Page 1: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation

Power Calculators in Data Center Energy Efficiency Planning

Joe [email protected]

Page 2: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation2

Agenda

Power Calculator BackgroundIndustry LandscapeIBM Systems Energy Estimator (SEE)IBM SEE EnhancementsFuture Direction

Page 3: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation3

Agenda

Power Calculator BackgroundIndustry LandscapeIBM Systems Energy Estimator (SEE)IBM SEE EnhancementsFuture Direction

Page 4: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation4

InstallationCapacityDesign PointOperating Point

EquipmentNameplateMaximum measured power consumptionActual power consumption

Cap

acity

Des

ign

Poi

nt

Operating Point

Nam

epla

te

Max

mea

sure

dpo

wer Actual measured

power

Motivation for Power Calculators

Power Calculators

Page 5: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation5

Capacity– Ultimate limitation– Usually influenced by outside factors

Design Point– Redundancy (n+1, 2n)– Availability

Operating Point– Reliability– Additional safety margin

Capacity – 1600 kW (2 x 800 kW UPSs)

Design Point – 800 kW (2n)

Operating Point – 600 kW (each UPS has 4 x 200 kW modules)

Installation Definitions

Page 6: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation6

CB

IEC 60950-1, Clause 1.6.2

NEC, Table 400.5(B)

IEC 60950-1, Clause 3.2.1NEC, Article 210.20 (A)

NEC, Article 645.5 (A)

NEC, Article 210.21(B)(1)NEC, Article 240.4 (B)

Equipment Definitions - Nameplate

Page 7: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation7

Definition– Highest expected power consumption– Accounts for worst case operating conditions

Use maximum measured power for – Size loading on electrical infrastructure– Can determine number of devices downstream of a breaker

15A

15A

15A

4A 4A 4A

4A4A4A

4A4A4A

Power Panel

Equipment Definitions – Max Measured Power Consumption

Page 8: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation8

Definition– Power consumption in typical use– Most representative of a particular configuration

Use actual power for – Size loading on mechanical infrastructure– Total Cost of Ownership

Equipment Definitions – Actual Power Consumption

Page 9: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation9

Air Conditioning Cooling Capacity

Air conditioning capacity based on actual power consumption

Air conditioning capacity based on max power consumption

Planning based on maximum measured power consumption results in a reduction of sensible cooling capacity (19 kW) and the operation of three additional Cooling Room Air Conditioning (CRAC) units.

Page 10: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation10

Total Cost of Ownership (TCO)

Acquisition OperationGrowth and

Change

Hardware

Software

Personnel

Facilities

System Life CycleR

esou

rces

The difference between the worst case configuration and the rating label results in an annual hardware operating cost increase of $590 ($0.11/kW•hr)

ExampleWorst case configuration………………………… 390 wattsPower supply nameplate………………………… 700 wattsAC power from rating label…………...………….1000 watts

Page 11: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation11

Agenda

Power Calculator BackgroundIndustry LandscapeIBM Systems Energy Estimator (SEE)IBM SEE EnhancementsFuture Direction

Page 12: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation12

Calculator Tool Links

http://thegreengrid.org/en/Global/Content/white-papers/Proper-Sizing-of-IT-Power-and-Cooling-Loads

Page 13: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation13

Agenda

Power Calculator BackgroundIndustry LandscapeIBM Systems Energy Estimator (SEE)IBM SEE EnhancementsFuture Direction

Page 14: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation14

IBM SEE Overview

IBM Systems Energy Estimator– Standalone web application

“The IBM Systems Energy Estimator is a web-based tool for estimating power requirements for IBM Power Systems. You can use this tool to estimate typical power requirements (watts) for a specific system configuration under normal operating conditions.”

– Deployed initial offering October 2008, latest update was August 18, 2009

– Supports Power Systems (POWER6 and newer)Follow-on to Power Load Calculator (POWER5)

– Averages 400 energy estimations per weekUser feedback has been positive, affirms that energy requirements are an increasingly

important component of purchase decision

– Represents significant collaboration between STG Development, Systems Assurance, WW Tech Support Tools, and Systems Performance

Page 15: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation15

Energy Estimator Welcome Page

launch the Energy Estimator

Page 16: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation16

IBM Systems Energy Estimator

Step 1:select a model

Processor model drop-down

Page 17: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation17

IBM Systems Energy Estimator

Step 2:specify system configuration

Page 18: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation18

IBM Systems Energy Estimator Output

Step 3:energy estimate

results

list of included components

Page 19: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation19

IBM SEE Integration

IBM System Planning Tool (SPT)– Planning and deployment for Power Systems, System i, System p– Integrated “Energy Estimate” function via energy estimator plug-in

IBM Systems Workload Estimator (WLE)– STG strategic sizing tool for Power Systems, System i, System p,

System x– Integrated “Energy Estimate” function via energy estimator plug-in

Page 20: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation20

IBM System Planning Tool integration

*The calculated energy estimate is an expected, typical value for this system

configuration under normal environmental operating conditions. It should not be used

in planning the electrical supply infrastructure.

Page 21: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation21

IBM Systems Workload Estimator integration

From WLE Selected System screen, select:

Energy estimate

Page 22: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation22

Agenda

Power Calculator BackgroundIndustry LandscapeIBM Systems Energy Estimator (SEE)IBM SEE EnhancementsFuture Direction

Page 23: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation23

Estimated energy result(s)utilization-based result for

supported models

Utilization-based Processor Curve ExamplekW

atts

Page 24: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation24

Utilization

utilization-based result for supported models

Page 25: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation25

Number of Cores

number of cores configured and

active

Page 26: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation26

Agenda

Power Calculator BackgroundIndustry LandscapeIBM Systems Energy Estimator (SEE)IBM SEE EnhancementsFuture Direction

Page 27: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation27

IBM Systems Energy Estimator

What’s next?– Increase disk expansion options– P7, EnergyScale, Power Saver Modes– Active Energy Manager power

management settings– Power blades

Energy consumption

020406080

100

0% 20% 40% 60% 80% 100%

System utilization

Rel

ativ

e En

ergy

Energy Estimate: reflects configuration and utilization

(green curve)

Energy Estimate: optimized for power

management settings

daynight

max

Page 28: Power Calculators in Data Center Energy Efficiency Planning · Design Point Operating Point Equipment Nameplate Maximum measured power consumption Actual power consumption Design

© 2009 IBM Corporation28

The End