+ All Categories
Home > Documents > Electrical Equipment Room Design Considerations

Electrical Equipment Room Design Considerations

Date post: 10-Apr-2018
Category:
Upload: faganron
View: 224 times
Download: 0 times
Share this document with a friend

of 53

Transcript
  • 8/8/2019 Electrical Equipment Room Design Considerations

    1/53

    Electrical Equipment Room Design

    Considerations

    Atlanta Chapter IEEE Industry

    Applications Society

    presented at the

    Sheraton Buckhead Hotel

    Atlanta, Georgia

    November 20, 2006

  • 8/8/2019 Electrical Equipment Room Design Considerations

    2/53

    Outline

    1. Definitions2. Power Distribution Configurations

    3. Selection of Transformer

    4. Installation and Location of Transformer

    5. Service Entrance Equipment

    6. Selection of Circuit Breaker

    7. Electrical Equipment Room Construction (New)

    8. Electrical Equipment Room Construction

    (Existing)

    9. Maximum Impedance in a Ground Return Loop to

    Operate an Overcurrent Protective Device

    10. 2005 NEC Requirements

  • 8/8/2019 Electrical Equipment Room Design Considerations

    3/53

    Outline

    11. Ground Fault Sensing12. Zero Sequence Sensing vs. Residual Sequence

    Sensing

    13. Power Distribution Systems with Multiple Sources14. Modified Differential Ground Fault (MDGF)

    Protection Systems

    15. Designing a MDGF Protection System

    16. Reported Ground Fault Losses

  • 8/8/2019 Electrical Equipment Room Design Considerations

    4/53

    1. Definitions

    The system configuration of any PowerDistribution System is based strictly on howthe secondary windings of the Power Class

    Transformer, or generator, supplying theService Entrance Main or loads, areconfigured. (This includes whether or not

    the windings are referenced to earth.) The system configuration is not based on

    how any specific load or equipment is

    connected to a particular power distributionsystem.

    System Configuration

  • 8/8/2019 Electrical Equipment Room Design Considerations

    5/53

    1. Definitions

    A designed, coordinated, functional, and properly installedsystem that provides

    protection from electrical faults or short

    circuit conditions that result from any

    unintentional, electrically conducting

    connection between an ungroundedconductor of an electrical circuit and the

    normally noncurrent-carrying conductors,

    metallic enclosures, metallic raceways,metallic equipment, or earth.

    Ground Fault Protection System

  • 8/8/2019 Electrical Equipment Room Design Considerations

    6/53

    1. Definitions

    A system intended to provide protection ofequipment from damaging line-to-ground

    fault currents by operating to cause a

    disconnecting means to open all

    ungrounded conductors of the faulted

    circuit. This protection is provided at currentlevels less than those required to protect

    conductors from damage through the

    operation of a supply circuit overcurrentdevice.

    Ground Fault Protection of Equipment

    (Per Article 100 in the 2005 NEC)

  • 8/8/2019 Electrical Equipment Room Design Considerations

    7/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    8/53

    1. Definitions

    An unintentional, electrically conducting

    connection between an ungroundedconductor of an electrical circuit and the

    normally noncurrent-carrying conductors,

    metallic enclosures, metallic raceways,metallic equipment, or earth.

    Ground Fault

    (per Article 250-2 in the 2005 NEC)

  • 8/8/2019 Electrical Equipment Room Design Considerations

    9/53

    1. Definitions

    An electrically conductive path from

    the point of a ground fault on a wiringsystem through normally noncurrent-

    carrying conductors, equipment, or the

    earth to the electrical supply source.

    Ground Fault Current Path

    (per Article 250-2 in the 2005 NEC)

  • 8/8/2019 Electrical Equipment Room Design Considerations

    10/53

    2. Power Distribution Configurations

  • 8/8/2019 Electrical Equipment Room Design Considerations

    11/53

    3. The Selection of the Power Class

    Transformer to Install

    Dry Type Air/Dry

    Cast Resin

    Liquid Filled Mineral Oil (flammable, marketed or perceived biohazard)

    Silicone (non-flammable)

    Bio [Corn Oil] (flammable, but not a marketed orperceived bio hazard )

    Gas Type

  • 8/8/2019 Electrical Equipment Room Design Considerations

    12/53

    4. The Location and Installation of the

    Power Class Transformer

    Outdoors Enclosure Types Relative to Environment

    Accessibility

    Camouflage to Meet Local Requirements Hazardous Locations

    Protection for and from people

    Required Markings

    Security

    Indoors To Vault or Not To Vault

    Fire Ratings of Location

    Rating of NEMA Environment

    Environmental Considerations

    Cooling Ability

    Accessibility

    Security

  • 8/8/2019 Electrical Equipment Room Design Considerations

    13/53

    5. Service Entrance Equipment

    Switchboards (UL 891)

    The UL 891 Standard applies to switchboardsnominally rated at 600 V or less and intended for

    use in accordance with the Canadian ElectricalCode, Part 1 (CE Code, Part 1), the NationalElectrical Code (NEC), ANSI/NFPA 70, and theMexican Standard for Electrical Installations(Utility), NOM-001-SEDE.

    The term switchboard is intended to refer to adead-front switchboards only.

    Not associated with the following switchboardtypes:

    Preset and dimmer control (theater) Live front, railway control, or electrification

    Constructions intended only for receiving motorcontrol center units.

    Covers switchboards for use on circuits havingavailable rms symmetrical short-circuit currents ofnot more than 200 000 A.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    14/53

    5. Service Entrance Equipment

    Switchboards (UL 891) continued

    Traditionally have less bus clearances thanswitchgear.

    Bussing is rarely insulated (unless specified andpaid for).

    The spaces between all distribution circuitbreakers are not usually compartmentalized.

    Employs a greater use of barriers within a sectionversus compartments.

    There are barriers between sections.

    Circuit Breakers employed within a switchboardsection can be molded case, insulated case, or apower type.

    Instantaneous trip functions on molded case andinsulated case circuit breakers employed within aswitchboard assembly are not generally ANSI

    rated for higher short time withstand capability Can possibly be accessible from only one side.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    15/53

    5. Service Entrance Equipment

    Switchgear (UL 1558)

    Covers metal-enclosed low-voltage power circuitbreaker switchgear assemblies containing but not

    limited to such devices as low-voltage powercircuit breakers, other interrupting devices,switches, control, instrumentation and metering,protective and regulating equipment.

    Covers power equipment intended for use inordinary locations in accordance with the NationalElectrical Code.

    UL 1558 requirements are intended to supplementand be used in conjunction with the Standard for

    Metal-Enclosed Low Voltage Power CircuitBreaker Switchgear, ANSI C37.20.1, and theStandard for Conformance Testing of Metal-Enclosed Low-Voltage AC Power Circuit BreakerSwitchgear Assemblies, ANSI C37.51.

    Covers equipment rated 600 Vac or less nominal,635 Vac maximum.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    16/53

    5. Service Entrance Equipment

    Switchgear (UL 1558) continued

    For use on circuits having available rmssymmetrical short-circuit currents of not more than

    200 000 A. Switchgear is 30 cycle rated and can be installed

    without instantaneous overcurrent protection toassist in selectivity.

    Traditionally switchgear has more bus clearances Insulated bussing is commonly employed as astandard

    Compartmentalized cubicles versus barriersbetween sections

    Circuit breakers employed are by definition (ANSIstandards) classified as power class circuitbreakers having a higher short time withstandcapability than switchboards.

    Switchgear is front and rear accessible.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    17/53

    6. Selection of MCCB Circuit Breakers as

    Overcurrent Protective Devices

    Molded Case Circuit Breakers (MCCB)

    Thermal Magnetic

    Low Voltage Applications up to 600Vac

    Typical Current Ratings are from 5A to 2000A

    Originally designed for overload and phase-to-phase shortcircuit protection

    If intended to provide ground fault protection, these typecircuit breakers must be employed on a circuit with aneffective low impedance, ground fault current return path

    Mechanism is totally sealed Mainly require manual operations

    Not designed or intended to be serviceable

    Typically bolted onto or plugged into bus

    Should be installed with equipment turned off

    A ground fault module can be installed on some devices Most are only 80% rated. 100% rating is optional

    Same size and ampere rating of same circuit breakers aremanufactured with various short circuit ratings. (Knowing theavailable short circuit current available at point ofconnections is imperative!)

    MICROLOGIC or Electronic Trip Units Offers a combination of LSIG function to the specifier or user

    Provides for improved time/current or fault coordinationfunction

  • 8/8/2019 Electrical Equipment Room Design Considerations

    18/53

    6. Selection of ICCB Circuit Breakers as

    Overcurrent Protective Devices

    Insulated Case Circuit Breakers (ICCB)

    Generally are only UL Rated and not ANSI Rated

    Low Voltage Applications up to 600Vac Typical Current Ratings are from 400A to 4000A

    They provide limited internal access to replacement of specific parts

    Can be fixed mounted directly onto bus or manufactured as a draw-outtype within a specifically designed cubicle

    Can be fitted at the factory with multiple auxiliary functions

    Multiple Auxiliary Contacts Shunt Trip and Shunt Close Coils

    LSIG Trip Alarms

    Electric Motor Operator

    Most are only 80% rated, 100% rating is optional

    Ampere rating of circuit breakers can be manufactured with variousshort circuit ratings. (Knowing the available short circuit currentavailable at point of connections is imperative!)

    MICROLOGIC or Electronic Trip Units

    Offers a combination of LSIG functions to the specifier or user

    Provides for improved time/current or fault coordination function

  • 8/8/2019 Electrical Equipment Room Design Considerations

    19/53

    6. Selection of PCB Circuit Breakers as

    Overcurrent Protective Devices

    Power Circuit Breakers (PCB) ANSI Rated and not UL Rated

    Low Voltage Applications up to 600Vac

    Typical Current Ratings are from 800A to 6000A They provide internal access to inspection, maintenance, and

    replacement specific parts

    Manufactured as draw-out type construction with isolated compartmentor cubicle

    Can be fitted at the factory with multiple auxiliary functions

    Multiple Auxiliary Contacts Shunt Trip and Shunt Close Coils

    LSIG Trip Alarms

    Electric Motor Operator

    100% rated

    Tested and rated to a higher level of initial or asymmetrical short circuit

    current More robustly constructed than ICCBs

    Intended for longer use life and more open and close operations

    MICROLOGIC or Electronic Trip Units with LSIG functions are standard

    Has higher initial cost.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    20/53

    7 Electrical Room Construction

  • 8/8/2019 Electrical Equipment Room Design Considerations

    21/53

    7. Electrical Room Construction(New) - continued

    Conflicts between the architecture and electrical engineer of

    record concerning available/needed space for all electrical

    equipment rooms.

    Dual use spaces (Electrical Equipment Room and StorageArea)

    Fire alarms

    Security Cameras and their location

    Is all electrical equipment effectively bonded and grounded?

    Effective lighting within electrical rooms or closets.

    Equipment installation requirements and guidelines provided by

    the electrical equipment manufacturer

    Operations and Maintenance Manuals provided by the

    electrical equipment manufacturer

    Startup and Testing requirements

    Lock Out / Tag Out Requirements

    Danger and Warning Labels (Inform and Warn Requirements)

    ec r ca oom ons ruc on

  • 8/8/2019 Electrical Equipment Room Design Considerations

    22/53

    . ec r ca oom ons ruc on(New) - continued

    The need for a house keeping pad under the equipment.

    Locations within a specific building or facilities for the

    placement of service equipment, distribution equipment, power

    panels, motor control centers, ATS Units, battery banks, UPSUnits, onsite generators, etc

    Requirements for any house keeping pad constructed (material

    composition and necessary height)

    Flooding concerns from either external and internal sources Structural and seismic requirements for the electrical room

    Structural and bracing requirements for the electrical

    equipment enclosures

    Structural and bracing requirements for overhead busways,busducts, and conduits

    Need for floor drains or sump pumps in electrical rooms

    Critter protection

    Internal heater and humidity controls

    Will any local employees have access to water hoses???

  • 8/8/2019 Electrical Equipment Room Design Considerations

    23/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    24/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    25/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    26/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    27/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    28/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    29/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    30/53

  • 8/8/2019 Electrical Equipment Room Design Considerations

    31/53

    8 Electrical Room Construction

  • 8/8/2019 Electrical Equipment Room Design Considerations

    32/53

    8. Electrical Room Construction(New to Existing Equipment Additional

    Considerations)

    Bringing existing Service Equipment into

    compliance to current electrical Codes

    Additions of multiple power sources fromanother transformer or generator

    Dissimilar power or service equipment

    are rarely compatible (BIG RED FLAGS)

    Are all power sources effectively bonded

    together via a low impedance path Complex technical issues to resolve

    because of incompatible ground fault

    protection systems

  • 8/8/2019 Electrical Equipment Room Design Considerations

    33/53

    9. Maximum Impedance in a Ground Return Loop to

    Operate an Overcurrent Protective Device

    0.924 OHMS200A100A

    1.23 OHMS150A75A

    1.75 OHMS100A50A

    2.31 OHMS80A40A

    3.08 OHMS60A30A

    4.62 OHMS40A20A

    6.12 OHMS30A15A

    9.23 OHMS20A10A

    18.48 OHMS10A5A

    * (480/1.732)/ 3A (or)

    1.5b

    Maximum %Z in Ground

    Return Loop*

    Circuit Breaker Ampere

    Rating

    Value b

    Fuse Size in Amperes

    Value a

  • 8/8/2019 Electrical Equipment Room Design Considerations

    34/53

    9. Maximum Impedance in a Ground Return Loop to

    Operate an Overcurrent Protective Device

    0.154 OHMS1200A600A

    0.185 OHMS1000A500A

    0.231 OHMS800A400A

    0.308 OHMS600A300A

    0.370 OHMS500A250A

    0.462 OHMS400A200A

    0.528 OHMS350A175A

    0.616 OHMS300A150A

    0.739 OHMS250A125A

    * (480/1.732)/ 3A (or)

    1.5b

    Maximum %Z in Ground

    Return Loop*

    Circuit Breaker Ampere

    Rating

    Value b

    Fuse Size in Amperes

    Value a

  • 8/8/2019 Electrical Equipment Room Design Considerations

    35/53

    9. Maximum Impedance in a Ground Return Loop to

    Operate an Overcurrent Protective Device

    0.047 OHMS4000A2000A

    0.062 OHMS3000A1500A

    0.074 OHMS2500A

    0.093 OHMS2000A1000A

    0.116 OHMS1600A800A

    * (480/1.732)/ 3A (or)

    1.5b

    Maximum %Z in Ground

    Return Loop*

    Circuit Breaker Ampere

    Rating

    Value b

    Fuse Size in Amperes

    Value a

  • 8/8/2019 Electrical Equipment Room Design Considerations

    36/53

    10. 2005 NEC Requirements

    Ground-fault protection of equipment shall beprovided for solidly grounded wye electricalservices of more than 150 volts to ground butnot exceeding 600 volts phase-to-phase foreach service disconnect rated 1000 amperesor more. The grounded conductor for the

    solidly grounded wye system shall beconnected directly to ground without insertingany resistor or impedance device.

    The rating of the service disconnect shall beconsidered to be the rating of the largest fusethat can be installed or the highest continuouscurrent trip setting for which the actualovercurrent device installed in a circuit breakeris rated or can be adjusted.

    Ground-Fault Protection of Equipment(per Article 230-95 in the 2005 NEC)

  • 8/8/2019 Electrical Equipment Room Design Considerations

    37/53

    10. 2005 NEC Requirements

    The ground-fault protection systemshall operate to cause the servicedisconnect to open all ungroundedconductors of the faulted circuit. Themaximum setting of the ground-faultprotection shall be 1200 amperes, andthe maximum time delay shall be one

    second for ground-fault currents equal toor greater than 3000 amperes.

    Setting for Ground-Fault Protection(per Article 230-95(A) in the 2005 NEC)

  • 8/8/2019 Electrical Equipment Room Design Considerations

    38/53

    10. 2005 NEC Requirements

    The maximum setting for ground-fault sensors is 1200

    amperes. There is no minimum, but it should be notedthat settings at low levels increase the likelihood ofunwanted shutdowns. The requirements of 230.95 placea restriction on fault currents greater than 3000 amperesand limit the duration of the fault to not more than 1

    second. This restriction minimizes the amount of damagedone by an arcing fault, which is directly proportional tothe time the arcing fault is allowed to burn.

    Care should be taken to ensure that interconnectingmultiple supply systems does not negate proper sensingby the ground-fault protection equipment. A carefulengineering study must be made to ensure that faultcurrents do not take parallel paths to the supply system,thereby bypassing the ground-fault detection device. See215.10, 240.13, 517.17, and 705.32 for furtherinformation on ground-fault protection of equipment.

    Ground-Fault Protection of Equipment(NECH Commentary for Article 230-95(A) in the 2005 NEC)

  • 8/8/2019 Electrical Equipment Room Design Considerations

    39/53

    10. 2005 NEC Requirements

    The ground-fault protection system shall beperformance tested when first installed on site. The test

    shall be conducted in accordance with instructions thatshall be provided with the equipment. A written record ofthis test shall be made and shall be available to theauthority having jurisdiction.

    (The requirement for ground-fault protection systemperformance testing is a result of numerous reports ofground-fault protection systems that were improperlywired and could not or did not perform the function for

    which they were intended. This Code and qualifiedtesting laboratories require a set of performance testinginstructions to be supplied with the equipment.Evaluation and listing of the instructions fall under the jurisdiction of those best qualified to make such

    judgments, the qualified electrical testing laboratory (see90.7). If listed equipment is not installed in accordancewith the instructions provided, the installation does notcomply with 110.3(B).)

    Testing the Ground-Fault ProtectionSystem (per Article 230-95(C) in the 2005 NEC)

  • 8/8/2019 Electrical Equipment Room Design Considerations

    40/53

    10. 2005 NEC Requirements

    Electrical equipment and wiring and otherelectrically conductive material likely to becomeenergized shall be installed in a manner thatcreates a permanent, low-impedance circuit

    facilitating the operation of the overcurrentdevice or ground detector for high-impedancegrounded systems. It shall be capable of safelycarrying the maximum ground-fault currentlikely to be imposed on it from any point on thewiring system where a ground fault may occurto the electrical supply source. The earth shall

    not be considered as an effective ground-faultcurrent path.

    Effective Ground-Fault Current Path(per Article 250-4(A)(5) in the 2005 NEC)

    11 G d F lt S i

  • 8/8/2019 Electrical Equipment Room Design Considerations

    41/53

    11. Ground Fault Sensing

    There are three basic types of sensor arrangement usedto sense abnormal current flow in a Zero Sequence

    Relaying Scheme. They are;

    A. Zero Sequence Sensing Where one sensor isemployed to surround all phase conductors and neutral

    conductor.

    B. Modified Zero Sequence Sensing Where one sensor is

    employed to surround all phase conductors and a

    separate sensor surrounding the neutral sensor.

    C. Residual Sequence Sensing Where one sensor

    surrounds each phase conductor and neutral conductor.

    12 Zero Sequence Sensing vs Residual

  • 8/8/2019 Electrical Equipment Room Design Considerations

    42/53

    12. Zero Sequence Sensing vs. Residual

    Sequence Sensing

    Zero Sequence Sensing

    Current sensors or current transformer

    are external to disconnecting device

    Usually associated with a separate and

    externally mounted Ground Fault Relay No internal relationship to disconnect to

    be operated. All GFP components are

    externally mounted. Disconnect requires a shunt trip coil

    Requires a separate and reliable sourceof control power. (Weakest Link)

    12 Zero Sequence Sensing vs Residual

  • 8/8/2019 Electrical Equipment Room Design Considerations

    43/53

    12. Zero Sequence Sensing vs. Residual

    Sequence Sensing

    Residual Sequence Sensing

    Phase sensors are usually internal to

    protective device to be operated. Ground fault relaying is usually

    performed internal to protective device

    or circuit breaker to be operated.

    No external control power supply

    required. Protective device or circuit

    breaker is self-powered.

    Self powered residual sequence sensing

    GFP is referred to as Integral GroundFault Protection.

    13 Power Distribution Systems with

  • 8/8/2019 Electrical Equipment Room Design Considerations

    44/53

    13. Power Distribution Systems with

    Multiple Sources

    Two or more sources of power connected to the

    switchboard or switchgear.

    Separate Main Circuits Breakers

    Tie Circuit Breakers

    Separate Load Busses

    Neutral Bus associated with each power source are

    interconnected together. Multiple neutral-to-ground bonds via the connection of

    multiple System Bond Jumpers and Main Bonding

    Jumpers (MBJ).

    The interconnection of multiple grounding conductors onthe line side of the main circuit breakers can function as

    a parallel neutral bus.

    Multiple current paths for imbalanced neutral currents

    and ground fault currents to flow.

    13 Power Distribution Systems with

  • 8/8/2019 Electrical Equipment Room Design Considerations

    45/53

    13. Power Distribution Systems with

    Multiple Sources

    14 Modified Differential Ground Fault

  • 8/8/2019 Electrical Equipment Room Design Considerations

    46/53

    14. Modified Differential Ground Fault

    (MDGF) Protection Systems

    The purpose of a MDGF Protection System is to senseand properly relay all of the phase and neutral currentswhich circulate through and within a multiple source

    power distribution system at all times during normal andabnormal conditions.

    The MDGF Protection System prevents nuisance trippingof circuit breakers from the flow of imbalanced currents

    from imbalanced loads. The MDGF Protection System prevents nuisance tripping

    of circuit breakers from the flow circulating currents inand out of the switchboard or switchgear from closed

    transition operations. The MDGF Protection System opens all of the

    appropriate circuit breakers closes to the faulted locationwithin a switchboard or switchgear.

    The MDGF Protection System provides for thesectionalization of load busses.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    47/53

    15. Designing a MDGF Protection System

    Before a MDGF Protection Systems for a

    multiple sourced switchboard can be

    configured the following must be evaluated.A. Type of circuit breaker?

    1. The internal sensors and ground fault

    relaying are not always configured the same.B. Frame size of the circuit breaker?

    1. Different frame size breakers often have

    different C.T. ratios.

    2. Different series circuit breakers can have the

    frame size and C.T. ratios, but different

    instantaneous C.T. polarities.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    48/53

    15. Designing a MDGF Protection System

    C. How are the circuit breakers supplied withpower?

    1. Are the circuit breakers top feed?2. Are the circuit breakers bottom feed?

    D. Are the circuit breakers fixed or draw outtype?

    The MDGF must be maintained when anycircuit breaker is open or removed from its cell(drawn out).

    E. Is the tie circuit breaker (52T) specified toground fault protection?1. Non-Relayed Tie Circuit Breaker has noGF Protection

    2. Relayed Tie Circuit Breaker has GFProtection

  • 8/8/2019 Electrical Equipment Room Design Considerations

    49/53

    16. Reported Ground Fault Losses

    One Major Loss (Claim) Every Two

    Weeks

    Special Notes for Consideration

  • 8/8/2019 Electrical Equipment Room Design Considerations

    50/53

    Special Notes for Consideration

    Phase-to-ground faults are the most common form of electrical

    faults. (95% to 98%)

    During any phase-to-ground fault the ground fault return path is50% of the power circuit.

    Phase-to-ground faults are the most destructive type of electricalfaults.

    Contrary to popular belief or some marketing publications, fuses do

    NOT provide selective coordination from most phase-to-groundfaults.

    For a current limiting fuse to limit current as designed and intendeda fault must be a bolted fault. Current limiting fuses do not

    coordinate well during high impedance phase-to-ground faults.

    Multiple levels of ground fault protection via MICROLOGIC CircuitBreakers provides the best form of selective coordination fromphase-to-ground fault condition.

    Complex ground fault protection systems (MDGF) require aspecific level of electrical engineering expertise.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    51/53

    Code NEC, NFPA 70

    The NEC is a minimum construction andinstallation requirement document.

    The NEC is NOT a design or performancestandard .

    Minimum requirements are often insufficient forthe construction and installation of mission criticalfacilities as Data Centers, Communication

    Centers, Hospitals, Industrial Plants, MilitaryFacilities, Prisons, and Transportation Centers.

  • 8/8/2019 Electrical Equipment Room Design Considerations

    52/53

    Questions & Answers

    Speaker Contact Information

  • 8/8/2019 Electrical Equipment Room Design Considerations

    53/53

    Speaker Contact Information

    S. Frank Waterer III Staff EngineerSchneider Electric Engineering Services

    2979 Pacific Drive, Suite ENorcross, Georgia 30071

    Office Phone: 770-447-0351, Ext. 102

    Office Fax: 770-447-4985

    E-MAIL: [email protected]


Recommended