State Hygienic Laboratory The University of Iowa
JON MARTENS ATLANTIC MUNICIPAL UTILITIES 15 W 3RD ST ATLANTIC, IA 50022-
Accession Number Date Sample Finalized
Date Received Date Collected Sample Source
Collector PWS ID
PWS Name Facility ID
Sample Type Sample Category
Sampling Point ID Collection Site
Client Reference
195852 2014-10-16 10:24 2014-10-08 09:42 2014-10-07 13:26 Drinking Water young kenny IA1509074 ATLANTIC MUNICIPAL UTILITII WL06 SP - Special Chemical WL06 well 6 tap
Note: Upon arrival, sample met container and preservation requirements for the analysis requested. Please review carefully your sample results for additional analyte comments or method exceptions.
Results of Analyses GCMS V, EPA 524.2
Units Date Analyzed
Analyst
Analyte
mg/L 2014-10-13 10:25 LJL
Result
Analyzed In Date Verified
Verifier
Coralville 2014-10-16 10:24 JM
Quant Limit T etrachloroethylene 0.012 0.0005 0.005
Note: The MCL (maximum contaminant level) is only applicable to compliance monitoring samples under the Safe Drinking Water Act (SDWA).
Description of Units used within this report mg/L = Milligrams per Liter
The result(s) of this report relate only to the items analyzed. This report shall not be reproduced except in full without the written approval of the laboratory. Iowa Environmental Laboratory IDs are: Ankeny #397, Iowa City/Coralville #027, Lakeside #393. If you have any questions, please call Client Services at 800/421-IOWA (4692) or 319/335-4500. Thank you.
Page 1 of
flraa,
ouoo
40483087
Superfund
•0
Michael D. Wichman, Ph.D.
Associate Director http://www.shl. uiowa. edu
University of Iowa Research Park 2490 Crosspark Road Coralville, IA 52241 319/335-4500 Fax: 319/335-4555
Lakeside Laboratory 1838 Highway 86 Milford, IA 51351 712/337-3669 ext. 6 Fax: 712/337-0227
Iowa Laboratories Complex 2220 S. Ankeny Blvd Ankeny, IA 50023 515/725-1600 Fax: 515/725-1642
State Hygienic Laboratory The University of Iowa
JON MARTENS ATLANTIC MUNICIPAL UTILITIES 15 W 3RD ST ATLANTIC, IA 50022-
Accession Number Date Sample Finalized
Date Received Date Collected Sample Source
Collector PWSID
PWS Name Facility ID
Sample Type Sample Category
Sampling Point ID Collection Site
Client Reference
195851 2014-10-16 10:24 2014-10-08 09:42 2014-10-07 13:50 Drinking Water young kenny IA 1509074 ATLANTIC MUNICIPAL UTILITIE 0 1
RT - Routine Chemical 0 1
clear well tap
Note: Upon arrival sample met container and preservation requirements for the analysis requested. Please review carefully your sample results for additional analyte comments or method exceptions.
Results of Analyses GCMS Volatiles, EPA 524.2
Units Date Analyzed
Analyst
Analyte
mg/L 2014-10-13 09:55 LJL
Result
Analyzed In Date Verified
Verifier
Coralville 2014-10-16 10:24 JM
Quant Limit Tetrachloroethylene <0.0005 0.0005 0.005
Note: The MCL (maximum contaminant level) is only applicable to compliance monitoring samples under the Safe Drinking Water Act (SDWA).
Description of Units used within this report mg/L = Milligrams per Liter
The result(s) of this report relate only to the items analyzed. This report shall not be reproduced except in fill] without the written approval of the laboratory. Iowa Environmental Laboratory IDs are: Ankeny #397, Iowa City/Coralville #027, Lakeside #393. If you have any questions, please call Client Services at 800/421-IOWA (4692) or 319/335-4500. Thank you.
Page I of 1 Michael D. Wichman, Ph.D.
Associate Director http://www.shl. uiowa. edu
University of Iowa Research Park 2490 Crosspark Road Coralville, IA 52241 319/335-4500 Fax: 319/335-4555
Lakeside Laboratory 1838 Highway 86 Milford, IA 51351 712/337-3669 ext. 6 Fax: 712/337-0227
Iowa Laboratories Complex 2220 S. Ankeny Blvd Ankeny, IA 50023 515/725-1600 Fax: 515/725-1642
State Hygienic Laboratory The University of Iowa
JON MARTENS ATLANTIC MUNICIPAL UTILITIES 15 W 3RD ST ATLANTIC, IA 50022-
Accession Number Date Sample Finalized
Date Received Sample Source
Project Date Collected Collection Site
Collection Town Sample Description
Client Reference Collector
Phone
195848 2014-10-16 10:12 2014-10-08 09:42 Non-Drinking Water
2014-10-07 13:05 amu well 7 ATLANTIC waste water well 7 waste water young kenny 712/243-1395
Note: Upon arrival, sample met container and preservation requirements for the analysis requested. Please review carefully your sample results for additional analyte comments or method exceptions.
Results of Analyses GCMS V(
Units Date Analyzed
Analyst
mg/L 2014-10-14 16:35 LJL
Result
EPA 524.2
Analyzed In Date Verified
Verifier
Quant Limit
Coralville 2014-10-16 10:12 JM
Analyte Tetrachloroethylene 0.052 0.0005 0.005
Note• The MCL (maximum contaminant level) is only applicable to compliance monitoring samples under the Safe Drinking Water Act (SDWA).
Description of Units used within this report mg/L = Milligrams per Liter
The result(s) of this report relate only to the items analyzed. This report shall not be reproduced except in full without the written approval of the laboratory. Iowa Environmental Laboratory IDs are: Ankeny #397, Iowa City/Coralville #027, Lakeside #393. If you have any questions, please call Client Services at 800/421-IOWA (4692) or 319/335-4500. Thank you.
Michael D. Wichman, Ph.D.
Associate Director http://www.shl. uiowa. edu
University of Iowa Research Park 2490 Crosspark Road Coralville, IA 52241 319/335-4500 Fax: 319/335-4555
Page 1 of 1 Lakeside Laboratory 1838 Highway 86 Milford, IA 51351 712/337-3669 ext. 6 Fax: 712/337-0227
Iowa Laboratories Complex 2220 S. Ankeny Blvd Ankeny, IA 50023 515/725-1600 Fax: 515/725-1642