+ All Categories
Home > Documents > KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE...

KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE...

Date post: 13-May-2020
Category:
Upload: others
View: 1 times
Download: 0 times
Share this document with a friend
16
©2017, KEPCO, INC Data subject to change without notice 228-1692 REV 7 1 QUICK START GUIDE KEPCO KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102 http://www.kepcopower.com email: [email protected] An ISO 9001 Company. BOP 1KW BOP 1KW-MG/ME POWER SUPPLY This guide gives a brief introduction to the BOP 1KW-MG/ME Power supply, shows simple load connections, and allows you to verify the power supply is working. The guide also shows you how to use the front panel controls to perform the most commonly used functions. BOP 1KW models with MG and ME suffixes are identical except that the MG units have a factory-installed GPIB interface and in the ME units the GPIB interface is replaced with a LAN interface. Unless otherwise noted this guide applies to both models. ACCESSING MANUALS. First determine your Firmware Version (see below), then download the BOP 1KW-MG, ME applicable Operator’s Manual from www.kepcopower.com/support/opmanls.htm#bop-1k Refer to the BOP 1KW-MG/ME Operator’s Manual for full specifications, installation considerations and operating instruc- tions, including an Installation/Operation Summary which inclu des hyperlinked r eferences to det ailed procedures, but which can be printed as a ha ndy reference.The BOP 1KW-MG/ME Operator’s Manual also includes a full de scription of the digital interfaces and the SCPI command language. FIRMWARE VERSION. Refer to www.kepcopower.com/support/bophifirm.htm to determine which firmwa re ver- sion is installed. ACCESSING DRIVERS. Drivers are accessed from www.kepcopower.com/drivers/drivers-dl3.htm.
Transcript
Page 1: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

©2017, KEPCO, INC Data subject to change without notice 228-1692 REV 7 1

QUICK START GUIDE

KEPCO

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

An ISO 9001 Company. BOP1KW

BOP 1KW-MG/ME POWER SUPPLYThis guide gives a brief introduction to the BOP 1KW-MG/ME Power supply, shows simple load connections, and allows you toverify the power supply is working. The guide also shows you how to use the front panel controls to perform the most commonlyused functions.

BOP 1KW models with MG and ME suffixes are identical except that the MG units have a factory-installed GPIB interfaceand in the ME units the GPIB interface is replaced with a LAN interface. Unless otherwise noted this guide applies to bothmodels.

ACCESSING MANUALS. First determine your Firmware Version (see below), then download the BOP 1KW-MG, MEapplicable Operator’s Manual from www.kepcopower.com/support/opmanls.htm#bop-1k

Refer to the BOP 1KW-MG/ME Operator’s Manual for full specifications, installation considerations and operating instruc-tions, including an Installation/Operation Summary which inclu des hyperlinked r eferences to detailed procedures, butwhich can be printed as a handy reference.The BOP 1KW-MG/ME Operator’s Manual also includes a full de scription ofthe digital interfaces and the SCPI command language.

FIRMWARE VERSION. Refer to www.kepcopower.com/support/bophifirm.htm to determine which firmware ver-sion is installed.

ACCESSING DRIVERS. Drivers are accessed from www.kepcopower.com/drivers/drivers-dl3.htm.

Page 2: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

2 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

CONTENTS

I — DESCRIPTION.The BOP 1KW-MG/ME Series hereafter referred toas BOP, are true 4-quadrant programmable voltageand current power supplies, meaning they are capa-ble of both sourcing and sinking power (see Figure1). These bipolar power supplies pass smoothlythrough zero without switching to provide true ± volt-age and ± current. These BOP power supplies useswitch mode techno logy for low dissip ation. A bi-directional, isolating, a-c input power factor correct-ing (PFC) circuit recuperates energy sinked from anactive load and sends it back into the line to maintainlow dissipation.

These BOP power supplies are controlled digitallyfrom a menu-driven front-panel keypad or one of theremote digital interfaces (GPIB o r RS 2 32 on MG

models, LAN or RS 232 on ME models) to set volt-age and current and the four protection limits (+volt-age, –voltage, +current and –current.) A front panelrotary adjuster allows real-time adjustment of theoutput. A large LCD displays the mode of operation,the settings, and the actual output voltage and cur-rent. Additionally, these BOP mode ls can beremotely controlled by an analog ±10V input for themain channel (voltage or current), and a +1 to +10Vinput for the limit channels. BOP models are suitable for driving inductive loadssuch as large magnets or motors, and for exercisingbatteries. They are a lso suitable for chara cterizingsolar cell arrays, and powering many electrochemi-cal reactions.

II — UNPACKING.This instrument has been thoroughly inspected andtested prior to p acking and is r eady for operation.After careful unpacking, inspect for shipping damagebefore attempting to operate. Perform the “Installa-

tion.” on p age 5. If a ny indication of damag e isfound, file an immediate claim with the responsibletransport service.

Description. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Unpacking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2Equipment Supplied. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Preliminary Operational Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

Input Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Load Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5Local Sensing (Factory Default). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Remote Sensing Select. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Analog I/O Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6Trigger Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6GPIB Connections (MG SUFFIX). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6LAN Connections (ME SUFFIX ONLY). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6FINDING KEPCO POWER SUPPLIES ON THE LAN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6RS 232 Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Turning The Power Supply On. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9Accessing the Menus. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9How to Modify a Parameter. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10Adjusting LCD Brightness, contrast and Background . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Enabling/Disabling Audible Beeps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Setting Voltage or Current Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Programming Voltage or Current and Associated Protect Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11Software Limits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

Changing Main Channel Software limit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Determining How the Unit Responds when Output is OFF (Load Type) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12Configure Load Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14Enabling/disabling Output Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Additional Features. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14BOP 1KW Outline Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

Page 3: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

081817 228-1692 REV 7 3

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

.

III — EQUIPMENT SUPPLIED. See Table 2.

IV — SAFETY. See Table 3

V — PRELIMINARY OPERATIONAL CHECK.A simple operational check after unpacking andbefore equipment installation is advisable to ascer-tain whether the power supply has suffered damageresulting from shipping.

1. With POWER switch set to o ff position, connectthe power supply to so urce power (see “InputConnections.” on page 5.

2. With no lo ad connected, set PO WER switch tothe ON position . Each time the unit is tu rned onan internal self-test is performed. If all tests pass,the unit goes into the default mode. If a failureoccurs, the failure is d isplayed. Figure 5 showsthe factory-configured power on defaults dis-played on the LCD.

3. Connect a digital voltmeter (DVM) (resolution andaccuracy of 0.01 % or better) to the OUT S a ndCOM S terminals at the rear panel terminal block.

4. Use the keypad to enter the rated maximum volt-age of the power supply (e.g., enter 36 for amodel BOP 36-28MG) and pr ess ENTER. IfSTANDBY indicator is lit, press STANDBY key.

5. Verify DVM voltage reading agrees with pro-grammed voltage within 0.03% of rated maximumvoltage and agrees with disp layed voltage onLCD within 0.05% of rated maximum voltage.

TABLE 1. BOP 1KW-MG/ME MODEL PARAMETERS

Model (1)

d-c Output Range Closed Loop Gain Output Impedance

Voltage (2)

(V d-c)Current(A d-c)

Voltage ChannelGV (V/V)

Current ChannelGI (A/V)

Voltage Mode(Series R - L)

Current Mode(Parallel R - C)

Rd-c(mOhms)

L(H)

Rd-c(Ohms)

C(F)

1000 WATT MODELS

BOP 6-125MG/ME 0 to ±6 0 to ±125 0.6 12.5 0.05 1.5 24 1150

BOP 10-100MG/ME 0 to ±10 0 to ±100 1.0 10.0 0.1 2.0 50 1100

BOP 10-75MG/ME 0 to ±10 0 to ±75 1.0 7.5 0.13 2.0 67 976

BOP 20-50MG/ME 0 to ±20 0 to ±50 2.0 5.0 0.40 8.3 200 371

BOP 25-40MG/ME 0 to ±25 0 to ±40 2.5 4.0 0.63 15.8 313 165

BOP 36-28MG/ME 0 to ±36 0 to ±28 3.6 2.8 1.30 25 640 103

BOP 50-20MG/ME 0 to ±50 0 to ±20 5.0 2.0 2.50 50 1250 55

BOP 72-14MG/ME 0 to ±72 0 to ±14 7.2 1.4 5.14 104 2570 33

BOP 100-10MG/ME 0 to ±100 0 to ±10 10.0 1.0 10.0 163 5000 16

(1) Models with MG suffix include GPIB and RS 422 digital interfaces. Models with ME suffix include LAN and RS 422 digital interfaces.(2) When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of the BOP.

Otherwise the overvoltage protection will shut down the power supply.

TABLE 2. EQUIPMENT SUPPLIED

ITEM FUNCTION PART NUMBER

Source Power Entry mating connector

Mates with source power entry connector

142-0381 (Kepco) (IEC 320)

PAR/SER CONTROL - IN mating connector

Mates with PAR/SER CONTROL - IN port to allow access to pins required for calibration

142-0488 (Kepco)

TABLE 3. SAFETY SYMBOLS

SYMBOL MEANING

CAUTION: RISK OF ELECTRIC SHOCK.

CAUTION: REFER TO REFERENCED PROCE-DURE.

WARNING INDICATES THE POSSIBILITY OF BODILY INJURY OR DEATH.

CAUTION INDICATES THE POSSIBILITY OF EQUIPMENT DAMAGE.

!

Page 4: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

4 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

FIGURE 1. BOP OUTPUT CHARACTERISTICS

Page 5: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

081817 228-1692 REV 7 5

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

VI — ACCESSORIES. See Table 4.

VII — INSTALLATION.Install units either on a bench or in a 1 9 inch-widerack. For rack mounting: remove four feet first; rackmust provide support at the rear). Optional slidesmay be used. Leave the front and rear panels clearof obstructions to ensure adequate cooling. For par-allel, series and master-slave configurations, refer tothe Operator’s Manual.

INPUT CONNECTIONS. Source power is con-nected to the power supply via thr ee-wire inputpower using the sour ce power mating connectorsupplied (see Table 4). This power supply operatesfrom single phase a-c mains power (or between two

phases of 3-phase a-c mains power), 230V, 50/60Hznominal (range: 176 - 264V, 47-63Hz) without anyneed for range selection. The user must provide aproperly sized and rated mains lead (line cord) andservice with a c urrent rating compatible with theanticipated input curre nt. Line cords available a saccessories are listed in Table 4. Plug the sourcepower connector into the source power inlet connec-tor at the rear panel.

LOAD CONNECTIONS. Power connections re-quire wires that are properly rated for the nominal out-put current of the unit. Connect the load to the OUT-

TABLE 4. ACCESSORIES

ITEM FUNCTION PART NUMBER

Line Cord (250V, 20A) Provides connection to a-c mains via Nema 6-20P connector. 118-1087

Line Cord (250V, 20A) Provides connection to a-c mains via Nema L6-20P locking type connector. 118-1088

Mating Connector, Trigger Mates with Trigger port. 142-0527 (Kepco)SP2501 (CUI Stack)

IEEE 1118 (BITBUS) Mating connector

Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco)KMDLA-5P (Kycon Inc.)

IEEE 488 Cable, (1 meter long) For MG models only. Connects BOP power supply to GPIB bus. SNC 488-1

IEEE 488 Cable, (2 meter long) For MG models only. Connects BOP power supply to GPIB bus. SNC 488-2

IEEE 488 Cable, (4 meter longs)

For MG models only. Connects BOP power supply to GPIB bus. SNC 488-4

Interconnection Kits for parallel/series configurations.

Cables required to connect multiple BOP models in parallel, series, or paral-lel/series configurations.

See Operator’s Manual.

RS 232 Cable Kit Contains RJ11 to RJ45 Patch cord, RJ 45 Patch cord, two RS 232 adapters, one with male pins to connect to DTE equipment and one with female pins to connect to a PC (personal computer), two RS 232 Loop Back test Connec-tors (one 6-pin and one 8-pin) to test RS 232 communication and aid in iso-lating RS 232 communication problems.

KIT 219-0436

RS 232 Adapter (Male pins) Allows RS 232 port to be connected to DTE equipment. (Supplied in KIT 219-0436.)

142-0487(L-COM RA098M)

RS 232 Adapter (Female pins) Allows RS 232 port to be connected to a PC (personal computer). (Supplied in KIT 219-0436.)

142-0506(L-COM RA098F)

15-pin DSUB Connector Mating connector for Analog input connector A2A5J6Dsub 15 pin hood

Dsub 15 pin male

108-0374 (Tyco-Amp 207470-1)

142-0449(Amphenol 17S-DA15P)

IDC 6-pin connector Mating connector for RS-232 PORT, connector A1J5 and PROTECTION EXT. PORT, connector A2A5J7

142-0536(Amphenol 5-555176-3)

IDC 8-pin plug Mating connector for PAR/SER PROTECT PORT (IN and OUT) connectors. 142-0535(Amphenol 5-555176-3)

Slides Allows easy withdrawal of unit from rack (see Figure 1). (Model CS 04 includes slides, brackets, all mounting hardware and installation instruc-tions.)

CS 04

Heat Sink Provides adequate cooling for calibration sense resistors. 136-0451

Output Terminal Cover Protects against inadvertent contact with output and barrier strip terminals 129-0423

Page 6: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

6 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

PUT and C OMMON power terminals on the rearpanel (see Figure 3). OUT S and COM S terminal ofthe Monitor and Sensing Terminal block are for con-nection of remote sensing lea ds (after removing thefactory-installed local sensing links). NOTE: OutputSense lines must be connected for proper opera-tion, either locally, or at the load (remote). Alsouse OUT S a nd COM S to monitor voltage at theload using external equipment such as a DVM, oscil-loscope, etc. Use OUT MO N and C OM MON tomonitor voltage at the BOP output.

It is critical th at configurations comprised of BOP,load, and external programming devices, have a sin-gle earth-ground point. Observe the following cau-tion and refer to the applicable BOP 1KW -MGOperator Manual for earth-ground recommenda-tions. Failure to observe this caution will void thewarranty!

CAUTION: Never connect both the loadterminal tied to the BOP COM terminaland the programming device commonto earth-ground. This compromisesaccuracy and will cause catastrophicdamage to the BOP if the connectionbetween BOP COM and the load termi-nal tied to earth-ground is lost.

LOCAL SENSING (FACTORY DEFAULT). Unit is shi pped with local sensing links installed:OUT S conne cted to OUT MON and COM MO Nconnected to COM S (see Figure 4A). REMOTE SENSING SELECT. First remove thefactory-installed local sensing links between OUT Sand OUT MON and between COM MON an d COMS. Then connect the OUT S and COM S lines at theload (see Figure 4B) using #22 AWG wire, twistedpair.

ANALOG I/O CONNECTIONS. The Analog I/OPort connector, located on the rear panel of the BOP1KW power supply (see Figure 3), provides accessto analog programming inputs which can control themode of operation (voltage or cur rent), output volt-age or current, and establish positive and negativevoltage and current limits. An o utput analog corre-sponding to output current is also provided. Refer toOperator’s manual for details.

TRIGGER CONNECTIONS. The Trigger Port(see Figure 3) provides for an external trigger inputfor use with SCPI *TRG and TRIG commands. Referto Operator’s manual for details.

GPIB CONNECTIONS (MG SUFFIX). Yourcomputer must have a GPIB interface card installed.Connect the power supply to the computer’s GPIBinterface card. Use a standard GPIB interface cableat the GPIB port on the rear panel (see Figure 3). The default GPIB address is 6; refer to the Opera-tor’s Manual to change it.

LAN CONNECTIONS (ME SUFFIX ONLY). Connect the BOP 1KW to a Microsoft Windows-basedcomputer via the LAN connector (see Figure 3). Use astandard ethernet cable whether using a router or hub,or connecting the BOP 1KW directly to a computer.The BOP 1KW -ME is Auto-MDI-X enabled and doesnot require a crossover cable for direct connection. ForUnix and Safari connections see full Operator Manual(refer to “Accessing Manuals.” on page 1).

FINDING KEPCO POWER SUPPLIES ON THE LAN.

The PSfind utility can be downloaded from theKepco web site at:www.kepcopower.com/drivers/drivers-dl3.htm#bop1k

This utility finds all o perational Kepco power sup-plies connected to the LAN and then shows theMAC and IP addresses of the models found.

To run the utility from your PC download thepsfind.zip file to your computer . Extract psfind.exefrom the zip file to a location of your choice, thendouble-click psfind.exe to run the application. Aseparate window opens as shown on Figure1.Once the search is completed, all found units aredisplayed in the Select a Unit window (the MACaddress appears in parentheses). If you do not seeyour device in the Select a Unit window or if the iconto the lef t of the selected instrument is red (notgreen), make sure it is turned on and con nected tothe network, then click the Search Again button.

FIGURE 1. PS FIND SCREEN

!

Page 7: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

081817 228-1692 REV 7 7

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

FIGURE 2. BOP 1KW SERIES, FRONT PANEL CONTROLS AND INDICATORS

RS 232 CONNECTIONS. Connect the BOP1KW to a modem using a Null Modem patch cable atthe RS 232 port located on the rear panel (See Fig-ure 3). A Null Modem cable is not required for older

MAC computers with D-sub serial port in which theRXD and TXD line transposition is accomplished viaexternal hardware. The default baud rate is 9 600;refer to the Operator Manual to change it.

ENTER

Page 8: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

8 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

FIGURE 3. BOP 1KW SERIES, REAR PANEL VIEW, LINKS INSTALLED FOR LOCAL SENSING

FIGURE 4. LOAD CONNECTION

A. LOCAL SENSING B. REMOTE SENSING

GNDNET

OUTMON

N / C OUTS

COMS

COMMON

GND

Page 9: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

081817 228-1692 REV 7 9

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

VIII — OPERATION.Additional features covered in the Operator Manualare: Quick Boot (eliminating the power- up displays),use of the internal relay, operation via the LAN inter-face or analog signals and setting coarse/fineadjustment preference of the VOLTAGE and CUR-RENT controls. An Installation/Operation Summaryis also included in the Operator Manual. The Opera-tor Manual also co vers the GPIB an d RS232interfaces, including the use of the drivers down-loadable from: www.kepcopower.com/drivers/drivers-dl3.htm#bop1k.TURNING THE POWER SUPPLY ON.

CAUTION:

DO NOT repeatedly toggle the cir-cuit breaker/switch as this maydamage the unit.

Set POWER ON/OFF circuit breaker/switch on frontpanel to ON. If actua tor does not lock whe nreleased, wait a fe w seconds before trying again.The circuit breaker is “tri p-free” design; if overloa dexists, contacts cannot be held closed by actuator.

• When the power supply is turn ed on, it per -forms a brief self-test that includes testing thethree processors (analog, interface and dis-play), then displays the power-up screen (seeFigure 5). If an erro r is detected, the FAULTindicator will light, information about the errorwill be briefly displayed on the LCD.

• If the unit powers up in REMOTE mode, press! to set the unit to LOCAL mode.

• If the display is not viewable, press # twice.The display will cycle thro ugh the r ange ofcontrast settings. Press # again to lo ck inthe preferred contrast.

ACCESSING THE MENUS. From the power-upscreen, pressing the Function keys indicated on theLCD opens the associated menu. The menu openedmay list su bmenus that may b e opened eitherdirectly by pressing the associated Function keys, orby highlighting an item on th e list and pressing theView/Modify function key. Menus and submenus willdisplay a list o f parameters, with the top one high-lighted. The function key assignments can vary, butgenerally offer the following choices:

• ! allows the highlighted parameter to beviewed or modified. After changing the param-eter, the following choices are available: $ -SAVE or ENTER to save the change, % -EXIT to abort the change and exit to the previ-ous menu.

• @ - RESTORE DEFAULT restores factorydefaults for the parameters displayed (exceptfor GPIB add ress). The factory defaults maybe saved as power-up defaults by pressing$.

• # - The function varies, dep ending on themenu. In most cases # is used to a bort achange without applying the modified setting.From the pow er-up screen # is used toadjust contrast. In the Revisions/TEST sub-menu of the General Setup Menu, # is usedto execute a test.

• $ - SAVE FOR POWER-UP Saves the con-figuration shown as a power-up setting so thechanges will not be lo st when the uni t isturned off.

• % - APPL Y EXIT applies the current(changed) setting without saving for power-upand exits to the p revious menu or to thepower-up screen, EXIT leaves the currentmenu without saving or applying changes.

The menu structure is as follo ws (NOTE: BOLD =Factory Default):

Power-up Screen (Power up menu)• ! - Save/Recall• • Saved Setups: Recall one of 99 saved set-

ups.• • • Saved Setup Details: Mode (voltage/

current), main channel reference (inter-nal/external/external reference level)and setting, protection limit (internal/external/lesser limit) and setting(s), out-put status (on/off)

• @ - Waveform • • Saved Waveforms: Choose one of 16

saved waveforms.• • • New Waveform Settings: Name (max.

10 characters), protection settings,count, mode (voltage/current)

• • • Waveform Settings: Name , protectionsettings, count, segment list, mode

• • • • Segment Details: Type (square/±ramp/triangle/sine/level),frequency or period, p-p amplitude,offset, start/stop angle for sine andtriangle, initial/repeat

!

Page 10: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

10 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

• # - Display• • Display and Beep Settings: Display

(meters/graphics (12 choices)), back-ground (white/black), contrast, beep (On/Off/Error only)

• $ - Analog Remote Setup• • Analog Remote Settings: Reference input

(internal/external/external referencelevel), protection limit ( internal/external/lesser limit), exter nal mode (enable/dis-able)

• % - General Setup• • Interface Settings: • • • Serial Settings: *RST sets Output (on/

off), Serial Baud ( Off/9600/19200),Xon/Xoff (enable/disable), prompt(enable/disable)

• • • GPIB Settings: GPIB ad dress (default= 6), Data format ( SCPI/CIIL), Deviceclear (SCPI/MATE)

• • • LAN Settings: IP Address, IP MASK,AUTO IP ON, DHCP ON, Name andindex (MDNS name)

• • Max/Min Settings: Protect Entry (Bipolar/Independent); for volt age mode: +Voltagemax, –Voltage min, ±CProtect max/min; forcurrent mode: +Current max, –Curr entmin, ±VProtect max/min

• • Load Type: Active/Resistive/Battery• • Revisions/Test: (Tests: display, keypad,

interface, serial, analog and output)• • Calibration: Voltage, Current and External

and Controls calibration• • Power-up Settings: Mode ( Voltage/Cur-

rent), Main channel refer ence (Internal/External/External Reference Level), pr o-tect channel type (Internal/External/LesserLimit), Voltage Protect Limit (cur rentmode), Current Protect Limit (voltagemode) output on/off

• • Password• • • Password Settings: Menu pro tection

(Interface/Max-Min/Load/Test/Power-up/Keypad @ local/Keypad@power-up), Save Display chg (Enable/Dis-able), Passwords (Main/Admin1/Admin2 or Unprotected)

• • Series/Parallel: Configuration (Standalone/Parallel/Series/Master 2X2/Master 3X2);for parallel or se ries: Unit T ype (Stand-alone/Master+1 to+4/Slave #1 to #5) andConnection Type: shows Series or Paral-lel).

FIGURE 5. POWER-UP SCREEN SHOWING GRAPHIC METERS

HOW TO MODIFY A PARAMETER. First access the parameter by accessing the propermenu as described above. To modify a p arameterlisted in a menu or submenu, proceed as follows:

1. Highlight the parameter using the Y and U keys.2. When the desired choice is highlighted, press !

to modify the active setting. The choices are dis-played with the a ctive setting highlighted. In th ecase of numerals, the units digit is highlighted.

• To change a numeric setting, press the num-ber keys, then press ENTER to program thenumbers entered. Use the CLEAR key toclear numbers entered and start over. TheADJUST control can also be used to incre-ment or decrement t he highlighted digit.Pressing ADJUST while rotating adjusts theleast significant digit. If the output is on (un itnot in Standby) changes made using the

Page 11: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

081817 228-1692 REV 7 11

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

ADJUST control are immediately applied tothe output.

• For alphanumeric characters use multiplepresses of the number keys for letters or sym-bols: 0 (space), 1 (+, –, / ), 2 (ABC), 3(DEF), 4 (GHI), 5 (JKL), 6 (MNO). 7(PQRS), 8 (TUV), 9 (WXYZ). Use the Tkey to highlight the next character. As an alter-native, the U or Y keys or ADJUST controlwill scroll through numbers, and letters andsymbols. Use the CLEAR key to clear theentire alphanumeric field and start over

3. Press $ to apply the change and return to themenu (to change another parameter, repeat steps1 and 2). To abort (return to the menu withoutapplying the change), press %.

NOTE:Press HELP key for more information,press HELP again to see mu ltiplescreens; press CLEAR key to exit thehelp screen.

ADJUSTING LCD BRIGHTNESS, CON-TRAST AND BACKGROUND From the power-up screen, (Figure 5), press # twice to initiate con-trast adjustment. The cont rast gradually alternatesbetween light and dark. When the contrast is accept-able, press # to apply the change and exit contrastadjust. Use the T and R keys for fine adjustmentof contrast. Contrast can also be a djusted from thepower-up screen by pressing # once, then press-ing T and R as needed for fine adjustment.

To change the background, press # from thepower-up screen, Highlight Background, press !,highlight Black or White, then $ to save. Press $exit and save for power-up or % to ap ply thechanges (without saving for power-up) and exit.

ENABLING/DISABLING AUDIBLE BEEPS From the p ower-up screen, press #, then modifythe setting. Even though audible beeps are set to off,the beeps will still sound upon power-up or detectionof a power supply fault.

SETTING VOLTAGE OR CURRENT MODE The BOP use s two sep arate channels, one to setoutput voltage or current and one to set the corre -sponding protection limit. The main channel is deter-mined by th e MODE key (in local mode) whichalternately selects either Voltage mode or Currentmode or by SCPI command (in digital remote mode).The protection channel is determined automaticallyby the main channel selected. When Voltage mode

is selected, the current protection channel is active,and when Current mode is selected, the Voltage pro-tection channel is active. PROGRAMMING VOLTAGE OR CURRENT AND ASSOCIATED PROTECT LIMITS Fromthe power-up screen the sett able voltage/currentparameters are displayed at the bottom of the LC Dabove the HELP message. Use Y or U to highlightthe main or protect channel.

1. To verify that the unit is configured for internal ref-erences press $ from the power-up screen andverify that Reference Input and Protection Limitare set to Internal, and External Mode is set toDisable. If necessary to change a setting, use Yor U to highlight the parameter, and press ! tomodify. Highlight the desired selection and press$ to save, then press $ to save for power-upor % to exit. If an alog programming is desired,refer to Operator’s Manual.

2. Verify that the load type has been configuredproperly to e nsure that the unit behaves asexpected when the output is of f (see “” onpage 13 for details).

3. Press MODE key to select the main chan nel(VOLTAGE or CURRENT); the associated PRO-TECT channel is automatically selected and dis-played.

4. Set the output on o r off as desired using theSTANDBY key. The output is off (disabled) whenthe STANDBY indicator is lit, on (enabled) whennot lit.

5. Use Y or U to highlight the main channel. Thereare two ways to program the output in local mode.These methods can be used either when the out-put is disabled (STANDBY indicator lit) orenabled.

WARNING:

When the ADJUST control isrotated, the active parameter isimmediately effective if the outputis enabled (on = STANDBY indica-tor not lit). The voltage/currentapplied to the load changes as theADJUST control is rotated.

• Use the ADJUST control to increa se ordecrease the main channel setting (e.g., volt-age when the un it is in volt age mode). Startwith the most significant digit of the d esiredvalue, then use T to highlight the next digit.

Page 12: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

12 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

For fine adjustment press the ADJUST controlin while rotating the knob to modify the leastsignificant digit.

• Enter the desired value on the keypad usingthe number keys. For example, to program theBOP to 75.8V, press the following keys inorder 75.8 then press ENTER. For fineadjustment use Y, and U to modify the leastsignificant digit. T o correct the en try beforeactivation press the CLEAR key to set thevalue to zero and start over. When the desiredvalue is displayed, press ENTER. This causesthe new value to appear at the output and beapplied to the load if the output is enabled.

6. To program the cor responding Protect channel,press Y or U as necessary to highlight the Pro-tect channel. Then set the value u sing either ofthe two methods described above. If the ProtectEntry setting is set to Independent, separateentries for the positive and negative protect chan-nel are possible. Otherwise the value entered isapplied to bo th positive and negative protectchannels.

NOTE: The BOP can be configured to showthe protection limits as either a singlevalue that applies to both protectionchannels or show individual settingsfor positive and nega tive protectionlimits. See Operator’s Manual fordetails

SOFTWARE LIMITS. Software limits preventprogramming of the main chan nel or the Protectchannel beyond the software limit value. Re fer toOperator’s Manual for a fu ll explanation of softwarelimits.Changing Main Channel Software limit. This procedure allows the user to determine themaximum value of voltage or current that can b eprogrammed.

1. Press % from the power-up screen to enter theGeneral Setup menu, then highlight Max/Min Set-tings.

2. Press ! to enter the Max/Min Settings submenu(Figure 6). (If a Password is required, see Opera-tor’s Manual for instructions.)

3. Highlight the voltage or current max/min va lueand press ! to change it. Sof tware limits areabsolute values (do not use minus sign for nega-

tive limits). Use number keys to change the set-ting, then $ to save.

4. When complete, press $ to save for power-up,# to abort, or % to apply the changes (withoutsaving for power-up) and exit.

5. Upon return to the power-up screen, the mainchannel (voltage or current) is compared againstthe main channel limits in effect. If the main chan-nel exceeds the limit, it is set to zero.

6. Highlight the ±CPROTECT or ±VPROTECT max/min value and press ! to cha nge it. Softwarelimits are absolute values (do not use minus signfor negative limits). Use number keys to changethe setting. Press $ to save, or % to abort.

7. When complete, press $ to save for power-up,or # to abort, or % to apply the changes (with-out saving for power-up) and exit.

Upon return to the power-up screen, the new protec-tion limit (voltage or current) is compared against theprotection limits in effect. If the ne w protection limitsetting is below the existing setting for the protectionlimit, the protection channel (voltage or current) isset to zero.DETERMINING HOW THE UNIT RESPONDS WHEN OUTPUT IS OFF (LOAD TYPE) TheBOP supports three Load Type selections (see Table5) which determine how the power supply respondswhen the outpu t is of f: ACTIVE, RESISTIVE andBATTERY. The Load Type selection does not affectthe settings of the power supply for ON state; it onlyaffects the main internal reference level and the pro-tection levels during the OFF state.

WARNING

For inductive loads, and especiallysuperconducting magnet typeloads, the inherent offset of theBOP in the OFF state may generatesignificant current in the circuit. Aproperly rated switch in parallelwith a resistor must be connectedbetween the power supply and theload. The switch must be open andthe BOP front panel LCD must read0V, 0A before removing or installingconnections between BOP andload.

Active. Active mode (default setting) is necessar yfor the power supply to function properly and safelywith inductive loads and constant-current-type active

Page 13: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

081817 228-1692 REV 7 13

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

electronic loads. Active mode can also be used withresistive loads. Table 5 indicates how the power sup-ply responds to a command to go from Output ON toOFF. When the output is disabled, the unit is set tovoltage mode, voltage is set to zero and both currentprotect and voltage limit are set to maximum. When

the unit is enabled, the pre-existing settings for volt-age, current protect and voltage limit are restored.

FIGURE 6. MAX/MIN SETTING MENU

WARNING

For both inductive loads and con-stant-current-type active electronicloads when the BOP output is setto OFF, a path is provided forabsorbing either the energy accu-mulated in the reactance of the loadduring the ON state, or energydelivered by an electronic load.

This prevents damage to the loadand power supply as well as pro-viding safety for the user. However,In addition to the built-in safety fea-tures, constant-current-type activeelectronic loads must be adjustedto zero and the BOP front panelLCD must read 0V, minimum cur-rent, before handling the powersupply-to-load connections.

VOLTAGESOURCE

VOLTAGE CURRENT

0.0000 0.0000

TABLE 5. POWER SUPPLY BEHAVIOR WHEN OUTPUT IS SET TO OFF

LOAD TYPESETTING

If unit was in Voltage Mode when output OFF command issued.

If unit was in Current Mode when output OFF command issued.

ACTIVE

• Unit remains in voltage mode.• Voltage set to zero.• Both ± Current Protect set to maximum.• Both ± Voltage Limit remain at maximum.

• Unit set to voltage mode.• Voltage set to zero.• Both ± Current Protect remain at maximum.• Both ± Voltage Limit set to maximum.

RESISTIVE

• Unit remains in voltage mode.• Voltage set to zero.• Both ± Current Protect set to minimum box values.• Both ± Voltage Limit. remain at maximum.

• Unit remains in current mode.• Current set to zero.• Both ± Current Protect set to minimum box values.• Both ± Voltage Limit set to maximum,

BATTERY

• Unit set to current mode.• Current set to zero.• Both ± Voltage Protect. remain at maximum.• Both ± Current Limit set to maximum.

• Unit remains in current mode,• Current set to zero.• Both ± Voltage Protect set to maximum.• Both ± Current Limit remain at maximum.

Page 14: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

14 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

Resistive. This mode, as th e name sugg ests, isuseful for resistive loads. Table 5 indicates how thepower supply respond s to a co mmand to go fromOutput ON to OFF.

WARNING

Accessing the BOP after the outputis disabled in BATTERY mode ishazardous because (1) high currentarcing is possible and (2) either theexternal battery voltage, or the volt-age (±Voltage Protection max) onthe BOP output terminals may bedangerous. Therefore, for batteryand constant-voltage-type activeelectronic loads it is recommendedthat two properly rated externalswitches be installed for safety:one in series with the battery, andone across the BOP output. Afterthe unit is set to OFF, first open theswitch in series with the battery,then close the switch across theBOP output to ensure safety beforehandling BOP connections. Whenconnecting the battery, the switchacross the output should beopened after the connections arecomplete and then the switch inseries with the battery should beclosed. If the constant-voltage-typeactive electronic load is adjusted tozero before handling the powersupply-to-load connections, onlythe switch across the BOP outputis required.

Battery. This mode is necessary for the power sup-ply to function properly and safely with either batteryor constant-voltage-type active electronic loads. Thismode prevents the battery from discharging duringthe OFF state. When the output is disabled (set toOFF), the BOP will go to current mode, current willbe set to zero , with voltage protect and current limitset to maximum. In this way the battery will not bedischarged while the output is OFF . For constant-voltage-type active electronic loads this mode stopsenergy flow during the OFF state. Table 5 indicateshow the power supply responds to a command to gofrom Output ON to OFF.

CONFIGURE LOAD TYPE. To configure, press% from the power-up screen, then highlight LoadType and press ! to m odify. (If a Pas sword isrequired, see Operator’s Manual for instructions.)Highlight Active, Resistive or Battery (see explana-tions and associated WARNINGS above) and press$ to save . Then press $ to save for power-up,# to ab ort, or % to a pply the changes (withoutsaving for power-up) and exit. After configuring, thenew setting will be effective when the power supplygoes from output on to output off.

To restore factory default (Active), press % from thepower-up screen, highlight Load Type, press !,then press @ to restore default. Press $ to savefor power-up or % to exitENABLING/DISABLING OUTPUT POWER. The BOP output can be disabled (OFF) or enabled(ON) by toggling the STANDBY key in local mode.The behavior of the un it when disabled depends onthe Load Type setting (See “” on page 13. and Table5 for details).

IX — ADDITIONAL FEATURES. The user is urged to refer to the Operator’s Manualfor full e xplanations all BOP 1KW features, includ-ing:

• Passwords - three independent levels ofaccess

• Changing the Default Power up Settings• Digital Remote Operation - using SCPI com-

mands via RS 232, GPIB or LAN ports; opera-tion via web pages

• Analog Remote Operation - via Ana log I/Oport

• Details about Protect Limits and Software-controlled limits

• Storing/Recalling Power Supply Output Set-tings

• Waveform Generation - Sine , Triangle,±Ramp, Square and Level segments. Localoperation allows up to 16 wa veforms, maxi-mum 10 segments per waveform. Remoteoperation allows 1 waveform, maximum of126 segments, or using LIST commands.

• Operator Testing• Calibration - via either local keypad or remote

SCPI commands• Parallel/Series Configurations -increase cur-

rent capability, voltage capability, or both.

Page 15: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

081817 228-1692 REV 7 15

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

FIGURE 1. BOP 1KW OUTLINE DIMENSIONS (SHEET 1 OF 2)

20.0

00 [5

08.0

0 ]21

.43 9

[544

.54 ]

22.8

00 [ 5

79.1

1]

21. 5

64 [5

47.7

3]22

. 000

[558

.79]

23.8

63 [6

06.1

2]

18.235 [463.16]18.985 [482.21]

1.47

0 [3

7.3 4

]

1 .73

8 [4

4.1 5

]5.

218

[ 132

.54]

2.21

5 [5

6 .27

]

OBROUND 0.25x0.453 (4 LOC.)

16.835 [427.60]17.675 [448.93]18.018 [457.64]18.805 [477.63]

Page 16: KEPCO An ISO 9001 Company. BOP 1KW · IEEE 1118 (BITBUS) Mating connector Allows connection to IEEE 1118 (BITBUS) port. 142-0485 (Kepco) KMDLA-5P (Kycon Inc.) IEEE 488 Cable, (1 meter

16 228-1692 REV 7 081817

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102http://www.kepcopower.com email: [email protected]

FIGURE 1. BOP 1KW OUTLINE DIMENSIONS (SHEET 2 OF 2)

SLIDES TRAVEL DISTANCE: 23.000 [584.2]22.000 [558.79]

SEE NOTE 6.

REAR VIEW

REMOVE FEET FOR RACK MOUNTING.


Recommended