-4B KRCS01-4B

11 Adaptor for multi tenant

Wired type

Wireless type

Option List

Control Systems

Note 3

KRP4AA53

KRP1B98

1 Remote controllerWired typeNote 1

Wireless type

BRC1C61

— Note 2

——

BRC7C613WNote 3

KRP1BA57

KRP1BA54

3 Wiring adaptor for electrical appendices

4 Installation box for adaptor PCB

Notes: 1. Wiring for wired remote controller should be obtained locally.2. A wireless remote controller is a standard accessory for FDKS and FTKS models.3. Installation box for adaptor PCB (KRP1B98) is necessary.4. Installation box for adaptor PCB (KRP1BA101) is necessary.5. Time clock and other devices should be obtained locally.

2Note 4

KRP1BA57Adaptor for wiring

BRC7E531W

Note 4

KRP4AA53 KRP4AA51

KRP1BA101KRCS01-1B5 Remote sensor (for indoor temperature)

FCQ-B FFQ-B FBQ-B FDKS-EAFDKS-C(A)

FTKS-DFTKS-F

7 Remote controller loss prevention chain KKF917A4

6Wiring adaptor for time clock/remote controller Note 5

(Normal open pulse contact/normal open contact) KRP413AB1S

Page 45: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

44

System Configuration

•Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one system.

Note 2

DCS302CA61Central remote controller2

•Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF, temperature settings and scheduling can be controlled individually for indoor units.

Note 3

DCS303A51Residential central remote controller1

•Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.

Note 2

DCS301BA61Unified ON/OFF controller3

KJB212AAElectrical box with earth terminal (2 blocks)3-1

KEK26-1ANoise filter (for electromagnetic interface use only)3-2

KJB311AAElectrical box with earth terminal (3 blocks)2-1

DTA102A52Interface adaptor for SkyAir-series7

DTA107A558

DTA103A51Wiring adaptor for other air-conditioner9

No. Item Model No. Function

•Up to 1024 units can be centrally controlled in 64 different groups.

•Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16) apply to each adaptor.

DTA109A51D -NET

Expander Adaptor10

•Fixing plate for DTA109A51KRP4A92Mounting plate10-1

•Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET communication system adopted for the VRV System.

* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be controlled.

For UAT(Y)-K(A),FD-K

For SkyAir, FD(Y)M-FA, FDY-KAFDYB-KA, FVY(P)J-A, FXUQ-MA

Central control adaptor kit

Notes: 1. Installation box for adaptor must be obtained locally. 2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary. For residential indoor units, an interface adaptor (KRP928BB2S or DTA112BA51) is required for each indoor unit.3. For residential use only. Cannot be used with other centralised control equipment.4. A wiring adaptor (KRP413AB1S) is also required for each indoor unit.

•Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units (128 units). Can turn units ON/OFF twice per day.

Note 2

DST301BA61Schedule timer4

KRP928BB2S

5-room centralised controllerfor residential indoor units5

DTA112BA51

Interface adaptor for residentialindoor units6

Building Management System

•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through LONWORKS® communication.DMS504B514

3

•Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable independently.DAM411B513-1

•Enables ON/OFF command, operation and display of malfunction; can be used in combination with up to 4 units.DPF201A515

•Enables temperature measurement output for 4 groups; 0-5VDC.DPF201A526

•Enables temperature setting input for 16 groups; 0-5VDC.DPF201A537

No. Item Model No. Function

*2 Interface for use in LONWORKS®

•Interface unit to allow communications between VRV and BMS. Operation and monitoring of air-conditioning systems through BACnet® communication.DMS502B51*1 Interface for use in BACnet®

Optional DIII board

Con

tact

/ana

logu

esi

gnal

Parallel interfaceBasic unit

Temperaturemeasurement units

Temperaturesetting units

•Air conditioner management system that can be controlled by personal computers.

DAM602B51

KJB411A

DAM602B52

256 units

DAM602B51x2512 units

DAM602B51x3768 units

DAM602B51x41024 unitsintelligent Manager III

128 units

2Number of units to be connected

HardwareBasic

•Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable independently.

•External temperature sensor for intelligent Manager III.

DAM412B51

DAM101A51

Optional Di board

Optional DIII Ai unit2-4

•8 pairs based on a pair of On/Off input and abnormality input.DEC101A51Di unit2-5

3-2

1-1

1-4

1

Electrical box with earth terminal (4 blocks)

DCS601A521-1 •Additional 64 groups (10 outdoor units) is possible.

DCS004A511-3 •Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.

•Wall embedded switch box.

DCS601C51 •Air-Conditioning management system that can be controlled by a compact all-in-one unit.

Com

mun

icat

ion

line

Notes: *1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).

*2. LONWORKS® is a trademark of Echelon Corporation registered in the United States and other countries. *3. Installation box for adaptor must be obtained locally.

DCS002C511-2

intelligent Touch

Controller

DIII-NET plus adaptor

Web

intelligent Touch Controller

PPD

Hardware

Hardware

Software

Basic

Option •PPD: Power Proportional Distribution function

•4 pairs based on a pair of On/Off input and abnormality input.DEC102A51Dio unit2-6

2-1

2-2

2-3

•Power Proportional Distribution functionDAM002A51

Option Software

2-1

•Monitors and controls the air conditioning system using the Internet and a Web browser application on a PC.DAM004A512-2

•ECONO (Energy saving functions.)DAM003A51

PPD

Web

ECONO2-3

•Interface between the central monitoring board and central control units.DCS302A528 Unification adaptor forcomputerised control

For FCQ-B, FFQ-B, FBQ-B

For FTKS-D/F, FDKS-EA/C(A)

•Up to 5 indoor units can be controlled. This is a low cost system which can only control ON/OFF.Note 4

KRC72For FTKS-D/F, FDKS-EA/C(A)

Page 46: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

Memo

Page 47: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world
Page 48: VRV indoor units combine with residential indoor units, all in ......VRV and residential indoor units First launched in Japan in 1982, the Daikin VRV system has been embraced by world

1. Air conditioners should not be installed in area s where corrosiv e gas es, suc h as acid gas or alkalin e gas, are produced.2. If the outdoor unit is to be installed close to the se a shore, direct exposure to the sea breeze should be avoide d. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Daiki n products are manufactured for export to numerous countries throughout the world. P rior to purchas e, please confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standar ds, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any loca l legis lation.

Ask a qualified installer or contractor to install this product. Do not try to install the product yourse lf. Improper installation can result in water or refrigera nt leakage, electrical shoc k, fire or explosion.

Us e only those parts and accessories supplied or specified by Da ikin. A sk a qualified installer or contractor to install those parts and accessorie s . Use of unauthorised parts and accessorie s or improper installation of parts and accessories ca n result in water or refrigera nt leakage, electrical shock, fire or explosion.

Rea d the User's Manua l carefully before using this product. The User's Manua l provides important safety instructions and warnings. B e sure to follow these instructions and warnings.

If you have any enquiries , pleas e contact your local importer, distributor and/or retailer.

JMI-0107 JQA-1452

Organization:DAIKIN INDUSTRIES, LTD.AIR CONDITIONING MANUFACTURING DIVISION

Scope of Registration:THE DESIGN/DEVELOPMENT AND MANUFACTURE OF COMMERCIAL AIR CONDITIONING, HEATING, COOLING, REFRIGERATING EQUIPMENT, HEATING EQUIPMENT, RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, COMPRESSORS AND VALVES.

Organization:DAIKIN INDUSTRIES(THAILAND) LTD.

Scope of Registration:THE DESIGN/DEVELOPMENTAND MANUFACTURE OF AIR CONDITIONERS AND THE COMPONENTS INCLUDING COMPRESSORS USED FOR THEM

All of the Daikin Group’s business facilities and subsidiaries in Japan

international standard for environment management.

All rights reservedPrinted in Vietnam 07/12/001 VK

HEAD OFFICE

HNÍHC GNØOHP NÊAV

IÄON ØAH HNÙAHN IHC

GNÜAN ØAÑ HNÙAHN IHC

MIK TÄEIV NÀAHP ÅOC YT GNÂOCUmeda Center Bldg., 2-4-12, Nakazaki-Nishi, Kita-ku, Osaka, 530-8323 Japan

MCH.PT ,3.Q ,4.P ,8 gnùahT gnïaM hcùaC 302-102 ,ÙA maN øahn aøot ,51-41 gnàaTTel: (08) 62 504 888 Fax: (08) 62 504 999

Tel: (04) 35 657 677 Fax: (04) 35 657 688

Tel: (0511) 362 4250 Fax: (0511) 362 4251

www.daik in .com.vn

iäoN øaH ,aÑ gnáoÑ näauQ ,hnA yuD oøaÑ 1 ,rewoT kraP naecO øahn aøot ,21 gnàaT

gnüaN øaÑ .PT ,uâahC iûaH .Q ,céaB gnøôöC aøoH .P ,4/03 gnøôöÑ ,1.2A âoL ,21 gnàaT

iáohp nâahp ùyl iïaÑ

Miễn phí cöôùc cuoäc goïi

TRUNG TÂMDICH VU KHÁCH HÀNG


Recommended